Specifications. Honeywell VNT5200E1000, VNT5150H1000, VNT5150E1000, VNT5200H1000


Add to My manuals
68 Pages

advertisement

Specifications. Honeywell VNT5200E1000, VNT5150H1000, VNT5150E1000, VNT5200H1000 | Manualzz

Specifications

Dimensions in inches (mm):

2

1

H

1

2

FRONT CLEARANCE OF 25 INCHES

(635 MM) IS REQUIRED FOR

SERVICING UNIT.

ALL DUCT CONNECTIONS ARE

6 IN. (150 MM).

L

W

VNT5150H1000 or VNT5150E1000: H = 22 1/2 in. (572 mm), W = 11 1/2 in. (295 mm), L = 29 1/2 in. (749 mm)

VNT5200H1000 or VNT5200E1000: H = 22 1/2 in. (572 mm), W = 16 1/2 in. (422 mm), L = 29 1/2 in. (749 mm)

M28919

Physical Specifications:

Model Product Weight

VNT5150H1000

VNT5150E1000

VNT5200H1000

VNT5200E1000

42 lbs. (19 kg)

50 lbs. (22.68 kg)

Shipping Weight Heat/Energy Core

Dimensions

47.5 lbs. (21.55 kg)

H = 12 in. (305 mm)

W = 10 in. (254 mm)

57.5 lbs. (26.08 kg)

L = 12 in. (305 mm)

H = 12 in. (305 mm)

W = 15 in. (381 mm)

L = 12 in. (305 mm)

Filter Dimensions

H = 12 in. (305 mm)

W = 10 in. (254 mm)

H = 12 in. (305 mm)

W = 15 in. (381 mm)

Operating Ranges:

Ambient Temperature: 34 to 135 ºF (1 to 57 ºC)

Humidity: 0-99% RH

Electrical Ratings:

Input Voltage: 120 VAC, 60 Hz

Input Current: 1.5 A

Output Power to Terminals: 5 VDC, 1.0 A maximum

Drain tubing diameter: 1/2 in. (12.7 mm)

Flexible Duct (2): 6 in. round for inlet and outlet. Flexible vinyl, compatible for connection to rigid or flexible ducting with sheet metal screws and/or tape.

Cabinet: 20 gauge galvanized steel

Standards and Certifications:

4

Install the ERV/HRV Ventilation System according to national and local regulations, building, and safety codes.

ERV/HRV Ventilation Systems 69-2480EF—01

Specifications (continued)

VNT5150H1000 Ventilation Performance

External Static Pressure Net Supply Air Flow

Pa

25

50

75

100

125

150

175

200

225

250

in. W.C.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

L/s

92

85

80

73

65

59

56

50

45

37

CFM

195

182

171

156

139

126

120

107

95

79

L/s

92

86

81

74

66

60

57

50

45

38

Supply

Gross Air Flow

CFM

196

183

L/s

113

105

Exhaust

CFM

241

223

172

157

140

127

120

107

96

80

91

84

75

65

57

48

40

34

193

178

159

137

120

103

86

73

0.5

EXTERNAL

STATIC

PRESSURE

(IN. W. C)

0.4

0.3

0.2

0.1

0

0

0.8

0

0.7

0.6

10 20 30

NET SUPPLY AIR FLOW

50

40

VNT5150H1000

AIR FLOW (L/S)

50 60 70

100

AIR FLOW (CFM)

150

80 90

200

100 110

200

175

150

250

0

50

25

125

100

75

EXTERNAL

STATIC

PRESSURE

(PA)

M32358

VNT5150H1000 Energy Performance

Supply Temperature Net Supply Air Flow

°C

0

0

0

-25

°F

32

32

32

-13

L/s

31

42

56

32

CFM

66

89

119

67

Average

Power

Watts

88

104

114

86

Sensible

Recovery

Apparent

Sensible

Efficiency % Effectiveness %

66

64

63

59

78

76

72

77

ERV/HRV Ventilation Systems 69-2480EF—01 5

6

Specifications (continued)

VNT5200H1000 Ventilation Performance

External Static

Pressure

Pa

25

50

75

100

125

150

175

200

225

250

in. W.C.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

Net Supply Air Flow

L/s

117

108

102

94

85

77

69

61

52

45

CFM

248

229

218

200

181

163

146

129

110

96

L/s

118

109

103

95

86

78

70

61

52

46

Supply

Gross Air Flow

CFM

250

231

L/s

130

119

Exhaust

CFM

277

253

220

202

183

165

148

131

111

97

110

101

92

82

71

60

49

40

234

216

197

175

151

128

104

86

0.5

EXTERNAL

STATIC

PRESSURE

(IN. W. C)

0.4

0.3

0.2

0.1

0

0

0.8

0

0.7

0.6

10 20 30 40

NET SUPPLY AIR FLOW

50 100

50

VNT5200H1000

AIR FLOW (L/S)

60 70 80

150

AIR FLOW (CFM)

90

200

100 110 120 130

250

140

200

175

150

300

0

50

25

125

100

75

EXTERNAL

STATIC

PRESSURE

(PA)

M32354

VNT5200H1000 Energy Performance

Supply Temperature Net Supply Air Flow

°C

0

0

0

-25

°F

32

32

32

-13

L/s

55

75

87

57

CFM

118

160

185

120

Average

Power

Watts

106

132

150

105

Sensible

Recovery

Apparent

Sensible

Efficiency % Effectiveness %

61

58

55

58

71

65

62

72

ERV/HRV Ventilation Systems 69-2480EF—01

Specifications (continued)

VNT5150E1000 Ventilation Performance

External Static Pressure Net Supply Air Flow

Pa

25

50

75

100

125

150

175

200

225

250

in. W.C.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

L/s

92

87

82

75

69

62

55

48

41

38

CFM

197

185

173

160

146

132

116

102

88

81

L/s

96

93

88

83

76

72

67

60

54

42

Supply

Gross Air Flow

CFM

204

199

L/s

93

88

Exhaust

CFM

199

186

186

176

162

152

143

127

114

89

82

76

70

63

55

48

42

39

175

162

148

134

117

103

89

82

0.6

0.5

EXTERNAL

STATIC

PRESSURE

(IN. W. C)

0.4

0.3

0.2

0.1

0.8

0

0.7

0.0

0

10 20 30 40

VNT5150E1000

AIR FLOW (L/S)

50 60 70 80

NET SUPPLY AIR FLOW

50 100 150

AIR FLOW (CFM)

90

200

100 110

200

25

250

0

175

150

125

100

75

EXTERNAL

STATIC

PRESSURE

(PA)

50

M32370

VNT5150E1000 Energy Performance

Supply Temperature Net Supply Air Flow

0

0

°C

0

-15

35

°F

32

32

32

5

95

L/s

30

45

55

30

30

CFM

64

96

117

64

64

Average

Power

Watts

75

100

126

80

75

Sensible

Recovery

Apparent

Sensible

Efficiency % Effectiveness %

52

44

40

52

67

64

62

67

Total Recovery Efficiency = 49%

ERV/HRV Ventilation Systems 69-2480EF—01 7

Specifications (continued)

8

VNT5200E1000 Ventilation Performance

External Static

Pressure

Pa

25

50

75

100

125

150

175

200

225

250

in. W.C.

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1

Net Supply Air Flow

L/s

98

94

87

82

74

65

60

53

44

38

CFM

208

200

186

175

157

138

127

112

94

81

L/s

102

99

93

88

78

72

64

60

54

41

Supply

Gross Air Flow

CFM

218

210

L/s

99

95

Exhaust

CFM

210

202

199

188

167

152

135

127

114

86

88

83

75

65

60

53

45

39

188

176

159

139

128

113

95

82

0.8

0

0.7

0.6

EXTERNAL

STATIC

PRESSURE

(IN. W. C)

0.5

0.4

0.3

0.2

0.1

0.0

0

10 20 30 40

VNT5200E1000

AIR FLOW (L/S)

50 60 70 80

NET SUPPLY AIR FLOW

50 100 150

AIR FLOW (CFM)

90

200

100 110

200

175

150

25

250

0

125

100

75

EXTERNAL

STATIC

PRESSURE

(PA)

50

M32369

VNT5200E1000 Energy Performance

Supply Temperature Net Supply Air Flow

°C

0

0

0

-15

35

°F

32

32

32

5

95

L/s

35

50

70

35

35

CFM

74

106

149

74

74

Average

Power

Watts

75

100

126

80

75

Sensible

Recovery

58

51

44

58

Apparent

Sensible

Efficiency % Effectiveness %

69

66

64

69

Total Recovery Efficiency = 53%

ERV/HRV Ventilation Systems 69-2480EF—01

advertisement

Key Features

  • Improves indoor air quality by removing pollutants, allergens, and moisture.
  • Recovers heat and moisture from the outgoing air stream, reducing energy costs.
  • Helps to prevent condensation and mold growth.
  • Provides a constant supply of fresh air, even when windows and doors are closed.
  • Can be controlled manually or with an optional remote control or wall-mounted thermostat.
  • Easy to install and maintain.

Related manuals

Frequently Answers and Questions

What is the difference between an ERV and a HRV?
An ERV (Energy Recovery Ventilator) transfers both heat and moisture from the outgoing air stream to the incoming air stream, while a HRV (Heat Recovery Ventilator) only transfers heat.
How do I know if I need an ERV or a HRV?
If you live in a humid climate, an ERV is a better choice because it will help to remove moisture from the air. If you live in a dry climate, a HRV is a better choice because it will help to add moisture to the air.
How do I install an ERV?
ERVs are typically installed in the attic or basement. The installation process involves connecting the ERV to the ductwork in your home and wiring it to a power source.
How do I maintain an ERV?
ERVs require minimal maintenance. You should change the filters every few months and clean the core once a year.