CP-Series
CP20.245-R2
24V, 20A, S INGLE P HASE I NPUT
4.
DC-I
NPUT
DC input
DC input range
DC input current
Allowed Voltage L/N to Earth
Turn-on voltage
Shut-down voltage
Fig. 4-1 Wiring for DC Input nom. typ. max. typ. typ.
Battery
+
Power Supply
AC
L
N
PE
+
-
Load
DC 110-150V
88-180Vdc
4.64A
375Vdc
80Vdc
70Vdc
±20%
Continuous operation
At 110Vdc, at 20A
Continuous, IEC 62477-1
Steady state value
Steady state value
Instructions for DC use: a) Use a battery or a similar DC source. A supply from the intermediate DC-bus of a frequency converter is not recommended and can cause a malfunction or damage the unit. b) Connect +pole to L and – pole to N. c) Connect the PE terminal to an earth wire or to the machine ground.
-
DC
5.
I
NPUT
I
NRUSH
C
URRENT
An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V AC 120V AC 230V
Inrush current
Inrush energy max. typ. max.
15A peak
12A peak
12A
10A peak peak negligible small
5.5A
peak
4.5A
peak
Temperature independent
Temperature independent
Fig. 5-1 Typical input inrush current behaviour at nominal load and 25°C ambient
Input Current 5A / DIV
Input
Output
100mS/DIV
230Vac
24Vdc
Jun. 2020 / Rev 1.0 DS-CP20.245-R2 EN
All parameters are typ. values specified at 24.1V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
5/28
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 8 DC-OK Relay Contact
- 9 Efficiency and Power Losses
- 10 Lifetime Expectancy and MTBF
- 10 Functional Diagram
- 11 Terminals and Wiring
- 12 Replacing Units while the System is Running
- 13 Front Side and User Elements
- 15 Environment
- 16 Protection Features
- 16 Safety Features
- 17 Dielectric Strength
- 18 Approvals
- 19 RoHS, REACH and Other Fulfilled Standards
- 20 Physical Dimensions and Weight
- 21 Accessories
- 21 Wall/Panel Mount Bracket
- 22 Application Notes
- 22 Peak Current Capability
- 23 Adjustment of the Output Voltage
- 24 Back-feeding Loads
- 24 External Input Protection
- 24 Output Circuit Breakers
- 25 Series Operation
- 25 Parallel Use to Increase Output Power
- 26 Parallel Use for Redundancy
- 27 Inductive and Capacitive Loads
- 27 Operation on Two Phases
- 27 Use in a Tightly Sealed Enclosure
- 28 Mounting Orientations