DS72 Host Module
Sel M/P Identifier Lo V Lvl Sel M/P Identifier Lo V Lvl
1 2/1 rpc14 900 2 5/1 DS-RPC 900
Enter Request :1
Type #1 for the selection, press <cr> and the Host Module responds:
Enter voltage threshold value in tenths of a volt:
Over Voltage Alarm Threshold
Select 4), Over Voltage Alarm Threshold and the Host Module responds:
Sel M/P Identifier Hi V Lvl Sel M/P Identifier Hi V Lvl
1 2/1 rpc14 1300 2 5/1 DS-RPC 1300
Enter Request :1
Type #1 for the selection, press <cr> and the Host Module responds:
Enter voltage threshold value in tenths of a volt:
Low Current Alarm Threshold
Select 5), Low Current Alarm Threshold and the Host Module responds:
Sel M/P Identifier Low Curr Sel M/P Identifier Low Curr
1 2/1 rpc14 0 2 5/1 DS-RPC 0
Enter Request :1
Type #1 for the selection, press <cr> and the Host Module responds:
Enter low current threshold value in tenths of an amp:
Environmental Sensors
Select 6), Environmental Sensors with no environmental probes are attached the Host Module responds:
None of the installed devices support this option (no temperature probes installed).
Strike ENTER to continue
If you have environmental probes attached the Host Module responds:
Environmental Sensor Configuration Menu
Sel M/P Identifier
1 2/1 RPC3ADE
2 All Sensors
Enter Request :1
28
DS72 Host Module
Selection 1), the Host Module responds:
Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A Ds
2 Contact External Sensor2 N/A N/A Ds
Enter Request :1
Select the probe port to enable or disable the SNMP change trap, the Host Module responds with the change.
Selected State Change Trap is..... Disabled
Enable ? (Y/N), CR for no change) :y
Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A En
2 Contact External Sensor2 N/A N/A Ds
Enter Request :
Select 2), from the Environmental Sensor Configuration Menu allows the administrator to identify the probe type, the Host Module responds
For configuration of all sensors of selected type in system with a
single user-supplied value.
1...Contact
2...Temperature
3...Humidity
4...Air Flow
Enter Request :1
Selected State Change Trap is..... NP
Enable ? (Y/N), CR for no change) :
Enter Request :2
Select 2), from the probe type menu allows the administrator to set the High and Low Temperature range. Option 2 and 4 will enable/disable their corresponding SNMP traps.
RPC/RPS External Environmental Sensor Configuration Menu
Sensor Number: All Name: all RPCs/RPSs Type: Temperature
1...High Threshold (tenths of meas. unit): NP
2...High Threshold Trap Enable: NP
3...Low Threshold (tenths of meas. unit): NP
4...Low Threshold Trap Enable: NP
Enter Request :
Select 3), from the probe type menu allows the administrator to set the High and Low Humidity range.
Option 2 and 4 will enable/disable their corresponding SNMP traps.
29