Sensaphone STATIONSitter Manual
SOUND LEVEL CALIBRATION
This feature allows you to program the level of sound that will cause the STATIONSitter to respond to an alarm and dial out. It may be useful to desensitize the STATIONSitter to sound if it is installed in an area with a relatively high noise level, or where a loud noise occurs frequently but is not associated with an alarm. In some applications, it may be desireable to increase sound sensitivity to low Sound Levels. The sensitivity setting (calibration) for sound alarm monitoring ranges from 1 to 255. A value of 1 makes the microphone the MOST sensitive to changes in sound. The value
255 makes the microphone the LEAST sensitive to sound. The default value is 32.
To calibrate the Sound Level:
1. Press the SET key.
2. Press the CALIBRATE key.
3. Press the SOUND key.
The STATIONSitter responds: “Enter number.”
4. Using the number keys, enter a value for sound calibration and press ENTER
46
Chapter 4: Zone Programming
STATIONSitter will say, “OK.”
To play back the Sound Level calibration:
1. Press the WHAT IS key.
2. Press the CALIBRATE key.
3. Press the SOUND key.
The STATIONSitter will recite the programmed sound sensitivity level.
47
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 5 FCC Requirements
- 7 Canadian Department of Communications Statement
- 9 3 YEAR LIMITED WARRANTY
- 18 FEATURES
- 19 LAYOUT
- 20 TECHNICAL SUPPORT
- 21 OPERATING ENVIRONMENT
- 21 Mounting the STATIONSitter
- 22 Grounding
- 23 TURNING THE STATIONSITTER ON
- 23 Backup Battery (optional)
- 24 Telephone Line
- 24 WIRING SENSORS AND TRANSDUCERS TO ZONE INPUTS
- 26 Wiring Recommendations
- 27 LED INDICATORS
- 29 HOW THE KEYPAD COMMANDS WORK
- 29 ABORTING A COMMAND
- 29 ERROR MESSAGES
- 30 ACKNOWLEDGING A FALSE ALARM
- 30 RECOMMENDED PROGRAMMING STEPS
- 31 CONFIGURE ZONE TYPE
- 32 MANUAL ZONE CONFIGURATION
- 33 ENABLE/DISABLE ZONE ALARMS
- 34 ENABLE/DISABLE SOUND LEVEL ALARM
- 34 ENABLE/DISABLE POWER
- 35 CONFIGURE TEMPERATURE SCALE
- 35 CONFIGURE TABLE RANGE FOR 4-20mA SENSORS
- 38 ALARM RECOGNITION TIME
- 41 ALARM LIMITS
- 44 ZONE CALIBRATION
- 46 SOUND LEVEL CALIBRATION
- 48 DESIGNATING A ZONE AS UNUSED
- 49 EXIT DELAY
- 51 DATE and TIME
- 53 VOICE MESSAGES
- 56 ID NUMBER
- 58 ALARM DIAL-OUT TELEPHONE NUMBERS
- 58 Voice Dialout
- 60 Numeric Pager Dialout
- 63 Alphanumeric Pager Dialout
- 67 SPECIAL DIALING OPTIONS
- 68 Blind Dialing
- 69 DIAL-OUT TEST MODE
- 70 ALARM ACKNOWLEDGMENT CODES
- 72 ALARM HISTORY
- 72 Deleting the Alarm History
- 73 TONE OR PULSE DIALING
- 74 RINGS UNTIL ANSWER
- 75 CALL DELAY TIME
- 77 INTERCALL TIME
- 79 CALL PROGRESS
- 80 VOICE REPETITIONS
- 81 MAX CALLS
- 83 TELEPHONE ANSWERING DEVICE (TAD) COMPATIBILITY
- 84 LISTEN-IN TIME
- 85 LOCKING THE KEYPAD
- 87 SPEAKER MUTE
- 88 CALLBACK ACKNOWLEDGMENT
- 89 Output Wiring
- 90 Level Sensor or Float Switch Selection
- 91 Analog Level Sensor Wiring
- 91 Float Switch Wiring for Draining the Well
- 92 Float Switch Wiring for Filling the Well
- 93 Installation Recommendations
- 93 Pump Control Programming
- 93 Analog Level Sensor Programming
- 95 Programming the Pump Control Mode
- 97 Float Switch Programming
- 99 Manually Controlling the Pump Outputs
- 100 Application Example
- 101 AUTOMATIC MODES
- 102 MANUAL MODE
- 102 Manually Switching the Auxiliary Output
- 107 ALARM DIALOUT AND ACKNOWLEDGMENT
- 107 Alarm Recognition
- 107 Alarm Notification
- 107 Dialout Note: Call Progress
- 107 Alarm Dialout—Voice
- 108 Alarm Dialout - Pager
- 108 Alarm Dialout - Alphanumeric Pager
- 109 ALARM ACKNOWLEDGMENT
- 109 Alarm Acknowledgment—Voice Dialout
- 110 Alarm Acknowledgment—Numeric Pager Dialout
- 111 Alarm Acknowledgment—Alphanumeric Pager Dialout
- 112 Alarm Acknowledgment—Automatic (Max Calls)
- 113 CALL-IN STATUS
- 114 REMOTE COMMANDS VIA TOUCH-TONE PHONE