Chapter 3 Deployment

Project engineering under WinNCS

Preconditions

The project engineering happens via WinNCS starting with V3.09. For project engineering , the following preconditions should be met:

Recent VIPA_ETH200V.GSD is stored in WinNCS/GSD/Englisch.

For project engineering of the System 200V modules in WinNCS you receive the features of the VIPA components with a GSD-file.

The GSD-file for the IM 253NET Ethernet coupler from VIPA is:

VIPA_ETH200V.GSD

Copy this GSD-file into WinNCS/GSD/Englisch.

The latest version is to find under ftp.vipa.de/support.

For online project engineering, the IM 253NET should be assembled with the according modules, connected to the Ethernet and supplied with voltage.

Approach online project engineering

Attention!

For every Ethernet slave is delivered with the IP address 10.0.0.1, you must not install more than one new Ethernet slave at a time!

Start WinNCS and create a new "Ethernet" project via File >

Create/Open project

.

A parameter windows for online search of "Slaves" and "Stations"

opens. [Slaves] lists all Ethernet coupler and [Stations] all CPs.

Click at [Slaves]

All Ethernet coupler are searched and listed with IP address and

where applicable with label.

Via double-click at a listed slave, this is overtaken into the network window and listed with the concerning I/O periphery.

If there is no parameterization yet, the modules are listed as symbol

(without label).

Now you assign the according module type to the listed module symbol in the parameter window and adjust the parameters when needed. The address range that is occupied by the module in the TCP data stream is automatically preset by the Ethernet coupler.

As soon as you click at [apply], you have to type the password. The password request happens once per session and coupler. In delivery state, the password is 00000000.

With correct password, the data is transferred online to the Ethernet coupler. Repeat this for all listed modules.

Save your project.