Below you will find brief information for C200H CPU01-E, C200H CPU03-E, C200H CPU11-E. This guide provides instructions on installing the C200H series programmable controllers, covering their main components (CPU rack, CPU, expansion I/O rack, power supply, I/O Units, Memory Units), mounting procedures, system connections, and environmental considerations. You'll also find details on power requirements and safety measures and troubleshooting.
Advertisement
Advertisement
Cat. No. W111-E1-10
SYSMAC
Programmable Controllers
C200H
(CPU01-E/03-E/11-E)
INSTALLATION GUIDE
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
C200H Programmable Controllers
(CPU01-E/03-E/11-E)
Installation Guide
Revised January 2001
Downloaded from Elcodis.com
electronic components distributor
Terms and Conditions of Sale
1.
Offer; Acceptance. These terms and conditions (these "Terms") are deemed part of all quotes, agreements, purchase orders, acknowledgments, price lists, catalogs, manuals, brochures and other documents, whether electronic or in writing, relating to the sale of products or services (collectively, the "Products") by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron objects to any terms or conditions proposed in Buyer’s purchase order or other documents which are inconsistent with, or in addition to, these Terms.
2.
Prices; Payment Terms. All prices stated are current, subject to change without notice by Omron. Omron reserves the right to increase or decrease prices on any unshipped portions of outstanding orders. Payments for Products are due net 30 days unless otherwise stated in the invoice.
3.
Discounts. Cash discounts, if any, will apply only on the net amount of invoices sent to Buyer after deducting transportation charges, taxes and duties, and will be allowed only if (i) the invoice is paid according to Omron’s payment terms and (ii) Buyer has no past due amounts.
4.
Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or the maximum legal rate, whichever is less, on any balance not paid within the stated terms.
5.
Orders. Omron will accept no order less than $200 net billing.
6.
Governmental Approvals. Buyer shall be responsible for, and shall bear all costs involved in, obtaining any government approvals required for the importation or sale of the Products.
7.
Taxes. All taxes, duties and other governmental charges (other than general real property and income taxes), including any interest or penalties thereon, imposed directly or indirectly on Omron or required to be collected directly or indirectly by Omron for the manufacture, production, sale, delivery, importation, consumption or use of the Products sold hereunder (including customs duties and sales, excise, use, turnover and license taxes) shall be charged to and remitted by Buyer to Omron.
8.
Financial. If the financial position of Buyer at any time becomes unsatisfactory to Omron, Omron reserves the right to stop shipments or require satisfactory security or payment in advance. If Buyer fails to make payment or otherwise comply with these Terms or any related agreement, Omron may (without liability and in addition to other remedies) cancel any unshipped portion of Products sold hereunder and stop any Products in transit until Buyer pays all amounts, including amounts payable hereunder, whether or not then due, which are owing to it by Buyer. Buyer shall in any event remain liable for all unpaid accounts.
9.
Cancellation; Etc. Orders are not subject to rescheduling or cancellation unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery resulting from causes beyond its control, including earthquakes, fires, floods, strikes or other labor disputes, shortage of labor or materials, accidents to machinery, acts of sabotage, riots, delay in or lack of transportation or the requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron: a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall constitute delivery to Buyer; c. All sales and shipments of Products shall be FOB shipping point (unless otherwise stated in writing by Omron), at which point title and risk of loss shall pass from Omron to Buyer; provided that Omron shall retain a security interest in the Products until the full purchase price is paid; d. Delivery and shipping dates are estimates only; and e. Omron will package Products as it deems proper for protection against normal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing to Omron within 30 days of receipt of shipment and include the original transportation bill signed by the carrier noting that the carrier received the Products from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above warranty.
See http://oeweb.omron.com or contact your Omron representative for published information.
14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and their employees from and against all liabilities, losses, claims, costs and expenses (including attorney's fees and expenses) related to any claim, investigation, litigation or proceeding (whether or not Omron is a party) which arises or is alleged to arise from Buyer's acts or omissions under these Terms or in any way with respect to the Products. Without limiting the foregoing, Buyer (at its own expense) shall indemnify and hold harmless Omron and defend or settle any action brought against such Companies to the extent based on a claim that any Product made to Buyer specifications infringed intellectual property rights of another party.
16. Property; Confidentiality. Any intellectual property in the Products is the exclusive property of Omron Companies and Buyer shall not attempt to duplicate it in any way without the written permission of Omron. Notwithstanding any charges to Buyer for engineering or tooling, all engineering and tooling shall remain the exclusive property of Omron. All information and materials supplied by Omron to Buyer relating to the Products are confidential and proprietary, and Buyer shall limit distribution thereof to its trusted employees and strictly prevent disclosure to any third party.
17. Export Controls. Buyer shall comply with all applicable laws, regulations and licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of regulated technology or information.
18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right and no course of dealing between Buyer and Omron shall operate as a waiver of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder without Omron's written consent. (c) Law. These Terms are governed by the law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law principles). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed or waived unless in writing signed by the parties. (e) Severability. If any provision hereof is rendered ineffective or invalid, such provision shall not invalidate any other provision. (f) Setoff. Buyer shall have no right to set off any amounts against the amount owing in respect of this invoice. (g) Definitions. As used herein, “including” means “including without limitation”; and “Omron Companies” (or similar words) mean Omron Corporation and any direct or indirect subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1.
Suitability of Use. Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the combination of the
Product in the Buyer’s application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to this Product.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-
ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
2.
Programmable Products. Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
3.
Performance Data. Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
4.
Change in Specifications. Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change part numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to confirm actual specifications of purchased Product.
5.
Errors and Omissions. Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical or proofreading errors or omissions.
Downloaded from Elcodis.com
electronic components distributor
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!
DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
!
WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
!
Caution Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1, 2, 3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
©
OMRON, 1990
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
Downloaded from Elcodis.com
electronic components distributor
vi
Downloaded from Elcodis.com
electronic components distributor
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions
5 Application Precautions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 1
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-1 What is a Control System?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 The Role of the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 How Does a PC Work?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 2
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-1 CPU Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Expansion I/O Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Memory Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 3
Assembly Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-1 Mounting the Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Memory Packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 4
System Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1 IR Word Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Maximum Current and Power Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 5
Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . .
5-1 Installation Environment
5-2 Mounting Requirements
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Duct Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Preventing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 6
Power Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-1 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Emergency Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SECTION 7
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-1 Interlock Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor vii
TABLE OF CONTENTS
Appendices
A Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C Standard Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
D Programming Console Operation
E Programming Instructions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Glossary
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . viii
Downloaded from Elcodis.com
electronic components distributor
About this Manual:
This manual explains how to install a C-series C200H Programmable Controller
(CPU01-E/03-E/11-E).
Section 1 is an introduction to Programmable Controllers. General information about what a Programmable Controller can do and how a Programmable Controller works is provided.
Section 2 provides a description of all the components of the C200H. The names of all the individual parts of each Unit are given.
Section 3 explains how to assemble the C200H. A detailed description of how to mount each Unit is provided.
Section 4 outlines the system connections involved in installing a C200H Programmable Controller System. All I/O, including Remote I/O, are included.
Section 5 contains the requirements for the installation environment of the C200H. Suggestions for preventing electrical noise are included.
Section 6 explains the power considerations involved in installing the C200H.
Section 7 lists safety considerations that should be kept in mind while installing the C200H.
Appendixes , a Glossary , and an Index are also provided.
!
WARNING Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
PRECAUTIONS
This section provides general precautions for using the Programmable Controller (PC) and related devices.
The information contained in this section is important for the safe and reliable application of the Programmable Controller. You must read this section and understand the information contained before attempting to set up or operate a
PC system.
1 Intended Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Application Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor xi
Safety Precautions
1
3
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
•
Personnel in charge of designing FA systems.
•
Personnel in charge of managing FA systems and facilities.
2 General Precautions
The user must operate the product according to the performance specifications described in the operation manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
!
WARNING It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC System to the above-mentioned applications.
3 Safety Precautions
!
WARNING Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
!
WARNING Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!
Caution Tighten the screws on the terminal block of the AC Power Supply Unit to the torque specified in this manual. The loose screws may result in burning or malfunction.
xii
Downloaded from Elcodis.com
electronic components distributor
Application Precautions
4
5
Operating Environment Precautions
!
Caution Do not operate the control system in the following places:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
•
Locations subject to corrosive or flammable gases.
•
Locations subject to dust (especially iron dust) or salts.
•
Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!
Caution Take appropriate and sufficient countermeasures when installing systems in the following locations:
• Locations subject to static electricity or other forms of noise.
• Locations subject to strong electromagnetic fields.
•
Locations subject to possible exposure to radioactivity.
•
Locations close to power supplies.
!
Caution The operating environment of the PC System can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC System. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
5 Application Precautions
Observe the following precautions when using the PC System.
!
WARNING Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
•
Always ground the system to 100
Ω
or less when installing the Units. Not connecting to a ground of 100
Ω
or less may result in electric shock.
• Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting Power Supply Units, I/O Units, CPU Units,
Memory Cassettes, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
•
Connecting or wiring the cables.
•
Connecting or disconnecting the connectors.
!
Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these precautions.
•
Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
xiii
Downloaded from Elcodis.com
electronic components distributor
Application Precautions 5
• Interlock circuits, limit circuits, and similar safety measures in external circuits
(i.e., not in the Programmable Controller) must be provided by the customer.
•
Always use the power supply voltage specified in the operation manuals. An incorrect voltage may result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
•
Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
• Do not apply voltages to the Input Units in excess of the rated input voltage.
Excess voltages may result in burning.
•
Do not apply voltages or connect loads to the Output Units in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
• Disconnect the functional ground terminal when performing withstand voltage tests. Not disconnecting the functional ground terminal may result in burning.
• Install the Unit properly as specified in the operation manual. Improper installation of the Unit may result in malfunction.
•
Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in the relevant manuals. Incorrect tightening torque may result in malfunction.
•
Leave the label attached to the Unit when wiring. Removing the label may result in malfunction.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
•
Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
• Double-check all the wiring before turning ON the power supply. Incorrect wiring may result in burning.
• Mount the Unit only after checking the terminal block completely.
•
Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
• Check the user program for proper execution before actually running it on the
Unit. Not checking the program may result in an unexpected operation.
•
Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC.
•
Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Do not pull on the cables or bend the cables beyond their natural limit. Doing either of these may break the cables.
•
Do not place objects on top of the cables. Doing so may break the cables.
xiv
Downloaded from Elcodis.com
electronic components distributor
SECTION 1
Introduction
This section provides general information about Programmable Controllers (PCs) and how they fit into a Control System.
1-1 What is a Control System? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2 The Role of the PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-1 Input Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-2-2 Output Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1-3 How Does a PC Work?
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
1
What is a Control System?
Section 1-1
1-1 What is a Control System?
A Control System is the electronic equipment needed to control a particular process. It may include everything from a process control computer, if one is used, to the factory computer, down through the PCs (and there may be many of them networked together) and then on down through the network to the control components: the switches, stepping motors, solenoids, and sensors which monitor and control the mechanical operations.
Process Control Computer
Factory Computer
PC
PCs
PC PC
Control Components
A Control System can involve very large applications where many different models of PC are networked together or it could be an application as small as a single
PC controlling a single output device.
2
Downloaded from Elcodis.com
electronic components distributor
What is a Control System?
A Position Control System
Position Control Unit
Signal line for
Servomotor driver control
Input Unit
PC
Power source
Section
Power source
DC Servomotor
Driver
Hand-held Programming
Console
Control panel
Control switch
1-1
DC Servomotor Driver
DC Servomotor
DC Servomotor
In the typical Control System example shown above, a PC controls the movement of the workpiece bed across two horizontal axes using Limit Switches and
Servomotors to monitor and control movement.
3
Downloaded from Elcodis.com
electronic components distributor
The Role of the PC Section 1-2
1-2 The Role of the PC
The PC is the part of the Control System that directly controls the manufacturing process. According to the program stored in its memory, the PC accepts data from the input devices connected to it, and uses this data to monitor the controlled system. When the program calls for some action to take place, the PC sends data to the output devices connected to it, to cause that action to take place. The PC may be used to control a simple, repetitive task, or it may be connected to other PCs, or to a host computer in order to integrate the control of a complex process.
1-2-1 Input Devices
PCs can receive input from either automated or manual devices. The PC could receive data from the user via a pushbutton switch, keyboard, or similar device.
Automated input could come from a variety of devices: microswitches, timers, encoders, photosensors, and so on. Some devices, like the Limit Switch shown below, turn ON or OFF when the equipment actually makes contact with it. Other devices, like the Photoelectric Switch and Proximity Switch shown below, use other means, such as light or inductance, in order to get information about the equipment being monitored.
Photoelectric Switch Limit Switch
Proximity Switch
4
Downloaded from Elcodis.com
electronic components distributor
The Role of the PC Section 1-2
1-2-2 Output Devices
A PC can output to a myriad of devices for use in automated control. Almost anything that you can think of could be controlled (perhaps indirectly) by a PC. Some of the most common devices are motors, Solenoids, Servomotors, Stepping
Motors, valves, switches, indicator lights, buzzers, and alarms. Some of these output devices; such as the motors, Solenoids, Servomotors, Stepping Motors, and valves; affect the controlled system directly. Others; such as the indicator lights, buzzers, and alarms; provide output to notify personnel.
Solenoid
Servomotor
Stepping Motor
5
Downloaded from Elcodis.com
electronic components distributor
How Does a PC Work?
Section 1-3
1-3 How Does a PC Work?
PCs operate by monitoring input signals and providing output signals. When changes are detected in the signals, the PC reacts, through the user-programmed internal logic, to produce output signals. The PC continually cycles the program in its memory to achieve this control.
Block Diagram of PC
Power Supply
Memory
Signals from switches, sensors, etc.
Input
CPU
Output
Signals to
Solenoids, motors, etc.
Programming
Device
A program for your applications must be designed, and stored in the PC. This program is then executed as part of the cycle of internal operations of the PC.
Cycle
When a PC operates, that is, when it executes its program to control an external system, a series of operations are performed inside the PC. These internal operations can be broadly classified into the following four categories:
1, 2, 3...
1. Common (or overseeing) processes, such as watchdog timer operation and testing the program memory.
2. Data input and output.
3. Instruction execution.
4. Peripheral device servicing.
Cycle Time
The total time required for a PC to perform all these internal operations is called the cycle time. The flowchart and diagram on the following page illustrate these internal operations for a typical PC.
Timing is one of the most important factors in designing a Control System. For accurate operations, it is necessary to have answers to such questions as these:
•
How long does it take for the PC to execute all the instructions in its memory?
•
How long does it take for the PC to produce a control output in response to a given input signal?
The cycle time of the PC can be automatically calculated and monitored, but it is necessary to have an understanding of the timing relationships within the PC for effective System design and programming.
6
Downloaded from Elcodis.com
electronic components distributor
How Does a PC Work?
PC Operation Flowchart
Section
Power application
Clears data areas and resets System counters
Checks I/O Units
Resets watchdog timer
Initial processing on power application
Checks hardware and program memory
No
Sets error flag and lights indicator
Check OK?
Yes
Error or alarm?
Alarm
Error
IR data to Output Units
Proceses remote I/O
Resets watchdog timer and program counter
Executes program
Common processes
Output refreshing
Remote processing
Resets watchdog timer
Services peripherals
End of program?
No
Yes
Servicing peripheral devices
End of program?
Yes
Resets watchdog timer
No
Instruction execution
PC cycle time
Input Unit data to IR area
Input refreshing
1-3
7
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
SECTION 2
Description
This section provides information about the individual Units that make up a PC. The names of all the parts of a Unit are given, followed by any details that apply to that Unit alone. For a description of how the Units fit together to become a PC, refer to
Section 3 Assembly Instructions . For information about the model numbers of any of the parts described in this section, refer to
Appendix C Standard Models .
2-1 CPU Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-2 CPU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-3 Expansion I/O Rack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-4 Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-5 I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2-6 Memory Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
9
CPU Rack
2-1 CPU Rack
Section 2-1
The following figure shows the names of all the parts of a CPU Rack. There are four models of Backplanes available with 3, 5, 8 and 10 slots for I/O Units. You can use any of these Backplanes to build a CPU or Expansion I/O Rack. However, the C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1
B7A Interface Unit must be mounted to a C200H-BC jj
1-V1/V2 Backplane.
This connector not used:
Cover with a cap.
Backplane
I/O Units
I/O Connecting Cable connector
Connects CPU Rack to Expansion I/O Rack
When not used, cover with a cap.
CPU Backplane mounting screws (four, with
4-mm dia. heads)
10
Downloaded from Elcodis.com
electronic components distributor
CPU
2-2 CPU
Section 2-2
C200H-CPU01-E/03
The CPU is available in three models. The C200H-CPU01-E and C200H-
CPU11-E both run on 100 to 120 or 200 to 240 VAC, and the C200H-CPU03-E runs on 24 VDC. The C200H-CPU11-E is unique in that it connects the SYSMAC
LINK Unit or SYSMAC NET Link Unit to the CPU. These two Units are mounted to either of the two slots located directly to the left of the the CPU and connected to the CPU via a bus connector. A separate Unit, the Bus Connector Unit, is required to connect the SYSMAC NET Link Unit or the SYSMAC LINK Unit to the
CPU.
Also note that model C200H-CPU11-E has an additional battery connected to the CPU.
Note If you are using the SYSMAC LINK Unit or SYSMAC NET Link Unit in your
C200H system, use model C200H-CPU11-E as the CPU. Otherwise, the link
Units cannot be used.
Indicators Power fuse
Memory Pack connector
Detachable terminal block
Peripheral device mounting hole
Programming Console connector cover storage slot
Programming Console connector
(Peripheral device connector)
Remove cover to gain access to connector; store cover in cover storage slot.
Handheld Programming Console connector
Remove cover to gain access to connector.
11
Downloaded from Elcodis.com
electronic components distributor
CPU
C200H-CPU11-E
Indicators
Section 2-2
Power fuse
MF51NR (5.2 dia. x 20 mm) 2A 250 V
Memory
Pack connector
Battery compartment
Bus connector
Available only with the
C200H-CPU11-E.
Used to connect this
Unit to a SYSMAC
LINK Unit or SYSMAC
NET Link Unit.
Programming Console connector cover storage slot
Handheld Programming Console connector
Programming Console connector
(Peripheral device connector)
CPU Indicators The following figure shows the indicators that are located on the front panel of the three CPU models.
RUN indicator (green)
Lights when the PC is operating normally.
POWER (green)
Lights when power is supplied to the CPU.
ALARM (blinking red)
Blinks if an error occurs that does not stop the CPU.
ERROR (solid red)
Lights if an error occurs that stops the
CPU, at which time the RUN indicator turns OFF and the outputs are turned
OFF.
OUT INHIBIT (red)
Lights when the Load OFF flag (SR bit 25215) turns ON, at which time all the outputs are turned OFF.
12
Downloaded from Elcodis.com
electronic components distributor
CPU
Peripheral Device
Connectors
Section 2-2
All three CPU models are equipped with two connectors for peripheral devices.
One is used for the Handheld Programming Console or the Data Access Console; the other is used for the CPU-Mounting Programming Console. The
C200H-CPU11-E, however, has a third connector that is used for connecting the
SYSMAC LINK Unit or the SYSMAC NET Link Unit to the CPU.
To connect the Handheld Programming Console to the CPU, a Connecting
Cable is required, as shown in the following diagram.
Note If you are using the SYSMAC LINK Unit or SYSMAC NET Link Unit in your system, you must use model C200H-CPU11-E as the CPU. The other two models mentioned above are not equipped with the appropriate connectors.
Cable Connection
Handheld
Programming Console
Connecting Cable
Direct Mounting
The CPU-mounting Programming Console can be mounted directly to the CPU and does not require a Connecting Cable. To mount the CPU-Mounting Programming Console (or any other peripheral device) directly to the CPU, follow the steps below.
The CPU-mounting Programming Console, when mounted to the CPU, covers the two I/O Units located directly to the left of the CPU. For this reason it is important to know which shapes can be mounted to these slots.
Notice, in the following diagram, that the two I/O Units mounted directly to the left of the CPU are A-shape Units. The CPU-mounting Programming Console can be mounted to the CPU provided A-shape I/O Units are mounted to these two slots. Make sure the protective covers of the two I/O Units are in place to avoid electrical interference with the CPU.
Because the surface of B-shape and E-shape I/O Units protrudes a few centimeters from surface of the CPU, B-shape and E-shape I/O Units cannot be mounted to the two slots to the left of the CPU unless a Programming Console
Base Unit is first mounted to the CPU to increase the mounting height of the Programming Console.
13
Downloaded from Elcodis.com
electronic components distributor
CPU Section 2-2
If you are using the C200H-CPU11-E, a SYSMAC LINK Unit or a SYSMAC LINK
Unit can be mounted to either of the two slots to the left of the CPU. They are then connected to the CPU with the Bus Connector Unit.
Peripheral device
CPU Rack
A-shape I/O Units
1, 2, 3...
1. Remove the cover from the peripheral device connector with a standard screwdriver.
2. Connect the CPU-Mounting Programming Console to the peripheral device connector.
3. Attach the CPU-Mounting Programming Console to the CPU by tightening the mounting screws.
14
Downloaded from Elcodis.com
electronic components distributor
Expansion I/O Rack Section 2-3
2-3 Expansion I/O Rack
The Backplane used to construct a CPU Rack is also used to construct an Expansion I/O Rack. An Expansion I/O Rack is identical to a CPU Rack, except the
CPU has been replaced with a Power Supply. The parts of an Expansion I/O
Rack are shown in the following diagram.
I/O Connecting Cable Connector
Connects Expansion I/O Rack to preceding Expansion I/O Rack or to CPU.
Backplane Power Supply
I/O Connecting Cable Connector.
Connects Expansion I/O Rack to next Expansion I/O Rack.
When not used, cover with a cap.
I/O Units
Backplane mounting screws
(four, with 4-mm dia. heads)
Downloaded from Elcodis.com
electronic components distributor
15
Power Supply Section 2-4
2-4 Power Supply
The Power Supply used for Expansion I/O Racks is available in two models. One runs on 100 to 120 or 200 to 240 VAC, and the other runs on 24 VDC.
AC Power Supply
POWER indicator (green)
Lights when power is supplied to Power Supply
Power fuse 2 A 250 V
(5.2-dia. x 20) MF51NR
Terminals for external connections
+
NC
NC
AC Input
Voltage selector terminals
Short: 100 to
120 VAC
Open: 200 to
240 VAC
LG
GR
24 VDC
0.3 output
16
Downloaded from Elcodis.com
electronic components distributor
Power Supply
DC Power Supply
POWER indicator (green)
Lights when power is supplied to Power Supply
Power fuse 5 A 125 V
(5.2-dia. x 20)
MF51NR
Section
Terminals for external connections
+
+
24 VDC
NC
NC
NC
NC
NC
NC
LG
GR
(See note.)
Note The LG and GR terminals are connected internally.
2-4
Downloaded from Elcodis.com
electronic components distributor
17
I/O Units
2-5 I/O Units
A-shape I/O Units
Section 2-5
I/O Units come in three shapes: A-shape, B-shape, and E-shape. Refer to Appendix B Specifications for the dimensions of each Unit.
I/O Unit lock notch
Nameplate
I/O indicators
Indicate ON/OFF status of points
10-terminal terminal block
B-shape I/O Units
I/O Unit lock notch
Nameplate
I/O indicators
Indicate ON/OFF status of points
19-terminal terminal block
18
Downloaded from Elcodis.com
electronic components distributor
Memory Units
E-shape I/O Units
Section 2-6
I/O Unit lock notch
Nameplate
I/O indicators
Indicate ON/OFF status of points
10-terminal terminal block
2-6 Memory Units
There are three types of Memory Units, having three different types of memory.
The three types of memory are EPROM, EEPROM, and RAM.
Backup Clock 1 Memory
EPROM
Model Capacity Maximum program size
C200H-MP831 8K words 6,974 words
EEPROM C200H-ME431 4K words 2,878 words
C200H-ME831 8K words 6,974 words
RAM C200H-MR431 4K words 2,878 words
C200H-MR831 8K words 6,974 words
C200H-MR432 4K words 2,878 words
C200H-MR832 8K words 6,974 words
---
Battery
Capacitor
NO
NO
Contents for Memory Unit Registration
Fixed DM area
(DM 1000 to DM 1999)
I/O table (see note)
UM (ladder program area)
Note I/O tables are also saved in the Memory Unit at the time of creation. Therefore, if the Memory Unit is set to write-protect, it will be impossible to create an I/O table.
19
Downloaded from Elcodis.com
electronic components distributor
Memory Units
EPROM Unit
EEPROM Unit
RAM Unit
Section 2-6
The data that you wish to store in an EPROM Unit must first be written to an
EPROM Chip, using the PROM Writer. Then the EPROM Chip must be mounted to the inside of the EPROM Unit. Once this has been done, the data cannot be changed. In addition, the data will be retained indefinitely when the power is turned OFF.
Data can be stored in the EEPROM Unit while the Unit is mounted to the PC. The data is retained indefinitely when the power is turned OFF.
Data can be randomly written to and read from the RAM Unit. However, the Unit requires battery or capacitor back-up in order to retain the information when the power is OFF. Units with battery back-up can retain their data for approximately five years at room temperature (25 ° C). Units with capacitor back-up retain their data for approximately 20 days at room temperature, but the length of time varies with temperature as shown below.
Switches on Memory
Units
Battery Failure Flag
20
Capacitor back-up time
(days) 10
7
1
25 50 80
Ambient temperature ( ° C)
Two switches are provided on Memory Units, as shown below.
1
2
ON OFF
Write-enable switch
(SW1)
Initial mode selector
(SW2)
SW1 (the write enable switch) only has an effect if the Unit is a RAM Unit or EE-
PROM Unit. Peripheral devices can only write data to these Memory Units if
SW1 is ON. When you wish to write data to this Memory Unit, make sure SW1 is set to the ON position. After you have finished writing the data to the Memory
Unit, turn SW1 to the OFF position so that the data will be protected from any further changes. If you try to write data to the Memory Unit while SW1 is in the
OFF position, the message “DISABLED ROM” will appear on the Programming
Console.
SW2 Selects what operating mode the PC will be in when power is applied to the
System. If there is no peripheral device connected to the CPU, the PC will enter
RUN mode when power is applied. If a Programming Console is connected to the CPU, the PC will enter the mode that the Programming Console is set to. If a peripheral device other than the Programming Console is connected to the
CPU, the PC will enter the mode specified by SW2.
The C200H-CPU11-E, unlike the other two CPU models, has an additional battery connected to the CPU. A flag, assigned to the bits listed in the following table, indicates where battery failure occurred (in the RAM Unit or in the CPU) and in which Unit.
20
Downloaded from Elcodis.com
electronic components distributor
Memory Units Section 2-6
Model
C200H-CPU01-E/03
C200H-CPU11-E
25308
25308
Bit
AR2404
Function
Battery failure in RAM Unit
Battery failure in RAM Unit or
CPU
Battery failure in CPU
In the following table, the ON/OFF status of the bits indicate where battery failure took place in the C200H-CPU11-E. For example, when bit 25308 is ON the battery in the CPU failed.
25308
ON
ON
ON
OFF
AR2404 Unit in which the battery failed
CPU
RAM Unit
Downloaded from Elcodis.com
electronic components distributor
21
Downloaded from Elcodis.com
electronic components distributor
SECTION 3
Assembly Instructions
When we speak of a PC, we usually think of it as a single object. But actually even the simplest PCs are usually composed of several different devices. In fact a single PC can be physically spread throughout a building, but we still call it one PC.
3-1 Mounting the Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-2 Memory Packs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-3 System Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
23
Mounting the Units Section 3-1
3-1 Mounting the Units
There is no single Unit that can be said to constitute a Rack PC. To build a Rack
PC, we start with a Backplane. The Backplane for the C200H is shown below.
C200H Backplane
The Backplane is a simple device having two functions. The first is to provide physical support for the Units to be mounted to it. The second is to provide the connectors and electrical pathways necessary for connecting the Units mounted to it.
The core of the PC is the CPU. The CPU contains the program consisting of the series of steps necessary for the control task. The CPU has a built-in power supply, and fits into the rightmost position of the Backplane.
The CPU of the C200H has no I/O points built in. So, in order to complete the PC we need to mount one or more I/O Units to the Backplane. Mount the I/O Unit to the Backplane by locking the top of the I/O Unit into the slot on the Backplane and rotating the I/O Unit downwards as shown in the following diagram. Press down on the yellow tab at the bottom of the slot, press the I/O Unit firmly into position, and then release the yellow tab.
24
Downloaded from Elcodis.com
electronic components distributor
Mounting the Units Section 3-1
The figure below shows one I/O Unit mounted directly to the left of the CPU.
I/O Units are where the control connections are made from the PC to all the various input devices and output devices. As you can see from the figure above, there is still some space available on the left side of the Backplane. This space is for any additional I/O Units that may be required.
The figure above shows a total of eight I/O Units mounted to the Backplane. I/O
Units come in three shapes; A-shape, B-shape, and E-shape (refer to Appendix
B Specifications for dimensions). Normally, only A-shape I/O Units can be mounted to the two rightmost I/O Unit positions on the Backplane (the ones next to the CPU). This is so that there will be enough room to mount peripheral devices such as a Programming Console to the CPU. However, if you use a Programming Console Base Unit to increase the mounting height of the Programming Console, you will be able to mount the Programming Console to the CPU even if there are B-shape and/or E-shape I/O Units mounted to the two rightmost slots.
The C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1
B7A Interface Unit can be mounted only to a C200H-BC jj 1-V1/V2 Backplane.
If a Backplane other than these two models is used, the Units will not operate properly.
Backplanes are available in different lengths (three, five, eight, ten slots), and can hold a different number of I/O Units accordingly (refer to Appendix B Specifications for dimensions). Of course, not all I/O Units look exactly alike, but the ones in the figure show their typical appearance. This configuration of Backplane, CPU, and I/O Units is called a CPU Rack. This term refers to the Backplane and all the Units mounted to it. However, if we want to include more than eight I/O Units in our configuration we can add an additional Backplane.
25
Downloaded from Elcodis.com
electronic components distributor
Mounting the Units Section 3-1
This Backplane has I/O Units mounted to it, but it has no CPU of its own. The additional Backplane must also have an Expansion I/O Power Supply mounted to its rightmost position. This configuration of additional Backplane, Expansion
I/O Power Supply, and I/O Units is called an Expansion I/O Rack.
The CPU Rack and Expansion I/O Rack shown above are connected by a Connecting Cable (the length of Cable between individual Racks can be up to 10 m, but the total length of Cable between all Racks must be within 12 m).
Remember that this whole configuration is still referred to as one PC. It is possible to add up to two Expansion I/O Racks to one CPU Rack. When installing I/O
Connecting Cables, cover any unused connectors with the caps provided.
26
Downloaded from Elcodis.com
electronic components distributor
Memory Packs Section 3-2
3-2 Memory Packs
The CPU has a removable Memory Pack that stores the user program. Memory
Packs are available with three types of memory; EPROM, EEPROM, and RAM
(refer to Section 2-6 Memory Packs). If this is your first C200H, then you must have a RAM Pack in order to write and test the program you are going to use. If this is not your first C200H and you have a complete, tested program already, you can copy the program to an EPROM or EEPROM Pack for use on this
C200H. The EEPROM chip can be written to without removing the chip from the
Memory Pack by using an appropriate peripheral device (refer to Appendix C
Standard Models). The EPROM Chip may be programmed using a PROM Writer or a FIT Ladder Pack. Then the EPROM Chip must be mounted inside the
EPROM Pack.
Note Only PROM Writer Model C500-PRW06 may be used with the SYSMAC C200H.
How to Mount an
EPROM Chip to the
Memory Pack
After the data has been written to the EPROM Chip, mount it to the inside of the
EPROM Pack by following these steps.
1, 2, 3...
1. Remove the cover of the EPROM Pack as shown below.
2. Unlock the holding bracket and slide it upward to remove it as shown below
Downloaded from Elcodis.com
electronic components distributor
3. Pull the printed circuit board out of the EPROM Pack.
27
Memory Packs Section 3-2
4. On the printed circuit board there is a socket for the EPROM Chip. On the socket you will find a notch. Align the notch on the socket with the notch on the EPROM Chip and mount the EPROM Chip to the socket as shown below.
28
Downloaded from Elcodis.com
electronic components distributor
Notch
5. Reassemble the EPROM Pack in the reverse order of disassembly. During reassembly, ensure that the circuit board is inserted along the guides on the top and bottom of the Pack housing and that the projections on the housing fit into the holes in the holding bracket. Be sure to lock the holding bracket into the right side of the housing. When reassembled, the Pack should appear as shown below.
Circuit board guide
Bracket
Hole
Holding bracket
Circuit board
Circuit board guide
System Configurations Section 3-3
How to Mount the
Memory Pack to the CPU
Mount the Memory Pack to the CPU by following the steps below.
1, 2, 3...
1. Turn OFF the power to the PC.
!
Caution Do not attempt to mount the Memory Pack to the CPU while the power to the PC is ON. Doing so may cause data to be lost, or may damage the CPU or Memory
Pack.
2. Set the selector switches on the Memory Pack to the desired positions (refer to Section 2-6 Memory Packs).
3. Insert the Memory Pack into its compartment as shown below. As you do this, you will feel a slight resistance as the connector on the Memory Pack mates with the connector on the CPU. Continue pushing on the Memory
Pack until it is inserted completely into the CPU.
Guide
Guide
3-3 System Configurations
When building your C200H system there may be some restrictions depending on the Unit you are using and the Rack you are mounting it to. The following figure shows an assembled CPU Rack, Expansion I/O Rack, and Remote I/O
Slave Rack. Use it as a quick reference when assembling your PC. For details about the individual Units, refer to that Unit’s operation manual.
The items listed below should be kept in mind.
•
The SYSMAC LINK Unit and the SYSMAC NET Link Unit are always mounted to either of the two slots to the left of the C200H-CPU11-E CPU. When using
SYSMAC NET, a power supply adapter is mounted to the left of the Units.
•
The C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1
B7A Interface Unit can be mounted only to a C200H-BC jj
1-V1/V2 Backplane.
29
Downloaded from Elcodis.com
electronic components distributor
System Configurations Section 3-3
Special I/O Units
•
Up to ten Special I/O
Units can be mounted.
•
Mount Special I/O Units to any slot on the CPU
Rack (except the two slots to the left of the
CPU) or the Expansion
I/O Rack.
Host Link Unit and
Remote I/O Master Unit
•
Up to two Units can be mounted.
•
Host Link Units and Remote I/O Master Units can be mounted to any slot on the CPU Rack
(except the two slots to the left of the CPU) or the the Expansion I/O Rack.
I/O Units
•
I/O Units available with 5, 8,
12, or 16 points.
•
Units available with 10- or
19-terminal terminal blocks.
•
Units with 5 and 8 points have 10-terminal terminal blocks and Units with 10 and
12 points have 19-terminal terminal blocks.
•
There are some restrictions on the mounting position of
19-terminal I/O Units (refer to
Appendix B Specifications).
Memory Packs
•
RAM, EPROM, or EE-
PROM Packs available.
•
EEPROM requires an optional EEPROM Chip.
•
EPROM requires a separately available EPROM
Chip.
SYSMAC NET LINK Unit and SYSMAC LINK Unit
•
Use up to two Units, mounted to either of the two slots to the left of the CPU.
•
When using either of these two Units the use of peripheral devices is limited. Refer to
Section 4-3 Maximum Current and Power
Supplied.
CPU
Built-in power supply
I/O Unit Cover
For 10-terminal block I/O Units
Backplane
3-, 5-, 8-, 10-slot types available
Expansion I/O Racks
Up to two Expansion I/O
Racks can be connected to one CPU Rack.
Expansion I/O Power Supply
I/O Connecting Cable
•
Available in lengths from 30 cm to 1 m.
•
Total length of I/O Connecting Cables between all Racks must not exceed 12 m.
Remote I/O Slave Unit
Up to five Units can be connected.
Backplane
3-, 5-, or 8-slot types available
Remote I/O Slave Unit
Power supply built-in
Optical Fiber Cable or Wire Cable
30
Downloaded from Elcodis.com
electronic components distributor
SECTION 4
System Connections
In the preceding sections we have covered what all the parts of a PC are and how they should be assembled. This section provides detailed information about the types of considerations involved in making all of the PC connections. Also included in this section are considerations that should be kept in mind when using the C200H-CPU11-E as the CPU.
4-1 IR Word Allocation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-2 Remote I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3 Maximum Current and Power Supplied . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-4 I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
31
IR Word Allocation Section 4-1
4-1 IR Word Allocation
Each slot of the Backplane is assigned a hardware word number. This word is accessible for I/O use only in the given slot. However, standard I/O Units are available in 5-, 8-, 12-, and 16-point models. If an I/O Unit other than a 16-point model is mounted, the unused points of that word are accessible only as “work bits” (refer to the C200H Operation Manual). The number of I/O bits available for the entire system, therefore, varies according to the model of I/O Units used, as well as the model of Backplanes used. The figure below shows the relationship between the model of I/O Unit and work bits. The shaded bits can only be used as work bits.
5-point Unit
09
10
11
12
13
14
15
04
05
06
07
08
00
01
02
03
8-point Unit
09
10
11
12
13
14
15
04
05
06
07
08
00
01
02
03
12-point Unit
09
10
11
12
13
14
15
04
05
06
07
08
00
01
02
03
16-point Unit
09
10
11
12
13
14
15
04
05
06
07
08
00
01
02
03
32
Downloaded from Elcodis.com
electronic components distributor
IR Word Allocation Section 4-1
The CPU Rack begins with word 000 at the leftmost slot. The first Expansion I/O
Rack begins with word 010, and the second Expansion I/O Rack with word 020.
The first word of each Rack is fixed, regardless of the model of Backplane used.
As with the I/O bits unused by individual I/O Units, the bits of the I/O words unused by a Backplane can be used as work bits. The following figure shows the relationship between the model of Backplane and I/O words. The shaded bits can only be used as work bits.
C200H-BC031 Backplane
Word 000
00 bits
15
001 002 003 004
00 00 00 00
005
00
15 15 15 15 15
006
00
15
C200H-BC051-V1 Backplane
007
00
15
008
00
15
009
00
15
Word 000
00 bits
15
001 002 003 004
00 00 00 00
15 15 15 15
005
00
15
006 007 008 009
00 00 00 00
15 15 15 15
Word 000
00 bits
15
C200H-BC081-V1 Backplane
001 002 003 004
00 00 00 00
005
00
006
00
007
00
008
00
009
00
15 15 15 15 15 15 15 15 15
Note The C200H-OC225/OD212/OD21A 16-point Output Unit and C200H-B7AO1
B7A Interface Unit can be mounted only to a C200H-BC 1-V1/V2 Backplane.
For example, if a PC consists of three 8-slot Racks with 8-point I/O Units mounted to all I/O Unit mounting positions, the number of I/O points for the entire
PC will be:
8 points x 8 slots x 3 Racks = 192 points
If a PC consists of three 8-slot Racks with the I/O Unit mounting positions equally divided between 16-point Input Units and 12-point Output Units, the number of
I/O points for the entire PC will be:
Input points = 16 points x 4 slots x 3 Racks = 192 points
Output points = 12 points x 4 slots x 3 Racks = 144 points
Total I/O points = 192 + 144 = 336
33
Downloaded from Elcodis.com
electronic components distributor
Remote I/O Section 4-2
The following figure shows the word allocation for a fully expanded C200H with three 8-slot Backplanes.
word
000 word
001 word
002 word
003 word
004 word
005 word
006 word
007
CPU word
010 word
011 word
012 word
013 word
014 word
015 word
016 word
017
Power
Supply word
020 word
021 word
022 word
023 word
024 word
025 word
026 word
027
Power
Supply
4-2 Remote I/O
There are limits to how long the normal wiring between the PC and its Expansion
I/O Racks can be. A Remote I/O Unit can extend this distance greatly, so that the
PC and its Expansion I/O Racks can even be located in separate buildings.
There are two types of Remote I/O Systems, optical and wired.
By locating a Rack farther from the CPU Rack, a Remote I/O System eliminates the time and mess in wiring (or changing wiring) to many devices that are separated from the CPU Rack. Although all I/O points must ultimately be wired individually, the question is one of distance: Do you want to wire dozens of terminals all the way across a factory complex or do you want to run a single cable for most of the distance and then wire individual terminals locally? A PC with an Expansion I/O System is called an Expanded PC.
I/O words 100 through 199 and DM words 1000 through 1999 are allocated to
Special I/O Units. There are limitations to the number and model of Special I/O
Units that can be mounted to a Remote I/O Slave Rack. Provided no other models of Special I/O Units are mounted to a Remote I/O Slave Rack, the maximum number of Special I/O Units that can be mounted is shown below for each model.
Group
A
B
C
D
Units
High-speed Counter, Position Control
(NC111/NC112), ASCII, Analog I/O, ID Sensor,
Fuzzy Logic Unit
High-density and Mixed I/O, Cam Positioner,
Temperature Control, PID Control, Heat/Cool
Temperature Control
Temperature Sensor, Voice
Position Control (NC221)
Total number
4 Units
8 Units
6 Units
2 Units
When using a combination of A, B, C, and D Units on a Remote I/O Slave Rack, the number of each model of Unit being used must satisfy the following two formulas.
3A + B + C + 6D 12
A + B + C + D 8
34
Downloaded from Elcodis.com
electronic components distributor
Maximum Current and Power Supplied Section 4-3
In addition, when PC Link Units are used, a maximum of ten Special I/O Units and PC Link Units total can be mounted to one Expanded PC. When a High-density I/O Unit is mounted to a Remote I/O Slave Rack, the RM001-PV1 or RM201
Remote I/O Master Unit must be used.
4-3 Maximum Current and Power Supplied
The power supplies, including those built in the CPUs, are limited in the total current they can supply to I/O units.
The table below shows the maximum currents supplied by each power supply.
There are three categories in the “Maximum current supplied”:
1, 2, 3...
1. The 5-V internal logic current powers I/O Cards and communications cards.
Refer to the deductions table to determine what trade-offs must be made when the total I/O and peripherals exceed the CPUs internal logic current capacity.
2. The 26-V relay current powers relay output cards and ID Sensor Units.
3. Finally, the external 24-VDC power supply on the CPU powers external input devices.
The total wattage of all three categories cannot exceed the wattage listed in the last column, “Maximum power”.
You should not exceed any of the individual current ratings for the voltage supplied by any single unit, nor should you exceed the total maximum power output.
Current Supplied
Name Model number Maximum power
CPU Rack
Expansion
I/O Rack
Slave Rack
C200H-CPU01-E
C200H-CPU03-E
C200H-CPU11-E
C200H-PS221
C200H-PS211
C200H-RT001-P
C200H-RT002-P
C200H-RT201
C200H-RT202
5 V
(internal logic current)
Max. current supplied
26 V
(relay current)
24 V
(No-voltage contact current)
1.6 A 0.6 A
1.4 A
2.7 A 0.6 A
0.8 A
---
0.8 A
0.8 A
2.7 A 0.6 A
---
0.8 A
---
0.8 A
---
23 W
18 W
22 W
28 W
23 W
28 W
23 W
28 W
23 W
Note The figures shown in the “maximum current supplied” and “maximum power supplied” columns are computed with the power consumed by the Backplanes,
CPU, Memory Cassettes, Peripheral Devices, I/O Power Supply Units, and
Slave Units already calculated.
Design the system so that the following two conditions are satisfied.
Condition 1
(1) (Total current consumption of all Units in the 5-V system) ≤ (the figure in the
5-V column)
(2) (Total current consumption of all Units in the 26-V system) ≤ (the figure in the
26-V column)
(3) (Total current consumption of all Units in the 24-V system) ≤ (the figure in the
24-V column)
Condition 2
(1) x 5 V + (2) x 26 V + (3) x 24
≤
(maximum power supplied)
35
Downloaded from Elcodis.com
electronic components distributor
Maximum Current and Power Supplied Section 4-3
Deductions Table
CPU11-E 5-V consumption (I/O card)
≤
1.4 A
> 1.4 A, but
> 1.7 A, but
≤
1.7 A
≤
1.9 A
> 1.9 A, but
≤
2.1 A
CPU01/03-E 5-V consumption (I/O card)
≤
1.6 A
> 1.6 A, but
> 1.9 A, but
≤
1.9 A
≤
2.1 A
> 2.1 A, but
≤
2.3 A
Peripheral device deductions
None
PROM Writer and CPU-mounting Host Link Unit
PROM Writer, CPU-mounting Host Link Unit, Peripheral Interface
Unit
PROM Writer, CPU-mounting Host Link Unit, Peripheral Interface
Unit, and Printer Interface Unit
Current Drawn from 5-V
Supply
Unit
DC Input
No-Voltage Contact
Input
AC Input
AC/DC Input
Contact Output
Transistor Output
Triac Output
Analog Timer Unit
B7A Interface Unit
Host Link
PC Link
Remote Master
SYSMAC LINK Unit
Model number
C200H-ID211
C200H-ID212
C200H-ID001
C200H-ID002
C200H-IA121
C200H-IA122/IA122V
C200H-IA221
C200H-IA222/IA222V
C200H-IM211
C200H-IM212
C200H-OC221
C200H-OC222
C200H-OC223
C200H-OC224
C200H-OC225
C200H-OD411
C200H-OD211
C200H-OD212
C200H-OD213
C200H-OD214
C200H-OD216
C200H-OD217
C200H-OD21A
C200H-OA121-E
C200H-OA122-E
C200H-OA223
C200H-OA222V
C200H-OA224
C200H-TM001
C200H-B7AI1
C200H-B7AO1
C200H-LK101-PV1
C200H-LK201-V1
C200H-LK202-V1
C200H-LK401
C200H-RM001-PV1
C200H-RM201
C200HW-SLK13/SLK14/
SLK23/SLK24
Current consumption
0.01 A each
0.05 A
0.14 A
0.16 A
0.18 A
0.14 A
0.01 A each
0.25 A
0.15 A
0.25 A
0.35 A
0.20 A
0.25 A
0.8 A
0.16 A
0.14 A
0.18 A
0.18 A
0.20 A
0.27 A
0.06 A
0.10 A
36
Downloaded from Elcodis.com
electronic components distributor
Maximum Current and Power Supplied Section 4-3
Unit Model number
SYSMAC NET Link Unit C200HS-SNT32
Feed Adapter C200H-APS01/ASP02
TTL Input
DC Input
C200H-ID501
C200H-ID215
TTL Output
Transistor Output
TTL I/O
DC Input/Transistor
Output
High-speed Counter
C200H-OD501
C200H-OD215
C200H-MD501
C200H-MD115
C200H-MD215
Position Control
C200H-CT001-V1
C200H-CT002
C200H-NC111
C200H-NC112
Analog Input
Temperature Control
C200H-NC211
C200H-AD001
C200H-AD002
C200H-DA001
C200H-DA002
C200H-TC001
C200H-TC002
C200H-TC003
C200H-TC101
C200H-TC102
Heat/Cool Temperature l U i
PID Control Units
Temperature Sensor
Input
ASCII
Voice Output
ID Sensor
Fuzzy Logic Unit
Cam Positioner
C200H-TC103
C200H-TV001
C200H-TV002
C200H-TV003
C200H-TV101
C200H-TV102
C200H-TV103
C200H-PID01
C200H-PID02
C200H-PID03
C200H-TS001/TS002
C200H-TS101/TS102
C200H-ASC02
C200H-OV001
C200H-IDS01-V1
C200H-IDS21
C200H-FZ001
C200H-CP114
Current consumption
1.0 A
0 A
0.13 A
0.22 A
0.18 A
0.30 A
0.15 A
0.15 A
0.50 A
0.55 A
0.45 A
0.65 A
0.6 A
0.33 A
0.33 A
0.33 A
0.45 A
0.35 A
0.15 A
0.30 A
0.25 A
0.30 A
0.30 A
Current Drawn from 26-V
Supply
Unit
Contact Output
Transistor Output
ID Sensor
Model number
C200H-OC221/OC222/OC223/
OC224/OC225
C200H-OD216/OD217
C200H-IDS01-V1/IDS21
Current consumption
0.075 A*
0.12 A
37
Downloaded from Elcodis.com
electronic components distributor
Maximum Current and Power Supplied Section 4-3
Current Drawn from 24-V
Supply
Note *With all eight bits on simultaneously.
Unit Model number
No-Voltage Contact
Input Units
C200H-ID001/ID002
Calculation Examples
Example 1
Example 2
Example 3
Current consumption
0.06 A
The total power consumption for each Rack can be obtained from the following formulas:
CPU Rack =
Total power consumption for each Unit + 7 (8)
0.6 x 0.55 (1)
(VA)
7 = CPU power consumption, (8) = Power consumption of the CPU11-E
0.6 = 60% efficiency
0.55 (1) = Power rate (Number in parentheses: when CPU03-E is used.)
All other Racks =
Total power consumption for each Unit + 2
0.6 x 0.55 (1)
(VA)
2 = I/O Power Supply Unit (Remote I/O Slave Unit) power consumption
0.6 = 60% efficiency
0.55 (1) = Power rate (Number in parentheses: when PS211, RT002-P or RT202 is used.)
Assume that four Contact Output Units, three No-Voltage Contact Input Units, and one Host Link Unit are mounted to a Rack, along with CPU01-E. The following table shows how the total power consumption is calculated.
Voltage
5 V
26 V
24 V
Total
Current consumption
(1) 0.01 x 7 + 0.25 = 0.32 A (
≤
1.6 A)
(2) 0.075 x 4 = 0.30 A (
≤
0.6 A)
(3) 0.06 x 3 + 0.3 = 0.48 A (
≤
0.8 A)
---
Power consumption
(1) x 5 V = 1.6 W
(2) x 26 V = 7.8 W
(3) x 24 V = 11.52 W
20.92 W (
≤
23 W)
Assume that six DC Input Units and two High-speed Counter Units are mounted to a Rack, along with the PS221 Power Supply. The following table shows how the total power consumption is calculated.
Voltage
5 V
26 V
24 V
Total
Current consumption
(1) 0.01 x 6 + 0.3 x 2 = 0.66 A (
≤
2.7 A)
Power consumption
(1) x 5 V = 3.3 W
(2) 0 (2) 0
(3) Service power supply = 0.8 A (
≤
0.8A) (3) x 24 V = 19.2 W
--22.5 W (
≤
28 W)
Assume that the following Units are mounted to a Rack to which a C200H-
CPU11-E is mounted. The following table shows how the total power consumption is calculated.
Voltage
5 V
26 V
24 V
Total
Current consumption
(1) 0.01 x 6 + 0.18 = 0.24 A (
≤
1.1 A)
(2) 0.075 x 4 = 0.30 A(
≤
0.6 A)
(3) 0.06 x 2 + 0.3 = 0.42 A(
≤
0.8 A)
---
•
Peripheral Interface Unit (IP006)
• SYSMAC LINK Units (SLK22):
• Contact Output Units (OC221):
•
No-Voltage Contact Input Units (ID001):
1
6
2
Power consumption
(1) x 5 V = 1.2 W
(2) x 26V = 7.8 W
(3) x 24 V = 10.08 W
19.08 W (
≤
20.5 W)
38
Downloaded from Elcodis.com
electronic components distributor
Maximum Current and Power Supplied
Example 4
Calculation of Power
Consumption for Each
Rack (Examples)
Section 4-3
• High-density and Mixed I/O Units (MD215):
• Current for MD215:
1
0.3 A
Assume that the following Units are mounted to a rack to which is mounted the
C200H-CPU11-E. The following table shows how the total power consumption is calculated.
Voltage
5 V
26 V
24 V
Total
Current consumption
(1) 0.01 x 5 + 0.3 x 1 = 0.35 A (
≤
0.7 A)
(2) 0
(3) Current=0.5 A(
≤
0.8 A)
---
Power consumption
(1) x 5 V = 1.75 W
(2) 0
(3) x 24 V = 12 W
13.75 W (
≤
18.5 W)
•
Peripheral Interface Unit (IP006)
• SYSMAC NET Link Units (SNT32):
•
Central Power Supply Adapter (Current 0):
•
DC Input Units (ID212):
• High-speed Counter Units (CT002):
•
Current for ID212:
1
1
5
1
0.5 A
The total power consumption for each Rack can be obtained from the following formulas:
•
CPU Rack: Total power consumption for each Unit + 7 (8)
0.6 x 0.55 (1)
(VA)
Where:
7 = Power consumption of the CPU,
(8) = Power consumption of the CPU11-E,
0.6 = 60% efficiency, and
0.55 (1) = Power rate (Number in parentheses: when CPU03-E is used.)
•
Expansion I/O Power Supply/Remote I/O Slave Unit:
Total power consumption for each Unit + 2
0.6 x 0.55 (1)
Where:
2 = Power consumption of the I/O Power Supply or
Remote I/O Slave Unit,
0.6 = 60% efficiency, and
0.55 (1) = Power rate (Number in parentheses: when
PS211, RT002-P or RT202 is used.)
(VA)
39
Downloaded from Elcodis.com
electronic components distributor
I/O Connections Section 4-4
4-4 I/O Connections
Connect the I/O Devices to the I/O Units using AWG 22 (cross-sectional area of
0.3 mm
2
) for 19-terminal terminal blocks and AWG 22 to 18 lead wire (cross-sectional area of 0.3 to 0.75 mm
2
) for 10 terminal terminal blocks. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown below. Tighten the screws with a torque of 0.8 N S m.
Terminal Block
If you wish to attach solderless type terminals to the ends of the lead wires, use terminals having the dimensions shown below.
7 mm max.
7 mm max.
The terminal block of an I/O Unit can be removed by loosening the mounting screws. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit.
Locks for terminal block.
Unlock to remove the terminal block from the I/O Unit. Make sure the terminal block is locked securely after wiring is complete.
40
Downloaded from Elcodis.com
electronic components distributor
I/O Connections
I/O Unit Cover
Section 4-4
A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the illustration below.
Attach
Remove
I/O Unit cover
DC Two-wire Sensor
Connection Precautions
If a two-wire sensor is used with a 12-VDC or 24-VDC input device, make sure that the following conditions are satisfied. Malfunctions will occur if these conditions are not satisfied.
• The relationship between the PC ON voltage and the sensor residual voltage is as follows:
V
ON x
V
CC
– V
R
•
The relationship between the PC ON current and the sensor control output
(load current) is as follows:
I
OUT (min)
I
ON
= (V x
CC
I
ON
– V
R x I
OUT (max)
– 1.5 (PC internal residual voltage))/R
IN
Connect R bleeder resistance if I
ON is less than I
OUT (min)
.
The constant for bleeder resistance is determined by the following equation.
R x
(V
CC
– V
R
)/(I
Power W y
(V
OUT (min)
CC
– V
R
)
2
– I
ON
)
/R 4 (margin)
• The relationship between the PC OFF current and sensor leakage current is as follows:
I
OFF x I leak
Refer to the information on input and output leakage current on page 56 for details.
The value of I
OFF
depends on the Unit used. For Input Units that have an unspecified OFF current, however, the value of I
OFF is always 1.8 mA.
DC Input Unit
Two-wire sensor
V
R R R
IN
V
CC
Wiring Examples
V
CC
:
V
ON
:
I
ON
:
I
OFF
:
R
IN
:
Power supply voltage
PC ON voltage
PC OFF current
PC OFF current
PC input impedance
V
R
:
I
OUT
:
I leak
:
R:
Sensor output residual voltage
Sensor control output (load current)
Sensor leakage current
Bleeder resistance
The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output
Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix B Specifications).
41
Downloaded from Elcodis.com
electronic components distributor
I/O Connections
DC Input Units
Section 4-4
Contact output
IN DC input
COM
When using the configuration shown below, the sensor and Input Unit should receive their power from the same supply.
NPN current output
+
Current regulator
IN DC input
Output
7 mA
0 V
Sensor
Power
Supply
COM
NPN open-collector output
+
Sensor
Power
Supply
IN DC input
Output
7 mA
0 V
COM
PNP current output
+
Output
7 mA
0 V
0 V
Sensor
Power
Supply
IN AC/DC input
COM
The circuit below should be used for I/O devices having a voltage output.
Voltage output
+
COM
Output
IN DC input
0 V Sensor
Power
Supply
The circuit below should NOT be used for I/O devices having a voltage output.
Voltage output
+
Output
Sensor
Power
Supply
IN DC input
0 V
COM
42
Downloaded from Elcodis.com
electronic components distributor
I/O Connections
AC Input Units
Section 4-4
Contact output
IN AC input
COM
AC Switching
Prox.
switch main circuit
IN AC input
COM
Output Units
!
Caution When using Reed switch as the input contacts for AC Input Units, be sure the allowable current of the switch is at least 1 A. Using switches with lower capacities may cause the contacts to fuse due to surge current.
A fuse placed in the output circuit will protect the output element, circuit board, etc., in the event of a short circuit in the output circuit. Although some transistor
Output Units and Triac Output Units have a built-in fuse, it is recommended that you connect an external fuse to each Output Unit for extra safety and ease of maintenance.
Downloaded from Elcodis.com
electronic components distributor
43
Downloaded from Elcodis.com
electronic components distributor
SECTION 5
Installation Environment
This section details the necessary environment and conditions for installation of the PC. For specific instructions on mounting
Units and wiring for I/O and power, refer to Section 2-4 Power Supply and Section 3-3 System Configurations .
5-1 Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-2 Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-3 Duct Work . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5-4 Preventing Noise . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
45
Installation Environment Section 5-1
5-1 Installation Environment
This section details the necessary environmental conditions for installing the
PC.
!
Caution Static electricity can damage PC components. Your body can carry an electrostatic charge, especially when the humidity is low. Before touching the PC, be sure to first touch a grounded metallic object, such as a metal water pipe, in order to discharge any static build-up.
Ambient Conditions
Cooling
Clearance Between
Racks
Cooling Fan
Do not install the PC in any of the following locations. Doing so will affect PC life and may affect operating performance.
•
Locations subject to ambient temperatures lower than 0
°
C or higher than
55
°
C.
• Locations subject to drastic temperature changes or condensation.
• Locations subject to ambient humidity lower than 10% or higher than 90%.
• Locations subject to corrosive or flammable gases.
• Locations subject to excessive dust (especially iron dust) or chloride.
•
Locations that would subject the CPU to direct shock or vibration.
•
Locations that would subject the PC to water, oil, or chemical reagents.
•
Locations exposed to direct sunlight.
There are two points to consider in order to ensure that the PC does not overheat. The first is the clearance between Racks, and the second is installation of a cooling fan.
The Racks need to have sufficient room between each other to allow for I/O wiring, and additional room to ensure that the I/O wiring does not hamper cooling.
However, the Racks must be mounted close enough to each other that the length of the Connecting Cable between any two Racks does not exceed 10 m, and the total length of the Connecting Cables between all Racks does not exceed 12 m. As a general rule, about 70 to120 mm should be left between any two
Racks.
A cooling fan is not always necessary, but may be needed in some installations.
Try to avoid mounting the PC in a warm area, or over a source of heat. A cooling fan is needed if the ambient temperature may become higher than that specified
(refer to Appendix B Specifications). If the PC is mounted in an enclosure, a cooling fan may need to be installed, as shown below, to maintain the ambient temperature within specifications.
Fan
PC
Control Panel
46
Downloaded from Elcodis.com
electronic components distributor
Mounting Requirements Section 5-2
5-2 Mounting Requirements
The PC consists of from one to three Racks. Each Rack must be mounted vertically, that is with the printing on the front panels oriented as it would normally be read. The Racks should be mounted one above the other with the CPU Rack uppermost as shown below.
CPU Rack
These connectors are not used.
Cover them with caps.
Expansion Rack
Expansion Rack
DIN Rail Mounting
The C200H is approved by Underwriters Laboratories under the condition that,
“The device must be mounted vertically for ventilation purposes”.
The PC may be mounted using DIN Rail if desired. This type of mounting is not required, and the PC may be directly mounted to any sturdy support meeting the environmental specifications (refer to Appendix B Specifications). If you want to mount the PC on DIN Rail, you can order a DIN Rail from OMRON (refer to Appendix B Standard Models). DIN Rails come in the two heights shown below.
7.3-mm Height
16-mm Height
47
Downloaded from Elcodis.com
electronic components distributor
Mounting Requirements
DIN Rail Mounting
Bracket
Section 5-2
The DIN Rail Mounting Bracket shown below is necessary for mounting the PC to the DIN Rail.
Procedure
DIN Rail Mounting
Bracket
1, 2, 3...
1. The following diagram is a view of the back of the Backplane. Attach one
Mounting Bracket to the left and right sides of the Backplane as shown below.
Backplane
There are two Backplane mounting screws each on the left and right sides of the Backplane. Use these screws to attach the DIN Rail
Mounting Brackets to the Backplane.
2. Mount the Backplane to the DIN Rail so that the claws on the Mounting
Brackets fit into the upper portion of the DIN Rail as shown below.
This claw fits into the DIN Rail DIN Rail
48
Downloaded from Elcodis.com
electronic components distributor
Backplane
DIN Rail Mounting Bracket
Duct Work Section 5-3
3. Loosen the screws attaching the Mounting Brackets to the Backplane. Slide the Backplane upward as shown below so that the Mounting Bracket and
Backplane clamp securely onto the DIN Rail. Tighten the screws.
DIN Rail Mounting Bracket
Hold-down bracket
DIN Rail
Projections
Slide this screw to the top of the projection and then tighten it.
5-3 Duct Work
If power cables carrying more than 10 A 400 V, or 20 A 220 V must be run alongside the I/O wiring (that is, in parallel with it), at least 300 mm must be left between the power cables and the I/O wiring as shown below.
Low current cable
1
Control cable
2
300 mm min.
Power cable
3
300 mm min.
Grounding at resistance of less than 100 W
Where: 1 = I/O wiring
2 = General control wiring
3 = Power cables
Downloaded from Elcodis.com
electronic components distributor
49
Preventing Noise Section 5-4
If the I/O wiring and power cables must be placed in the same duct (for example, where they are connected to the equipment), they must be shielded from each other using grounded metal plates.
Metal plate (iron)
200 mm min.
1 2 3
Grounding at resistance of less than 100 W
Where: 1 = I/O wiring
2 = General control wiring
3 = Power cables
5-4 Preventing Noise
In order to prevent noise from interfering with the operation of the PC, use AWG
14 twisted-pair cables (cross-sectional area of at least 2 mm 2 ). Avoid mounting the PC close to high-power equipment, and make sure the point of installation is at least 200 mm away from power cables as shown in the following diagram.
Power lines
200 mm min.
PC
200 mm min.
Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring conduit should be used, and it should be long enough to completely contain the
I/O wiring and keep it separated from other cables.
50
Downloaded from Elcodis.com
electronic components distributor
SECTION 6
Power Considerations
Use a commercially available 100 to 120 VAC, 200 to 240 VAC, or 24 VDC power source, according to the model of PC you are using (refer to Appendix B Specifications ). Expansion I/O Racks, if used, must also be connected to the power source. If possible, use independent power sources for the PC, input devices, and output devices. All Racks of the PC may be connected to one power source.
6-1 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-2 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-3 Emergency Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6-4 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
51
Emergency Stop
6-1 Grounding
Section 6-3
The Line Ground (LG) terminal is a noise-filtered neutral terminal that does not normally require grounding. If electrical noise is a problem, however, this terminal should be connected to the Ground (GR) terminal.
To avoid electrical shock, attach a grounded (earth ground) AWG 14 wire (crosssectional area of at least 2 mm
2
) to the GR terminal. The resistance to ground must be less than 100
W
. Do not use a wire longer than 20 m. Care must be taken, because ground resistance is affected by environmental conditions such as soil composition, water content, time of year, and the length of time since the wire was laid underground.
PC operation may be adversely affected if the ground wire is shared with other equipment, or if the ground wire is attached to the metal structure of a building.
When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections.
6-2 Insulation
If a separate ground is being supplied to different Racks, Insulating Plates must be used to insulate the Racks from each other. Insulating Plates are supplied as an accessory (refer to Appendix B Specifications).
6-3 Emergency Stop
An external relay should be used to form an emergency stop circuit that turns the power to the PC OFF in the event of an emergency. An emergency stop routine in the PC program is not sufficient to ensure safety. The circuit shown below is an example of an emergency stop circuit.
MCB1
Power section
MCB2
CR1
Control section
Transformer or noise filter
Twisted
PC
PC RUN
output
CR1
DC voltage regulator
DC input/output
+
-
Surge suppressor
52
Downloaded from Elcodis.com
electronic components distributor
Wiring
Power Failure
Section 6-4
A sequential circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below.
The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms. If the interruption lasts between 10 and 25 ms, the interruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ms (less for the DC Power Supply), the PC will stop operating and the external outputs will be automatically turned OFF. Operation is resumed automatically when the voltage is restored to more than 85% of the rated value.
6-4 Wiring
The following diagrams show the proper way to connect the power source to the
PC. The terminals marked “NC” are not connected internally.
C200H-CPU01-E/CPU11-E
C200H-PS221
Screw (3.5 mm head with self-raising pressure plate)
Voltage selector
Short: 100 to 120 VAC
Open: 200 to 240 VAC
Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC leave them open.
Screw (3.5 mm head with self-raising pressure plate)
1:1 isolation transformer
Breaker
Isolation transformer
•
Noise between the PC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer.
Voltage selector
Short: 100 to 120 VAC
Open: 200 to 240 VAC
Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to
240 VAC, leave them open.
Power line
•
Use AWG 14 twisted pair cable (cross-sectional area of 2 mm 2 min).
AC power source
•
Supply 100 to
120 or 200 to 240
VAC
•
Keep voltage fluctuations within the specified range
(refer to Appendix
B Specifications)
AC Power Supply Wiring Use 1.25-mm 2 cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit.
53
Downloaded from Elcodis.com
electronic components distributor
Wiring
C200H-CPU03-E
Section 6-4
!
Caution Tighten the AC Power Supply terminals on the terminal blocks to the torque of
0.8 N S m. Insufficient tightening may cause short-circuiting, malfunction, or burning.
Screw (3.5 mm head with self-raising pressure plate)
Breaker
•
Supply 24 VDC
•
Keep voltage fluctuations within the specified range
(refer to Appendix
B Specifications)
C200H-PS211
Power Supply Wiring
Screw (3.5 mm head with self-raising pressure plate)
Voltage selector
Short: 100 to 120 VAC
Open: 200 to 240 VAC
Short-circuit these terminals with the shorting bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240
VAC, leave them open.
Power line
•
Use AWG 14 twisted pair cable (cross-sectional area of 2 mm 2 min).
Use 1.25-mm
2
cables or larger. The terminal blocks have screws with 3.5-mm diameter heads and self-raising pressure plates. For connecting to the terminal blocks, use round crimp terminals for 3.5-mm diameter heads. Directly connecting stranded wires to the terminal blocks may cause a short-circuit.
Tighten the terminals on the terminal blocks to the torque of 0.8 N S m.
54
Downloaded from Elcodis.com
electronic components distributor
SECTION 7
Safety Considerations
There are certain safety requirements to be considered when installing the PC. Some of these, such as the emergency stop circuit (refer to Section 2-4 Power Supply ), are part of the initial wiring. The considerations described below should be kept in mind when operating the PC and when connecting I/O devices to the PC.
7-1 Interlock Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7-2 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Downloaded from Elcodis.com
electronic components distributor
55
Wiring Section 7-2
7-1 Interlock Circuits
When the PC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown below to prevent both the forward and reverse outputs from turning ON at the same time.
Interlock circuit
MC2
00501
MC1 Motor clockwise
PC
MC1
00502
MC2 Motor counterclockwise
This circuit prevents outputs MC1 and MC2 from ever both being ON at the same time. Even if the PC is programmed improperly or malfunctions, the motor is protected.
7-2 Wiring
Power Supply Output
Input Leakage Current
The 24 VDC output of the CPU and Expansion I/O Power Supply may be used to power other devices. The output current of these supplies is limited to 0.3 A. A separate power supply must be provided if the devices being powered require a higher current.
When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are connected to the PC as input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below.
Input power supply
Bleeder resistor
R PC
Sensor
If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the value and rating for the bleeder resistor using the following formulas.
I = leakage current in mA
R =
W =
7.2
2.4 x I – 3 k W
2.3
––– W min.
R
max.
56
Downloaded from Elcodis.com
electronic components distributor
Wiring
Output Leakage Current
Output Surge Current
Section 7-2
If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below.
PC
OUT
L
R
Bleeder resistor
COM
Load power supply
Determine the value and rating for the bleeder resistor using the following formula.
R
E on
–––
I
Where
E on
= ON voltage of the load
I = leakage current in mA
R = bleeder resistance
When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and triac Output Units are capable of withstanding a surge current of ten times the rated current. If the surge current for a particular device exceeds this amount, use the circuit shown below to protect the Output Unit.
OUT L
+
R
COM
Another way of protecting the Output Unit lets the load draw a small current
(about one third the rated current) while the output is OFF, significantly reducing the surge current. This circuit (shown below) not only reduces the surge current, but also reduces the voltage across the load at the same time.
R
OUT L
+
COM
Transistor Output
Residual Voltage
When connecting TTL circuits to transistor Output Units, it is necessary to connect a pull-up resistor and a CMOS IC between the two. This is because of the residual voltage left on the transistor output after the output turns OFF.
57
Downloaded from Elcodis.com
electronic components distributor
Wiring
Inductive Load Surge
Suppressor
Electrical Noise
Section 7-2
When an inductive load is connected to an I/O Unit, it is necessary to connect a surge suppressor or diode in parallel with the load as shown below. This is so that the back EMF generated by the load will be absorbed.
L
OUT
Relay Output Unit
Triac Output Unit
Surge suppressor
COM
OUT
L
Relay Output Unit
Transistor Output Unit
+
Diode
COM
Be sure to take appropriate measures when any electrical device likely to produce noise is connected to the PC as a load. Devices generating noise of more than 1,200 V (such as electromagnetic relays and valves) require noise suppression. For noise sources running off of AC power, connect a diode in parallel with the coil of each device.
When mounting a CPU Rack and an Expansion I/O Rack together on a mounting plate, be sure to provide a solid ground the mounting plate. The mounting plate must be plated with a highly conductive surface in order to ensure noise immunity.
58
Downloaded from Elcodis.com
electronic components distributor
Appendix A
Inspection and Maintenance
Certain consumable items in a PC (such as fuses, Relays, or batteries) need occasional replacement. This Appendix explains how to replace each of these items. Refer to Appendix B for the specifications of individual consumable items. Always keep spare items on hand so that they can be used as immediate replacements when needed.
CPU and Power Supply Fuses
Turn counterclockwise to remove, clockwise to attach
Standard screwdriver
To replace a fuse, follow the steps below:
1, 2, 3...
1. Turn OFF the power to the PC.
2. Remove the fuse holder by turning it approximately 50
° counterclockwise with a standard screwdriver.
3. Remove the fuse from the holder.
4. Insert a new fuse.
5. Reattach the fuse holder by turning it approximately 50
° clockwise with a standard screwdriver.
Output Unit Fuses
To replace a fuse, follow the steps below. Use only UL/CSA certified replacement fuses.
Fuse Specifications (5.2-dia. x 20)
Rating Model
C200H-OD411
F indicator (fuse blowout detection circuit)
Yes
C200H-OD211
C200H-OD212
C200H-OD213
No
No
Yes
C200H-OA121-E Yes
C200H-OA122-E Yes
C200H-OA222V No
C200H-OA223 Yes
C200H-OA224 No
5 A 125 V
8 A 125 V
5 A 125 V
3 A 250 V
5 A 250 V
3.15 A 250 V
59
Downloaded from Elcodis.com
electronic components distributor
Inspection and Maintenance Appendix A
1, 2, 3...
1. Turn OFF the power to the PC.
2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.
3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.
4. Remove the screw from the top of the Unit (Phillips screwdriver).
5. Detach the case from the Unit (flat-blade screwdriver).
6. Pull out the printed circuit board.
7. Insert a new fuse. A spare fuse is provided inside the rear of the case when the Unit is delivered.
8. Reassemble in reverse order of assembly.
Output Unit Relays
To replace a Relay, follow the steps below:
1, 2, 3...
1. Turn OFF the power to the PC.
2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.
60
Downloaded from Elcodis.com
electronic components distributor
Inspection and Maintenance Appendix A
3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.
4. Remove the screw from the top of the Unit (Phillips screwdriver).
5. Detach the case from the Unit (flat-blade screwdriver).
OC221/OC224
6. Pull out the printed circuit board. The Relays are placed on the PC boards of individual Units as shown in the figures below.
5
6
3
4
7
0
1
2
61
Downloaded from Elcodis.com
electronic components distributor
Inspection and Maintenance
OC222
Appendix A
5
7
9
11
4
6
8
10
0
1
2
3
OC223
0
1
2
3
4
OC225
8
9
10
11
12
13
14
15
5
6
3
4
7
0
1
2
7. A Relay puller is provided inside the rear of the case when the Unit is delivered. Use the Relay puller to pull out the Relay as shown below. Insert a new
Relay.
Relay puller
Using the Relay puller, pull the relay up and out of the socket.
Printed circuit board
62
Downloaded from Elcodis.com
electronic components distributor
8. Reassemble in reverse order of assembly.
Inspection and Maintenance
Batteries
Appendix A
Some RAM Packs use a battery (refer to Appendix B for specifications). When the battery is nearly discharged, the ALARM indicator blinks and the message
“BATT FAIL” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The battery comes together with its connector as a set. To replace the Battery Set, follow the steps below.
The entire replacement must be completed within five minutes to ensure that the data will not be lost.
If you are using model C200H-CPU11-E as the CPU, the battery is installed in the Unit upon delivery.
1, 2, 3...
1. Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.)
2. Remove the cover from the battery compartment of the RAM Pack.
3. Remove the old Battery Set.
4. Install the new Battery Set as shown shown in the following diagram.
Battery connector
Battery Set
5. Replace the cover of the battery compartment.
6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF and then ON again to clear the error message on the Programming Console.
63
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
Appendix B
Specifications
The following series of figures and tables provides a complete set of specifications for each Unit of the C200H.
Note that I/O Units may take on one of three different shapes. Thus I/O Units are sometimes referred to as A-shape
I/O Units, B-shape, or E-shape I/O Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these three shapes of I/O Unit.
General Specifications
Item
Supply Voltage
Operating Voltage Range
Power Consumption
Surge Current
Output Capacity
Fuse
24 VDC Output
Dielectric Strength
Noise Immunity
Vibration
Shock
Ambient Temperature
Humidity
Atmosphere
Grounding
Degree of Protection
Weight
C200H-CPU01-E, CPU11-E/PS221
100 to 120/200 to 240 VAC selectable
50/60 Hz
85 to 132/170 to 264 VAC
120 VA max. per Rack (Backplane)
Approx. 5 times the normal current
24 VDC
C200H-CPU03/PS211
20.4 to 26.4 VDC
40 W max. per Rack (Backplane)
CPU Rack: 3 A 5 VDC (1.6 A supplied to I/O Units)
Refer to Section 4-4 Special Considerations for C200H-CPU11
Expansion I/O Unit Rack: 3 A 5 VDC (2.7 A supplied to I/O Units)
2 A 250 V 5.2 dia. x 20 (MF51NR) 2 A 125 V 5.2 dia. x 20 (MF51NR)
0.3 A 24 VDC +10% /
–20%
2,000 VAC 50/60 Hz for 1 minute between
AC terminals and housing 500 VAC 50/60
Hz for 1 minute between DC terminals and housing leakage current: 10 mA max.
None
See Caution.
1,000 Vp-p, pulse width: 100 ns to 1 m s, rise time: 1 ns
Mechanical durability: 10 to 35 Hz, 1 mm double amplitude (24.5 m/s 2 ) in X, Y, and Z directions, for 2 hours each (When mounted on DIN Rail, 16.7 Hz, 1 mm double amplitude (4.9 m/s 2 ) in X, Y, and Z directions, for 1 hour each)
Malfunction durability: 2 to 55 Hz, 19.6 m/s 2 , in X, Y, and Z directions, for 20 minutes each (When mounted on DIN Rail, 2 to 55 Hz, 2.94 m/s 2 , in X, Y, and Z directions, for 20 minutes each)
98 m/s
2
in X, Y, and Z directions, 3 times each
Operating: 0 ° to 55 ° C (0 ° to 45 ° C for Programming Console) Storage: –20 ° to 65 ° C
35 to 85% RH (without condensation)
Must be free of the following:
•
Corrosive gases
•
Abrupt temperature changes
•
Direct sunlight
•
Dust, salt, or metal filings
•
Water, oil, or chemicals
Less than 100 W
Mounted in a panel
6 kg max.
!
Caution When conducting an insulation resistance or dielectric strength test, disconnect the power supply terminals from the LG and GR terminals. Do not conduct a dielectric strength test on the C200H-
CPU03-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the
24 VDC Power Supply are not isolated from each other. If a dielectric strength test is conducted, the Power Supply will be damaged.
65
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
CPU Specifications
Main Control Element
Programming Method
Instruction Length
Number of Instructions
Execution Time
Memory Capacity
I/O bits
IR bits
MPU, CMOS, LS-TTL
Ladder diagram
1 address/instruction, 1 to 4 words/instruction
145 (12 basic instructions + 133 special instructions)
C200H-CPU11 159 (12 basic instructions + 147 special instructions)
Basic instructions: 0.75 to 2.25 m s
6,974 words (with 8k-word memory)
Special instructions: 34 to 724 m s
480
(00000 through 02915)
3,296
(03000 through 23515)
I/O Units mounted to Remote I/O Slave
Racks 800 (05000 through 09915)
Special I/O Units
1,600
(10000 through
19915)
Optical I/O Units and I/O Terminals
512
(20000 through
23115)
SR bits
TR bits
HR bits
AR bits
LR bits
Timers/Counters
312 (23600 through 25507)
8 (TR 0 through 7)
1,600 (HR 0000 through 9915)
448 (AR 0000 through 2715
1,024 (LR 0000 through 6315)
512 (TIM/CNT 000 through 511)
TIMHs: 0 through 99.99 s
TIMs: 0 through 999.9 s
CNT: 0 through 9999 counts
DM words Read/write: 1,000 (DM 0000 through 0999)
Read only: 1,000 (DM 1000 through 1999) DM area is in Memory Pack.
RUN Output
Memory Protection
Contacts are closed while PC is in RUN mode and operating.
Max. switching capacity: 2A 250 VAC (resistive load)
0.5 A 250 VAC (inductive load, cos of phase angle = 0.4)
2 A 24 VDC
Status of HR bits, AR bits, preset value of counters (CNT), and contents of data memory
(DM) are retained during power failure. Length of memory protection depends on the
Memory Pack model being used (refer to Section 2-6 Memory Packs).
Self-diagnostic Functions CPU failure (watchdog timer)
Cycle time error
I/O bus failure
Remote I/O error, etc.
Program Check
Battery failure
Memory failure
Host Link error
Program check (executed on start of RUN operation):
END missing Instruction errors
(Program can be checked by Programming Console or GPC at three levels.)
66
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC Input Unit C200H-IA121
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
100 to 120 VAC 50/60 Hz
85 to 132 VAC 50/60 Hz
9.7 k W (50 Hz), 8 k W (60 Hz)
10 mA typical (at 100 VAC)
60 VAC min.
20 VAC max.
35 ms max. (at 100 VAC, 25 ° C)
55 ms max. (at 100 VAC, 25 ° C)
1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 250 g max.
Dimensions A-shape
Circuit Configuration
Appendix B
IN
100 to
120 VAC
IN
COM
0.33
m F 470
W
330 k
W
910
W
Internal circuit
Input LED indicator
Terminal Connections
100 to
120 VAC
COM
3
4
1
2
5
6
7
NC
0
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
67
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC Input Unit C200H-IA122/IA122V
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
100 to 120 VAC 50/60 Hz
85 to 132 VAC 50/60 Hz
9.7 k W (50 Hz), 8 k W (60 Hz)
10 mA typical (at 100 VAC)
60 VAC min.
20 VAC max.
35 ms max. (at 100 VAC, 25 ° C)
55 ms max. (at 100 VAC, 25 ° C)
1 (16 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight IA122: 300 g max.
IA122V: 400 g max.
Dimensions B-shape
Circuit Configuration
Appendix B
IN
100 to
120 VAC
IN
COM
0.33
m
F 470
W
330 k
W
910
W
Internal circuit
Input LED indicator
Terminal Connections
100 to
120 VAC
1
7
9
3
5
11
13
15
COM
A0
A1
A2
A3
A4
A5
A6
0
B0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
12
B7
14
A7
A8
B8
B9
NC
NC
68
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC Input Unit C200H-IA221
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
200 to 240 VAC 50/60 Hz
170 to 264 VAC 50/60 Hz
21 k W (50 Hz), 18 k W (60 Hz)
10 mA typical (at 200 VAC)
120 VAC min.
40 VAC max.
35 ms max. (at 200 VAC, 25 ° C)
55 ms max. (at 200 VAC, 25 ° C)
1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 250 g max.
Dimensions A-shape
Circuit Configuration
Appendix B
IN
0.15
m
F 820 W (IA221)
IN
200 to
240 VAC
COM
680 k
W
910
W
Internal circuit
Input LED indicator
Terminal Connections
100 to
120 VAC
COM
3
4
1
2
5
6
7
NC
0
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
69
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC Input Unit C200H-IA222/IA222V
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
200 to 240 VAC 50/60 Hz
170 to 264 VAC 50/60 Hz
21 k W (50 Hz), 18 k W (60 Hz)
10 mA typical (at 200 VAC)
120 VAC min.
40 VAC max.
35 ms max. (at 200 VAC, 25 ° C)
55 ms max. (at 200 VAC, 25 ° C)
1 (16 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight IA222: 300 g max.
IA222V: 400 g max.
Dimensions B-shape
Circuit Configuration
Appendix B
IN
0.15
m
F 680 W (IA222)
IN
200 to
240 VAC
COM
680 k
W
910
W
Internal circuit
Input LED indicator
Terminal Connections
100 to
120 VAC
1
9
11
13
15
3
5
7
COM
A0
A1
A2
A3
A4
A5
A6
0
B0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
12
B7
14
A7
B8
A8
B9
NC
NC
70
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
No-Voltage Contact Input Unit C200H-ID001
Input Voltage
Input Impedance
Input Current
No-voltage contact/NPN output type (negative common)
3 k W
7 mA typical
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
(14.4 VDC min.)
(5.0 VDC max.)
1.5 ms max. (no-voltage contact, at 25
°
C)
1.5 ms max. (no-voltage contact, at 25 ° C)
1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight
Dimensions
200 g max.
A-shape
Circuit Configuration
Current IN
IN
COM
3 k
W
0.01
m
F
1.8
k
W
Internal circuit
Input LED indicator
0.3 A
24 VDC
Power supply
+
–
Internal 24 VDC power supply
CPU, Expansion I/O Power
Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion
I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections
Current
(NPN output)
COM
NC
0
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
3
4
1
2
5
6
7
71
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
No-Voltage Contact Input Unit C200H-ID002
Input Voltage
Input Impedance
Input Current
No-voltage contact/NPN output type (positive common)
3 k W
7 mA typical
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
(14.4 VDC min.)
(5.0 VDC max.)
1.5 ms max. (no-voltage contact, at 25
°
C)
1.5 ms max. (no-voltage contact, at 25 ° C)
1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight
Dimensions
200 g max.
A-shape
Circuit Configuration
IN
IN
COM
3 k
W
0.01
m
F
1.8
k W
Internal circuit
Current
Input LED indicator
0.3 A
24 VDC
Power supply
+
–
Internal 24 VDC power supply
CPU, Expansion I/O Power
Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion
I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals.
Terminal Connections
Current
(PNP output)
COM
NC
0
A6
A7
A8
A9
A0
A1
A2
A3
A4
A5
5
6
7
1
2
3
4
72
Downloaded from Elcodis.com
electronic components distributor
Specifications
DC Input Unit C200H-ID211
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
12 to 24 VDC
10.2 to 26.4 VDC
2 k W
10 mA (at 24 VDC)
10.2 VDC min.
3.0 VDC max.
1.5 ms max. (at 24 VDC, 25 ° C)
1.5 ms max. (at 24 VDC, 25 ° C)
1 (8 point/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 200 g max.
Dimensions A-shape
Circuit Configuration
Appendix B
IN
IN
12 to 24 VDC
COM
2 k
W
0.01
m
F
1.8
k
W
Internal circuit
Input LED indicator
Terminal Connections
12 to 24 VDC
COM
NC
0
1
2
3
4
5
6
7
A4
A5
A6
A7
A0
A1
A2
A3
A8
A9
73
Downloaded from Elcodis.com
electronic components distributor
Specifications
DC Input Unit C200H-ID212
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
24 VDC
20.4 to 26.4 VDC
3 k W
7 mA (at 24 VDC)
14.4 VDC min.
5.0 VDC max.
1.5 ms max. (at 24 VDC, 25 ° C)
1.5 ms max. (at 24 VDC, 25 ° C)
1 (16 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 300 g max.
Dimensions B-shape
Circuit Configuration
Appendix B
IN
IN
COM
3 k
W
0.01
m
F
1.8
k
W
Internal circuit
24 VDC
Input LED indicator
Terminal Connections
24 VDC
COM
1
3
5
7
9
11
13
15
A0
A1
A2
A3
A4
A5
A6
A7
B8
A8
B9
B0
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
12
B7
14
NC
NC
74
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC/DC Input Unit C200H-IM211
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
12 to 24 VDC
10.2 to 26.4 VDC
2 k W
10 mA typical (at 24 VDC)
10.2 VDC min.
3.0 VDC max.
15 ms max. (at 24 VDC, 25 ° C)
15 ms max. (at 24 VDC, 25 ° C)
1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 200 g max.
Dimensions A-shape
Circuit Configuration
Appendix B
IN
12 to
24 VAC/DC
IN
COM
2 k
W
0.01
m
F 1.8
k
W
Input LED indicator
Internal circuit
Terminal Connections
12 to
24 VAC/DC
COM
NC
0
A4
A5
A6
A7
A0
A1
A2
A3
A8
A9
3
4
1
2
5
6
7
75
Downloaded from Elcodis.com
electronic components distributor
Specifications
AC/DC Input Unit C200H-IM212
Rated Input Voltage
Operating Input Voltage
Input Impedance
Input Current
ON Voltage
OFF Voltage
ON Response Time
OFF Response Time
No. of Circuits
24 VDC
20.4 to 26.4 VDC
3 k W
7 mA typical (at 24 VDC)
14.4 VDC min.
5.0 VDC max.
1.5 ms max. (at 24 VDC, 25 ° C)
1.5 ms max. (at 24 VDC, 25 ° C)
1 (16 points/common)
Internal Current Consumption 10 mA 5 VDC max.
Weight 250 g max.
Dimensions B-shape
Circuit Configuration
Appendix B
IN
IN
COM
3 k W
0.01
m
F 1.8
k
W
24 VAC/DC
Input LED indicator
Internal circuit
Terminal Connections
24 VAC/DC
COM
11
13
15
7
9
1
3
5
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
12
B7
14
B8
NC
B9
NC
76
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Triac Output Unit C200H-OA222V
Max. Switching Capacity
Min. Switching Capacity
Leakage Current
Residual Voltage
ON Response Time
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max./6 mA (200 VAC) max.
1.2 V max.
OFF Response Time
No. of Circuits
1/2 of load frequency or less.
1/2 of load frequency or less.
1 (12 points/common)
Internal Current Consumption 200 mA 5 VDC max.
Fuse Rating 3 A 250 V (5.2-dia.x20)
Power for External Supply
Weight
Dimensions
N/A
400 g max.
B-shape
Circuit Configuration
Output indicator
OUT
L
OUT
L
Internal circuit
Fuse
COM
250 VAC max.
Fuse: 3 A 250 V (5.2-dia.x20) MF51SH (JIS)
Note No blown fuse detector circuit is provided.
Terminal Connections
250 VAC max.
(0.3 A max., 2 A/Unit)
L
L
L
L
L
L
NC
NC
COM
5
7
1
3
9
11
A0
A1
A2
A3
A4
A5
A6
A7
B7
B8
A8
B9
0
B0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
NC
NC
NC
NC
L
L
L
L
L
L
Downloaded from Elcodis.com
electronic components distributor
77
Specifications Appendix B
Triac Output Unit C200H-OA121-E
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
1 A 120 VAC, 50/60 Hz (4 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max.
1.2 V max.
1 ms max.
1/2 of load frequency or less.
1 (8 points/common)
Internal Current Consumption 140 mA 5 VDC max.
Fuse Rating 5 A 125 V (5.2-dia.x20)
Power for External Supply
Weight
Dimensions
N/A
250 g max.
A-shape
Circuit Configuration
Output LED indicator
OUT
L
OUT
L
Internal circuit Fuse
COM
120 VAC max.
Fuse blowout detection circuit
F LED
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
120 VAC max
(1 A max. 4 A/Unit)
L
L
L
L
L
L
L
L
COM
NC
A6
A7
A8
A9
A0
A1
A2
A3
A4
A5
4
5
6
2
3
0
1
7
78
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Triac Output Unit C200H-OA122-E
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min.
1.5 mA (120 VAC) max.
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
No. of Circuits 1 (8 points/common)
Internal Current Consumption 180 mA 5 VDC max.
Fuse Rating
Power for External Supply
Weight
Dimensions
5 A 125 V (5.2-dia.x20)
N/A
300 g max.
E-shape
Circuit Configuration
Output indicator
OUT
L
OUT
L
Internal circuit
Fuse
COM
120 VAC max.
Fuse blowout detection circuit
F indicator
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
120 VAC max.
(1.2 A max. 4 A/Unit)
L
L
L
L
L
L
L
L
COM
NC
3
4
0
1
2
5
6
7
A6
A7
A8
A9
A0
A1
A2
A3
A4
A5
79
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Triac Output Unit C200H-OA223
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
15 A (pulse width: 100 ms)
30 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to
50 mA)
1 ms max.
1/2 of load frequency+1 ms or less.
No. of Circuits 1 (8 points/common)
Internal Current Consumption 180 mA 5 VDC max.
Fuse Rating
Power for External Supply
Weight
Dimensions
5 A 250 V (5.2-dia.x20)
N/A
300 g max.
E-shape
Circuit Configuration
Output indicator
OUT
L
OUT
L
Internal circuit
Fuse
COM
250 VAC max.
Fuse blowout detection circuit
F indicator
Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
250 VAC max.
(1.2 A max. 4 A/Unit)
L
L
L
L
L
L
L
L
COM
NC
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
6
7
4
5
0
1
2
3
80
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Triac Output Unit C200H-OA224
Max. Switching Capacity
Max. Inrush Current
Min. Switching Capacity
Leakage Current
Residual Voltage
0.5 A 250 VAC, 50/60 Hz (2 A/Unit)
10 A (pulse width: 100ms)
20 A (pulse width: 10 ms)
100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min.
1.5 mA (120 VAC) max./3 mA (240 VAC) max.
1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to
50 mA)
1 ms max.
ON Response Time
OFF Response Time
No. of Circuits
1/2 of load frequency + 1 ms or less.
1 (12 points/common)
Internal Current Consumption 270 mA 5 VDC max.
Fuse Rating 3.15 A 250 V (5.2-dia.x20)
Power for External Supply
Weight
Dimensions
N/A
300 g max.
B-shape
Circuit Configuration
Output indicator
OUT
L
OUT
L
Internal circuit
Fuse
COM
250 VAC max.
Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)
Note 1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
250 VAC max.
(0.5 A max., 2 A/Unit)
L
L
L
L
L
L
1
3
5
7
9
11
NC
NC
COM
A0
A1
A2
A3
A4
A5
A6
B7
A7
B6
B8
0
B0
B1
2
B2
4
B3
6
B4
8
B5
10
NC
NC
NC
A8
B9
NC
L
L
L
L
L
L
Downloaded from Elcodis.com
electronic components distributor
81
Specifications Appendix B
Contact Output Unit C200H-OC221
Max. switching capacity
Min. switching capacity
Relay
Service Life of Relay
2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
8 A/Unit
10 mA 5 VDC
G6B-1174P-FD-US (24 VDC) w/socket
Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
ON Response Time
OFF Response Time
10 ms max.
10 ms max.
No. of Circuits 1 (8 points/common)
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
Dimensions
250 g max.
A-shape
Circuit Configuration
Internal circuit
Output LED indicator
OUT
L
OUT
L
COM
250 VAC 24 VDC max.
Terminal Connections
L
L
L
L
L
L
L
L
0
COM
NC
A4
A5
A6
A7
A0
A1
A2
A3
A8
A9
3
4
5
2
1
6
7
250 VAC 24 VDC max.
(inductive load: 2 A resistive load: 2 A) (8 A/Unit)
82
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Contact Output Unit C200H-OC222
Max. switching capacity
Min. switching capacity
Relay
Service Life of Relay
2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
8 A/Unit
10 mA 5 VDC
G6B-1174P-FD-US (24 VDC) w/socket
Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
ON Response Time
OFF Response Time
10 ms max.
10 ms max.
No. of Circuits 1 (12 points/common) 8 points max. can be ON simultaneously.
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
Dimensions
300 g max.
B-shape
Circuit Configuration
Internal circuit
Output LED indicator
OUT
L
OUT
L
COM
250 VAC
24 VDC max.
Terminal Connections
L
L
L
L
L
L
1
3
5
7
9
11
NC
NC
COM
A0
A1
A2
A3
A4
A5
A6
B7
A7
B6
B8
0
B0
B1
2
B2
4
B3
6
B4
8
B5
10
NC
NC
NC
A8
B9
NC
L
L
L
L
L
L
250 VAC 24 VDC max.
(inductive load: 2 A resistive load: 2 A) (8 A/Unit)
83
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Contact Output Unit C200H-OC223
Max. switching capacity 2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
10 A/Unit
Min. switching capacity relay 10 mA 5 VDC
Service Life of Relay Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
ON Response Time 10 ms max.
OFF Response Time
No. of Circuits
10 ms max.
5 independent contacts
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
Dimensions
250 g max.
A-shape
Circuit Configuration
Internal circuit
Output LED indicator
OUT
L
OUT
250 VAC
24 VDC max.
Terminal Connections
250VAC 24 VDC max.
(inductive load: 2 A resistive load: 2 A)
(8 A/Unit)
L
L
L
L
L
0 c0
A0
A1
1
A2 c1
A3
2
A4 c2
A5
3
A6 c3
A7
4
A8 c4
A9
84
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Contact Output Unit C200H-OC224
Max. switching capacity 2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
16 A/Unit
Min. switching capacity relay 10 mA 5 VDC
Service Life of Relay Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
ON Response Time
OFF Response Time
10 ms max.
10 ms max.
No. of Circuits 8 independent contacts
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
Dimensions
300 g max.
B-shape
Circuit Configuration
Internal circuit
Output LED indicator
OUT
L
OUTc
250 VAC
24 VDC max.
Terminal Connections
250 VAC 24
VDC max. (inductive load: 2
A resistive load: 2 A) (16
A/Unit) c0 c1 c2 c3 c4 c5 c6 c7
NC
B0
A0
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6
B7
A7
0
1
2
3
4
5
6
7
B8 NC
A8
B9 NC
L
L
L
L
L
L
L
L
85
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Contact Output Unit C200H-OC225
Max. switching capacity
Min. switching capacity
Relay
Service Life of Relay
2 A 250 VAC (cos of phase angle = 1), 2 A
250 VAC (cos of phase angle = 0.4), 2 A 24 VDC
8 A/Unit
10 mA 5 VDC
G6B-1174P-FD-US (24 VDC) w/socket
Electrical: 500,000 operations (resistive load)/
100,000 operations (inductive load)
Mechanical: 50,000,000 operations
ON Response Time
OFF Response Time
10 ms max.
10 ms max.
No. of Circuits 1 (16 points/common) 8 points max. can be ON simultaneously.
Internal Current Consumption 50 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Weight
Dimensions
400 g max.
B-shape
Circuit Configuration
Output LED indicator
Internal circuit
OUT
L
OUT
L
COM
250 VAC
24 VDC max.
Terminal Connections
L
L
L
L
L
L
L
L
1
3
5
7
9
11
13
15
COM
A0
A1
A2
A3
A4
A5
B0
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6 12
A6
B7 14
A7
A8
B8
B9
NC
NC
L
L
L
L
L
L
L
L
250 VAC 24 VDC max.
(inductive load: 2 A resistive load: 2 A) (8 A/Unit)
Note This Unit must be mounted to a C200H-BC jj 1-V1/V2 Backplane.
86
Downloaded from Elcodis.com
electronic components distributor
Specifications
Transistor Output Unit C200H-OD211
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
0.3 A 24 VDC +10% /
–15%
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (12 points/common)
(2 A/Unit)
Internal Current Consumption 160 mA 5 VDC max.
Fuse Rating
Power for External Supply
Weight
5 A 125 V (5.2-dia.x20)
25 mA 24 VDC
+10%
/
–15% max.
300 g max.
Dimensions B-shape
Circuit Configuration
Appendix B
OUT
L
+ V
Output LED indicator
Internal circuit Fuse
OUT
L
COM
24 VDC
Fuse: GGS (Nagasawa)
Note No blown fuse detector circuit is provided.
Terminal Connections
24 VDC
(0.3 A max., 2 A/Unit)
L
L
L
L
L
L
3
5
7
9
11
NC
1
NC
COM (0 V)
A0
A1
A2
A3
A4
B0
0
B1
2
B2
4
B3
6
B4
8
B5
10
A5
A6
B6
B7
A7
NC
NC
B8
A8
NC
+ 24 VDC
B9
L
L
L
L
L
L
Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.
87
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD212
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
0.3 A 24 VDC +10%
None
0.1 mA max.
/
–15%
ON Response Time
OFF Response Time
1.4 V max.
0.2 ms max.
0.3 ms max.
No. of Circuits 1 (16 points/common)
Internal Current Consumption 180 mA 5 VDC max.
(4.8 A/Unit)
Fuse Rating
Power for External Supply
Weight
Dimensions
8 A 125 V (5.2-dia.x20)
35 mA 24 VDC +10% /
–15%
max.
350 g max.
B-shape
Circuit Configuration
Output LED indicator
Internal circuit Fuse
OUT
L
+ V
OUT
L
COM
24 VDC
Fuse: GGS (Nagasawa)
Note No blown fuse detector circuit is provided.
Terminal Connections
24 VDC
(0.3 A max )
L
L
L
L
L
L
L
L
1
A0
3
A1
5
A2
7
A3
9
A4
11
13
A5
A6
15
A7
COM (0 V)
A8
B8
B9
B0
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
12
B7
14
L
L
L
L
L
L
L
L
NC
+ 24 VDC
Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.
2. This Unit must be mounted to a C200H-BC jj
1-V1/V2 Backplane.
88
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD213
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
2.1 A 24 VDC +10%
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
/
–15%
1 (8 points/common)
(5.2 A/Unit) NPN output
Internal Current Consumption 140 mA 5 VDC max.
Fuse Rating
Power for External Supply
Weight
8 A 125 V (5.2-dia.x20)
30 mA 24 VDC
+10%
/
–15%
max.
250 g max.
Dimensions A-shape
Circuit Configuration
Output LED indicator
Internal circuit
OUT
L
+ V
OUT
L
Fuse
Fuse blowout detection circuit
COM
24 VDC
F LED
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
24 VDC
(2.1 A max., 5.2 A/Unit)
L
L
L
L
L
L
L
L
COM (0 V)
24 VDC
0
A4
A5
A6
A7
A0
A1
A2
A3
A8
A9
3
4
1
2
5
6
7
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
89
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD214 (Sourcing Type)
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
24 VDC +10% /
–15%
0.8 A (2.4 A/Unit) surge current
2 A (sourcing type) PNP output
None
1 mA max.
1.5 V max.
1 ms max.
1 ms max.
1 (8 points/common)
Internal Current Consumption 140 mA 5 VDC max.
Fuse Rating Short-circuit protection Overcurrent protection
Power for External Supply
Weight
Dimensions
Thermal protection
150 mA 24 VDC +10% /
–15%
max.
250 g max.
A-shape
Circuit Configuration
Source
Driver
Internal circuit
Reset button
Out put
LED indicator
OUT
L
+ V
OUT
L
+
COM
Alarm
Output LED
24 VDC
Terminal Connections
24 VDC
(2.1 A max., 5.2 A/Unit)
L
L
L
L
L
L
L
L
COM (0 V)
24 VDC
0
5
6
7
1
2
3
4
A3
A4
A5
A6
A0
A1
A2
A7
A8
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
90
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
C200H-OD214 Short-Circuit Protection
The C200H-OD214 Output Unit is equipped with two types of short-circuit protection. One is overcurrent protection, and the other is thermal protection. The short-circuit should be eliminated immediately in order to avoid damage to the
Unit.
Overcurrent Protection When the output current reaches 2 A, the alarm output turns ON, and the alarm LED lights. Make sure the surge current of the load does not exceed 2 A, or the alarm may be activated.
Thermal Protection When the junction temperature of the output transistor reaches its upper limit, the output turns OFF, the alarm output turns ON, and the alarm LED blinks. But the output transistor is provided with a heat sink. So in some cases, when the output is short-circuited the thermal protection may not activate because the extra heat is dissipated by the heat sink. However, the alarm LED will still light and the alarm output will still turn ON.
How It Works When the short-circuit protection activates, the output displays the characteristic shown below.
Output
Voltage
Overcurrent limit alarm output point
0 Output current
2 A (minimum value)
Each pair of outputs share one alarm LED and one alarm output bit as shown below (bits 12 through 15 cannot be used as work bits)
Output No.
0 1 2 3 4 5 6 7
Alarm LED No.
0
Alarm Output Point No.
08
2
09
4
10
6
11
Both the alarm LED and alarm output bit for the short-circuited output turn ON even if only one of the outputs is short-circuited. Both outputs should be disconnected until the short-circuit can be traced.
Clearing the Alarm When the short-circuit has been eliminated, reset the Unit by pressing the reset button. The alarm LED will go out, the alarm output will turn
OFF, and the output will be reset.
Output LED
Alarm LED
Reset button (use a screwdriver or other similar object to press it).
91
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Programming Example If there is a short-circuit in an output, we want the program to turn that output OFF. Assume that the Unit is mounted at word 000. A program to turn OFF output bits 00 and 01 is shown below.
A 00008
B 00008
00000
00001
Since alarm output bit 08 covers both output bits 00 and 01, both these outputs are forced OFF as soon as output bit 08 turns ON (bits A and B can be any other bits required in the program).
92
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD216
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
0.3 A 5 to 24 VDC
10 mA 5 VDC
0.1 mA max.
1.5 V max.
1.5 ms max.
2 ms max.
1 (8 points/common) positive common (sourcing type)
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Fuse Rating
Power for External Supply
None
N/A
Weight
Dimensions
250 g max.
A-shape
Circuit Configuration
Internal
Circuit
Output
LED indicator
OUT
L
OUT
L
5 to 24 VDC
COM
Terminal Connections
5 to 24 VDC
L
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
COM A8
NC A9
93
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD217
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
0.3 A 5 to 24 VDC
10 mA 5 VDC
0.1 mA max.
1.5 V max.
1.5 ms max.
2 ms max.
1 (12 points/common) positive common (sourcing type)
Internal Current Consumption 10 mA 5 VDC max. 75 mA 25 VDC (8 points ON simultaneously.)
Fuse Rating
Power for External Supply
None
N/A
Weight
Dimensions
300 g max.
B-shape
Circuit Configuration
Internal circuit
Output
LED indicator
OUT
L
OUT
L
5 to
24 VDC
COM
Terminal Connections
5 to 24 VDC
L
L
L
L
L
L
1
3
5
7
9
11
NC
NC
A0
B0
B1
A1
B2
A2
A3
B3
B4
A4
B5
A5
B6
A6
A7
B7
B8
COM A8
B9
0
2
4
6
8
10
NC
NC
NC
NC
L
L
L
L
L
L
94
Downloaded from Elcodis.com
electronic components distributor
Specifications
Transistor Output Unit C200H-OD411
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
12 to 48 VDC 1 A (3 A/Unit)
None
0.1 mA max.
1.4 V max.
0.2 ms max.
0.3 ms max.
1 (8 points/common)
Internal Current Consumption 140 mA 5 VDC max.
Fuse Rating 5 A 125 V (5.2-dia.x20)
Power for External Supply
Weight
Dimensions
30 mA 12 to 48 VDC max.
250 g max.
A-shape
Circuit Configuration
OUT
L
V
Output LED indicator
OUT
L
Internal circuit
Fuse
COM
12 to
48 VDC
Fuse blowout detection circuit
F LED
Appendix B
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through 15 cannot be used as work bits.
Terminal Connections
12 to 48 VDC
(1 A max., 3 A/Unit)
L
L
L
L
L
L
L
L
COM (0 V)
0
5
6
7
1
2
3
4
12 to 48 VDC
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.
95
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Transistor Output Unit C200H-OD21A (Sourcing Type with Load Circuit
Protection)
Max. switching capacity
24 VDC
+10%
/
–15%
, 1.0 A (4 A/Unit) surge current 1.6 A (sourcing type)
PNP output
None
No. of Circuits 1 (16 points/common)
Min. switching capacity
Leakage Current 0.1 mA max.
Residual Voltage 0.8 V max.
ON Response Time 0.1 ms max.
OFF Response Time 0.3 ms max.
Internal Current
Consumption
160 mA, 5 VDC max.
Load Short-circuit
Protection
Detection current: 1.2 A min
(1.6 A typical)
Power for External Supply 35 mA 24 VDC +10% /
–15%
min.
Alarm Output (See note) No. of outputs: 1 (2 k
Ω internal resistor)
Connectable Units: Only the following DC Input Units and alarm output LED indicators can be connected:
C200H-ID001, ID211, ID212,
IM211 (DC), IM212 (DC),
ID215, ID501, MD115,
MD215, MD501
Weight
Dimensions
400 g max.
B-shape
Circuit Configuration
Output LED indicator
2 k Ω
0 V to
Note When short-circuit/overload protection is activated, all 16 outputs will be switched OFF and the ALARM output becomes active (low level). The problem can be detected externally by connecting a DC Input Unit to the ALARM output or by connecting an alarm output indicator. It’s not possible to connect both the Input Unit and the indicator at the same time.
96
Downloaded from Elcodis.com
electronic components distributor
Specifications
Terminal Connections
Appendix B
+24 VDC
24 VDC
Note 1. When the ALARM output turns ON, remove the cause of the high current and then shut off the external power supply for approx. 1 second. After confirming that the cause has been removed, turn ON the power supply again to reset the output. As shown in the diagram, it is recommended that a relay or switch that turns ON or OFF only the external power supply be connected right before the B9 (+V). Check that this relay or switch has a contact capacity higher than the external power supply current consumption
(35 mA + load current min.).
2. This Unit must be mounted to a C200H-BC jj
1-V1/V2 Backplane.
Downloaded from Elcodis.com
electronic components distributor
97
Specifications Appendix B
Analog Timer Unit
Item
Oscillation Method
Time Setting Range
Specifications
RC oscillation
Use the DIP switch to set any of the following four ranges, according to the chart shown on the next page.
0.1 to 1 second (typical)
1 to 10 seconds (typical)
10 to 60 seconds (typical)
1 to 10 minutes (typical)
Timer Pause Function The timing operation can be paused if so specified by the program. Therefore, the timers can also be used as cumulative registers.
Number of Timer Points 4
Indicators SET and TIME UP
External Variable
Resistor
Bit Allocation
External variable resistors can be used to set the time value when the IN/EXT selector is set to OFF (EXT). Use 20 k W variable resistors.
Bit Function
The word is determined by the system configuration.
00
01
02
03
T0 start output
T1 start output
T2 start output
T3 start output
“1” when time is running
04
05
06
07
T0 pause output
T1 pause output
T2 pause output
T3 pause output
0
1
Operates
Stops
Programming and
Timing Chart
08
09
10
11
T0 time-up input
T1 time-up input
T2 time-up input
T3 time-up input
12
13
14
15
Cannot be used
Timer start input
“1” when time is up
Timer start input word n bits 08 through 11
Timer setting
(word n bits 00 through 03)
Time-up output Time-up output
Time-up flag
Timer set value
Internal Current
Consumption
60 mA 5 VDC max.
98
Downloaded from Elcodis.com
electronic components distributor
Specifications
I nternal variable resistors
These variable resistors are used to set the timers. The settings of these resistors are effective only when the corresponding IN/EXT selector is ON. To set or adjust the time, use the screwdriver supplied with the
Unit. Turn the variable resistor clockwise to increase the time value. The numbers 0 through
3 correspond to T0 through T3, respectively.
TM001
0
2
Min.
Max.
IN/EXT selectors
When the internal variable resistor is used, set the corresponding pin to ON; when an external variable resistor is used, set the corresponding pin to OFF. Pin numbers 4 through 1 correspond to T0 through T3, respectively.
2
3
0
1
1
3
Appendix B
Indicators
The SET indicators in the top row light when the corresponding timer is operating. The TIME UP indicators in the bottom row light when the corresponding timer (T0 through T3) turns ON.
Time range setting
External variable resistor connectors
External variable resistors can also be used to set the timers. The IN/EXT selector pin must be set to the
OFF position. Numbers 0 through 3 correspond to T0 through T3, respectively. Use 20-k W variable resistors and AWG 22 to 28 lead wires. The connector has solderless terminals and must be wired as shown below.
Timers
T0
T1
T2
T3
(0: OFF 1: ON)
Pin No.
8
7
6
5
4
3
2
1
0.1 to 1 s 0.1 to 10 s 10 to 60 s
0 1 0
0
0
0
1
1
0
0
0
0
0
0
0
1
0
1
0
1
0
1
0
1
1 to 10 m
1
1
1
1
1
1
1
1
99
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
!
Caution Ensure that the external variable resistor connectors are open when using the internal variable resistor.
External variable resistor connector
External variable resistor
B7A Interface Unit C200H-B7A
j
1 (Basic I/O Unit Type)
The B7A Interface Unit used with the B7A Link Terminal allows the transmission and reception of 16-point I/O data over two wires.
The following B7A Interface Unit and B7A Link Terminal models are available.
B7A Interface Unit
16-point input: C200H-B7AI1
16-point output: C200H-B7AO1
B7A Link Terminals
B7A-T6 j 1 (Screw terminal models)
B7A-T6D2 (Modular models)
B7A-R6 jj 1 (Screw terminal models)
B7A-R6A52 (Modular models)
Mount the B7A Interface Unit to the C200H-BC jj
1-V1 or C200H-BC jj
1-V2 Backplane.
Note If the B7A Interface Unit is connected to the C200H-CPU03-E or C200H-PS211, supply 24 VDC from an independent power supply to the B7A Interface Unit or use a transformer to separate the power supply line to the B7A Interface Unit from the power supply lines to the CPU and I/O Power Supply Unit.
I/O indicator
ERR indicator
Connection terminals
Connection terminals for the B7A Link Terminal:
Connect this terminal to the SIG terminal of the
B7A Link Terminal.
Connect this terminal to the negative power terminal of the B7A Link Terminal.
Supply 12 to 24 VDC.
12 to 24 VDC
I/O Indicator
Indicates the ON or OFF status of input from the B7A Link Terminal or the ON and OFF status of output to the B7A Link Terminal.
ERR Indicator
Incorporated by the B7AI1 and lit when the B7AI1’s data transmission or reception is abnormal.
100
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Connection Terminals
SIG: Connects to the SIG terminal of the B7A Link Terminal.
V–: Connects to the negative power terminal of the B7A Link Terminal.
!
Caution If the terminals are not connected correctly, the internal circuitry of the B7A Link Terminal will be damaged.
Note 1. The transmission cable must be a VCTF cable with a thickness of 0.75 mm 2 minimum.
2. Do not wire power lines or high-tension lines along with the transmission cable in the same conduit.
Input Mode Selector
The B7AI1 incorporates an input mode selector on the back panel of the Unit, with which the following modes can be set.
Function
Input mode 15 points + 1 error
Fifteen-point input from the B7A Link
Terminal is effective. Bit 15 is used as transmission error bit.
16 points
Sixteen-point input from the B7A Link
Terminal is effective.
Switch setting
Bit no.
i
00 to 14
Status of the ERR indicator
Upper side
Input 00 to input 14
15 Transmission error bit
Status of input indicator lamp 15 Not used
Lower side
Input 00 to input 14
Input 15
Lit when input 15 is ON. Not lit when input 15 is OFF.
Lit when there is a transmission error and OFF during normal transmission
The ERR indicator is lit when an error occurs. If the error is corrected, the ERR indicator is OFF at the next transmission cycle.
When there is a transmission error, the B7A Link Terminal will hold the data just before the occurrence of the transmission error. If there is a transmission error because the B7A Link Terminal is turned off, however, data 0 is transmitted in the first transmission cycle when the B7A Link Terminal is turned on again.
Transmission errors between the C200H-B7A01 and B7A Link Terminal are detected by the B7A Link Terminal only. Check the ERR indicator and error bit for any error.
Performance Specification
I/O points
Item
Transmission distance
Transmission delay
Minimum input time (see note 2)
Internal current consumption
External power supply (see note 1)
Weight
C200H-B7AI1
16 points or 15 points and 1 error input
C200H-B7AO1
16 output points
500 m max. if power is supplied to the Interface Unit and B7A Link Terminal separately.
100 m max. if power is supplied to the Interface Unit and B7A Link Terminal from a single power supply.
Typ. 19.2 ms, 31 ms max.
---
5 VDC, 100 mA max.
12 to 24 VDC ± 10%, 10 mA min.
200 g max.
16 ms
12 to 24 VDC ± 10%, 30 mA min.
Note 1. The external power supply capacity does not include the capacity required by the B7A Link Terminal.
2. The minimum input time is the minimum time required to read input signals from the CPU. Be sure that the ON/OFF width of signals sent to B7A Interface Unit output relays is at least 16 ms.
101
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
Dimensions
Racks
The dimensions shown below are for both the CPU Rack and Expansion I/O Rack. The C dimension for the Programming Console will increase by 30mm when the Programming Console Adapter C200H-BP001 is used, and will increase by 50 mm when the Programming Console Adapter C200H-BP002 is used.
M-4 screws
130 118
6.5
C200H-BC101
505
491
270.5
A
W
7.5
Model
C200H-BC031
C200H-BC051-V1
C200H-BC081-V1
C200H-BC101
246
316
421
491
A
260
330
435
505
W
135
Peripheral device
102
Downloaded from Elcodis.com
electronic components distributor
CPU Unit
C200H-CPU01/02/03
C200H-CPU11
C
D
118
143
D
Specifications Appendix B
Mounted Unit
Programming Console
Other peripheral devices
B-shape I/O Units
E-shape I/O Units
CPU01/03
148
160
145
138
C
CPU11
173
185
145
138
I/O Units
The dimensions shown below are for the three shapes of I/O Units mentioned throughout these specifications.
A-shape I/O Units x x
130
35 x x
B-shape I/O Units
101
118
Backplane
130 x x x x x x x x
35
128
145
Backplane
103
Downloaded from Elcodis.com
electronic components distributor
Specifications Appendix B
E-shape I/O Units x x
130 x x
35
Backplane Insulation Plates
The dimensions shown below are for Backplane Insulation Plates.
PC mounting screws
Four screws with 4-mm diameter heads are provided.
121
138
Insulation plate mounting screws
Four screws with 5-mm diameter shafts are provided.
B
135 118 110
D
A
E
C
12 dia
6
5 dia
10
104
Downloaded from Elcodis.com
electronic components distributor
Specifications
3 slots
5 slots
8 slots
10 slots
Model
C200H-ATT31
C200H-ATT51
C200H-ATT81
C200H-ATTA1
D
210
280
385
455
E
261
331
436
506
C
---
---
---
227.5
A
246
316
421
491
B
---
---
---
270.5
Specifications
I/O Connecting Cables
The dimensions shown below are for I/O Connecting Cables.
L
Cable
C200H-CN311
C200H-CN711
C200H-CN221
C200H-CN521
C200H-CN131
30 cm
70 cm
2 m
Length (L)
5 m
10 m
Appendix B
Downloaded from Elcodis.com
electronic components distributor
105
Downloaded from Elcodis.com
electronic components distributor
Appendix C
Standard Models
The C200H is a Rack-type PC that can be configured many different ways. Here is a series of tables listing the
Units available for the C200H, along with a brief description of the Unit and its model number.
C200H Racks
Name
Backplane (same for all Racks)
CPU Rack CPU
Expansion
I/O R k
Memory Unit
EPROM l
Specifications
10 slots
8 slots
5 slots
3 slots
100 to 120/200 to 240 VAC (Does not support SYSMAC
LINK and SYSMAC NET Link Systems.)
100 to 120/200 to 240 VAC (Supports SYSMAC LINK and
SYSMAC NET Link Systems.)
24 VDC
CMOS-RAM Unit; built-in backup battery
UM: 3K words;
DM: 1K words
UM: 7K words;
DM: 1K words
CMOS-RAM Unit; capacitor backup UM: 3K words;
DM: 1K words
EPROM Unit
(EPROM ordered separately)
EEPROM Unit
UM: 7K words;
DM: 1K words
UM: 7K words;
DM: 1K words
EEPROM Unit
UM: 3K words;
DM: 1K words
UM: 7K words;
DM: 1K words
27128; 150 ns; write voltage: 12.5 V
100 to 120/200 to 240 VAC
24 VDC
30 cm
70 cm
2 m
5 m
10 m
Model number
C200H-BC101-V2
C200H-BC081-V2
C200H-BC051-V2
C200H-BC031-V2
C200H-CPU01-E
C200H-CPU11-E
C200H-CPU03-E
C200H-MR431
C200H-MR831
C200H-MR432
C200H-MR832
C200H-MP831
C200H-ME431
C200H-ME831
ROM-ID-B
C200H-PS221
C200H-PS211
C200H-CN311
C200H-CN711
C200H-CN221
C200H-CN521
C200H-CN131
107
Downloaded from Elcodis.com
electronic components distributor
Standard Models Appendix C
C200H I/O Units
Input Units
Output
Name
AC Input Unit
DC Input Unit
AC/DC Input Unit
Relay Output Unit
Specifications
8 pts 100 to 120 VAC
16 pts 100 to 120 VAC
8 pts 200 to 240 VAC
16 pts 200 to 240 VAC
8 pts
8 pts
No-voltage contact; NPN
No-voltage contact; PNP
8 pts 12 to 24 VDC
16 pts 24 VDC
8 pts 12 to 24 VAC/DC
16 pts 24 VAC/DC
8 pts 2 A, 250 VAC/24 VDC (For resistive loads)
12 pts 2 A, 250 VAC/24 VDC (For resistive loads)
16 pts 2 A, 250 VAC/24 VAC (For resistive loads)
5 pts
8 pts
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
2 A, 250 VAC/24 VDC (For resistive loads)
Independent commons
Triac Output Unit
Transistor Output
Analog Timer Unit 4 timer pts
B7A Interface Units
(Basic I/O Units)
Variable Resistor
Connector (Related
Product)
15 or
16 input pts
16 output pts
8 pts
8 pts
1 A, 120 VAC
1.2 A, 120 VAC
8 pts 1.2 A, 250 VAC
12 pts 0.3 A, 250 VAC
12 pts 0.5 A, 250 VAC
8 pts 1 A, 12 to 48 VDC
12 pts 0.3 A, 24 VDC
16 pts 0.3 A, 24 VDC
8 pts 2.1 A, 24 VDC
8 pts 0.8 A, 24 VDC; sourcing type (PNP); with load short protection
5 to 24 VDC; sourcing type (PNP) 8 pts
12 pts 5 to 24 VDC; sourcing type (PNP)
16 pts 1 A, 24 VDC; sourcing type (PNP); with load short protection
0.1 to 1 s, 1 to 10 s, 10 to 60 s, or 1 min to
10 min (switchable)
Connector with lead wire (2 m) for 1 external resistor
Connects to B7A Link Terminals.
Model number
C200H-IA121
C200H-IA122/IA122V
C200H-IA221
C200H-IA222/IA222V
C200H-ID001
C200H-ID002
C200H-ID211
C200H-ID212
C200H-IM211
C200H-IM212
C200H-OC221
C200H-OC222
C200H-OC225
C200H-OC223
C200H-OC224
C200H-OA121-E
C200H-OA122-E
C200H-OA223
C200H-OA222V
C200H-OA224
C200H-OD411
C200H-OD211
C200H-OD212
C200H-OD213
C200H-OD214
C200H-OD216
C200H-OD217
C200H-OD21A
C200H-TM001
C4K-CN223
C200H-B7AI1
C200H-B7AO1
Note The C200H-OC225/OD212/OD21A 16-point Output Unit and the C200H-B7AO1 B7A Interface Unit must be mounted to a C200H-BC jj 1-V1/V2 Backplane.
108
Downloaded from Elcodis.com
electronic components distributor
Standard Models Appendix C
C200H Special I/O Units
All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit.
High-density I/O
Units
Name
DC Input
Units
32 pts
Specifications
Transistor
Output Units
DC Input/
Transistor
Output Units
32 pts
32 pts
32 pts
24 VDC; with high-speed inputs
0.1 A, 24 VDC (usable as 128-point dynamic output unit)
35 mA, 5 VDC (TTL outputs) (usable as 128-point dynamic output unit)
16 input/
16 output pts
16 input/
16 output pts
12-VDC inputs; with high-speed input function
0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit)
24-VDC inputs; with high-speed input function
0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit)
16 input/
16 output pts
5 VDC (TTL inputs); with high speed input function
35 mA, 5 VDC Output (TTL outputs) (usable as
128-point dynamic input unit)
1 to 5/0 to 10 V; 4 inputs Analog I/O
Units
Analog Input
Unit
Temperature Sensor Units
Platinum resistance thermometer (JPt) (switchable), DIN standards; 4 inputs
Platinum resistance thermometer (Pt) (switchable);
4 inputs
Temperature Control Units Thermocou-
Platinum re-
Transistor output
Voltage output
Current output
Transistor output
Voltage output
Current output
Heat/Cool Temperature l U i
4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V; 8 inputs
1 to 5/0 to 10 V; 2 outputs
4 to 20 mA, –10 to 10 V; 4 outputs
Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs
Thermocouple (K(CA) or L(Fe-CuNi)) (switchable);
4 inputs
PID Control Units
Thermocou-
Platinum re-
Transistor output
Voltage output
Current output
Transistor output
Voltage output
Current output
Transistor output
Voltage output
Current output
Model number
5 VDC (TTL inputs); with high-speed input function C200H-ID501
C200H-ID215
C200H-OD215
C200H-OD501
C200H-MD115
C200H-MD215
C200H-MD501
C200H-AD001
C200H-AD002
C200H-DA001
C200H-DA002
C200H-TS001
C200H-TS002
C200H-TS101
C200H-TS102
C200H-TC001
C200H-TC002
C200H-TC003
C200H-TC101
C200H-TC102
C200H-TC103
C200H-TV001
C200H-TV002
C200H-TV003
C200H-TV101
C200H-TV102
C200H-TV103
C200H-PID01
C200H-PID02
C200H-PID03
109
Downloaded from Elcodis.com
electronic components distributor
Standard Models Appendix C
Position Control Units
Cam Positioner Unit
High-speed Counter Units
ASCII Unit
I/D Sensor Units
Voice Unit
Name
Read/Write
H d
Data Carrier
( )
Connecting
Cable
Fuzzy Logic Unit
1 axis
Specifications
Pulse output; speeds: 1 to 99,990 pps
1 axis Directly connectable to servomotor driver; compatible with line driver; speeds:
1 to 250,000 pps
1 to 250000. pps. 53 pts per axis 2 axis
Detects angles of rotation by means of a resolver and provides ON and OFF outputs at specified angles. A maximum of 48 cam outputs
(16 external outputs and 32 internal outputs) maximum are available.
1 axis Pulse input; counting speed: 50 kcps;
5 VDC/12 VDC/24 VDC
1 axis Pulse input; counting speed: 75 kcps;
RS-422 line driver
EEPROM
Local application, electromagnetic coupling
Remote application, microwave transmissions
Model number
C200H-NC111
C200H-NC112
C200H-NC211
C200H-CP114
C200H-CT001-V1
C200H-CT002
C200H-ASC02
C200H-IDS01-V1
C200H-IDS21
Electromagnetic type V600-H series
Microwave type
SRAM type for V600-H series.
EEPROM type for V600-H series.
V620-H series
V600-D jj R jj
V600-D jj P jj
60 messages max.; message length: 32, 48, or 64 s (switchable) C200H-OV001
RS-232C C200H-CN224
Up to 8 inputs and 4 outputs. (I/O to and from specified data area words)
C200H-FZ001
Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EE -
PROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM
Data Carriers Operation Manual and Supplement.
C200H Link Units
Name
Host Link Unit Rack-mounting
Specifications
C200H only
PC Link Unit
Remote I/O Master Unit
Remote I/O Slave Unit
CPU-mounting C1000H/C2000H
C500
C200H
C120
Multilevel
Up to two per PC; connectable to up to 5
PC l
100 to 120/200 to 240 VAC (switchable)
24 VDC
100 to 120/200 to 240 VAC (switchable)
24 VDC
APF/PCF
RS-422
RS-232C
PCF
APF/PCF
RS-232C
RS-422
RS-485
APF/PCF
Wired
APF/PCF
Wired
Model number
C200H-LK101-PV1
C200H-LK202-V1
C200H-LK201-V1
3G2A6-LK101-EV1
3G2A6-LK101-PEV1
3G2A6-LK201-EV1
3G2A6-LK202-EV1
C200H-LK401
C200H-RM001-PV1
C200H-RM201
C200H-RT001-P
C200H-RT002-P
C200H-RT201
C200H-RT202
110
Downloaded from Elcodis.com
electronic components distributor
Standard Models
Optional Products
Appendix C
Name
I/O Unit Cover
Terminal Block Cover
Connector Cover
Space Unit
Battery Set
Specifications
Cover for 10-pin terminal block
Short protection for 10-pin terminal block
Short protection for 19-pin terminal block
Protective cover for unused I/O Connecting Cable connectors
Used for vacant slots
For C200H RAM Memory Unit only
Relay 24 VDC
Backplane Insulation Plate For 10-slot Backplane
For 8-slot Backplane
Model number
C200H-COV11
C200H-COV02
C200H-COV03
C500-COV01
C200H-SP001
C200H-BAT09
G6B-1174P-FD-US DC24
C200H-ATTA1
C200H-ATT81
I/O Bracket
Memory Unit Lock Fitting
External Connector
For 5-slot Backplane
For 3-slot Backplane
For 5-slot Backplane
For 8-slot Backplane
C200H-ATT51
C200H-ATT31
C200H-ATT53
C200H-ATT83
For 3-slot Backplane
To secure Memory Unit to CPU
C200H-ATT33
C200H-ATT03
Solder terminal; 40 pin with connector cover C500-CE401
Solderless terminal; 40 pin with connector cover (crimp-type) C500-CE402
Pressure welded terminal; 40 pin
Solder terminal; 40 pin with connector cover (rightangle type)
C500-CE403
C500-CE404
Solderless terminal; 40 pin with connector cover
(right-angle type)
Solder terminal; 24 pin with connector cover
C500-CE405
C500-CE241
Solderless terminal; 24 pin with connector cover (crimp-type) C500-CE242
Pressure welded terminal; 24 pin C500-CE243
Optical Units
Optical I/O Unit
Repeater Unit
Name
No-voltage Input Unit
AC/DC Input Unit
AC Input Unit
Relay Output Unit
Triac Output Unit
8 pts.
Specifications
12 to 24 VAC/DC 8 pts.
100 to 120 VAC 8 pts.
100 to 120 VAC
100 to 120/200 to
( / l k ) 8 240 VAC
1A, 100 to 120/200 to surge killer) 8 pts.
Transistor Output Unit 0.3 A, 12 to 48 VDC
8 pts.
Connected between 32nd and 33rd Units
Model no.
APF/PCF 3G5A2-ID001-PE
PCF 3G5A2-ID001-E
APF/PCF 3G5A2-IM211-PE
PCF 3G5A2-IM211-E
APF/PCF 3G5A2-IA121-PE
PCF 3G5A2-IA121-E
APF/PCF 3G5A2-OC221-PE
PCF 3G5A2-OC221-E
APF/PCF 3G5A2-OA222-PE
PCF 3G5A2-OA222-E
APF/PCF 3G5A2-OD411-PE
APF/PCF 3G5A2-RPT01-PE
Remote Subsystem; power supply: 85 to
250 VAC.
PCF 3G5A2-RPT01-E
111
Downloaded from Elcodis.com
electronic components distributor
Standard Models
Link Adapters
Name
Link Adapter
Specifications
3 RS-422 connectors
3 optical connectors (APF/PCF)
3 optical connectors (PCF)
1 connector for RS-232C; 2 for RS-422
1 connector each for APF/PCF, RS-422, and RS-232C
1 connector each for PCF, RS-422, and RS-232C
1 connector each for APF/PCF and APF
1 connector each for PCF and AGF
1 connector for APF/PCF; 2 for AGF
1 connector for PCF; 2 for AGF
O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF
Used for on-line removal of FIT or SYSMAC NET Link Units from the
SYSMAC NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for APF/PCF.
Appendix C
Model no.
3G2A9-AL001
3G2A9-AL002-PE
3G2A9-AL002-E
3G2A9-AL003
3G2A9-AL004-PE
3G2A9-AL004-E
3G2A9-AL005-PE
3G2A9-AL005-E
3G2A9-AL006-PE
3G2A9-AL006-E
B500-AL007-PE
B700-AL001
DIN Products
Name
DIN Track Mounting Bracket 1 set (1 included)
DIN Track
Specification
Length: 50 cm; height: 7.3 cm
Length: 1 m; height: 7.3 cm s
Length: 1 m; height: 16 mm
Model number
C200H-DIN01
PFP-50N
PFP-100N
PFP-100N2
Optical Fiber Cable
Plastic Optical Fiber Cable (APF) APF stands for “All-Plastic Fiber”. This cable can be used to connect only Units having the suffix “-P” in their model number.
The maximum length is 20 m. The 3G5A2-PF002 cable comes without connectors and must be assembled by the user.
Product
Plastic Optical Fiber Cable
Optical Connector A
Optical Connector B
Plastic Optical Fiber Cable
Description
Cable only (optical connectors not provided)
Order in units of 5 m for cable less than 100 m, or in units of
200 m or 500 m.
2 pcs (brown),for plastic Optical fiber 10 m long max.
2 pcs (black) for plastic Optical fiber 8 to 20 m long
1 m, w/optical connector A provided at both ends
Model no.
3G5A2-PF002
3G5A2-CO001
3G5A2-CO002
3G5A2-PF101
112
Downloaded from Elcodis.com
electronic components distributor
Standard Models Appendix C
Product
Optical Fiber Cable
(f i d )
Optical Fiber Cable d )
Plastic-Clad Optical Fiber Cable (PCF) PCF stands for “Plastic-Clad Fiber”.
This cable can be used to connect any Units. The maximum length for Units having the suffix “-P” in their model number is 200 m. The maximum length for Units without the suffix “-P” in their model number is 800 m.
0.1 m, w/connector
1 m, w/connector
2 m, w/connector
3 m, w/connector
5 m, w/connector
10 m, w/connector
Description
Ambient temperature: –10 ° to 70 ° C
20 m, w/connector
30 m, w/connector
40 m, w/connector
50 m, w/connector
1 to 500 m (Order in Units of 10 m) Ambient temperature: –10 ° to 70 ° C
501 to 800 m (Order in Units of 10 m) Ambient temperature: 0 ° to 55 ° C
(Must not be subjected to direct sunlight)
Model no.
3G5A2-OF011
3G5A2-OF101
3G5A2-OF201
3G5A2-OF301
3G5A2-OF501
3G5A2-OF111
3G5A2-OF211
3G5A2-OF311
3G5A2-OF411
3G5A2-OF511
3G5A2-OF002
Crystal Optical Fiber Cable (AGF) AGF stands for “All-Glass Fiber”. Crystal optical fiber cable is not available from OMRON.
Cable Length
The connectors may be difficult to attach to the cables. Therefore, always leave a little extra length when cutting the cable. The lengths given for pre-assembled cables are as shown below.
Fiber length (m)
113
Downloaded from Elcodis.com
electronic components distributor
Standard Models
Peripheral Devices
Appendix C
Programming Console
Data Access Console
Programming Console and
Connecting Cables
Data Setting Console ti
Product
C bl
Panel Mounting Bracket
Cassette Tape Recorder
Connecting Cable
PROM Writer
Floppy Disk Interface Unit
Printer Interface Unit
Memory Pack (for Printer
Interface)
Printer Connecting Cable
Peripheral Interface Unit
Connecting Cable
Graphic Programming
Console
Memory Pack
CRT Interface Unit
Programming Console
Description
Vertical, w/backlight
Horizontal, w/backlight
Vertical type, w/backlight (Connecting cable required)
Connecting cable required
For vertical type 2 m
4 m
Used for data input and process value display for the
C200H-TC jjj /C200H-TV jjj /C200H-PID jj .
For C200H-DSC01 2 m
4 m
For vertical Programming Console, Data Access Console
1 m
For C-series PCs (12.5/21 V)
For C-series PCs
For C-series PCs
For C200H/C1000H/C2000H
For printer, 2 m
High-density I/O
12-/16-point I/O
Special I/O Unit
To connect GPC to Peripheral Interface Unit 2 m
5 m
10 m
20 m
30 m
40 m
50 m
100 to 120 VAC, w/comment
For C200H/C1000H/C2000H
For connection between GPC and CRT
To attach peripheral Space between the
B-type or E-type I/O Units mounted to the CPU Rack.
29 mm
Console Adapter and
CPU surface.
49 mm
Model no.
3G2A5-PRO13-E
3G2A6-PRO15-E
C200H-PRO27-E
C200H-DAC01
C200H-CN222
C200H-CN422
C200H-DSC01
C200H-CN225
C200H-CN425
C200H-ATT01
SCYP0R-PLG01
C500-PRW06
3G2C5-FDI03-E
3G2A5-PRT01-E
C2000-MP103-EV3
SCY-CN201
C200H-IP006
3G2A2-CN221
C500-CN523
C500-CN131
C500-CN231
C500-CN331
C500-CN431
C500-CN531
3G2C5-GPC03-E
3G2C5-MP304-EV3
C500-GDI01
C200H-BP001
C200H-BP002
SYSMAC Support Software (SSS)
Product
SYSMAC Support Software
Description
3.5”, 2HD for IBM PC/AT compatible
Connection Cable
114
Downloaded from Elcodis.com
electronic components distributor
Model no.
C500-ZL3AT1-E
CQM1-CIF02
CV500-CIF01
Standard Models Appendix C
SYSMAC LINK Unit/SYSMAC NET Link Unit
If you are using any of the Units listed in the table below, they must be mounted to a CPU Rack that uses model C200H-CPU11-E as the CPU. Otherwise, these
Units will not operate properly.
Name
SYSMAC LINK Unit
Terminator
Attachment Stirrup
F Adapter
F Adapter Cover
Communications
Wired via coaxial cable.
Specifications
Must be mounted to leftmost 2 slots on Rack
Wired via optical fiber cable.
d ith APS P S l U it
One required for each node at ends of System
Provided with SYSMAC LINK Unit
---
---
Coaxial cables Manufactured by Hitachi
Manufactured by Fujigura
For use with the C200H-SLK13/SLK14
918 data link words
2,966 data link words
918 data link words
2,966 data link words
Model number
C200HW-SLK23
C200HW-SLK24
C200HW-SLK13
C200HW-SLK14
C1000H-TER01
C200H-TL001
C1000H-CE001
C1000H-COV01
ECXF5C-2V
5C-2V
C200H-APS03 Auxiliary Power Supply Unit
SYSMAC NET Link Unit
Power Cable
Bus Connection Unit
Must be mounted to leftmost 2 slots on Rack with
C200H-CPU11-E
S l
Connects SYSMAC LINK Unit or SYSMAC
NET Li k U i CPU
C200HS-SNT32
For 1 Unit C200H-APS01
For 2 Units C200H-APS02
For 1 Unit C200H-CN111
For 2 Units C200H-CN211
For 1 Unit C200H-CE001
For 2 Units C200H-CE002
Downloaded from Elcodis.com
electronic components distributor
115
Downloaded from Elcodis.com
electronic components distributor
Appendix D
Programming Console Operation
System Operations
Operation
Data All
Clear
Mode
RUN MON.
PROG.
NO NO YES
CLR
I/O Table
Register
I/O Table
Verify
I/O Table
Read
NO NO YES
YES YES YES
YES YES YES
Key Sequence
CLR
CLR
CLR
PLAY
SET
NOT
REC
RESET
[Address]
HR
MONTR All Clear
Partial
Clear
FUN
FUN
FUN
CNT Retained if pressed
DM
SHIFT
SHIFT
SHIFT
CH
*
CH
*
CH
*
CHG
VER
9
VER
7
B
1
D
3
WRITE
[0-7]
Rack no.
[0-7]
Unit no.
MONTR SHIFT
SHIFT
Setting
Address
Error
Message
Read
YES YES YES
YES YES YES
CLR
CLR
[Address]
FUN MONTR MONTR
117
Downloaded from Elcodis.com
electronic components distributor
Programming Console Operation
Programming Operations
Operation
Setting
Address
Mode
RUN MON.
PROG.
YES YES YES
CLR
[Address]
Key Sequence
Program
Read
YES YES YES
Address currently displayed
Search YES YES YES
CLR
[Instruction]
SRCH
SRCH
Appendix D
Instruction
Insert and
Instruction
Delete
NO NO YES
Program
Check
NO NO YES
SHIFT
CONT
#
[Address]
LR
SHIFT HR
HR
(AR)
SRCH SRCH
TIM
CNT
Locate position in program then enter
CLR SRCH
[Instruction]
INS
Instruction currently displayed
A
0
B
1
C
2
SRCH
DEL
SRCH
CLR
(0, 1, 2: check level)
To check up to END (01)
To abort
118
Downloaded from Elcodis.com
electronic components distributor
Programming Console Operation
Monitoring and Data Change Operations
Operation
Monitor
Mode
RUN MON.
PROG.
YES YES YES
CLR
SHIFT
SHIFT
CONT
#
CH
*
Key Sequence
LR
HR
SHIFT HR
LD
OUT
TIM
CNT
DM
[Address]
MONTR
Appendix D
CLR
SHIFT CLR
(Monitor Clear)
3 Word
Monitor
NO NO YES
Bit/Hex monitor in progress
EXT
Forced
Set/Reset
NO YES YES
MONTR
PLAY
SET
REC
RESET
SHIFT
SHIFT
PLAY
SET
REC
RESET
NOT
PV
Change 1
NO
PV
Change 2
NO
YES YES
YES YES
Change or Timer/Counter currently displayed
Change currently displayed in binary
CHG
CHG [Data]
WRITE
B
1
A
0
WRITE
119
Downloaded from Elcodis.com
electronic components distributor
Programming Console Operation
Operation
SV Increment/
Decrement, SV
Reset
RUN
NO
NO
Mode
MON.
YES
YES
PROG.
YES
NO Timer/Counter currently displayed
Key Sequence
CHG EXT
Appendix D
3-Word
Change
NO YES YES
Cycle
Time Read
YES YES NO
HEX-AS-
CII Display
Convert
YES YES YES
3 Word Monitor in progress
CLR MONTR
Word currently displayed
CHG
MONTR
[New SW]
WRITE
[Data]
WRITE
TR
120
Downloaded from Elcodis.com
electronic components distributor
Programming Console Operation
Cassette Tape Operations
Operation
Mode
RUN MON. PROG.
CLR
EXT
A
0
Cassette
Tape
Write
NO NO YES
Key Sequence
[File no.]
WRITE
Appendix D
[Start address]
CLR
WRITE [Stop address]
Start recording with the tape recorder.
SHIFT
REC
RESET
Wait for about 5 seconds.
(Cancel with the CLR key.)
EXT
A
0 [File no.]
WRITE [Start address]
Cassette
Tape
Read
NO NO YES
Start tape recorder playback.
SHIFT
REC
RESET
Wait for about 5 seconds.
Cassette
Tape
Verify
NO NO YES
CLR EXT
A
0 [File no.]
WRITE [Start address]
Start tape recorder playback.
VER
Wait for about 5 seconds.
DM<–>
Cassette
Tape
NO NO YES
CLR
EXT
B
1 [File no.]
5 second tape leader
Start tape recorder recording.
Start tape recorder playback.
SHIFT
REC
RESET
SHIFT
PLAY
SET
VER
121
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
AND LOAD
AND LD
Appendix E
Programming Instructions
Basic Instructions
Name
Mnemonic
AND
AND
Symbol
B
Function Operand Data Areas
Logically ANDs the status of the designated bit with the current execution condition.
Logically ANDs the resultant execution conditions of the preceding logic blocks.
B:
IR
SR
HR
AR
LR
TC
None
AND NOT
AND NOT
COUNTER
CNT
LOAD
LD
LOAD NOT
LD NOT
B
CP
R
CNT N
SV
Logically ANDs the inverse of the designated bit with the current execution condition.
A decrementing counter. SV: 0 to 9999;
CP: count pulse; R: reset input. The TC bit is entered as a constant.
B:
IR
SR
HR
AR
LR
TC
N:
TC
SV:
IR
HR
AR
LR
DM
#
B
B
Defines the status of bit B as the execution condition for subsequent operations in the instruction line.
Defines the status of the inverse of bit B as the execution condition for subsequent operations in the instruction line.
B:
IR
SR
HR
AR
LR
TC
B:
IR
SR
HR
AR
LR
TC
TR
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
123
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
OR
OR
Symbol
B
OR LOAD
OR LD
Appendix E
Function Operand Data Areas
Logically ORs the status of the designated bit with the current execution condition.
Logically ORs the resultant execution conditions of the preceding logic blocks.
B :
IR
SR
HR
AR
LR
TC
None
OR NOT
OR NOT
OUTPUT
OUT
OUTPUT NOT
OUT NOT
TIMER
TIM
B
B
B
TIM N
SV
Logically ORs the inverse of the designated bit with the execution condition.
Turns ON B for an ON execution condition; turns OFF B for an OFF execution condition.
B:
IR
SR
HR
AR
LR
TR
B:
IR
SR
HR
AR
LR
TC
Turns OFF B for an ON execution condition; turns ON B for an OFF execution condition.
B:
IR
SR
HR
AR
LR
ON-delay (decrementing) timer operation.
Set value: 000.0 to 999.9 s. The same TC bit cannot be assigned to more than one timer/counter. The TC bit is entered as a constant.
N:
TC
SV :
IR
HR
AR
LR
DM
#
Special Instructions
Symbol Name
Mnemonic
NO OPERATION
NOP(00)
None
Function Operand Data Areas
Nothing is executed and program operation moves to the next instruction.
None
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
124
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
END
END(01)
Symbol
END(01)
Appendix E
Function Operand Data Areas
Required at the end of each program. Instructions located after END(01) will not be executed.
None
INTERLOCK
IL(02)
INTERLOCK CLEAR
ILC(03)
JUMP
JMP(04)
JUMP END
JME(05)
FAILURE ALARM
(@)FAL(06)
SEVERE FAILURE
ALARM
FALS(07)
IL(02)
ILC(03)
JMP(04) N
JME(05) N
FAL(06) N
FALS(07) N
If an interlock condition is OFF, all outputs and all timer PVs between the current
IL(02) and the next ILC(03) are turned OFF or reset, respectively. Other instructions are treated as NOP. Counter PVs are maintained. If the execution condition is ON, execution continues normally.
None
When the execution condition for the
JMP(04) instruction is ON, all instructions between JMP(04) and the corresponding
JME(05) are to be ignored or treated as
NOP(00). For direct jumps, the corresponding JMP(04) and JME(05) instructions have the same N value in the range
01 through 99. Direct jumps are usable only once each per program (i.e., N is 01 through 99 can be used only once each) and the instructions between the JUMP and JUMP END instructions are ignored;
00 may be used as many times as necessary, instructions between JMP 00 and the next JME 00 are treated as NOP, thus increasing cycle time, as compared with direct jumps.
N:
00 to 99
(not applicable for
C jj P, C jj K, or
C120 PCs)
Assigns a failure alarm code to the given execution condition.When N can be given a value between 01 and 99 to indicate that a non-fatal error (i.e., one that will not stop the CPU) has occurred. This is indicated by the PC outputting N (the FAL number) to the FAL output area. To reset the FAL area, N can be defined as 00. This will cause all previously recorded FAL numbers in the FAL area to be deleted. FAL data sent after a 00 will be recorded in the normal way. The same code numbers can be used for both FAL(06) and FALS(07).
N:
00 to 99
A fatal error is indicated by outputting N to the FAL output area and the CPU is stopped. The same FAL numbers are used for both FAL(06) and FALS(07).
N:
01 to 99
STEP DEFINE
STEP(08)
STEP START
SNXT(09)
STEP(08) B
SNXT(09) B
When used with a control bit (B), defines the start of a new step and resets the previous step. When used without B, it defines the end of step execution.
B:
IR
HR
AR
LR
Used with a control bit (B) to indicate the end of the step, reset the step, and start the next step which has been defined with the same control bit.
B:
IR
HR
AR
LR
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
125
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
SHIFT REGISTER
SFT(10)
I
P
R
Symbol
SFT(10)
St
E
Appendix E
Function Operand Data Areas
Creates a bit shift register for data from the starting word (St) through to the ending word (E). I: input bit; P: shift pulse; R: reset input. St must be less than or equal to E. St and E must be in the same data area.
St/E:
IR
HR
AR
LR
KEEP
KEEP(11)
S
R
KEEP(11)
B
15
E
00 15
St
00
IN
Defines a bit (B) as a latch, controlled by the set (S) and reset (R) inputs.
B:
IR
HR
AR
LR
REVERSIBLE
COUNTER
CNTR (12)
DIFFERENTIATE UP
DIFU(13)
DIFFERENTIATE
DOWN
DIFD(14)
HIGH-SPEED TIMER
TIMH(15)
WORD SHIFT
(@)WSFT(16)
II
DI
R
CNTR(12)
N
SV
Increases or decreases the PV by one whenever the increment input (II) or decrement input (DI) signals, respectively, go from OFF to ON. SV: 0 to 9999; R: reset input. Each TC bit can be used for one timer/counter only. The TC bit is entered as a constant.
N:
TC
DIFU(13) B
DIFU(13) turns ON the designated bit (B) for one cycle on reception of the leading
(rising) edge of the input signal; DIFD(14) turns ON the bit for one cycle on reception of the trailing (falling) edge.
B:
IR
HR
AR
LR
DIFD(14) B
TIMH(15) N
SV
WSFT(16)
St
E
A high-speed, ON-delay (decrementing) timer. SV: 00.02 to 99.99 s. Each TC bit can be assigned to only one timer or counter.
The TC bit is entered as a constant.
N:
TC
The data in the words from the starting word (St) through to the ending word (E), is shifted left in word units, writing all zeros into the starting word. St must be less than or equal to E, and St and E must be in the same data area.
St/E:
IR
HR
AR
LR
DM
SV:
IR
SR
HR
AR
LR
DM
#
SV :
IR
SR
HR
AR
LR
HR
#
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
126
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
REVERSIBLE WORD
SHIFT
(@)RWS(17)
(CPU11)
CYCLE TIME
(@)SCAN(18)
(CPU11)
MULTI-WORD
COMPARE
(@)MCMP(19)
(CPU11)
COMPARE
(@)CMP(20)
MOVE
(@)MOV(21)
Symbol
RWS(17)
C
St
E
SCAN(18)
Mi
–––
–––
MCMP(19)
S
1
S
2
D
CMP(20)
Cp1
Cp2
MOV(21)
S
D
Appendix E
Function Operand Data Areas
Creates and controls a reversible non-synchronous word shift register between St and E. Exchanges the content of a word containing zero with the content of either the preceding or following word, depending on the shift direction. Bits 13, 14, and 15 of control word C determine the mode of operation of the register according to the following: The shift direction is determined by bit 13 (OFF shifts the non-zero data to higher addressed words;
ON to lower addressed words). Bit 14 is the register enable bit (ON for shift enabled). Bit 15 is the reset bit (if bit 15 is ON, the register will be set to zero between St and E when the instruction is executed with bit 14 also ON). St and E must be in the same data area.
Sets the minimum cycle time, Mi, in tenths of milliseconds. The possible setting range is from 0 to 999.0 ms. If the actual cycle time is less than the time set using
SCAN(18), the CPU will wait until the designated time has elapsed before starting the next cycle.
Compares the data within a block of 16 words of 4-digit hexadecimal data (S
S
1
+15) with that in another block of 16 words (S
2
to S
2
1
to
+15) on a word-by-word basis. If the words are not in agreement, the bit corresponding to unmatched words turns ON in the result word, D. Bits corresponding to words that are equal are turned OFF.
Compares the data in two 4-digit hexadecimal words (Cp1 and Cp2) and outputs result to the GR, EQ, or LE Flags.
C:
IR
SR
HR
AR
LR
TC
DM
#
Mi:
IR
SR
HR
AR
LR
TC
DM
#
S
1
IR
/S
2
:
SR
HR
AR
LR
TC
DM
Transfers data from source word, (S) to destination word (D).
St/E:
IR
SR
HR
AR
LR
TC
DM
–––:
Not used.
D:
IR
SR
HR
AR
LR
TC
DM
S:
IR
SR
HR
AR
LR
TC
DM
#
Cp1/Cp2:
IR
SR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
127
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
MOVE NOT
(@)MVN(22)
Symbol
MVN(22)
S
D
BCD-TO-BINARY
(@)BIN(23)
BINARY-TO-BCD
(@)BCD(24)
BIN(23)
S
R
BCD(24)
S
R
Appendix E
Function
Transfers the inverse of the data in the source word (S) to destination word (D).
S:
IR
SR
HR
AR
LR
TC
DM
#
Converts 4-digit, BCD data in source word
(S) into 16-bit binary data, and outputs converted data to result word (R).
S
(BCD )
R
( BIN )
S:
IR
SR
HR
AR
LR
TC
DM x10 0 x10 1 x10 2 x10 3 x16 0 x16 1 x16 2 x16 3
Operand Data Areas
D:
IR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
Converts binary data in source word (S) into BCD, and outputs converted data to result word (R).
S R
( BIN) (BCD ) x16 0 x16 1 x16 2 x16 3 x10
0 x10 1 x10 2 x10 3
S:
IR
SR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
ARITHMETIC SHIFT
LEFT
(@)ASL(25)
ARITHMETIC SHIFT
RIGHT
(@)ASR(26)
ASL(25)
Wd
ASR(26)
Wd
Each bit within a single word of data (Wd) is shifted one bit to the left, with zero written to bit 00 and bit 15 moving to CY.
CY
15 00
Wd 0
Wd:
IR
HR
AR
LR
DM
Each bit within a single word of data (Wd) is shifted one bit to the right, with zero written to bit 15 and bit 00 moving to CY.
0
15
Wd
00
CY
Wd:
IR
HR
AR
LR
DM
ROTATE LEFT
(@)ROL(27)
ROL(27)
Wd
Each bit within a single word of data (Wd) is moved one bit to the left, with bit 15 moving to carry (CY), and CY moving to bit 00.
15 00
Wd CY
Wd:
IR
HR
AR
LR
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
128
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions Appendix E
Name
Mnemonic
ROTATE RIGHT
(@)ROR(28)
COMPLEMENT
(@)COM(29)
Symbol
ROR(28)
Wd
COM(29)
Wd
Function Operand Data Areas
Each bit within a single word of data (Wd) is moved one bit to the right, with bit 00 moving to carry (CY), and CY moving to bit
15.
15 00
CY Wd
Wd:
IR
HR
AR
LR
DM
Inverts bit status of one word (Wd) of data, changing 0s to 1s, and vice versa.
Wd Wd
Wd:
IR
HR
AR
LR
DM
BCD ADD
(@)ADD(30)
BCD SUBTRACT
(@)SUB(31)
BCD MULTIPLY
(@)MUL(32)
ADD(30)
Au
Ad
R
SUB(31)
Mi
Su
R
MUL(32)
Md
Mr
R
Adds two 4-digit BCD values (Au and Ad) and content of CY, and outputs the result to the specified result word (R).
Au + Ad +
Subtracts both the 4-digit BCD subtrahend
(Su) and content of CY, from the 4-digit
BCD minuend (Mi) and outputs the result to the specified result word (R).
Mi – Su – CY
Multiplies the 4-digit BCD multiplicand
(Md) and 4-digit BCD multiplier (Mr), and outputs the result to the specified result words (R and R + 1). R and R + 1 must be in the same data area.
Md x Mr R + 1
R CY
R
Au/Ad:
IR
SR
HR
AR
LR
TC
DM
#
Mi/Su:
IR
SR
HR
AR
LR
TC
DM
#
Md/Mr:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
BCD DIVIDE
(@)DIV(33)
DIV(33)
Dd
Dr
R
Divides the 4-digit BCD dividend (Dd) by the 4-digit BCD divisor (Dr), and outputs the result to the specified result words. R receives the quotient; R + 1 receives the remainder. R and R + 1 must be in the same data area.
Dd
÷
Dr R + 1 R
Dd/Dr:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
LOGICAL AND
(@)ANDW(34)
ANDW(34)
I1
I2
R
Logically ANDs two 16-bit input words (I1 and I2) and sets the bits in the result word
(R) if the corresponding bits in the input words are both ON.
I1/I2:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
129
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
LOGICAL OR
(@)ORW(35)
EXCLUSIVE OR
(@)XORW(36)
EXCLUSIVE NOR
(@)XNRW(37)
INCREMENT
(@)INC(38)
DECREMENT
(@)DEC(39)
SET CARRY
(@)STC(40)
Symbol
ORW(35)
I1
I2
R
XORW(36)
I1
I2
R
XNRW(37)
I1
I2
R
INC(38)
Wd
DEC(39)
Wd
Appendix E
Function
Logically ORs two 16-bit input words (I1 and I2) and sets the bits in the result word
(R) when one or both of the corresponding bits in the input words is/are ON.
Exclusively ORs two 16-bit input words (I1 and I2) and sets the bits in the result word
(R) when the corresponding bits in input words differ in status.
Exclusively NORs two 16-bit input words
(I1 and I2) and sets the bits in the result word (R) when the corresponding bits in both input words have the same status.
Increments the value of a 4-digit BCD word
(Wd) by one, without affecting carry (CY).
I1/I2:
IR
SR
HR
AR
LR
TC
DM
#
I1/I2:
IR
SR
HR
AR
LR
TC
DM
#
Wd:
IR
HR
AR
LR
DM
I1/I2:
IR
SR
HR
AR
LR
TC
DM
#
Decrements the value of a 4-digit BCD word by 1, without affecting carry (CY).
Wd:
IR
HR
AR
LR
DM
Operand Data Areas
R:
IR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
Sets the Carry Flag (i.e., turns CY ON).
None
STC(40)
CLEAR CARRY
(@)CLC(41)
Clears the Carry Flag (i.e, turns CY OFF). None
CLC(41)
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
130
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
DISPLAY MESSAGE
(@)MSG(46)
LONG MESSAGE
(@)LMSG(47)
(CPU11)
TERMINAL MODE
(@)TERM(48)
(CPU11)
SET SYSTEM
(@)SYS(49)
(CPU11)
Symbol
MSG(46)
FM
LMSG(47)
S
D
–––
TERM(48)
–––
–––
–––
SYS(49)
P
–––
–––
Appendix E
Function Operand Data Areas
Displays eight words of ASCII code, starting from FM, on the Programming Console or GPC. All eight words must be in the same data area.
FM A B
C D
FM:
IR
HR
AR
LR
TC
DM
#
FM+ 7
D P
ABCD........DP
Outputs a 32-character message to either a Programming Console, or a device connected via the RS-232C interface. The output message must be in ASCII beginning at address S. The destination of the message is designated in D: 000 specifies that the message is to be output to the
GPC; 001 specifies the RS-232C interface, starting with the leftmost byte; and
002 specifies the RS-232C interface, starting from the rightmost byte.
When the execution condition is ON, the
Programming Console operation mode is changed to TERMINAL mode. There is no program command available to change the mode back to CONSOLE mode. Pressing the CHNG key on the Programming Console manually toggles between the two modes.
Used to either control certain operating parameters, or to execute the system commands that can be executed from the
AR area.
The contents of the leftmost 8 bits (i.e., bits
08 to 15) of P determine which function
SYS(49) will have. If they contain A3, then bit 00 specifies whether the battery will be checked, and bit 07 specifies whether I/O status will be maintained on start up. Bit 06 specifies whether the Force Status Hold
Bit is set.
To be effective SYS(49) must be programmed at address 00001 with LD AR
1001 at address 00000.
S:
IR
HR
AR
LR
TC
DM
None
P:
#
D:
#000
#001
#002
–––:
Not used.
–––:
Not used.
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
131
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
BINARY ADD
(@)ADB(50)
Symbol
ADB(50)
Au
Ad
R
BINARY SUBTRACT
(@)SBB(51)
SBB(51)
Mi
Su
R
Appendix E
Function Operand Data Areas
Adds the 4-digit augend (Au), 4-digit addend (Ad), and content of CY and outputs the result to the specified result word (R).
+ A
Au d
+ CY
Au/Ad:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
R
CY
Subtracts the 4-digit hexadecimal subtrahend (Su) and content of carry, from the
4-digit hexadecimal minuend (Mi), and outputs the result to the specified result word
(R).
–
Mi
Su
Mi/Su:
IR
SR
HR
AR
LR
TC
DM
#
– CY
R:
IR
HR
AR
LR
DM
R
CY
BINARY MULTIPLY
(@)MLB(52)
MLB(52)
Md
Mr
R
Multiplies the 4-digit hexadecimal multiplicand (Md) and 4-digit multiplier (Mr), and outputs the 8-digit hexadecimal result to the specified result words (R and R+1). R and R+1 must be in the same data area.
X
Md
Mr
Md/Mr:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
Quotient R
Remainder
R+1
BINARY DIVIDE
(@)DVB(53)
DVB(53)
Dd
Dr
R
Divides the 4-digit hexadecimal dividend
(Dd) by the 4-digit divisor (Dr), and outputs result to the designated result words ( R and R + 1). R and R + 1 must be in the same data area.
÷
Dd
Dr
Dd/Dr:
IR
SR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
Quotient R
Remainde r R + 1
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
132
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
DOUBLE BCD ADD
(@)ADDL(54)
DOUBLE BCD
SUBTRACT
(@)SUBL(55)
DOUBLE BCD
MULTIPLY
(@)MULL(56)
Symbol
ADDL(54)
Au
Ad
R
SUBL(55)
Mi
Su
R
MULL(56)
Md
Mr
R
Appendix E
Function Operand Data Areas
Adds two 8-digit values (2 words each) and the content of CY, and outputs the result to the specified result words. All words for any one operand must be in the same data area.
Au + 1 Au
Au/Ad:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
+ Ad + 1 Ad
+ CY
CY R + 1 R
Subtracts both the 8-digit BCD subtrahend and the content of CY from an 8-digit BCD minuend, and outputs the result to the specified result words. All words for any one operand must be in the same data area.
Mi + 1 Mi
Mi/Su:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
– Su + 1 Su
– CY
CY R + 1 R
Multiplies the 8-digit BCD multiplicand and
8-digit BCD multiplier, and outputs the result to the specified result words. All words for any one operand must be in the same data area.
Md/Mr:
IR
SR
HR
AR
LR
TC
DM
Md + 1 Md
R:
IR
HR
AR
LR
DM
X Mr + 1 Md
R + 3 R + 2 R + 1 R
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
133
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
DOUBLE BCD DIVIDE
(@)DIVL(57)
DOUBLE
BCD-TO-DOUBLE
BINARY (@)BINL(58)
DOUBLE
BINARY-TO-DOUBLE
BCD
(@)BCDL(59)
Symbol
DIVL(57)
Dd
Dr
R
BINL(58)
S
R
BCDL(59)
S
R
Appendix E
Function Operand Data Areas
Divides the 8-digit BCD dividend by an
8-digit BCD divisor, and outputs the result to the specified result words. All words for any one operand must be in the same data area.
Dd/Dr:
IR
SR
HR
AR
LR
TC
DM
Dd + 1 Dd
R:
IR
HR
AR
LR
DM
÷
Dr + 1 Dr
Quotient
Remainder
R + 1 R
R + 3 R + 2
Converts the BCD value of the two source words (S: starting word) into binary and outputs the converted data to the two result words (R: starting word). All words for any one operand must be in the same data area.
S:
IR
SR
HR
AR
LR
TC
DM
S R
R:
IR
HR
AR
LR
DM
S + 1 R + 1
Converts the binary value of the two source words (S: starting word) into eight digits of BCD data, and outputs the converted data to the two result words (R: starting result word). Both words for any one operand must be in the same data area.
S:
IR
SR
HR
AR
LR
DM
R:
IR
HR
AR
LR
DM
DOUBLE COMPARE
CMPL(60)
(CPU11)
CMPL(60)
S
1
S
2
S
S + 1
R
R + 1
Compares the 8-digit hexadecimal values in words S
1
+1 and S
1
with the values in
S
2
+1 and S
2
, and indicates the result using the Greater Than, Less Than, and Equal
Flags in the AR area. S
1
+1 and S
2
+1 are regarded as the most significant data in each pair of words.
S
1
IR
,S
2
:
SR
HR
AR
LR
TC
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
134
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
COLUMN-TO-WORD
(@)CTW(63)
(CPU11)
Symbol
CTW(63)
S
C
D
Appendix E
Function
Fetches data from the same numbered bit
(C) in 16 consecutive words (where S is the address of the first source word), and creates a 4-digit word by consecutively placing the data in the bits of the destination word, D.
The bit from word S is placed into bit 00 of
D, the bit from word S+1 is placed into bit
01, etc.
S:
IR
SR
HR
AR
LR
TC
DM
S
S+1
Bit C
0
1
D
0
1
00
01
Operand Data Areas
C:
IR
SR
HR
AR
LR
TC
DM
#
D:
IR
SR
HR
AR
LR
TC
DM
WORD-TO-COLUMN
(@)WTC(64)
(CPU11)
HOURS-TO-SECONDS
(@)HTS(65)
(CPU11)
SECONDS-TO-HOURS
(@)STH(66)
(CPU11)
WTC(64)
S
D
C
S+15 0 0 15
Places bit data from the source word (S), consecutively into the same numbered bits of the 16 consecutive destination words (where D is the address of the first destination word).
Bit 00 from word S is placed into bit C of word D, bit 01 from word S is placed into bit C of word D+1, etc.
S:
IR
SR
HR
AR
LR
TC
DM
S
00
01
1
1
Bit C
1
1
D
D+1
D:
IR
SR
HR
AR
LR
TC
DM
C:
IR
SR
HR
AR
LR
TC
DM
#
HTS(65)
S
R
–––
STH(66)
S
R
–––
15 0 0 D+15
Converts a time given in hours/minutes/ seconds (S and S+1) to an equivalent time in seconds only (R and R+1). S and S+1 must be BCD and within one data area. R and R+1 must also be within one data area.
Converts a time given in seconds (S and
S+1) to an equivalent time in hours/minutes/seconds (R and R+1). S and S+1 must be BCD between 0 and 35,999,999, and within the same data area. R and R+1 must also be within one data area.
S:
IR
SR
HR
AR
LR
TC
DM
S:
IR
SR
HR
AR
LR
TC
DM
R:
IR
SR
HR
AR
LR
TC
DM
R:
IR
SR
HR
AR
LR
TC
DM
–––:
Not used.
–––:
Not used.
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
135
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
BIT COUNTER
(@)BCNT(67)
Symbol
BCNT(67)
N
SB
R
BLOCK COMPARE
(@)BCMP(68)
BCMP(68)
S
CB
R
Appendix E
Function
Counts the number of ON bits in one or more words (SB is the beginning source word) and outputs the result to the specified result word (R). N gives the number of words to be counted. All words in which bit are to be counted must be in the same data area.
Compares a 1-word binary value (S) with the 16 ranges given in the comparison table (CB is the starting word of the comparison block). If the value falls within any of the ranges, the corresponding bits in the result word (R) will be set. The comparison block must be within one data area.
S:
IR
SR
HR
AR
LR
TC
DM
#
N:
IR
SR
HR
AR
LR
TC
DM
S
Lower limit Upper limit
CB CB+1 1
CB+2 CB+3
CB+4 CB+5
0
1
Result
CB+30 CB+31 0
Lower limit
≤
S
≤
Upper limit 1
Operand Data Areas
R:
IR
HR
AR
LR
TC
DM
CB:
IR
SR
HR
LR
TC
DM
SB:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
TC
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
136
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
VALUE CALCULATE
(@)VCAL(69)
(CPU11)
Symbol
VCAL(69)
C
S
D
Appendix E
Function Operand Data Areas
Calculates the cosine, or sine of the given degree value, or determines the y-coordinate of the given x value in a previously established line graph. For the sine and cosine conversions, S is entered in BCD as an angle (in the range 0.0 to 90.0 degrees).
When calculating the y-coordinate in a graph, S gives the address of the value of the x-coordinate. The calculated data is transferred to the destination word (D).
Sine and cosine results are given in BCD.
Line graph coordinate calculations (interpolation) can be in BCD or BIN.
The data in the control word (C) determines which operation is performed. If C is entered as a constant with a value of 0000 or 0001, the sine or cosine, respectively, of the source data value is calculated. If C is entered as a word designation, it gives the address of the first word of the data table for the line graph. The value of the first two digits gives m–1, where m is the number of data points for which coordinates are given on the line graph. Bits 14 and 15, respectively, specify the output and input data formats (0 indicates BCD, 1 indicates binary).
C:
IR
SR
HR
AR
LR
TC
DM
#
Y
Y m
Y
4
Y
3
Y
1
Y
2
Y
0
X
1
Input data format
Output data format
X
2
X
3
X
4
X m m–1, where m is the number of data points whose coordinates are specified in the table
X
S:
IR
SR
HR
AR
LR
TC
DM
D:
IR
SR
HR
AR
LR
TC
DM
C
C+1
C+2
C+3
C+4
C+5
C+6
15 14 08 07 00
000000
X m
(max. x-coordinate for this table)
Y
0
X
1
Y
1
X
2
Y
2
C+(2m+1)
C+(2m+2)
X m
Y m
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
137
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
BLOCK TRANSFER
(@)XFER(70)
BLOCK SET
(@)BSET(71)
SQUARE ROOT
(@)ROOT(72)
DATA EXCHANGE
(@)XCHG(73)
Symbol
XFER(70)
N
S
D
BSET(71)
S
St
E
ROOT(72)
Sq
R
XCHG(73)
E1
E2
Appendix E
Function Operand Data Areas
Moves the content of several consecutive source words (S gives the address of the starting source word) to consecutive destination words (D is the starting destination word). All source words must be in the same data area, as must all destination words. Transfers can be within one data area or between two data areas, but the source and destination words must not overlap.
N:
IR
SR
HR
AR
LR
TC
DM
#
S :
IR
HR
AR
LR
TC
DM
D:
IR
SR
HR
AR
LR
TC
DM
#
S
S + 1
D
D + 1
No. of
Words
S+N–1 D+N–1
Copies the content of one word or constant
(S) to several consecutive words (from the starting word, St, through to the ending word, E). St and E must be in the same data area.
S
St
St/E:
IR
HR
AR
LR
TC
DM
S:
IR
SR
HR
AR
LR
TC
DM
#
E
Computes the square root of an 8-digit
BCD value (Sq and Sq + 1) and outputs the truncated 4-digit, integer result to the specified result word (R). Sq and Sq + 1 must be in the same data area.
Sq+1 Sq
Sq:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
R
Exchanges the contents of two words (E1 and E2).
E1 E2
E1/E2:
IR
HR
AR
LR
TC
DM
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
138
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
ONE DIGIT SHIFT LEFT
(@)SLD(74)
Symbol
SLD(74)
St
E
Appendix E
Function Operand Data Areas
Shifts all data, between the starting word
(St) and ending word (E), one digit (four bits) to the left, writing zero into the rightmost digit of the starting word. St and E must be in the same data area.
St/E:
IR
HR
AR
LR
DM
St 0
St + 1
ONE DIGIT SHIFT
RIGHT
(@)SRD(75)
4-TO-16 DECODER
(@)MLPX(76)
16-TO-4 ENCODER
(@)DMPX(77)
SRD(75)
E
St
MLPX(76)
S
Di
R
DMPX(77)
S
R
Di
E
Shifts all data, between starting word (St) and ending word (E), one digit (four bits) to the right, writing zero into the leftmost digit of the ending word. St and E must be in the same data area.
St/E:
IR
HR
AR
LR
DM
E
E – 1
0 St
Converts up to four hexadecimal digits in the source word (S), into decimal values from 0 to 15, and turns ON the corresponding bit(s) in the result word(s) (R). There is one result word for each converted digit.
Digits to be converted are designated by
Di. (The rightmost digit specifies the first digit. The next digit to the left gives the number of digits to be converted minus 1.
The two leftmost digits are not used.)
S:
IR
SR
HR
AR
LR
TC
DM
S 0 to F
Di:
IR
HR
AR
LR
TC
DM
#
R:
IR
HR
AR
LR
DM
R
15 00
Determines the position of the leftmost ON bit in the source word(s) (starting word: S) and turns ON the corresponding bit(s) in the specified digit of the result word (R).
One digit is used for each source word.
Digits to receive the converted values are designated by Di. (The rightmost digit specifies the first digit. The next digit to left gives the number of words to be converted minus 1. The two leftmost digits are not used.)
15 00
S
S:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
Di:
IR
HR
AR
LR
TC
DM
#
R 0 to F
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
139
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
7-SEGMENT DECODER
(@)SDEC(78)
FLOATING POINT
DIVIDE
(@)FDIV(79)
SINGLE WORD
DISTRIBUTE
(@)DIST(80)
Symbol
SDEC(78)
S
Di
D
FDIV(79)
Dd
Dr
R
DIST(80)
S
DBs
Of
Appendix E
Function
Converts hexadecimal values from the source word (S) into 7-segment display data. Results are placed in consecutive half-words, starting at the first destination word (D). Di gives digit and destination details. (The rightmost digit gives the first digit to be converted. The next digit to the left gives the number of digits to be converted minus 1. If the next digit is 1, the first converted data is transferred to left half of the first destination word. If it is 0, the transfer is to the right half).
S:
IR
SR
HR
AR
LR
TC
DM
S
Operand Data Areas
Di:
IR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
DM
D
0 to F
Divides one floating point value by another and outputs a floating point result. The rightmost seven digits of each set of two words (eight digits) are used for mantissa, and the leftmost digit is used for the exponent and its sign (Bits 12 to 14 give the exponent value, 0 to 7. If bit 15 is 0, the exponent is positive; if it’s 1, the exponent is negative).
Dd/Dr:
IR
SR
HR
AR
LR
TC
DM
R:
IR
HR
AR
LR
DM
Dd + 1 Dd
÷
Dr + 1 Dr
R + 1 R
Moves one word of source data (S) to the destination word whose address is given by the destination base word (DBs) plus offset (Of).
S
Base (DBs)
+
Offset (OF)
S:
IR
SR
HR
AR
LR
TC
DM
#
(S) (DBs + Of)
DBs:
IR
HR
AR
LR
TC
DM
Of:
IR
HR
AR
LR
TC
DM
#
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
140
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
DATA COLLECT
(@)COLL(81)
MOVE BIT
(@)MOVB(82)
Symbol
COLL(81)
SBs
Of
D
MOVB(82)
S
Bi
D
Appendix E
Function
Extracts data from the source word and writes it to the destination word (D). The source word is determined by adding the offset (Of) to the address of the source base word (SBs).
SBs:
IR
SR
HR
AR
LR
TC
DM
Base (DBs)
+
Offset (OF)
(SBs+Of) (D)
Transfers the designated bit of the source word or constant (S) to the designated bit of the destination word (D). The rightmost two digits of the bit designator (Bi) specify the source bit. The two leftmost digits specify the destination bit.
S:
IR
SR
HR
AR
LR
DM
#
S
Operand Data Areas
Of:
IR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
TC
DM
Bi:
IR
HR
AR
LR
TC
DM
#
D:
IR
HR
AR
LR
DM
MOVE DIGIT
(@)MOVD(83)
MOVD(83)
S
Di
D
D
Moves hexadecimal content of up to four specified 4-bit source digit(s) from the source word to the specified destination digit(s) (S gives the source word address.
D specifies the destination word). Specific digits within the source and destination words are defined by the Digit Designator
(Di) digits. (The rightmost digit gives the first source digit. The next digit to the left gives the number of digits to be moved.
The next digit specifies the first digit in the destination word.)
S:
IR
SR
HR
AR
LR
TC
DM
#
S
15 00
Di:
IR
HR
AR
LR
TC
DM
#
D:
IR
SR
HR
AR
LR
TC
DM
D
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
141
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
REVERSIBLE SHIFT
REGISTER
(@)SFTR(84)
TABLE COMPARE
(@)TCMP(85)
Symbol
SFTR(84)
C
St
E
TCMP(85)
CD
TB
R
Appendix E
Function Operand Data Areas
Shifts bits in the specified word or series of words either left or right. Starting (St) and ending words (E) must be specified. Control word (C) contains shift direction, reset input, and data input. (Bit 12: 0 = shift right,
1 = shift left. Bit 13 is the value shifted into the source data, with the bit at the opposite end being moved to CY. Bit 14: 1 = shift enabled, 0 = shift disabled. If bit 15 is ON when SFTR(89) is executed with an ON condition, the entire shift register and CY will be set to zero.) St and E must be in the same data area and St must be less than or equal to E.
15 14 13 12 11 00
C
Not used
St/E/C:
IR
HR
AR
TC
LR
DM
15 00 15 00
E St IN
CY
15 00 15 00
IN E St
CY
Compares a 4-digit hexadecimal value
(CD) with values in table consisting of 16 words (TB: is the first word of the comparison table). If the value of CD falls within any of the comparison ranges, corresponding bits in result word (R) are set (1 for agreement, and 0 for disagreement).
The table must be entirely within the one data area.
R
CD Tb 0
Tb + 1 1
0
CD:
IR
SR
HR
AR
LR
TC
DM
#
TB/R:
IR
HR
AR
LR
TC
DM
Tb + 13
Tb + 14
Tb + 15
1
0
1
1: agreement
0: disagreement
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
142
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
ASCII CONVERT
(@)ASC(86)
Symbol
ASC(86)
S
Di
D
Appendix E
Function Operand Data Areas
Converts hexadecimal digits from the source word (S) into 8-bit ASCII values, starting at leftmost or rightmost half of the starting destination word (D). The rightmost digit of Di designates the first source digit. The next digit to the left gives the number of digits to be converted. The next digit specifies the whether the data is to be transferred to the rightmost (0) or leftmost
(1) half of the first destination word. The leftmost digit specifies parity:
0: none,
1: even, or
2: odd.
S:
IR
SR
HR
AR
LR
TC
DM
Di:
IR
HR
LR
TC
DM
#
D:
IR
HR
LR
DM
S 0 to F
D
15 08 07 00
8-bit data
INTERRUPT CONTROL
(@)INT(89)
INT(89)
CC
N
D
Controls programmed (scheduled) interrupts and interrupts from Interrupt Input
Units. Each PC can have up to 4 IIUs. N defines the source of the interrupt: 000 to 003 designate the no. of the IIU; 004 designates a scheduled interrupt. In IIUs, bits 00 to 07 identify the interrupting subroutine, higher bits are not used. Bit 00 of Unit 0 corresponds to interrupt subroutine 00, through to bit 07 of Unit 3 which corresponds to subroutine 31. CC is the control code, the meaning of which depends on the value of N, as follows:
CC:
000 to
002
CC
000
001
002
N = 000 to 003 N = 004
Masks and unmasks interrupt bits for the designated Unit (N) according to the data in D. Bits corresponding to ON bits in
D are masked, those corresponding to OFF bits are unmasked. Masked bits are recorded and will be executed when they are unmasked (unless previously cleared).
Clears the masked interrupt bits of the designated
Unit (N) according to the corresponding ON bits in
D. The subroutines corresponding to bits cleared in this manner will not be executed when the bit is unmasked.
Copies the mask status of the designated IIU to D.
The interrupt time interval is set according to the data in D (00.01 to
99.99 s) The decimal point is not entered. The interrupt is cancelled if D is
00.00.
The time to the first interrupt is set according to the data in D (00.01 to
99.99 s) The decimal point is not entered. The interrupt is cancelled if D is
00.00.
Copies the time interval data to D.
N:
000 to
004
D:
IR
HR
AR
LR
TC
DM
#
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
143
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
NETWORK SEND
(@)SEND(90)
(CPU11)
Symbol
SEND(90)
S
D
C
Appendix E
Function
Transfers data from n source words (S is the starting word) to the destination words
(D is the first address) in node N of the specified network (in a SYSMAC LINK or NET
Link System). The format of the control words varies depending on the type of system. In both types of systems, the first control word (C) gives the number of words to be transferred.
For NET Link Systems, in word C+1, bit 14 specifies the system (0 for system 1, and
1 for system 0), and the rightmost 7 bits define the network number. The left half of word C+2 specifies the destination port
(00: NSB, 01/02: NSU), and the right half specifies the destination node number. If the destination node number is set to 0, data is transmitted to all nodes.
For SYSMAC LINK Systems, the right half of C+1 specifies the response monitoring time (default 00: 2 s, FF: monitoring disabled), the next digit to the left gives the maximum number of re-transmissions (0 to 15) that the PC will attempt if no response signal is received. Bit 13 specifies whether a response is needed (0) or not
(1), and bit 14 specifies the system number
(0 for system 1, and 1 for system 0). The right half of C+2 gives the destination node number. If this is set to 0, the data will be sent to all nodes.
S:
IR
SR
HR
AR
LR
TC
DM
NET Link
C n: no. of words to be transmitted (0 to 1000)
C+1
C+2
0X00 0000 Network no. (0 to 127)
Destination port no.
Destination node no.
(0 to 126)
SYSMAC LINK
C
C+1
C+2 n: no. of words to be transmitted, 0 to 1000
0XX0
0000
Re-transmissions
Response monitor time
(0.1 to 25.4 s)
0000 Destination node no.
(0 to 62)
Source N
S
S+1
Destination node N
D
D+1
Operand Data Areas
D/C :
IR
HR
AR
LR
TC
DM
S+n–1 D+n–1
SUBROUTINE ENTER
(@)SBS(91)
SBS(91) N
Calls subroutine N. Moves program operation to the specified subroutine.
N:
00 to 99
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
144
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
SUBROUTINE START
SBN(92)
Symbol
SBN(92) N
Function
Marks the start of subroutine N.
RETURN
RET(93)
Marks the end of a subroutine and returns control to the main program.
None
RET(93)
Appendix E
Operand Data Areas
N:
00 to 99
WATCHDOG TIMER
REFRESH
(@)WDT(94)
I/O REFRESH
(@)IORF(97)
WDT(94) T
IORF(97)
St
E
Sets the maximum and minimum limits for the watchdog timer (normally 0 to 130 ms).
New limits:
Maximum time = 130 + (100 x T)
Minimum time = 130 + (100 x (T–1))
T:
0 to 63
Refreshes all I/O words between the start
(St) and end (E) words. Only I/O words may be designated. Normally these words are refreshed only once per cycle, but refreshing words before use in an instruction can increase execution speed. St must be less than or equal to E.
St/E:
IR
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
145
Downloaded from Elcodis.com
electronic components distributor
Programming Instructions
Name
Mnemonic
NETWORK RECEIVE
(@)RECV(98)
(CPU11)
Symbol
RECV(98)
S
D
C
Appendix E
Function
Transfers data from the source words (S is the first word) from node N of the specified network (in a SYSMAC LINK or NET Link
System) to the destination words starting at D. The format of the control words varies depending on the type of system. In both types of systems, the first control word (C) gives the number of words to be transferred.
For NET Link Systems, in the second word
(C+1), bit 14 specifies the system (0 for system 1, and 1 for system 0), and the rightmost 7 bits define the network number. The left half of word C+2 specifies the source port (00: NSB, 01/02: NSU), and the right half specifies the source node number.
For SYSMAC LINK Systems, the right half of C+1 specifies the response monitoring time (default 00: 2 s, FF: monitoring disabled), the next digit to the left gives the maximum number of re-transmissions (0 to 15) that the PC will attempt if no response signal is received. Bit 13 specifies whether a response is needed (0) or not
(1), and bit 14 specifies the system number (0 for system 1, and 1 for system 0).
The right half of C+2 gives the source node number.
S:
IR
SR
HR
AR
LR
TC
DM
NET Link
C n: no. of words to be transmitted (0 to 1000)
C+1
C+2
0X00 0000
Source port no.
(NSB: 00, NSU: 01/02)
Network no. (0 to 127)
Source node no.
(0 to 126)
SYSMAC LINK
C
C+1
C+2 n: no. of words to be transmitted, 0 to 1000
0XX0
0000
Re-transmissions
Response monitor time
(0.1 to 25.4 s)
0000 Source node no.
(0 to 62)
Source node N
S
S+1
Destination node
D
D+1
Operand Data Areas
C/D:
IR
HR
AR
LR
TC
DM
S+n–1 D+n–1
Data Areas
These footnote tables show the actual ranges of all data areas. Bit numbers are provided (except for DM and TC areas); remove the rightmost two digits for word numbers.
IR SR HR TR AR LR TC DM #
00000 to 23515 23600 to 25507 HR 0000 to 9915 TR 0 to 7 AR 0000 to 2715 LR 0000 to 6315 TC 000 to 511 Read/Wr: DM 0000 to DM 0999
Rd only: DM 1000 to DM 1999
0000 to 9999 or 0000 to FFFF
146
Downloaded from Elcodis.com
electronic components distributor
Glossary
ASCII code
ASCII Unit
Backplane back-up baud rate bit central processing unit communication cable
Control System counter
CPU cycle time data area
[A(merican) S(tandard) C(ode for) I(nformation) I(nterchange)] A standard computer code used to facilitate the interchange of information among various types of data-processing equipment.
An Intelligent I/O Unit. The ASCII Unit has its own CPU and 16 kilobytes of memory. This Unit enables communication between the PC and any other device which uses ASCII code. The ASCII Unit can be programmed in BA-
SIC.
A base to which Units are mounted to form a Rack. Backplanes provide a series of connectors for these Units along with wiring to connect them to the
CPU and Power Supply. Backplanes also provide connectors used to connect them to other Backplanes. In some Systems, different Backplanes are used for different Racks; in other Systems, Racks differ only by the Units mounted to them.
A copy of existing data which is valuable if data is accidentally erased.
Transfer speed between two devices in a system measured in bits per second. For example, an optical sensor might be configured to send its information to the FIT at 9600 baud. It is important for both of the devices to be set to the same baud rate.
The smallest piece of information that can be represented on a computer. A bit has the value of either zero or one, corresponding to the electrical signals
ON and OFF. A bit is one binary digit.
A device that is capable of storing a program and data, and executing the set of instructions contained in the program. In a PC System, the central processing unit executes the program, processes I/O signals, communicates with external devices, etc.
Cable used to transfer data between components of a control system and conforming to the RS-232C or RS-422 standards.
All of the hardware and software components used to control other devices.
A Control System includes the PC System, the PC programs, and all I/O devices that are used to control or obtain feedback from the controlled system.
A PC function that counts the number of occurrences of a certain event.
An acronym for central processing unit.
The total time it takes the PC to perform internal operations, i.e., reset the watchdog timer, read the program, receive input data, send output data, and execute instructions. Cycle time is monitored by the watchdog timer within the PC, and if it takes longer than a certain specified amount of time, an error message may be generated, or the CPU may just stop. Cycle times will differ depending on the configuration of the system.
An area in the PC’s memory that is designed to hold a specific type of data, e.g., the LR area is designed to hold common data in a PC Link System.
147
Downloaded from Elcodis.com
electronic components distributor
data disk data link debugging default condition distributed control
EEPROM electrical noise
EPROM
Expansion I/O Unit factory computer flag
High-speed Counter host computer
Glossary
Floppy disk used to store information such as programs or I/O tables. The data disk should be used in drive B of the FIT.
Allows for the connection of up to 32 PCs in a Net Link System where each is contributing information to a common memory area. Data links may be established in the LR and/or DM memory areas.
The process of checking for errors in a program.
The original condition of a function or system. For example, the FIT’s default condition is to start from its hard drive, but this default condition can be changed so that it starts from a floppy disk drive.
An automation concept in which control of each portion of an automated system is located near the devices actually being controlled, i.e., control is decentralized and “distributed” over the system. Distributed control is a concept basic to PC Systems.
[E(lectrically) E(rasable) P(rogrammable) R(ead) O(nly) M(emory)] A type of
ROM in which stored data can be erased and reprogrammed. This is accomplished using a special control lead connected to the EEPROM chip and can be done without having to remove the EEPROM chip from the device in which it is mounted.
Electric ‘static’ that can disturb electronic communications. The ‘snow’ that can appear on a TV screen is an example of the effects of electrical noise.
[E(rasable) P(rogrammable) R(ead) O(nly) M(emory)] A type of ROM in which stored data can be erased, by ultraviolet light or other means, and reprogrammed.
An I/O Unit for a Package-type PC that provides more I/O points to the PC.
A general-purpose computer, usually quite similar to a business computer, that is used in automated factory control.
A bit that is turned ON and OFF automatically by the system in order to provide status information.
A Special I/O Unit. A High Speed Counter Unit counts independently of the
PC’s cycle time. This allows counting of very short, fast signals.
A computer that is used to transfer data to or receive data from a PC in a
Host Link system. The host computer is used for data management and overall system control. Host computers are generally small personal or business computers.
IBM PC/XT or AT, or compatibles instruction line
A computer that has similar architecture to, and is logically compatible with an IBM PC/XT computer; and that can run software designed for that computer.
A succession of instructions which begins with a load instruction at the left bus bar and ends at a right bus bar.
148
Downloaded from Elcodis.com
electronic components distributor
interface
I/O devices
I/O point
I/O table
I/O Unit
Limit Switch
Link Unit operating mode page parallel interface
PC
PCB
PC Link Unit
Photoelectric Switch
Power Supply printed circuit board
Glossary
An interface is the conceptual boundary between systems or devices and usually involves changes in the way the communicated data is represented.
Interface devices such as NSBs perform operations such as changing the coding, format, or speed of data.
The devices which are connected to the terminals on I/O Units, Special I/O
Units, or Intelligent I/O Units. I/O devices may be part of the Control System if they function to help control other devices, or they may be part of the controlled system if they interact directly with it.
The place at which an input signal enters the PC System or an output signal leaves the PC System. In physical terms, an I/O point corresponds to terminals or connector pins on a Unit; in terms of programming, an I/O point corresponds to an I/O bit in the IR area.
Diagram written to the IR memory area listing the type of I/O units controlled by a PC. It must be cleared before programming or when I/O units are changed. Tables can be read, verified, or transferred to a EPROM.
The most basic type of Unit mounted to a Backplane. I/O Units include Input
Units and Output Units, each of which is available in a range of specifications. I/O Units do not include Special I/O Units, Link Units, etc.
A switch that detects when an object has reached the limit of its movement by actually making contact with the object. Limit Switches are fitted to electric elevators, traveling cranes, etc. to indicate when a certain part of the equipment has traveled to the specified limit.
Any of the Units used to connect a PC to a Link System. These are Remote
I/O Units, I/O Link Units, PC Link Units, Host Link Units, and Net Link Units.
The Display Terminal Unit can operate in five different modes: Page Read,
Terminal, Dynamic Scan, Read/Write, and Self-Diagnosis.
One complete Display Terminal Unit screen. Two hundred screens can be stored on one RAM card .
The parallel interface uses the RS-232 connector, but is not serial communication. When parallel mode is selected as the communication mode, up to 16
Display Terminal Units can be connected to a PC in parallel.
An acronym for Programmable Controller.
An acronym for printed circuit board.
A Unit used to connect two or more PCs together so that they can exchange data through their LR areas.
A switch that uses light to detect the presence of an object.
A Unit that mounts to a Backplane in a Rack PC. It provides power at the voltage required by the other Units on the Rack.
A board onto which electrical circuits are printed for mounting into a computer or electrical device.
149
Downloaded from Elcodis.com
electronic components distributor
Glossary
Programmable Controller A small, computer-like device that can control peripheral equipment, such as an electric door or quality control devices, based on programming and peripheral input devices. Any process that can be controlled using electrical signals can be controlled by a PC. PCs can be used independently or networked together into a system to control more complex operations.
programming device
PROM
A peripheral device used to write programs and to input a program to a PC or to alter or monitor a program already stored in the PC. There are dedicated programming devices, such as Programming Consoles, and there are nondedicated programming devices, such as a host computer.
[P(rogrammable) R(ead) O(nly) M(emory)] A type of ROM into which the program or data may be written after manufacture, by a customer, but which is fixed from that time on.
PROM Writer
Proximity Switch
Rack PC
RAM register/registered
A PROM Writer is a device used to write data to ROM, PROM, and EPROM storage chips.
A switch that uses magnetic induction to measure the distance of a metallic object from the front of the switch.
A PC that is composed of Units mounted to one or more Racks. This configuration is the most flexible, and most large PCs are Rack PCs. A Rack PC is the opposite of a Package-type PC, which has all of the basic I/O, storage, and control functions built into a single package.
[R(andom) A(ccess) M(emory)] RAM will not retain data when power is disconnected. Therefore data should not be stored in RAM.
Storing text and graphics in the RAM/ROM card from a personal computer or the ASCII Unit. Graphics that have been written to the RAM/ROM card are referred to as registered messages.
Remote I/O Unit
ROM switching capacity stepping motor switch system configuration
A Unit that extends the distance an Expansion I/O Unit can be from the CPU.
[R(ead) O(nly) M(emory)] A type of digital storage that cannot be written to. A
ROM chip is manufactured with its program or data already stored in it, and it can never be changed. However, the program or data can be read as many times as desired.
The voltage/current that relay can switch ON and OFF.
An output device that rotates according to signals from the Control System.
The rotation is very precise and occurs in pre-defined “steps”.
An input device that sends either an ON or OFF signal to the Control System.
A switch can be operated either by a person or by the movement of a piece of equipment or material.
The arrangement in which Units in a System are connected. This term refers to the conceptual arrangement and wiring together of all the devices needed to comprise the System. In OMRON terminology, system configuration is used to describe the arrangement and connection of the Units comprising a
Control System that includes one or more PCs.
150
Downloaded from Elcodis.com
electronic components distributor
Unit watchdog timer word work bits
Glossary
In OMRON PC terminology, the word Unit is capitalized to indicate any product sold for a PC System. though most of the names of these products end with the word Unit, not all do, e.g., a Remote Terminal is referred to in a collective sense as a Unit. Context generally makes any limitations of this word clear.
A special timer inside the CPU that monitors the PC’s cycle time. The watchdog timer sets a flag if the cycle time becomes longer than a certain specified value. This is useful if the correct operation of your System depends on a certain maximum cycle time.
In digital circuits, a group of bits. Usually a word consists of four, eight, or sixteen bits. In C-series PCs, a word consists of sixteen bits. Words can be used to store data, or they can be used for I/O.
Bits in the IR area that are not being used for input or output. These bits can be used in the program in any way desired.
Downloaded from Elcodis.com
electronic components distributor
151
Downloaded from Elcodis.com
electronic components distributor
A-B
Assembly backplane, , connecting cable,
CPU,
Expansion I/O Unit,
I/O Units, mounting the Units,
Backplane,
IR word allocation, ,
Backplane Insulating Plates,
Battery, Memory Packs, replacement,
C
C200H-CPU1 1 battery, replacement, power consumption, calculation examples,
Cables, control components,
Control System,
Cooling clearance between Racks, cooling fan,
CPU,
C200H-CPU01/03,
C200H-CPU1 1, indicators,
Peripheral Device Connectors, cable connection, direct mounting, wiring,
CPU Rack,
Current consumption
24-V supply,
26-V supply,
5-V supply, calculation examples, cycle, cycle time,
D-E
Duct work
I/O wiring, power cables, electrostatic charge,
Emergency stop circuit,
Expansion I/O Rack,
Downloaded from Elcodis.com
electronic components distributor
Index
F-H factory computer,
Fuse
CPU and power supply, replacement,
Output, replacement,
Output Units,
Grounding ground terminal, line ground terminal, wire, humidity,
I-L
I/O Devices, connections,
I/O points, calculating the number of,
I/O Unit Cover,
I/O Units,
A-shape,
B-shape, connections,
E-shape, input devices, installation, environment, ambient conditions,
Insulating plates,
IR word allocation, work bits,
Limit Switch,
M
Memory Packs assembly, battery failure flag,
EEPROM chip,
EEPROM Pack,
EPROM chip how to mount, mounted to the printed circuit board,
EPROM Pack, how to mount to CPU,
RAM Pack, switches,
Mounting requirements,
DIN Rail mounting,
16-mm DIN Rail,
7.3-mm DIN Rail,
DIN Rail mounting bracket, procedure,
153
N-O
Noise cables,
I/O wiring, output devices,
Output Units, external fuse,
P
PC block diagram, flow chart, operation, role of,
Photoelectric Switch,
Power source, wiring,
Power supply,
AC power supply,
DC power supply, wiring, precautions, general, process control computer,
Programming Console, Hand–held,
Proximity Switch,
R
Relay, printed circuit board,
Relays, Output Unit, replacement,
Remote I/O,
PC Link Units,
Special I/O Units, word allocation,
Index
S
Sequential circuit (for power failure),
Servomotor, servomotor drivers, servomotors,
Solenoid,
Special I/O Units,
Remote I/O Slave Rack, static electricity, preventing, stepping motor, system configuration,
System Configurations,
Expansion I/O Racks,
Host Link Unit,
I/O Connecting cable,
Memory Packs,
Optical Fiber Cable,
Remote I/O Master Unit,
Remote I/O Slave Unit,
Special I/O Units,
Standard I/O Units,
SYSMAC Link Unit,
T
Terminal block, terminal block, wiring,
W
Wiring
AC Input Units,
DC Input Units, examples,
I/O devices,
I/O Units, terminal blocks, word allocation, for expanded PC, work bits,
154
Downloaded from Elcodis.com
electronic components distributor
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W111-E1-10
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
6
7
8
8A
8B
8C
Date
July 1989
February 1990
October 1990
May 1991
May 1992
December 1993
Revised content
Corrections to pages: 3, 6, 16 to 18, 21, 23, 26, 27, 31, 32, 33, 41, 51, 52, 53, 57,
58, and 60.
Entire manual reorganized and reproduced.
Revision of text and inclusion of new product information (C200H-CPU11-E, SYS-
MAC NET, SYSMAC LINK, C200H-OC225, and C200H-OD212)
Corrections to pages: 7, 10, 12, 13, 15, 16, 23, 27, 28, 34 to 39, 61, 63, 64, 82,
85, 94, 97 to 100, 103, 104.
Pages 33 to 38: Completely redone.
Page 102: Backplane model numbers revised.
Page 103: BC031-V1 and BC101-V1 added to note at bottom of page.
Page 104: Microwave ID Sensor and Analog I/O Units added.
Page 110: Terminal Resistor and Power Supply Adapter model numbers revised.
The manuals has also been reformatted, changing page numbers slightly.
Page 7: PC Operation Flowchart redone.
Page 27: The section reference in the second line corrected to Section 2-6
Memory Packs.
Page 28: “Optical Fiber Cable” in the lower left corner corrected to “Optical
Fiber Cable or Wire Cable”.
Pages 113 to 128: The following instructions are missing from Appendix E
Programming Instructions: LMSG(47), TERM(48), SYS(49), CMPL(60),
CTW(63), WTC(64), HTS(65), STH(66), VAL(69), SEND(90), and RECV(98).
(These instructions were originally added in revision 8, but inadvertently omitted from revision 8A.)
Multipoint I/O changed to High-density I/O throughout the manual. Scan time changed to cycle time throughout the manual.
Page 10: Model number corrections made in the first paragraph of CPU.
Page 28: Reference corrected for SYSMAC NET Link Unit and SYSMAC LINK
Unit.
Page 32: Table updated.
Page 33: Note added, 1.4 V corrected to 1.4 A in the top table.
Pages 34, 35: Models added and updated.
Page 37: Calculation of power consumption corrected.
Page 38: I/O Unit Cover description added.
Page 42: Ambient conditions added.
Page 79: “8 A/Unit” in Terminal Connections changed to “16 A/Unit”.
Page 82: Max. switching capacity changed.
Page 92: B7A Interface Unit specifications added.
Pages 97 to 105: Appendix C completely updated.
155
Downloaded from Elcodis.com
electronic components distributor
Revision code
9
10
Revision History
Date
February 1999
January 2001
Revised content
References to C200H-OA221 removed throughout the manual.
Pages 10, 23, 27, 31, 34, 92: C200H-OD21A added.
Pages 10, 23, 27, 31, 82, 84: Backplane model information corrected.
Pages 13, 19, 23, 63, 98. 99: Added information on E-shape I/O Units.
Page 18: Number of terminals for B-shape I/O Units corrected.
Pages 34: Model numbers of SYSMAC LINK and SYSMAC NET Link Units changed. C200H-OA224 added.
Pages 34, 66: C200H-IA222V added.
Pages 34, 76: C200H-OA222V added. C200H-OA222 removed.
Pages 34, 78: C200H-OA122-E added. C200H-OA224/OA223 added.
Pages 35: Analog I/O Units added/corrected.
Pages 39 to 40: Precautions for connecting DC two-wire sensors added.
Page 41: Caution added.
Page 57: Fuse specifications table added.
Pages 60, 61: Added step to procedures.
Page 63: Power consumption and dielectric strength corrected, and surge current added.
Pages 73 to 76: Specifications for C200H-ID218 and C200H-ID219 DC Input
Units added.
Page 77: Circuit configuration corrected for C200H-OA121-E.
Pages 84, 85: Circuit configurations changed for C200H-OD212 and
C200H-OD213.
Pages 95, 96: B7A Interface Unit information modified.
Page 99: Insulation plate mounting dimensions corrected.
Pages 100 to 111: Standard models list updated.
Page xii: Minor change made to last caution.
Page xiii: Changes made to wording of information on grounding and mounting.
Pages 16, 17: Minor changes made to graphics.
Page 17: Information on LG and GR terminals added.
Page 19: “Pack” changed to “Unit” in several places. Information on Memory
Units added.
Page 37: Minor change to last sentence.
Pages 51, 52: Information on power supply wiring added.
Page 63: S.I. data replaced with metric equivalent.
156
Downloaded from Elcodis.com
electronic components distributor
Downloaded from Elcodis.com
electronic components distributor
W111-E1-10
Downloaded from Elcodis.com
electronic components distributor
Download
Advertisement
Key features
Modular design for flexible system configuration
Supports a variety of I/O Units for diverse control applications
Offers expansion capabilities with I/O Racks
Includes safety precautions for safe and reliable operation
Provides memory unit support for program storage
Frequently asked questions
Avoid locations subject to direct sunlight, extreme temperatures or humidity, corrosive or flammable gases, dust, exposure to water, oil, or chemicals, and shock or vibration.
Always ground the system to 100 Ω or less, and ensure the power supply is OFF when mounting or dismounting units, assembling units, setting DIP switches, connecting cables, or connecting connectors.