Control circuit
2.6.5
When supplying 24 V external power to the control circuit
Connect a 24 V external power supply across terminals +24 and SD. Connecting a 24 V external power supply enables I/O terminal ON/OFF operation, operation panel displays, control functions, and communication during communication operation even at power-OFF of inverter's main circuit power supply. When the main circuit power supply is turned ON, the power supply source changes from the 24 V external power supply to the main circuit power supply.
Specification of the applicable 24 V external power supply
Item
Input voltage
Input current
Rated specification
23 to 25.5 VDC
1.4 A or less
Commercially available products (as of February 2015)
Model
S8JX-N05024C
Specifications: Capacity 50 W, output voltage (DC) 24 V, output current 2.1 A
Installation method: Front installation with cover or
Manufacturer
OMRON Corporation
Specifications: Capacity 60 W, output voltage (DC) 24 V, output current 2.5 A
Installation method: DIN rail installation
For the latest information about OMRON power supply, contact OMRON corporation.
Starting and stopping the 24 V external power supply operation
• Supplying 24 V external power while the main circuit power is OFF starts the 24 V external power supply operation.
Likewise, turning OFF the main circuit power while supplying 24 V external power starts the 24 V external power supply operation.
• Turning ON the main circuit power stops the 24 V external power supply operation and enables the normal operation.
NOTE
• When the 24 V external power is supplied while the main circuit power supply is OFF, the inverter operation is disabled.
• In the initial setting, when the main power supply is turned ON during the 24 V external power supply operation, a reset is performed in the inverter, then the power supply changes to the main circuit power supply. (The reset can be disabled using
Pr.30
. (For the details of Pr.30
, refer to the FR-F800 Instruction Manual (Detailed).))
Confirming the 24 V external power supply input
• During the 24 V external power supply operation, the 24 V external power supply operation (EV) signal is output. To use the
EV signal, set "68 (positive logic) or 168 (negative logic)" in one of Pr.190 to Pr.196 (output terminal function selection) to assign function to an output terminal.
2
41
advertisement
Related manuals
advertisement
Table of contents
- 13 Inverter and peripheral devices
- 15 Peripheral devices
- 19 Inverter installation environment
- 21 Inverter installation
- 26 Details on the main circuit terminals
- 26 Terminal layout of the main circuit terminals, wiring of power supply and the motor
- 27 Wiring method
- 30 Applicable cables and the wiring length
- 32 Earthing (grounding) precautions
- 33 Details on the control circuit terminals
- 37 Control logic (sink/source) change
- 39 Wiring of control circuit
- 41 Wiring precautions
- 42 When supplying 24 V external power to the control circuit
- 43 Safety stop function
- 45 Components of the operation panel
- 46 Outline of the Main monitor indicator
- 47 Basic operation of the operation panel
- 48 PU connector
- 49 Ethernet connector
- 50 USB connector
- 52 Connection of the brake unit (FR-BU2)
- 54 Connection of the brake unit (FR-BU)
- 55 Connection of the brake unit (BU type)
- 56 Connection of the high power factor converter (FR-HC2)
- 57 Connection of the power regeneration common converter (FR-CV)
- 58 Connection of the power regeneration converter (MT-RC)
- 61 Leakage currents and countermeasures
- 63 Countermeasures against inverter-generated EMI
- 65 Built-in EMC filter
- 66 Power supply harmonics
- 67 Harmonic suppression guidelines in Japan
- 81 Daily inspection
- 81 Periodic inspection
- 82 Daily and periodic inspection
- 84 Checking the inverter and converter modules
- 84 Cleaning
- 85 Replacement of parts
- 104 Precautions for removal and reinstallation of the control circuit terminal block
- 107 Measurement of powers
- 107 Measurement of voltages and use of PT
- 108 Measurement of currents
- 108 Use of CT and transducer
- 108 Measurement of inverter input power factor
- 108 Measurement of converter output voltage (across terminals P and N)
- 109 Measurement of inverter output frequency
- 109 Insulation resistance test using megger
- 109 Pressure test
- 119 Appendix 1 Differences and compatibility with the FR-F
- 120 Appendix 2 Instructions for compliance with the EU Directives
- 123 Appendix 3 Instructions for UL and cUL
- 125 Appendix 4 Instructions for EAC
- 126 Appendix 5 Restricted Use of Hazardous Substances in Electronic and Electrical Products