Connection of stand-alone option units
2.9.5
Connection of the power regeneration common converter (FR-CV)
When connecting the power regeneration common converter (FR-CV), connect the inverter terminals (P/+, N/-) and the power regeneration common converter (FR-CV) terminals as shown below so that their symbols match with each other.
The FR-CV is applicable to FR-F846-01160(55K) or lower.
After making sure that the wiring is correct, set "2" in Pr.30 Regenerative function selection .
R/L1
S/L2
T/L3
∗1
U
V
W
M
Three-phase
AC power supply
MCCB MC1
Dedicated stand-alone reactor (FR-CVL)
FR-CV type
Power regeneration common converter
R/L11
S/L21
T/L31
R2/L12
S2/L22
T2/L32
R2/L1
S2/L2
T2/L3
P/L+
N/L-
R/L11
S/L21
T/MC1
∗5
P24
SD
RDYA
RDYB
RSO
SE
Inverter
∗2
P1
P/+
N/-
∗3
PC
SD
∗6
X10 ∗4
RES
Do not connect anything to power input terminals (R/L1, S/L2, T/L3). Incorrect connection will damage the inverter. (E.OPT (option fault) will occur.
Remove the jumper across terminals P/+ and P1.
Do not insert an MCCB between terminals P/+ and N/- (between terminals P/L+ and P/+ or between N/L- and N/-). Connecting the opposite polarity of terminals N/- and P/+ will damage the inverter.
Use Pr.178 to Pr.189 (input terminal function selection) to assign the terminals used for the X10 signal.
Be sure to connect the power supply and terminals R/L11, S/L21, and T/MC1. Operating the inverter without connecting them will damage the power regeneration common converter.
Always connect terminal RDYB of the FR-CV to the inverter terminal where the X10 signal or the MRS signal is assigned to. Always connect terminal SE of the FR-CV to the inverter terminal SD. Not connecting these terminals may damage the FR-CV.
NOTE
• The voltage phases of terminals R/L11, S/L21, and T/MC1 and the voltage phases of terminals R2/L1, S2/L2, and T2/L3 must be matched.
• Use the sink logic (initial setting for the FM type) when the FR-CV is connected. It cannot be connected when the source logic is selected.
• For the parameter details, refer to the FR-F800 Instruction Manual (Detailed).
56
advertisement
Related manuals
advertisement
Table of contents
- 13 Inverter and peripheral devices
- 15 Peripheral devices
- 19 Inverter installation environment
- 21 Inverter installation
- 26 Details on the main circuit terminals
- 26 Terminal layout of the main circuit terminals, wiring of power supply and the motor
- 27 Wiring method
- 30 Applicable cables and the wiring length
- 32 Earthing (grounding) precautions
- 33 Details on the control circuit terminals
- 37 Control logic (sink/source) change
- 39 Wiring of control circuit
- 41 Wiring precautions
- 42 When supplying 24 V external power to the control circuit
- 43 Safety stop function
- 45 Components of the operation panel
- 46 Outline of the Main monitor indicator
- 47 Basic operation of the operation panel
- 48 PU connector
- 49 Ethernet connector
- 50 USB connector
- 52 Connection of the brake unit (FR-BU2)
- 54 Connection of the brake unit (FR-BU)
- 55 Connection of the brake unit (BU type)
- 56 Connection of the high power factor converter (FR-HC2)
- 57 Connection of the power regeneration common converter (FR-CV)
- 58 Connection of the power regeneration converter (MT-RC)
- 61 Leakage currents and countermeasures
- 63 Countermeasures against inverter-generated EMI
- 65 Built-in EMC filter
- 66 Power supply harmonics
- 67 Harmonic suppression guidelines in Japan
- 81 Daily inspection
- 81 Periodic inspection
- 82 Daily and periodic inspection
- 84 Checking the inverter and converter modules
- 84 Cleaning
- 85 Replacement of parts
- 104 Precautions for removal and reinstallation of the control circuit terminal block
- 107 Measurement of powers
- 107 Measurement of voltages and use of PT
- 108 Measurement of currents
- 108 Use of CT and transducer
- 108 Measurement of inverter input power factor
- 108 Measurement of converter output voltage (across terminals P and N)
- 109 Measurement of inverter output frequency
- 109 Insulation resistance test using megger
- 109 Pressure test
- 119 Appendix 1 Differences and compatibility with the FR-F
- 120 Appendix 2 Instructions for compliance with the EU Directives
- 123 Appendix 3 Instructions for UL and cUL
- 125 Appendix 4 Instructions for EAC
- 126 Appendix 5 Restricted Use of Hazardous Substances in Electronic and Electrical Products