5. Operating the Inverter
Fault History Display Method
Fault description is displayed when U09 is selected.
(Example)
: Fault description
“---” is displayed if there is no fault.
(Refer to page 97 for details.)
Clearing the Fault History
Set constant n01 to 6 to clear the fault history. Set data returns to its initial value after 6 is set.
Note: Initializing the constants (n01=8, 9) also clears the fault history.
Setting and Referencing Constants
The following diagram shows how to select and change constants.
LO/RE
REMOTE/LOCAL selection
DSPL • Setting n02 (RUN command selection)
PRGM
Constant
No./ data
DSPL
PRGM n02
RUN command selection
ENTER
PRGM
Initial setting: 0 operator reference
PRGM
ENTER
Set to 1
Control circuit terminal reference
(flashing at changing)
FREF
PRGM
Return to constant No.
display
After
1 s
PRGM
Data set
Simple Data Setting
Digital setting (refer to 5. Operating the Inverter ) and potentiometer setting are both possible for simple acceleration/deceleration operation of the VS mini.
Frequency reference by potentiometer signal is set with initial setting
(n03=0).
Factory setting of the model with operator (without potentiometer) is set by Digital Operator (n03=1).
41
Following is an example in which the function LEDs are used to set frequency reference, acceleration time, deceleration time, and motor direction.
Operation Steps
1. Turn ON the power supply.
Operator
Display
0.0
Function
Indicators
Status
Indicators
FREF
RUN
ALARM
2. Set constant n03 to 1.
1
PRGM
RUN
ALARM
3. Set the following constants.
n16: 15.0 (Acceleration Time) n17: 5.0 (Deceleration Time)
4. Select forward or reverse run by pressing the or key.
NOTE
Examine the application. (Never select REV when reverse run is prohibited.)
15.0
5.0
(Forward) or
(Reverse)
PRGM
FR
RUN
ALARM
RUN
ALARM
5. Set the reference by pressing the
key.
6. Press .
or 60.0
FREF
RUN
ALARM
FOUT
RUN
ALARM
7. Press to stop.
Status indicators :ON
60.0 to 0.0
RUN
FOUT
RUN
ALARM
:Flashing (long flashing) :Flashing :OFF
42