5.10 o: Operator Related Settings
No.
o2-05
Name
Frequency Reference Setting Method Selection
Setting Range
0, 1
Default
0
Setting 0: ENTER Key Required
The ENTER key must be pressed every time the frequency reference is changed using the digital operator for the drive to accept the change.
Setting 1: ENTER Key Not Required
The output frequency changes immediately when the reference is changed by the up or down arrow keys on the digital operator.
The ENTER key does not need to be pressed. The frequency reference (Fref) is saved to memory after remaining unchanged for 5 seconds.
n o2-06: Operation Selection when Digital Operator is Disconnected
Determines whether the drive will stop when the remote control extension cable of the digital operator is removed in LOCAL mode or when b1-02 or b1-16 is set to 0. When the operator is reconnected, the display will indicate that it was disconnected.
No.
o2-06
No.
o2-07
Setting 0: Forward
Name
Digital Operator Disconnection Operation
Setting Range
0, 1
Default
1
Setting 0: Continue Operation
The operation continues.
Setting 1: Trigger a Fault
The operation stops and triggers an oPr fault. The motor coasts to stop.
n o2-07: Motor Direction at Power Up when Using Operator
Determines the direction the motor will rotate after the drive is powered up and the Run command is given from the digital operator.
Note: This parameter is effective only when the Run command is set to be given from the digital operator (b1-02, b1-16 = 0).
Name
Motor Direction at Power Up when Using Operator
Setting Range
0, 1
Default
0
Setting 1: Reverse n o2-19: Selection of Parameter Write during Uv
Selects whether parameter settings can be changed during a DC bus undervoltage condition. To be used with 24 V Power
Supply option (PS-A10L, PS-A10H) revision B or later.
Note: Enabling this function may trigger a CPF06 fault when used with a 24 V Power Supply option revision earlier than B, as the parameter changes might not occur correctly.
No.
o2-19
Setting 0: Disabled
Name
Selection of Parameter Write during Uv
Setting Range
0, 1
Default
0
Setting 1: Enabled u
o3: Copy Function
These parameters control the Copy function of the digital operator. The Copy function stores parameter settings into the memory of the digital operator to facilitate the transfer of those settings to other drives that are the same model, capacity, and
same control mode setting. Refer to Copy Function Related Displays on page 445
for a description of errors and displays.
n o3-01: Copy Function Selection
Instructs the drive to Read, Write, or Verify parameter settings.
No.
o3-01
Name
Copy Function Selection
Setting Range
0 to 3
Default
0
382 YASKAWA ELECTRIC SIEP C710616 41G YASKAWA AC Drive – A1000 Technical Manual