advertisement
COMBUSTION - AIR
INTAKE
VENT
A 12-IN. (305 mm) MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT
SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
30
″
(762 mm)MIN
WORK AREA
5
3
/
4
″
(146 mm)
MANUAL
SHUTOFF
GAS VALVE
ACCESS OPENING
FOR TRAP
SEDIMENT
TRAP
DRAIN
CONDENSATE
TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 11—Attic Location and Working Platform
c. Route extended tube (blue label) to condensate trap and cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube a. Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to condensate trap.
b. Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was previously connected to the condensate trap by splicing to small diameter tube (factory-supplied in loose parts bag).
b. Route extended collector box pressure tube to relief port connection on the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
CONDENSATE TRAP FIELD DRAIN ATTACHMENTS
Refer to Condensate Drain section for recommendations and procedures.
PRESSURE SWITCH TUBING
The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. This tube MUST be discon-
A93031 nected, extended, rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces.
NOTE: See Fig. 10 or tube routing label on main furnace door to check for proper connections.
Modify tube as described below:
1. Disconnect collector box pressure tube (pink label) attached to
High Pressure Switch.
2. Use smaller diameter tube (factory-supplied in loose parts bag) to extend tube disconnected in item 1.
3. Route extended tube: a. Behind inducer housing.
b. Between blower shelf and inducer housing.
4. Determine appropriate length, cut, and reconnect tube to High
Pressure Switch connection labeled COLLECTOR BOX.
CONDENSATE TRAP FREEZE PROTECTION
Refer to Condensate Drain Protection section for recommendations and procedures.
CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 11.)
11
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 2 Safety Considerations
- 2 Introduction
- 5 Codes and Standards
- 5 Safety
- 5 General Installation
- 5 Combustion and Ventilation Air
- 5 Duct Systems
- 5 Acoustical Lining and Fibrous Glass Duct
- 5 Gas Piping and Gas Pipe Pressure Testing
- 5 Electrical Connections
- 5 Electrostatic Discharge (ESD) Precautions Procedure
- 6 Applications
- 6 General
- 6 Upflow Applications
- 6 Orientation)
- 8 Condensate Trap Field Drain Attachment
- 8 Pressure Switch Tubing
- 8 Drain Connections
- 8 Condensate Trap Freeze Protection
- 8 Downflow Applications
- 8 Condensate Trap Location
- 9 Condensate Trap Tubing
- 9 Condensate Trap Field Drain Attachment
- 9 Pressure Switch Tubing
- 10 Condensate Trap Freeze Protection
- 10 Applications
- 10 Condensate Trap Location
- 10 Condensate Trap Tubing
- 11 Condensate Trap Field Drain Attachments
- 11 Pressure Switch Tubing
- 11 Condensate Trap Freeze Protection
- 11 Construct a Working Platform
- 12 Horizontal Right (Supply-Air Discharge) Applications
- 12 Condensate Trap Location
- 12 Condensate Trap Tubing
- 13 Condensate Trap Field Drain Attachment
- 13 Pressure Switch Tubing
- 13 Condensate Trap Freeze Protection
- 13 Construct a Working Platform
- 13 Location
- 13 General
- 14 Equipment
- 14 Hazardous Locations
- 14 Installation
- 14 Leveling Legs (If Desired)
- 15 Applications
- 16 Installation in Horizontal Applications
- 16 Air Ducts
- 16 General Requirements
- 17 Ductwork Acoustical Treatment
- 17 Supply Air Connections
- 18 Return Air Connections
- 18 Filter Arrangement
- 18 Bottom Closure Panel
- 19 Gas Piping
- 20 Electrical Connections
- 20 115-V Wiring
- 21 24-V Wiring
- 22 Accessories
- 22 Direct Venting
- 25 Systems
- 25 Combustion-Air and Vent Piping
- 28 Kit Installation
- 32 Multiventing and Vent Terminations
- 32 Condensate Drain
- 32 General
- 33 Application
- 34 Condensation Drain Protection
- 34 Start-Up Adjustment and Safety Check
- 34 General
- 35 Sequence of Operation
- 36 (Adaptive Mode)
- 36 (Non-Adaptive Heating Mode)
- 37 Cooling Mode
- 39 Continuous Blower Mode
- 39 Thermidistat Mode
- 39 Continuous Blower Mode
- 40 Heat Pump
- 40 Start-Up Procedures
- 40 Purge Gas Lines
- 42 Component Self-Test
- 44 Prime Condensate Trap With Water
- 44 Operate Furnace
- 44 Furnace Restart
- 44 Adjustments
- 44 Set Gas Input Rate
- 47 Set Temperature Rise
- 47 Adjust Blower Off Delay (Heat Mode)
- 47 Set Thermostat Heat Anticipator
- 48 Check Safety Controls
- 48 Checklist