YASKAWA VS mini CIMRJ7 A40P2 Series Instruction Manual
विज्ञापन
विज्ञापन
YASKAWA
VS mini J7 Series
INSTRUCTION MANUAL
COMPACT GENERAL-PURPOSE INVERTER
Upon receipt of the product and prior to initial operation, read these instructions thoroughly and retain them for future reference.
YASKAWA MANUAL NO. TOE-S606-12.1G
PREFACE
Yaskawa’s VS mini J7 (hereinafter called VS mini) is a small and simple
Inverter; as easy to use as a contactor. This instruction manual describes installation, maintenance, inspection, troubleshooting, and specifications of the VS mini. Read this instruction manual thoroughly before operation.
YASKAWA ELECTRIC CORPORATION
General Precautions
• Some drawings in this manual are shown with protective covers or shields removed in order to show detail with more clarity. Make sure all covers and shields are replaced before operating the product.
• This manual may be modified when necessary because of improvements to the product, modifications, or changes in specifications.
Such modifications are indicated by revising the manual number.
• To order a copy of this manual, or if your copy has been damaged or lost, contact your Yaskawa representative.
• Yaskawa is not responsible for any modification of the product made by the user, since that will void the guarantee.
1
2
NOTATION FOR SAFETY PRECAUTIONS
Read this instruction manual thoroughly before installation, operation, maintenance, or inspection of the VS mini. In this manual, safety precautions are classified as either warnings or cautions and are indicated as shown below.
WARNING
Indicates a potentially hazardous situation which, if not avoided, may result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury or damage to equipment.
It may also be used to alert against unsafe practices.
Even items classified as cautions may result in serious accidents in some situations. Always follow these important precautions.
NOTE
: Indicates information to insure proper operation.
PRECAUTIONS FOR UL/cUL MARKING
• Do not connect or disconnect wiring, or perform signal checks while the power supply is turned ON.
• The Inverter internal capacitor is still charged even after the power supply is turned OFF. To prevent electric shock, disconnect all power before servicing the Inverter, and then wait at least one minute after the power supply is disconnected. Confirm that all indicators are OFF before proceeding.
• Do not perform a withstand voltage test on any part of the Inverter. The
Inverter is an electronic device that uses semiconductors, and is thus vulnerable to high voltage.
• Do not remove the Digital Operator or the blank cover unless the power supply is turned OFF. Never touch the printed circuit board (PCB) while the power supply is turned ON.
• This Inverter is not suitable for use on a circuit capable of delivering more than 18,000 RMS symmetrical amperes, 250 V maximum (200 V Class
Inverters) or 18,000 RMS symmetrical amperes, 480 V maximum (400 V
Class Inverters).
CAUTION
• Use 75 ° C copper wire or equivalent.
Low voltage wires must be wired with Class I Wiring.
PRECAUTIONS FOR CE MARKINGS
• Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to
CE requirements.
• For 400 V class Inverters, make sure to ground the supply neutral to conform to CE requirements.
• For conformance to EMC directives, refer to the relevant manuals for the requirements.
Document No. EZZ008389 for Japanese version,
Document No. EZZ008390 for English version
3
4
RECEIVING THE PRODUCT
CAUTION
• Do not install or operate any Inverter that is damaged or has missing parts.
Failure to observe this caution may result in injury or equipment damage.
MOUNTING
(Ref. page)
19
CAUTION
• Lift the Inverter by the heatsinks. When moving the Inverter, never lift it by the plastic case or the terminal cover.
Otherwise, the main unit may fall and be damaged.
• Mount the Inverter on nonflammable material
(i.e., metal).
Failure to observe this caution may result in a fire.
• When mounting Inverters in an enclosure, install a fan or other cooling device to keep the intake air temperature below 50 ° C.
Overheating may cause a fire or damage the Inverter.
• The VS mini generates heat. For effective cooling, mount it vertically.
Refer to the figure in Mounting Dimensions on page 22 .
(Ref. page)
21
21
21
22
WIRING
WARNING
• Only begin wiring after verifying that the power supply is turned OFF.
Failure to observe this warning may result in an electric shock or a fire.
• Wiring should be performed only by qualified personnel.
Failure to observe this warning may result in an electric shock or a fire.
• When wiring the emergency stop circuit, check the wiring thoroughly before operation.
Failure to observe this warning may result in injury.
• For 400 V class, make sure to ground the supply neutral.
Failure to observe this warning can result in an electric shock or a fire.
• Always ground the ground terminal according to the local grounding code.
Failure to observe this warning may result in an electric shock or a fire.
• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multifunction input terminal parameter is set.
Failure to observe this warning may result in injury.
(Ref. page)
24
24
24
29
29
70
5
6
CAUTION
• Verify that the Inverter rated voltage coincides with the AC power supply voltage.
Failure to observe this caution may result in personal injury or a fire.
• Do not perform a withstand voltage test on the
Inverter.
Performing withstand voltage tests may damage semiconductor elements.
• Always tighten terminal screws of the main circuit and the control circuits.
Failure to observe this caution may result in a malfunction, damage, or a fire.
• Never connect the AC main circuit power supply to output terminals U/T1, V/T2, or W/T3.
The Inverter will be damaged and the guarantee will be voided.
• Do not connect or disconnect wires or connectors while power is applied to the circuits.
Failure to observe this caution may result in injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
(Ref. page)
24
24
OPERATION
WARNING
• Only turn ON the input power supply after confirming that the front cover, top cover, and bottom cover are in place. Do not remove the covers while current is flowing.
Failure to observe this warning may result in an electric shock.
• Never operate the Digital Operator or DIP switches with wet hands.
Failure to observe this warning may result in an electric shock.
• Never touch the terminals while current is flowing, even if the Inverter is stopping.
Failure to observe this warning may result in an electric shock.
• When the fault retry function is selected, stand clear of the Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
• When continuous operation after power recovery is selected, stand clear of the Inverter or the load. The Inverter may restart suddenly after stopping.
(Construct the system to ensure safety, even if the
Inverter should restart.) Failure to observe this warning may result in injury.
• The Digital Operator stop button can be disabled by a setting in the Inverter. Install a separate emergency stop switch.
Failure to observe this warning may result in injury.
(Ref. page)
60
56
7
8
WARNING
• If an alarm is reset with the operation signal ON, the Inverter will restart automatically. Reset an alarm only after verifying that the operation signal is OFF.
Failure to observe this warning may result in injury.
• When the 3-wire sequence is set, do not make the wiring for the control circuit unless the multifunction input terminal parameter is set.
Failure to observe this warning may result in injury.
CAUTION
(Ref. page)
32
70
(Ref. page)
• Never touch the heatsinks, which can be extremely hot.
Failure to observe this caution may result in harmful burns to the body.
• It is easy to change operation speed from low to high. Verify the safe working range of the motor and machine before operation.
Failure to observe this caution may result in injury and machine damage.
• Install a holding brake separately if necessary.
Failure to observe this caution may result in injury.
• If using an Inverter with an elevator, take safety measures on the elevator to prevent the elevator from dropping.
Failure to observe this caution can result in personal injury.
• Do not perform signal checks during operation.
The machine or the Inverter may be damaged.
CAUTION
• All the constants set in the Inverter have been preset at the factory. Do not change the settings unnecessarily.
The Inverter may be damaged.
MAINTENANCE AND INSPECTION
33
WARNING
(Ref. page)
• Never touch high-voltage terminals on the
Inverter.
Failure to observe this warning may result in an electric shock.
• Disconnect all power before performing maintenance or inspection, and then wait at least one minute after the power supply is disconnected.
Confirm that all indicators are OFF before proceeding.
If the indicators are not OFF, the capacitors are still charged and can be dangerous.
• Do not perform withstand voltage test on any part of the VS mini.
The Inverter is an electronic device that uses semiconductors, and is thus vulnerable to high voltage.
• Only authorized personnel should be permitted to perform maintenance, inspection, or parts replacement.
(Remove all metal objects (watches, bracelets, etc.) before starting work.)
(Use tools which are insulated against electric shock.)
Failure to observe these warnings may result in an electric shock.
93
9
CAUTION
(Ref. page)
• The control PCB employs CMOS ICs.
Do not touch the CMOS elements.
They are easily damaged by static electricity.
• Do not connect or disconnect wires, connectors, or the cooling fan while power is applied to the circuit.
Failure to observe this caution may result in injury.
OTHERS
93
WARNING
• Never modify the product.
Failure to observe this warning may result in an electric shock or injury and will void the guarantee.
CAUTION
• Do not subject the Inverter to halogen gases, such as fluorine, chlorine, bromine, and iodine, at any time even during transportation or installation.
Otherwise, the Inverter can be damaged or interior parts burnt.
10
WARNING LABEL
A warning label is provided on the front cover of the Inverter, as shown below.
Follow the warnings when handling the Inverter.
Plastic Case
Qualification Mark
Status
Indicators
Warning Display
Nameplate
11
English and French Warning Labels
Warning Labels at End of
Instruction Manual
A Japanese warning label is attached when the VS mini is shipped.
If a English or French label is required, attach the warning label at the end of the Instruction Manual over the Japanese warning label.
Example: 3-phase (200 V Class, 1.5 kW) Inverter
12
WARRANTY INFORMATION
Free Warranty Period and Scope
Warranty Period
This product is warranted for twelve months after being delivered to
Yaskawa’s customer or if applicable eighteen months from the date of shipment from Yaskawa’s factory, whichever comes first.
Scope of Warranty
Inspections
Periodic inspections must be conducted by the customer. However, upon request, Yaskawa or one of Yaskawa’s Service Centers can inspect the product for a fee. In this case, if after conferring with the customer, a
Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period, then this fee will be waived and the problem remedied free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and the defect occurs during the warranty period,
Yaskawa will provide a replacement, repair the defective product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with a Yaskawa product is not due to defects in Yaskawa’s workmanship or materials, then the customer will be responsible for the cost of any necessary repairs. Some problems that are outside the scope of this warranty are:
• Problems due to improper maintenance or handling, carelessness, or other reasons where the customer is determined to be responsible.
• Problems due to additions or modifications made to a Yaskawa product without Yaskawa’s understanding.
• Problems due to the use of a Yaskawa product under conditions that do not meet the recommended specifications.
• Problems caused by natural disaster or fire.
• Or other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan.
However, after-sales service is available for customers outside of Japan for a reasonable fee. Contact your local Yaskawa representative for more information.
13
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawa's defective products whether within or outside the warranty period are NOT covered by this warranty.
RESTRICTIONS
• The VS mini was not designed or manufactured for use in devices or systems that may directly affect or threaten human lives or health.
• Customers who intend to use the product described in this manual for devices or systems relating to transportation, health care, space aviation, atomic or electric power, or underwater use must contact their Yaskawa representatives or the nearest Yaskawa sales office beforehand.
• This product has been manufactured under strict quality-control guidelines. However, if this product is to be installed in any location where failure of this product could involve or result in a life-and-death situation or loss of human life or in a facility where failure may cause a serious accident or physical injury, safety devices must be installed to minimize the likelihood of any accident.
14
CONTENTS
NOTATION FOR SAFETY PRECAUTIONS - - - - - - 2
1. Receiving the Product - - - - - - - - - - - - - - - - - - - 19
■ Checking the Nameplate - - - - - - - - - - - - - - - - - - - - - - - - - - - 19
2. Identifying the Parts - - - - - - - - - - - - - - - - - - - - 20
3. Mounting - - - - - - - - - - - - - - - - - - - - - - - - - - - - 21
■ Choosing a Location to Mount the Inverter - - - - - - - - - - - - - - 21
■ Mounting Dimensions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 22
■ Mounting/Removing Components- - - - - - - - - - - - - - - - - - - - - 23
4. Wiring - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 24
■ Wiring Instructions - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 24
■ Wire and Terminal Screw Sizes - - - - - - - - - - - - - - - - - - - - - - 25
■ Wiring the Main Circuits- - - - - - - - - - - - - - - - - - - - - - - - - - - - 29
■ Wiring the Control Circuits - - - - - - - - - - - - - - - - - - - - - - - - - - 31
■ Wiring Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 32
5. Operating the Inverter - - - - - - - - - - - - - - - - - - - 33
■ Test Run - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 33
Operation Check Points- - - - - - - - - - - - - - - - - - - - - - - - - - - - 34
■ Operating the Digital Operator - - - - - - - - - - - - - - - - - - - - - - - 35
Description of Status Indicators - - - - - - - - - - - - - - - - - - - - - - 36
■ Function Indicator Description - - - - - - - - - - - - - - - - - - - - - - - 38
MNTR Multi-function Monitoring - - - - - - - - - - - - - - - - - - - - - - 39
Input/Output Terminal Status - - - - - - - - - - - - - - - - - - - - - - - - 40
■ Simple Data Setting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 41
6. Programming Features - - - - - - - - - - - - - - - - - - 43
Hardware - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
Software (Constant) - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 43
15
16
■ Constant Setup and Initialization - - - - - - - - - - - - - - - - - - - - - - 44
Constant Selection/Initialization (n01) - - - - - - - - - - - - - - - - - - 44
■ Selecting V/f Pattern - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 45
Adjusting Torque According to Application - - - - - - - - - - - - - - - 45
■ Switching LOCAL/REMOTE Mode - - - - - - - - - - - - - - - - - - - - 48
How to Select LOCAL/REMOTE Mode - - - - - - - - - - - - - - - - - 48
■ Selecting RUN/STOP Commands - - - - - - - - - - - - - - - - - - - - - 49
LOCAL Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
REMOTE Mode - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 49
Operating (RUN/STOP Commands) Using Communications
(When Option Card is Installed) - - - - - - - - - - - - - - - - - - - - - - 50
■ Selecting Frequency Reference - - - - - - - - - - - - - - - - - - - - - - 50
Setting by Operator - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 50
■ Setting Operation Conditions - - - - - - - - - - - - - - - - - - - - - - - - 51
Reverse Run Prohibit (n05) - - - - - - - - - - - - - - - - - - - - - - - - - 51
Multi-step Speed Selection - - - - - - - - - - - - - - - - - - - - - - - - - - 51
Operating at Low Speed - - - - - - - - - - - - - - - - - - - - - - - - - - - - 52
Adjusting Speed Setting Signal - - - - - - - - - - - - - - - - - - - - - - - 53
Adjusitng Frequency Upper and Lower Limits- - - - - - - - - - - - - 54
Using Two Acceleration/Deceleration Times - - - - - - - - - - - - - - 55
Momentary Power Loss Ridethrough Method (n47)- - - - - - - - - 56
S-curve Selection (n20) - - - - - - - - - - - - - - - - - - - - - - - - - - - - 56
Torque Detection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 57
Frequency Detection Level (n58)- - - - - - - - - - - - - - - - - - - - - - 59
Jump Frequencies (n49 to n51)- - - - - - - - - - - - - - - - - - - - - - - 60
Continuing Operation Using Automatic Retry Attempts (n48) - - 60
Operating a Coasting Motor without Tripping - - - - - - - - - - - - - 61
Holding Acceleration/Deceleration Temporarily - - - - - - - - - - - - 62
Using Frequency Meter or Ammeter (n44) - - - - - - - - - - - - - - - 63
Calibrating Frequency Meter or Ammeter (n45) - - - - - - - - - - - 63
Reducing Motor Noise or Leakage Current Using Carrier
Frequency Selection (n46) - - - - - - - - - - - - - - - - - - - - - - - - - - 64
Operator Stop Key Selection (n06) - - - - - - - - - - - - - - - - - - - - 66
■ Selecting the Stopping Method- - - - - - - - - - - - - - - - - - - - - - - 67
Stopping Method Selection (n04) - - - - - - - - - - - - - - - - - - - - - 67
Applying DC Injection Braking - - - - - - - - - - - - - - - - - - - - - - - 68
■ Building Interface Circuits with External Devices - - - - - - - - - - 69
Using Input Signals - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 69
Using Output Signals (n40) - - - - - - - - - - - - - - - - - - - - - - - - - 73
■ Setting Frequency by Current Reference Input - - - - - - - - - - - 75
■ Preventing the Motor from Stalling (Current Limit) - - - - - - - - - 77
■ Decreasing Motor Speed Fluctuation - - - - - - - - - - - - - - - - - - 80
Slip Compensation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 80
■ Motor Protection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 81
Motor Overload Detection - - - - - - - - - - - - - - - - - - - - - - - - - - 81
■ Selecting Cooling Fan Operation - - - - - - - - - - - - - - - - - - - - - 83
■ Using MEMOBUS (MODBUS) Communications - - - - - - - - - - 83
■ Using Constant Copy Function- - - - - - - - - - - - - - - - - - - - - - - 84
Constant Copy Function - - - - - - - - - - - - - - - - - - - - - - - - - - - 84
READ Function- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 86
COPY Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 87
VERIFY Function - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 89
Inverter Capacity Display- - - - - - - - - - - - - - - - - - - - - - - - - - - 90
Software No. Display- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
Display List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 91
7. Maintenance and Inspection - - - - - - - - - - - - - - 93
■ Periodic Inspection - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 93
■ Part Replacement- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 94
Replacement of Cooling Fan - - - - - - - - - - - - - - - - - - - - - - - - 95
8. Fault Diagnosis - - - - - - - - - - - - - - - - - - - - - - - 97
■ Protective and Diagnostic Functions- - - - - - - - - - - - - - - - - - - 97
■ Troubleshooting - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 104
17
9. Specifications - - - - - - - - - - - - - - - - - - - - - - - 106
■ Standard Specifications (200 V Class) - - - - - - - - - - - - - - - - - 106
■ Standard Specifications (400 V Class) - - - - - - - - - - - - - - - - - 109
■ Standard Wiring- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 113
■ Sequence Input Connection with NPN/PNP Transistor - - - - - 115
■ Dimensions/Heat Loss (Unit: mm) - - - - - - - - - - - - - - - - - - - - 117
■ Recommended Peripheral Devices - - - - - - - - - - - - - - - - - - - 119
■ Constants List - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 122
10 Conformance to CE Markings - - - - - - - - - - - - 129
■ CE Markings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 129
■ Requirements for Conformance to CE Markings - - - - - - - - - - 129
Low Voltage Directive- - - - - - - - - - - - - - - - - - - - - - - - - - - - - 129
EMC Directive - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 130
Revision History
18
1. Receiving the Product
1. Receiving the Product
After unpacking the VS mini, check the following.
• Verify that the model number matches your purchase order or packing slip.
• Check the Inverter for physical damage that may have occurred during shipping.
If any part of VS mini is missing or damaged, call for service immediately.
Checking the Nameplate
Example for 3-phase, 200-VAC, 0.1-kW Inverter
Inverter Model
Input Spec.
Output Spec.
Lot No.
Serial No.
MODEL :
CIMR-J7AA20P1
SPEC : 20P10
INPUT : AC3PH 200-230V 50/60Hz 1.1A
OUTPUT : AC3PH 0-230V 0-400Hz 0.8A 0.3 kVA
LOT NO :
SER NO :
MASS : 0.5 kg
PRG :
FILE NO. : E131457
IP20
INSTALLATION CATEGORY
YASKAWA ELECTRIC CORPORATION JAPAN MS
Mass
Software Number
Model
Inverter
VS mini J7 Series
C I M R J 7 A A 2 0 P 1
No. Type
A
B
C
With Digital Operator (with potentiometer)
Without Digital Operator
With Digital Operator (without potentiometer)
No.
0P1
0P2
0P4
0P7
1P5
2P2
3P0
3P7
Note: Contact your Yaskawa representatives
for models without heatsinks.
No.
A
Specifications
Japan domestic standards
No.
B
2
4
Applicable maximum motor output
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
Voltage Class
Single-phase 200 VAC
Three-phase 200 VAC
Three-phase 400 VAC
Specifications
2 0 P 1 0
B
2
4
Single-phase 200 VAC
Three-phase 200 VAC
Three-phase 400 VAC
No.
0P1
0P2
0P4
0P7
1P5
2P2
3P0
3P7
Applicable maximum motor output
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
No. Protective structure
0 Open chassis(IP20)
19
2. Identifying the Parts
Front Cover
Wiring Holes for
Control Circuit
Digital Operator
Option
Cover
Bottom Cover
Ground
Terminal
Fan Cover
Cooling Fan
Heatsink
Wiring Holes for
Main Circuit
Digital Operator (with potentiometer)
Used for setting or changing constants.
Frequency can be set using potentiometer.
Top Cover
Digital Operator (without potentiometer)
Used for setting or changing constants.
Without Digital Operator
In models without digital operator, only status can be displayed.
Opening the covers
20
Ground Terminal
Input
Polarity
Switch
Short Circuit Bar
Ground Terminal
Short Circuit Bar
Status
Indicators
Status Indicators
Frequency
Setting
Potentiometer
Voltage/Current
Change Switch
Input
Polarity
Switch
Control Circuit
Terminal Block
Main Circuit Terminal Block
Ground Terminal Main Circuit Terminal Block
Frequency
Setting
Potentiometer
Voltage/Current
Change Switch
Control Circuit
Terminal Block
Ground
Terminal
CIMR-J7 ∗∗ 21P5, 22P2, 23P7
B0P7, B1P5
40P2, 40P4, 40P7, 41P5
42P2, 43P0, 43P7
CIMR-J7 ∗∗ 20P1, 20P2, 20P4, 20P7
B0P1, B0P2, B0P4
3. Mounting
3. Mounting
Choosing a Location to Mount the Inverter
Be sure the Inverter is protected from the following conditions.
• Extreme cold and heat. Use only within the specified ambient temperature range:
− 10 to 50 ° C
• Rain and moisture
• Oil sprays and splashes
• Salt spray
• Direct sunlight (Avoid using outdoors.)
• Corrosive gases (e.g., sulfurized gas) or liquids
• Dust or metallic particles in the air
• Physical shock or vibration
• Magnetic noise (Examples: Welding machines, power devices, etc.)
• High humidity
• Radioactive substances
• Combustibles, such as thinner or solvents
21
22
Mounting Dimensions
To mount the VS mini, the dimensions shown below are required.
30 mm or more
30 mm or more
Air
100 mm or more
100 mm or more
Air
Mounting/Removing Components
Removing and Mounting the Digital Operator and Covers
• Removing the Front Cover
Use a screwdriver to loosen the screw on the front cover and then remove it in direction 1.
Then press the right and left sides in direction 2 and lift the front cover in direction 3.
• Mounting the Front Cover
Insert the tab of the upper part of the front cover into the groove of the Inverter, and press the lower part of the front cover onto the plastic case until the cover snaps shut. Then, tighten the screws.
• Removing the Option Cover
After removing the front cover, remove the option cover in direction 2 with section A as a supporting point.
• Mounting the Option Cover
Mount the terminal cover by reversing the order of the above procedure for removal.
• Removing the Upper/Bottom
Covers
After removing the front cover, lift the covers in direction 1.
• Mounting the Upper/Bottom
Covers
Mount the front cover by reversing the order of the above procedure for removal.
3. Mounting
23
4. Wiring
Wiring Instructions
1. Always connect the power supply to the power input terminals R/L1,
S/L2, and T/L3 (R/L1, S/L2 for single-phase power) via a moldedcase circuit breaker (MCCB) or a fuse. Never connect the power supply to terminals U/T1, V/T2, W/T3, − , +1, or +2.
Refer to page 119 for recommended peripheral devices. For singlephase Inverters, always use terminals R/L1 and S/L2. Never connect terminal T/L3.
Inverter Power Supply Connection Terminals
200-V 3-phase Input
Power Supply Specification Inverters
CIMR-J7 2
200-V Single Input
Power Supply Specification Inverters
CIMR-J7 B
400-V 3-phase Input
Power Supply Specification Inverters
CIMR-J7 4
Connect to R/L1,
S/L2, and T/L3.
Connect to R/L1 and
S/L2.
Connect to R/L1,
S/L2, and T/L3.
2. Connect the motor wiring to terminals U/T1, V/T2 and W/T3 on the main circuit output side (bottom of the Inverter)
3. If the wiring distance between Inverter and motor is long, reduce the
Inverter carrier frequency. For details, refer to Reducing Motor
Noise or Leakage Current Using Carrier Frequency Selection (n46) on page 64.
4. Control wiring must be less than 50 m in length and must be separated from the power wiring. Use shielded twisted-pair cable when inputting the frequency signal externally.
5. Tighten the screws on the main circuit and control circuit terminals.
6. Do not connect or disconnect wiring, or perform signal check while the power supply is turned ON.
7. For 400 V Class Inverters, always ground the supply neutral to conform to CE requirements.
8. Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to CE requirements.
24
4. Wiring
9. Closed-loop connectors should be used when wiring to the main circuit terminals.
10.Voltage drop should be considered when determining the wire size.
Voltage drop can be calculated using the following equation:
Phase-to-phase voltage drop (V)
= Ω /km) × wiring distance (m) × current
(A) × 10 -3
Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.
Wire and Terminal Screw Sizes
1. Control Circuits
Model Terminal
Symbols
Common to all models
MA, MB, MC
S1 to S5,
SC, FS, FR,
FC, AM, AC
Screws
M3
M2
Tightening
Torque
N x m
0.5 to 0.6
0.22 to 0.25
Applicable Size mm
2
Twisted wires:
0.5 to 1.25,
Single:
0.5 to 1.25
Twisted wires:
0.5 to 0.75,
Single:
0.5 to 1.25
AWG
20 to 16,
20 to 16
20 to 18,
20 to 16
Wires
Recommended Size mm
2 AWG
0.75
18
0.75
18
Type
Shielded or equivalent
25
Model
CIMR-
J7 ∗ A
20P1
2. Main Circuits
Terminal
Symbols
R/L1, S/L2, T/L3,
-, +1, +2
200 V Class 3-phase Input Inverters
Screws Tightening
Torque
N x m
Applicable Size
M3.5
0.8 to 1.0
mm 2
0.75 to 2
AWG
18 to 14
Wires
Recommended
Size mm 2 AWG
2 14
Type
600 V vinylsheathed or equivalent
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
20P2
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
1.24
(10.97)
0.8 to 1.0
0.75 to 2 18 to 14 2 14
CIMR-
J7 ∗ A
20P4
U/T1, V/T2, W/T3
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
1.24
(10.97)
0.8 to 1.0
0.75 to 2 18 to 14 2
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
20P7
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
1.24
(10.97)
0.8 to 1.0
0.75 to 2 18 to 14 2
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
21P5
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
1.24
(10.97)
0.8 to 1.0
2 to 5.5
14 to 10 2
14
14
14
CIMR-
J7 ∗ A
22P2
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10 3.5
12
CIMR-
J7 ∗ A
23P7
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 5.5
10
26
Note: The wire size is given for copper wire at 75 ° C.
4. Wiring
Model Terminal
Symbols
200 V Class Single-phase Input Inverters
Screws
CIMR-
J7 ∗ A
B0P1
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
Tightening
Torque
N x m
0.8 to 1.0
Applicable Size mm 2
0.75 to 2
AWG
18 to 14
Wires
Recommended
Size mm 2 AWG
2 14
Type
600 V vinylsheathed or equivalent
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
B0P2
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
1.24
(10.97)
0.8 to 1.0
0.75 to 2 18 to 14 2 14
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
B0P4
R/L1, S/L2, T/L3,
-, +1, +2
M3.5
1.24
(10.97)
0.8 to 1.0
0.75 to 2 18 to 14 2 14
U/T1, V/T2, W/T3
CIMR-
J7 ∗ A
B0P7
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
1.24
(10.97)
0.8 to 1.0
2 to 5.5
14 to 10 3.5
12
2 14
CIMR-
J7 ∗ A
B1P5
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10 5.5
10
2 14
Note: 1. The wire size is given for copper wire at 75 ° C.
2. Do not use terminal T/L3 on Inverters with single-phase input.
27
Model Terminal Symbols
400 V Class 3-phase Input Inverters
Screws
CIMR-
J7 ∗ A
40P2
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
Tightening
Torque
N x m
0.8 to 1.0
Applicable Size mm 2
2 to 5.5
AWG
14 to 10
Wires
Recommended
Size mm 2 AWG
2 14
Type
600 V vinylsheathed or equivalent
CIMR-
J7 ∗ A
40P4
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10 2 14
CIMR-
J7 ∗ A
40P7
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10 2 14
CIMR-
J7 ∗ A
41P5
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M3.5
0.8 to 1.0
2 to 5.5
14 to 10 2 14
CIMR-
J7 ∗ A
42P2
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M4 1.2 to 1.5
2 to 5.5
14 to 10 2 14
CIMR-
J7 ∗ A
43P0
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M4
CIMR-
J7 ∗ A
43P7
R/L1, S/L2, T/L3,
-, +1, +2, U/T1,
V/T2, W/T3
M4
1.2 to 1.5
2 to 5.5
14 to 10 2
1.2 to 1.5
3.5
2 to 5.5
14 to 10 2
14
12
14
3.5
12
Note: The wire size is given for copper wire at 75 ° C.
28
4. Wiring
Wiring the Main Circuits
R S T
MCCB or
Leakage
Breaker
[Example of 3-phase,
200 V Class, 1.5 kW Inverters]
Ground
• Main Circuit Input Power Supply
Always connect the power supply line to input terminals R/L1, S/L2, and T/L3 (R/L1, S/
L2 for single-phase Inverters). Never connect them to terminals U/T1, V/T2, W/T3, B1,
B2, − , +1, or +2. The Inverter may be damaged if the wrong terminals are connected.
NOTE
For single-phase Inverters, always use terminals R/L1 and S/L2. Never connect terminal T/L3.
• Grounding (Use ground terminal .)
Always ground the ground terminal according to local grounding codes.
Never ground the VS mini to the same ground as welding machines, motors, or other electrical equipment.
When several VS mini Inverters are used side by side, ground each as shown in examples.
Do not loop the ground wires.
Good Good Poor
29
30
• Inverter Output
Connect the motor terminals to U/T1, V/T2, and W/T3.
• Wiring the Main Circuit Terminals
Pass the cables through wiring hole to connect them. Always mount the cover in its original position.
Connect with a Phillips screwdriver.
4. Wiring
Wiring the Control Circuits
Only basic insulation is provided for the control circuit terminals.
Additional insulation may be necessary in the end product.
• Control Circuit Terminals
Pass the cable through wiring hole to connect it. Always mount the cover in its original position.
SW7 can be changed according to sequence input signal (S1 to S5) polarity.
0 V common: NPN side (Initial setting)
+24 V common: PNP side
Refer to page 115 for SW7.
Refer to page 75 for SW8.
Wiring the Control Circuit Terminals Screwdriver Blade Width
0.4 mm max
2.5 mm max
5.5 mm
Insert the wire into the lower part of the terminal block and connect it tightly with a screwdriver.
The wire sheath strip length must be 5.5 mm.
31
32
Open the front cover and verify that the strip length is 5.5 mm.
Scale
Wiring Inspection
After completing wiring, check the following.
• Wiring is proper.
• Wire clippings or screws are not left in the Inverter.
• Screws are securely tightened.
• Bare wires in the terminals do not contact other terminals.
NOTE
If the FWD (or REV) RUN command is given when the RUN command from the control circuit terminal is selected (n02 =
1), the motor will start automatically after the main circuit input power supply is turned ON.
5. Operating the Inverter
5. Operating the Inverter
Test Run
The Inverter operates when a frequency (speed) is set.
There are three operating modes for the VS mini:
1. RUN command from the Digital Operator (potentiometer/digital setting)
2. RUN command from the control circuit terminals
3. RUN command from MEMOBUS communications
Prior to shipping, the Inverter is set up to receive the RUN command and frequency reference from the Operator. Below are instructions for running the VS mini using the Digital Operator (with potentiometer).
For instructions on operation, refer to page 41.
Operation reference or frequency reference constants can be selected separately as shown below.
Name
RUN
Command
Selection
Frequency
Reference
Selection n02 n03
Constant
= 0 --- Enables run, stop, and reset from Digital Operator.
= 1 --- Enables run and stop from control circuit terminals.
= 2 --- Enables MEMOBUS communications.
= 0 --- Enables the Digital Operator’s potentiometer setting.
= 1 --- Enables Frequency Reference 1 (constant n21).
= 2 --- Enables a voltage reference (0 to 10 V) of control circuit terminal.
= 3 --- Enables a current reference (4 to 20 mA) of control circuit terminal.
= 4 --- Enables a current reference (0 to 20 mA) of control circuit terminal.
= 6 --- Enables MEMOBUS communications.
33
Operation Steps
1. Turn the potentiometer fully counterclockwise, and then turn the power ON.
Operator
Display
0.0
Function
Indicators
Status
Indicators
RUN
ALARM
2. F/R will flash.
Select FWD or REV RUN using the keys.
(Forward) or
NOTE
Never select REV when reverse run is prohibited.
(Reverse)
F/R
RUN
ALARM
3. Press DSPL to make FREF flash. Then press RUN.
0.0
RUN
ALARM
4. Operate the motor by turning the potentiometer clockwise. (A frequency reference corresponding to the potentiometer position will be displayed.)
0.0 to 60.0
(min
-1
)
Minimum output frequency is 1.5 Hz.
NOTE
If the potentiometer is switched rapidly, the motor also accelerates or decelerates rapidly in proportion to the potentiometer movement. Pay attention to load status and switch the potentiometer at a speed that will not adversely affect motor movement.
Status indicators : ON : Flashing : OFF
Operation Check Points
• Motor rotates smoothly.
• Motor rotates in the correct direction.
• Motor does not have abnormal vibration or noise.
• Acceleration and deceleration are smooth.
• Current matching the load flows.
• Status indicators and Digital Operator display are correct.
RUN
ALARM
34
5. Operating the Inverter
Operating the Digital Operator
All functions of the VS mini are set using the Digital Operator. Below are descriptions of the display and keypad sections.
Digital Operator
Status indicators
Data display section
Function indicators
Indicators switch to another function each time DSPL is pressed.
The displayed data can be changed.
Press to switch between functions.
Press to enter the constant data.
(Displays the constant data when selecting a constant No.
for PRGM indicator.)
Press to decrease constant No./data value.
Press to increase constant No./data value.
Frequency setting potentiometer
Used to change frequency setting.
Press to run the motor.
Press to stop the motor.
(Press to reset faults.)
Details of Indicators (Color in parenthesis indicates the color of indicator.)
FREF
Frequency reference setting/monitoring
(GREEN)
F/R
Operator RUN command FWD/REV selection
(GREEN)
FOUT
Output frequency monitoring
(GREEN)
IOUT
Output current monitoring
(GREEN)
LO/RE
LOCAL/REMOTE
Selection
(RED)
MNTR
Multi-function monitoring
(GREEN)
PRGM
Constant No./data
(RED)
35
36
Description of Status Indicators
There are two status indicators on the middle right section of the face of the VS mini. The combinations of these indicators indicate the status of the Inverter (ON, flashing, and OFF). RUN indicator and status indicator on RUN button have the same function.
:ON :Flashing (long flashing) :Flashing :OFF
The following table shows the relationship between the Inverter conditions and the indicator on the RUN button of the Digital Operator as well as the RUN and ALARM indicators on the face of the VS mini.
The indicators are lit, unlit or flashing reflecting the order of priority.
Priority
Digital
Operator
(Optional)
RUN
Face of the VS mini
RUN ALARM
Conditions
1
Power supply is shut down.
Until the Inverter become ready after the power is turned ON.
Fault
2
3
4
5
Emergency stop (STOP command is sent from the
Digital Operator when the control circuit terminals were used to operate the Inverter.)
Emergency stop (Emergency stop alarm is sent from the control circuit terminal.)
Note: Indicators will be the same as with alarm
(stopped) occurring after the Inverter is stopped.
Emergency stop (Emergency stop fault is sent from the control circuit terminal.)
Note: Indicators will be the same as with fault occurring after the Inverter is stopped.
Alarm (Stopped)
6
Alarm (Operating)
The RUN command is carried out when the External baseblock command using the multi-function contact input terminal is issued.
Stopped (During baseblock)
7
8
9
Operating (Including the status that the Inverter is operating at a frequency below the minimum output frequency.)
During dynamic braking when starting.
During deceleration to a stop
During dynamic braking when stopping.
For details on how the status indicators function for Inverter faults, refer to Chapter 8. Fault Diagnosis . If a fault occurs, the ALARM indicator will light.
5. Operating the Inverter
NOTE
The fault can be reset by turning ON the FAULT RESET signal (or by pressing the key on the Digital Operator) with the operation signal OFF, or by turning OFF the power supply. If the operation signal is ON, the fault cannot be reset using the FAULT RESET signal.
37
38
Function Indicator Description
By pressing on the Digital Operator, each of the function indicators can be selected.
The following flowchart describes each function indicator.
Power ON
Frequency reference setting/monitoring
(Hz)
Sets VS mini operating speed.
Output frequency monitoring (Hz)
Displays frequency that VS mini is currently outputting.
Setting disabled.
Output current monitoring (A)
Displays current that VS mini is currently outputting.
Setting disabled.
Multi-function monitoring
Description of the selected monitor is displayed.
(Refer to pages 39 for details.)
FWD/REV run selection
Sets the motor rotation direction when the RUN command is given from the Digital Operator.
Setting can be changed using the or key.
(forward run) (reverse run)
If the VS mini loses power while in one of these modes, it will return to the same mode once power is restored.
Monitor No.
U01: Frequency reference (FREF)
U02: Output frequency (FOUT)
U03: Output current (IOUT)
U04: Output voltage reference (Unit: 1V)
U05: DC voltage (Unit: 1V)
U06: Input terminal status
U07: Output terminal status
U09: Fault history
U10: Software number
U15: Data reception error
5. Operating the Inverter
LOCAL/REMOTE Selection
This function switches the operation; operation using the digital operator including frequency setting with potentiometer, or that using the input terminals, or through communications
Setting can be changed using the or key.
(Local) (Remote)
Constant No./data
Sets and changes data for a constant No.
(Refer to page 41.)
If the VS mini is stopped after it has changed to any of these modes during operation, it changes to Program mode from Drive mode.
Even if the Run command is turned ON again, the VS mini does not operate.
However, if n01=5, the
Run command can be received and the
VS mini will operate.
Return to
WARNING
If n01=5, a Run command can be received even while changing a constant. If sending a Run command while changing a constant, such as during a test run, be sure to observe all safety precautions.
Failure to observe this warning may result in injury.
MNTR Multi-function Monitoring
Selecting the Monitor
Press the DSPL key. When selecting the monitor number.
MNTR is ON, data can be displayed by
Example: Monitoring the Output Voltage Reference
IOUT
DSPL
Select U04 by pressing
or key.
DSPL
MNTR
ENTER
MNTR
DSPL
Output voltage reference is displayed.
or ENTER
F/R
39
40
Monitoring
The following items can be monitored using U constants.
Constant
No.
U01
U02
U03
U04
U05
U06
U07
U09
U10
U15
Name
Frequency Reference
(FREF)
Output Frequency
(FOUT)
Output Current (IOUT)
Output Voltage
DC Voltage
Input Terminal Status
Output Terminal Status
Fault History
Software No.
Data Reception Error
Unit
Hz
Hz
A
-
-
-
V
V
-
-
Input/Output Terminal Status
Input terminal status
Description
Frequency reference can be monitored. (Same as
FREF)
Output frequency can be monitored.
(Same as FOUT)
Output current can be monitored.
(Same as IOUT)
Output voltage can be monitored.
Main circuit DC voltage can be monitored.
Input terminal status of control circuit terminals can be monitored.
Output terminal status of control circuit terminals can be monitored.
The last four fault history records are displayed.
Software number can be checked.
Contents of MEMOBUS communication data reception error can be checked.
(Contents of transmission register No. 003DH are the same.)
Output terminal status
1: Terminal S1 is closed.
1: Terminal S2 is closed.
1: Terminal S3 is closed.
1: Terminal S4 is closed.
1: Terminal S5 is closed.
Not used
1: Terminal MA-MC is closed.
Not used
5. Operating the Inverter
Fault History Display Method
Fault description is displayed when U09 is selected.
(Example)
: Fault description
“---” is displayed if there is no fault.
(Refer to page 97 for details.)
Clearing the Fault History
Set constant n01 to 6 to clear the fault history. Set data returns to its initial value after 6 is set.
Note: Initializing the constants (n01=8, 9) also clears the fault history.
Setting and Referencing Constants
The following diagram shows how to select and change constants.
LO/RE
REMOTE/LOCAL selection
DSPL • Setting n02 (RUN command selection)
PRGM
Constant
No./ data
DSPL
PRGM n02
RUN command selection
ENTER
PRGM
Initial setting: 0 operator reference
PRGM
ENTER
Set to 1
Control circuit terminal reference
(flashing at changing)
FREF
PRGM
Return to constant No.
display
After
1 s
PRGM
Data set
Simple Data Setting
Digital setting (refer to 5. Operating the Inverter ) and potentiometer setting are both possible for simple acceleration/deceleration operation of the VS mini.
Frequency reference by potentiometer signal is set with initial setting
(n03=0).
Factory setting of the model with operator (without potentiometer) is set by Digital Operator (n03=1).
41
Following is an example in which the function LEDs are used to set frequency reference, acceleration time, deceleration time, and motor direction.
Operation Steps
1. Turn ON the power supply.
Operator
Display
0.0
Function
Indicators
Status
Indicators
FREF
RUN
ALARM
2. Set constant n03 to 1.
1
PRGM
RUN
ALARM
3. Set the following constants.
n16: 15.0 (Acceleration Time) n17: 5.0 (Deceleration Time)
4. Select forward or reverse run by pressing the or key.
NOTE
Examine the application. (Never select REV when reverse run is prohibited.)
15.0
5.0
(Forward) or
(Reverse)
PRGM
FR
RUN
ALARM
RUN
ALARM
5. Set the reference by pressing the
key.
6. Press .
or 60.0
FREF
RUN
ALARM
FOUT
RUN
ALARM
7. Press to stop.
Status indicators :ON
60.0 to 0.0
RUN
FOUT
RUN
ALARM
:Flashing (long flashing) :Flashing :OFF
42
6. Programming Features
6. Programming Features
Factory settings of the constants are shaded in the tables.
After wiring is complete, be sure to make the following settings before operation.
Hardware
Make the following settings before the Inverter is turned ON.
Ref.
115
75
Item
Sequence input signal (S1 to S5) polarity selection
Voltage reference / current reference input selection of control circuit terminal FR
Software (Constant)
Environment setting
Item
Constant Selection / Initialization (n01)
RUN Command Selection (n02)
Frequency Reference Selection (n03)
Stopping Method Selection (n04)
Basic characteristics and frequency reference setting
V/f pattern setting (n09 to n15)
Acceleration Time 1 (n16),
Deceleration Time 1 (n17)
Frequency Reference 1 to 8
(n21 to n28)
Motor protection Motor Rated Current (n32)
Electric Thermal Motor Protection
Selection (n33)
Carrier Frequency Reference (n46) Countermeasure for noise and leakage current,
Using an optional braking resistor
51
81
81
64
Ref.
44
49
50
67
45
55
43
44
Constant Setup and Initialization
Constant Selection/Initialization (n01)
The following table lists the data that can be set or read when n01 is set.
Unused constants between n01 and n79 are not displayed.
6
7
8 n01 Setting Constant That Can Be Set Constant That Can Be Referenced
0 n01 n01 to n79
1 n01 to n79
*1
5 n01 to n79 *1
(Run command can be received in Program mode.)
Fault history cleared
Not used
Initialize
9 Initialize (3-wire sequence)
*2
* 1. Excluding setting-disabled constants.
* 2. Refer to page 70.
NOTE
appears on the display for one second and the set data returns to its initial values in the following cases.
1. If the set values of input terminal function selection 2 to 5
(n36 to n39) are the same.
2. If the following conditions are not satisfied in the V/f pattern setting:
Max. Output Frequency (n09) ≥ Max. Voltage Output
Frequency (n11)
> Mid. Output Frequency
(n12)
≥ Min. Output Frequency
(n14)
For details, refer to Adjusting Torque According to Application (V/f Pattern Setting) on page 45.
3. If the following conditions are not satisfied in the jump frequency settings:
Jump Frequency 2 (n50) ≤ Jump Frequency 1 (n49)
6. Programming Features
4. If the Frequency Reference Lower Limit (n31) ≤ Frequency Reference Upper Limit (n30)
5. If the Motor Rated Current (n32) ≤ 120% of Inverter rated current
Selecting V/f Pattern
Adjusting Torque According to Application
Adjust motor torque by using the V/f pattern and full-range automatic torque boost settings.
V/f Pattern Setting
Set the V/f pattern in n09 to n15 as described below. Set each pattern when using a special motor (e.g., high-speed motor) or when requiring special torque adjustment of the machine.
V: (VOLTAGE) n10 n13 n15 n14 n12 n11 n09 f
(FREQUENCY)
Be sure to satisfy the following conditions for the settings of n09 to n15.
n14 ≤ n12 < n11 ≤ n09
If n14 = n12, the setting of n13 will be disabled.
Constant
No.
n09 n10
Name
Max. Output Frequency
Max. Voltage n11
Unit
0.1 Hz
1 V
Setting Range
50.0 to 400 Hz
1 to 255 V (1 to 510 V)
0.2 to 400 Hz
Initial
Setting
60.0 Hz
200 V
(400 V)
60.0 Hz n12 n13 n14 n15
Max. Voltage Output Frequency (Base Frequency)
Mid. Output Frequency
Mid. Output Frequency
Voltage
Min. Output Frequency
Min. Output Frequency
Voltage
0.1 Hz
0.1 Hz
1 V
0.1 Hz
1 V
1 to 399 Hz
1 to 255 V (1 to 510 V)
0.1 to 10.0 Hz
1 to 50 V (1 to 100 V)
1.5 Hz
12 V
(24 V)
1.5 Hz
12 V
(24 V)
45
46
Typical Setting of the V/f Pattern
Set the V/f pattern according to the application as described below. For
400-V Class Inverters, the voltage values (n10, n13, and n15) should be doubled. When running at a frequency exceeding 50/60 Hz, change the
Maximum Output Frequency (n09).
Note: Always set the maximum output frequency according to the motor characteristics.
1. For General-purpose Applications
V
200
12
Motor Specification: 60 Hz
(Factory setting)
1.5
60 f
Constant n09 n10 n11 n12 n13 n14 n15
Setting
60.0
200.0
60.0
1.5
12
1.5
12
Motor Specification: 50 Hz
V
200
12
1.3
50 f
Constant n09 n10 n11 n12 n13 n14 n15
Setting
50.0
200.0
50.0
1.3
12
1.3
12
2. For Fans/Pumps
V
200
50
10
Motor Specification: 60 Hz
1.5
30 60 f
Constant n09 n10 n11 n12 n13 n14 n15
Setting
60.0
200.0
60.0
30.0
50
1.5
10
Motor Specification: 50 Hz
V
200
50
10
1.3
25 50 f
Constant Setting n09 n10 n11 n12 n13 n14 n15
50.0
200.0
50.0
25.0
50
1.3
10
3. For Applications Requiring High Starting Torque
V
200
24
18
Motor Specification: 60 Hz
1.5
3 60 f
Constant n09 n10 n11 n12 n13 n14 n15
Setting
60.0
200.0
60.0
3.0
24
1.5
18
Motor Specification: 50 Hz
V
200
24
18
1.3
2.5
50 f
Constant Setting n09 n10 n11 n12 n13 n14 n15
50.0
200.0
50.0
2.5
24
1.3
18
Increasing the voltage of the V/f pattern increases motor torque, but an excessive increase may cause motor overexcitation, motor overheating, or vibration.
6. Programming Features
When operating with frequency larger than 60 Hz/50 Hz, change only max. output frequency (n09).
Constant
Torque
Constant
Output or
Variable Output n10
=200 V
Base Point n11=60 Hz n09=90 Hz
Full-range Automatic Torque Boost
The motor torque requirement changes according to load conditions.
The full-range automatic torque boost adjusts the voltage of the V/f pattern according to requirements. The VS mini automatically adjusts the voltage during constant-speed operation, as well as during acceleration.
The required torque is calculated by the Inverter.
This ensures tripless operation and energy-saving effects.
Output voltage Torque compensation gain (n63) Required torque
Operation
V
(Voltage)
Required torque Increase voltage f (Frequency)
Normally, no adjustment is necessary for the Torque Compensation
Gain (n63 factory setting: 1.0). When the wiring distance between the
Inverter and the motor is long, or when the motor generates vibration, change the automatic torque compensation gain. In these cases, set the
V/f pattern (n09 to n15).
47
Switching LOCAL/REMOTE Mode
The following functions can be selected by switching LOCAL or
REMOTE mode. To select the RUN/STOP command or frequency reference, change the mode in advance depending on the following applications.
• LOCAL mode: Enables the Digital Operator for RUN/STOP commands and FWD/REV RUN commands. The frequency reference can be set using the potentiometer or .
• REMOTE mode: Enables RUN Command Selection (n02). The frequency reference can be set by n03 (frequency reference selection) setting.
How to Select LOCAL/REMOTE Mode
When LOCAL/REMOTE switching function is not set for multi-function input selection
(When 17 is not set for any of constants n36 to n39)
When LOCAL/REMOTE switching function is set for multi-function input selection
(When 17 is set for any of constants n36 to n39)
Select Lo for operator
LO/RE selection.
Select rE for operator
LO/RE selection.
Turn ON multifunction input terminal.
Turn OFF multifunction input terminal.
LOCAL mode REMOTE mode
48
6. Programming Features
Selecting RUN/STOP Commands
Refer to Switching LOCAL/REMOTE Mode (page 48) to select either the LOCAL mode or REMOTE mode.
The operation method (RUN/STOP commands, FWD/REV RUN commands) can be selected using the following method.
LOCAL Mode
When Lo (local mode) is selected for Digital Operator ON mode, or when the LOCAL/REMOTE switching function is set and the input terminals are turned ON, run operation is enabled by the
on the Digital Operator, and FWD/REV is enabled by the
ON mode (using or key).
or
is not effective when local/remote switching function is selected for multi-function input selection.
REMOTE Mode
1. Select remote mode.
There are following two methods to select remote mode.
• Select rE (remote mode) for the selection.
• When the local/remote switching function is selected for the multi-function input selection, turn OFF the input terminal to select remote mode.
2. Select the operation method by setting constant n02.
n02 =0: Enables the Digital Operator (same with local mode).
=1: Enables the multi-function input terminal (see fig. below).
=2: Enables communications (refer to page 83) (When option
card is installed).
• Example when using the multi-function input terminal as operation reference (two-wire sequence)
FWD RUN/STOP
REV RUN/STOP n02: 1 (Initial setting: 0) n36: 2
For an example of three-wire sequence, refer to page 70.
49
50
Operating (RUN/STOP Commands) Using Communications
(When Option Card is Installed)
Setting constant n02 to 2 in REMOTE mode enables using RUN/STOP commands via MEMOBUS communications. For commands using
MEMOBUS communications, refer to page 83.
Selecting Frequency Reference
Frequency reference can be selected by the following methods.
Setting by Operator
Select REMOTE or LOCAL mode in advance. For the method for selecting the mode, refer to page 48.
LOCAL Mode
Select command method using constant n07.
n07=0: Enables using the potentiometer on the Digital Operator
(initial setting).
The factory setting for models with the Digital Operator
(without a potentiometer) is n07=1.
=1: Enables digital setting on the Digital Operator, setting value is
stored in constant n21 (frequency reference 1).
• Digital Setting Using the Digital Operator
Input the frequency while FREF is lit (press ENTER after setting the numeric value).
Frequency reference setting is effective when 1 is set for constant n08 instead of pressing ENTER.
n08 =0: Enables frequency reference setting using the ENTER key
(initial setting).
=1: Disables frequency reference setting using the ENTER key.
REMOTE Mode
Select the command method in constant n03.
n03 =0: Enables frequency reference setting using the potentiometer
on the Digital Operator (initial setting).
Factory setting of models with the Digital Operator (without a
potentiometer) is n03=1.
=1: Enables using frequency reference 1 (n21)
=2: Enables a voltage reference. (0 to 10 V) (See the following
figure.)
=3: Enables current reference. (4 to 20 mA) (Refer to page 75.)
=4: Enables current reference. (0 to 20 mA) (Refer to page 75.)
6. Programming Features
=6: Enables communications. (Refer to page 83.)
Example of frequency reference by voltage signal
IM
Master Speed
Frequency
Reference
2 k Ω
(0 to +10 V)
FS (Frequency Setting Power
+12 V 20 mA)
FR
FC (0 V) n03 : 2
(Factory setting: 0)
Setting Operation Conditions
Reverse Run Prohibit (n05)
The Reverse Run Prohibit setting disables accepting a reverse RUN command from the control circuit terminal or Digital Operator. This setting is used for applications where a reverse RUN command can cause problems.
Setting
0
1
Description
Reverse run enabled.
Reverse run disabled.
Multi-step Speed Selection
Up to 16 speed steps (including Jog frequency reference) can be set using the following combinations of frequency reference and input terminal selections.
8-step speed change
n02=1 (Operation mode selection) n03=1 (Frequency reference selection) n21=25.0 Hz (Frequency reference 1) n22=30.0 Hz (Frequency reference 2) n23=35.0 Hz (Frequency reference 3) n24=40.0 Hz (Frequency reference 4) n25=45.0 Hz (Frequency reference 5) n26=50.0 Hz (Frequency reference 6) n27=55.0 Hz (Frequency reference 7) n28=60.0 Hz (Frequency reference 8)
NOTE
When all multi-function reference inputs are OFF, the frequency reference selected by constant n03 (frequency reference selection) becomes effective.
n36=1 n37=6 (Multi-function contact input terminal S3) n38=7 (Multi-function contact input terminal S4) n39=8 (Multi-function contact input terminal S5)
FWD
RUN/STOP
REV
RUN/STOP
MULTI-STEP
SPEED REF 1
MULTI-STEP
SPEED REF 2
MULTI-STEP
SPEED REF 3
S1
S2
S3
S4
S5
SC n36=2 (Input terminal S2) Initial Setting n37=6 (Input terminal S3) Change the setting to 6.
n38=7 (Input terminal S4) Change the setting to 7.
n39=8 (Input terminal S5) Change the setting to 8.
51
52
(n28) 60.0 Hz
(n27) 55.0 Hz
(n25) 45.0 Hz
(n24) 40.0 Hz
(n23) 35.0 Hz
(n26) 50.0 Hz
(n22) 30.0 Hz
(n21) 25.0 Hz
Frequency reference
Time
FWD (REV) RUN/STOP
Multi-step speed ref. 1
(terminal S3)
Multi-step speed ref. 2
(terminal S4)
Multi-step speed ref. 3
(terminal S5)
Operating at Low Speed
By inputting a JOG command and then a FORWARD (REVERSE)
RUN command, operation is enabled at the jog frequency set in n29.
When multi-step speed references 1, 2, 3 or 4 are input simultaneously with the JOG command, the JOG command has priority.
Constant No.
n29 n36 to n39
Name
Jog Frequency
Setting
Initial setting: 6.0 Hz
Jog References Set to 10 for any constant.
6. Programming Features
Adjusting Speed Setting Signal
The relationship between the analog inputs and the frequency reference can be set to provide the frequency reference by analog input of control circuit terminal FR or FC.
Frequency Reference
Max. Output Frequency
Gain
100
Max. Output Frequency
Bias
100
(4 mA)
(0 mA)
(20 mA)
(20 mA)
( ) indicates the value when a current reference input is selected.
• Frequency reference gain (n41)
The analog input voltage value for the max. output frequency (n09) can be set in units of 1% (max. output frequency n09=100%).
* Factory setting: 100%
• Frequency reference bias (n42)
The frequency reference provided when analog input is 0 V (4 mA or 0 mA) can be set in units of 1% (max. output frequency n09=100%).
* Factory setting: 0%
Typical Settings
• To operate the Inverter with a frequency reference of 50% to
100% at an input voltage of 0 to 5 V
Max. frequency (100 %)
Gain n41 = 200
Bias n42 = 0
53
• To operate the Inverter with a frequency reference of 50% to
100% at an input voltage of 0 to 10 V
Max. frequency (100 %)
0 V 10 V
Gain n41 = 100
Bias n42 = 50
Adjusitng Frequency Upper and Lower Limits
Internal frequency reference
Frequency
Upper Limit
(n30)
Frequency
Lower Limit
(n31)
Set frequency reference
• Frequency Reference Upper Limit (n30)
Sets the upper limit of the frequency reference in units of 1%.
(n09: Max. Output Frequency = 100%)
Factory setting: 100%
• Frequency Reference Lower Limit (n31)
Sets the lower limit of the frequency reference in units of 1%.
(n09: Max. Output Frequency = 100%)
When operating at a frequency reference of
0, operation is continued at the frequency reference lower limit.
However, if the frequency reference lower limit is set to less than the Minimum Output
Frequency (n14), operation is not performed.
Factory setting: 0%
54
6. Programming Features
Using Two Acceleration/Deceleration Times
Output
Frequency
Accel
Time 1
(n16)
Decel
Time 1
(n17)
Accel
Time 2
(n18)
Decel
Time 2*
(n19)
Decel
Time 1*
(n17)
Time
FORWARD (REVERSE)
RUN command
Multi-Step
Speed Reference
Accel/Decel
Time Selection
(Terminals S2 to S5) (See note.)
ON
ON
ON
* When deceleration to a stop is selected (n04 = 0).
By setting input terminal function selection (either of n36 to n39) to 11
(acceleration/deceleration time select), the acceleration/deceleration time is selected by turning ON/OFF the acceleration/deceleration time selection terminals (terminals S2 to S5).
At OFF: n16 (Acceleration Time 1) n17 (Deceleration Time 1)
At ON: n18 (Acceleration Time 2) n19 (Deceleration Time 2)
• Acceleration time
Set the time needed for the output frequency to reach 100% from 0%.
• Deceleration time
Set the time needed for the output frequency to reach 0% from 100%.
(Max. Output Frequency n09 = 100%)
55
56
Momentary Power Loss Ridethrough Method (n47)
When constant n47 is set to 1 or 2, operation automatically restarts even if a momentary power loss occurs.
Setting
0
Description
Continuous operation after momentary power loss not enabled.
1 *1 Continuous operation after power recovery within momentary power loss ridethrough time
2
*1, *2 Continuous operation after power recovery
(Fault output not produced.)
* 1. Hold the operation signal to continue operation after recovery from a momentary power loss.
* 2. When 2 is selected, the Inverter restarts if power supply voltage recovers while the control power supply is held.
No fault signal is output.
S-curve Selection (n20)
To prevent shock when starting and stopping the machine, acceleration/ deceleration can be performed using an S-curve pattern.
Setting
0
1
2
S-curve Selection
S-curve characteristic not provided.
0.2 s
0.5 s
3 1.0 s
Note: The S-curve characteristic time is the time from acceleration/deceleration rate 0 to the normal acceleration/deceleration rate determined by the set acceleration/deceleration time.
Frequency
Reference
Output
Frequency
Output
Frequency
Time
S-curve Characteristic Time (Tsc)
6. Programming Features
The following time chart shows switching between FWD/REV run when decelerating to a stop.
FORWARD RUN Command
REVERSE RUN Command
Acceleration
Deceleration
MIN. OUTPUT FREQUENCY n53 n14
DC Injection Braking
Time at Stop
Output Frequency
Min. Output
Frequency n14
S-curve Characteristics in Acceleration
Deceleration
Torque Detection
If an excessive load is applied to the machine, an increase in the output current can be detected to output an alarm signal to multi-function output terminal MA or MB.
To output an overtorque detection signal, set one of the output terminal function selection n40 for overtorque detection (Setting: 6 (NO contact) or 7 (NC contact)).
Motor Current n60
Time
Multi-function output signal
(overtorque detection signal)
Terminal MA or MB n61 n61
* The overtorque detection release width (hysteresis) is set at approx. 5% of the Inverter rated current.
57
58
Overtorque Detection Function Selection (n59)
Setting
0
1
2
Description
Overtorque detection not provided.
Detected during constant-speed running. Operation continues after detection.
Detected during constant-speed running. Operation stops during detection.
3
4
Detected during running. Operation continues after detection.
Detected during running. Operation stops during detection.
1. To detect overtorque during acceleration/deceleration, set n59 to 3 or 4.
2. To continue operation after overtorque detection, set n59 to 1 or 3.
During detection, the operator will display an alarm (flashing).
3. To stop the Inverter and generate a fault at overtorque detection, set n59 to 2 or 4. At detection, the Digital Operator will display an
(ON).
fault
Overtorque Detection Level (n60)
Set the overtorque detection current level in units of 1%. (Inverter rated current = 100%)
Factory setting: 160%
Overtorque Detection Time (n61)
If the time that the motor current exceeds the Overtorque Detection
Level (n60) is longer than Overtorque Detection Time (n61), the overtorque detection function will operate.
Factory setting: 0.1 s
6. Programming Features
Frequency Detection Level (n58)
Effective when the Multi-function Output Selection n40 is set for frequency detection (setting: 4 or 5). Frequency detection turns ON when the output frequency is higher or lower than the setting for the Frequency Detection Level (n58).
Frequency Detection 1
Output frequency ≥ Frequency Detection Level n58 (Set n40 to 4.)
Frequency Detection
Level [Hz] (n58)
Release
Width
− 2Hz
Output
Frequency
Frequency
Detection
Signal
Frequency Detection 2
Output frequency ≤ Frequency Detection Level n58 (Set n40 to 5.)
Output
Frequency
Release
Width
+2Hz
Frequency
Detection
Level (Hz)
(n58)
Frequency
Detection
Signal
59
60
Jump Frequencies (n49 to n51)
This function allows the prohibition or “jumping” of critical frequencies so that the motor can operate without resonance caused by the machine system. This function is also used for dead band control. Setting the values to 0.00 Hz disables this function.
Set prohibited frequency 1 or 2 as follows:
Output Frequency n49 n50 n51 n51 n49
≥
n50
If this condition is not satisfied, the Inverter will display for one second and restore the data to initial settings.
Frequency Reference
Operation is prohibited within the jump frequency ranges.
However, the motor will operate without jumping during acceleration/ deceleration.
Continuing Operation Using Automatic Retry Attempts (n48)
The Inverter can be set to restart and reset fault detection after a fault occurs. The number of self-diagnosis and retry attempts can be set to up to 10 in n48. The Inverter will automatically restart after the following faults occur:
OC (overcurrent)
GF (ground fault)
OV (overvoltage)
The number of retry attempts is cleared to 0 in the following cases:
1. If no other fault occurs within 10 minutes after retry
2. When the FAULT RESET signal is ON after the fault is detected
3. When the power supply is turned OFF
6. Programming Features
Operating a Coasting Motor without Tripping
To operate a coasting motor without tripping, use the SPEED SEARCH command or DC injection braking at startup.
SPEED SEARCH Command
Restarts a coasting motor without stopping it. This function enables smooth switching between motor commercial power supply operation and Inverter operation.
Set a Multi-function Input Selection (n36 to n39) to 14 (SEARCH command from maximum output frequency) or 15 (SEARCH command from set frequency).
Build a sequence so that a FWD (REV) RUN command is input at the same time as the SEARCH command or after the SEARCH command.
If the RUN command is input before the SEARCH command, the
SEARCH command will be disabled.
Time Chart at SEARCH Command Input
FWD (REV) RUN Command
SEARCH Command
Max. Output Frequency or
Frequency Reference at
RUN Command Input
Output Frequency
Min. Baseblock
Time (0.5 s)
Speed Agreement
Detection
Speed
Search
Operation
DC Injection Braking at Startup (n52, n54)
Restarts a coasting motor after stopping it. Set the DC injection braking time at startup in n54 in units of 0.1 second. Set the DC Injection Braking Current in n52 in units of 1% (Inverter rated current =100%). When the setting of n54 is 0, DC injection braking is not performed and acceleration starts from the minimum output frequency.
When n52 is set to 0, acceleration starts from the minimum output frequency after baseblocking for the time set in n54.
Min. Output
Frequency n14 n54
DC Injection Braking
Time at Startup
61
62
Holding Acceleration/Deceleration Temporarily
To hold acceleration or deceleration, input an ACCELERATION/
DECELERATION HOLD command. The output frequency is maintained when an ACCELERATION/DECELERATION HOLD command is input during acceleration or deceleration.
When the STOP command is input while an ACCELERATION/
DECELERATION PROHIBITION command is being input, the acceleration/deceleration hold is released and operation ramps to a stop.
Set a Multi-function Input Selection (n36 to n39) to 16 (acceleration/ deceleration prohibit).
Time Chart for ACCELERATION/DECELERATION HOLD
Command Input
FWD (REV)
RUN Command
ACCELERATION/
DECELERATION
HOLD Command
Frequency
Reference
Output
Frequency
FREQUENCY
AGREE
Signal
Note: If a FWD (REV) RUN command is input at the same time as an
ACCELERATION/DECELERATION HOLD command, the motor will not operate. However, if the Frequency Reference Lower Limit (n31) is set to a value greater than or equal to the Min. Output Frequency (n14), the motor will operate at the Frequency Reference Lower Limit (n31).
6. Programming Features
Using Frequency Meter or Ammeter (n44)
Select to output either output frequency or output current to analog output terminals AM-AC for monitoring.
Setting
0
Description
Output frequency
1 Output current
In initial setting, analog voltage of approx. 10 V is output when output frequency (output current) is 100%.
Frequency Meter
Output Frequency
(Output Current)
100 %
AM FM
Analog monitor gain can be set by n45.
0 to 10 VDC
AC
0
3 V
Analog Output
10 V
Calibrating Frequency Meter or Ammeter (n45)
Used to adjust analog output gain.
(
Frequency Meter/Ammeter
3 V 1 mA Full-scale )
Output Frequency
(Output Current) n45 = 0.30
100%
Factory Setting n45 = 1.00
n45
AM
FM
AC
0
3 V 10 V
Analog Output
Set the analog output voltage at 100% of output frequency (output current).
Frequency meter displays 0 to 60 Hz at 0 to 3 V.
10 V × n45 setting
0.30
= 3 V
Output frequency becomes
100 % at this value.
63
64
Reducing Motor Noise or Leakage Current Using Carrier Frequency Selection (n46)
Set the Inverter output transistor switching frequency (carrier frequency).
Setting Carrier Frequency Metallic Noise from Motor
Noise and Current Leakage
2
3
9
1
7
8
12 fout (Hz)
24 fout (Hz)
36 fout (Hz)
2.5 (kHz)
5.0 (kHz)
7.5 (kHz)
Higher
Not audible
Smaller
Larger
4 10.0 (kHz)
If the set value is 7, 8, or 9, the carrier frequency will be multiplied by the same factor as the output frequency.
n46=7 fc=Carrier Frequency
2.5 kHz fc=12 fout
1.0 kHz fout=Output Frequency
83.3 Hz 208.3 Hz fc=Carrier Frequency n46=8 fc=24 fout
2.5 kHz
1.0 kHz fout=Output Frequency n46=9
41.6 Hz 104.1 Hz fc=Carrier Frequency
2.5 kHz fc=36 fout
1.0 kHz fout=Output Frequency
27.7 Hz 69.4 Hz
6. Programming Features
The factory setting depends on the Inverter capacity (kVA).
Voltage
Class (V)
200 V
Singlephase or
3-phase
400 V
3-phase
NOTE
Capacity
(kW)
3.7
0.2
0.4
0.75
0.1
0.2
0.4
0.75
1.5
2.2
1.5
2.2
3.0
3.7
3
3
3
3
3
3
3
3
4
4
3
3
Initial Setting
Setting Carrier Frequency (kHz)
4
4
10
10
10
10
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
7.5
Maximum
Continuous
Output Current (A)
17.5
1.2
1.8
3.4
0.8
1.6
3.0
5.0
8.0
11.0
4.8
5.5
7.2
8.6
Reduced
Current
(A)
-
1. Reduce the continuous output current when changing the carrier frequency to 4 (10 kHz) for 200 V Class (1.5 kW or more) and 400 V Class Inverters. Refer to the table above for the reduced current.
Operation Condition
• Input power supply voltage:
3-phase 200 to 230 V (200 V Class)
Single-phase 200 to 240 V (200 V Class)
3-phase 380 to 460 V (400 V Class)
• Ambient temperature:
− 10 to 50 ° C
(Protection structure: open chassis type IP20)
4.0
4.8
6.3
7.6
7.0
10.0
16.5
1.0
1.6
3.0
65
66
2. If the wiring distance is long, reduce the Inverter carrier frequency as described below.
Wiring Distance between Inverter and Motor
Carrier Frequency
(n46 setting)
Up to 50 m Up to 100 m
10 kHz or less
(n46=1, 2, 3, 4, 7,
8, 9)
5 kHz or less
(n46=1, 2, 7, 8, 9)
More than
100 m
2.5 kHz or less
(n46=1, 7, 8, 9)
3. The carrier frequency is automatically reduced to 2.5 kHz when the Reducing Carrier Frequency Selection at Low
Speed (n75) is set to 1 and the following conditions are satisfied:
Output frequency ≤ 5 Hz
Output current ≥ 110%
Factory setting: 0 (Disabled)
Operator Stop Key Selection (n06)
Set the processing when the STOP key is “pressed” during operation either from a multi-function input terminal or communications.
Setting
0
1
Description
The STOP key is effective either from a multifunction input terminal or communications. When the STOP key is pressed, the Inverter stops according to the setting of constant n04. At this time, the Digital Operator displays a alarm
(flashing). This STOP command is held in the
Inverter until both forward and reverse RUN commands are open, or until the RUN command from communications goes to zero.
The STOP key is ineffective either from multifunction input terminals or communications.
6. Programming Features
Selecting the Stopping Method
Stopping Method Selection (n04)
Select the stopping method suitable for the application.
Setting
0
1
Description
Deceleration to a stop
Coast to a stop
Deceleration to a Stop
Example when acceleration/deceleration time 1 is selected
Output
Frequency
Acceleration
Time 1
(n16)
Deceleration
Time 1 Deceleration
(n17) Time 1 (n17)
Min. OutputFrequency
(Frequency at
DC Injection Braking
Startup) n14
(Factory Setting: 1.5 Hz)
FWD (REV)
RUN
Command
Time
DC Injection Braking
Time at Stop (n53)
(Factory Setting: 0.5 s)
* Changing the Frequency Reference while Running
Upon termination of a FWD (REV) RUN command, the motor decelerates at the deceleration rate determined by the time set in Deceleration
Time 1 (n17) and DC injection braking is applied immediately before stopping. DC injection braking is also applied when the motor decelerates because the frequency reference is set lower than the Min. Output
Frequency (n14) when the FWD (REV) RUN command is ON. If the deceleration time is short or the load inertia is large, an overvoltage
(OV) fault may occur at deceleration. In this case, increase the deceleration time.
67
68
Coast to a Stop
Example when Acceleration/deceleration Time 1 is selected
Output
Frequency
Acceleration
Time 1
(n16)
Deceleration
Time 1
(n17) Coast to stop
Time
FWD (REV)
RUN Command
* Changing the Frequency Reference while Running
Upon termination of the FWD (REV) RUN command, the motor starts coasting.
Applying DC Injection Braking
DC Injection Braking Current (n52)
Sets the DC injection braking current in units of 1%. (Inverter rated current=100%)
DC Injection Braking Time at Stop (n53)
Sets the DC injection braking time at stopping in units of 0.1 second.
When the setting of n53 is 0, DC injection braking is not performed, but the Inverter output is turned OFF when DC injection braking is started.
n14 Min.
Output
Frequency n53
DC Injection Braking
Time at Stop
When coasting to a stop is specified in the Stopping Method Selection
(n04), DC injection braking is not applied when stopping.
6. Programming Features
Building Interface Circuits with External Devices
Using Input Signals
The functions of multi-function input terminals S2 to S5 can be changed as necessary by setting constants n36 to n39. The same value cannot be set for more than one of these constants.
Ref.
70
6
7
8
10
11
Setting
0
2
3
4
5
12
13
14
15
16
17
18
Name
FWD/REV RUN command
(3-wire sequence selection)
REVERSE RUN command
(2-wire sequence selection)
External fault,
NO contact input
External fault,
NC contact input
Fault reset
Description
Setting possible only for n37.
Inverter stops for an external fault signal input. Digital
Operator displays EF
Resets a fault. Fault reset not effective when the RUN signal is ON.
*.
Multi-step speed reference 1
Multi-step speed reference 2
Multi-step speed reference 3
JOG command
Acceleration/deceleration time selection
External baseblock,
NO contact input
External baseblock,
NC contact input
SEARCH command from maximum frequency
SEARCH command from set frequency
ACCELERATION/
DECELERATION HOLD command
LOCAL/REMOTE selection
Communications/control circuit terminal selection
Motor coasts to a stop for this signal input. Digital
Operator displays .
SPEED SEARCH command signal
49
-
-
-
-
-
61
61
62
48
73
51
51
51
52
55
69
70
Setting
19
20
21
22
34
35
Name
Emergency stop fault,
NO contact input
Emergency stop alarm,
NO contact input
Emergency stop fault,
NC contact input
Emergency stop alarm,
NC contact input
UP/DOWN commands
Self-test
Description
Inverter stops for an emergency stop signal input according to the Stopping
Method Selection (n04).
When frequency coasting to a stop (n04 is set to 1) is selected, the Inverter coasts to a stop according to
Deceleration Time Setting 2
(n19).
Digital Operator displays
. (Lit for fault, flashing for alarm.)
Setting enabled only for n39
(terminal S5)
Setting enabled only for n39
(terminal S5)
Set to one of 1, 9, 23 to 33 if a terminal is not used.
Ref.
-
-
-
-
-
72
1, 9, 23 to 33
Not used -
* Numbers 2 to 5 are displayed for to indicate the terminal numbers S2 to
S5.
Initial Settings
No.
n36 n37 n38 n39
Terminal
S2
S3
S4
S5
Initial Setting
2
5
3
6
Function
REVERSE RUN command (2wire sequence)
Fault reset
External fault (NO contact input)
Multi-step speed reference 1
Terminal Functions for 3-wire Sequence Selection
When 0 is set for terminal S3 (n37), terminal S1 is the RUN command, terminal S2 is the STOP command, and terminal S3 is the FWD/REV
RUN command.
RUN SW
STOP SW
(NC Contact)
(NO Contact)
VS mini
RUN Command
(Run when closed)
STOP Command
(Stop when open)
FWD/REV RUN Selection
FWD run when open
REV run when closed
6. Programming Features
WARNING
To select the 3-wire sequence, set terminal S3 (n37) to
0.
Failure to observe this warning may result in injury.
LOCAL/REMOTE Selection (Setting: 17)
Select the operation reference from either the Digital Operator or from the settings of the RUN Command Selection (n02) and Frequency Reference Selection (n03). The LOCAL/REMOTE Selection can be used only when stopped.
Open: Run according to the setting of RUN Command Selection
(n02) or Frequency Reference Selection (n03).
Closed: Run according to the frequency reference and RUN command from the Digital Operator.
Example: Set n02=1, n03=2, n07=0.
Open: Run according to the frequency reference from multi-function input terminal FR and RUN command from multi-function input terminals S1 to S5.
Closed: Run according to the potentiometer frequency reference and
RUN command from the Digital Operator.
UP/DOWN Commands (Setting: n39 = 034)
When the FWD (REV) RUN command is ON, acceleration/deceleration is enabled by inputting the UP or DOWN signal from multi-function input terminals S4 and S5 without changing the frequency reference.
Operation can thus be performed at the desired speed. When UP/
DOWN commands are specified in n39, any function set in n38 is disabled, terminal S4 is the input terminal for the UP command, and terminal S5 is the input terminal for the DOWN command.
Closed Open Open Closed Multi-function Input Terminal S4 (UP command)
Multi-function Input Terminal S5 (DOWN command)
Operation Status
Open Closed Open Closed
Acceleration
Deceleration
Hold Hold
71
FWD RUN
UP Command S4
DOWN Command S5
Upper Limit Speed
Lower Limit Speed
Output Frequency
FREQUENCY Agree
Signal
Time Chart for UP/DOWN Command Input
72
U = UP (accelerating) status
D = DOWN (decelerating) status
H = HOLD (constant speed) status
U1 = UP status, clamping at upper limit speed
D1 = DOWN status, clamping at lower limit speed
Note: 1. When UP/DOWN commands are selected, the upper limit speed is set regardless of frequency reference.
Upper limit speed =Maximum Output Frequency (n09)
× Frequency Reference Upper Limit (n30)/100%
2. Lower limit value is either the Minimum Output Frequency (n14) or
Maximum Output Frequency (n09) × Frequency Reference Lower
Limit (n31)/100% (whichever is larger.).
3. When the FWD (REV) RUN command is input, operation starts at the lower limit speed without using the UP/DOWN commands.
4. If the JOG command is input while running for an UP/DOWN command, the JOG command has priority.
5. Multi-step speed references 1 to 3 are not effective when an UP/
DOWN command is selected. Multi-step speed references are effective while running in hold status.
6. When 1 is set for the HOLD Output Frequency Memory Selection
(n62), the output frequency can be recorded during HOLD.
Setting Description
0
1
Output frequency is not recorded during
HOLD.
When HOLD status is continued for 5 seconds or longer, the output frequency during HOLD is recorded and the Inverter restarts at the recorded frequency.
Communications/Multi-function Input Terminal Selection
(Setting: 18)
(This function is effective when option card is installed.)
Operation can be changed from communications commands, or from multi-function input terminal or Digital Operator commands.
RUN commands from communications and the frequency reference are effective when the multi-function input terminal for this setting is closed.
RUN commands in LOCAL/REMOTE mode and the frequency reference are effective when the terminal is open.
Using Output Signals (n40)
The functions of multi-function output terminals MA and MB can be changed as necessary by setting constants n40.
• Terminal MA and MB functions: Set to n40
Setting
0 Fault
1
2
3
4
5
6
Name
Operating
Frequency agree
Zero speed
Frequency detection 1
Frequency detection 2
6. Programming Features
Description
Closed when Inverter fault occurs.
Closed when either FWD/REV command is input or voltage is output from the Inverter.
Closed when the set frequency agrees with Inverter output frequency.
Closed when Inverter output frequency is less than minimum output frequency.
Output frequency ≥ Frequency
Detection Level (n58)
Output frequency ≤ Frequency
Detection Level (n58)
-
Ref.
-
-
74
-
59
59
57
7
8, 9
Overtorque detection,
NO contact output
Overtorque detection,
NC contact output
Not used
57
-
10 Minor fault
Set to one of 8 or 9 if a terminal is not used.
Closed when an alarm has been detected.
-
73
74
Setting
11
12
13
14
15
16
17
18
Name
Base blocked
Description
Closed when the Inverter output is OFF.
Operating mode
Inverter operation ready Closed when an Inverter fault is not detected, and operation is ready.
Fault restart Closed during fault retries.
UV
Closed when LOCAL is selected for the LOCAL/REMOTE selection.
Reverse run
Speed search
Closed when undervoltage is detected.
Closed during reverse run.
Data output from communications
Closed when Inverter conducts a speed search.
Operates multi-function output terminal independently from Inverter operation (by MEMOBUS communications)
Ref.
-
-
-
-
-
-
-
83
No.
n40
Initial Settings
Terminal
MA, MB
Initial Setting
1 (operating)
• FREQUENCY AGREE Signal (setting=2)
Release Width
± 4 Hz
Detection width
± 2 Hz
Output Frequency
FREQUENCY AGREE Signal
6. Programming Features
Setting Frequency by Current Reference Input
When setting frequency by inputting current reference (4-20 mA or
0-20 mA) from the control circuit terminal FR, switch the DIP switch SW8 on the control circuit board to “I” side.
SW8 is accessed by removing the option cover.
SW8
SW8
V I
NOTE
Never input voltage reference to control circuit terminal FR when DIP switch SW8 is switched to “I” side.
75
76
Current Reference Selection
After changing DIP switch (V/I switch of SW8) to the “I” side, press
on the Digital Operator, then set the following constants.
4-20 mA.....n03=3
0-20 mA.....n03=4
• Setting: n02=0, n03=3 or 4
IM
Press the Digital Operator keys to run or stop the Inverter. Switch run and stop direction by setting
F/R LED.
Current
Reference
4-20 mA or
0-20 mA
(n03 =
3 or 4)
FS
FR
FC
Set frequency by the analog current signal [0-100% (max. frequency)/4-20 mA or 0-20 mA] connected to the control circuit terminal.
• Setting: n02=1, n03=3 or 4
FWD RUN/STOP
REV RUN/STOP
Current
Reference
4-20 mA or
0-20 mA
(n03 =
3 or 4)
S1
S2
SC
FS
FR
FC
IM
Switch run/stop and FWD/REV run with switching device connected to the control circuit terminal.
Multi-function input terminal S2 is set to Reverse run/stop (n36=2).
Set frequency by the analog current signal [0-100% (max. frequency)/4-20 mA or 0-20 mA] connected to the control circuit terminal.
Frequency reference gain (n41)/bias (n42) can be set even when current reference input is selected. For details, refer to Adjusting Speed Setting
Signal on page 53.
6. Programming Features
Preventing the Motor from Stalling (Current
Limit)
This function automatically adjusts the output frequency and output current according to the load to continue operation without stalling the motor.
Stall Prevention (Current Limit) Level during Acceleration
(n56)
Sets the stall prevention (current limit) level during acceleration in units of 1%. (Inverter rated current = 100%)
Factory setting: 170%
A setting of 200% disables the stall prevention (current limit) during acceleration. If the output current exceeds the value set for n56 during acceleration, acceleration stops and the frequency is maintained. When the output current goes to the value set for n56, acceleration starts.
Motor Current n56
Output
Frequency
*2
Time
* 1 : Stops the acceleration to prevent the motor
* 2 : Release width (hysteresis) of stall prevention during accel is approx. 5% of inverter rated current
Time
*1
77
In the constant output area (output frequency > Max. Voltage Output
Frequency (n11)), the stall prevention (current limit) level during acceleration is automatically decreased using the following equation.
Stall prevention (current limit) level during acceleration in constant output area
Stall prevention (current limit) level during acceleration (n56)
Max. voltage output frequency (n11)
Output frequency
Stall Prevention Level during Acceleration
Stall Prevention Level during
Acceleration (n56)
Stall Prevention Limit during
Acceleration (40% of n56)
Output Frequency
Maximum Voltage
Output Frequency n11
Stall Prevention (Current Limit) Level while Running (n57)
Sets the stall prevention (current limit) level while running in units of
1%. (Inverter rated current = 100%)
Factory setting: 160%
A setting of 200% disables stall prevention (current limit) while running.
If the stall prevention action current at speed agreement exceeds the value set for n57 for longer than 100 ms, deceleration starts.
If the output current exceeds the value set for n57, deceleration continues. If the output current goes to the value set for n57, acceleration to the set frequency starts.
Stall prevention acceleration/deceleration settings during operation are set either for the currently selected Acceleration Time, i.e., for Acceler-
78
6. Programming Features ation Time 1 (n16) and Deceleration Time 1 (n17), or for Acceleration
Time 2 (n18) and Deceleration Time 2 (n19).
Motor Current n57
Output
Frequency
* 2
Time
* 1 : Decreases frequency to prevent the motor
* 2 : At start of acceleration, the output current hysterisis is approx. 5% of Inverter rated
current.
100ms
Time
*1
• Stall Prevention (Current Limit) during Deceleration (n55)
To prevent overvoltage during deceleration, the Inverter automatically extends the deceleration time according to the value of main circuit DC voltage.
Controls the deceleration time to prevent overvoltage fault.
Setting
0
1
Stall Prevention
(Current Limit) during Deceleration
Provided
Not provided
Set
Decel
Time
Time
79
80
Decreasing Motor Speed Fluctuation
Slip Compensation
As the load becomes larger, the motor speed is reduced and the motor slip value is increased. The slip compensating function controls the motor speed at a constant value even if the load varies.
When the Inverter output current is equal to the Motor Rated Current
(n32), the compensation frequency is added to the output frequency.
Compensation frequency = Motor rated slip (n64)
Output current − Motor no-load current (n65)
×
Motor rated current (n32) − Motor no-load current (n65)
× Slip compensation gain (n66)
Related Constants
Constant
No.
n32
Name Unit Setting Range Initial
Setting
* n64 n65
Motor Rated Current
Motor Rated Slip
Motor No-load Current
0.1 A 0% to 120% of Inverter rated current
0.1 Hz 0.0 to 20 Hz
1% 0% to 99% (100%=Motor Rated Current n32)
0.1
0.0 to 2.5
*
* n66 Slip Compensation
Gain
0.0
n67 Slip Compensation
Time Constant
0.1 s 0.0 to 25.5 s
When 0.0 s is set, delay time is 2.0 s.
2.0 s
* Depends on Inverter capacity.
Note: 1. Slip compensation is not performed under the following condition:
Output frequency < Minimum Output Frequency (n14)
2. Slip compensation is not performed during regeneration.
3. Slip compensation is not performed when the Motor Rated Current
(n32) is set to 0.0 A.
6. Programming Features
Motor Protection
Motor Overload Detection
The VS mini protects against motor overload with a built-in electronic thermal overload relay.
Motor Rated Current (Electronic Thermal Reference Current, n32)
Set the rated current value shown on the motor nameplate.
Note: Setting n32 to 0.0 A disables the motor overload protective function.
Motor Overload Protection Selection (n33, n34) n33
Setting
0
1
2
Electronic Thermal Characteristics
For general-purpose motor
For Inverter motor
Electronic thermal overload protection not provided.
Constant
No.
Name Unit Setting Range Initial
Setting n34 Protection Constant
Selection
1 min 1 to 60 min 8 min
The electronic thermal overload function monitors the motor temperature based on Inverter output current and time to protect the motor from overheating. When the electronic thermal overload relay is enabled, an
error occurs, and the Inverter output is turned OFF to prevent excessive overheating in the motor. When operating with one Inverter connected to one motor, an external thermal relay is not needed. When operating more than one motor with one Inverter, install a thermal relay on each motor.
81
82
General-purpose Motors and Inverter Motors
Induction motors are classified as general-purpose motors or Inverter motors based on their cooling capabilities. The motor overload function operates differently for these two motor types.
Example for 200 V-Class Motors
Cooling Effect Torque Characteristics
Effective when operated at 50/
60 Hz from commercial power supply.
Torque
(%)
60 s
Short-term
Continuous
Rating
Electronic Thermal Overload error
(motor overload protection) occurs when continuously operated at 50/60 Hz or less at 100% load.
Effective even when operated at low speed
(approx. 6 Hz)
Operation Frequency (Hz)
Base Frequency 60 Hz
(V/f for 60-Hz, 220-V Input Voltage)
For low-speed operation, torque must be limited in order to stop motor temperature rise.
Torque
(%)
60 s
Short-term
Continuous
Rating
Electronic thermal overload protection is not activated even for continuous operation at 50/60 Hz or less at 100% load.
Operation Frequency (Hz)
Base Frequency 60 Hz
(V/f for 60-Hz, 220-V Input Voltage)
Use an Inverter motor for continuous operation at low speed.
6. Programming Features
Selecting Cooling Fan Operation
In order to increase the life of the cooling fan, the fan can be set to operate only when Inverter is running n35 = 0 (Initial setting): Operates only when Inverter is running
(Continues operation for 1 minute after
Inverter is stopped.)
=1: Operates with power ON
Using MEMOBUS (MODBUS) Communications
Serial communication is available with VS mini using programmable controller (MEMOCON series) and MEMOBUS. In order to perform serial communications, RS-485/422 interface card (optional) must be installed.
Refer to MEMOBUS Instruction Manual (Manual No.: TOEZ-C736-
70.1) for details of communications.
MEMOBUS (MODBUS) Communications
MEMOBUS system is composed of a single master (PLC) and slaves (1 to 31 VS-mini units).
Communication between master and slave (serial communication) is controlled according to the master program with the master initiating communication and the slave responding.
The master sends a signal to one slave at a time. Each slave has a preregistered address No., and the master specifies the number and conduct signal communications. The slave receives the communication to carry out designated functions and reply to the master.
MEMOCON Series
VS mini J7 VS mini J7 VS mini J7
Example of RS-485 communication
83
84
Communications Specifications
Interface
Synchronization
Communication
Parameters
RS-422, RS-485
Asynchronous (Start-stop synchronization)
Baud rate: Selected from 2400/4800/9600/19200 bps
Data length: 8 bits fixed
Parity: Selected from even/odd/none
Stop bits: 1 bit fixed
MEMOBUS (MODBUS) (RTU mode only) Communication
Protocol
Max. Number of
Inverters that can be
Connected
31 units (When using RS-485)
Using Constant Copy Function
Constant Copy Function
The Digital Operator for remote operation (Model JVOP-146, Optional) can store constants for one Inverter. A backup power supply is not necessary because EEPROM is used.
Note: When using a Digital Operator for remote operation, use with a remote interface unit for remote operation (optional) and the cable for remote operation (optional). Refer to the VS mini J7 catalog (Literature No.
KAE-S606-12) for details.
The constant copy function is possible only for the Inverters with the same product series and power supply specifications. However, some constants may not be copied. It is also impossible to copy constants between VS mini and VS-606V7 Inverters.
Prohibiting reading constants from the Inverter can be set in n77. The constant data cannot be changed when this constant is set.
If an alarm occurs when copying constants, PRGM will flash and copying will continue.
Constant Copy Function Selection (n76)
Depending on the setting of n76 (Constant Copy Function Selection), the following functions can be used.
1. Reading all the constants from the Inverter (READ) and storing them in EEPROM in the Digital Operator
2. Copying the constants stored in the Digital Operator to the Inverter
(COPY)
6. Programming Features
3. Verifying that the constants in the Digital Operator and the constants in the Inverter are the same (VERIFY)
4. Displaying the maximum applicable motor capacity and the voltage class of the Inverter for which constants are stored in the Digital
Operator
5. Displaying the software number of the Inverter for which constants are stored in the Digital Operator
Constant
No.
n76
Name
Constant
Copy Function Selection
Unit Setting Range Initial
Setting rdy rdy: READY rEd: READ
CPy: COPY vFy: VERIFY vA: Inverter capacity display
Sno: Software No. display
Prohibiting Constant Read Selection (n77)
Select this function to prevent accidentally overwriting the constants stored in EEPROM or in the Digital Operator. Reading is not possible when this constant is set to 0.
The constant data stored in the Digital Operator are safe from accidental overwriting.
If reading is attempted while this constant is set to 0, PrE will flash.
Press DSPL or ENTER and return to the constant No. display.
Constant
No.
n77
Name
Constant
Read Selection Prohibit
Unit
1
Setting Range
0: READ prohibited
1: READ allowed
Initial
Setting
0
85
READ Function
Reads out the constants in batch from the Inverter and stores them in
EEPROM inside the Digital Operator. When the read-out is executed, the previously stored constants data in the EEPROM are cleared and replaced with the newly entered constants.
Example: Storing Constants from Inverter in EEPROM in Operator.
Explanation
• Enable the setting of constants n01 to n79.
• Press DSPL to light
[PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
ENTER.
Operator Display
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.)
• Set Constant Read Prohibited Selection (n77) to read-enabled.
*1
• Change the constant No. to n77 by pressing the
• Press ENTER to display the set value.
• Change the set value to 1 by pressing the or key.
ENTER.
(Lit)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.) read-out using the Constant Copy
Function Selection (n76).
• Change the constant No. by pressing the or key.
• Press ENTER to display the set value.
• Change the set value to rEd by pressing the or
key.
• Press DSPL or ENTER.
(Lit)
(Lit)
(Flashes while executing the read)
↓
(End is displayed after the read has been completed.)
(The constant No. is displayed.)
86
6. Programming Features
Explanation
• Set Constant Read Prohibited Selection (n77) to read-disabled.
*2
• Change the constant No. to n77 by pressing the
Operator Display
• Press ENTER to display the set value.
• Change the set value to 0 by pressing the or key.
ENTER.
(Lit)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.)
Note: 1. When reading is enabled (n77=1), this setting is not necessary.
2. This setting is not necessary unless read-prohibition is selected.
COPY Function
This function writes the constants stored inside the Digital Operator in batch to the Inverter. Write-in is possible only for Inverters with the same product series and power supply specifications.
Therefore, writing from 200 V Class to 400 V Class Inverters (or vice versa), from V/f control mode to vector control mode Inverters (or vice versa), or from VS mini to VS-606V7 Inverters are not possible.
The Constant Copy Function Selection (n76), Constant Read Selection
Prohibit (n77), Fault History (n78), Software Version No. (n79), and hold output frequency are not written. vAE will appear (flashing) if the capacities of the Inverters differ.
Press ENTER to continue writing (the COPY function).
Press STOP/RESET to stop the COPY function.
The following constants are not written if the Inverter capacities differ.
Constant No.
n09 to n15 n32 n46
Name
V/f Settings
Motor Rated Current
Carrier Frequency
Selection
Constant No.
n64 n65
Name
Motor Rated Slip
Motor No-load
Current
87
Example: Writing Constants from EEPROM in Operator to Inverter
Explanation Operator Display
• Enable the settings for constants n01 to n79.
• Press DSPL to light
[PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
ENTER.
(May be a different constant No.)
(Lit)
(May be a different set value.)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.) write-in
(COPY) using the Constant Copy Function
Selection (n76).
• Change the constant No. to n76 by pressing the
• Press ENTER to display the set value.
• Change the set value to
CPy by pressing the or
key.
(Lit)
(Lit)
(Flashes while executing the copy.)
↓
(End is displayed after the copy has been completed.)
(The constant No. is displayed.) • Press DSPL or ENTER.
A setting range check and matching check for the written constants are executed after the constants are written from the Digital Operator to the
Inverter. If a constant error is found, the written constants are discarded and the constants stored before writing are restored.
When a setting range error is found, the constant No. where an error occurs is indicated by flashing.
When an inconsistency in the settings is found, is indicated by flashing.
( : a number)
88
6. Programming Features
VERIFY Function
This function compares the constants stored in the Digital Operator with the constant in the Inverter. Verification is possible only for the Inverters with same product series and power supply specifications.
When the constants stored in the Digital Operator are the same as those in the Inverter, vFy will flash, and then End will be displayed.
Example: Comparing Constants Stored in EEPROM in Operator with
Constants in Inverter
Explanation
• Enable the settings for constants n01 to n79.
• Press DSPL to light
[PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
ENTER.
Operator Display
(May be a different constant No.)
(Lit)
(May be a different constant No.)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.)
• Execute VERIFY by
Constant Copy Function
Selection (n76).
• Change the constant No. to n76 by pressing the or
key.
• Press ENTER to display the set value.
• Change the set value to vFy by pressing the or key.
ENTER.
(Lit)
(Lit)
(Flashes while executing VERI-
FY) the constant No.
ent.)
(Flashes) (When n011 is differthe value in the Inverter.
the value in the Digital
Operator.
• Continue the execution of VERIFY.
• Press the key.
(Flashes)
(Flashes)
• Press DSPL or ENTER.
(Flashes while executing the verification)
↓
(End is displayed when the verification has been completed.)
(The constant No. is displayed.)
While a constant No. that is not the same is displayed or a constant value is displayed, press STOP/RESET to interrupt the execution of the verification. End will be displayed. Press DSPL or ENTER to return to the constant No.
89
90
Inverter Capacity Display
The voltage class and maximum applicable motor capacity for which constants are stored in the Digital Operator are displayed.
Example: Displaying Voltage Class and Maximum Applicable Motor
Capacity for Inverter whose Constants are in EEPROM in Operator the for constants n01 to n79.
Explanation
• Press DSPL to light [PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
Operator Display
(May be a different constant No.)
(Lit)
(May be a different constant No.)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.)
Inverter
Capacity Display
(vA) using the Constant Copy Function
Selection (n76).
• Change the constant No. to n76 by pressing the or key.
• Press ENTER to display the set value.
• Change the set value to vA fy by pressing the or key.
(Lit)
(Lit)
• Press DSPL or ENTER.
(Lit) (For 20P7)*
(The constant No. is displayed.)
* The following figure shows the Inverter Capacity Display b
2
4
Voltage Class
Single-phase 200 V
Three-phase 200 V
Three-phase 400 V
1.5
2.2
3.0
3.7
No.
0.1
0.2
0.4
0.7
Max. Applicable Motor Capacity
0.1 kW
0.2 kW
0.4 kW
0.75 kW
1.5 kW
2.2 kW
3.0 kW
3.7 kW
6. Programming Features
Software No. Display
The software number of the Inverter for which constants are stored in the Digital Operator is displayed.
Example: Displaying Software No. of Inverter for which Constants are
Stored in EEPROM in Operator
• Enable the setting for constants n01 to n79.
Explanation
• Press DSPL to light [PRGM].
• Press ENTER to display the set value.
• Change the set value to 4 by pressing the or key.
Operator Display
(May be a different constant No.)
(Lit)
(May be a different constant No.)
(Flashes)
↓
(Lit for one second.)
(The constant No. is displayed.)
Software
Display (Sno)* using the Constant Copy
Function Selection
(n76).
• Change the constant No. to n76 by pressing the or key.
• Press ENTER to display the set value.
• Change the set value to Sno by pressing the or key.
(Lit)
(Lit)
• Press DSPL or ENTER.
(Lit)
(Software version: VSP020011)
(The constant No. is displayed.)
* Displays the lower 3 digits of the software version.
Display List
Operator
Display
Description Corrective Action
Lit: Constant copy function selection enabled.
Lit: READ selected.
Flashes: READ under execution.
Lit: Writing (COPY) selected.
Flashes: Writing (COPY) under execution.
Lit: VERIFY selected.
Flashes: VERIFY under execution.
Lit: Inverter capacity display selected.
-
-
-
-
-
Lit: Software No. display selected.
Lit: READ, COPY (writing), VERIFY completed.
-
-
91
92
Operator
Display
Description Corrective Action
Flashes: Attempt made to execute
READ while Constant Read Selection
Prohibit (n77) is set to 0.
Flashes: The constant could not be read properly for READ operation. Or, a main circuit low voltage is detected during READ operation.
Flashes: A checksum error occurred in the constant data stored in the Digital
Operator.
Confirm the necessity to execute
READ, then set Constant Read Selection Prohibit (n77) to 1 to execute
READ.
Confirm that the main circuit power supply voltage is correct, then re-execute READ.
The constants stored in the Digital Operator cannot be used.
Re-execute READ to store the constants in the Digital Operator.
Check if the Inverters are the same product series.
Flashes: The password for the connected Inverter and that for the constant data stored in the Digital
Operator disagree. Example: Writing
(COPY) from VS mini to VS-606V7
Flashes: No constant data stored in the Digital Operator.
Flashes: Attempt made to execute writing (COPY) or VERIFY between different voltage classes or different control modes.
Execute READ.
Check each voltage class and control mode.
Flashes: A main circuit low voltage was detected during writing (COPY) operation.
Lit: A checksum error occurred in the constant data stored in the Inverter.
Confirm that the main circuit power supply voltage is correct, then re-execute writing (COPY).
Initialize the constants. If an error occurs again, replace the Inverter due to a failure of constant memory element
(EEPROM) in the Inverter.
Flashes: Attempt made to execute
COPY or VERIFY between different
Inverters of different capacities.
Flashes: A communications error occurred between the Inverter and the
Digital Operator.
Press ENTER to continue the execution of COPY or VERIFY. Press STOP to interrupt the execution of COPY or
VERIFY.
Check the connection between the Inverter and Digital Operator.
If a communications error occurs during the READ operation or writing
(COPY) operation, always re-execute the READ or COPY.
Note: While rEd, CPy, or vFy is flashing, key input on the Digital Operator is disabled. While rEd, CPy and vFy are not flashing, pressing DSPL or
ENTER redisplays the constant No.
7. Maintenance and Inspection
7. Maintenance and Inspection
Periodic Inspection
Periodically inspect the Inverter as described in the following table to prevent accidents and to ensure high performance with high reliability.
Location to
Check
Terminals, Inverter mounting screws, etc.
Heatsinks
Printed circuit boards
Power elements and smoothing capacitor
Cooling fan
Check for Solution
Improper seating or loose connections in hardware.
Buildup of dust, dirt, and debris
Accumulation of conductive material or oil mist
Abnormal odor or discoloration
Properly seat and tighten hardware.
Blow with dry compressed air at a pressure of 39.2 × 10 4 to
58.8 × 10
4
Pa, 57 to
85 psi (4 to 6kg/cm 2 ).
Blow with dry compressed air at a pressure of 39.2 × 10 4 to
58.8 × 10 4 Pa, 57 to
2
85 psi (4 to 6kg/cm ).
If dust or oil cannot be removed, replace the
Inverter.
Replace the Inverter.
Abnormal noise or vibration
Cumulative operation time exceeding
20,000 hours
Replace the cooling fan.
93
94
Part Replacement
Inverter’s maintenance periods are given below. Keep them as guidelines.
Part Replacement Guidelines
Part
Cooling fan
Smoothing capacitor
Breaker relays
Standard Replacement
Period
2 to 3 years
5 years
-
Replacement Method
Fuses
Aluminum capacitors on PCBs
10 years
5 years
Note: Usage conditions are as follows:
• Ambient temperature: Yearly average of 30 ° C
• Load factor: 80% max.
• Operating rate: 12 hours max. per day
Replace with new part.
Replace with new part.
(Determine need by inspection.)
Determine need by inspection.
Replace with new part.
Replace board. (Determine need by inspection.)
7. Maintenance and Inspection
Replacement of Cooling Fan
Inverters with Width of 68 mm or 140 mm
1. Removal
1. Press the right and left catches on the fan cover in direction 1, and then pull them in direction
2 to remove the fan cover from the Inverter.
2. Pull the wiring in direction 3 from the fan cover rear face, and remove the protective tube and connector.
3. Open the left and right sides of the fan cover to remove the cooling fan from the cover.
2. Mounting
1. Mount the cooling fan on the fan cover. The arrow mark to indicate the airflow direction of the cooling fan must be on the opposite side to the cover.
2. Connect the connector and mount the protective tube firmly. Mount the connector joint section on the fan cover rear face.
3. Mount the fan cover on the
Inverter. Always mount the right and left catches on the fan cover on the heatsinks.
Airflow Direction
95
96
Inverters with Width of 108 mm
1. Removal
1. Remove the front cover, and then remove the cooling fan connector (CN4).
2. Press the right and left catches on the fan cover in direction 1, and pull the fan cover in direction 2 to remove it from the Inverter.
Pull out the wiring from the cable lead-in hole at the bottom of the plastic case.
3. Open the right and left sides of the fan cover to remove the cover from the cooling fan.
2. Mounting
Cooling
Fan Wire
Cable
Lead-in
Hole
1. Mount the cooling fan on the fan cover. The arrow mark to indicate the airflow direction must be opposite to the cover.
2. Mount the fan cover on the
Inverter. Always mount the right and left catches on the fan cover on the heatsinks.
Thread in the wiring from the cable lead-in hole at the bottom of the plastic case to the inside of the Inverter.
3. Connect the wiring to the cooling fan connector (CN4) and mount the front cover and the terminal cover.
Airflow Direction
8. Fault Diagnosis
8. Fault Diagnosis
Protective and Diagnostic Functions
This section describes the alarm and fault displays, the fault conditions, and the corrective actions to be taken if the VS mini malfunctions.
Corrective Actions of Models without Digital Operator
1. Input fault reset or cycle the power supply OFF and ON.
2. When a fault cannot be corrected:
Turn the power supply OFF and check the wiring and control logic.
Corrective Actions of Models with Digital Operator
: ON : Flashing : OFF
Alarm Displays and Meanings
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and
Corrective Actions
Flashing
Flashing
Flashing
Detected as an alarm only.
Fault contact output is not activated.
UV (Main circuit low voltage)
Main circuit DC voltage dropped below the lowvoltage detection level while the Inverter output is OFF.
200 V: Main circuit DC voltage drops below approx. 200
V (160 V for single-phase)
400 V: Main circuit DC voltage dropped below approx.
400 V.
Check the following:
• Power supply voltage
• Main circuit power supply connection.
• Terminal
Loose?
OV (Main circuit overvoltage)
Main circuit DC voltage exceeded the overvoltage detection level while the Inverter output is OFF.
Detection level
200 V Class: approx. 410 V or more
400 V Class: approx. 820 V or more
Check the power supply voltage.
OH (Heatsink overheat)
Intake air temperature increased while the Inverter output is OFF.
Check the intake air temperature.
97
98
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Flashing
Flashing
Flashing
Flashing
Inverter
Status
Description Causes and
Corrective Actions
Detected as an alarm only.
Fault contact output is not activated.
CAL (MEMOBUS communications waiting)
Correct data has not been received from the PLC when the constants n02
(RUN Command Selection) is 2 or n03 (Frequency Reference Selection) is 6, and power is turned
ON.
Check communications devices and transmission signals.
OP (Constant setting error when constants are set through MEMOBUS communications)
O P1: Two or more values are set for multi-function input selection.
(constants n36 to n39)
OP2: Relationship among V/f constants is not correct. (constants n09, n11, n12, n14)
OP3: Setting value of motor rated current exceeds
120% of Inverter
Rated Current.
(constant n32)
OP4: Upper/lower limit of frequency reference is reversed.
(constants n30, n31)
OP5: Setting values of jump frequencies
1 and 2 are not appropriate.
(constants n49, n50)
Check the setting values.
OL3 (Overtorque detection)
Motor current exceeded the preset value in constant n60.
SER (Sequence error)
Inverter received LOCAL/
REMOTE command or communications/control circuit terminal changing signals from the multifunction terminal while the
Inverter output is ON.
Reduce the load, and increase the acceleration/ deceleration time.
Check the external circuit
(sequence).
8. Fault Diagnosis
Alarm Display
Digital
Operator
RUN (Green)
ALARM (Red)
Flashing
Flashing
Flashing
Flashing
Flashing or
Inverter
Status
Description Causes and
Corrective Actions
Detected as an alarm only.
Fault contact output is not activated.
BB (External baseblock)
BASEBLOCK command at multi-function terminal is ON and the Inverter output is OFF (motor coasting). Condition is cleared when input command is removed.
Check the external circuit
(sequence).
EF (Simultaneous
FWD/REV RUN commands)
When FWD and REV
RUN commands are simultaneously input for over 500 ms, the Inverter stops according to constant n04.
Check the external circuit
(sequence).
STP (Operator function stop)
was pressed during running via a control circuit terminal FWD/REV command, or by a RUN command from communications. The Inverter stops according to constant n04.
STP (Emergency stop)
Inverter received emergency stop alarm signal.
Inverter stops according to constant n04.
FAN (Cooling fan fault)
Cooling fan is locked.
Open FWD/REV command of control circuit terminals.
Check the external circuit
(sequence).
Check the following:
• Cooling tion fan
• Cooling
CE (MEMOBUS communications fault)
Check the communication devices or signals.
99
100
Fault Displays and Meanings
Fault Display Inverter
Status
Description Causes and Corrective Actions
Digital
Operator
RUN (Green)
ALARM (Red)
Protective Operation
Output is turned OFF and motor coasts to a stop.
OC (Overcurrent)
Inverter output current momentarily exceeded approx. 200% of rated current.
(Control power supply fault)
Voltage fault of control power supply is detected.
GF (Ground fault)
*
Ground fault current at the Inverter output exceeded Inverter rated current.
• Short circuit or grounding at Inverter output side
GD
2 rapid
Acceleration/
Deceleration Time
(constants n16 to n19)
• Special motor used
• Starting motor during coasting
• Motor of a capacity greater than the
Inverter rating has been started.
contactor opened/closed at the
Inverter output side
⇓
Check the cause, and restore the operation.
power.
If the fault remains, replace the Inverter.
Note) Before turning the power ON again, make sure that no short-circuit or ground fault occurs at the Inverter output.
• Check that motor insulation has not deteriorated.
• Check the connection between Inverter and motor.
Note) Before turning the power ON again, make sure that no short-circuit or ground fault occurs at the Inverter output.
OV (Main circuit overvoltage)
Main circuit DC voltage exceeded the overvoltage detection level because of excessive regenerative energy from the motor.
Detection level:
200 V: Stop at main circuit DC voltage below approx.
410 V
400 V: Stops at main circuit DC voltage of approx. 820 V or more
• Insufficient
Deceleration Time
(constants n17 and n19) of load (e.g., elevator) time.
⇓ deceleration
* The ground fault here is one which occurs in the motor wiring while the motor is running.
A ground fault may not be detected in the following cases.
• A ground fault with low resistance which occurs in motor cables or terminals.
• A ground fault occurs when the power is turned ON.
8. Fault Diagnosis
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective Actions
Protective Operation
Output is turned OFF and motor coasts to a stop.
UV1 (Main circuit low voltage)
Main circuit DC voltage dropped below the lowvoltage detection level while the Inverter output is ON.
200 V: Stops at main circuit DC voltage below approx. 200
V (160 V for single-phase)
400 V: Stops at main circuit DC voltage of approx. 400 V or more
OH (Heatsink overheat)
Temperature increased because of Inverter overload operation or intake air temperature rise.
of power supply voltage
• Open phase of input supply
• Momentary loss
⇓
Check the following:
• Power supply voltage
• Main circuit power supply connections screws:
Loose?
load
• Improper V/f pattern setting
• Insufficient acceleration time if the fault occurs during acceleration
• Intake air temperature exceeding 50 ° C
OL1 (Motor overload)
Motor overload protection operated by built-in electronic thermal overload relay.
OL2 (Inverter overload)
Inverter overload protection operated by built-in electronic thermal overload relay.
⇓
Check the following: size
• V/f pattern setting
(constants n09 to n15)
• Intake air temperature.
• Check the load size or V/f pattern setting
(constants n09 to n15).
• Set the motor rated current shown on the nameplate in constant n32.
• Check the load size or V/f pattern setting
(constants n09 to n15).
• Check the Inverter capacity.
OL3 (Overtorque detection)
Inverter output current exceeded the preset value in constant n60.
When overtorque is detected, Inverter performs operation according to the preset setting of constant n59.
Check the driven machine and correct the cause of the fault, or increase the value of constant n60 up to the highest value allowed for the machine.
101
102
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red)
Inverter
Status
Description Causes and Corrective Actions
Protective Operation
Output is turned OFF and motor coasts to a stop.
EF (External fault)
Inverter receives an external fault input from control circuit terminal.
E F0: External fault reference through
MEMOBUS communications
EF2: External fault input command from control circuit terminal S2
EF3: External fault input command from control circuit terminal S3
EF4: External fault input command from control circuit terminal S4
EF5: External fault input command from control circuit terminal S5
Check the external circuit
(sequence).
CPF-00
Initial memory fault has detected.
CPF-01
ROM error has detected.
Cycle power.
If the fault remains, replace the Inverter.
Cycle power.
If the fault remains, replace the Inverter.
CPF-04
EEPROM fault of Inverter control circuit was detected.
all data and initialize the constants. (Refer to page 44 for constant initialization.)
• Cycle power. If the fault remains, replace the Inverter.
CPF-05
AD converter fault was detected.
Cycle power.
If the fault remains, replace the Inverter.
CPF-06 card tion fault non-corresponding option card is connected.
Remove power to the Inverter. Check the connection of the Digital
Operator. Verify Software
Version No.
CPF-07
Operator control circuit
(EEPROM or A/D converter) fault
CE (MEMOBUS communications fault)
Normal reception of communication data is not possible.
Cycle power. If the fault remains, replace the Inverter.
Check the communication devices or communication signals.
8. Fault Diagnosis
Fault Display
Digital
Operator
RUN (Green)
ALARM (Red) or
Inverter
Status
Description Causes and Corrective Actions
Stops according to constant
STP (Emergency stop)
The Inverter stopped according to constant n04 after receiving the emergency stop fault signal.
Check the external circuit
(sequence).
(OFF) power supply voltage
• Control power supply fault
Check the following:
• Power supply voltage
• Main circuit power supply connections
• Terminal
Loose?
sequence.
Replace the Inverter.
Note: To display or clear the fault history, refer to page 41.
103
Troubleshooting
Trouble
The motor does not operate when an external operation signal is input.
The motor stops. The torque is not output.
Cause
The operation method selection is wrong.
The run command (n02) is not set to
Control Circuit Terminal .
A 3-wire sequence is in effect.
The multi-function input method (n37) is set to 3-wire sequence, and the S2 control terminal is not closed.
Corrective Actions
Set the run command (n02) to
Control Circuit Terminal.
To use a 3-wire sequence, make the wiring so that the S2 control terminal is closed. To use a 2-wire sequence, set the multi-function input (n37) to a value other than 3-wire sequence.
Input a frequency reference greater than the min. output frequency (n14).
The frequency reference is too low.
The input frequency reference is lower than the setting for the min.output frequency (n14).
Local mode is in effect.
Set the LO/RE selection of the digital operator to RE.
For analog input, make sure that the frequency reference (n03) and SW8 settings are correct.
The SW setting for the reference selection is wrong.
Example: The reference 4-20 mA is input, but the SW is set to “V.”
The setting of NPN/PNP switch
(SW7) is not correct.
The stall prevention level during acceleration is too low.
Because the stall prevention level during acceleration (n56) is set too low, the output current reaches the set level, the output frequency is stopped, and the acceleration time is lengthened.
The stall prevention level during running is too low.
Because the stall prevention level during running (n57) is set too low, the output current reaches the set level, and the speed drops.
The load is too heavy.
If the load is too heavy, stall prevention is activated, the output frequency is stopped, and the acceleration time is lengthened.
When the maximum frequency was changed, the maximum voltage frequency was also changed.
Set SW7 correctly.
Check if the stall prevention level during acceleration (n56) is set to an appropriate value.
Check if the stall prevention level during running (n57) is set to an appropriate value.
• Lengthen the set acceleration time
(n16).
• Reduce the load.
To increase the speed of a generalpurpose motor, only change the maximum frequency.
The V/f set value is too low.
Set the V/f (n09 to n15) according to the load characteristics.
104
8. Fault Diagnosis
Trouble
The motor speed is unstable. The motor speed fluctuates when operating with a light load.
Cause
The stall prevention level during running is too low.
Because the stall prevention level during running (n57) is too low, the output current reaches the set level and the speed drops.
The load is too heavy.
If the load is too heavy, stall prevention is activated, the output frequency is stopped, and the acceleration time is lengthened.
The carrier frequency is too high.
If operating the motor with a light load, a high carrier frequency may cause the motor speed to fluctuate.
The V/f set value is too high for a low speed operation.
Because the set value for the V/f is too high, over-excitation occurs at low speeds.
The maximum frequency and base frequency were incorrectly adjusted.
Example: To operate a 60 Hz motor at
40 Hz or less, the maximum frequency and base frequency are set to 40 Hz.
The Inverter is used for an operation at 1.5 Hz or less.
Corrective Actions
Check if the stall prevention level during running (n57) is set to an appropriate value.
Reduce the load.
Decrease the carrier frequency (n46).
Set the V/f (n09 to n15) according to the load characteristics.
Set the maximum frequency and the base frequency according to the motor specifications.
Do not use the J7 Inverter for an operation that runs at 1.5 Hz or less.
For an operation at 1.5 Hz or less, use a different Inverter model.
Increase the set value for the filter time constant.
The Digital Operator does not turn ON.
The LED of the Digital
Operator is unlit.
The analog reference input is unstable and has noise interference.
The power is not being supplied.
The breaker or other component on the power input side is not turned ON, and the power is not being supplied.
Short-circuit bar for terminals
+1 and +2 is not connected.
Check if the power is being supplied.
Confirm that the short-circuit bar is connected properly.
105
9. Specifications
Standard Specifications (200 V Class)
Voltage Class
Model CIMR-
J7 ∗ A
3-phase
Singlephase
Max. Applicable Motor
Output kW *1
Inverter Capacity
(kVA)
Rated Output
Current (A)
Max. Output
Voltage (V)
Max. Output Frequency (Hz)
Rated Input
Voltage and
Frequency
Allowable Voltage
Fluctuation
Allowable
Frequency
Fluctuation
Control Method
Frequency
Control Range
Frequency
Accuracy (Temperature Change)
Frequency
Setting Resolution
20P1
B0P1
0.1
0.3
0.8
20P2
B0P2
0.2
0.6
1.6
200 V single-/3-phase
20P4
B0P4
20P7
B0P7
21P5
B1P5
3-phase, 200 to 230 V (proportional to input voltage)
3-phase, 200 to 240 V (proportional to input voltage)
400 Hz (Programmable)
3-phase, 200 to 230 V, 50/60 Hz
Single-phase, 200 to 240 V, 50/60 Hz
−
±
15% to +10%
5%
Sine wave PWM (V/f control)
0.1 to 400 Hz
Digital reference: ±
Analog reference: ±
0.4
1.1
3
0.01% ( −
0.75
10 to 50
0.5% (25
1.9
±
5
10 ° C)
°
1.5
3.0
C)
8
22P2
-
2.2
4.2
11
23P7
-
3.7
6.7
17.5
Output Frequency
Resolution
Overload Capacity
Frequency
Reference Signal
Acceleration/
Deceleration Time
Digital reference:
0.1 Hz (less than 100 Hz)/1 Hz (100 Hz or more)
Analog reference: 1/1000 of max. output frequency
0.01 Hz
150% rated output current for one minute
0 to 10 VDC (20 k Ω ), 4 to 20 mA (250 Ω ), 0 to 20 mA (250 Ω ), frequency setting potentiometer (Selectable)
0.0 to 999 s
(Acceleration/deceleration time are independently programmed.)
106
9. Specifications
Voltage Class
3-phase
Model CIMR-
J7 ∗ A Singlephase
Braking Torque
20P1
B0P1
20P2
B0P2
200 V single-/3-phase
20P4
B0P4
20P7
B0P7
21P5
B1P5
V/f Characteristics
Short-term average deceleration torque
*2
0.1, 0.2 kW: 150%
0.4, 0.75 kW: 100%
1.5 kW: 50%
2.2 kW or more: 20%
Continuous regenerative torque: Approx. 20%
Possible to program any V/f pattern
22P2
-
23P7
-
Motor Overload
Protection
Instantaneous
Overcurrent
Overload
Overvoltage
Undervoltage
Momentary Power
Loss
Heatsink Overheat
Stall Prevention
Level
Cooling Fan Fault
Ground Fault
*6
Power Charge Indication
Electronic thermal overload relay
Motor coasts to a stop at approx. 200% of Inverter rated current
Motor coasts to a stop after 1 minute at 150% of Inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 410 V
Stops when DC bus voltage is approx. 200 V or less (approx.
160 V or less for single-phase series).
Following items are selectable: Not provided (stops if power loss is 15 ms or longer), continuous operation if power loss is approx. 0.5 s or shorter, continuous operation.
Protected by electronic circuit.
Can be set individual level during acceleration/deceleration, provided/not provided available during coast to a stop.
Protected by electronic circuit (fan lock detection).
Protected by electronic circuit (rated output current level).
RUN indicator stays ON or Digital Operator indicator stays
ON.
(Charge LED is provided for 400 V.)
ON until the DC bus voltage becomes 50 V or less.
107
108
Voltage Class
3-phase
Model CIMR-
J7 ∗ A Singlephase
Multifunction
Input
Multifunction
Output
Standard
Functions
*3
Status
Indicators
Digital
Operator
Terminals
Wiring Distance between Inverter and Motor
Enclosure
20P1
B0P1
20P2
B0P2
200 V single-/3-phase
20P4 20P7 21P5
B0P4 B0P7 B1P5
22P2
-
23P7
-
Four of the following input signals are selectable: Reverse run
(3-wire sequence), fault reset, external fault (NO/NC contact input), multi-step speed operation, JOG command, acceleration/deceleration time select, external baseblock (NO/NC contact input), SPEED SEARCH command, ACCELERA-
TION/DECELERATION HOLD command, LOCAL/REMOTE selection, communication/control circuit terminal selection, emergency stop fault, emergency stop alarm
Following output signals are selectable (1 NO/NC contact output):
Fault, running, zero speed, frequency agree, frequency detection (output frequency ≤ or ≥ set value), overtorque detection, minor error, baseblock, operating mode, Inverter run ready, fault retry, UV, speed search, data output through communication
Full-range automatic torque boost, slip compensation, DC injection braking current/time at startup/stop, frequency reference bias/gain, frequency reference with built-in potentiometer, [MEMOBUS communications (RS-485/422, max. 19.2K bps) (optional)]
RUN and ALARM provided as standard indicators
Provided for monitor frequency reference, output frequency, output current
Main circuit: screw terminals
Control circuit: plug-in screw terminal
100 m or less
*5
Cooling Method
Open chassis IP20
Cooling fan is provided for the following models:
200 V, 0.75 kW or larger Inverters (3-phase)
200 V, 1.5 kW or larger Inverters (single-phase)
Other models are self-cooling.
Open chassis: − 10 to 50 ° C (not frozen) Ambient
Temperature
Humidity
Storage
Temperature *4
Location
Elevation
Vibration
95% or less (non-condensing)
− 20 to 60 ° C
Indoor (free from corrosive gases or dust)
1,000 m or less
Up to 9.8 m/s up to 2 m/s
2
2
(1G) at less than 20 Hz,
(0.2G) at 20 to 50 Hz
9. Specifications
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.
* 3. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 4. Temperature during shipping (for short period).
* 5. If the wiring distance between Inverter and motor is long, reduce the
Inverter carrier frequency. For details, refer to Reducing Motor Noise or
Leakage Current Using Carrier Frequency Selection (n46) on page 64.
* 6. The ground fault here is one which occurs in the motor wiring while the motor is running. A ground fault may not be detected in the following cases.
• A ground fault with low resistance which occurs in motor cables or terminals.
• A ground fault occurs when the power is turned ON.
Standard Specifications (400 V Class)
Voltage Class
Model CIMR-
J7 ∗ A
3-phase
Max. Applicable Motor
Output kW
*1
Inverter
Capacity (kVA)
Rated Output
Current (A)
Max. Output
Voltage (V)
Max. Output
Frequency (Hz)
Rated Input
Voltage and
Frequency
Allowable
Voltage
Fluctuation
Allowable
Frequency
Fluctuation
40P2
0.2
0.9
1.2
40P4
0.4
1.4
1.8
40P7
0.75
2.6
3.4
400 V 3-phase
41P5
1.5
3.7
4.8
42P2
2.2
4.2
5.5
43P0
3.0
5.5
7.2
3-phase, 380 to 460 V (proportional to input voltage)
400 Hz (Programmable)
3-phase, 380 to 460 V, 50/60 Hz
− 15% to +10%
± 5%
43P7
3.7
6.6
8.6
109
110
Voltage Class
Model CIMR-
J7 ∗ A
3-phase
Control Method
Frequency
Control Range
Frequency
Accuracy
(Temperature
Change)
40P2 40P4
0.1 to 400 Hz
Digital reference: ±
±
40P7
400 V 3-phase
Sine wave PWM (V/f control)
0.01%, −
±
41P5
10 to 50
10 ° C
° C
42P2 43P0 43P7
Frequency
Setting
Resolution
Output
Frequency
Resolution
Overload
Capacity
Frequency
Reference
Signal
Acceleration/
Deceleration
Time
Braking Torque
Digital reference:
0.1 Hz (less than 100 Hz)/1 Hz (100 Hz or more)
Analog reference: 1/1000 of max. output frequency
0.01 Hz
150% rated output current for one minute
0 to 10 VDC (20 k
0.0 to 999 s
Ω ), 4 to 20 mA (250 Ω ), 0 to 20 mA (250
(Acceleration/deceleration time are independently programmed.)
Short-term average deceleration torque *2
0.2 kW: 150%
0.4/0.75 kW: 100%
1.5 kW: 50%
2.2 kW or more: 20%
Continuous regenerative torque: Pyrex. 20%
Possible to program any V/f pattern V/f
Characteristics
Motor Overload
Protection
Electronic thermal overload relay
Ω ), fre-
Instantaneous
Overcurrent
Overload
Motor coasts to a stop at approx. 200% of Inverter rated current
Overvoltage
Undervoltage
Motor coasts to a stop after 1 minute at 150% of Inverter rated output current
Motor coasts to a stop if DC bus voltage exceed 820 V
Stops when DC bus voltage is approx. 400 V or less
9. Specifications
Voltage Class
Model CIMR-
J7 ∗ A
3-phase
Momentary
Power Loss
40P2 40P4 40P7
400 V 3-phase
41P5 42P2 43P0 43P7
Heatsink Overheat
Stall Prevention
Level
Cooling Fan
Fault
Ground Fault *6
Following items are selectable: Not provided (stops if power loss is
15 ms or longer), continuous operation if power loss is approx. 0.5 s or shorter, continuous operation.
Protected by electronic circuit.
Can be set individual levels during acceleration/deceleration, provided/not provided available during coast to a stop.
Protected by electronic circuit (fan lock detection).
Protected by electronic circuit (rated output current level).
Power Charge
Indication
Multifunction
Input
Multifunction
Output *3
Charge LED is provided.
ON until the DC bus voltage becomes 50 V or less.
Four of the following input signals are selectable: Reverse run (3wire sequence), fault reset, external fault (NO/NC contact input), multi-step speed operation, JOG command, acceleration/deceleration time select, external baseblock (NO/NC contact input),
SPEED SEARCH command, ACCELERATION/DECELERATION
HOLD command, LOCAL/REMOTE selection, communication/ control circuit terminal selection, emergency stop fault, emergency stop alarm
Following output signals are selectable (1 NO/NC contact output):
Fault, running, zero speed, frequency agree, frequency detection
(output frequency ≤ or ≥ set value), overtorque detection, minor error, baseblock, operating mode, Inverter run ready, fault retry, UV, speed search, data output through communication
Standard Functions
Full-range automatic torque boost, slip compensation, DC injection braking current/time at startup/stop frequency reference bias/ gain, frequency reference with built-in potentiometer, constant copy, [MEMOBUS communications (RS-485/422, max.19.2K bps)
(optional)]
RUN and ALARM provided as standard indicators Status
Indicators
Digital
Operator
Terminals
Provided for monitor frequency reference, output frequency, output current
Main circuit: screw terminals
Control circuit: plug-in screw terminal
100 m or less
*5 Wiring Distance between Inverter and Motor
Enclosure
Cooling Method
Open chassis IP20
Cooling fan is provided for the following models:
400 V, 1.5 kW or larger Inverters (3-phase)
Other models are self-cooling.
111
112
Voltage Class
Model CIMR-
J7 ∗ A
3-phase
Ambient Temperature
Humidity
Storage Temperature *4
Location
Elevation
Vibration
40P2 40P4 40P7
400 V 3-phase
41P5 42P2
Open chassis: − 10 to 50 ° C (not frozen)
95% or less (non-condensing)
− 20 to 60 ° C
43P0 43P7
Indoor (free from corrosive gases or dust)
1,000 m or less
Up to 9.8 m/s
2 up to 2 m/s
2
(1G) at less than 20 Hz,
(0.2G) at 20 to 50 Hz
* 1. Based on a standard 4-pole motor for max. applicable motor output.
* 2. Shows deceleration torque for uncoupled motor decelerating from 60 Hz with the shortest possible deceleration time.
* 3. Minimum permissible load: 5 VDC, 10 mA (as reference value)
* 4. Temperature during shipping (for short period).
* 5. If the wiring distance between Inverter and motor is long, reduce the
Inverter carrier frequency. For details, refer to Reducing Motor Noise or
Leakage Current Using Carrier Frequency Selection (n46) on page 64.
* 6. The ground fault here is one which occurs in the motor wiring while the motor is running. A ground fault may not be detected in the following cases.
• A ground fault with low resistance which occurs in motor cables or terminals.
• A ground fault occurs when the power is turned ON.
9. Specifications
Standard Wiring
U
DC Reactor
(Option)
X
Short-circuit bar
*1
MCCB
R
For single-phase, use R/L1 and S/L2.
S
T
FORWARD
RUN/STOP
REVERSE
RUN/STOP
FAULT RESET
EXTERNAL FAULT
(NO Contact)
MULTI-STEP
SPEED REF.1
S1
S2
S3
S4
S5
+2
R/L1
S/L2
T/L3
+1
−
2 k Ω
P P
Frequency Setting
Potentiometer
U/T1
V/T2
W/T3
IM
MA
MB
MC
RUNNING
Multi-function
*2 output
250 VAC 1 A or less
30 VDC 1 A or less
SC
Shielded Connection
Terminal
FS Frequency Setting Power Supply
(+12 V 20 mA)
FR
FC
Speed Frequency Reference
0 to +10 V (20 k Ω ) or
4 to 20 mA/0 to 20 mA (250 Ω )
0 V
Digital Operator
Frequency
Setting
Volume
MIN MAX
AM
AC
P FM
Analog Monitor
Output
0 to +10 VDC
(2 mA)
Output Frequency
Shielded P Shielded twisted-pair cable
: Only basic insulation (Protective class 1, overvoltage categoly II) is provided for the
control circuit terminals. Additional insulation may be necessary in the end product
to conform to CE requirements.
*1. Shorting bar must be removed when connecting DC reactor.
*2. Minimum permissible load: 5 VDC, 10 mA (as reference value)
113
114
Terminal Descriptions
Type Terminal
R/L1, S/L2,
T/L3
Name
AC power supply input
Function (Signal Level)
Use main circuit power input. (Use terminals
R/L1 and S/L2 for single-phase Inverters.
Never use terminal T/L3.)
Inverter output U/T1, V/T2,
W/T3
+2, +1
Inverter output
+1, -
DC reactor connection
DC power supply input
Grounding
When connecting optional DC reactor, remove the main circuit short-circuit bar between +2 and +1.
DC power supply input (+1: positive − : negative) *1
For grounding (according to the local grounding codes)
S1
S2
S3
Forward run input
Multi-function input selection 2
Multi-function input selection 3
Closed: FWD run, open: REV run
Factory setting closed:REV run open: FWD run
Factory setting: Fault reset
Photocoupler insulation,
24 VDC,
8 mA
S4
S5
SC
FS
Multi-function input selection 4
Multi-function input selection 5
Multi-function input selection common
Power for frequency setting
Factory setting: External fault (NO contact)
Factory setting: Multi-step speed reference 1
For control signal
+12 V (permissible current 20 mA max.)
FR
FC
MA
MB
Master speed frequency reference
Frequency reference common
NO contact output
NC contact output
0 to +10 VDC (20 k Ω ) or 4 to 20 mA (250 Ω ) or 0 to 20 mA (250 Ω ) (1/1000 resolution)
0 V
Factory setting: running Contact capacity
250 VAC 1 A or less,
30 VDC 1 A or less
MC Contact output common
AM
AC
Analog monitor output
Analog monitor common
Factory setting: Output frequency 0 to +10 VDC
0 V
0 to +10
VDC, 2 mA or less,
8-bit resolution
* 1. DC power supply input terminal is not applied to CE/UL standard.
* 2. Minimum permissible load: 5 VDC, 10 mA (as reference value)
9. Specifications
Sequence Input Connection with NPN/PNP
Transistor
When connecting sequence inputs (S1 to S5) with transistor, turn the rotary switch SW7 depending on the polarity (0 V common: NPN side,
+24 V common: PNP side).
Factory setting: NPN side
Sequence Connection with NPN Transistor (0 V Common)
VS mini J7
Multifunction
Inputs
Forward run/stop
Reverse run/stop
External fault (NO)
Fault reset
Multi-step speed reference 1
S1
S2
S3
S4
S5
SW7 NPN
+24 V
SC PNP
115
External
Power
Supply
+24V
Sequence Connection with PNP Transistor (+24 V Common)
VS mini J7
Forward run/stop
Reverse run/stop
External fault (NO)
Fault reset
Multi-step speed reference 1
S1
S2
S3
S4
S5
SW7 NPN
+24 V
SC PNP
116
9. Specifications
Dimensions/Heat Loss (Unit: mm)
The following diagram shows the external dimensions and heat loss of the open-chassis type (IP20).
2-d
W1
W
Fig. 1
8.5
D
W1
W 8.5
Fig. 2
D
117
Dimensions in mm/Mass in kg/Heat Loss (W)
Voltage class
Capacity
(kW)
W
200 V
3-phase
200 V singlephase
400 V
3-phase
0.4
0.75
1.5
0.2
2.2
3.7
0.1
0.2
0.1
0.2
0.4
0.75
1.5
0.4
0.75
1.5
2.2
3.0
3.7
H D W1
112
129
154
81
154
161
70
70
70
70
102
122
129
99
129
154
154
161
161
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
128
68
108
108
108
108
140
68
68
68
68
68
68
108
108
108
108
108
140
140
56
96
96
96
96
128
56
56
56
56
56
56
96
96
96
96
96
128
128
H1
118
118
118
118
118
118
118
118
118
118
118
118
118
118
118
118
118
118
118
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
5
H2
M4
M4
M4
M4
M4
M4
1.1
1.5
1.5
1.5
0.9
1.5
1.5
1.0
2.1
2.1
M4
M4
M4
M4
M4
M4
M4
M4 d
M4
M4
M4
M4
M4
1.5
2.1
0.5
0.5
0.5
0.8
0.9
1.3
Mass
0.5
Heat Loss (W)
Heatsink
Unit Total
3.7
9.3
13.0
Fig.
1
7.7
10.3
15.8 12.3
28.4 16.7
53.7 19.1
18.0
28.1
45.1
72.8
60.4 34.4
94.8
96.7 52.4 149.1
3.7
10.4
14.1
7.7
12.3
20.0
15.8 16.1
28.4 23.0
53.7 29.1
9.4
13.7
31.9
51.4
82.8
23.1
15.1 15.0
30.1
30.3 24.6
54.9
45.8 29.9
75.7
50.5 32.5
83.0
58.2 37.6
95.8
73.4 44.5 117.9
1
1
2
2
1
2
1
1
2
2
2
2
2
2
2
2
1
2
118
9. Specifications
Recommended Peripheral Devices
It is recommended that the following peripheral devices be mounted between the AC main circuit power supply and VS mini input terminals
R/L1, S/L2, and T/L3.
• MCCB (Molded-case Circuit Breaker)/Fuse:
Always connect for wiring protection.
• Magnetic Contactor:
Mount a surge suppressor on the coil. (Refer to the table shown below.) When using a magnetic contactor to start and stop the
Inverter, do not exceed one start per hour.
Recommended MCCB, Magnetic Contactors and Fuses
• 200 V 3-phase
VS mini Model
Capacity (kVA)
Rated Output Current
(A)
MCCB type NF30
(MITSUBISHI)
Magnetic contactor (Fuji
Electric FA
Components
& Systems)
Without reactor
With reactor
Fuse (UL Class RK5)
J7*A
20P1
0.3
0.8
5 A
SC-03
(11A)
SC-03
(11A)
5 A
J7*A
20P2
0.6
1.6
5 A
J7*A
20P4
1.1
3
5 A
SC-03
(11A)
SC-03
(11A)
5 A
SC-03
(11A)
SC-03
(11A)
5 A
J7*A
20P7
1.9
5
10 A
J7*A
21P5
3.0
8
20 A
J7*A
22P2
4.2
11
20 A
J7*A
23P7
6.7
17.5
30 A
SC-03
(11A)
SC-03
(11A)
10 A
SC-4-0
(18A)
SC-03
(11A)
20 A
SC-N1
(26A)
SC-4-0
(18A)
20 A
SC-N2
(35A)
SC-N1
(26A)
30 A
119
• 200 V Single-phase
VS mini Model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50 (MIT-
SUBISHI)
Magnetic contactor
(Fuji Electric FA Components & Systems)
Without reactor
With reactor
Fuse (UL Class RK5)
• 400 A 3-phase
J7* A
B0P1
0.3
0.8
5 A
SC-03
(11A)
SC-03
(11A)
5 A
VS mini Model
Capacity (kVA)
Rated Output Current (A)
MCCB type NF30, NF50
(MITSUBISHI)
Magnetic contactor (Fuji Electric FA
Components &
Systems)
Fuse (UL Class RK5)
Without reactor
With reactor
SC-03
(11A)
J7*A
40P2
0.9
1.2
5 A
SC-03
(11A)
5 A
J7*A
40P4
1.4
1.8
5 A
J7*A
40P7
2.6
3.4
5 A
J7* A
B0P2
0.6
1.5
5 A
SC-03
(11A)
SC-03
(11A)
5 A
J7*A
41P5
3.7
4.8
10 A
J7* A
B0P4
1.1
3
10 A
SC-03
(11A)
SC-03
(11A)
10 A
J7*A
42P2
4.2
5.5
15 A
J7* A
B0P7
1.9
5
20 A
SC-4-0
(18A)
SC-4-0
(18A)
20 A
J7*A
43P0
5.5
7.2
20 A
J7* A
B1P5
3.0
8
30 A
SC-N2
(35A)
SC-N1
(26A)
20 A
J7*A
43P7
6.6
8.6
20 A
SC-03
(11A)
SC-03
(11A)
5 A
SC-03
(11A)
SC-03
(11A)
5 A
SC-03
(11A)
SC-03
(11A)
10 A
SC-4-0
(18A)
SC-4-0
(18A)
SC-N1
(26A)
SC-03
(11A)
10 A
SC-03
(11A)
20 A
SC-4-0
(18A)
20 A
120
9. Specifications
Surge Suppressors
Coils and Relays
Surge Suppressors
200 V to
230 V
Large size magnetic contactors
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)
Model
DCR2-
50A22E
10A25C
Specifications
250 VAC
0.5
µ F
200 Ω
250 VAC
0.1
µ F
100 Ω
Code No.
C002417
C002482
• Ground Fault Interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the current should be 200 mA or higher and the operating time 0.1 s or longer.
Example:
• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and after)
• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and after)
• AC and DC Reactor:
Install an AC reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to improve power factor on the power supply side.
• Noise Filter:
Use a noise filter exclusively for Inverter if radio noise generated from the Inverter causes other control devices to malfunction.
NOTE
1. Never connect a general LC/RC noise filter to the Inverter output circuit.
2. Do not connect a phase-advancing capacitor to the I/O sides and/or a surge suppressor to the output side.
3. When a magnetic contactor is installed between the
Inverter and the motor, do not turn it ON/OFF during operation.
For the details of the peripheral devices, refer to the catalog.
121
Constants List
• Addition of Constants Accompanied by the Upgraded Software
Version
The constants marked with #1 are applicable for the upgraded software version No. VSP 020011 or later.
No.
Register No. for
Transmission
Name
01 0101H Password
Setting
Range
Setting
Unit
Initial
Setting
02 0102H RUN Command Selection
03 0103H Frequency Reference Selection
04 0104H Stopping Method
Selection
05 0105H Reverse Run Prohibit
06 0106H Stop Key Selection
07 0107H Frequency Reference Selection in
Local Mode
08 0108H Frequency Reference Setting Method From Digital
Operator
09 0109H Max. Output Frequency
10
11
12
13
010AH
010BH
Max. Voltage
Max. Voltage Output Frequency
010CH Mid. Output Frequency
010DH Mid. Output Frequency Voltage
0, 1, 6, 8,
9
0 to 2
0 to 4, 6
0, 1
0, 1
0, 1
0, 1
0, 1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
*4
*4
50.0 to
400 Hz
0.1 Hz
(less than
100 Hz)
1 V
60.0 Hz
200 V
*1 1 to
255 V
*1
0.2 to 400
Hz
1 Hz
(100 Hz or more)
60.0 Hz
1.5 Hz 0.1 to 399
Hz
1 to
255 V
*1
1 Hz
(100 Hz or more)
1 V
12 V *1
Change during
Operation
User
Setting
Ref.
Page
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
44
49
50
67
51
66
49
50
45
45
45
45
45
122
9. Specifications
No.
Register No. for
Transmission
14
15
010EH
010FH quency
Name
Min. Output Fre-
Min. Output Frequency Voltage
Setting
Range
0.1 to
10.0 Hz
1 to
50 V *1
Setting
Unit
0.1 Hz
1 V
16 0110H Acceleration Time 1 0.0 to 999 s
0.1 s (less than 100 s)
1 s (100 s or more)
17 0111H Deceleration Time 1 0.0 to 999 s
0.1 s (less than 100 s)
1 s (100 s or more)
18 0112H Acceleration Time 2 0.0 to 999 s
0.1 s (less than 100 s)
1 s (100 s or more)
19 0113H Deceleration Time 2 0.0 to 999 s
0.1 s (less than 100 s)
1 s (100 s or more)
20 0114H S-curve Selection
21 0115H Frequency Reference 1 (Master
Speed Frequency
Reference)
0 to 3
0.0 to
400 Hz
22
23
0116H
0117H
Frequency Reference 2
Frequency Reference 3
0.0 to
400 Hz
0.0 to
400 Hz
1
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
Initial
Setting
1.5 Hz
12 V
*1
10.0 s
10.0 s
10.0 s
10.0 s
0
6.0 Hz
0.0 Hz
0.0 Hz
Change during
Operation
User
Setting
Ref.
Page
Yes
Yes
No
No
No
No
Yes
No
No
No
45
45
55
55
55
55
56
51
51
51
123
No.
Register No. for
Transmission
Name
24 0118H Frequency Reference 4
25 0119H Frequency Reference 5
26 011AH Frequency Reference 6
27 011BH Frequency Reference 7
28 011CH Frequency Reference 8
29 011DH Jog Frequency
30 011EH Frequency Reference Upper Limit
31 011FH Frequency Reference Lower Limit
32 0120H Motor Rated Current
Setting
Range
Setting
Unit
Initial
Setting
0.0 to
400 Hz
0.0 to
400 Hz
0.0 to
400 Hz
0.0 to
400 Hz
0.0 to
400 Hz
0.0 to
400 Hz
0% to
110%
0% to
110%
0% to
120% of
Inverter rated current
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
0.1 Hz
(less than
100 Hz)
1Hz (100
Hz or more)
1%
1%
0.1 A
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
0.0 Hz
6.0 Hz
100%
0%
*2
Change during
Operation
User
Setting
Ref.
Page
No
No
No
No
No
No
Yes
Yes
Yes
51
51
51
51
51
52
54
54
81
124
9. Specifications
No.
Register No. for
Transmission
Name
33 0121H Electronic Thermal
Motor Protection
Selection
34 0122H Electronic Thermal
Motor Protection
Time Constant Setting
35 0123H Selecting Cooling
Fan Operation
36
37
38
39
0124H
0125H
0126H
0127H
Multi-function Input
Selection 2
Multi-function Input
Selection 3
Multi-function Input
Selection 4
Multi-function Input
Selection 5
Setting
Range
0 to 2
1 to 60 min
0, 1
40 0128H Multi-function Output Selection
41 0129H Analog Frequency
Reference Gain
42 012AH Analog Frequency
Reference Bias
43 012BH Analog Frequency
Reference Filter
Time Constant
44 012CH Multi-function Analog Output
(terminal AM-AC)
45 012DH Analog Monitor
Gain
46 012EH Carrier Frequency
Selection
47 012FH Momentary Power
Loss Ridethrough
Method
48 0130H Automatic Retry Attempts
0, 1
0.00 to
2.00
1 to 4, 7 to
9
0 to 2
0 to 10 times
2 to 8,
10 to 22
0, 2 to 8,
10 to 22
2 to 8,
10 to 22
2 to 8,
10 to 22,
34, 35
0 to 7,
10 to 18
0% to
255%
− 99% to
99%
0.00 to
2.00 s
Setting
Unit
1
1 min
1
1
1
1
1
1
1%
1%
0.01 s
1
0.01
1
1
1
Initial
Setting
Change during
Operation
User
Setting
Ref.
Page
0
8 min
0
2
5
3
6
1
100%
0%
0.10 s
0
1.00
*3
0
0 time
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes
81
81
83
69
69
69
69
73
53
53
---
63
63
64
56
60
125
No.
Register No. for
Transmission
Name
49 0131H Jump Frequency 1
50
51
52
53
54
0132H
0133H
0134H
0135H
0136H
Jump Frequency 2
Jump Frequency
Range
DC Injection Braking Current
DC Injection Braking Time at Stop
DC Injection Braking Time at Startup
55 0137H Stall Prevention
During Deceleration
56 0138H Stall Prevention
Level During Acceleration
57 0139H Stall Prevention while Running
58 013AH Frequency Detection Level
Setting
Range
Setting
Unit
0.0 to 400
Hz
0.1 Hz
(less than
100 Hz)/
1 Hz
(100 Hz or more)
0.0 to 400
Hz
0.1 Hz
(less than
100 Hz)
1 Hz
(100 Hz or more)
0.1 Hz 0.0 to 25.5
Hz
0% to
100%
1%
0.0% to
25.5%
0.0% to
25.5%
0, 1
0.1s
0.1s
1
30% to
200%
30% to
200%
0.0 to 400
Hz
0 to 4
1%
1%
0.1 Hz
(less than
100 Hz)/1
Hz (100
Hz or more)
1 59 013BH Overtorque Detection Function
60 013CH Overtorque Detection Level
61 013DH Overtorque Detection Time
62 013EH Hold Output
30% to
200%
0.1 to
10.0 s
0, 1
0.0 to 2.5
1%
0.1 s
1
0.1
63 013FH Torque Compensation Gain
126
Initial
Setting
Change during
Operation
User
Setting
Ref.
Page
0.0 Hz
0.0 Hz
0.0 Hz
50%
0.5 s
0.0 s
0
170%
160%
0.0 Hz
0
160%
0.1 s
0
1.0
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
60
60
60
61
68
61
79
77
78
59
58
58
58
72
47
9. Specifications
No.
Register No. for
Transmission
Name
64 0140H Motor Rated Slip
Setting
Range
65 0141H Motor No-load Current
66 0142H Slip Compensation
Gain
67 0143H Slip Compensation
Time Constant
68 0144H MEMOBUS Timeover Detection Selection
0.0 to
20.0 Hz
0% to 99%
0.0 to 2.5
0.0 to
25.5 s
0 to 4
0 to 3
0 to 32
69 0145H Baud Rate Setting
70 0146H MEMOBUS Slave
Address
71 0147H MEMOBUS BPS
Selection
72 0148H MEMOBUS Parity
Selection
73 0149H Transmission Waiting Time
74 014AH RTS Control
75
#1
76
#1
014BH Reducing Carrier
Frequency Selection At Low Speed
014CH Constant Copy
Function Selection
0 to 3
0 to 2 rdy, rEd,
Cpy, vFy, vA, Sno
0, 1 77
#1
014DH Constant Read Selection Prohibit
78 014EH Fault History
10 to 65 ms
0, 1
0, 1
79 014FH Software Version
No.
Stores, displays most recent alarm
Displays lowerplace 3 digits of software
No.
Setting
Unit
0.1 Hz
1%
0.1
0.1 s
1
1
1
1
1
1 ms
1
1
1
Setting disabled
Setting disabled
Initial
Setting
Change during
Operation
User
Setting
Ref.
Page
*2
*2
0.0
2.0 s
0
0
0
2
0
10 ms
0
0 rdy
0
-
-
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
80
80
80
80
---
---
---
---
---
---
---
66
84
85
41
---
127
* 1. Upper limit of setting range and initial setting are doubled for 400 V
Class.
* 2. Depends on Inverter capacity. Refer to the next page.
* 3. Depends on Inverter capacity. Refer to page 65.
* 4. Initial setting of the model with Digital Operator (without potentiometer) is 1. Setting can be set to 0 by constant initialization.
• 200 V Class 3-phase
No.
-
Name n32 Motor Rated
Current
Unit
Inverter Capacity kW
A n64 Motor Rated Slip Hz n65 Motor No-load
Current
%
0.1
0.6
2.5
72
• 200 V Class Single-phase
0.2
1.1
2.6
73
0.4
1.9
Initial Setting
0.75
1.5
3.3
6.2
2.9
62
2.5
55
2.6
45
2.2
8.5
2.9
35
-
-
-
-
3.7
14.1
3.3
32
No.
-
Name
Inverter Capacity n32 Motor Rated Current n64 Motor Rated Slip n65 Motor No-load Current
• 400 V Class 3-phase
No.
-
Name
Inverter Capacity n32 Motor Rated
Current n64 Motor Rated
Slip n65 Motor No-load
Current
Unit kW
A
Hz
%
-
-
-
-
Unit kW
A
Hz
%
0.2
0.6
2.5
73
0.1
0.6
2.5
72
0.4
1.0
2.7
63
0.2
1.1
Initial Setting
0.4
0.75
1.9
3.3
2.6
73
2.9
62
2.5
55
Initial Setting
0.75
1.5
1.6
2.6
52
3.1
2.5
45
2.2
4.2
3.0
35
3.0
7.0
3.2
33
1.5
6.2
2.6
45
3.7
7.0
3.2
33
128
10 Conformance to CE Markings
10 Conformance to CE Markings
Points regarding conformance to CE markings are given below.
CE Markings
CE markings indicate conformance to safety and environmental standards that apply to business transactions (including production, imports, and sales) in Europe. There are unified European standards for mechanical products (Machine Directive), electrical products (Low Voltage
Directive), and electrical noise (EMC Directive). CE markings are required for business transactions in Europe (including production, imports, and sales).
The VS mini Series Inverters bear CE markings indicating conformance to the Low Voltage Directive and the EMC Directive.
• Low Voltage Directive: 73/23/EEC
93/68/EEC
• EMC Directive: 89/336/EEC
92/31/EEC
93/68/EEC
Machinery and installations that incorporate the Inverter are also subject to CE markings. It is ultimately the responsibility of customers making products incorporating the Inverter to attach CE markings to the finished products. The customer must confirm that the finished products
(machines or installations) conform to the European Standards.
Requirements for Conformance to CE Markings
Low Voltage Directive
VS mini Series Inverters satisfy testing for conformance to the Low
Voltage Directive under the conditions described in European Standard
EN50178.
Requirements for Conformance to the Low Voltage Directive
VS mini Series Inverters must satisfy the following conditions in order to conform to the Low Voltage Directive.
• Only basic insulation to meet the requirements of protection class 1 and overvoltage category II is provided with control circuit terminals.
Additional insulation may be necessary in the end product to conform to CE requirements.
129
130
• For 400 V Class Inverters, always ground the supply neutral to conform to CE requirements.
EMC Directive
VS mini Series Inverters satisfy testing for conformance to the EMC
Directive under the conditions described in European Standard
EN61800-3.
Installation Method
In order to ensure that the machinery or installation incorporating the
Inverter conforms to the EMC Directive, perform installation according to the method below.
• Install a noise filter that conforms to European Standards on the input side. (Refer to EMC Noise Filter on page 133.)
• Use a shielded line or metal piping for wiring between the Inverter and Motor. Make the wiring as short as possible.
• For details of installation method, refer to Installation Manual (document No. EZZ008390.)
10 Conformance to CE Markings
Installation and Wiring of Inverter and Noise Filter
(Model: CIMR-J7 20P1 to 24P0),
(Model: CIMR-J7 40P2 to 44P0)
L1 L2 L3 PE
Control Panel
3-phase Noise Filter
Metal
Mounting
Plate
Grounding
Face
L1 L2 L3
E
RS T
VS mini J7
Grounding
Face
U V W
E
Shielded
Cable
IM
Motor cable: 20 m max.
131
Installation and Wiring of Inverter and Noise Filter
(Model: CIMR-J7 B0P1 to B1P5)
L N PE
Control Panel
Single-phase
Noise Filter
Metal
Mounting
Plate
Grounding
Face
E
R S
L N
132
Gronding
Face
VS mini J7
U V W
E
Shielded
Cable
IM
Motor cable: 20 m max.
10 Conformance to CE Markings
EMC Noise Filter
Voltage
Class
Inverter
Model
CIMR-
J7*
Model No.
200 V RS1010-J7
Number of
Phases
Noise Filter (Manufacturer: RASMI)
Rated
Current
(A)
Mass
(kg)
Dimensions
W × L × H
1 10 0.6
71 × 169 × 45
400 V
42P2
43P0
43P7
44P0
24P0
40P2
40P4
40P7
41P5
20P2
20P4
20P7
21P5
22P2
23P7
B0P1
B0P2
B0P4
B0P7
B1P5
20P1
RS1020-J7
RS2010-J7
RS2020-J7
RS2030-J7
RS3005-J7
RS3010-J7
RS3020-J7
1
3
3
3
3
3
3
20
10
16
26
5
10
15
1.0
0.8
1.0
1.1
1.0
1.0
1.1
111 × 169 × 50
82 × 194 × 50
111 × 169 × 50
Y × X φ d
51 × 156 5.0
91 × 156 5.0
62 × 181 5.0
91 × 156 5.0
144 × 174 × 50 120 × 161 5.0
111 × 169 × 45
111 × 169 × 45
91 × 156 5.0
91 × 156 5.0
144 × 174 × 50 120 × 161 5.0
133
134
H
The EMC-compliant J7 Series noise filter is footprint type.
φ d
C I M R - J 7
X L
A to Z : Specifications
A to Z : Type
Y
W
Revision History
The revision dates and numbers of the revised manuals are given on the bottom of the back cover.
MANUAL NO. TOE-S606-12.1
C Printed in Japan January 2000 99-10
Date of printing
1
Revision number
Date of original publication
October 1999
January 2000
June 2001
March 2002
April 2002
−
1
2
3
4
July 2002
August 2002
May 2003
July 2003
November 2003
October 2005
9
10
7
8
5
6
Section Revised Content
− First edition
End of a book Revision: Contents of sticker
Notation for safety precautions
Chapter 9
Revision: Warning/Caution mark
Partly deleted
Addition: Minimum permissible load
Notation for safety precautions
Chapter 8
Addition: Warnings for CE Markings
Addition: Troubleshooting
Front cover Deletion: CE and UL marks
Back cover
Chapter 5
Chapter 9
Chapter 6
Revision: Address
Partly revised
Revision: Inverter diagrams
Notation for safety precautions
Chapter 4
Addition: ・ WIRING
Precaution when the 3wire sequence is selected
・ Warranty Information
Revision: Descriptions of terminal symbols and tightening torque of the main circuits.
October 2005
February 2006
10
Section
Chapter 5
Chapter 6
Chapter 8
Chapter 9
11
Chapter 10
Back cover
Chapter 9
Revised Content
Addition: ・ Table in the Description of
Status Indicators
・ Flowchart in the Function
Indicator Description
Additional information for when LOCAL/REMOTE
Selection and Constant
No./data are selected
Addition: ・ Settings needed before operation after wiring
・ Setting 5 of Constant Selection/Initialization (n01)
・ *3 in the n081 Setting table
・ Settings 1, 9, 23 to 33 for multi-function input selection
・ Settings 8 and 9 for multifunction output selection.
Addition: ・ Descriptions of short circuit and grounding.
・ Description of setting for
NPN/PNP switch.
・ Description of short-circuit bar.
Revision: ・ Descriptions of recommended magnetic contactor in the Recommended
Peripheral Devices section.
・ A Change during Operation column has been inserted in the Constants list.
Added
Revision: Address
Revision: Max. output voltage in the
Standard Specifications
(200 V Class)
VS mini J7 Series
INSTRUCTION MANUAL
IRUMA BUSINESS CENTER (SOLUTION CENTER)
480, Kamifujisawa, Iruma, Saitama 358-8555, Japan
Phone 81-4-2962-5696 Fax 81-4-2962-6138
YASKAWA ELECTRIC AMERICA, INC.
2121 Norman Drive South, Waukegan, IL 60085, U.S.A.
Phone 1-847-887-7000 Fax 1-847-887-7370
YASKAWA ELETRICO DO BRASIL COMERCIO LTD.A.
Avenida Fagundes Filho, 620 Bairro Saude-Sao Paulo-SP, Brazil CEP: 04304-000
Phone 55-11-5071-2552 Fax 55-11-5581-8795
YASKAWA ELECTRIC EUROPE GmbH
Am Kronberger Hang 2, 65824 Schwalbach, Germany
Phone 49-6196-569-300 Fax 49-6196-569-312
YASKAWA ELECTRIC UK LTD.
1 Hunt Hill Orchardton Woods Cumbernauld, G68 9LF, United Kingdom
Phone 44-1236-735000 Fax 44-1236-458182
YASKAWA ELECTRIC KOREA CORPORATION
7F, Doore Bldg. 24, Yeoido-dong, Youngdungpo-Ku, Seoul 150-877, Korea
Phone 82-2-784-7844 Fax 82-2-784-8495
YASKAWA ELECTRIC (SINGAPORE) PTE. LTD.
151 Lorong Chuan, #04-01, New Tech Park 556741, Singapore
Phone 65-6282-3003 Fax 65-6289-3003
YASKAWA ELECTRIC (SHANGHAI) CO., LTD.
No.18 Xizang Zhong Road. Room 1702-1707, Harbour Ring Plaza Shanghai 200001, China
Phone 86-21-5385-2200 Fax 86-21-5385-3299
YASKAWA ELECTRIC (SHANGHAI) CO., LTD. BEIJING OFFICE
Room 1011A, Tower W3 Oriental Plaza, No.1 East Chang An Ave.,
Dong Cheng District, Beijing 100738, China
Phone 86-10-8518-4086 Fax 86-10-8518-4082
YASKAWA ELECTRIC TAIWAN CORPORATION
9F, 16, Nanking E. Rd., Sec. 3, Taipei, Taiwan
Phone 886-2-2502-5003 Fax 886-2-2505-1280
YASKAWA ELECTRIC CORPORATION
YASKAWA
In the event that the end user of this product is to be the military and said product is to be employed in any weapons systems or the manufacture thereof, the export will fall under the relevant regulations as stipulated in the Foreign Exchange and Foreign Trade
Regulations. Therefore, be sure to follow all procedures and submit all relevant documentation according to any and all rules, regulations and laws that may apply.
Specifications are subject to change without notice for ongoing product modifications and improvements.
©
1999-2006 YASKAWA ELECTRIC CORPORATION. All rights reserved.
MANUAL NO. TOE-S606-12.1G
Printed in Japan February 2006 99-10