WattMaster Water Source Heat Pump Operations Manual
Реклама
Реклама
WHP - Water Source Heat Pump
Design, Installation &
Operations Manual
Revision 02A
WattMaster WHP
Installation & Operations Manual
Section 1.................................................................................... Design Guide
Section 2................................................................... Installation and Wiring
Section 3....................................................................................Programming
Section 4....................................................... Start-Up and Troubleshooting
This document is subject to change without notice.
WattMaster Controls, Inc. assumes no responsibility for errors, or omissions herein.
WHP Installation & Operations Manual - Form WM-WHP-IO-02A
Copyright 2004 WattMaster Controls, Inc.
All rights reserved.
Section 1
Table of Contents
Conventions ..................................................................... 1
General Information......................................................... 2
Water Source Heat Pump Units .......................................................................................2
Water Source Heat Pump Systems ..................................................................................3
WattMaster WHP Control System...................................................................................4
WHP Controller ...........................................................................................................4
Make Up Air Controller...............................................................................................5
WHP Sequence of Operation ........................................... 6
HVAC Mode of Operation...............................................................................................6
Occupied/Unoccupied Mode of Operation ......................................................................7
Vent Mode Operation ......................................................................................................7
Off Mode of Operation ....................................................................................................7
HVAC Operation w/ Reversing Relay.............................................................................8
HVAC Operation w/ Heat/Cool Relays ...........................................................................9
WHP Loop Controller Sequence of Operations ............. 10
Summary ........................................................................................................................10
Pump Control .............................................................................................................10
Pump VFD Control ....................................................................................................11
Compressor Control ...................................................................................................11
Heat Rejection Control ..................................................................................................12
Staged Heat Rejection................................................................................................12
Heat Addition Control ...................................................................................................12
Staged Heat Addition .................................................................................................13
Proportional Heat Addition........................................................................................13
Water Temperature Alarming ........................................................................................14
Fire Alarm......................................................................................................................14
Notes: ............................................................................. 16
Table of Figures
Figure 1-1: Typical Water Source Heat Pump..............................................................3
Figure 1-2: Typical Water Source Heat Pump System.................................................3
Figure 1-3: Typical WattMaster WHP System...........................................................15
Design Guide
WattMaster WHP
Section 1
Conventions
This document uses the following definitions throughout as a guide to the user in determining the nature of the information presented:
Note: Additional information which may be helpful.
Tip: Suggestion to make installation, set-up, and troubleshooting easier.
Caution: Items which may cause the equipment not to function correctly but will not otherwise damage components.
Warning:
Errors which can result in damage to equipment and void warranties.
Design Guide
1-1
Section 1
WattMaster WHP
General Information
Water Source Heat Pump Units
A water source heat pump is a self-contained water-cooled packaged heating and cooling unit with a reversible refrigerant cycle. Its components are typically enclosed in a common casing, and include a tube-in-tube heat exchanger, a heating/cooling coil, a compressor, a fan, a reversing valve and controls .
1-2
Design Guide
WattMaster WHP
Section 1
Figure 1-1: Typical Water Source Heat Pump
During the cooling mode, the tube-in-tube heat exchanger functions as a condenser and the coil as an evaporator. In heating mode, the tube-in-tube heat exchanger functions as an evaporator and the coil as a condenser. A reversing valve is installed in the refrigerant circuit permitting changeover from heating to cooling, and vice versa. The condenser and evaporator tubes are designed to accept hot and cold refrigerant liquid or gas.
Water Source Heat Pump Systems
The water source heat pump system is, by definition, a heat recovery system. It is best applied to buildings that have simultaneous cooling and heating loads. This is the case during winter months when the interior zones of a typical building require cooling while the exterior zones require heating. When a water source heat pump system is used, the heat rejected by the cooling units is used to warm the zones calling for heat. A water heater is generally used for adding heat to the condensing water during peak heating periods, if necessary. The system also utilizes a water cooling tower to reject the heat energy from the condenser water loop during periods of high cooling demand.
Water source heat pump units can be suspended in the ceiling plenum, floor mounted behind walls or placed directly in the occupied space as a console unit. There are also rooftop and unit ventilator type water source heat pumps.
Figure 1-2: Typical Water Source Heat Pump System
Water source heat pump systems generally cost less to install than central built-up systems. They offer individual zone control with the added flexibility of being able to
Design Guide
1-3
Section 1
WattMaster WHP accommodate changes in location and sizes as thermal zones or zone occupancy change.
This system is often installed in ceiling plenums, which frees up valuable floor space.
Another valuable benefit of water source heat pumps is that they can accommodate simultaneous calls from zones requiring heating or cooling. Depending on the climate, outside air may require preheat or cooling prior to being introduced to the unit. In the example of ceiling mounted water source heat pumps, put outside air ducts near each unit to improve indoor air quality.
Normally, multiple units serve an occupied space. This gives component redundancy to the system so if one unit were to fail, the other units could back it up until the unit was repaired. The packaged design of most unit types allows quick change-out by service personnel so maintenance can typically be performed off site.
As with any HVAC system, there is a negative side as the water source heat pump system often requires higher maintenance costs than conventional air side systems. The system also typically has a shorter replacement life than other systems because of continuous fan and compressor operation during heating and cooling modes. The system can also create room noise since the compressor and fan are commonly located close to the zone occupant. Placing units away from the occupied space and ducting the supply air to the zone can minimize potential noise problems.
WattMaster WHP Control System
The WattMaster WHP system is used to control the water loop and the individual water source heat pumps installed in a typical water source heat pump system. The WHP system is an excellent alternative over programmable thermostats. The WHP control system provides one central location to monitor and program all the water source heat pumps on the system instead of having to program each water source heat pumps thermostat individually. The system has many features typically not found with programmable thermostats such as: central operators interface, heating/cooling failure alarm, auxiliary alarm, and holiday scheduling, to name but a few.
WHP Controller
The Water Source Heat Pump Controller (WHP) is used for controlling individual water source heat pump units. The WHP Controller can operate stand-alone or it can be used with the Water Source Heat Pump Loop Controller and in this configuration shares common data, such as outside air temperature, proof of flow etc., over a network. A
System Manager is connected to the WHP Controller to provide a central operators interface to all WHP Controllers on the network. WHP Controllers are designed with
Room Temperature, Room Setpoint Adjust, Discharge Air Temperature, Leaving Water
Temp or Dirty Filter Alarm and Auxiliary Lockout inputs. Relay outputs provided are;
Fan (Continuous or Cycling), Reversing Valve-ON/OFF, Compressor-ON/OFF, Heat
1-4
Design Guide
WattMaster WHP
Section 1
Pump Reset and Aux. Heating or Cooling. An internal seven day schedule and holiday schedule functions are also built into each WHP Controller.
With the WHP system the sometimes complex control requirements of a large water source heat pump system can be handled with an off the shelf controls system that has most of the features of a full blown building automation system but at a much lower cost.
Included with the WHP system is a communications interface module, which allows you to connect a computer to the system onsite and a modem connection for remote monitoring.
Prism, a Windows based software package is available at no additional charge. Some of
Prism’s features include graphics, trend logging, and remote alarm call out capabilities.
WHP Loop Controller
The Water Source Heat pump Loop Controller can be supplied with the system to control the water loop and its various pieces of equipment. The Loop Controller can operate stand-alone or used with the Water Source Heat Pump Controller (WHP) and in this configuration communicates common data, such as outside air temperature, proof of flow etc., over a network. A System Manager is connected to the Loop Controller to provide a central operator’s interface to the Loop Controller’s setpoints and operating configurations. The Loop Controller is designed with inputs for Supply and Return Water
Temperature, Outdoor Air Temperature, Loop Water Pressure Switch or 0-50 PSI Loop
Pressure Sensor (4-20ma), Manual Reset Contact, Phase Loss Contact, Request to Run
Relay, and Fire/Smoke Relay. Analog outputs (0-10VDC) are supplied for Pump VFD and Proportional Heat. Binary outputs are provided for Compressor Enable, Main Pump
Relay, Standby Pump Relay, Alarm Contacts and (8) Relays that can be configured for
Heat Rejection or Heat Addition.
Make Up Air Controller
A Make Up Air Controller, for treating 100% outdoor air, is available for use with the
Water Source Heat Pump system. Please consult factory for more information on this product.
Design Guide
1-5
Section 1
WattMaster WHP
WHP Sequence of
Operation
HVAC Mode of Operation
There are four possible modes of operation. These are Cooling Mode, Heating Mode,
Vent Mode, and the Off Mode. The HVAC mode of operation is calculated the same way in both occupied and unoccupied modes of operation.
Off Mode The schedule is off and no overrides are active. There is no heating or cooling demand in the space. Under these conditions, all outputs will be off and the analog output will be set to 0.0 vdc.
Vent Mode No heating or cooling demand exists during the occupied mode of operation. The fan will be on if the WHP is programmed for Constant Fan operation. The compressor demand request will not be sent to the Loop
Controller. If no WHP units are sending a request, the Loop Controller will discontinue operation after 15 minutes.
Cool Mode A cooling demand is generated when the space temperature rises half the amount of the Deadband Setpoint above the currently active Cooling
Setpoint. The space is considered satisfied when it drops that amount below the Cooling Setpoint.
Heat Mode A heating demand is generated when the space temperature drops half the amount of the Deadband Setpoint below the currently active Heating
Setpoint. The space is considered satisfied when it rises that amount above the Heating Setpoint.
1-6
Design Guide
WattMaster WHP
Section 1
Occupied/Unoccupied Mode of
Operation
Since the WHP contains its own built in Real Time Clock, it can operate from its own internal scheduling system. This schedule supports two Start & Stop events per day and up to 14 Holiday periods. The Holidays all use the same special Holiday Start/Stop times programmed by the user.
If the current operating mode is unoccupied, the WHP can accept a push-button override back to the occupied mode. Push-button overrides are not recognized if the current mode is already occupied. The push-button override duration is user programmed. If the user wants to extend the current override without reprogramming the Duration, they can reinitialize the existing programmed period by pressing the override button anytime during the current override. If the current override had been active for 1 hour and 45 minutes and the user presses the push-button again, the override will reset for another 2 hour period (if
they programmed a 2 hour period), bringing the total override time to 3 hours and 45 minutes. If the user wants to cancel an override before it can time-out, simply hold the push-button for a period of time between 3 and 10 seconds.
The WHP calculates its current heating and cooling setpoints based on the current mode of operation. If the command is for unoccupied mode, the WHP adds the unoccupied setbacks to the occupied heating and cooling setpoints.
Vent Mode Operation
During occupied hours when there is no heating or cooling demand, the WHP reverts to a
Vent Mode of operation. The fan is running and the heating and cooling outputs are held off.
See the section titled HVAC Mode of Operation for a graphical description of how the
Vent Mode is calculated.
Off Mode of Operation
After the schedule goes unoccupied and both heating and cooling demands go away, the fan stops running, all relay outputs are turned off. No outputs are allowed to activate in the Off Mode until a heating or cooling demand occurs. During occupied hours this would be the Vent Mode.
Design Guide
1-7
Section 1
WattMaster WHP
HVAC Operation w/ Reversing Relay
If the user has configured the WHP to control a Reversing Valve and a Compressor, the following sequence of operation occurs during a heating or cooling demand.
Note: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by the WHP during a demand condition and that the Loop Controller gave permission for the WHP to start its compressor. Otherwise, the WHP will ignore the Enable signal and operate anytime there is a heating or cooling demand.
a. b. If the unit is configured to control an Isolation Valve, the valve relay is activated ( Relay #5 ). The Minimum Off Timer is reset to ZERO and must be satisfied before any further operations are allowed.
c.
If the last mode was the opposite of the current demand mode, make sure the Changeover Delay has been satisfied.
If the current mode requires the Reversing Valve to be activated, its relay contact is closed and a 10 second delay is started.
d. Ten seconds after the Reversing Valve is activated, the Compressor relay is activated.
e. If the Space Temperature continues to exceed the affected setpoint by the full amount of Deadband and you have configured for 2 stages in the current mode of operation, relay #5 will activate for the second stage of heating and/or cooling. A second stage of either implies that no Isolation
Valve exists!
f. Once the Space Temperature has crossed back over the affected setpoint, stage 2 will be turned off if the unit has a stage 2.
g. As the Space Temperature continues to cross back over the affected setpoint by half the Deadband value, the compressor will then be allowed to turn off if the Minimum Run Time has been satisfied.
1-8
Design Guide
WattMaster WHP
Section 1
HVAC Operation w/ Heat/Cool Relays
If the user has configured the WHP to control Individual Heating and Cooling relays the following sequence of operation occurs during a heating or cooling demand.
NOTE: If you configure the WHP to look for a proof of flow Enable signal from the
Loop Controller then the following sequence assumes a request was made by the WHP during a demand condition and that the Loop Controller gave permission for the WHP to operate its heating or cooling. Otherwise, the WHP will ignore the Enable signal and operate anytime there is a heating or cooling demand.
Once a heating or cooling demand exists, the following conditions must be met before any relays can be activated: a. Make sure any stages of the opposite mode are staged off.
b. Verify the system has been configured for at least one stage of heating or cooling.
c. Make sure the Minimum Cycle Time has been satisfied.
d. If the last mode was the opposite demand mode, make sure the
Changeover Delay has been satisfied.
e. Check the current Minimum Off Timer to make sure this stage has been off long enough since the last time it was cycled on and back off.
f. g.
If there is more than 1 stage, check the Minimum Run Time from the previous stage to be sure it has elapsed before activating the second stage.
Make sure the Space Temperature Demand is the full amount of Deadband from the setpoint before activating the second stage.
h. Once the compressor or stage 2 has been turned off, a Minimum Off Time must be satisfied before it can stage on again. A Minimum Cycle time can also be utilized to limit the number of times per hour that the compressor can be activated. If you don’t need this limitation, set the Minimum Cycle
Time to be shorter than the Minimum Run Time setpoint.
i. If the Reversing Valve was configured to cycle with the compressor, it will now turn off also. It can be configured to remain active until the opposite mode of operation is called for to reduce wear on the valve.
Design Guide
1-9
Section 1
WattMaster WHP
WHP Loop Controller
Sequence of Operations
Summary
The Water Source Heat Pump Loop Controller waits for a Request to Run signal from a
Heat Pump or from a Binary Contact Closure. Once the request is received the Loop
Controller activates a Pump to initiate water flow to the Heat Pumps. Once the pump is activated and proof of flow has been determined, a Global is broadcast to all Heat Pumps to enable them to go ahead and run their compressors. The main goal of the Loop
Controller is to provide water flow and to maintain the loop water temperature by monitoring either the Loop Inlet or Loop Outlet temperature. If a higher temperature is required, Heat Addition is enabled. If the temperature needs to be lowered, Heat
Rejection is enabled.
Once the Loop Controller has been activated by a request, it will run for a minimum of 15 minutes to prevent cycling on and off due to borderline requests from the Heat Pumps.
If a Fire Alarm is detected, the Loop Controller generates a Global broadcast to all Heat
Pumps to turn off.
If the High Pressure option is configured, the Loop Controller can generate a Global broadcast to force the Heat Pumps to open their Isolation Valves to reduce loop pressure if the high limit has been exceeded.
Pump Control
If WattMaster Water Source Heat Pump Controllers are used in conjunction with the
Loop Controller, a Global Binary signal from the attached Heat Pumps sends a Request to run or Enable to Run command to the Loop Controller. If the Loop Controller is used in a stand alone configuration, a contact closure on the AIN 2 of the Analog Expansion board gives the controller a request to run. When a request to run is received, the Loop
Controller activates a pump to initiate water flow to the heat pumps. The pumps can either be constant flow or controlled by a VFD. If the request goes away for at least one minute, the request to run command is removed. If the loop controller has been running a minimum of 15 minutes then it can be turned off, since there is no longer a request to run.
If the proof of flow is lost while the pumps are running, the pump is shut off immediately if the changeover to the Standby Pump had already been made.
The pumps are Lead/Lag controlled based on a user definable number of hours. If one pump exceeds the other pumps run time by this amount, the lead is changed until that
1-10
Design Guide
WattMaster WHP
Section 1 pump exceeds the first pumps run time by the same amount. This keeps both pumps with roughly the same number of hours on each pump. Changeover occurs at the time the run time setpoint is exceeded. The running pump is shut off at the same time the standby pump is energized, this prevents any down time or alarms. The unit can be configured to control either the Loop Inlet temperature or the loop outlet temperature.
A user adjustable low outdoor air temperature setting of XX degrees will allow the unit to run the pumps continuously for protection against freezing.
If the pump is constant volume, and the pump has been started, it has 3 seconds to generate flow or the standby pump is activated. If the pump is controlled by a VFD, once it starts, it has 60 seconds to generate flow and if it doesn’t the standby pump is activated.
If the standby pump fails, an alarm is generated and the Loop controller deactivates any active heat rejection or addition stages. At the same time an alarm is generated, we energize relay #5 on the Loop Controller board so that it may used to turn on a local alarm signal.
Loop flow can be determined by a binary contact closure on input #3 or a 0 to 50 PSI pressure sensor on input #3. If a pressure sensor is used, the user can program the pressure setpoint that needs to be met for proof of flow.
Pump VFD Control
An optional Pump VFD signal can be modulated if the system is configured for proportional control and a pressure sensor is attached to analog input #3.
At a user defined rate, the VFD signal is ramped up when the pressure is below a user defined setpoint by a user defined deadband. The signal ramps down when the pressure exceeds the setpoint by the deadband value. If the pressure ever exceeds the high pressure setpoint, an emergency override activates and begins cutting the VFD signal in half each time the control loop is polled by the software. This protects against run away over-pressurization.
The pump relay outputs are still activated and Lead/Lagged as described above and the pump relay remains on until the Request signal is removed, provided it has been operating for at least 15 minutes.
Compressor Control
Anytime a pump is running and proof of flow has been established, the compressor output is activated.
Design Guide
1-11
Section 1
WattMaster WHP
Heat Rejection Control
If the compressor is not running, no heat rejection can be active. If any heat rejection is still active when the compressor is turned off, the heat rejection will be immediately removed, without regard to any minimum run or off times.
Heat rejection cannot be active at the same time as heat addition, so any heat addition is removed or staged off before the heat rejection can be started.
A maximum of 8 stages of heat rejection can be controlled.
Staged Heat Rejection
Heat Rejection is staged up based on a different deadband level for each stage. Basically, if the user programmed a 2° deadband, then the first stage could activate at the setpoint, stage 2 would activate 2° above the setpoint, stage 3 would activate 4° above the setpoint, etc...
Staging down is calculated in the same manner, except the water temperature would need to drop below the setpoint by the deadband amount. If stage 3 was activated at 4° above setpoint, it would de-activate when the temperature fell to within 2° of setpoint, stage 2 would de-activate at setpoint and stage 1 would de-activate 2° below setpoint.
A user defined staging up and down interval must be met before any heat rejection stages can be added or removed. If the selected Water Temperature is above the current staging level and the timer has been satisfied, an additional stage can be added, up to the maximum available 8 stages. If the selected Water Temperature is below the staging down level and the timer has been satisfied, a stage can be removed.
Heat Addition Control
If the compressor is not running, no heat addition can be active. If any heat addition is still active when the compressor is turned off, the heat addition will be immediately removed, without regard to any minimum run or off times.
Heat addition cannot be active at the same time as heat rejection, so any heat rejection is removed or staged off before the heat addition can be started.
A maximum of 4 stages of heat addition can be controlled or proportional heating can be configured, and an analog output signal will be modulated to control the heat.
1-12
Design Guide
WattMaster WHP
Section 1
Staged Heat Addition
Heat Addition is staged up based on a different deadband level for each stage. Basically, if the user programmed a 2° deadband, then the first stage could activate at the setpoint, stage 2 would activate 2° below the setpoint, stage 3 would activate 4° below the setpoint, etc...
Staging down is calculated in the same manner, except the water temperature would need to increase above the setpoint by the deadband amount. If stage 3 was activated at 4° below setpoint, it would de-activate when the temperature rises to within 2° of setpoint, stage 2 would de-activate at setpoint and stage 1 would de-activate 2° above setpoint.
A user defined staging up and down interval must be met before any heat addition stages can be added or removed. If the selected Water Temperature is below the current staging level and the timer has been satisfied, an additional stage can be added, up to the maximum available 8 stages. If the selected Water Temperature is above the staging down level and the timer has been satisfied, a stage can be removed.
Proportional Heat Addition
If the Water Temperature is below the addition setpoint, a Boiler Enable relay is activated. If the Water Temperature rises 1° above the setpoint the Boiler Enable relay is de-activated.
At a user defined rate, the analog output signal is proportionally controlled from 0.0 VDC at 1° above setpoint to the full 10.0 VDC signal as the water temperature drops below the setpoint by the user defined deadband amount. If a 5° deadband was entered, the maximum voltage would be reached at 4° below the setpoint and the minimum voltage would be set at 1° above the setpoint. Since this is strictly proportional control, at 1.5° below setpoint the controller would set 5.0 VDC since that would be half the deadband amount.
Design Guide
1-13
Section 1
WattMaster WHP
Water Temperature Alarming
The controlling water temperature is monitored to prevent it from exceeding both a user defined High and Low Alarm Limit. If either limit is exceeded for a user defined length of time, an alarm is generated and the compressor output is de-activated. If the high limit is exceeded, the heat addition outputs are de-activated and if the low limit is exceeded, the heat rejection outputs are de-activated. The alarming and shutdown only pertains to the controlling water temperature. This does not affect the pump operation.
If a external manual alarm reset button is connected between ground and input #5, All outputs are turned off and ALL timers are reset. This forces the loop controller to stage off. This reset WILL shut down the pumps and force them to restart!
Fire Alarm
If the Fire Alarm is activated on input #1 of the Analog Input Expansion Board (Contact
OPENS for Alarm!) then ALL outputs and timers are reset and held off for the duration of the Fire Alarm signal.
If the Fire Alarm is not required, input #1 of the Analog Input Expansion Board must have a shorting wire to ground to allow the equipment to operate.
1-14
Design Guide
WattMaster WHP
COMPUTER
(OPTIONAL)
Section 1
RS-485
Comm Loop
Room Sensor with Optional
Override & Adj.
COMM
T
LD4
REC.
SHLD
R
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
24 VAC
110/24 VAC
Power Pak
Supply
Air
Sensor
F
Dirty Filter Alarm or Leaving Water Temp
Modem
(Optional)
110/24 VAC
Power Pak
Typical WHP Controller Wiring
MR
TR
SD
RD
OH
CD
AA
HS
CommLink II
Multiple Loop
Interface
COMM
MM
LINK
II
P
C
P
Network Loop
RS-485
19200 Baud
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
3
OUT
4
OUT
4-5
5
COM
4-5
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
Loop #1
WHP
Controllers
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
3
OUT
4
OUT
4-5
5
COM
4-5
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
W
AT
TM
AST
ER C
ONT
L
S, I
MiniLink
Loop # 1
T
SH
R
16
32
24VAC
GND
T
SH
R
Local Loop
RS-485
9600 Baud
System Manager
24VAC
MiniLink
Loop # 2
T
SH
R
16
32
GND
T
SH
R
03:38PM
OCCUPIED
NO
ALARMS
WED
MiniLink
Loop # 3
T
SH
R
24VAC
Local Loop
RS-485
9600 Baud
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
(Beldon #82760 or Equivalent)
NOTE: * Only One Outside Air Sensor is Required per WHP System
MiniLink
Loop # 4
T
SH
R
16
32
T
SH
R
T
SH
R
24VAC
GND
24VAC
24VAC
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
WHP Loop
Controller
RN1
CX1
U1
U2 CX2
TB1
COMM
T
SHLD
R CX5
LD6
COMM
U5
RS-485
COMM
HH
LD8
LED1
R1
LD9
LED2 P1
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ R28
C1
INPUTS ADDRESS
RAM
U6
ADD
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1 C12
AOUT2
AIN7
GND
PJ1
C17 D15
D8
PU4
D9
PU5
PU1
D6
PU2
D7
PU3
D11
PU7
D14
U13
SW1
CX13
U15
16
TOKEN
NETWORK
JP1
X2
CX15
C15
R22
R24
R25
R15
C14
R19
C20
R26
PRESSURE
SENSOR
EXPANSION
U3
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U10
U14
CX10
U12
CX14
CX6
CX12
T'STAT
U4
CX4
U9
VR1
PAL
C7
D12
R13
SC1
D19
VR2
L1
7824CT
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
V4
V5
TB2
R6
C9
U8
NE5090NPB3192
0PS
MC34064A
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
Loop # 4 24VAC
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
2
3
OUT
4
OUT
4-5
5
COM
4-5
PWR GND
24VAC
#1
32K
8K
COMM
T
SHLD
R
LD4
REC.
485
COMM
RAM EPROM
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
1
OUT
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#1
32K
8K
COMM
T
SHLD
R
LD4
REC.
RAM EPROM
12V
AIN
1
AIN
2
AIN
AIN
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
24VAC
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
See Note #3
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
#30
32K
8K
COMM
T
SHLD
R
LD4
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
2
3
OUT
4
OUT
4-5
5
COM
4-5
PWR GND
24VAC
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
1
OUT
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#29
32K
8K
COMM
T
SHLD
LD4
R
REC.
RAM EPROM
12V
AIN
1
AIN
2
AIN
AIN
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult factory for systems that exceed these quantities.
RELAY
3
OUT
4
OUT
4-5
5
COM
4-5
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
Figure 1-3: Typical WattMaster WHP System
Design Guide
1-15
Section 1
Notes:
WattMaster WHP
1-16
Design Guide
Section 2
Table of Contents
Tips Before Beginning Installation.................................. 1
Communications Loops ................................................... 3
Communications Loop Wiring Overview....................................................4
WHP Loop Controller ....................................................... 6
WHP Loop Controller Addressing .................................... 9
Supply & Return Water Temperature Sensors .............. 10
Outside Air Temperature Sensor................................... 12
CommLink II Interface................................................... 13
WHP Controller .............................................................. 14
WHP Controller Addressing ........................................... 17
MiniLink Addressing ...................................................... 18
Room Sensors ................................................................ 19
Supply Air Temperature Sensor .................................... 21
Leaving Water Temperature Sensors............................ 22
Installation and Wiring
Section 2
Table of Figures
Figure 2-1: System Overview ........................................................................................2
Figure 2-2: Communication Loop Wiring, Daisy-Chain Configuration .......................4
Figure 2-3: WHP Loop Controller.................................................................................6
Figure 2-4: WHP Loop Controller Wiring ....................................................................7
Figure 2-5: WHP Loop Controller Address Switch Setting ..........................................9
Figure 2-6: Duct Sensor with Thermowell...................................................................10
Figure 2-7: Strap-On Water Temperature Sensor ........................................................11
Figure 2-8: Outside Air Temperature Sensor ...............................................................12
Figure 2-9: CommLink Interface Wiring.....................................................................14
Figure 2-10: WHP Controller .....................................................................................14
Figure 2-11: WHP Controller Wiring .........................................................................15
Figure 2-12: WHP Controller Address Switch Setting...............................................17
Figure 2-13: MiniLink Address Switch Setting.........................................................18
Figure 2-14: Room Sensor Wiring..............................................................................19
Figure 2-15: Room Sensor ..........................................................................................20
Figure 2-16: Supply Air Temperature Sensor..............................................................21
Figure 2-17: Water Temperature Sensor .....................................................................22
Figure 2-18: Water Temperature Sensor .....................................................................22
Installation and Wiring
WattMaster WHP Section 2
Tips Before Beginning
Installation
Take a few moments to review the following before beginning installation of the
WattMaster WHP System.
•
Familiarize yourself with all system components and review all documentation. Pay special attention to “Cautions” and “Warnings” since these may keep you from experiencing unnecessary problems.
•
Before installing controllers, be sure to tag it with its appropriate location. It is also best to set the controller address switches before mounting. Use the WHP Address
Worksheet to list all WHP unit locations. This will assist you greatly when setting up the system.
•
Be sure and install all wiring according to local, state, and national electric codes.
•
Pay close attention to communication wiring since the most common mistakes are made in this area. Polarity is the most important rule. Make notes on your wiring diagrams as to which color wire you will be using on each terminal.
•
When in doubt - ask! Contact your local WattMaster distributor if you have any questions. The only dumb questions are the ones you don’t ask.
•
Remember - each electronic device contains only one puff of smoke. If you release it, you have voided the warranty! So please be careful and pay attention.
Installation and Wiring 2-1
Section 2 WattMaster WHP
COMPUTER
(OPTIONAL)
RS-485
Comm Loop
Room Sensor with Optional
Override & Adj.
32K 8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
24 VAC
110/24 VAC
Power Pak
Supply
Air
Sensor
F
Dirty Filter Alarm or Leaving Water Temp
Modem
(Optional)
110/24 VAC
Power Pak
Typical WHP Controller Wiring
MR
TR
SD
RD
OH
CD
AA
HS
CommLink II
Multiple Loop
Interface
COMM
MM
LINK
II
P
C
P
Network Loop
RS-485
19200 Baud
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
3
OUT
4
OUT
4-5
5
COM
4-5
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
W
AT
TM
ASTE
R C
ONT
L
S, I
NC
MiniLink
Loop # 1
T
SH
R
16
32
24VAC
GND
T
SH
R
Local Loop
RS-485
9600 Baud
System Manager
24VAC
MiniLink
Loop # 2
T
SH
R
16
32
24VAC
GND
T
SH
R
03
/3
1/
04
NO
OC
03
:3
CU
PI
AL
AR
8P
M
WE
D
MiniLink
Loop # 3
24VAC
Local Loop
RS-485
9600 Baud
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
(Beldon #82760 or Equivalent)
T
SH
R
32 16
NOTE: * Only One Outside Air Sensor is Required per WHP System
MiniLink
Loop # 4
T
SH
R
16
32
T
SH
R
T
SH
R
24VAC
GND
GND
24VAC
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
WHP Loop
Controller
RN1
CX1
U1
U2 CX2
TB1
COMM
T
SHLD
R CX5
LD6
COMM
U5
RS-485
COMM
HH
INPUTS
LD8
LED1
LD9
LED2
R1
P1
C1
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ R28
ADDRESS
RAM
U6
ADD
U3
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
CX6
U4
CX4
PAL
TB3
+VDC
AIN1
RN5
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1
AOUT2
AIN7
GND
PJ1
C17
C12
D15
D8
PU4
D9
PU5
PU1
D6
PU2
D7
PU3
D11
PU7
D14
U13
CX13
U15
SW1
32
16
TOKEN
NETWORK
U10
CX15
JP1
C14
C15
X2
R15
R19
R22
R24
R25
U14
C20
R26
PRESSURE
SENSOR
EXPANSION
CX10
U12
CX14
CX12
T'STAT
U9
VR1
C7
D12
R13
SC1
D19
L1
VR2
7824CT
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
V1
V2
V3
U8
NE5090NPB3192
0PS
R6
C9
MC34064A
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
Loop # 4 24VAC
#1
32K
8K
COMM
T
SHLD
R
LD4
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
2
3
OUT
4
OUT
4-5
5
COM
4-5
PWR GND
24VAC
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
1
OUT
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
RAM EPROM
12V
AIN
1
AIN
2
AIN
AIN
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
3
OUT
4
OUT
4-5
5
COM
4-5
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
See Note #3
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
3
OUT
4
OUT
4-5
5
COM
4-5
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
1
OUT
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#29
32K
8K
COMM
T
SHLD
LD4
R
REC.
RAM EPROM
12V
AIN
1
AIN
2
AIN
AIN
AIN
5
GND
GND
AOUT
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
3
OUT
4
OUT
4-5
5
COM
4-5
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
OUT
PWR GND
24VAC
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult factory for systems that exceed these quantities.
3
OUT
4
OUT
4-5
5
COM
4-5
RELAY
OUTPUT
COM
1-3
OUT
1
2
PWR GND
24VAC
Figure 2-1: System Overview
2-2 Installation and Wiring
WattMaster WHP Section 2
Communications Loops
The Communications Loop is two wire shielded RS-485. The loop is best connected in
daisy chain configuration, meaning the loop is connected from one controller to another.
It is not necessary to sequentially address the WHP Controllers in relation to their location on the loop. Cable must be Belden No. 82760 or equivalent.
Tip: Incorrect wiring of the communications loop is the most common mistake made during installation. Before beginning installation, write down the wire color used on each terminal connection and consistently maintain that color code. It is recommended that a continuous wire run be made between devices. Anytime a splice is made in the cable you increase your chance of problems.
Caution: Make sure when you are inserting wires into the terminal blocks that strands of wire do not stick out and touch the next terminal. This could cause a short or erratic operation.
Installation and Wiring 2-3
Section 2 WattMaster WHP
Communications Loop Wiring Overview
03/31/04 03:38PM WED
OCCUPIED
NO ALARMS
COMPUTER
(OPTIONAL)
POWER
24VAC
GND
COMMUNICATIONS
T
RS-485
SHLD
R
SYSTEM MANAGER POWER SUPPLY
YS101716 REV. 1
SYSTEM MANAGER
COMM LINK II
INTERFACE
(SET TO MULTIPLE LOOP)
UNIT COMES WITH
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 24VAC )
Remote Link
(OPTIONAL)
NETWORK
LOOP
U3
1
RN1
CX1
U1
U2 CX2
U4
CX4
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
AIN1
AIN2
AIN3
AIN4
AIN5
1
+VDC
U5
RS-485
COM M
HH
LD8
LED1
R1
LD9
LED2 P1
+VREF
5.11V
U7 TE ST POINT
EWDOG
C1
RV1
VRE F A DJ R28
INPUTS
RN5
RA M
U6
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
ADDRESS
SW1
ADD
1
2
4
8
32
16
TOKEN
NETWORK
U10
J P1
X2
CX10
CX6
CX12
TB3
GND
GND
C10
C12
AOUT1
AOUT2
AIN7
GND
PJ1
C17 D15
C20
U13
CX13
U15
C14
R15
R19 U14
C15
R22
R24
R25
U12
CX14
CX15
U9
1
PAL
C7
1
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION
T'STAT VR1
L1
VR2
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
V1
V2
V3
U8
NE5090NPB3192
0PS
R6
C9
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
32K
8K
COMM
T
LD4
SHLD
R
REC.
12V
AIN
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
5
GND
GND
AOUT
YS101564
0-5 VD
PWR
GND
24VAC
RELAY
OUTPUT
1-3
OUT
OUT
OUT
4-5
32K
8K
COMM
T
SHLD
LD4
R
REC.
12V
AIN
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
5
GND
GND
AOUT
YS101564
PWR
GND
24VAC
COM
1-3
OUT
OUT
4-5
TO OTHER WHP CONTROLLERS
TO OTHER MINILINKS
(NETWORK TERMINALS ONLY)
Figure 2-2: Communication Loop Wiring, Daisy-Chain Configuration
2-4 Installation and Wiring
WattMaster WHP Section 2
The daisy chain is the best method for running a communications loop since there is only one starting point and one ending point for each of the communications loops. Even though the daisy chain configuration is preferred, the star configuration can also be used.
If required, a combination of the two can also be used. Remember, the best communication loop wiring is the one which utilizes the minimum number of ends while using the shortest wiring path.
Note: The loop does not have to follow the controller address sequence.
Caution: If the comm loop is not installed in conduit, be careful to position the cable away from high noise devices like fluorescent lights, transformers,
VFD’s, etc. Conduit is not required for comm loop wiring unless required by local codes.
Make sure CommLink jumper is set for “Multi”.
Installation and Wiring 2-5
Section 2 WattMaster WHP
WHP Loop Controller
The WHP Loop Controller may be installed in any convenient protected location. It is recommended that the loop controller be mounted indoors in a secure location, that is not subject to extremes in temperature or moisture.
.20 Dia.
Typ. of 4
6.2’’
4.0”
7.3”
U3
1
RN1
CX1
U2
CX2
CX4
U1
U4
TB1
COMM
T
SHLD
R
CX5
U5
LD6
COMM
LD7
PWR
1
RS-485
COMM
HH
RAM EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
LD8
LED1
P1
C1
LD9
LED2
R1
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ
R28
U6
CX6
1
INPUTS
TB3
ADDRESS
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
R15
C14
R19
C20
CX15
C15
R22
R24
R25
U10
U14
CX10
U12
CX14
CX12
U9
PAL
C7
1
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION T'STAT
VR1
L1
VR2
7824CT
M
6.7”
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192
0PS
34064A
9936
R6
C9
MC
C13
C16
TB4
GND
24VAC
WHP Loop Controller Main Board
6.6”
9.5”
TB
1
TB
1
TB
1
0 2 R
V4
V1
V1
G
D
C A V
: T
0
S P P
N
5 2
C
4
A
1
T
A 5 L
C D
1 -
N
V
L
O
M
U
C
4 2
5 G
C
-IN
K1
R
C A V
: T
0
S P P
N
5 2
C
4
A
1
T
A 5 L
C D
1 -
N
V4
4RLY IO BD.
V
L
O
M
U
C
4 2
5 G
K4
C A V
: T
0
S P P
C
2
4
A
1
T
A 5 L
C D
1 -
N
L
V
O
4
5
C
2
G
N O R M O
4RLY IO BD.
K4
K1
C A V
: T
0
S P P
C
2
4
A
1
T
A 5 L
C D
1 -
N
L
V
O
4
5
C
2
G
N O R M O
N
D
+
24
VD
-O
C A V
: T
0 5
C
2
A T
S P P
N
A
O
UT
R
5
N O
4 1
C
1 -
D V
L
L
4
M
U
C
2
K2
O
K1
/ A 3 0 8 2 N L U
C A V
: T
S P P
0 5
N
C
4
2
A T
1
A
C
O R
-
5
N
V
L
L U
O C
4
M
2
O
K2
K3
RN1
YS101790
K2
C A V
:
S P P
T
0 5
C
4
2
1
T
A 5 L
C
1 -
N
V
L
O C
4 2
5 G
N O R M O
K3
K4
K1
K2
C A V
: T
S P P
0 5
C
4
2
1
T
A
C
1 -
5
L
V
O
L U
4 2
5 G
N O R M O
K3
RN1
0 4 7
P 4 7 5 8 F C P
/ A 3 0 8 2 N L U
0 4 7
P 4 7 5 8 F C P
YS101790
K3
K4
PHILIPS
HA
I D U1
U2
PHILIPS T L
I D U1
C
X2
U2
P1
U3
CX3
P1
U3
CX3
AIN1
R5
AIN2
AIN3
AIN4
R6
R7
GND
AOUT1
R8
R9
D5
1
R10
U2
PU1
PU2
C2
C3
PU3
C4
PU4
C5
C1
8 5 3 M L
JO1
JO2
JO3
JO4
R1
D1
R2
D2
R3
D3
R4
D4
4 ANALOG IN MOD. I/O BD.
YS101784
R9
CX1
1P
59
F8
PC
T L
PHILIP S
I D
U1
P1
YS
82
T
C
24
78
.
BD
I/O
D
UL
T M
O
0
2
1
1
1
R
R
1 R
P4
8.29”
8.96”
2.12” 0.28”
4.24”
WHP Loop Controller Expansion Board
Figure 2-3: WHP Loop Controller
2-6 Installation and Wiring
WattMaster WHP Section 2
Optional Pressure
Transmitter
Connect To Next WHP Controller
And/Or MiniLink On Local Loop
Local Loop RS-485
9600 Baud
Outside Air
Temp. Sensor
Return Water
Temp Sensor
Supply Water
Temp Sensor
See Note 4
Proof of
Flow
WHP Loop Controller Expansion Board
U3
CX1
1
RN1 U2
CX2
CX4
U1
U4
TB1
COMM
T
SHLD
R
CX5
LD6
U5
COMM
LD7
PWR
1
RS-485
COMM
HH
RAM
LD8
LED1
LD9
LED2
R1
P1
C1
+VREF
5.11V
U7 TEST POINT
EWDOG
RV1
VREF ADJ
R28
INPUTS
ADDRESS
TB3
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
RN5
GND
C10
GND
AOUT1
C12
AOUT2
AIN7
GND
PJ1
C17
D15
U6
PU4
D9
PU5
D11
PU7
D14
PU1
D6
PU2
D7
PU3
SW1
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
U13
CX13
U15
R15
C14
R19
C20
CX15
C15
R22
R24
R25
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U10
U14
CX10
U12
CX14
CX6
CX12
1
U9
PAL
1
C7
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION T'STAT
VR1
T
L1
VR2
7824C
M
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192
0PS
R6
C9
9936
34064A MC
C13
C16
TB4
GND
24VAC
R1
R2
R3
R (24 VAC By Others)
Compressor Enable
Main Pump
Standby Pump
N.C. Pilot Duty Relays
(By Others)
Alarm Indicator
Required VA For Transformer
Loop Controller = 8VA Min.
GND
Line Voltage
24VAC
See Note 1
Manual
Reset
Phase
Loss
Pump VFD
-
+
Optional
Modulating Heat
-
+
Notes:
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
3.)All Communication Wiring To Be
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Equivalent.
4.)When a Water Pressure Transmitter
Is Used, a 250 Ohm Resistor is
Installed Between AIN3 & GND and
The Pull Up Resistor PU3 is
Removed.
5.)If a Fire Alarm Contact is Not
Connected to AIN1 on The Analog
Expansion Board, Then a Jumper
Must Installed Between AIN1 and
GND.
Figure 2-4: WHP Loop Controller Wiring
N.C. Pilot Duty Relays
(By Others)
Heating/Cooling #1
Heating/Cooling #2
Heating/Cooling #3
Heating/Cooling #4
24 VAC
R5
R7
R4
R6
Heating/Cooling #1
Heating/Cooling #2
Heating/Cooling #3
R9
Heating/Cooling #4
24 VAC
Fire Alarm Contact (N.C.)(See Note 5)
R11
Request to Run Contact (N.O.)
R8
R10
Relay Contacts
(By Others)
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
WHP Loop Controller Expansion Board
Installation and Wiring 2-7
Section 2 WattMaster WHP
Warning:
Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to the terminal labeled GND on the controller. If a single transformer is used to power more than one controller you must connect GND-to-
GND and 24VAC-to-24VAC on each controller. Failure to observe polarity will result in damage to one or more components in your system.
The WHP Loop Controller requires the following electrical connections:
-24VAC Supply Voltage.................................................... 2 Conductors (18 Ga. Min.)
-Communications Loop ....... 2 Conductor twisted pair with shield (18 Ga. Minimum)
(Belden #82760, WattMaster Cable or equivalent)
-Supply Water Temperature Sensor................................... (24 ga. Min.) 2 Conductors
-Return Water Temperature Sensor .................................... (24 ga. Min.) 2 Conductors
-Outside Air Temperature Sensor ....................................... (24 ga. Min.) 2 Conductors
-Loop Pressure Sensor (Optional)........................................ (24 ga. Min) 2 Conductors
-Fire/Smoke Alarm Contacts .............................................. (24 ga. Min.) 2 Conductors
-Loop Pressure Switch ......................................................... (24 ga. Min) 2 Conductors
-Manual Reset Switch.......................................................... (24 ga. Min) 2 Conductors
-Request to Run Contacts .................................................... (24 ga. Min) 2 Conductors
-Analog Outputs................................................................... (24 ga. Min) 2 Conductors
-Binary Outputs.................................................................... (24 ga. Min) 2 Conductors
Tip: After making all electrical connections it is advised to unplug all terminal blocks on the WHP Loop Controller until you are ready to begin the checkout procedure. This may help to prevent damage if wiring errors occur elsewhere in the system during installation or start-up.
2-8 Installation and Wiring
WattMaster WHP Section 2
WHP Loop Controller
Addressing
The WHP Loop Controller must be set for address #30. See address setting instructions for the WHP Loop Controller that follow. A maximum of 29 WHP Controllers are allowed on the loop that contains the WHP Loop Controller. All other loops may have 30
WHP Controllers.
This Switch Should Be
In The OFF Position
As Shown
ADDRESS ADD
1
2
4
8
16
32
TOKEN
NETWORK
Controller
Address Switch
Address Switch Must Be Set For
Address 30 As Shown
Note:
The Power To The Controller Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution
Disconnect All Communication Loop Wiring From The
Controller Before Removing Power From The Controller.
Reconnect Power And Then Reconnect Communication
Loop Wiring.
INPUTS
TB3
ADDRESS
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
C10
GND
AOUT1 C12
AOUT2
AIN7
GND
PJ1
C17
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
ADD
1
2
4
8
16
32
TOKEN
NETWORK
JP1
X2
U10
CX10
R15
C14
R19 U14
U12
CX14
C15
R22
R24
R25
C20 CX15
CX12
R26
PRESSURE
SENSOR
EXPANSION
VR1
C7
D12
R13
SC1
D19
L1
VR2
R6
C9
C13
C16
TB4
GND
24VAC
Figure 2-5: WHP Loop Controller Address Switch Setting
Installation and Wiring 2-9
Section 2 WattMaster WHP
Supply & Return Water
Temperature Sensors
Sensors for monitoring supply and return water temperature are available in two main types, fluid immersion temperature sensors (See Figure 2-6) and strap-on sensors (See
Figure 2-7). Both are 0-10000 ohm thermistor type sensors. The fluid immersion sensor generally has better accuracy than the strap-on type but either is suitable for typical water source heat pump temperature requirements. The fluid immersion type sensor requires that a thermowell be installed in the pipe and the strap-on type, as its name implies, simply straps around the outside of the pipe. The fluid immersion sensor requires that the pipe be at least 4” in diameter in order to accept the thermowell. The strap-on type sensor is adjustable for use on 1/2” to 6” or larger diameter pipe.
The fluid immersion sensor is provided with a 4” long stainless steel thermowell. It has
½” MPT external threads and ½” FPT internal threads. A ½” FPT fitting to accept the thermowell must be provided by others in the pipe to be monitored, for connection of the thermowell. The thermowell is screwed into the ½” FPT fitting installed by others in the pipe and the sensor probe is then screwed into the ½” FPT fitting on the thermowell.
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
1/8-27 NPT External Thread
5.50
OE230 Duct Sensor
The OE230 Duct Sensor Threads Into The OE291 Stainless
Steel Thermowell. The OE291 Thermowell Threads Into A 1/2”
FPT Elbow or Tee in the Water Piping of the Water Coil
Where You Wish to Measure the Water Temperature. The
Pipe must be a minimum of 4” Diameter or an Extended Tee and Bushing Configuration Must be Used to Accommodate the
Length of the Thermowell Assembly.
1/8-27 NPSM Internal Thread
1/2" NPT External Thread
3.25
4.94
5.13
OE291 Stainless Steel Thermowell
0.5
Figure 2-6: Duct Sensor with Thermowell
2-10 Installation and Wiring
WattMaster WHP Section 2
The strap-on type sensor has a brass housing that senses the water temperature through contact with the exterior surface of the pipe. The sensor should be mounted in contact with the underside of the pipe in order to insure accurate temperature readings. The sensor assembly is secured to the pipe by using the supplied wire ties to wrap and secure the sensor to the pipe. Thermal conductive compound is also supplied to insure a good thermal connection with the pipe. The sensors are supplied with 3 foot long wire leads.
Wire Tire
(Supplied)
Supply Or Return
Water Pipe.
Sensing Element
(Supplied)
Thermal Mastic Strip
(Supplied)
Figure 2-7: Strap-On Water Temperature Sensor
Installation and Wiring 2-11
Section 2 WattMaster WHP
Outside Air Temperature
Sensor
The outside air sensor must be located where it will not be affected by direct sun or heat producing equipment. Mounting under the eve of a roof is often a good choice.
Caution: Complaints of inaccurate outside sensor readings are very common and can almost always be shown to be the result of poor sensor location.
Note: All temperature sensors supplied with the system utilize the same thermistor type sensing element. For troubleshooting sensor problems refer to the
TEMPERATURE SENSOR RESISTANCE CHART at the end of Section 4.
Gasketed Cover
3.00”
Cover
Mounting
Screw - Typ.
2.30”
2.70”
Closure Plug
0.21" Dia. x 0.73
Lg. Slot - Typ.
Mounting Tab
& Screws - Typ.
Sensor Tube
Front View Side View
Figure 2-8: Outside Air Temperature Sensor
Mounting Tab
& Screw - Typ.
Closure Plug
Back View
2-12 Installation and Wiring
WattMaster WHP Section 2
CommLink II Interface
The CommLink II Interface provides for communications between the MiniLink communication interfaces installed on the system. The CommLink II is required for proper communications, even if a PC is not used. Locate the CommLink II near the computer or modem if they are installed on the system. The cable connections between the CommLink II and the computer or modem should be kept to less than twenty-five feet. The CommLink II comes complete with computer and modem cables, and a plug-in power supply.
03/31/04 03:38PM WED
OCCUPIED
NO ALARMS
COMPUTER
(OPTIONAL)
POWER
24VAC
GND
COMMUNICATIONS
T
RS-485
SHLD
R
SYSTEM MANAGER POWER SUPPLY
YS101716 REV. 1
SYSTEM MANAGER
COMM LINK II
INTERFACE
(MULTIPLE LOOP)
UNIT COMES WITH
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 24VAC )
Remote Link
(OPTIONAL)
NETWORK
LOOP
U3
1
RN1
CX1
U1
U2 CX2
TB1
COMM
LD6
T
SHLD
R
CX5
U5
COMM
LD7
PWR
LD8
LED1
1
RS-485
COMM
C1
R1
LD9
LED2 P1
+VREF
5.11V
U7
RV1
TEST POINT
VREF ADJ
EWDOG
R28
HH
INPUTS ADDRESS
RAM
U6
ADD
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
CX6
U4
1
CX4
PAL
1
TB3
+VDC
RN5
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1
AOUT2
AIN7
GND
PJ1
C17
C12
D15
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U13
SW1
CX13
U15
1
2
4
8
16
32
TOKEN
NETW ORK
U10
JP1
X2
R15
C14
R19 U14
C15
R22
R24
R25
C20 CX15
CX10
U12
CX14
CX12
PRESSURE
SENSOR
R26
EX PANSION
T'STAT
U9
VR1
C7
D12
R13
SC1
D19
L1
VR2
7824CT
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
U8
NE5090NPB3192
0PS
9936
34064A
R6
C9
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
32K
8K
COMM
T
LD4
SHLD
R
REC.
12V
AIN
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
GND
AOUT
PRESSURE
SENSOR
YS101564
PWR
GND
24VAC
1-3
OUT
OUT
OUT
4-5
32K
8K
COMM
REC.
12V
AIN
4
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
OUT
OUT
4-5
PWR
GND
24VAC
TO OTHER WHP CONTROLLERS
TO OTHER MINILINKS
(NETWORK TERMINALS ONLY)
Figure 2-9: CommLink Interface Wiring
Installation and Wiring 2-13
Section 2 WattMaster WHP
WHP Controller
The WHP Controller may be installed in any convenient protected location. Observe the recommended environmental limitations for the WHP Controller when selecting a installation location. The environmental limitations are a temperature range of 10
°
F to
149
°
F, and a maximum operating humidity of 90% RH non-condensing.
The WHP Controller may be mounted by fastening to a flat surface through the mounting plate. The unit is mounted by four (4) screws in the corners. Select the correct screws or other fasteners for the type of mounting material being utilized.
RS-485
COMMUNICATIONS
LOOP
COMMUNICATIONS
LED
ADDRESS SWITCH
( ADDRESS 18 SHOWN )
ANALOG INPUTS
Space Sensor
Slide Adjust
Supply Air Temp
Leaving Water
Temp or
Dirty Filter
Lockout
COMMUNICATIONS
DRIVER CHIP
COMM
T
LD4
SHLD
R
REC.
12V
AIN
2
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
PIN 1
INDICATION
485
COMM
RAM
RAM EPROM
RAM SIZE
SELECT JUMPER
PAL
32K
8K
CPU
EPROM
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
2
OUT
OUT
4
OUT
5
COM
4-5
PWR
GND
STATIC PRESSURE
SENSOR INPUT
24VAC
24 VAC Common for Inputs 1 - 3
Fan-On/Off
Rev. Valve-On/Off (Heat 1)
Compressor-On/Off (Heat 2)
Heat Pump Reset (Cool 1)
Aux. Heating or Cooling (Cool 2)
24 VAC Common for Inputs 1 - 3
DIAGNOSTIC BLINK
CODE LED
REAL TIME
CLOCK CHIP
POWER LED
24VAC
POWER
INPUT
Mounting Backplate
Figure 2-10: WHP Controller
2-14 Installation and Wiring
WattMaster WHP
T
All Comm Loop Wiring Is
Straight Thru
T T T
SH SH SH SH
R R R R
Connect To
Next Controller
And/Or
MiniLink On
Local Loop
RS-485
9600 Baud
Room Sensor
TMP
NORMAL
OVR
E
R
W
A
R
M
C
O
O
L
E
R
Discharge
Air Temp.
Sensor
Mount In HVAC
Unit Supply
Air Duct
GND
AUX
Connection To
AUX Terminal is Reqd
Only When Sensor
Is Specified With
Slide Adjust Option
COMM
T
SHLD
R
LD4
REC.
WHP Controller
R
A
M
E
P
R
O
M
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
ADDRESS ADD
COMM
TEST
Dirty Filter
Alarm Contact
Section 2
RELAY
OUTPUTS
COM
1-3
OUT
1
OUT
2
OUT
3
OUT
4
OUT
5
COM
4-5
Water Source Heat Pump
Unit Connections
24VAC
Fan-On/Off
Rev. Valve-On/Off
Compressor-On/Off
Heat Pump Reset
Aux. Heating Or Cooling
Diagnostic Blink Code LED
PWR
GND
GND
Required VA For Transformer
Each WHP Controller = 10VA MIN.
24VAC
24VAC
Thermowell
Or Surface Mount
Temp Sensor
(Leaving Water Temp)
Lockout
Optional Features
CAUTION!
WHP CONTROLLERS
MUST HAVE ADDRESS SWITCHES
SET BETWEEN 1 AND 30
(UP TO 30 UNITS PER LOCAL LOOP)
EXCEPT ON THE LOOP WITH THE
LOOP CONTROLLER CONNECTED.
THE LOOP CONTROLLER ADDRESS
IS 30, WHICH ALLOWS FOR ONLY
29 WHP CONTROLLERS ON THIS
LOCAL LOOP.
Figure 2-11: WHP Controller Wiring
Warning:
Polarity is very important when connecting power to the controllers!
The grounded side of the control transformer must be connected to the terminal labeled GND on the WHP Controller. If a single transformer is used to power more than one WHP Controller you must connect GND-to-GND and 24VAC-to-24VAC on each WHP
Controller. Failure to observe polarity will result in damage to one or more components in your system.
Warning:
Use extreme care not to damage any of the electronic components while mounting the backplate. Mark the holes then remove the WHP
Controller from the backplate before drilling.
Do not allow metal shavings to fall onto the circuit boards.
Installation and Wiring 2-15
Section 2 WattMaster WHP
The WHP Controller requires the following electrical connections:
18 Gauge minimum unless otherwise noted.
-24VAC Supply Voltage........................................................................... 2 Conductors
-Communications Loop ...................................... 2 Conductor twisted pair with shield
(WattMaster Cable, Belden #82760 or equivalent)
-Discharge Air Temperature Sensor .................................. (24 ga. Min.) 2 Conductors
-Room Air Temperature Sensor...........(24 ga. Min.) 2 Conductors for standard sensor
3 Conductors for sensors with setpoint adjustment
-Outside Air Temperature Sensor ....................................... (24 ga. Min.) 2 Conductors
-WHP Unit Control Wiring ......................................................... (24 ga.Min.) 24 VAC
Fan- ON/OFF
Rev Valve-ON/OFF
Compressor-ON/OFF
Heat Pump Reset
Aux. Heating or Cooling
Tip: After making all electrical connections it is advised to unplug all terminal blocks on the WHP Controller until you are ready to begin the checkout procedure. This may help to prevent damage if wiring errors occur elsewhere in the system during installation or start-up.
2-16 Installation and Wiring
WattMaster WHP
WHP Controller
Addressing
NOTE:
IGNORE ANY MARKINGS
OR NUMBERS ON THE SWITCH
USE THE CHART!
To determine the boards address, add the values of all the switches which are toggled down in the direction of the arrow
Section 2
Figure 2-12: WHP Controller Address Switch Setting
NOTE:
ADDRESS 30 CANNOT BE USED
ON THE LOOP THAT HAS THE WHP LOOP
CONTROLLER ATTACHED. ADDRESS 30
ON THAT LOOP IS RESERVED FOR THE
WHP LOOP CONTROLLER.
CAUTION:
YOU MUST POWER DOWN THE CONTROLLER
AFTER CHANGING THE ADDRESS SWITCHES
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.
ALWAYS REMOVE THE COMMUNICATIONS LOOP
PRIOR TO DISCONNECTING POWER. RECONNECT
POWER AND THEN RECONNECT THE COMMUNICATIONS
LOOP TO THE CONTROLLER.
Installation and Wiring 2-17
Section 2 WattMaster WHP
MiniLink Addressing
Connect To Next
MiniLink And/Or
CommLink On
Network Loop
MiniLink Communications Interface
Network Loop
RS-485
19200 Baud
ADD
T
NETWORK
SH 8
16
32
2
4
R
1
OFF >
All Communication Loop
Wiring Is Straight Through
T
SH
T
SH
T
SH
T
SH
R R R R
24VAC
GND
24VAC
T
SH
LOOP
R
Local Loop
RS-485
9600 Baud
Line Voltage
Required VA For Transformer
MiniLink = 6VA Min.
See Note 1.
Connect To Next
Controller or
System Manager
1
2
4
8
16
32
ADD
Caution!
The MiniLinks Must Have Address Switches Set Between 1
And 30 (Up To 30 MiniLinks Are Allowed Per WHP System
System). The MiniLinks Should Be Addressed In
Consecutive Order Starting With Address #1. Address #1
Must Be Present On The Loop For The System To Function.
Note:
The Power To The MiniLink Must Be Removed And
Reconnected After Changing The Address Switch
Settings In Order For Any Changes To Take Effect.
Caution:
Disconnect All Communication Loop Wiring
From The MiniLink Before Removing Power
From The MiniLink. Reconnect Power And Then
Reconnect Communication Loop Wiring.
Notes:
1.)24 VAC Must Be Connected So
That All Ground Wires Remain
Common.
2.)All Wiring To Be In Accordance
With Local And National Electrical
Codes And Specifications.
3.) All Communication Wiring To Be
2 Conductor Twisted Pair With
Shield. Use Belden #82760 Or
Equivalent.
These Switches Must Be
In The OFF Position
As Shown
MiniLink
Address Switch
Address Switch Shown Is
Set For Address 1
Address Switch Shown Is
Set For Address 4
The Address For Each MiniLink
Must Be Unique To The Other MiniLinks
On The Network Loop. Loop #1 MiniLink
Should Be Addressed As #1
Loop #2 MiniLink Should Be Addressed
As #2 Etc..
Figure 2-13: MiniLink Address Switch Setting
2-18 Installation and Wiring
WattMaster WHP Section 2
Room Sensors
The room sensor uses a patented flush mount design to isolate the temperature sensing element from the housing which mounts flush with the wall surface.
Room sensors should be located on an inside wall away from direct sunlight or heat producing equipment such as computers, copiers, etc. Such devices can adversely affect the accuracy of the sensor.
Although the sensor eliminates most of the effects of thermal coupling to the walls, try to avoid walls which retain large amounts of thermal energy (such as marble or steel). Walls containing either cold or warm air currents should also be avoided whenever possible.
Avoid locating the sensor in dead air areas of a room. This will result in slow response to temperature changes in the space.
Mount the sensor approximately 50-60 inches from the floor for best results.
The room sensor is designed to mounted vertically in a standard 2 by 4 inch electrical box. The sensor may be mounted directly into the drywall where electrical codes do not require low voltage wiring to be enclosed in conduit. See enclosed sheet for dimensional and installation data.
Tip: Be careful when cutting the hole for the sensor or the plastic bezel of the sensor may not completely cover the opening.
WHP CONTROLLER
ROOM SENSOR WITH OVERRIDE
AND ADJUSTABLE SETPOINT
OVR
C
O
O
L
E
R
W
A
R
M
E
R
TMP
GND
AUX
ADJUSTABLE
SETPOINT
OVERRIDE
ONLY REQUIRED WHEN
USING ADJUSTABLE
SETPOINT
12V
2
3
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS
Figure 2-14: Room Sensor Wiring
Installation and Wiring 2-19
Section 2 WattMaster WHP
Connect the terminal labeled GND on the zone sensor to the terminal labeled GND on the
WHP Controller Analog Input terminal block. Connect the terminal labeled TMP on the zone sensor to the terminal labeled AIN 1 on the WHP Controller Analog Input terminal block. If the zone sensor has a setpoint adjust slider, then connect the sensor terminal labeled AUX to the WHP Controller AIN 2 terminal block.
Tip: If sensors must be installed on walls which are solid and cannot be penetrated, surface mounted boxes and raceway can be purchased from your local electrical distributor.
2.00“
2.75“
0.88“
TMP
GND
AUX
OUT W
A
R
M
E
R
C
O
O
L
E
R
0.25“
Wall Cut-Out Dimensions
When Sensor Is To Be
Mounted Without
Handy Box (By Others)
Figure 2-15: Room Sensor
2-20 Installation and Wiring
WattMaster WHP Section 2
Supply Air Temperature
Sensor
The supply air temperature sensor should be located in the duct, as close to the rooftop unit discharge as possible for best response.
Locate the sensor in the center of the widest part of the duct. Use the supplied template and a 5/16" drill to make a hole for the sensor. Install the gasket over the probe and mount securely to the duct using the supplied sheet metal screws. Be sure the gasket is compressed to provide an air tight seal.
For best accuracy, apply insulation on the outside of the duct, over the sensor. This will help prevent thermal gradients from affecting the sensor.
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
Thread
Together
4.0"
3/4"
5-1/2" (OE230)
11-1/2" (OE231)
Mounting Plate
1/4" Hex Head Sheet Metal Screws
Mounting Plate
Gasket
Adhesive Backed Drill Guide
Mounting Template
Duct Work
Drill 5/16" Hole In Ductwork For Probe
Figure 2-16: Supply Air Temperature Sensor
Installation and Wiring 2-21
Section 2 WattMaster WHP
Leaving Water
Temperature Sensors
The leaving water temperature sensor (optional) when used should be located on the leaving water piping close to the water source heat pump unit. Either a thermowell type or a surface mount sensor may be used depending on job requirements.
Leads Are Non-polarized.
Butt Splice Leads To 24 Gauge
Wire Minimum. Connect Leads
To "Analog In" And "Ground"
At Controller.
1/8-27 NPT External Thread
5.50
OE230 Duct Sensor
The OE230 Duct Sensor Threads Into The OE291 Stainless
Steel Thermowell. The OE291 Thermowell Threads Into A 1/2”
FPT Elbow or Tee in the Water Piping of the Water Coil
Where You Wish to Measure the Water Temperature. The
Pipe must be a minimum of 4” Diameter or an Extended Tee and Bushing Configuration Must be Used to Accommodate the
Length of the Thermowell Assembly.
1/8-27 NPSM Internal Thread
1/2" NPT External Thread
3.25
4.94
5.13
OE291 Stainless Steel Thermowell
0.5
Figure 2-17: Water Temperature Sensor
Supply Or Return
Water Pipe.
Wire Tire
(Supplied)
Sensing Element
(Supplied)
Figure 2-18: Water Temperature Sensor
2-22
Thermal Mastic Strip
(Supplied)
Installation and Wiring
Section 3
Table of Contents
LCD/Keypad Operations................................................... 1
System Manager Layout...................................................................................................2
Keypad Functions ............................................................................................................2
System Manager LED Indicators .....................................................................................3
Heat Pump Status Screens.............................................. 4
View Status Only .............................................................................................................4
View Alarms ....................................................................................................................8
Menu Setpoints ................................................................................................................9
Set Time & Date .............................................................. 9
New Passcodes.............................................................. 11
Rebuild Alarm Map......................................................... 12
Heat Pump Setpoints ..................................................... 13
Heat Pump Setpoint Menu .............................................................................................13
1) WHP Setpoints ..........................................................................................................13
2) WHP Schedules .........................................................................................................20
Holidays .........................................................................................................................21
3) Reset Pumps ..............................................................................................................22
Loop Controller Status .................................................. 23
Loop Controller Status Menu.........................................................................................23
Loop Controller Status Screens .................................... 23
Loop Controller Setpoints ............................................. 27
Loop Controller Setpoint Menu .....................................................................................27
Notes: ............................................................................. 32
Programming
WattMaster WHP Section 3
LCD/Keypad Operations
Main Screen
Heat Pump v1.xx
Tuesday Operations
04/13/04 09:15 AM
Outdoor Air 58.7°F
The Water Source Heat Pump System Manager is the operator’s interface to the status and setpoints of any WattMaster Water Source Heat Pump (WHP) component on your communications loop. With the System Manager, you can view any temperature or output condition and change any setpoint to fine tune the operations of the total system. All keypad operations are simple and straight-forward, utilizing non-cryptic plain English messages. The System Manager automatically detects the type of unit that has been selected, and displays the appropriate status and setpoint screens. The attractive plastic case of the System Manager allows for placement in any area of your building.
The remainder of this document will lead the user through the system menus and keypad operation.
All user functions are accessed by pressing the Menu button. Once the button is pressed, the Main User Menu is displayed.
Programming 3-1
Section 3
System Manager Layout
WattMaster WHP
Heat Pump v2.11
Wednesday Operations
7/21/04 04:35 PM
Outdoor Air 85.6°
Keypad Functions
The System Manager keypad is labeled either numerically or as to actual function for that key. Below is a summary of the labeled keys and their functions.
MENU
ESC
CLEAR
ENTER
DEC
MINUS
UP/DOWN
Arrows
LEFT/RIGHT
Arrows
This key is used to gain access to the first menu, and the user will be notified, on the LCD, if any subsequent use of the key will be required for further access.
The ESCape key allows the user to abort what they are doing or exit back to previous menus. Also, anytime you want to leave the system unattended you should press the ESC key until the Main Screen appears.
If you make a mistake while entering setpoint data, you can clear the bad data from the display by pressing the Clear key.
Use the Enter key to close out a data entry. It can also be used to advance to the next field or screen.
If entering a setpoint that requires a decimal point, press this key where the decimal is located while entering the value.
If you need to enter a negative value, you must press the Minus key before entering the digits for that value.
Use these keys to step forward or backward through Status Screens or
Setpoint Data Fields.
If the screen prompts you to use these keys, it is used normally to toggle modes of operation.
3-2 Programming
WattMaster WHP Section 3
System Manager LED Indicators
There are two LED indicators located on the right hand side of the System Manager.
The top LED indicates an Alarm condition if the Manager detects an alarm condition while polling the system.
The bottom LED is active during actual communications or packet transfers. This LED will normally “flicker” and not remain on constantly.
Main User Menu
1) View Status Only
2) View Alarms
MENU) Setpoints
ESC) Main Screen
1) View Status Only
2) View Alarms
MENU) Setpoints
ESC) Main Screen
For quick access to an individual heat pump or the loop controller, select this menu item. No passcode is required to access the status of any unit installed on your system.
If the System Manager has been configured for Alarm Polling, the user can select this item to get a list of unit addresses that are currently in alarm. If an alarm exists, the Alarm LED will be active on the right side of the panel.
If you are a Level 2 user, all system setpoints are available to you.
These setpoints are accessed via this Menu button.
When you have finished viewing the system you can exit this menu and return to the Main Screen by pressing the ESC button.
Programming 3-3
Section 3 WattMaster WHP
Heat Pump Status
Screens
View Status Only
Status Only View
[ Enter Unit ID# ]
Selected Unit: 101
By selecting the View Status Only menu item, you can access any heat pump or the loop controller and read all available temperatures, outputs, and operating conditions for the selected unit. No passcode is required to access these status screens, and no setpoints are available to the user from these screens. To access a unit, enter the Unit ID you wish to view. The Unit ID is actually two separate numbers, combined into one value. The first part of the number contains the Loop Address at which the zone is located. The second part of the number contains the actual
Board Address.
EXAMPLE: You would like to view the 3rd heat pump on the 5th loop. Enter 503 as the Unit ID
You would like to view the 12th heat pump on the 24th loop. Enter 2412 as the Unit ID
3-4 Programming
WattMaster WHP Section 3
If you selected menu item #1 View Status Only and you entered the Unit ID of an installed WHP Controller, the following Status Screens are available.
Status Screen #1
WSHPRV 1 V2.03
Space Temp.:xxx.x
°
F
CSP xx.x
°
HSP xx.x
°
Slide Adjust: x.x
°
F
Line 2 Current Zone Temperature
Line 3 -
Current Cooling Setpoint ( CSP
) and Heating
Setpoint ( HSP )
Line 4 Effect of optional Sensor Slide Adjustment on the current operating setpoints.
Status Screen #2
WSHPRV 1 V2.03
Supply Air.:xxx.x
°
F
Water Temp.:xxx.x
°
F
Outdoor Air:xxx.x
°
F
Line 2 Current Supply Air Temperature
Line 3 Current Leaving Water Temperature if Sensor is installed.
Line 4 -
Current Outdoor Air Temperature.
Programming 3-5
Section 3 WattMaster WHP
Status Screen #3
WSHPRV 1 V2.03
Occupied Mode
Fan Status...: ON
Operations Enabled
Line 2 Current Operating Status
Unoccupied Mode
Occupied Mode
Pushbutton Override
Forced Occupied
Forced Unoccupied
Forced Fan Only Mode
Line 3 Current Fan Status
Fan Start Delay!
ON
OFF
Line 4 Current Enable Status from Loop
Controller
Operations Disabled
Operations Enabled
Status Screen #4
WSHPRV 1 V2.03
Compressor...: ON
Reverse Valve: OFF
Aux / Stage#2: OFF
Line 2 Current Compressor ON/OFF Status
Line 3 Current Reversing Valve ON/OFF Status
Line 4 Current Status of Relay #5. Operation depends on how the user configures this output.
Status Screen #5
WSHPRV 1 V2.03
Cooling Mode
Line 2 Current HVAC Operating Mode
Neutral Mode
Cooling Mode
Heating Mode
Line 3 Reserved for future option.
Line 4 Reserved for future option.
3-6 Programming
WattMaster WHP
Status Screen #6
WSHPRV 1 V2.03
Space Temp Sensor OK
Filter OK
Cooling Failure
Line 2 -
Line 3 -
Line 4 -
Bad Space Sensor
Hi Space Temp Alarm!
Lo Space Temp Alarm!
Space Temp Sensor OK
Dirty Filter Alarm
Filter OK
Cooling Failure!
Heating Failure!
Section 3
Note: If no alarms exist, then the screen displays the message shown for No Alarms!
If ANY alarm exists then the three lines display one of the messages shown above.
The Cooling Failure and Heating Failure alarms are generated as follows:
As the unit enters the cooling mode, the current Supply Air Temperature reading is stored in memory. After 10 minutes, if the temperature hasn’t changed by 5 ° F a
Cooling Failure alarm is generated.
A Heating Failure is generated in the same manner, only during the heating mode instead of the cooling mode.
The Hi Space Temp and Lo Space Temp Alarms are generated as follows:
If the space temperature gets 5 ° F above the cooling setpoint, a Hi Space Temp
Alarm is generated. If the space temperature gets 5 ° F below the heating setpoint, a Lo Space Temp Alarm is generated.
Programming 3-7
Section 3
View Alarms
WattMaster WHP
Alarm Address Locations
SYSTEM ALARM STATUS
Alarm @ Unit ID 118
The System Manager can be programmed to poll all the units on your heat pump system for alarm information. This allows the centrally located System Manager to display an
Alarm Indicator whenever an alarm condition exists anywhere on your system. The actual alarms are not displayed on this screen, only the Unit ID where the alarm is located. The example screen shows that a unit at location
118 has experienced an alarm condition. This alarm may or may not be current, as the System Manager latches the condition. This makes it possible to determine if any intermittent alarm conditions have occured. To find out what the alarm is, if it is still current, access the status screens for the Unit IDs that are displayed on the SYSTEM
ALARM STATUS screens.
Alarm Clearing
SYSTEM ALARM STATUS
Clear Alarms? YES
To Change Response
Use Left/Right Arrow
If all the alarm conditions have been corrected at the individual units, you can clear these alarms from the
System Manager on the following screen. Use the
Left/Right arrow keys to select the YES/NO response desired. If you clear the alarms, but some still exist, the
System Manager will show an alarm indication, when the affected unit is polled again.
3-8 Programming
WattMaster WHP
Menu Setpoints
Section 3
Full Setpoint Access
1) Set Time & Date
2) Access Units
3) New Passcodes
4) Rebuild Alarm Map
If you selected the Menu key from the first menu screen you can access all setpoints available from any unit on your system.
You must be a Level 2 user to access these setpoints. If you haven’t already been asked to enter the passcode, you will be asked before the Full Setpoint Access menu is displayed. This prevents the casual user from being able to affect the operation of your heat pump system.
Set Time & Date
The System Manager has its own built in Real Time Clock. It broadcasts this time once a day, at midnight, to synchronize all of the WHPs on your system. Although the times are displayed on the Main Screen in a standard 12-hour format, they are programmed using the 24-hour Military format. Once the time has been entered, it is also broadcast immediately to all other units on the system. That means that you only need to program the System Manager time to set the Real Time Clocks for all units on your system. In order for the System Manager to broadcast the time and date to all controllers, they must be powered up and communicating.
Programming Time
Program Time/Date
Day (Sunday=0): 1
Enter Hr. (0-23): 9
Enter Minutes : 53
Day
Hours (Hr)
Minutes
- Enter the Day of the Week (0 to 6) with
Sunday = 0
- Enter Hours in 24-Hour Military Format
(1700 = 5:00 PM)
- Enter the Minutes (0 to 59)
Programming 3-9
Section 3 WattMaster WHP
Programming Date
Program Time/Date
Month (1-12): 4
Day (1-31): 18
Year (00-99): 04
Month
Day
Year
- Enter the Month (1 to 12)
- Enter the Day of the Month (1 to 31)
- Enter the current Year with 2 digits (00 to 99)
Daylight Savings Adjustments
Daylight Savings
Adjustments Enabled
Use Left/Right Arrow
If your area of the country requires Daylight Savings changes, you can enable the System Manager to automatically reset its own clock during the Daylight Savings changeover. If you enable this operation, it knows to changeover the first Sunday in April and then switch back the last Sunday in October. No other programming is required for this function.
Use the Left or Right arrow keys to toggle the second line of the display between Adjustments Enabled and Adjustments
Disabled.
3-10 Programming
WattMaster WHP Section 3
New Passcodes
Programming Passcodes
Enter New Passcode
Level 1....: XXXX
Level 2....: XXXX
[Must Be 4 Digits]
The System Manager has two levels of passcode.
Level 1 users are limited to viewing Setpoints and Alarms only.
Level 2 users have complete system access. Any status or setpoint field can be read or reset from WHP System Manager.
The default passcode is “1111” for level 1 and “2222” for level
2. If you need to change these defaults you can enter any 4 digit number between 1000 and 9999.
If you “forget” the passcode you programmed, you can still access the system with a built in backdoor code. This backdoor code is “9288” and is not programmable. It is not recommended that you give out this backdoor code since it would allow the user access without regard to the standard programmable passcode that most operators should be using.
The actual digits in your passcodes are never displayed. An "X" is used as a place holder for each digit entered. Passcodes must
always be four digits in length.
Programming 3-11
Section 3 WattMaster WHP
Rebuild Alarm Map
Rebuilding Screens
Clearing Old Map
....................
................
Build New Map?
(ESC = NO)
Building New Map
Loop: 1 Unit: 1
Dec) Go To Next Loop
ESC) Abort Process
Alarm Unit Map Built
Press Any Key To
Continue
If you would like the LED Alarm Indicator to function on the front of your System Manager, you must enable Alarm Polling by building an Alarm Map. This map keeps track of which units exist on your communications loop so the System
Manager will poll only those units. That means you will need to rebuild this map anytime units are added or removed from your system. It also means you can disable alarm polling. To do this, disconnect the RS-485 communications plug from the back of your Comm Link II. Then, select the Rebuild Alarm
Map menu. The System Manager will not find any units to poll for alarms since none are connected. This is useful during building startup, when you don't want nuisance alarms bothering you.
The screen will display each address it is testing and if a unit is found at that address. If you don't want to wait for the System
Manager to check for all 30 loops, you can press the ESC key as soon as the number of loops on your system are exceeded and the test will conclude. All units found up to that point will be saved in memory.
The System Manager does not rebuild this map
automatically on powerup! You must do this manually. This rebuild need only be performed one time, when all units are up and running. It is not a regular requirement. As mentioned above, only when the number of units connected changes should the alarm map be rebuilt.
3-12 Programming
WattMaster WHP
Heat Pump Setpoints
Section 3
Heat Pump Setpoint Menu
1) WHP Setpoints
2) WHP Schedules
3) Reset Pumps
ESC) To Exit
From the main menu screen select MENU on the keypad, select MENU again for Setpoints. Then select “Access Units”
(keypad #2) and finally enter the loop and zone number for the desired unit.
As the screen above shows, there are three areas of programming available for each WHP Controller. Menu item
#1 accesses all the standard temperature and configuration settings for the heat pump. Menu item #2 accesses the week schedule and holiday programming for the individual unit.
Menu item #3 can be selected to force the heat pump to manually reset in the case of an operating problem.
1) WHP Setpoints
Setpoint Screen #1
WHP #1 Setpoints
Occupied Setpoints
Cooling Setpt: xx
°
F
Heating Setpt: xx
°
F
The Occupied Heating and Cooling Setpoints are programmed on this screen. The setpoints must be at least one degree apart. If you try to enter the same value or to cross the cooling and heating setpoints, the value you enter will not be accepted.
Cooling Setpt
Heating Setpt
Minimum Default Maximum
50 ° F 74 ° F 90 ° F
50 ° F 72 ° F 90 ° F
Programming 3-13
Section 3 WattMaster WHP
Setpoint Screen #2
WHP #1 Setpoints
Unoccupied Setpoints
Cool Setup.: xx
°
F
Heat SetBk.: xx
°
F
The Unoccupied Heating and Cooling Setbacks are programmed on this screen. The Cooling SetUp is added to the Occupied
Cooling Setpt to create the Unoccupied Cooling Setpoint. The
Heating SetBack is added to the Occupied Heating Setpt to create the Unoccupied Heating Setpt.
Cool SetUp
Heat SetBack
Minimum Default Maximum
1 ° F 10 ° F 30 ° F
-1 ° F -10 ° F -30 ° F
Setpoint Screen #3
WHP #1 Setpoints
Slide Effect: x
°
F
SP Deadband.: xx
°
F
OV Duration.:x.x Hr
If the Space Temperature Sensor has the optional slide adjustment, then the Slide Effect is the maximum amount of change that it can have on the Heating and Cooling Setpoint and it is programmed here.
The SP Deadband is divided in half across the current heating and cooling setpoint, and is used in staging the heating and cooling on or off.
If you have an override pushbutton on the space sensor, the OV
Duration is the length of time the unit will be in the occupied mode after pushing the button
Slide Effect
Minimum Default Maximum
0 ° F 3 ° F 5 ° F
SP Deadband
OV Duration
0 ° F
0.0 Hr
1 ° F
1.0 Hr
20 ° F
8.0 Hr
Setpoint Screen #4
WHP #1 Setpoints
Cooling Stages: x
Heating Stages: x
If the Heat Pump is configured to operate with a Reversing
Valve, relay #5 can be configured as a second stage for either heating or cooling or both. If the Heat Pump is configured for individual heating and cooling, this determines how many of each stage there are.
Cooling Stages
Heating Stages
Minimum Default Maximum
0 1 2
0 1 2
3-14 Programming
WattMaster WHP Section 3
Setpoint Screen #5
WHP #1 Setpoints
Min Run Time: x Min
Min Off Time: x Min
Min Cycle...:xx Min
The Min Run Time determines how long the compressor must remain on once it has been activated. The Min Off Time determines how long the compressor must remain off once it is de-activated. The Min Cycle time determines how many times per hour the compressor can be started. If you entered
10 minutes, the compressor could start a maximum of 6 times in a one hour period.
Min Run Time
Minimum Default Maximum
0 Min 1 Min 20 Min
Min Off Time
Min Cycle
0 Min
0 Min
6 Min
12 Min
20 Min
60 Min
Setpoint Screen #6
WHP #1 Setpoints
Changeover Delay
Between Heat/Cool
Modes......:xx Min.
To prevent rapid cycling between heating and cooling modes, you can enter a time period that must be satisfied before the changeover can occur.
Changeover Delay
Minimum Default Maximum
1 Min 30 Min 60 Min
Setpoint Screen #7
WHP #1 Setpoints
Enable Signal Select
NO ENABLE REQUIRED
Use Left/Right Arrow
Normally you would want to have an Enable Signal that gave assurance of water flow before you activate the heat pumps compressor. If you need to operate without this enable signal, use the arrow keys to select the NO ENABLE REQUIRED message. Otherwise, select the LOOP FLOW REQUIRED message so that the signal must be present for the compressor to run.
Programming 3-15
Section 3 WattMaster WHP
Setpoint Screen #8
WHP #1 Setpoints
WHP Configuration
R/VALVE & COMPRESSOR
Use Left/Right Arrow
If your heat pump uses a reversing valve to determine the heating or cooling mode of operation, select the message
R/VALVE & COMPRESSOR. If you are controlling separate stages of heating and cooling select the
INDIVIDUAL STAGING
message.
Setpoint Screen #9
WHP #1 Setpoints
Reversing Valve Used
During: COOLING MODE
Use Left/Right Arrow
If you have configured the system to use the reversing valve, you must select which mode requires it to be active. Select either the COOLING MODE or the HEATING MODE message.
Setpoint Screen #10
WHP #1 Setpoints
Reverse Valve Mode
CYCLES w/COMPRESSOR
Use Left/Right Arrow
If you have configured the system to use the reversing valve, you can also set it to cycle on and off with the compressor,
(CYCLES w/COMPRESSOR) or, to remain on once it is activated, and stay on until the opposite mode or unoccupied mode is selected (RUNS CONTINUOUS MODE). The valve always activates 10 seconds before the compressor starts no matter which method you select.
3-16 Programming
WattMaster WHP Section 3
Setpoint Screen #11
WHP #1 Setpoints
Relay5 Configuration
AUXILIARY RELAY MODE
Use Left/Right Arrow
If your system is configured to use the reversing valve and you only have one stage of heating and cooling, that last relay becomes available for other uses. The AUXILIARY
RELAY MODE can be used to operate the relay manually from the Prism computer front end program. If you select
ISOLATION VALVE MODE, the relay activates anytime the compressor is called for or whenever the Loop Controller sends an override command to activate and reduce loop pressure.
If the relay needs to follow an external week schedule, select the AUXILIARY RELAY MODE and then see the Aux
Relay #5 Schedule assignment screen.
Setpoint Screen #12
WHP #1 Setpoints
Fan Mode of Op
RUNS CONTINUOUS MODE
Use Left/Right Arrow
You can program the fan to run continuously during the occupied mode,
(RUNS CONTINUOUS MODE) or you can program it to cycle on and off with the compressor during both the occupied and the unoccupied mode of operation.
(CYCLES W/COMPRESSOR)
Setpoint Screen #13
WHP 1# Setpoints
Aux Relay #5 Uses
Uses Schedule #: x
0) None 1-7) Clock
If you configured relay #5 as an Auxiliary Relay, you can also program it to follow an external schedule command.
You must have an OSS Optimal Start Scheduler installed somewhere on you communications loop to provide the external schedule you select here.
Programming 3-17
Section 3 WattMaster WHP
Setpoint Screen #14
WHP #1 Setpoints
Heat Pump Scheduling
Uses Schedule #: x
0) Int. 1-7) Clock
The Heat Pump Controller can use the internal time clock for a setting an occupied schedule, for this the setpoint will be 0.
It can also be programmed to follow an external schedule command. You must have an OSS Optimal Start Scheduler installed somewhere on you communications loop to provide the external schedule, and you select the schedule number here.
Setpoint Screen #15
WHP Setpoints
Startup Delay Period
x Seconds Times
Board Address Switch
If you entered the same starting time for several heat pumps, they are prevented from all starting their fans at the same time by a Startup Delay Period that is determined by their address switch setting. The address is multiplied by the number of seconds you enter on this screen, up to a maximum of 60 seconds per address. This is the time period the fan must wait before it starts when the schedule goes occupied.
If you entered 5 seconds and the address was 10 then the fan would start 5 x 10 or 50 seconds after the schedule goes occupied.
Setpoint Screen #16
WHP Setpoints
Energy Demand Limits
Max Effect: xx
°
F
An Energy Demand Limit sequence is programmed into all heat pump controllers. It is currently an option that is not
supported by a controller that can send the Demand Limit signal to initiate a limiting condition. It is included here for future use only.
Max Effect
Minimum Default Maximum
0 ° F 3 ° F 30 ° F
3-18 Programming
WattMaster WHP Section 3
Setpoint Screen #17
WHP # 1 Setpoints
Heat Stage #2
SAT Lockout: 60 ° F
This setpoint is to shut the heating off when the supply air temperature is too warm. When the supply air temperature is above this setpoint, it will prevent the second stage of heat from coming on.
Max Effect
Minimum Default Maximum
30 ° F 60 ° F 200 ° F
Setpoint Screen #18
SENSOR CALIBRATION
SPC xxx.x
°
xxxx.x
°
°
SAT xxx.x
°
° xxxx.x
°
°
WAT xxx.x
°
° xxxx.x
°
°
The Thermister Type III Sensor readings can be calibrated.
Enter Positive values to increase the reading or Negative values to decrease the reading. If no sensor is attached, the calibration offset will still allow a value to be input and read for diagnostic purposes.
Minimum Default Maximum
Space Sensor SPC -100.0°F 0.0°F +100.0°F
Supply Air Sensor SAT -100.0°F 0.0°F +100.0°F
Water Sensor WAT -100.0°F 0.0°F +100.0°F
Setpoint Screen #19
WHP #1 Setpoints
Alarms: Enabled
Use Left/Right Arrow
Select if you want the notification LED on the front of the
System manager to illuminate when an alarm occurs. If
Enabled is selected, any WHP alarm will cause the Alarm
LED on the front panel to light up. If Disable is selected, the
Alarm LED will not light up but the alarm will still show up in the Status screen.
Note: You must do a Rebuild Alarm Map after all controllers are powered up and communicating.
Programming 3-19
Section 3 WattMaster WHP
2) WHP Schedules
The Water Source Heat Pump controllers contain their own built in scheduling capability for calculating Occupied/Unoccupied periods. Select item #2 from Schedules menu to access the following schedule programming menu.
Schedule Menu
WSHP Schedules
1) Week Schedules
2) Holidays
MENU) Previous Menu
Week Schedule Programming
Event #1
WEEK SCHEDULES
Sunday Event #1
Start Time..: xxxx
Stop Time..: xxxx
Event #2
WEEK SCHEDULES
Sunday Event #2
Start Time..: xxxx
Stop Time..: xxxx
There are two Start / Stop events available per day.
The first line is the start time for event #1 and the next line is the stop time for event #1.
The screens will step through the Start Time and then the Stop
Time for each day of the week. You can quit at any point in the process by pressing the "ESC" key.
If no second event is required, simply leave a ZERO for both the start and stop times on the event #2 screens.
All times are in 24-hour format, so 5:00 PM would be entered as 1700.
If both the Start and Stop Times are ZERO, the schedule is in a
Continuous OFF mode.
If both the Start and Stop Times are 2359, the schedule is in a
Continuous ON mode.
3-20 Programming
WattMaster WHP
Holidays
Section 3
Holiday Day Selection
There are 14 Holiday periods available, organized as a Start Day / Stop Day event. If the
Holiday only lasts one day, enter the same date for the Start & Stop days. There is no limit to the duration or number of days that can be included in one holiday, other than it cannot extend past December 31st. If you have a holiday that crosses the end of year border, you will need to use two holiday periods to accomplish this event.
Program Holidays
Holiday # 1
Start Mon/Day: xxxx
(EX: 101 = Jan. 1)
The screens will step through the 14 possible holidays, one at a time. Line 2 shows which holiday is currently being programmed.
Program Holidays
Holiday # 1
Stop Mon/Day: xxxx
(EX: 102 = Jan. 2)
Line 3 shows which event, the Start Day or Stop Day, is currently being programmed.
Remember to combine the month and day into a single four digit value.
EXAMPLE: 0704 = July 4th
1225 = December 25th
Holiday Start / Stop Times
WHP CONTROLLER
Holiday Schedule
Start Event #1..: xxxx
Stop Event #1..: xxxx
The 14 holidays all use the same Holiday Start / Stop time. The start/stop times are programmed back on the
Week Schedule screens. The holiday schedule screen appears after the Saturday schedule screen, as you are stepping through the days of the week.
Note: Normally there is no schedule in the Loop Controller device. It simply looks at all the Water Source Heat Pumps for a request to run signal. Scheduling is maintained separately in each Water Source Heat Pump. If you want to be able to schedule all Water Source Heat Pumps on and off at the same time, you can input a schedule on the Loop Controller and it will broadcast that schedule to all
WHPs.
Programming 3-21
Section 3 WattMaster WHP
3) Reset Pumps
WSHPRV 1 v2.03
Tripped Pump Reset
Reset Mode: Disabled
Use Left/Right Arrow
If one of your heat pumps has tripped off, it can be manually reset from the following screen. You will have entered the
Unit ID to access the WHP Menu screen, so that is the unit that will receive this reset command. If you don’t want to send the command, select the Disabled message with the arrow keys. If you do want to send the command, select the
Enabled message with the arrow keys and then press the
Enter button. This command will automatically clear itself when the WHP detects it and performs the reset.
There are two methods of resetting:
1.
Relay #4, on the WHP will activate with the reset command and can be wired to provide the reset action.
2.
The compressor relay will be cycled off. On newer heat pumps, this is all that is required to reset the operation.
3-22 Programming
WattMaster WHP Section 3
Loop Controller Status
Loop Controller Status Menu
1) View Status Only
2) View Alarms
Menu) Setpoints
ESC) To Exit
From the main menu screen select MENU on the keypad. Then select “View Status
Only” (keypad #1) and finally enter the loop and zone number for the desired unit.
As the screen above shows, there are two areas of status available for the Loop
Controller. Menu item #1 accesses all the status screens for the Loop Controller. Menu item #2 accesses the alarms for the Loop Controller. “Menu” can be selected to access the
Setpoints screens.
Loop Controller Status
Screens
If you selected menu item #1, View Status Only, and you entered the Unit ID of the Loop
Controller, the following Status Screens are available.
Status Screen #1
Loop Control v1.06
OCCUPIED
Return Temp: xx.x
° F
Supply Temp: xx.x
°
F
Line 2 Current operating Mode:
OCCUPIED
UNOCCUPIED
Line 3 Current Return Water Temperature
Line 4 -
Current Supply Water Temperature
Programming 3-23
Section 3 WattMaster WHP
Status Screen #2
Loop Control v1.06
No Call to Run
Water Flow Proved!
LOOP ENABLED
Line 2 Current operating Mode:
No Call To Run
ACTIVE CALL TO RUN
FREEZE PROTECTION!
Line 3 Current Water Flow Status:
Water Flow Proved!
No Flow Detected
Line 4 Current Request to Operate Status:
LOOP ENABLED
LOOP DISABLED
Status Screen #3
Loop Control v1.06
LEAD Pump #1: ON
STANDBY Pump #2: OFF
Line 2 -
LEAD Pump #1 On or Off
Line 3 STANDBY Pump #2 On or Off
Status Screen #4
Cool Stage # 1.: OFF
Cool Stage # 2.: OFF
Cool Stage # 3.: OFF
Cool Stage # 4.: OFF
Line 1 -
Line 2 -
Cool/Heat Stage #1 On/Off
Cool/Heat Stage #2 On/Off
Line 3 -
Line 4 -
Cool/Heat Stage #3 On/Off
Cool /Heat Stage #4 On/Off
3-24 Programming
WattMaster WHP
Status Screen #5
Cool Stage # 5.: OFF
Cool Stage # 6.: OFF
Cool Stage # 7.: OFF
Cool Stage # 8.: OFF
Line 1 -
Line 2 -
Cool/Heat Stage #5 On/Off
Cool/Heat Stage #6 On/Off
Line 3 -
Line 4 -
Cool/Heat Stage #7 On/Off
Cool/Heat Stage #8 On/Off
Section 3
Status Screen #6
Loop Control v1.06
Pressure.: xxx.x PSI
Pump VFD.: xx.x VDC
Heat VFD.: xx.x VDC
Line 2 Current Loop Water Pressure
Line 3 Current Variable Speed Pump Voltage Signal
Line 4 Current Proportional Heat Voltage Signal
Note: If none of the above options have been configured, then the values in this status screen will be 0.
Programming 3-25
Section 3 WattMaster WHP
Status Screen #7
Loop Control v1.06
No Alarms!
Line 2 Pump Failure or Blank Line
Line 3 -
Line 4 -
Hi Control Water Temp
Lo Control Water Temp
Fire/Smoke Alarm
Phase Shutdown
Note: If no alarms exist, then the screen displays the message shown for No Alarms! If
ANY alarm exists, then the three lines display one of the messages shown above.
The Fire/Smoke Alarm is generated as follows:
If the NC (normally closed) contact from a firestat or smoke detector that is wired between GND and AIN1, on the Analog Input expansion board, opens, the
Fire/Smoke Alarm is generated.
The Phase Shutdown Alarm is generated as follows:
If the NO (normally open) contact from a phase monitoring device, that is wired between GND and AIN7 is made, the Phase Shutdown Alarm is generated.
Status Screen #8
Loop Control v1.06
Pump Run Times
#1: xxxxx Hrs xx Min
#2: xxxxx Hrs xx Min
Line 2 -
Message Only
Line 3 Pump #1 Hours and Minutes Run Time
Line 4 Pump #2 Hours and Minutes Run Time
3-26 Programming
WattMaster WHP Section 3
Loop Controller Setpoints
Loop Controller Setpoint Menu
1) LC Setpoints
2) LC Schedules
3) LC Force Modes
ESC) To Exit
Setpoint Screen #1
WHP Loop Setpoints
HEAT REJECTION
Setpoint......: xx
°
F
Stage Deadband: xx
°
F
If the controlling water temperature rises above this Setpoint, the Heat Rejection or Cooling Stages begin to stage on. As the temperature continues to rise above the Setpoint by the
Deadband amount, an additional stage is added. Each additional stage can only activate if the temperature rises above the Setpoint by the number of active stages times the deadband value.
Example: There are 2 stages on, a 3 ° deadband and the setpoint is 79 °
2 x 3 ° + 79 ° = 85 ° before stage 3 can activate
Minimum Default Maximum
Setpoint 50 ° F 79 ° F 99 ° F
Stage Deadband 1 ° F 3 ° F 10 ° F
Setpoint Screen #2
WHP Loop Setpoints
HEAT REJECTION
Stage Delay...: x M
The Staging Delay period must also be satisfied before an additional stage of cooling or heat rejection can be activated.
The maximum number of heat rejection stages are programmed on this screen also.
Stage Delay
Minimum Default Maximum
1 Minute 1 Minute 60 Minutes
Programming 3-27
Section 3 WattMaster WHP
Setpoint Screen #3
WHP Loop Setpoints
HEATING ADDITION
Setpoint......: xx
°
F
Stage Deadband: xx
°
F
If the controlling water temperature drops below this Setpoint, the Heat Addition or Boilers begin to stage on. As the temperature continues to drop below the Setpoint by the
Deadband amount, an additional stage is added. Each additional stage can only activate if the temperature drops below the Setpoint by the number of active stages times the deadband value.
Example: There are 2 stages on, a 3 ° deadband and the setpoint is 79 °
79 ° - 2 x 3 ° = 73 ° before stage 3 can activate
Setpoint
Stage Deadband
Minimum Default Maximum
50 ° F 76 ° F 99 ° F
1 ° F 3 ° F 10 ° F
Setpoint Screen #4
WHP Loop Setpoints
HEATING ADDITION
Stage Delay...: x M
The Staging Delay period must also be satisfied before an additional boiler or heat addition stage can be activated.
The maximum number of heat addition stages are programmed on this screen also.
Stage Delay
Minimum Default Maximum
1 Minute 1 Minute 60 Minutes
Setpoint Screen #5
WHP Loop Setpoints
OA FREEZE PROTECTION
Setpoint.....: xx ° F
If the outdoor air temperature drops below this setpoint, the pump will be energized to prevent the water lines from freezing.
Setpoint
Minimum Default Maximum
-50
°
F 40
°
F 50
°
F
3-28 Programming
WattMaster WHP Section 3
Setpoint Screen #6
WHP Loop Setpoints
Water Hi Limit: xx
°
Water Lo Limit: xx
°
Alarm Delay...: xM
If the controlling water temperature rises above the Water Hi
Limit setpoint, all heat addition will be removed and one stage of heat rejection will be activated. If the controlling water temperature drops below the Water Lo Limit setpoint, all heat rejection stages will be removed and one heat addition stage will be activated. An alarm will be generated if it remains out of limits for the Alarm Delay Time.
Water Hi Limit
Water Lo Limit
Alarm Delay
Minimum Default Maximum
0 ° F 120 ° F 120 ° F
0 ° F
0 Min
0 ° F
30 Min
120 ° F
120 Min
Setpoint Screen #7
WHP Loop Setpoints
Pump Speed: CONSTANT
Flow Proof: CONTACT
Use Left/Right Arrow
The Loop Controller can modulate a Variable Speed Pump.
Select the PRESSURE option in place of the CONSTANT option for variable speed pumping.
The water flow proving can be accomplished by a differential pressure contact closure or an actual pressure sensor. If you select Variable Speed Pumping, you must select the
PRESSURE option in place of the CONTACT option for
Flow Proof.
Setpoint Screen #8
WHP Loop Setpoints
STEP HEATING CONTROL
RETURN WATER CONTROL
Use Left/Right Arrow
There are two methods of Heat Addition control, STEP
HEATING CONTROL or PROPORTIONAL HEATING
The Loop Controller can be configured to maintain Return
Water Temperature ( RETURN WATER CONTROL ) or the Supply Water Temperature ( SUPPLY WATER
CONTROL )
Programming 3-29
Section 3 WattMaster WHP
Setpoint Screen #9
WHP Loop Setpoints
Lead/Lag Changeover
Switch After xxx Hrs
The two pumps will switch after this programmed amount of time so that each pump accumulates roughly the same number of run time hours. If a pump is currently running and this time period is exceeded, the changeover will occur as soon as pump run time exceeds the setpoint. The current pump will shut off and the standby pump will start at the same time.
Changeover
Minimum Default Maximum
1 Hour 40 Hours 240 Hours
Setpoint Screen #10
WHP Loop Setpoints
Water Loop Proof Of
Flow Pr. SP: xxx PSI
If you attached a Pressure Sensor for proof of flow instead of a differential pressure contact closure for proof of flow, the controlling pressure is programmed on this screen. This
Setpoint represents the amount of pressure that you set to prove water flow exists in the system. Otherwise, this screen will not appear.
Flow PR. SP
Minimum Default Maximum
0 5 PSI 50 PSI
Setpoint Screen #11
WHP Loop Setpoints
Pressure SP: xxx PSI
SP Deadband: xx PSI
Adjust Time: x.x Sec
If you configured the system for Variable Speed Pumping with a Pressure Sensor for proof of flow, the controlling pressure, deadband and control adjust time period are programmed on this screen. Otherwise, this screen will not appear.
Pressure SP
SP Deadband
Adjust Time
Minimum Default Maximum
1 PSI 40 PSI 50 PSI
1 PSI 2 PSI 50 PSI
0.1 Seconds 1.0 Seconds 25 Seconds
3-30 Programming
WattMaster WHP Section 3
Setpoint Screen #12
WHP Loop Setpoints
Isolation Valves Set
Open if PSI is Above
Hi Limit...: xxx PSI
If you configured the system for Variable Speed Pumping with a
Pressure Sensor for proof of flow, the Loop Controller can send a signal to all the Heat Pumps to open their Isolation Valves whenever a Hi Limit Pressure is exceeded. If the Heat Pumps do not control an Isolation Valve, then the only reaction is to reduce the variable speed pump voltage signal.
Hi Limit
Minimum Default Maximum
1 PSI 50 PSI 50 PSI
Setpoint Screens #13
SENSOR CALIBRATION
RWT xxx.x
°
xxxx.x
°
°
SWT xxx.x
°
° xxxx.x
°
°
OAT xxx.x
°
° xxxx.x
°
°
The Thermister Type III Sensor readings can be calibrated.
Enter a Positive value to increase the reading or a Negative value to decrease the reading. If no sensor is attached, the calibration offset will still allow a value to be input and read for diagnostic purposes.
Minimum Default Maximum
Return Water RWT -10.0°F 0.0°F +10.0°F
Supply Water SWT -10.0°F 0.0°F +10.0°F
Outdoor Air OAT -10.0°F 0.0°F +10.0°F
Note: Due to memory limitations in the Loop Controller, the maximum amount of calibration offset is 10.0
° F.
Setpoint Screen #14
WHP Loop Setpoints
Alarms: Enabled
Use Left/Right Arrow
Alarms can be configured to light the LED on the front of the
System Manager by setting Alarms to Enabled, if you do not wish to report alarms, select Disabled.
Setpoint Screen #15
WHP Loop Setpoints
Relay Configurations
Rly 1: ADDITION
Use Left/Right Arrow
Use this screen to configure the relays on the expansion board for heat ADDITION, REJECTION or NOT USED. All 8 relays come up one at a time.
Programming 3-31
Section 3
Notes:
WattMaster WHP
3-32 Programming
Section 4
Table of Contents
1.0 Communications Overview........................................ 1
1.1 How It Works...........................................................................................................1
1.2 WattMaster WHP System ........................................................................................1
2.0 WHP Controller Overview .......................................... 4
2.1 How It Works...........................................................................................................4
2.1.1
Initialization .....................................................................................................4
2.1.2
Operating Summary .........................................................................................4
2.2 Becoming Familiar with the WHP Controller .........................................................5
2.2.1
24 VAC Power Connector ...............................................................................5
2.2.2
Analog Inputs ...................................................................................................6
2.2.3
Analog Output Description ..............................................................................6
2.2.4
Relay Output Descriptions ...............................................................................6
2.2.5
RS-485 Communications Connector ...............................................................7
2.2.6
WHP Controller Wiring...................................................................................8
3.0 Loop Controller Overview......................................... 9
3.1 How It Works...........................................................................................................9
3.1.1
Initialization .....................................................................................................9
3.1.2
Operating Summary .........................................................................................9
3.2 Loop Controller Inputs & Outputs .........................................................................10
3.2.1
Analog Inputs .................................................................................................10
3.2.2
Analog Output................................................................................................10
3.2.3
Binary Output.................................................................................................11
3.2.4
Relay Expansion Board - Outputs..................................................................11
3.2.5
Analog Input Expansion Board......................................................................11
3.2.6
Comm Connector - Communications ............................................................12
3.2.7
Power Terminal..............................................................................................12
4.0 Start-Up.................................................................... 14
4.1 Blink Codes for WHP Controllers .........................................................................14
4.2 Blink Codes for Loop Controllers..........................................................................15
4.3 Communications Checklist ...................................................................................15
4.4 Installation and Commissioning Information ........................................................16
4.5 Setting Address Switches.......................................................................................19
4.5.1
Setting the MiniLink Address Switch............................................................19
4.5.2
Loop Controller Addressing...........................................................................20
4.5.3
WHP Controller Addressing ..........................................................................20
Start-Up and Troubleshooting
Section 4
5.0 Troubleshooting ...................................................... 21
5.1 General Troubleshooting........................................................................................21
5.1.1
Communications Troubleshooting Checklist.................................................21
5.1.2
General Troubleshooting Checklist ...............................................................22
5.2 Alarms......................................................................................................................23
5.3 Checking Comm. Loop Voltages.............................................................................24
5.3.1
Checking the CommLink II Network Loop ...................................................24
5.3.2
Checking the Comm Loop at the CommLink II ............................................25
5.3.3
Checking the CommLink II Driver ................................................................26
5.3.4
Checking the MiniLink Network Loop..........................................................27
5.3.5
Checking the MiniLink Network Driver........................................................28
5.3.6
Checking the MiniLink Local Loop...............................................................29
5.3.7
Checking the Local Loop at MiniLink...........................................................30
5.3.8
Checking the MiniLink Local Loop Driver ...................................................32
5.3.9
Checking the Local Loop at a WHP Controller .............................................33
5.3.10 Checking WHP Controller Driver Chip.........................................................34
5.4 Troubleshooting Loop Controller ..........................................................................35
5.4.1
Checking the Loop Controller Analog Inputs ................................................35
5.4.2
Checking the Loop Controller Outputs ..........................................................37
5.4.3
Checking the Local Loop at a WHP Loop Controller....................................38
5.4.4
Checking WHP Loop Controller Driver Chip ...............................................39
5.4.5
Comm Driver Chip Replacement...................................................................40
5.5 Temperature Sensor Resistance Chart ...................................................................41
5.6 Pressure Sensor Voltage Chart...............................................................................42
Notes: ............................................................................ 43
Table of Figures
Figure 4-1: System Wiring Overview.............................................................................2
Figure 4-2: Communications Loop Routing...................................................................3
Figure 4-3: WHP Controller Component Layout ...........................................................5
Figure 4-4: Typical WHP Controller Wiring Diagram...................................................8
Figure 4-5: Loop Controller Inputs & Outputs .............................................................13
Figure 4-6: Diagnostic LED Blink Codes.....................................................................14
Figure 4-7: Diagnostic LED Blink Codes.....................................................................15
Figure 4-8: Communications Loop Wiring ..................................................................18
Figure 4-9: MiniLink Address Switch Setting.............................................................19
Figure 4-10: WHP Controller Address Switch Setting...............................................20
Figure 4-11: Comm Driver Chip Replacement............................................................40
Start-Up and Troubleshooting
WattMaster WHP Section 4
1.0 Communications
Overview
Perhaps no other portion of the system seems as difficult to diagnose as the communications loop, yet it really can be quite simple if you understand how it works. In fact, much of the troubleshooting can be done by simple observation. We will lead you through the system functions and then provide you with detailed instructions for checking each piece of equipment.
1.1 How It Works
WattMaster uses a token-passing loop architecture, which means in simple terms that an
“electronic message” called a token is passed from controller to controller in a roundrobin fashion. A controller must wait to receive the token before it can send or request any data.
Note: It is very important to know which device is the loop master on the loop you are troubleshooting.
1.2 WattMaster WHP System
The standard WattMaster WHP system may have only one communications loop or as many as thirty communication loops depending on the number of WHP Controllers to be connected to the system. It is important to remember that each loop must have its own master.
If you are using the multiple loop version of the WHP system (for systems with more than
30 WHP Controllers) a loop is required for each group of 30 WHP Controllers. The WHP
Loop Controller may be connected to any of the Local Loops. The Local Loop that has the WHP Loop Controller installed can only have 29 WHP Controllers on that loop. Each
Local Loop is connected to a MiniLink loop interface. The MiniLink is always the
master on the Local Loops. The MiniLinks are connected to the CommLink II and to each other via the Network Loop.
.
The CommLink II is always the master on the Network Loop. You must be sure the
CommLink II is connected and functioning if you are troubleshooting the communications loops. Make sure the CommLink II is set for multiple loops
Start-Up and Troubleshooting 4-1
WattMaster WHP
COMPUTER
(OPTIONAL)
Section 4
RS-485
Comm Loop
Room Sensor with Optional
Override & Adj.
32K 8K
COMM
T
SHLD
R
LD4
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR GND
24VAC
24 VAC
110/24 VAC
Power Pak
Supply
Air
Sensor
F
Dirty Filter Alarm or Leaving Water Temp
Modem
(Optional)
110/24 VAC
Power Pak
Typical WHP Controller Wiring
MR
TR
SD
RD
OH
CD
AA
HS
CommLink II
Multiple Loop
Interface
LINK
II
Network Loop
RS-485
19200 Baud
O
P
C
O
M
P
O
E
W
AT
TM
AST
ER
C
ONTR
O L
S,
I
NC
MiniLink
Loop # 1
T
SH
R
16
32
24VAC
GND
T
SH
R
Local Loop
RS-485
9600 Baud
System Manager
24VAC
MiniLink
Loop # 2
T
SH
R
16
32
24VAC
GND
T
SH
R
03:38PM
WED
MiniLink
Loop # 3
24VAC
Local Loop
RS-485
9600 Baud
24VAC
Typical Network & Local Loop Wiring
2 Conductor Twisted Pair with Shield
(Beldon #82760 or Equivalent)
T
SH
R
16
32
NOTE: * Only One Outside Air Sensor is Required per WHP System
MiniLink
Loop # 4
T
SH
R
16
32
T
SH
R
T
SH
R
GND
24VAC
GND
24VAC
Local Loop
RS-485
9600 Baud
*OutsideAir
Sensor
WHP Loop
Controller
RN1
CX1
U1
U2 CX2
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
U5
RS-485
COMM
LD8
LED1
C1
R1
LD9
LED2 P1
+VREF
5.11V
TEST POINT
U7
RV1
VREF ADJ
EWDOG
R28
INPUTS
HH
ADDRESS
RAM
U6
ADD
+VDC
AIN1
RN5
AIN2
AIN3
AIN4
AIN5
GND
GND
C10
AOUT1
C12
TB3
AOUT2
AIN7
GND
PJ1
C17 D15
D8
PU4
D9
PU5
PU1
D6
PU2
D7
PU3
D11
PU7
D14
U13
SW1
CX13
U15
TOKEN
NETWORK
JP1
X2
CX15
U3
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
U10
CX10
R15
C14
R19
C15
U14
R22
R24
R25
U12
CX14
CX6
CX12
C20
PRESSURE
R26
SENSOR
EXPANSION T'STAT
U4
CX4
U9
PAL
VR1
C7
D12
R13
SC1
D19
VR2
L1
7824CT
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V5
V4
R6
C9
MC34064A
U8
NE5090NPB3192
0PS
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
Loop # 4
24VAC
Notes:
1.) 24 VAC Must Be Connected
So That All Ground Wires
Remain Common.
#1
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
COMM
TEST
ADDRESS ADD
RELAY
OUTPUT
COM
1-3
OUT
1
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#1
32K
8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
1
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
485
COMM
RAM EPROM
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4 OUT
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#1
RAM EPROM
32K
8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#1
RAM EPROM
32K
8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
Loop #1
WHP
Controllers
Loop #2
WHP
Controllers
Loop #3
WHP
Controllers
See Note #3
Loop #4
WHP
Controllers
Local Loop
RS-485
9600 Baud
3.) The Local Loop With The Loop Controller
Installed Can Only Have Up To 29
WHP Controllers Attached As The WHP
Loop Controller Occupies Address #30.
2.) All Wiring To Be In Accordance
With Local And National Electrical
Codes and Specifications.
#30
32K
8K
COMM
T
SHLD
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
1
AIN
2
AIN
3
AIN
4
AIN
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
COMM
TEST
ADDRESS ADD
RELAY
OUTPUT
COM
1-3
OUT
1
2
OUT
3
OUT
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#30
32K
8K
COMM
T
LD4
REC.
SHLD
R
485
COMM
RAM EPROM
12V
AIN
1
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4 OUT
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#30
RAM EPROM
32K
8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
#29
RAM EPROM
32K
8K
COMM
T
LD4
REC.
SHLD
R
12V
AIN
2
AIN
3
AIN
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
1
OUT
2
OUT
3
4
OUT
4-5
5
COM
4-5
PWR
GND
24VAC
4.) Systems may consist of up to 20 Local
Loops (600 WHP Controllers). Consult factory for systems that exceed these quantities.
Figure 4-1: System Wiring Overview
4-2 Start-Up and Troubleshooting
WattMaster WHP Section 4
All communications wiring should be labeled to avoid confusion and to aid future servicing.
03/31/04 03:38PM WED
OCCUPIED
NO ALARMS
COMPUTER
(OPTIONAL)
POWER
24VAC
GND
COMMUNICATIONS
T
RS-485
SHLD
R
SYSTEM MANAGER POWER SUPPLY
YS101716 REV. 1
SYSTEM MANAGER
COMM LINK II
INTERFACE
(MULTIPLE LOOP)
UNIT COMES WITH
STANDARD WALL MOUNT
120/24 VAC POWER SUPPLY
( MAY ALSO BE POWERED FROM 24VAC )
Remote Link
(OPTIONAL)
NETWORK
LOOP
U3
1
RN1
CX1
U1
U2
CX2
U4
CX4
TB1
COMM
T
SHLD
R
CX5
LD6
COMM
LD7
PWR
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
1
U5
RS-485
RN5
COMM
GND
AOUT1
C12
HH
U13
RAM
R15
EPROM
TUC-5R PLUS
(1 MEG)
YS101816 REV. 2
LD8
LED1
C1
LD9
LED2
R1
U7
+VREF
5.11V
TEST POINT
EWDOG
RV1
VREF ADJ
R28
INPUTS
P1
ADDRESS
C10
PU1
D6
PU2
D7
PU3
D8
PU4
D9
PU5
D11
PU7
D14
U6
SW1
ADD
1
2
4
32
8
16
TOKEN
NETWORK
U10
JP1
X2
CX10
CX6
CX12
AOUT2
U12
CX14 C14
R19 U14
TB3
AIN7
GND
PJ1
C17
D15 CX13
U15
C20 CX15
C15
R22
R24
R25
1
U9
PAL
1
C7
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION T'STAT VR1
L1
VR2
7824C T
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V5
V1
V2
V3
U8
NE5090NPB3192
0PS
R6
64A
9936
C9
MC340
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
32K
8K
COMM
T
LD4
SHLD
R
REC.
RAM EPROM
12V
AIN
1
2
3
4
AIN
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
PWR
GND
24VAC
OUTPUT
COM
OUT
OUT
OUT
OUT
4-5
32K
8K
COMM
485
COMM
RAM EPROM
REC.
12V
2
3
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
PWR
GND
24VAC
RELAY
OUTPUT
1-3
OUT
OUT
2
OUT
OUT
4-5
TO OTHER WHP CONTROLLERS
TO OTHER MINILINKS
(NETWORK TERMINALS ONLY)
Figure 4-2: Communications Loop Routing
Start-Up and Troubleshooting 4-3
Section 4 WattMaster WHP
2.0 WHP Controller
Overview
2.1
How It Works
2.1.1
Initialization
On system powerup the COMM LED remains extinguished for five seconds. After this delay, the COMM LED will blink out the address of the controller (Address Switch
Setting). The COMM LED will then extinguish for another five seconds and then begin to blink for a twenty second startup delay. At the conclusion of this twenty second period, the COMM LED will begin blinking a diagnostic code every ten seconds. This code is described later in this document. The duration of a powerup initialization sequence is roughly one minute.
During this initialization period, the controller retrieves all operating setpoints from its non-volatile EEPROM memory and initializes all outputs to an OFF condition.
Note: All future references to the Water Source Heat Pump Controller in this document use WHP as the designation.
2.1.2
Operating Summary
At all times, after the conclusion of the initialization sequence, the WHP performs a specific set of operating instructions in the following order: (a - g repeat continuously) a. Read Analog Inputs for Temperatures and Overrides.
b. Check the RS-485 communications port for any new setpoints from the System
Manager and keeps the status updated for the System Manager.
c. If the push-button override is active, it checks the timer to see if the override is finished.
d. Calculates the current occupied/unoccupied mode from its internal week scheduling.
e. Calculates what state the output relays and analog output should be set to.
f.
Updates the diagnostic COMM LED blinking.
g. Stores data in the internal trend log if ready for another log.
4-4 Start-Up and Troubleshooting
WattMaster WHP Section 4
2.2
Becoming Familiar with the WHP
Controller
COMMUNICATIONS
DRIVER CHIP PIN 1
INDICATION
RAM EPROM
RAM SIZE
SELECT JUMPER
PAL
32K
8K
RS-485
COMMUNICATIONS
LOOP
COMMUNICATIONS
LED
ADDRESS SWITCH
( ADDRESS 18 SHOWN )
ANALOG INPUTS
Space Sensor
Slide Adjust
Supply Air Temp
Leaving Water
Temp or
Dirty Filter
Lockout
COMM
T
SHLD
LD4
R
REC.
12V
2
3
AIN
4
AIN
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
485
COMM
RAM
CPU
EPROM
ADDRESS ADD
COMM
TEST
RELAY
OUTPUT
COM
1-3
OUT
2
OUT
OUT
4
OUT
5
COM
4-5
24 VAC Common for Inputs 1 - 3
Fan-On/Off
Rev. Valve-On/Off (Heat 1)
Compressor-On/Off (Heat 2)
Heat Pump Reset (Cool 1)
Aux. Heating or Cooling (Cool 2)
24 VAC Common for Inputs 1 - 3
DIAGNOSTIC BLINK
CODE LED
REAL TIME
CLOCK CHIP
POWER LED
24VAC
POWER
INPUT
STATIC PRESSURE
SENSOR INPUT
24VAC
Figure 4-3: WHP Controller Component Layout
2.2.1
24 VAC Power Connector
This connector provides power to the WHP Controller.
Mounting Backplate
24VAC - The “hot” side of the control transformer.
GND - The grounded side of the control transformer. If the secondary of the control transformer is not grounded, you must still observe polarity if the trans- former powers any other device!
Warning:
Connect only the GND terminal to the grounded side of a transformer
- Failure to properly observe polarity will result in damage to the system. Observe polarity at all points in the system.
Start-Up and Troubleshooting 4-5
WattMaster WHP Section 4
2.2.2
Analog Inputs
This connector carries the analog and binary control input signals.
AIN1 - Space Temp - This input accepts a two wire 10K Type III thermistor temperature sensor. The sensor measures 10,000 Ohms @ 77
°
F. The resistance drops as the temperature increases. The sensor is connected between this terminal and the GND terminal. This input is also monitored for push-button override commands. The push-button is only active during unoccupied hours so a push during occupied hours has no effect.
AIN2 - Slide Adjust - If the OE212 or OE213 space temperature sensor is installed, the sensor contains a slide adjust control for varying the current heating and cooling setpoints. If the OE210 or OE211 sensors are used, this input will not be used.
AIN3 - Discharge Temp - The discharge temperature reading is used to detect discharge air temperature and to monitor for equipment failure. Once the compressor has activated, the discharge air temperature has 10 minutes to change by
5
°
F or the controller assumes a mechanical failure has occurred.
AIN4 - Leaving Water Temp and/or Dirty Filter Alarm - Can provide status only water temperature and/or dirty filter contact closure. If both are used at the same time, water temperature will be lost when the dirty filter contact is closed.
AIN5 - Lockout - If this input is active all operations are terminated to protect the equipment.
GND - Common return wire. This point is tied to ground on the WHP
Controller.
2.2.3
Analog Output Description
AOUT - Analog Output - This output is not used.
2.2.4
Relay Output Descriptions
COM1-3 - Common 1 thru 3. - This ties the common return of the first 3 outputs together.
OUT1 - Fan On/Off - The fan is enabled to run when this contact is closed.
OUT2 - Reversing Valve or Heat 1 - This output enables the reversing valve if you have configured the WHP Controller for a compressor and reversing valve configuration. If the WHP Controller is configured for individual staging of heating and cooling (no reversing valve) then this output enables heating stage 1.
4-6 Start-Up and Troubleshooting
WattMaster WHP Section 4
OUT3 - Compressor or Heat 2 - This output enables the compressor if you have configured the WHP Controller for a compressor and reversing valve configuration. If the WHP Controller is configured for individual staging of heating and cooling (no reversing valve) then this output enables heating stage 2.
OUT4 - Heat Pump Reset or Cool 1 - This output can be used to reset a compressor that has gone off line. If the WHP Controller is configured for individual staging of heating and cooling (no reversing valve) then this output enables cooling stage 1.
OUT5 - Aux. Relay or Cool 2 - If you have configured the WHP Controller for a compressor and reversing valve configuration this output can be configured as follows:
1.) Stage 2 for cooling and/or heating mode.
2.) Auxiliary scheduling relay. In this mode it can be programmed to follow an externally broadcast schedule signal.
3.) Auxiliary relay. In this mode it can be used for any function requiring a manual user intervention.
4.) Isolation valve. May be used to initiate opening of an isolation valve in case of high loop water pressure even if the WHP Controller is satisfied or in an unoccupied mode. In occupied mode this relay operates in conjunction with the compressor.
If the WHP Controller is configured for individual staging of heating and cooling
(no reversing valve) then this output enables cooling stage 2.
COM4-5 - Common 4 and 5. - This ties the common return of the last 2 outputs together. Jumper this terminal to COM1-3 if the unit does not have separate cooling and heating power supplies.
2.2.5
RS-485 Communications Connector
This connector provides the connection point for the Local Loop RS-485 communications loop. The wiring consists of a twisted pair of wires with a shield.
T - RS-485 (+) Communications terminal
SHLD - Common return wire, this point is internally tied to GND on the WHP
Controller.
R - RS-485 (-) Communications terminal
Start-Up and Troubleshooting 4-7
WattMaster WHP
2.2.6
WHP Controller Wiring
Communication LED
Section 4
Figure 4-4: Typical WHP Controller Wiring Diagram
4-8 Start-Up and Troubleshooting
WattMaster WHP Section 4
3.0 Loop Controller
Overview
3.1
How It Works
3.1.1
Initialization
On system powerup LED2 remains extinguished for five seconds. After this delay, the
LED2 will blink out the address of the controller (Address Switch Setting). The LED2 will then extinguish for another five seconds and then the LED2 will begin blinking a diagnostic code every ten seconds. This code is described in the troubleshooting section.
The duration of a powerup initialization sequence is roughly thirty seconds.
During this initialization period, the controller retrieves all operating setpoints from its non-volatile EEPROM memory and initializes all outputs to an OFF condition.
3.1.2
Operating Summary
There is a standard set of operating instructions that are continuously performed over and over during normal Loop Controller operations. They are listed below.
a b
Read analog inputs for temperatures, pressures and binary contact closures
Checks for new setpoints from System Manager or Prism Software and keeps the status values updated for these interfaces.
c Looks for “request to run” broadcast from any installed WHP Controller or from an on-board binary input.
d. Set all outputs to match calculations for heat rejection or addition.
e. Store data in internal trend log if ready for another log f. Broadcasts the operating commands to all WHP Controllers.
g. Tests for lead/lag pump changeover if both pumps are off.
h. Repeat steps a-g continuously
Start-Up and Troubleshooting 4-9
WattMaster WHP Section 4
3.2
Loop Controller Inputs & Outputs
3.2.1
Analog Inputs
AIN1 - Return Water Temp - This input accepts a two wire 10K Type III thermistor temperature sensor. The sensor measures 10,000 Ohms @ 77
°
F. The resistance drops as the temperature increases. The sensor is connected between this terminal and the GND terminal.
AIN2 - Supply Water Temp - This input accepts a two wire 10K Type III thermistor temperature sensor. The sensor measures 10,000 Ohms @ 77
°
F. The resistance drops as the temperature increases. The sensor is connected between this terminal and the GND terminal.
AIN3 – Proof of Flow/Loop Pressure - This input accepts a differential pressure contact closure for proof of flow or a 0-50 PSI (0-5VDC) pressure transducer signal.
AIN4 - Outdoor Air Temp - The OA temperature is used to determine if pumps should be turned on during off periods, to prevent freezing. When the OA temperature is below 40
°
F, the pumps will be turned on.
AIN5 - Manual Reset Input - Used to restart equipment after alarm condition has occurred. When this input is shorted to GND by a momentary pushbutton, a signal to restart is sent.
AIN7 – Phase Loss – If a phase monitor is being used, a normally open contact is connected here. When a loss of phase is detected, this contact closes shutting down the Loop Controller.
GND - Common return wire. This point is tied to ground on the Loop Controller.
3.2.2
Analog Output
This connector carries a 0-10 volt control signal for the following items:
AOUT1- Pump VFD Signal - If you have selected the variable speed pump option this output signal is used to control the loop pressure.
AOUT2 - Proportional Heat Signal - This output may be used when a modulating signal is required to control heat addition temperature.
GND - Common return wire, this point is tied to GND on the Loop Controller.
4-10 Start-Up and Troubleshooting
WattMaster WHP Section 4
3.2.3
Binary Output
R1 – Compressor Enable – Energizes the first stage of cooling.
R2 – Main Pump – Energizes the lead water pump.
R3 – Standby Pump – Energizes the standby pump if the main pump fails to start.
R4 – Alarm Indicator – Energizes when an alarm occurs on the Loop Controller.
R5 – Not Used – This output is not used.
COM 1-3 - Common – 24 VAC from the AHU is connected to this terminal and is the common for inputs 1 through 3.
COM 4-5 - Common – 24 VAC from the AHU is connected to this terminal and is the common for inputs 4 and 5.
3.2.4
Relay Expansion Board - Outputs
This connector carries the output relay dry contact open/closed signal.
Relays 1-4 - Heat Addition/Rejection Stages - Can be configured to be used for either stages of heating or cooling of water when required.
Relays 5-8 - Heat Addition/Rejection Stages – Same as above, can be used for heating or cooling of the water.
3.2.5
Analog Input Expansion Board
The following inputs use dry contact open/closed signals.
AIN1 – Fire Alarm Contact - Used to shut down all equipment in case of a smoke or fire condition.
AIN2 - Request to Run - Used to initiate system start when a water source heat pump controller other than the WattMaster WHP Controller is used.
Warning:
Fire Alarm Contact input must be connected to the AIN1- GND terminal if it is not used, a jumper must be connected between AIN1 and GND, since this is a normally closed contact input. If this is not done the system will not operate.
Start-Up and Troubleshooting 4-11
WattMaster WHP Section 4
3.2.6
Comm Connector - Communications
RS-485 Communications Connector - This connector provides the connection point for the Local Loop RS-485 communications loop. The wiring consists of a twisted pair of wires with a shield.
T - RS-485 (+) Communications terminal
SHLD - Common return wire, this point is internally tied to GND on the WHP
Controller.
R - RS-485 (-) Communications terminal
3.2.7
Power Terminal
This connector provides power to the Loop Controller
24 VAC - Connect to the “HOT” side of the control transformer.
GND - The grounded side of the control transformer. If the secondary of the control transformer is not grounded, you must still observe polarity if the trans- former powers any other device!
Warning:
Connect only the GND terminal to the grounded side of a transformer
Failure to properly observe polarity will result in damage to the
system. Observe polarity at all points in the system.
4-12 Start-Up and Troubleshooting
WattMaster WHP
Connect To Next Controller And/Or
MiniLink On Local Loop
Local Loop RS-485
9600 Baud
(See Note 3).
Optional
Pressure sensor
Section 4
Line Voltage
Figure 4-5: Loop Controller Inputs & Outputs
Start-Up and Troubleshooting 4-13
WattMaster WHP Section 4
4.0 Start-Up
4.1
Blink Codes for WHP Controllers
The WHP Controller uses an on board LED to indicate various diagnostic conditions during powerup and operation. The WHP Unit LED is labeled “COMM”. Starting with power up the LED blink codes are as follows:
•
Off for five seconds
•
COMM LED blinks the board address (Address 14 = 14 blinks)
•
Five second pause
•
Twenty second time delay - LED blinks twenty times
•
Status code is repeatedly blinked every ten seconds to indicate controller status:
Priority
Lowest
-
-
-
Highest
No. of Blinks
1
2
3
4
5
Figure 4-6: Diagnostic LED Blink Codes
Status
Normal Operation
Override Active
Bad Space Sensor
Heat Pump Lockout
Communication Failure
Only the highest priority failure code will be shown. You must correct the highest priority alarm before other problems will be indicated.
4-14 Start-Up and Troubleshooting
WattMaster WHP Section 4
4.2
Blink Codes for Loop Controllers
The Loop Controller uses an on board LED to indicate various diagnostic conditions during powerup and operation. The Loop Controller Unit LED is labeled “LED2”.
Starting with power up the LED blink codes are as follows:
•
Off for five seconds
•
COMM LED blinks the board address (Address 14 = 14 blinks)
•
Five second pause
•
Status code is repeatedly blinked every ten seconds to indicate controller status:
Priority
Lowest
-
-
-
-
Highest
No. of Blinks
1
2
3
4
5
6
Figure 4-7: Diagnostic LED Blink Codes
Status
Normal Operation
Pump and/or Flow Failure
Bad Water Temp Sensor
Single Phase Shutdown
Water Pressure Alarm
Fire Alarm
Only the highest priority failure code will be shown. You must correct the highest priority alarm before other problems will be indicated.
4.3
Communications Checklist
•
WHP Controllers are addressed from 1 to 30 on each loop except the loop with the
WHP Loop Controller. This loop can only use address 1 thru 29 for the WHP Controllers. WHP Loop Controller is addressed as 30 on the loop it is connected to.
•
Power has been cycled after changing addresses
•
A multiple loop CommLink II is powered and connected to the communications loop.
•
System Manager is connected to one of the local loops.
•
The MiniLinks on each local loop are addressed with a unique address 1 thru 30, depending on the number of loops on your system.
Start-Up and Troubleshooting 4-15
WattMaster WHP Section 4
4.4
Installation and Commissioning
Information
Familiarize yourself with the installation manual and system wiring diagrams before installing!
1. Check to see if you have all the correct components for your installation.
2. Establish the location for the CommLink Interface first. This is where your communication cable will begin.
3. Layout your communication wiring. For systems with more than 30 WHPs or more than one MiniLink, there are multiple communication loops:
A. The Network Loop - This loop originates at the CommLink and interconnects
MiniLinks together.
B. The Local Loop – This loop originates at the MiniLink. The WHPs, Loop
Controllers and the System Manager are connected to this loop.
Tip: Using the WattMaster color-coded and labeled Communication Cable insures a quality installation. It also makes your installation much easier and less likely to have communications wiring errors!
4 .
Communication cable must always be shielded – no exceptions!
5. Mount controllers in appropriate locations according to their operating specification.
6. Address controllers according to location and addressing instructions located in the system manual.
7. With no power connected, wire controller according to wiring diagrams and in accordance with local codes. Never apply power until you have completed these procedures in accordance to all system instructions.
8. After completing all wiring connections, unplug the terminals for power and communications. Always unplug the communications loop first and then the power. When reconnecting the wiring, connect the power first and then the communication loop.
9. Continue step 8 until all devices have been wired and the power and communication terminals have been unplugged.
4-16 Start-Up and Troubleshooting
WattMaster WHP Section 4
10. Install CommLink and power-up. At this point you are ready to begin commissioning the system. It is preferred, though not necessary, to use a PC with Prism software to assist in the commissioning process.
11. Start with the first controller on the communication loop or in multiple loop systems; start with the MiniLink or with the System Manager. Plug in the Communication terminal then plug in the Power terminal.
12. Observe the LED indicator for the blink codes as outlined in the troubleshooting section of the manual. The blink code will first verify the address, then the operation.
If the address is incorrect, reset the dipswitch, then reapply power to the controller.
13. After each controller is connected and completes its initialization sequence, use the
PC or System Manager to verify communication to that device. If you cannot communicate, verify wiring, voltages, etc. in accordance with the troubleshooting section in the system manual. Do not proceed to the next device until you are properly communicating with the current device.
Continue this process until all controllers are connected and properly communicating.
By following the above steps and procedures, your installation will be much faster and trouble free. Remember that each controller only contains one puff of smoke. Making sure that all wiring terminations and voltages are correct prior to applying power to a controller will insure that you don’t use that one puff.
Start-Up and Troubleshooting 4-17
WattMaster WHP
COMM LINK II
INTERFACE
(MULTIPLE LOOP)
03/31/04 03:38PM WED
OCCUPIED
NO ALARMS
POWER
24VAC
GND
COMMUNICATIONS
T
SHLD
RS-485
R
SYSTEM MANAGER POWER SUPPLY
YS101716 REV. 1
SYSTEM MANAGER
Section 4
NETWORK
LOOP
U3
1
RN1
CX1
U1
U2 CX2 CX4
U4
T B1
COMM
T
SHLD
LD6
COMM
U5
RS -485
COMM
LD7
P WR
1
HH
LD8
LED1
P1
C1
R1
LD9
LED2
U7
+V RE F
5.11V
TES T POINT
EWDOG
RV 1
V REF ADJ
R28
INPUTS ADDRES S
RAM
U6
+VDC
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
RN5
C10
AOUT1
C12
P U1
D6
P U2
D7
P U3
D8
P U4
D9
P U5
D11
P U7
D14
U13
SW1
ADD
1
2
4
8
16
32
TO KEN
NE TWORK
U10
J P1
X2
R15
EP ROM
TUC-5R PLUS
( 1 MEG)
YS101816 RE V. 2
CX10
U12
CX6
CX12
TB 3
R
CX 5
AOUT2
AIN7
GND
PJ 1
C17
D15
C20
CX13
U15
CX15
C14
R19
U14
CX14
C15
R22
R24
R25
U9
1
PA L
1
C7
D12
R13
SC1
D19
R26
PRESSURE
SENSOR
EXPANSION T'STAT
V R1
L1
VR2
V1
V2
V3
COM1-3
R1
R2
R3
R4
R5
COM4-5
TB2
V4
V 5
U8
NE 5090NP B3192
0P S
R6
C9
340 64A
C13
C16
TB4
GND
24VAC
4RLY IO BD.
YS101790
4RLY IO BD.
YS101790
AIN1
AIN2
AIN3
AIN4
GND
AOUT1
4 ANALOG IN MOD I/O BD.
YS101784
32K
8K
COMM
LD4
SHLD
R
REC.
RAM EPROM
12V
AIN
3
4
AIN
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
PWR
GND
24VAC
RELAY
OUTPUT
1-3
OUT
OUT
COM
4-5
32K
8K
COMM
LD4
R
REC.
485
COMM
RAM EPROM
12V
AIN
2
3
4
AIN
5
GND
GND
AOUT
PRESSURE
SENSOR
YS101564
CPU
ADDRESS ADD
COMM
TEST
PWR
GND
24VAC
OUTPUT
COM
1-3
OUT
2
OUT
OUT
5
4-5
TO OTHER WHP CONTROLLERS
TO OTHER MINILINKS
(NETWORK TERMINALS ONLY)
Figure 4-8: Communications Loop Wiring
4-18 Start-Up and Troubleshooting
WattMaster WHP
4.5
Setting Address Switches
4.5.1
Setting the MiniLink Address Switch
LOOP
ADDRESS SWITCH
ADD
8
16
32
1
2
4
4
3
2
8
7
6
5
1
OFF >
LOOP
ADDRESS SWITCH
ADDRESS SWITCH SHOWN IS
SET FOR ADDRESS 1
ADDRESS SWITCH SHOWN IS
SET FOR ADDRESS 13
T
SH
R
4
8
1
2
16
32
8
7
6
5
4
3
2
1
OFF >
T
SH
R
24VAC
GND
NOTE:
THE POWER TO THE MINILINK MUST BE
REMOVED AND RECONNECTED AFTER
CHANGING THE ADDRESS SWITCH SETTINGS
IN ORDER FOR ANY CHANGES TO TAKE
EFFECT.
CAUTION:
DISCONNECT ALL COMMUNICATION
LOOP WIRING FROM THE MINILINK BEFORE
REMOVING POWER FROM THE MINILINK.
RECONNECT POWER AND THEN RECONNECT
COMMUNICATION LOOP WIRING.
Figure 4-9: MiniLink Address Switch Setting
Section 4
Start-Up and Troubleshooting 4-19
WattMaster WHP Section 4
4.5.2
Loop Controller Addressing
The Loop Controller address should always be set for address #30. A maximum of 29
WHP Controllers on the loop that contains the Loop Controller. All other loops may have
30 WHP Controllers. (Refer to Figure 2-10 for more detail)
4.5.3
WHP Controller Addressing
NOTE:
IGNORE ANY MARKINGS
OR NUMBERS ON THE SWITCH
USE THE CHART!
To determine the boards address, add the values of all the switches which are toggled down in the direction of the arrow
Figure 4-10: WHP Controller Address Switch Setting
NOTE:
ADDRESS 30 CANNOT BE USED
ON THE LOOP THAT HAS THE WHP LOOP
CONTROLLER ATTACHED. ADDRESS 30
ON THAT LOOP IS RESERVED FOR THE
WHP LOOP CONTROLLER.
CAUTION:
YOU MUST POWER DOWN THE CONTROLLER
AFTER CHANGING THE ADDRESS SWITCHES
IN ORDER FOR ANY CHANGES TO TAKE EFFECT.
ALWAYS REMOVE THE COMMUNICATIONS LOOP
PRIOR TO DISCONNECTING POWER. RECONNECT
POWER AND THEN RECONNECT THE COMMUNICATIONS
LOOP TO THE CONTROLLER.
4-20 Start-Up and Troubleshooting
WattMaster WHP
5.0 Troubleshooting
Section 4
5.1
General Troubleshooting
The following is a guide to assist in troubleshooting the WattMaster WHP System. It is provided as a systematic approach to determining and resolving common system problems.
5.1.1
Communications Troubleshooting Checklist
No WHP or Loop Controller Units are Communicating
•
Is the CommLink II connected and plugged in?
•
Is the CommLink II installed, a single or multiple loop version. A jumper in the
CommLink can be set for “Single” or “Multi”. On the WHP system is considered a
Multiple Loop version and the CommLink jumper must be set on Multi.
•
Are Comm Loop voltages correct? See the Comm Loop troubleshooting guides.(page
4-24)
•
Is the Comm Loop open or shorted?
•
Is the CommLink II connected and plugged in?
•
Is the MiniLink Voltage correct?
•
Are the WHP and Loop Controller address switches set correctly? See the addressing chart. (WHP Loop Controller should always be set to address 30, see Figure 4-10)
•
Is the MiniLink address switch set correctly? See the addressing chart.(see Figure 4-
10)
•
Are the WHP and Loop Controllers powered? Check 24 VAC to the controllers.
•
Is the System Manager connected to the Local Communications loop?
Some WHP Units are communicating but others are not:
•
Are the WHP Controller address switches set correctly? See the addressing chart.
•
Is the WHP Loop Controller address switch set correctly? See the addressing chart.
•
Are the WHP Controllers and Loop Controller powered? Check 24 VAC to the controllers.
•
Is the REC LED on the missing WHP Controller “flickering”? See WHP Controller introduction for location of the REC LED. (see Figure 4-4)
•
Is the COMM LED on the WHP Controller blinking an error code? See the Blink
Code chart. (see Figure 4-6)
•
Are Comm Loop voltages correct at the missing unit? See Comm Loop troubleshooting guide starting on page 4-24.
Start-Up and Troubleshooting 4-21
WattMaster WHP Section 4
5.1.2
General Troubleshooting Checklist
Begin troubleshooting by locating the general problem in the list below. Detailed component troubleshooting information follows later in this section.
Zone is too warm
•
Is zone calling for cooling?
•
Is the compressor disabled due to minimum off time setting?
•
Is water proof of flow signal disabled?
•
Is the LED blinking an error code? See Figure 4-6.
Zone is too cool
•
Is zone calling for heating?
•
Is the compressor disabled due to minimum off time setting?
•
Is water proof of flow signal disabled?
•
Is the LED blinking an error code? See Figure 4-6.
Zone Sensor reading incorrectly
•
Is the sensor near a source of heat or a cold draft? Location is a common problem.
The sensor should be mounted on an inside wall away from heat sources and in a location with adequate room air circulation.
•
Is the resistance reading correct? Check with the Temperature/Resistance Chart in this section. (see page 4-42)
•
Is wiring correct? Check for errors.
Check the Room sensor
•
To meter the Room sensor:
Unplug the room sensor terminal block. Using your meter, check the resistance of the unplugged terminal block. Use the supplied Temperature/Resistance Chart (page 4-
42) to see if the sensor is within a reasonable range. Readings which are much too high or too low generally indicate wiring problems.
•
To meter the Slide Adjust (optional):
Use your ohmmeter to check the resistance between the room sensor GND wire and the AIN2 terminal on the unplugged terminal block.
The resistance for various positions of the slider on the sensor should be as follows:
Full UP position 15K
Ω
(
±
500
Ω
)
MID position 12.5K
Ω
(
±
500
Ω
)
Full DN position 10K
Ω
(
±
500
Ω
)
4-22 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.2 Alarms
When an alarm occurs in the WHP or Loop Controller, it is reported to the System
Manager. The alarms cause the light on the System Manager to illuminate. The View
Alarms screen will indicate the address of the alarms. The Status screen will display the type of alarm that has occurred. Here is a list of the alarms that are reported to the System
Manager.
WHP:
Bad Space Sensor – Space sensor is either open or shorted
Hi Space Temp Alarm – If space temperature is 5
°
or more above cooling setpoint
Lo Space Temp Alarm – If space temperature is 5
°
or more below heating setpoint
Dirty Filter Alarm – Contacts between AIN4 and GND are shorted
Cooling Failure – If supply air doesn’t drop 5
°
in 10 minutes in cooling mode
Heating Failure - If supply air doesn’t go up 5
°
in 10 minutes in heating mode
Loop Controller:
Pump Failure – No proof of flow within 5 seconds after pump starts
No Flow Detected – The contact between AIN3 and GND is open, no water flow
Phase Shutdown – The contact between AIN7 and GND is open, loss of phase
Lo Water Temp Alarm – Water Temp is below Lo Limit setpoint
Hi Water Temp Alarm - Water Temp is above Hi Limit setpoint
Start-Up and Troubleshooting 4-23
WattMaster WHP Section 4
5.3 Checking Comm. Loop Voltages
5.3.1
Checking the CommLink II Network Loop
Diagram
Overview
This test checks for proper Network loop voltages at the CommLink II.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink II is attempting to communicate. The Loop LED will flicker more noticeably for a few seconds when first powered up. If the Loop LED does not flicker, the unit is defective.
Make sure CommLink II jumper is set to “Multi” position.
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations at this point on the CommLink II. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 10-15 seconds as the unit attempts to communicate.
Measurements
Network Loop
T - G (SHLD) 2.9 - 3.1 Volts DC
Acceptable Range
R - G (SHLD)
Action
1.9 - 2.1 Volts DC
Condition
If voltages are too high or too low on either side
Action
1. Unplug the Network loop from the
CommLink II and check for proper loop voltages. If a problem exists, disconnect each MiniLink Network loop until the problem is isolated.
2. Check the CommLink II Driver chip.
Replace the driver chip if necessary
4-24 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.3.2
Checking the Comm Loop at the CommLink II
Diagram
The indicated values are typical of a normal system, actual readings may deviate slightly due to the number of units connected and other system specific factors.
Note: All of the connected Minilinks should be powered up for this test.
Overview
This is a “quick check” to determine if any of the driver chips on the Network loop are damaged. Since all units will “float” both of their communications connections at about
2.45 Volts, you can quickly check the Network loop by unplugging it at the CommLink II.
Note: Be sure that the loop you are testing does not have a short circuit from T to R.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink II is attempting to communicate with the MiniLinks. There is a noticeable change in the flicker when the loop is disconnected, if you observe a normal functioning unit. When the loop is reconnected it may take up to 60 seconds before the CommLink II reestablishes communications with the MiniLinks.
Measurements
Network Loop
T – G (SHLD) 2.4-to-2.5 Volts DC
Acceptable Range
R – G (SHLD) 2.4-to-2.5 Volts DC
Action
Condition
If voltages are too high or too low on either side
Action
One or more of the MiniLinks has a damaged
Network driver chip. Disconnect the Mini-
Links one at a time to isolate the problem.
Start-Up and Troubleshooting 4-25
WattMaster WHP
5.3.3
Checking the CommLink II Driver
Diagram
Section 4
Overview
This test checks for proper Network loop voltages coming from the CommLink II.
Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink II is attempting to communicate. The Loop LED will flicker more noticeably for a few seconds when first powered up. If the LED does not flicker, the unit is not functioning.
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations at this point on the CommLink II. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 10-15 seconds as the unit attempts to communicate.
Measurements
Local Loop
T – G
(SHLD)
2.4 - 2.5 Volts DC
Acceptable Range
R – G
(SHLD)
Action
2.5 - 2.7 Volts DC
Condition
If voltages are too high or too low on either side
Action
1. The CommLink II has a damaged comm driver chip. Replace the driver chip.
See instructions in section 1.3.11 for
“Comm Driver Chip Replacement”.
2. The CommLink II is defective.
4-26 Start-Up and Troubleshooting
WattMaster WHP
5.3.4
Checking the MiniLink Network Loop
Diagram
Meter Set To Read DC Volts
Section 4
The indicated readings are typical of a normally operating system. Actual readings may vary slightly due to the number of units installed and other factors. Any significant deviation from these values generally indicates a problem.
Note: These tests assume that the CommLink II is connected and powered, and that all
MiniLinks which are connected are also powered.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations on an operating communications loop. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 15-30
seconds as normal communications occur.
Measurements
LOCAL LOOP
T - G (SHLD) 2.9 - 3.1 Volts DC
Acceptable Range
R - G (SHLD)
Action
1.9 - 2.1 Volts DC
Condition
Readings near Zero Volts
If voltages are too high or too low on either side
Action
Check for shorted wiring.
1. One or more devices connected to this loop may have damaged Comm driver chips.
2. Wiring errors. Check for multiple loops
“cross connected”, short circuits, etc.
Start-Up and Troubleshooting 4-27
WattMaster WHP
5.3.5
Checking the MiniLink Network Driver
Diagram
Meter Set To Read DC Volts
Section 4
Note: These tests assume that the MiniLink being checked is powered up
Overview
This check is intended to determine if the Network Comm Driver chip on a MiniLink is damaged.
Tip: Before unplugging the Network loop from the MiniLink, observe the Network Loop
LED (located near the connector). It should periodically “flicker” as the CommLink II requests data from the MiniLink. The LED will also flicker when power to the
CommLink II is cycled. If the LED is not flickering, the unit is not communicating with the CommLink II.
Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.
Measurements
Network Loop
T – SHLD 2.4 - 2.5 Volts DC
Acceptable Range
R – SHLD 2.4 - 2.5 Volts DC
Note: Minor variances may not indicate a problem if both tests indicate similar values
Action
Condition
If voltages are too high or too low on either side
Action
The MiniLink has a damaged Network
Comm Driver chip. Replace the driver
chip. See "1.3.11Comm Driver Chip Re- placement”.
4-28 Start-Up and Troubleshooting
WattMaster WHP
5.3.6
Checking the MiniLink Local Loop
Diagram
Meter Set To Read DC Volts
Section 4
The indicated readings are typical of a normally operating system. Actual readings may vary slightly due to the number of units installed and other factors. Any significant deviation from these values generally indicates a problem.
Note: These tests assume the MiniLink is powered up
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations on an operating communications loop. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 30-45 seconds. Voltages fluctuate as normal communications occur.
Measurements
Local Loop
T – SHLD 2.9 - 3.1 Volts DC
Acceptable Range
R – SHLD 1.9 - 2.1 Volts DC
Action
Condition
Readings near zero volts
Action
Check for shorted wiring.
If voltages are too high or too low on either side
1. One or more devices connected to this loop may have damaged Comm Driver chips.
2. Wiring errors. Check for multiple loops inadvertently “cross connected”, short circuits, etc.
Start-Up and Troubleshooting 4-29
WattMaster WHP
5.3.7
Checking the Local Loop at MiniLink
Diagram
Meter Set To Read DC Volts
Section 4
The indicated values are typical of a normal system. Actual readings may deviate slightly due to the number of units connected and other system specific factors
Note: These tests assume that the controllers being checked are powered up.
Overview
This is a “quick check” to determine if any of the WHP Controllers or WHP Loop Controller on a Local Communications Loop are damaged. Since all WHP Controllers will “float” both of their communications connections at about 2.45 Volts, you can quickly check an entire loop by unplugging it at the MiniLink.
Note: Be sure that the loop you are testing does not have a short circuit from T - R.
Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation, due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur due to wiring related problems.
Measurements
Local Loop
T – SHLD 2.4 - 2.5 Volts DC
Acceptable Range
R – SHLD 2.4 - 2.5 Volts DC
Note: Minor variances may not indicate a problem if both tests indicate similar values.
4-30 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.3.7
(continued)
Action
Condition
If voltages are too high or too low on either side
Action
1. One or more of the attached controllers has a damaged Comm Driver chip. Lo- cate and replace the driver chip(s).
See "1.3.11 Comm Driver Chip Replacement”.
2. Wiring errors such as "crossed connections", short circuits, etc.
Start-Up and Troubleshooting 4-31
WattMaster WHP
5.3.8
Checking the MiniLink Local Loop Driver
Diagram
Meter Set To Read DC Volts
Section 4
The indicated values are typical of a normal operating system. Actual readings may deviate slightly.
Note: These tests assume that the MiniLink is powered up.
Overview
This test checks for proper Local Loop voltages coming from the MiniLink.
Tip: The Local Loop LED (located near the connector) should “flicker” when the Mini-
Link is operating and when first powered up. If the LED is not flickering, the unit is not functioning.
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations at this point on the MiniLink. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 10-15 seconds. The voltage will fluctuate as the unit attempts to communicate.
Measurements
Local Loop
T – G
(SHLD)
2.9 - 3.1 Volts DC
Acceptable Range
R – G
(SHLD)
1.9 - 2.1 Volts DC
Action
Condition
If voltages are too high or too low on either side
Action
1. The MiniLink has a damaged Comm
Driver chip. Locate and replace the
driver chip(s). See "1.3.11 Comm
Driver Chip Replacement”.
2. The MiniLink is not functioning.
4-32 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.3.9
Checking the Local Loop at a WHP Controller
Diagram
Meter Set To Read DC Volts
The indicated readings are typical of a normal operating system. Actual readings may vary slightly due to the number of units installed and other factors. Any significant deviation from these values generally indicates a problem.
Note: These tests assume that a MiniLink is connected and powered up.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations on an operating communications loop. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 30-45 seconds. The voltages may fluctuate as normal communications occur.
Measurements
Local Loop
T – SHLD 2.9 - 3.1 Volts DC
Acceptable Range
R – SHLD 1.9 - 2.1 Volts DC
Action
Condition
If meter reads between 2.4 VDC and 2.5
VDC
The Comm Loop “floats” at 2.4 - 2.5VDC
when only controllers are connected to the loop. When a MiniLink is connected it will
“bias” each side of the loop to the values listed above.
If voltages are too high or too low on either side
Action
1) No CommLink II or MiniLink is connected and powered up.
2) If a CommLink II or MiniLink is connected, look for “open” wiring.
One or more devices connected to this loop have damaged Comm Driver chips.
Start-Up and Troubleshooting 4-33
WattMaster WHP
5.3.10 Checking WHP Controller Driver Chip
Diagram
Meter Set To Read DC Volts
Section 4
Note: These tests assume that the controller being checked is powered up.
Overview
This check is intended to determine if the Comm Driver chip on a controller is damaged.
Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation, due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.
Measurements
Local Loop
T – SHLD 2.4 - 2.5 Volts DC
Acceptable Range
R – SHLD 2.4 - 2.5 Volts DC
Note: Minor variances may not indicate a problem if both tests indicate similar values.
Action
Condition
If voltages are too high or too low on either side
Action
The controller has a damaged Comm
Driver chip. Replace the driver chip. See
"1.3.11 Comm Driver Chip Replacement”.
4-34 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.4
Troubleshooting Loop Controller
5.4.1
Checking the Loop Controller Analog Inputs
Diagram
SET METER TO
READ DC VOLTS
+
R
ALL READINGS ARE TAKEN
WITH THE (-) LEAD OF THE
METER ON THE GND
TERMINAL
-
+
12V
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
Overview
The analog input wiring can be checked at the
Loop Controller by checking voltages on the
Analog Input Connector.
If any of the RWT, SWT, OAT inputs read greater than 5.0 volts then it is OPEN (no sensor is connected), an input that reads less than 0.1 volts is SHORTED. Check for wiring problems before proceeding.
The Loop Pressure, Manual Reset, Phase
Loss, Fire Alarm and Request to Run inputs should read greater than 5.0 volts if the attached contact is OPEN and less than 0.5 volts if the contact is CLOSED (contacts CLOSE between the input and GND). The Fire Alarm and Request to Run contacts are located on the Analog Input Expansion Board.
Note The Loop Controller must be powered for these tests.
Measurements
Meter
AIN1
Return Water Temp
AIN2
Supply Water Temp
AIN3
Proof of Flow
Acceptable Range
Ignore readings for any connections which are not used in the equipment.
1.9 volts (100
°
F) - 3.6 volts (40
°
F)
Typical is 2.5 volts @ 77
°
F
1.9 volts (100
°
F) - 3.6 volts (40
°
F)
Typical is 2.5 volts @ 77
°
F
When used with the Low Pressure Switch option:
If the input is OPEN, the voltage will be greater than 5.0 volts
If the input is CLOSED, the voltage will be less than 0.5 volts
When used with 0-50 PSI Loop Pressure Sensor option:
5.1 VDC = 50 PSI – 0.0 VDC = 0 PSI
Start-Up and Troubleshooting 4-35
WattMaster WHP Section 4
5.4.1
(continued)
AIN4
Outdoor Air Temp
1.9 volts (100
°
F) - 3.6 volts (40
°
F)
Typical is 2.5 volts @ 77
°
F
AIN5 If the input is OPEN, the voltage will be greater than 5.0 volts
Manual Reset If the input is CLOSED, the voltage will be less than 0.5 volts
AIN7
Phase Loss
If the input is OPEN, the voltage will be greater than 5.0 volts
If the input is CLOSED, the voltage will be less than 0.5 volts
AIN1-Exp. Bd.
Fire Alarm
If the input is OPEN, the voltage will be greater than 5.0 volts
If the input is CLOSED, the voltage will be less than 0.5 volts
Caution:
AIN1 – Fire/Smoke input must be connected to the AIN1- GND terminal. If it is not used, a jumper must be installed, since this is a normally closed contact input. If this is not done the system will not operate.
AIN2-Exp. Bd.
If the input is OPEN, the voltage will be greater than 5.0 volts
Request to Run If the input is CLOSED, the voltage will be less than 0.5 volts
Condition Action
SWT, RWT, OAT Input voltage reads too low
1. Check for shorts or other wiring errors.
2. Defective Sensor. Check using the chart.
3. High temperature at sensor. See chart.
SWT, RWT, OAT input voltage reads too high
LPR (when optional 0-5VDC Loop Pressure Sensor is used) input voltage reads too low.
1. Check for open circuit wiring errors.
2. Defective sensor. Check using the chart.
3. Low temperature at sensor. See chart.
1. Check for shorts or other wiring errors.
2. Defective Sensor. Check using the chart.
3. High pressure at sensor. See chart.
LPR (When Loop Pressure Switch is used) input voltage reads too high.
1. Check for open circuit wiring errors.
4-36 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.4.2
Checking the Loop Controller Outputs
Diagram
SET METER TO
READ DC VOLTS
+
Overview
The analog output wiring can be checked at the Loop Controller by checking voltages on the Analog Output Connector.
Note: The Loop Controller must be powered for these tests.
ALL READINGS ARE TAKEN
WITH THE (-) LEAD OF THE
METER ON THE GND
TERMINAL
R
-
+
12V
AIN1
AIN2
AIN3
AIN4
AIN5
GND
GND
AOUT1
AOUT2
AIN7
GND
Measurements
Meter Acceptable Range
Ignore readings for any connections which are not used in the equipment.
AOUT1
Pump VFD
AOUT2
Mod. Heat
This output will vary between 0 and 10 VDC to correspond with pump pressure setpoint.
This output will vary between 0 and 10 VDC to correspond with Heat
Addition setpoint.
Start-Up and Troubleshooting 4-37
WattMaster WHP Section 4
5.4.3
Checking the Local Loop at a WHP Loop Controller
Diagram
Meter Set To Read DC Volts
The indicated readings are typical of a normal operating system. Actual readings may vary slightly due to the number of units installed and other factors. Any significant deviation from these values generally indicates a problem.
Note: These tests assume that a MiniLink is connected and powered up.
Overview
Proper loop voltages are essential for reliable communications. It is normal to see fluctuations on an operating communications loop. The average value should be close to the acceptable range described below. Values will vary upon initial powerup for about 30-45 seconds. The voltages may fluctuate as normal communications occur.
Measurements
Local Loop
T – SHLD 2.9 - 3.1 Volts DC
Acceptable Range
R – SHLD 1.9 - 2.1 Volts DC
Action
Condition
If meter reads between 2.4 VDC and 2.5
VDC
The Comm Loop “floats” at 2.4 - 2.5VDC
when only controllers are connected to the loop. When a MiniLink is connected it will
“bias” each side of the loop to the values listed above.
If voltages are too high or too low on either side
Action
1) No CommLink II or MiniLink is connected and powered up.
2) If a CommLink II or MiniLink is connected, look for “open” wiring.
One or more devices connected to this loop have damaged Comm Driver chips.
4-38 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.4.4
Checking WHP Loop Controller Driver Chip
Diagram
Meter Set To Read DC Volts
Note: These tests assume that the controller being checked is powered up.
Overview
This check is intended to determine if the Comm Driver chip on a controller is damaged.
Damage typically occurs when the communications loop is exposed to excessive voltage, as may occur during installation, due to wiring errors. The driver chips are socketed on all boards to facilitate servicing. It is unusual for driver chips to fail during normal operation.
Almost all failures occur as a result of wiring related problems.
Measurements
Local Loop
T – SHLD 2.4 - 2.5 Volts DC
Acceptable Range
R – SHLD 2.4 - 2.5 Volts DC
Note: Minor variances may not indicate a problem if both tests indicate similar values.
Action
Condition
If voltages are too high or too low on either side
Action
The controller has a damaged Comm
Driver chip. Replace the driver chip. See
"1.3.11Comm Driver Chip Replacement”.
Start-Up and Troubleshooting 4-39
WattMaster WHP Section 4
5.4.5
Comm Driver Chip Replacement
WHP CONTROLLER
PIN 1
MINILINK COMMUNICATIONS INTERFACE
T
SH
R
1
2
4
8
16
32
WHP CONTROLLER
COMM DRIVER CHIP
( U5 )
NETWORK LOOP
COMMUNICATIONS
DRIVER CHIP
(U5) T
SH
R
24VAC
GND
U7
R1
R4
U2
U1
SYSTEM MANAGER
U3 CX4
U4
RN1
CX5
C3
X2
CX6
U6
CX7
U8
SC1
U9
Comm Driver Chip
(U13) Pin 1
U13
U3
PJ1
D1
R5
R6
D2
DSPY1
R13
U12
System Manager
RV1
LOCAL LOOP
COMMUNICATIONS
DRIVER CHIP
(U8)
R7
PIN 1
LOOP CONTROLLER CPU BOARD
COMMUNICATIONS
DRIVER CHIP
PIN 1
COMM DRIVER CHIP
( U1 )
COMMLINK II
DOT
PIN 1
SOCKET
PRINTED
CIRCUIT
BOARD
TYPICAL RS-485
DRIVER CHIP
WARNING!
USE EXTREME CAUTION WHEN REMOVING ANY CHIPS
TO AVOID DAMAGING ANY CIRCUIT BOARD TRACES WHICH
ARE UNDER THE CHIP.
BE SURE THAT ANY SMALL SCREWDRIVER OR OTHER
SHARP OBJECT USED TO REMOVE THE CHIP DOES NOT
COME INTO CONTACT WITH THE PRINTED CIRCUIT BOARD
SURFACE.
A SMALL SCREWDRIVER MAY BE INSERTED BETWEEN THE
CHIP AND THE SOCKET TO AID IN REMOVAL OF THE CHIP.
BE VERY CAREFUL NOT TO INSERT THE SCREWDRIVER UNDER
THE SOCKET!! DAMAGE TO THE BOARD IS NOT COVERED
BY WARRANTY.
Figure 4-11: Comm Driver Chip Replacement
4-40 Start-Up and Troubleshooting
WattMaster WHP Section 4
5.5 Temperature Sensor Resistance
Chart
21094
18655
17799
16956
16164
15385
14681
14014
13382
12758
12191
11906
11652
RESISTANCE
Ω*
93333
80531
69822
60552
52500
45902
40147
35165
30805
27140
23874
11379
11136
10878
10625
10398
10158
9711
9302
68
69
70
62
64
66
56
58
60
45
50
52
54
TEMPERATURE
º
F
-10
-5
0
5
10
30
35
40
15
20
25
74
75
76
71
72
73
78
80
3.470
3.330
3.275
3.217
3.160
3.100
3.042
2.985
2.927
2.867
2.810
2.780
2.752
VOLTAGE AT
INPUT*
4.620
4.550
4.474
4.390
4.297
4.200
4.095
3.982
3.862
3.737
3.605
2.722
2.695
2.665
2.635
2.607
2.577
2.520
2.465
TEMPERATURE
º
F
82
84
86
88
90
95
100
105
110
115
120
125
130
135
140
145
150
RESISTANCE
Ω*
8893
8514
8153
7805
7472
6716
6047
5453
4923
4449
4030
3656
3317
3015
2743
2502
2288
*Notes:
1. Use the resistance column to check the thermistor sensor while disconnected from the controllers (not powered).
2. Use the voltage column to check sensors while connected to powered controllers. Read voltage with meter set on DC volts. Place the
“-”(minus) lead on GND terminal and the
“+”(plus) lead on the sensor input terminal being investigated.
If the voltage is above 5.08 VDC, then the sensor or wiring is “open.” If the voltage is less than 0.05 VDC, the sensor or wiring is shorted.
VOLTAGE AT
INPUT*
2.407
2.352
2.297
2.242
2.187
2.055
1.927
1.805
1.687
1.575
1.469
1.369
1.274
1.185
1.101
1.024
0.952
Start-Up and Troubleshooting 4-41
WattMaster WHP Section 4
5.6 Pressure Sensor Voltage Chart
22
23
24
19
20
21
16
17
18
13
14
15
10
11
12
8
9
6
7
PRESSURE
PSI
0
1
2
3
4
5
28
29
30
25
26
27
31
32
33
2.52
2.60
2.68
2.76
2.84
2.92
2.04
2.12
2.20
2.28
2.36
2.44
VOLTAGE AT
INPUT
VDC*
1.00
1.08
1.16
1.24
1.32
1.40
1.48
1.56
1.64
1.72
1.80
1.88
1.96
3.00
3.08
3.16
3.24
3.32
3.40
3.48
3.56
3.64
10.08
10.40
10.72
11.04
11.36
11.68
8.16
8.48
8.80
9.12
9.44
9.76
CURRENT
MILIAMPS
4.00
4.32
4.64
4.96
5.28
5.60
5.92
6.24
6.56
6.88
7.20
7.52
7.84
12.00
12.32
12.64
12.96
13.28
13.60
13.92
14.24
14.56
44
45
46
40
41
42
43
PRESSURE
PSI
34
35
36
37
38
39
47
48
49
50
CURRENT
MILIAMPS
14.88
15.20
15.52
15.84
16.16
16.48
16.80
17.12
17.44
17.76
18.08
18.40
18.72
19.04
19.36
19.78
20.00
VOLTAGE AT
INPUT
VDC*
3.72
3.80
3.88
3.96
4.04
4.12
4.20
4.28
4.36
4.44
4.52
4.60
4.68
4.76
4.84
4.92
5.00
*Notes:
1. Use the voltage column to compare the meter voltage with the sensor connected to the controller and with the controller powered.
2. Read voltage with meter set on DC volts.
Place the “-”(minus) lead on GND terminal and the “+”(plus) lead on the sensor input terminal being investigated.
3. If the voltage is less than 0.05 VDC, then the sensor or wiring is “shorted” or “open”
4-42 Start-Up and Troubleshooting
WattMaster WHP
Notes:
Section 4
Start-Up and Troubleshooting 4-43
Form: WM-WHP-IO-02A Printed in the USA October 2004
All rights reserved Copyright 2004
Wattmaster Controls Inc.
•
8500 NW River Park Drive
•
Parkville MO
•
64152
Phone (816) 505-1100 E-mail: [email protected]
Fax (816) 505-1101