When supplying 24 V external power to the control circuit

Connect a 24 V external power supply across terminals +24 and SD. Connecting a 24 V external power supply enables I/O terminal ON/OFF operation, operation panel displays, control functions, and communication during communication operation even at power-OFF of inverter's main circuit power supply. When the main circuit power supply is turned ON, the power supply source changes from the 24 V external power supply to the main circuit power supply.

Specification of the applicable 24 V external power supply

Item

Input voltage

Input current

Rated specification

23 to 25.5 VDC

1.4 A or less

Commercially available products (as of February 2015)

Model

S8JX-N05024C



Specifications: Capacity 50 W, output voltage (DC) 24 V, output current 2.1 A

Installation method: Front installation with cover or

Manufacturer

OMRON Corporation

S8VS-06024 

Specifications: Capacity 60 W, output voltage (DC) 24 V, output current 2.5 A

Installation method: DIN rail installation

 For the latest information about OMRON power supply, contact OMRON corporation.

Starting and stopping the 24 V external power supply operation

• Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.

Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply operation.

• Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.

NOTE

• When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter operation is disabled.

• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using

Pr.30

. (For the details of Pr.30

, refer to the FR-F800 Instruction Manual (Detailed).))

Confirming the 24 V external power supply input

• During the 24 V external power supply operation, the 24 V external power supply operation (EV) signal is output. To use the

EV signal, set "68 (positive logic) or 168 (negative logic)" in one of Pr.190 to Pr.196 (output terminal function selection) to assign function to an output terminal.

2