CP-Series
CP20.245-R2
24V, 20A, S INGLE P HASE I NPUT
8.
DC-OK R
ELAY
C
ONTACT
Contact closes
Contact opens
Contact ratings
Isolation voltage
As soon as the output voltage reaches typ. 22Vdc.
As soon as the output voltage dips below 22Vdc.
Short dips will be extended to a signal length of 100ms. Dips shorter than 1ms will be ignored. max. min.
60Vdc 0.3A, 30Vdc 1A, 30Vac 0.5A
1mA at 5Vdc
See dielectric strength table in chapter 19.
Resistive load
Min. permissible load
Fig. 8-1 DC-ok relay contact behavior
22Vdc
<
1ms
>
1ms 100ms open closed open closed
Jun. 2020 / Rev 1.0 DS-CP20.245-R2 EN
All parameters are typ. values specified at 24.1V, 20A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
8/28
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 3 Installation instructions
- 4 AC-Input
- 5 DC-Input
- 5 Input Inrush Current
- 6 Output
- 7 Hold-up Time
- 8 DC-OK Relay Contact
- 9 Efficiency and Power Losses
- 10 Lifetime Expectancy and MTBF
- 10 Functional Diagram
- 11 Terminals and Wiring
- 12 Replacing Units while the System is Running
- 13 Front Side and User Elements
- 15 Environment
- 16 Protection Features
- 16 Safety Features
- 17 Dielectric Strength
- 18 Approvals
- 19 RoHS, REACH and Other Fulfilled Standards
- 20 Physical Dimensions and Weight
- 21 Accessories
- 21 Wall/Panel Mount Bracket
- 22 Application Notes
- 22 Peak Current Capability
- 23 Adjustment of the Output Voltage
- 24 Back-feeding Loads
- 24 External Input Protection
- 24 Output Circuit Breakers
- 25 Series Operation
- 25 Parallel Use to Increase Output Power
- 26 Parallel Use for Redundancy
- 27 Inductive and Capacitive Loads
- 27 Operation on Two Phases
- 27 Use in a Tightly Sealed Enclosure
- 28 Mounting Orientations