Sensaphone STATIONSitter Manual
ZONE CALIBRATION
Due to tolerance variations or other factors, you may need to program an offset to calibrate the sensor Zones. The offset can range from -15 to +15 for Zones configured as temperature, and -100 to
+100 for Zones configured as 4–20mA. Setting a positive number will add that number to the Zone reading. Setting a negative number will subtract the programmed value from the Zone reading.
For instance, if a temperature sensor consistently read two degrees high, you could use the calibration feature to adjust that temperature down two degrees. To make a value negative, precede the value with the [RINGS/TAD/*] Key.
To calibrate a Zone:
1. Press the SET key.
2. Press the CALIBRATE key.
Express will say “Enter number.”
3. Press the corresponding Zone key (1–8).
44
STATIONSitter will say “Enter Number.”
4. Enter the number. Then press ENTER.
Chapter 4: Zone Programming
STATIONSitter will say “OK.”
To play back the present calibration:
1. Press the WHAT IS key.
2. Press the CALIBRATE key.
3. Press the corresponding Zone key (1–8).
STATIONSitter will recite the programmed calibration.
45
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 FCC Requirements
- 7 Canadian Department of Communications Statement
- 9 3 YEAR LIMITED WARRANTY
- 18 FEATURES
- 19 LAYOUT
- 20 TECHNICAL SUPPORT
- 21 OPERATING ENVIRONMENT
- 21 Mounting the STATIONSitter
- 22 Grounding
- 23 TURNING THE STATIONSITTER ON
- 23 Backup Battery (optional)
- 24 Telephone Line
- 24 WIRING SENSORS AND TRANSDUCERS TO ZONE INPUTS
- 26 Wiring Recommendations
- 27 LED INDICATORS
- 29 HOW THE KEYPAD COMMANDS WORK
- 29 ABORTING A COMMAND
- 29 ERROR MESSAGES
- 30 ACKNOWLEDGING A FALSE ALARM
- 30 RECOMMENDED PROGRAMMING STEPS
- 31 CONFIGURE ZONE TYPE
- 32 MANUAL ZONE CONFIGURATION
- 33 ENABLE/DISABLE ZONE ALARMS
- 34 ENABLE/DISABLE SOUND LEVEL ALARM
- 34 ENABLE/DISABLE POWER
- 35 CONFIGURE TEMPERATURE SCALE
- 35 CONFIGURE TABLE RANGE FOR 4-20mA SENSORS
- 38 ALARM RECOGNITION TIME
- 41 ALARM LIMITS
- 44 ZONE CALIBRATION
- 46 SOUND LEVEL CALIBRATION
- 48 DESIGNATING A ZONE AS UNUSED
- 49 EXIT DELAY
- 51 DATE and TIME
- 53 VOICE MESSAGES
- 56 ID NUMBER
- 58 ALARM DIAL-OUT TELEPHONE NUMBERS
- 58 Voice Dialout
- 60 Numeric Pager Dialout
- 63 Alphanumeric Pager Dialout
- 67 SPECIAL DIALING OPTIONS
- 68 Blind Dialing
- 69 DIAL-OUT TEST MODE
- 70 ALARM ACKNOWLEDGMENT CODES
- 72 ALARM HISTORY
- 72 Deleting the Alarm History
- 73 TONE OR PULSE DIALING
- 74 RINGS UNTIL ANSWER
- 75 CALL DELAY TIME
- 77 INTERCALL TIME
- 79 CALL PROGRESS
- 80 VOICE REPETITIONS
- 81 MAX CALLS
- 83 TELEPHONE ANSWERING DEVICE (TAD) COMPATIBILITY
- 84 LISTEN-IN TIME
- 85 LOCKING THE KEYPAD
- 87 SPEAKER MUTE
- 88 CALLBACK ACKNOWLEDGMENT
- 89 Output Wiring
- 90 Level Sensor or Float Switch Selection
- 91 Analog Level Sensor Wiring
- 91 Float Switch Wiring for Draining the Well
- 92 Float Switch Wiring for Filling the Well
- 93 Installation Recommendations
- 93 Pump Control Programming
- 93 Analog Level Sensor Programming
- 95 Programming the Pump Control Mode
- 97 Float Switch Programming
- 99 Manually Controlling the Pump Outputs
- 100 Application Example
- 101 AUTOMATIC MODES
- 102 MANUAL MODE
- 102 Manually Switching the Auxiliary Output
- 107 ALARM DIALOUT AND ACKNOWLEDGMENT
- 107 Alarm Recognition
- 107 Alarm Notification
- 107 Dialout Note: Call Progress
- 107 Alarm Dialout—Voice
- 108 Alarm Dialout - Pager
- 108 Alarm Dialout - Alphanumeric Pager
- 109 ALARM ACKNOWLEDGMENT
- 109 Alarm Acknowledgment—Voice Dialout
- 110 Alarm Acknowledgment—Numeric Pager Dialout
- 111 Alarm Acknowledgment—Alphanumeric Pager Dialout
- 112 Alarm Acknowledgment—Automatic (Max Calls)
- 113 CALL-IN STATUS
- 114 REMOTE COMMANDS VIA TOUCH-TONE PHONE