Sensaphone STATIONSitter Manual

2. Press the CONFIGURE key.

The STATIONSitter will announce each Zone number and its detected Zone type.

The Zones are now considered normal. If a normally closed Zone becomes open, an alarm will occur. If a normally open Zone becomes closed, an alarm will occur.

MANUAL ZONE CONFIGURATION

If you would like to program the Zone type (NO, NC, temperature,

4–20mA) without going through the automatic process that scans all Zones, this command will allow you to configure a single Zone.

This command is useful if you have alarms on other channels and cannot use the automatic configuration process, or if you wish to configure the Zone type without actually connecting the sensor.

NOTE: You MUST use manual configuration for any zone connecting to a 2.8K temperature sensor.

To configure the Zone Type:

1. Press the SENSOR ON/OFF key.

2. Press the TABLE RANGE key.

32

The STATIONSitter will say “Enter Number.”

3. Press the corresponding Zone key (1–8).

advertisement