OMRON C200H-TC @@@@ Temperature Control Unit Operation Manual
The C200H-TC@@@@ Temperature Control Unit measures the temperature of an object with a connected temperature sensor (thermocouple or platinum resistance thermometer) and controls the temperature according to a preset control mode. It features PID with feed-forward circuitry (Feed-forward PID) for stable temperature control, offering two control loops and various output specifications.
Advertisement
Advertisement
Cat. No. W225-E1-05
SYSMAC
C200H-TC
@@@
Temperature Control Units
OPERATION MANUAL
C200H-TC
@@@
Temperature Control Units
Operation Manual
Revised December 2005
iv
Notice:
OMRON products are manufactured for use according to proper procedures by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
!DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. Additionally, there may be severe property damage.
!WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Additionally, there may be severe property damage.
!Caution
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury, or property damage.
OMRON Product References
All OMRON products are capitalized in this manual. The word “Unit” is also capitalized when it refers to an OMRON product, regardless of whether or not it appears in the proper name of the product.
The abbreviation “Ch,” which appears in some displays and on some OMRON products, often means
“word” and is abbreviated “Wd” in documentation in this sense.
The abbreviation “PC” means Programmable Controller and is not used as an abbreviation for anything else.
Visual Aids
The following headings appear in the left column of the manual to help you locate different types of information.
Note Indicates information of particular interest for efficient and convenient operation of the product.
1,2,3...
1.
Indicates lists of one sort or another, such as procedures, checklists, etc.
OMRON, 1993
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in this publication.
v
vi
TABLE OF CONTENTS
PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
System Configuration and Features . . . . . . . . . . . . . . . . 1
Connections and Settings . . . . . . . . . . . . . . . . . . . . . . . . . 7
Data Setting Console Operation . . . . . . . . . . . . . . . . . . . 21
PC Memory Allocation and Programming. . . . . . . . . . . 35
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
B Sensor Temperature Measurement Ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
vii
About this Manual:
This manual describes the installation and operation of the C200H-TC @@@ Temperature Control Units and includes the sections described below. Also briefly described is the basic operation and installation of the C200H-DSC01 Data Setting Console.
Please read this manual carefully and be sure you understand the information provided before attempting to install and operate a Temperature Control Unit or Data Setting Console.
Section 1 provides Temperature Control Unit features and describes its basic system configuration.
Section 2 provides information on the connections and settings of the Temperature Control Units.
Section 3 provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
Section 4 provides the C200H PC’s memory allocation for the Temperature Control Units. Basic programming procedures and examples are also provided.
Section 5 provides possible errors and error remedies.
The four Appendices provide references dealing with specifications, sensor temperature measurement ranges, heater burnout detection, and dimensions.
!WARNING
Failure to read and understand the information provided in this manual may result in personal injury or death, damage to the product, or product failure. Please read each section in its entirety and be sure you understand the information provided in the section and related sections before attempting any of the procedures or operations given.
ix
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representative if you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-
INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE
PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS
DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT
LIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS
REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS
WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO
CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
xi
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products.
At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products:
• Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this manual.
• Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations.
• Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR
PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND
INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof.
xii
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other reasons.
It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and
Limitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
xiii
xiv
PRECAUTIONS
This section provides general precautions for using C200H Temperature Control Units and related devices.
The information contained in this section is important for the safe and reliable application of the C200H
Temperature Control Units. You must read this section and understand the information contained before attempting to set up or operate a C200H Temperature Control Unit.
Operating Environment Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
xv
Intended Audience
1
1
Intended Audience
This manual is intended for the following personnel, who must also have knowledge of electrical systems (an electrical engineer or the equivalent).
• Personnel in charge of installing FA systems.
• Personnel in charge of designing FA systems.
• Personnel in charge of managing FA systems and facilities.
2 General Precautions
The user must operate the product according to the performance specifications described in the relevant manuals.
Before using the product under conditions which are not described in the manual or applying the product to nuclear control systems, railroad systems, aviation systems, vehicles, combustion systems, medical equipment, amusement machines, safety equipment, and other systems, machines, and equipment that may have a serious influence on lives and property if used improperly, consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for the systems, machines, and equipment, and be sure to provide the systems, machines, and equipment with double safety mechanisms.
This manual provides information for programming and operating the Unit. Be sure to read this manual before attempting to use the Unit and keep this manual close at hand for reference during operation.
3
!WARNING
It is extremely important that a PC and all PC Units be used for the specified purpose and under the specified conditions, especially in applications that can directly or indirectly affect human life. You must consult with your OMRON representative before applying a PC system to the above-mentioned applications.
Safety Precautions
!WARNING
Do not attempt to take any Unit apart while the power is being supplied. Doing so may result in electric shock.
!WARNING
Do not touch any of the terminals or terminal blocks while the power is being supplied. Doing so may result in electric shock.
!WARNING
Do not attempt to disassemble, repair, or modify any Units. Any attempt to do so may result in malfunction, fire, or electric shock.
!WARNING
Provide safety measures in external circuits (i.e., not in the Programmable
Controller), including the following items, to ensure safety in the system if an abnormality occurs due to malfunction of the PC or another external factor affecting the PC operation. Not doing so may result in serious accidents.
• Emergency stop circuits, interlock circuits, limit circuits, and similar safety measures must be provided in external control circuits.
• The PC will turn OFF all outputs when its self-diagnosis function detects any error or when a severe failure alarm (FALS) instruction is executed.
xvi
Operating Environment Precautions
4
As a countermeasure for such errors, external safety measures must be provided to ensure safety in the system.
• The PC outputs may remain ON or OFF due to deposits on or burning of the output relays, or destruction of the output transistors. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
• When the 24-V DC output (service power supply to the PC) is overloaded or short-circuited, the voltage may drop and result in the outputs being turned OFF. As a countermeasure for such problems, external safety measures must be provided to ensure safety in the system.
!WARNING
Provide double safety mechanisms to handle incorrect signals that can be generated by broken signal lines or momentary power interruptions. Faulty operation may result in serious accidents.
!Caution
The Heating and Cooling Temperature Control Unit will not operate normally if the cycle time of the CPU Unit is less than 8 ms.
• If the cycle time is less than 8 ms (e.g., the program execution time is short), increase it to at least 8 ms.
• For the C200H, C200HS, or C200HX/HG/HE(-Z), use the SCAN instruction to set a minimum cycle time.
• For a CS-series PC, set the cycle time in the PC Setup (Programming
Console address 208, bits 00 to 15).
• If the IORF instruction is used for a Heating and Cooling Temperature
Control Unit, allow at least 8 ms between IORF executions.
4
!Caution
The write life for the EEPROM built into the Heating and Cooling Temperature
Control Unit is 100,000 operations. Bit corruption will occur if the memory is written more than 100,000 times. Do not use a Unit in which memory has been written more than 100,000 times.
Operating Environment Precautions
!Caution
Do not operate the control system in the following locations:
• Locations subject to direct sunlight.
• Locations subject to temperatures or humidity outside the range specified in the specifications.
• Locations subject to condensation as the result of severe changes in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust (especially iron dust) or salts.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to shock or vibration.
!Caution
Take appropriate and sufficient countermeasures when installing systems in the following locations:
• Locations subject to static electricity or other forms of noise.
xvii
Application Precautions
5
5
• Locations subject to strong electromagnetic fields.
• Locations subject to possible exposure to radioactivity.
• Locations close to power supplies.
!Caution
The operating environment of the PC system can have a large effect on the longevity and reliability of the system. Improper operating environments can lead to malfunction, failure, and other unforeseeable problems with the PC system. Be sure that the operating environment is within the specified conditions at installation and remains within the specified conditions during the life of the system.
Application Precautions
Observe the following precautions when using the PC system.
!WARNING
Always heed these precautions. Failure to abide by the following precautions could lead to serious or possibly fatal injury.
• Always ground the system to 100
Ω
or less when installing the Units. Not connecting to a ground of 100
Ω
or less may result in electric shock.
• Always turn OFF the power supply to the PC before attempting any of the following. Not turning OFF the power supply may result in malfunction or electric shock.
• Mounting or dismounting I/O Units, CPU Units, Memory Units, Power
Supply Units, or any other Units.
• Assembling the Units.
• Setting DIP switches or rotary switches.
• Connecting cables or wiring the system.
• Connecting or disconnecting the connectors.
!Caution
Failure to abide by the following precautions could lead to faulty operation of the PC or the system, or could damage the PC or PC Units. Always heed these precautions.
• Fail-safe measures must be taken by the customer to ensure safety in the event of incorrect, missing, or abnormal signals caused by broken signal lines, momentary power interruptions, or other causes.
• Always use the power supply voltages specified in this manual. An incorrect voltage may result in malfunction or burning.
• Take appropriate measures to ensure that the specified power with the rated voltage and frequency is supplied. Be particularly careful in places where the power supply is unstable. An incorrect power supply may result in malfunction.
• Install external breakers and take other safety measures against short-circuiting in external wiring. Insufficient safety measures against short-circuiting may result in burning.
• Install Units as far as possible away from devices that generate strong, high-frequency noise.
• Do not drop a Unit or subject it to excessive shock or vibration.
• Do not apply voltages to the Input Units in excess of the rated input voltage. Excess voltages may result in burning.
xviii
Application Precautions
5
• Do not apply voltages or connect loads to the Output Units in excess of the maximum switching capacity. Excess voltage or loads may result in burning.
• Disconnect the LG and GR terminal on the Power Supply Unit when performing withstand voltage tests or insulation resistance tests. Not disconnecting the functional ground terminal may result in burning.
• Be sure that all the mounting screws, terminal screws, and cable connector screws are tightened to the torque specified in this manual. Incorrect tightening torque may result in malfunction.
• Leave the label attached to the Unit when wiring. Removing the label may result in malfunction if foreign matter enters the Unit.
• Remove the label after the completion of wiring to ensure proper heat dissipation. Leaving the label attached may result in malfunction.
• Double-check all wiring and switch settings before turning ON the power supply. Incorrect wiring may result in burning.
• Wire correctly. Incorrect wiring may result in burning.
• Mount Units only after checking terminal blocks and connectors completely.
• Be sure that the terminal blocks, Memory Units, expansion cables, and other items with locking devices are properly locked into place. Improper locking may result in malfunction.
• Check the user program for proper execution before actually running it on the Unit. Not checking the program may result in an unexpected operation.
• Confirm that no adverse effect will occur in the system before attempting any of the following. Not doing so may result in an unexpected operation.
• Changing the operating mode of the PC (including changing the Startup Mode).
• Force-setting/force-resetting any bit in memory.
• Changing the present value of any word or any set value in memory.
• Resume operation only after transferring to the new CPU Unit the contents of the DM Area, HR Area, and other data required for resuming operation. Not doing so may result in an unexpected operation.
• Do not pull on the cables or bend the cables beyond their natural limit.
Doing either of these may break the cables.
• Do not place objects on top of the cables or other wiring lines. Doing so may break the cables.
• Use crimp terminals for wiring. Do not connect bare stranded wires directly to terminals. Connection of bare stranded wires may result in burning.
• When replacing parts, be sure to confirm that the rating of a new part is correct. Not doing so may result in malfunction or burning.
• Before touching a Unit, be sure to first touch a grounded metallic object in order to discharge any static built-up. Not doing so may result in malfunction or damage.
xix
Application Precautions
5 xx
SECTION 1
System Configuration and Features
This section describes Temperature Control Unit features and describes its basic system configuration.
1
2
Features
1-1 Features
Section 1-1
The Temperature Control Unit measures the temperature of an object with a connected temperature sensor (thermocouple or platinum resistance thermometer) and controls the temperature according to a preset control mode.
PID with Feed-forward Circuitry (Feed-forward PID)
Stable temperature control is achieved using PID control with feed-forward circuitry and an auto-tuning feature.
ON/OFF control can also be selected.
Two Temperature Control Loops with a Single Unit
Two versions of Temperature Control Unit are available: the C200H-TC00 @ for thermocouple use and the C200H-TC10 @ for platinum resistance thermometers, each offering two control loops.
Comprehensive Output Specifications
Three types of output specification versions are available: C200H-TC
@@
1 for transistor output, C200H-TC
@@
2 for voltage output, and C200H-TC
@@
3 for current output.
Heater Burnout Detection
Through a Current Transformer, heater burnout can be quickly detected with a minimum current difference of 0.5 A and a heater burnout detection setting range of 0.1 to 4.9 A, and allows for the rapid correction of problems. Heater burnout detection is possible for each of the two control loops.
Eight Banks of Data Settings
Eight data values such as set point (SP) and alarm set values can be preset in eight data banks for easy selection.
Data Input and Display
The C200H-DSC01 Data Setting Console (sold separately) is used to input data and display process values (PV) and set values (SV).
The easy-to-read display can be panel-mounted.
User Programs Allow Reading and Writing of Data
The 21 commands are used to read and set data with the C200H user programs.
Basic System Configuration
1-2 Basic System Configuration
C200H/C200HS, C200HX/HG/HE, or CS-series PC
Section 1-2
Temperature Control Unit:
C200H-TC00 @ (for thermocouples)
C200H-TC10 @ (for platinum resistance thermometers)
RUN
Connecting cables:
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Recommended cable:
ES1000-CA021@@@
(1/2 m)
24 VDC
Data Setting Console
C200H-DSC01
Loop 1
Temperature sensor
Electric furnace
Heater
Current
Transformer
(CT)
Loop 2
Temperature sensor
Electric furnace
Heater
Current
Transformer
(CT)
Relay box
Remote I/O Terminal or
Connector Terminal
Block Converter Unit
Solenoid switch
3
Basic System Configuration
Section 1-2
Temperature Control Unit Models
Sensor
Thermocouple
Platinum resistance thermometer
Output type
Transistor output Voltage output
C200H-TC001
C200H-TC101
C200H-TC002
C200H-TC102
Current output
C200H-TC003
C200H-TC103
Applicable CPU Units
PC Series CPU Unit Mounting restrictions
None CS Series
C200HX/HG/HE
C200HS
CS1H-CPU @@ -E
CS1G-CPU @@ -E
C200HE-CPU11/32/42-E/ZE
C200HG-CPU33/43-E/ZE
C200HX-CPU34/44-E/ZE
C200HG-CPU53/63-E/ZE
C200HX-CPU54/64-E/ZE
C200HX-CPU65-ZE/85-ZE
C200HS-CPU01-E/01-EC/21-E/21-EC/31-E/03-E/
23-E/33-E
C200H-CPU01-E/03-E/11-E/21-E/22-E/23-E/31-E
None
None
None
C200H
Number of Units
Note
The Temperature Control Unit belongs to the C200H Special I/O Unit group. A maximum of ten Special I/O Units (including PC Link Units) can be mounted on the CPU Rack, Expansion I/O Rack, and Slave Rack.
1.
Refer to the manual for your CPU Unit for information on which Units belong to the Special I/O Unit group.
2.
The Units used are limited by the maximum supply current and current consumption. Refer to the manual for your CPU Unit for specific information.
3.
The number of Units used with a Slave Rack is limited by data transmission considerations, as described below.
Number of Units
Mountable on Slave Rack
A
High-speed Counter Units
Position Control Units
(NC111/112)
ASCII Unit
Analog I/O Units
ID Sensor Units
Fuzzy Logic Unit
4 units max.
The number of Special I/O Units used with a Slave Rack is limited by data transmission considerations, as shown in the table below. The numbers in the table indicate the maximum number of Units of groups A, B, C, or D which can be used with a single Slave Rack.
B
High-density and Mixed I/O
Units
Temperature Control Units
Heat/Cool Temperature Control Units
PID Control Units
Cam Positioner Unit
C
Temperature Sensor Units
Voice Unit
8 units max.
6 units max.
D
Position Control Unit
(NC211)
2 units max.
Note
Cannot be mounted to the two rightmost slots on the CPU Rack.
1.
When a combination of Units from groups A, B, C, and D is used, the number from each group must satisfy both the following equations:
3A + B + 2C + 6D
≤
12
A + B + C + D
≤
8
4
Basic System Configuration
Section 1-2
Precautions
2.
Other Units can be added until the total number of units reaches ten. If PC
Link Units are used, the number of Units including the PC Link Units must not exceed ten.
The IR area of the C200H Special I/O Unit is allocated according to the setting of the unit number switch on the front panel, not the address of the slot where
for the allocation of the memory area.
Leave the two slots next to the CPU free. It is not possible to use devices connected to the CPU (such as the Programming Console) if these slots are occupied.
If the C200H Slave Rack is connected to another SYSMAC model Remote I/O
Master Unit, such as the C500, C1000H, or C2000H, it is not possible to use a
Special I/O Unit with the C200H Slave Rack.
!WARNING
Always turn the PC power OFF before connecting or disconnecting a Unit, terminal block, or output connector.
New Functions
!Caution
Connect thermocouples with the appropriate compensating conductor.
Wire I/O leads in separate ducts from power leads to prevent noise problems.
Units with the following lot number or later support the following new functions.
01 Z 4 0
Year (1994): Last digit of the Christian year
Month (December): (9: September, X: October,
Y: November, X: December)
Day (1st)
Descriptions of New Functions
RUN/STOP Bits
Stop Bits have been added. These bits are supported with either fixed or normal memory allocations.
Word (n+2), bit 06
Word (n+2), bit 04
Loop 1 Stop Bit
Loop 2 Stop Bit
Turn OFF to perform temperature control for the loop. Turn ON to stop control.
Note These bits cannot be used when SW203-5 is set to ON to stop control in
PROGRAM mode. When SW203-5 is ON, control is always stopped.
Unit status will be as shown in the following table depending on the combination of SW203-5 settings and operating mode of the CPU Unit.
SW203-5 setting
Operating mode of CPU
Unit
Stop Bits OFF (Run)
ON (Stop)
OFF (control continues)
RUN or
MONITOR
RUN
STOP
PROGRAM
RUN
STOP
ON (control stops)
RUN or
MONITOR
RUN
STOP
PROGRAM
STOP
STOP
• To run or stop the temperature control using the Stop Bits, set SW203-5 to
OFF.
• To run or stop the temperature control only through the operating mode of the CPU Unit, keep the Stop Bit OFF (RUN).
5
Basic System Configuration
Section 1-2
RUN/STOP Monitor Flags
Stop Flags have been added. These flags are supported with either fixed or normal memory allocations.
Word (n+8), bit 08
Word (n+9), bit 08
Loop 1 Stop Flag
Loop 2 Stop Flag
When OFF, temperature control is being performed for the loop. When ON, control is not being performed.
These Flags turn ON and OFF depending on whether temperature control is run or stopped. Therefore, they do not necessarily have the same status as the Stop Bits described above.
RAM Write Commands
Previously, commands could be used to read and write to the EEPROM only.
These new commands allow writing to RAM.
When various settings require frequent rewriting, write to RAM, verify the setting values, and then save the data by writing it to EEPROM. The data written to the RAM will be deleted when the power is turned OFF.
The following commands can be used to write to RAM.
Parameter
Set point 4
Execution bank number 4
Alarm SV 1
Alarm SV 2
4
4
Input shift value
Proportional band
Integral (reset) time
Derivative (rate) time
SP lower limit
SP upper limit
Control period
Hysteresis
Alarm hysteresis
Heater burnout current
Alarm 1 mode
Alarm 2 mode
6
6
5
5
5
5
5
5
4
4
4
4
Command
3
4
0
2
7
8
0
1
7
8
5
6
4
5
9
B
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Write
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
Read
6
SECTION 2
Connections and Settings
This section provides information on the connections and settings of the Temperature Control Unit.
2-3-3 Data Setting Console Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
8
Nomenclature
2-1 Nomenclature
C200H-TC00
@
(For Thermocouple)
Front Panel
Model label
Cover
RUN indicator
SW2
(switching memory contents and setting direction under the cover)
SW1
(Unit number setting)
Data Setting Console connector
Rear Panel
Section 2-1
SW202
(sensor type setting)
SW203
(operation and function settings)
Rack connector
Output connector
Sensor input terminal block
Cold junction compensator
Switch Settings
C200H-TC10
@
(For Platinum Resistance Thermometer)
Front Panel
Model label
Cover
Rear Panel
RUN indicator
SW2
(switching memory contents and setting direction under the cover)
SW1
(Unit number setting)
Data Setting Console connector
Section 2-2
SW202
(sensor type setting)
SW203
(operation and function settings)
Rack connector
Output connector
Sensor input terminal block
Indicators
RUN
Lit when the Temperature Control Unit is operating normally. Unlit when an alarm occurs, and Unit operation stops.
2-2 Switch Settings
The function and setting of switches are identical for all models, except
SW202.
Unit Number
SW1
Unit number setting
8
6
4
2
(1)
0
(9)
(3)
(7)
(5)
The cut-out indicates the selected position. Turn the switch with a flat-blade screwdriver. Turn the switch until it clicks in position.
Do not leave the switch between two settings.
9
Switch Settings
Section 2-2
The addresses are allocated as shown in the following table according to the
Unit number setting.
7
8
5
6
9
0
3
4
1
2
Unit No. setting Allocated address
Wd 100 to 109
Wd 110 to 119
Wd 120 to 129
Wd 130 to 139
Wd 140 to 149
Wd 150 to 159
Wd 160 to 169
Wd 170 to 179
Wd 180 to 189
Wd 190 to 199
The switch is factory-set to 0.
Note If the Unit number is set to an existing unit number, an alarm occurs and the
PC does not operate.
Turn the PC power OFF before setting the unit number. If the setting is changed with the power ON, the new setting will not be valid until the power is turned OFF and back ON again.
Switching Memory Contents and Setting Direction
SW2
Switching memory contents and setting direction
Remove the cover and set the switch with the tip of a ballpoint pen or similar object.
ON
O F F
Pin Pin 1
Function Switching memory contents
ON Normal
OFF Fixed
OFF
Pin 2
Setting direction
CPU Unit
Data Setting Console
The switch is factory-set to OFF: Parameters can be set from the Data Setting
Console only.
The new setting is valid immediately after the switch setting is changed.
10
Switch Settings
Removing and Attaching the Cover
Removing the Cover Attaching the Cover
Section 2-2
Switching Memory
Contents
Setting Direction
Sensor Type
C200H-TC00
@
Insert a small flat-blade screwdriver between the case and the cover at the top of the Unit and lever off the cover.
Place the right edge of the cover against the case and press into position.
The contents of the allocated memory differ according to the Unit number setting.
Normal
Fixed
Data can be set as required using commands (Refer to
).
Fixed data is allocated to memory. Direct reading and writing of data is possible.
Refer to
for details of the memory contents.
Selects whether the data settings are made from the Data Setting Console or from the C200H PC, using a user program or Programming Console.
Executed Bank Number
The reading and setting of the executed bank number are possible from a user program or from a device, such as the Programming Console, regardless of the ON/OFF setting of switch SW2-2.
SW202
Sensor type setting
Setting
0
Sensor type
R
1
S
2
K
3
J
4
T
5
E
6
B
7
N
8
L
9
U
The switch is factory-set to 2.
The selected position is shown by the arrow. Turn the switch with a small flatblade screwdriver.
Selected position
11
Switch Settings
C200H-TC10
@
Section 2-2
OFF
ON
OFF
Setting
ON
Sensor type
JPt
Pt
The switch is factory-set to OFF.
See Appendix B Sensor Temperature Measurement Range for the measurable temperature range.
Operation and Function Setting
SW203
Operation and Function Setting
NO
4
3
2
1
6
5
Pin
OFF ON
Function
Not used
Operation in C200H program mode
Loop 2
Display units
Control action
Control method
OFF
---
Continue control
---
ON
Interrupt control
Enabled
°
C
Disabled (not used)
°
F
Reverse (heating control) Normal (cooling control)
Feed-forward PID ON/OFF control
The switch is factory-set to OFF.
Operation in CPU Unit
Program Mode
Selects if the temperature control is continued or interrupted when the CPU
Unit is set to PROGRAM mode.
Note Units with a lot number of 01Z40 or later are provided with Stop Bits for loops
1 and 2 in bits 06 and 04 of word (n+2). For further information, refer to
Loop 2
Display Units
Note
Selects if input Loop 2 is used or not.
1.
Always set this switch to the ON (disabled) position when input Loop 2 is not used. A sensor error occurs if this switch is set to the OFF (enabled) position when no temperature sensor is connected to Loop 2.
2.
Use input Loop 1 when only one loop is used.
It is not possible to use Loop 2 if Loop 1 is not used.
Selects whether setting and SVs displayed on the Data Setting Console are in
Celsius or Fahrenheit.
12
Wiring
Control Action
Control Method
2-3 Wiring
2-3-1 Input Wiring
C200H-TC00
@
Thermocouple
Section 2-3
Reverse:
For heating control with a heater. The heater output is increased when the measured temperature is below the SP (i.e., a negative temperature difference).
Normal:
For cooling control of overheated objects using cooling water or some other method. The cooling water output is increased when the measured temperature is above the SP (i.e., a positive temperature difference).
Selects the method of control.
CT: Current Transformer
TC: Thermocouple
Loop 1
Heater wire
CT
TC
CT
Loop 2
TC
24 VDC
0.2 A
The 24-VDC output from the
C200H CPU or the Power
Supply Units is convenient.
A4
A5
A6
A7
A8
A9
Terminal No.
A0
A1
A2
A3
CT
CT
TC (–)
TC (+)
CT
CT
TC (–)
TC (+)
24 VDC
0 V
Terminal name
Loop 1
Loop 2
A4
A5
A6
A7
A0
A1
A2
A3
A8
A9
Refer to the table below.
13
Wiring
C200H-TC10
@
Platinum Resistance Thermometer
Section 2-3
CT: Current Transformer
Pt: Platinum resistance thermometer
Loop 1
CT
Heater wire
Pt
CT
Loop 2
Pt
24 VDC
0.2 A
The 24-VDC output from the
C200H CPU or the Power
Supply Units is convenient.
A5
A6
A7
A8
A9
Terminal No.
A0
A1
A2
A3
A4
CT
CT/Pt (B)
Pt (B)
Pt (A)
CT
Terminal name
Loop 1
Loop 2
CT/Pt (B)
Pt (B)
Pt (A)
24 VDC
0 V
Screw down Pt(B) and CT together at terminals A1 and A5.
A3
A4
A5
A6
A0
A1
A2
A7
A8
A9
Refer to the table below.
Input Wiring Precautions
1,2,3...
1.
Set the type of temperature sensor to thermocouple or platinum resistance thermometer with SW202 on the rear of the Unit.
The Unit will not operate correctly if the switch setting does not match the type of temperature sensor connected.
Do not connect different types of temperature sensors to Loop 1 and Loop
2.
2.
If no input lead is connected to Loop 2, turn SW203-4 on the rear of the
Unit ON to disable Loop 2. A sensor error occurs if this switch is set to the
OFF (enabled) position when no temperature sensor is connected to Loop
2.
3.
Be sure to connect (+) and (–), and (A) and (B) correctly.
4.
Wire I/O leads in separate ducts from power leads to prevent noise problems.
5.
A voltage of 24 VDC is used for the voltage output, current output and Data
Setting Console power supply. (The power for the transistor output is supplied from the output connector.)
14
Wiring
Terminal Block
Connections
Section 2-3
6.
The terminal block is removable. Make sure that it is attached correctly after the input wiring connections are completed.
Tighten the terminal block screws to a torque of 0.8 N • m.
Crimp Terminals
The screws on the terminal block are M3.5 self-rising terminal screws. Use the following types of M3.5 crimp terminals.
7 mm max.
7 mm max.
Soldered Lead
Strip insulation from 7 to 10 mm at the end of the wire and carefully solder the lead.
7 to 10 mm
10
Compensating
Conductors
B
R
S
Type of thermocouple
Symbol
---
---
Previous symbol
(reference)
---
K
E
J
CA
CRC
IC
Connect a thermocouple with the appropriate compensating conductor from the table below.
Compensating conductor Classification by
Symbol Previous symbol
(reference) application and tolerance
BX-G ---
RX-G, SX-G ---
General-purpose, standard class
RX-H, SX-H --Heat-resistant, standard class
KX-G
KX-GS
KX-H
WCA-G
WCA-GS
WCA-H
General-purpose, standard class
KX-HS WCA-HS
Heat-resistant, standard class
Heat-resistant, precision class
WX-G
WX-H
VX-G
EX-G
EX-H
JX-G
JX-H
WCA-G
WCA-H
WCA-G
WCRC-G
WCRC-H
WIC-G
WIC-H
General-purpose, standard class
Heat-resistant, standard class
General-purpose, standard class
General-purpose, standard class
Heat-resistant, standard class
General-purpose, standard class
Heat-resistant, standard class
Copper
Iron
Copper
Iron
Constituent materials
+ conductor
Alloy with nickel or chrome as major constituent
Alloy with nickel or chrome as major constituent
– conductor
Copper
Alloy with copper or nickel as major constituent
Alloy with nickel as major constituent
Alloy with copper or nickel as major constituent
15
Wiring
Section 2-3
T
Type of thermocouple
Symbol Previous symbol
(reference)
CC
Compensating conductor Classification by
Symbol Previous symbol application and tolerance
(reference)
TX-G WCC-G
TX-GS ---
General-purpose, standard class
General-purpose, precision class
TX-H
TX-HS
WCC-H
---
Heat-resistant, standard class
Heat-resistant, precision class
Copper
Constituent materials
+ conductor – conductor
Alloy with copper or nickel as major constituent
Wiring Platinum
Resistance Thermometers
Current Transformer
Connect a platinum resistance thermometer with copper wire. All three leads should have the same thickness and the same length to give them identical resistances. Do not branch the two (B) leads near the terminal block as this increases measurement errors.
Use an E54-CT1 or E54-CT3 Current Transformer (CT). Refer to Appendix C
Heater Burnout Detection for details of the Current Transformer specifications and installation dimensions.
2-3-2 Output Wiring
Connection Diagrams
C200H-TC
@
01 Transistor Output
24 VDC
OUT1
OUT2
B
A
NC
10
9
NC
NC
NC
NC NC
COM
24 VDC
2
1
2
1
COM
24 VDC
NC: Not connected
The pairs of terminals B2 to A2 and B1 to A1 are shorted internally. Always supply power to the 24-VDC terminal (B1) as this drives the internal circuits.
C200H-TC
@
02/TC
@
03 Voltage/Current Output
A
B
OUT1 (+)
OUT2 (+)
NC NC
10 10
9 9
NC NC
OUT1 (−)
OUT2 (−)
16
Wiring
Circuit Diagrams
C200H-TC
@
01 Transistor Output
C200H-TC
@
02 Voltage Output
OUT (+)
OUT (−)
24 VDC
OUT
COM
Section 2-3
C200H-TC
@
03 Current Output
OUT (+)
OUT (−)
Applicable Connectors
Connector Wiring
Precautions
Connection Precautions
The following connector set manufactured by Fujitsu is included with the Unit:
FCN-361J032-AU (soldering connector)
FCN-360C032-B (cover)
After soldering the lead to each pin, insulate with heat-shrink tube to prevent shorting with the adjacent terminal.
Tighten the screws after inserting the connector into the Unit. Push the connector firmly into the Remote I/O Terminal or Connector Terminal Block Converter Unit until it fully locks.
17
Wiring
Output Cable
Wiring Diagrams
63
Section 2-3
The output cables in the table below are recommended.
Model
ES1000-CA021-102
ES1000-CA021-202
1 m
2 m
Cable length (L)
32-pin connector
(manufactured by Fujitsu)
FCN-361J032-AU
L
20-pin connector
(manufactured by OMRON)
XG4M-2030
30
28
46
32-pin connector
B
A
16 16
10 10
9 9
2
1
2
1
B10
B9
A10
A9
B2
B1
A2
A1
20-pin connector
16.1
1 11
2 12
9 19
10 20
1
11
2
12
9
10
19
20
Note
The pin numbers of the 20-pin connector are marked for convenience.
Refer to them from the
∆
mark.
18
Wiring
Remote I/O Terminal
Section 2-3
Remote I/O Terminal in the table below is recommended for transistor output.
Model Specification
G7TC-OC08 Common (+)
Relays used
8 x G7T-1112S (max. resistive load: 220 VAC, 2A)
Note One P7TF-OS08 I/O Terminal and two G7T-1112S Relays may be purchased separately and used.
Wiring Diagram External View
OUT1 OUT2
24 VDC
Wiring to the heater
Connector Terminal Block
Converter Unit
The Connector Terminal Block Converter Units in the table below are recommended for voltage output and current output type.
Model
XW2B-20G4
XW2B-20G5
Terminal screw size
M 2.4
M 3.5
External View
2-3-3 Data Setting Console Cables
Connecting Cable
Use the connecting cables in the table below (sold separately) to connect the
Unit to the Data Setting Console.
Model
C200H-CN225
C200H-CN425
2 m
4 m
Cable length (L)
L
39
17.3
17.5
16.1
10
19
Wiring
Section 2-3
Connection Precautions
1,2,3...
1.
Tighten the lock screws after inserting the connector into the Unit.
2.
Push the connector firmly into the Data Setting Console until the clips fully lock.
3.
Power is supplied through the connecting cable from the Temperature
Control Unit. Nothing appears on the Data Setting Console display if no power is supplied to input terminals A8 and A9 of the Temperature Control
Unit.
4.
Install the supplied connector cover when the cable is not connected.
20
SECTION 3
Data Setting Console Operation
This section provides the basic operating procedures of the Data Setting Console including parameter settings and displays.
3-4-1 Table of Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3-4-2 How to Display and Set Parameter Data . . . . . . . . . . . . . . . . . . . . .
21
Operating Procedure
Section 3-1
3-1 Operating Procedure
After preparing the CPU Unit, follow the procedure below to use the Temperature Control Unit.
1,2,3...
1.
Set the switches on the front and rear panels according to the operating conditions. (Refer to
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
2.
Mount to Rack.
Turn OFF the PC power supply before mounting or dismounting the C200H on the Rack.
3.
Connect the input wiring. (Refer to
.)
The 24-VDC power supply must be connected. The Data Setting Console will not operate unless the 24-VDC power supply is connected. The sensors can be connected immediately before the system is tested.
4.
Connect the Data Setting Console. (Refer to
5.
Turn ON the 24-VDC power supply and the PC power supply.
Set the CPU Unit to PROGRAM mode.
6.
Set data from the Data Setting Console. (Refer to the rest of this section.)
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in PROGRAM mode) and the CPU Unit is set to PROGRAM mode.
• When the Stop Bit (word n+2, bit 06 for loop 1 and bit 04 for loop 2) is
ON.
In all other cases, the executed bank number (default value = 1) is displayed and the bank number cannot be changed from the Data Setting
Console. Change the executed bank number with a user program or with a device, such as the Programming Console.
7.
Test operation and adjust data. (Refer to the rest of this section.)
Connect the output wiring and turn on the heater power to start the test operation. Monitor the control conditions and adjust the data until the required control is achieved.
8.
Create the user programs. (Refer to
SECTION 4 PC Memory Allocation and Programming
Create the user programs for data setting, monitoring, and switching the bank number, as required. Set SW2-2 under the display cover to the ON position to enable data setting from the CPU Unit.
9.
Start operation.
22
Data Flow
3-2 Data Flow
Section 3-2
The data flow in the Temperature Control Unit is shown in the diagram below.
If SW2-2 is ON
Write
Temperature
Control Unit
I/O bus
Read
CS-series or
C200H CPU
Unit
Read Write If SW2-2 is OFF
Data Setting
Console
Data Settings from Data
Setting Console
The read operation and setting the executed bank number are possible from a user program or from a device, such as the Programming Console, regardless of the ON/OFF setting of SW2-2.
Data written from the Data Setting Console and data written with the
EEPROM write commands when SW2-1 (switching memory contents) is set to Normal are written to the Temperature Control Unit EEPROM and are consequently retained when the power supply is turned OFF.
Data written with RAM write commands when SW2-1 (switching memory contents) is set to Normal, the SP value set when SW2-1 (switching memory contents) is set to Fixed and executed bank number settings made from the CPU
Unit are written directly to RAM and are not saved to EEPROM. This data is lost when the power supply is turned OFF.
Set SW2-2 under the display cover to the OFF position to enable data setting from the Data Setting Console.
While Temperature Control Unit is in control operation, all data can be set using the specified executed bank number (default value = 1).
Change the executed bank number with a user program or with a device, such as the Programming Console. The executed bank number cannot be changed from the Data Setting Console.
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in the PROGRAM mode) and the CPU Unit is set to PROGRAM mode.
23
Nomenclature and Features
Section 3-3
• When the Stop Bit (word n+2, bit 06 for Loop 1 and bit 04 for Loop 2) is
ON.
3-3 Nomenclature and Features
3-3-1 Nomenclature
Front View Side View
Data display
Operation indicators
Display for Cam
Positioner
Cover
Display Key
(With cover open)
Level Key
Down Key
Up Key
Operation keys
Select parameters
Set data
Switch Loops
Loop Key
Temperature Control Unit connector
Connecting cable (sold separately)
C200H-CN225 (2 m)
C200H-CN425 (4 m)
Panel mounting bracket
(Refer to
Appendix D Dimensions for details about panel mounting.)
Rear View
The bottom row of the operation keys have upper and lower labels. The upper labels apply to Temperature Control Unit operation. The lower labels are for the Cam Positioner Unit.
Two display sheets are supplied: one for the Temperature Control Unit and one for the Cam Positioner Unit. If the Data Setting Console is to be used with the Temperature Control Unit only, stick the display sheet for the Temperature
Control Unit.
24
Nomenclature and Features
Section 3-3
3-3-2 Features
Data Display
Name Function
PV (Process Value) Displays the PV or the parameter symbol selected with the
Level or Display Key (Refer to next page).
SV (Set Value) Displays the SV or setting/monitored data corresponding to the parameter symbol selected with the Level, Display or Loop
Keys and indicated in the PV display. Displays the SP when the PV is indicated in the PV display.
BK (Bank Number) Displays the executed bank number. Displays the bank number of the displayed data when temperature control is interrupted. (See note.)
Note Temperature control is interrupted when SW203-5 on the rear panel is set to
ON and also the CPU Unit is set to PROGRAM mode, or when the Stop Bit
(word n+2, bit 06 for loop 1 and bit 04 for loop 2) is ON.
Operation Indicators
Name Function
LOOP2
OUT (Output)
Indicates whether the displayed settings relate to Loop 1 or Loop
2. Press the Loop Key and hold down for approximately 2 seconds to switch between Loop 1 and Loop 2.
Indicator OFF:Loop 1
Indicator ON: Loop 2
Turns ON when the output is ON for transistor output or voltage output types.
AT (Auto-tuning) Blinks at approximately 1 second intervals during auto-tuning.
These indicators relate to the currently displayed loop.
HB (Heater
Burnout)
Turns ON to indicate a heater burnout alarm.
ALM1 (Alarm) Turns ON to indicate the temperature is in the alarm range set with Alarm SV 1
(upper- and lower-limit alarm). Refer to the following page.
Display Patterns
Note The Data Setting Console will not operate unless a 24-VDC power supply is connected to the Temperature Control Unit input terminals.
Display Pattern 1 Display Pattern 2
Process value
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Set point
Executed bank number or displayed bank number
Indicator OFF: Loop 1
Indicator ON: Loop 2
Parameter symbol
SV (Set value)
Monitored value
Execution status
25
Parameter Displays and Settings
Operation Keys
Name
Level Key
Display Key
Loop Key
Up Key
Down Key
Section 3-4
Function
The parameter items are divided into three display groups (Refer to display levels 0 to 2 on the next page). Press this key to switch from one group to another. The display levels automatically cycle in the sequence 0 –> 1 –> 2 –> 0 when the key is held down for approximately 2 seconds.
Press this key to select the required parameter from the selected display level 0 to 2 (Refer to table below).
The parameters cycle automatically when the key is held down.
Press this key for approximately two seconds to switch between
Loop 1 and Loop 2.
Press this key to increment SV.
The SV increment continuously while the key is held down. The
SV display blinks when the value reaches its maximum limit.
Press this key to decrement an SV.
The SV decreases continuously while the key is held down. The
SV display blinks when the value reaches its minimum limit.
3-4 Parameter Displays and Settings
3-4-1 Table of Parameters
0
Display level
Parameter
Set point
1
Bank number
Alarm SV 1 (see note 4)
Alarm SV 2 (see note 4)
Input shift value
Proportional band
(see note 1)
Integral (reset) time (see note 1)
Derivative (rate) time (see note 1)
SP lower limit
SP upper limit
Display symbol
Write Read Loop no.
Bank no.
Data range
---
Yes Yes Yes Yes SP lower limit to
SP upper limit
Default value Page
0
°
C
bk
See note 5
Yes Yes No 1 to 8 1
al-1
Yes Yes Yes Yes Alarm mode 0
°
C
al-2
Yes Yes Yes Yes
TC 1, 4, 5:
0
°
to 9999
°
C
Other TCs:
–999
°
to 9999
°
C
0
°
C
Pt 1, 4, 5:
0.0
°
to 999.9
°
C
Other Pts:
–99.9
°
to 999.9
°
C
in-5
Yes Yes Yes Yes –99.9
°
to 999.9
°
C 0.0
°
C
p
Yes Yes Yes Yes 0.0
°
to 999.9
°
C 40.0
°
C
i d sl-l sl-h
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
0 to 9999 s
0 to 9999 s
240 s
40 s
Sensor measuring range lower limit to (SP upper limit – 1 digit)
(Sensor measuring range lower limit + 1 digit) to
SP upper limit
TC: –200
°
C
Pt: –99.9
°
C
TC: 1,300
°
C
Pt: 450.0
°
C
26
Parameter Displays and Settings
Section 3-4
1
Display level
Parameter
Control period
(see note 1 and 3)
Hysteresis (see note 2)
Alarm hysteresis
(see note 4)
Heater current monitor (see note 3)
Heater burnout current (see note 3)
2
Display symbol
Write Read Loop no.
Bank no.
cp
Yes Yes Yes No
Data range
1 to 99 s
hys hysa ct hb o
Yes
Yes
No
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
0.0
°
to 999.9
°
C
Default value Page
20 s
0.8
°
C
0.0
°
to 999.9
°
C 0.2
°
C
0.0 to 5.5 A ---
0.0 to 5.0
0.0: No heater burnout detection, alarm signal OFF
0.0 A
5.0: No heater burnout detection, alarm signal ON
0.0% to 100.0% ---
Control output variable monitor
Auto-tuning start/ stop (see note 1)
Copy bank
Sensor-type monitor
Alarm 1 mode
Alarm 2 mode
at bcpy in-t alt1 alt2
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
Yes
No
No
No
No
No
---
---
0 to 9
0 to 9
Mode for Alarm
SV 1/2 (0: no alarm)
---
---
Setting for
SW202
2
2
Note
Yes: Possible.
No: Not possible or not required.
1.
Only when PID control with feed-forward circuitry is selected
2.
Only when ON/OFF control is selected.
3.
Does not apply to current output.
4.
Does not apply when Alarm Mode = 0
5.
Under either one of the following conditions (i.e., when control is stopped), the bank number can be changed to set data using the Data Setting Console.
• When SW203-5 on the rear panel is set to ON (to stop temperature control in the PROGRAM mode) and the CPU Unit is set to PRO-
GRAM mode.
• When the Stop Bit (word n+2, bit 06 for loop 1 and bit 04 for loop 2) is
ON.
In all other cases, the executed bank number (default value = 1) is displayed and the bank number cannot be changed from the Data Setting
Console. Change the executed bank number with a user program or with a device, such as the Programming Console.
6.
Thermocouple = TC
Platinum Resistance Thermometer = Pt
27
Parameter Displays and Settings
3-4-2 How to Display and Set Parameter Data
PV and SV (Display Level 0)
Section 3-4
PV Process value (monitored every 500 ms)
SV
Currently set set value. Units:
°
C or
°
F. The SV can be changed from this display.
Valid SV Range
Set the SV in the range between the SV lower limit and the SV upper limit.
Error Display
When a sensor error occurs, one of the codes below and the detected temperature blink alternately in the PV display.
ser1 ser2
Temperature is out of the range: (sensor measurement range
±
10%FS).
That is, 10%FS below the lower limit or 10%FS above the upper limit.
Includes broken or incorrect sensor wiring.
ser1 : Loop 1; ser2 : Loop 2
serr
Abnormality in the cold junction compensating circuit. Applies to thermocouple type only.
SP Lower Limit (Display Level 1)
PV SP lower limit parameter symbol
SV
Currently set SV lower limit. Units:
°
C or
°
F.
The SV lower limit can be changed from this display.
When the sensor type is set with SW202 on the rear of the Unit, the SV lower limit is automatically set to the measuring range lower limit of the selected sensor, as shown below. However, the SP lower limit cannot be changed if the current SV lies inside the sensor measuring range.
Default values TC: –200
°
C
Pt: –99.9
°
C
Change the set limit, if required. Set the lower limit in the following range:
Sensor measuring range lower limit to (SP upper limit – 1 digit)
The SV and “----” blink alternately on the display if the SP lower limit is set outside the limit defined above to indicate that the value is out-of-range. Reset the SP lower limit inside the permitted range.
SP Upper Limit (Display Level 1)
PV SP upper limit parameter symbol
SV
Currently set SV upper limit. Units:
°
C or
°
F.
The SV upper limit can be changed from this display.
When the sensor type is set with SW202 on the rear of the Unit, the SV upper limit is automatically set to the measuring range upper limit of the selected sensor, as shown below. However, the SP upper limit cannot be changed if the current SV lies inside the sensor measuring range.
Default values TC: 1300
°
C
Pt: 450.0
°
C
Change the set limit, if required. Set the upper limit in the following range:
(Sensor measuring range lower limit + 1 digit) to SP upper limit
28
Parameter Displays and Settings
Section 3-4
The SV and “----” blink alternately on the display if the SP upper limit is set outside the limit defined above to indicate that the value is out-of-range. Reset the SP upper limit inside the permitted range.
Alarms SV 1 and SV 2 (Display Level 0)
PV
SV
Alarm 1/2 parameter symbol
Currently set alarm value. Units: C or F. The setting can be changed from this display. The alarm mode is set with the Alarm 1/2 Mode parameter described on the following page.
Two alarm SVs can be set for each loop and bank.
Alarm 1 and Alarm 2 Modes (Display Level 2)
PV
Alarm 1/2 Mode parameter symbol
SV
Currently set alarm mode.
The setting can be changed from this display.
Two alarm modes can be set for each loop.
Alarm
Mode
Alarm Type
0
Alarm Range
SP
0 No alarm
1 Upper- and lower-limit alarm x x
7
8
9
5
6
2
3
4
Upper-limit alarm
Lower-limit alarm
Upper- and lower-limit range alarm
Upper- and lower-limit alarm with standby sequence
Upper-limit alarm with standby sequence
Lower-limit alarm with standby sequence
Absolute-value upper-limit alarm
Absolute-value lower-limit alarm x x x x x x x x x x
29
Parameter Displays and Settings
Section 3-4
About the Standby Sequence
Select the standby sequence to avoid an alarm output immediately after power is turned ON where the value is in the alarm range. The standby sequence recognizes that the value is out of the alarm range and then outputs an alarm when the value enters the alarm range once more.
Lower Limit Alarm with Standby Sequence
Hysteresis
OFF point
Standby sequence cancel point
Alarm SV
0
°
C
Alarm output
The standby sequence is restarted in the following situations.
• When SV is changed.
• When executed bank number is changed.
• When alarm mode is changed.
• When PC power supply is turned ON.
• When restart flag is set ON.
• When PROGRAM mode is switched to MONITOR or RUN while the control interrupt is set (SW203-5 is ON).
• When the Stop Bit (word n+2, bit 06 or 04) goes OFF.
Alarm Hysteresis (Display Level 1)
PV
Alarm hysteresis parameter symbol
SV
Current setting. Units:
°
C or
°
F.
The setting can be changed from this display.
A hysteresis band is provided to prevent chattering of the alarm output when the alarm output is turned from ON to OFF.
Hysteresis bandwidth Hysteresis bandwidth
ON
OFF
ON
OFF
Input Input
Alarm SV Alarm SV
The alarm output is OFF if the process value lies within the hysteresis band when the Unit is turned on.
Heater Burnout Current (Display Level 1)
PV
SV
Heater burnout current parameter symbol
Currently set heater burnout current value. Units:
Amperes (A).
The setting can be changed from this display.
30
Parameter Displays and Settings
Section 3-4
Set the heater burnout current value in the range shown in the table below.
Refer to Appendix C Heater Burnout Detection for more details about the alarm SVs.
0.0
No heater burnout detection. Alarm signal OFF.
0.1 to 4.9
Within heater burnout current SV range.
5.0
No heater burnout detection. Alarm signal ON.
Heater Current Monitor (Display Level 1)
PV
SV
Heater current monitor parameter symbol
Currently set heater current value. Units: Amperes (A).
If the current exceeds 5.5 A, a CT Input Overflow error occurs and
BBBB is displayed.
Input Shift Value (Display Level 0)
PV
SV
Input shift value parameter symbol
Currently set input shift value. Units:
°
C or
°
F. The setting can be changed from this display.
If the displayed temperature value differs from the actual temperature value due to the sensor position or some other conditions, set the input shift value such that the correct temperature is displayed.
Control Period (Display Level 1)
PV Control period parameter symbol
SV
Currently set control period. Units: Seconds (s). The setting can be changed from this display.
The control period is the time required to complete one transistor output or voltage output ON/OFF cycle.
ON
OFF
ON time
Control period
Control Output Variable Monitor (Display Level 2)
PV
SV
Control output variable monitor parameter symbol
Current control output variable. Units: percentage (%).
The relationship between the control output variable and control period is defined by the formula below:
ON time
Control output variable (%) = x 100
Control period
The control output variable during ON/OFF control (when SW203-1 on the rear panel is ON) is ON = 100% and OFF = 0%.
31
Parameter Displays and Settings
Hysteresis (Display Level 1)
Section 3-4
PV Hysteresis parameter symbol
SV
Currently set hysteresis value. Units:
°
C or
°
F. The setting can be changed from this display.
Hysteresis is an operating band provided for ON/OFF operation to prevent output chattering (repeated ON/OFF switching) and eliminate noise influences.
Hysteresis
ON
OFF
SV
Hysteresis is applied in the following situations.
• When ON/OFF control is selected (SW203-1 is ON).
• When PID control with feed-forward circuitry (SW203-1 is OFF) and P
(proportional band) is 0.
Bank Number (Display Level 0)
PV
SV
Bank number parameter symbol
Currently set bank number.
During control operation: Executed bank number (default value = 1)
Control operation interrupted: Currently displayed bank number
Changing the Settings
The bank number can be changed from the Data Setting Console in the following situations.
• When the CPU Unit is set to PROGRAM mode and SW203-5 on the rear panel is set to ON to interrupt temperature control.
• When the Stop Bit (word n+2, bit 06 for loop 1 or bit 04 for loop 2) is ON.
When the above conditions are not met, the executed bank number cannot be changed from the Data Setting Console and the executed bank number
(default value = 1) is displayed. Change the executed bank number with a user program or with a device, such as the Programming Console.
Copy Bank (Display Level 2)
Copies the data, except for the SV (set value) data, from bank number 1 to banks 2 to 8.
PV
SV
Execute bank copy Bank being copied Bank copy completed
32
Parameter Displays and Settings
Sensor-type Monitor (Display Level 2)
PV
SV
Section 3-4
Sensor-type monitor parameter symbol
Sensor type currently set with SW202 on the rear panel. Number refers to the following if a platinum resistance thermometer is used:
0: JPt (OFF), 1: Pt (ON)
Auto-tuning Start/Stop (Display Level 2)
PV
AT
AT indicator blinks
SV
AT start Process value (PV)
Set point (SP)
AT executing
To interrupt, press the Level and Display Keys again to display at . When at appears, press the Up Key. On interrupt, the at display disappears and the process value is displayed.
Auto-tuning operates only when SW203-1 on the rear panel is set to OFF to enable PID control with feed-forward circuitry. When auto-tuning is completed, the AT indicator stops blinking and the P, I, and D data is written to EEPROM.
If necessary, the P, I, and D data can be changed as described in the following.
Proportional Band (Display Level 0)
PV
SV
Proportional Band parameter symbol
Currently set Proportional Band. Units:
°
C or
°
F. The setting can be changed from this display.
Integral (Reset) Time (Display Level 0)
PV
SV
Integral time parameter symbol
Currently set integral time. Units: second. The setting can be changed from this display.
Derivative (Rate) Time (Display Level 0)
PV
SV
Derivative time parameter symbol
Currently set derivative time. Units: second. The setting can be changed from this display.
33
SECTION 4
PC Memory Allocation and Programming
This section provides the C200H PC’s memory allocation for the Temperature Control Unit. Basic programming procedures and examples are also provided.
4-1-1 Memory Allocation Table. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-2 Memory Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1-3 Table of Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-1 C200HX/HG/HE, C200HS, C200H . . . . . . . . . . . . . . . . . . . . . . . . .
4-3-3 Operation Timing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
Memory Allocation
Section 4-1
4-1 Memory Allocation
Memory Allocation
CS Series
The Temperature Control Unit is allocated 10 words in the IR or CIO Area according to the unit number switch setting on the front of the Unit. These words are used as an I/O refresh data area. The IR or CIO Area words used by the Temperature Control Unit are refreshed each I/O refresh scan of the
CPU Unit.
Temperature Control Unit
CIO area
Unit#0 CIO 2000 to CIO 2009
Unit#1 CIO 2010 to CIO 2019
Unit#2 CIO 2020 to CIO 2029
Unit#3 CIO 2030 to CIO 2039
Unit#4 CIO 2040 to CIO 2049
Unit#5 CIO 2050 to CIO 2059
Unit#6 CIO 2060 to CIO 2069
Unit#7 CIO 2070 to CIO 2079
Unit#8 CIO 2080 to CIO 2089
Unit#9 CIO 2090 to CIO 2099
I/O refresh data area
Wd (n)
to
Wd (n+2)
Output refresh
During PC I/O refresh, each scan is executed for the outputs (PC to Temperature Control Unit) followed by the inputs (Temperature
Control Unit to PC).
Wd (n+3)
to
Wd (n+9)
Input refresh
(n=2000 + 10 x Unit number)
The terms "output" and 'input" are defined from the CPU Unit.
C200HX/HG/HE, C200HS, or C200H
IR area
Unit#0 IR 100 to IR 109
Unit#1 IR 110 to IR 119
Unit#2 IR 120 to IR 129
Unit#3 IR 130 to IR 139
Unit#4 IR 140 to IR 149
Unit#5 IR 150 to IR 159
Unit#6 IR 160 to IR 169
Unit#7 IR 170 to IR 179
Unit#8 IR 180 to IR 189
Unit#9 IR 190 to IR 199
Temperature Control Unit
I/O refresh data area
During PC I/O refresh, each scan is executed for the outputs
(PC to Temperature Control Unit) followed by the inputs (Temperature Control Unit to PC).
Wd (n)
to
Wd (n+2)
Wd (n+3)
to
Wd (n+9)
Output refresh
Input refresh
(n=100 + 10 x Unit number)
The terms "output" and "input" are defined from the CPU Unit.
Note A Duplicate I/O Unit error occurs if the set Unit number corresponds to the number of an existing Special I/O Unit.
Selecting Allocated Data
The data allocated to each IR word due to the Unit number setting is determined by the setting of SW2-1 on the front of the Unit.
ON
OFF
Normal All data can be set using commands.
Fixed Fixed data is allocated to memory. Direct reading and writing of data is possible.
This setting becomes valid immediately after the switch is set.
36
Memory Allocation
Section 4-1
4-1-1 Memory Allocation Table
SW2-1 Set for Fixed Memory Allocations
(CS Series: n=2000+10 x Unit number)
(C200HX/HG/HE, C200HS, C200H: n=100 + 10 x Unit number)
I/O
Output
Input
Word
n n+1 n+2 n+3 n+4 n+5 n+6 n+7 n+8 n+9
15 14 13
Loop 1 SP (see note)
12 11 10 09
Loop 2 SP (see note)
Loop 1 executed bank number
08
Loop 2 executed bank number
Bit
07 06 05 04
Loop 1
0
Loop 2
Stop 0 Stop
0
03 02 01 00
Loop 1 PV (see note)
Loop 2 PV (see note)
Loop 1 SP (see note)
Loop 2 SP (see note)
Loop 1 executed bank number
Loop 2 executed bank number
0 0 0 SW data
2-2 2-1
Loop 1 status data
0 Sensor error
CT overflow
0 0 0 0 STOP 0 0 0 Control output
AT HB AL1 AL2
Loop 2 status data
0 Sensor error
CT overflow
0 0 0 0 STOP 0 0 0 Control output
AT HB AL1 AL2
Note For four-digit BCD and platinum resistance thermometer data, the least significant digit = 0.1, and the most significant digit (F) = minus (–). For example,
“F200” represents –20.0
°
C for a platinum resistance thermometer.
SW2-1 Set for Normal Memory Allocations
(CS Series: n=2000+10 x Unit number)
(C200HX/HG/HE, C200HS, C200H: n=100 + 10 x Unit number)
I/O
Output
Word
n n+1 n+2
15 14 13 12 11
Read/write instruction
Read/write Loop no.
Bank no.
10 09 08
Write data (see note)
Loop 1 executed bank number
Loop 2 executed bank number
Bit
07 06
Instruction
05 04
Loop 1
0 STOP
Loop 2
0 STOP
0
03
0
02
0
01 00
Write request
37
Memory Allocation
Section 4-1
I/O
Input
Word
n+3 n+4 n+5 n+6 n+7
Bit
15 14 13 12 11
Loop 1 PV (see note)
Loop 2 PV (see note)
Read data
0
Loop 1 executed bank number
10 09 08
Write error
0 0 Write complete
Loop 2 executed bank number
0
0
07 06 05 04
n+8 Loop 1 status data
0 Sensor error
CT overflow
0 0 0 0 STOP 0 0 0 Control output
0
0
03
0
0
02
0
01 00
Read complete
SW data
2-2 2-1
AT HB AL1 AL2 n+9 Loop 2 status data
0 Sensor error
CT overflow
0 0 0 0 STOP 0 0 0 Control output
AT HB AL1 AL2
Note For four-digit BCD and platinum resistance thermometer data, the least significant digit = 0.1, and the most significant digit (F) = minus (–). For example,
“1000” represents 100.0
°
C for a platinum resistance thermometer.
4-1-2 Memory Contents
SW2-1 Set for Fixed Memory Allocations
(CS Series: n=2000+10 x Unit number)
(C200HX/HG/HE, C200HS, C200H: n=100 + 10 x Unit number)
I/O
Output n n+1
Word
Address
Bit
15 to 00
15 to 00
Data item Data contents
n+2 15 to 12
11 to 08
07
06
05
04
03 to 00
Loop 1 SP Sets the Loop 1 and Loop 2 SP (set point) as 4-digit BCD data. For
Loop 2 SP platinum resistance thermometer data, the least significant digit is
0.1. Set the most significant digit to F for minus (–).
These specified values apply to the bank number set with Wd
(n+2) and can only be changed in RAM. (Refer page 44)
Loop 1 executed bank number
Loop 2 executed bank number
---
Sets the bank number executed for Loop 1 and Loop 2 as 1-digit
BCD data. Set executed bank numbers from 1 to 8. If the value is set out of this range, the bank number reverts to the previous value
(default value = 1).
Not used. Set to 0.
Loop 1
STOP
---
Loop 2
STOP
---
Bit set to 0 during temperature control of Loop 1 and set to 1 when the control stop is executed. This bit will not be available under the program mode with SW203-5 set to ON (same as the control stop).
Not used. Set to 0.
Bit set to 0 during temperature control of Loop 2 and set to 1 when the control stop is executed. This bit will not be available under the program mode with SW203-5 set to ON (same as the control stop).
Not used. Set each bit to 0.
38
Memory Allocation
Input
I/O
Section 4-1
n+3 n+4
Word
Address
Bit
15 to 00
15 to 00 n+5 n+6 n+7
15 to 00
15 to 00
15 to 12
11 to 08
07 to 02
01
00 n+8 Loop 1 n+9 Loop 2
15
14
13
12 to 09
08
07 to 05
04
03
02
Data item Data contents
Loop 1 PV Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit BCD
Loop 2 PV data. For platinum resistance thermometer data, the least significant digit is 0.1. The most significant digit is F for minus (–).
Loop 1 SP Outputs the Loop 1 and Loop 2 SP (set point) as 4-digit BCD data.
Loop 2 SP
For platinum resistance thermometer data, the least significant digit is 0.1. The most significant digit is F for minus (–).
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data. Executed bank numbers are from 1 to 8.
Loop 1 executed bank number
Loop 2 executed bank number
---
SW2-2
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: CPU Unit
SW2-1 Outputs the ON/OFF status of SW2-1 (switching memory contents).
0: Fixed
---
Sensor error
1: Normal
Not used. Set to 0.
Bit set to 1 if the sensor is not connected, a sensor wire is broken, or the input data exceeds the operational temperature range.
CT overflow Bit set to 1 when the detected heater current exceeds 5.5 A.
Loop 1/2 status data
---
STOP
---
Control output
AT
HB
AL1
AL2
Not used. Each bit is set to 0.
Bit set to 0 during temperature control and set to 1 when the control stop is executed.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or voltage output) is ON. The bit is always 0 for current output.
Bit set to 1 during auto-tuning (AT).
Bit set to 1 if the detected heater current drops below the set heater burnout current value. (HB: heater burnout)
Bit set to 1 when the temperature enters the set
alarm range (Refer to page 25).
01
00
Note If the setting direction of the Temperature Control Unit is set to the CPU Unit and the CPU Unit is in PROGRAM mode, all word data will be 0. Therefore, if the CPU Unit is in PROGRAM mode and has been set for continuous control, the Temperature Control Unit will continue executing temperature control even when the CPU Unit stops operating and will assume that the SP has been changed to 0
°
C. To prevent this, set SW2-2 on the Temperature Control Unit to OFF (i.e., the setting direction is set to the Data Setting Console) before the
CPU Unit stops operating and reset SW2-2 after the CPU Unit restarts.
39
Memory Allocation
Section 4-1
SW2-1 Set for Normal Memory Allocations
(CS Series: n=2000+10 x Unit number)
(C200HX/HG/HE, C200HS, C200H: n=100 + 10 x Unit number)
I/O
Output
Input n n+1 n+2
Word
Address
Bit
Data item Data contents
15 and 14 Read/Write The data bit sets operation to read or write.
Write = 01 Read = 00
13 and 12 Loop no.
The data bit sets the Loop Number to which the read or write operation applies.
Loop 1 = 01, Loop 2 = 10
11 to 08
Read/Write command
07 to 00
15 to 00
15 to 12
11 to 08
07
06
05
04
Bank no.
Sets the bank number to which the read or write operation applies as 1-digit BCD data. Set executed bank numbers from 1 to 8.
Command
Sets the command code (Refer to page 41) for the
read or write operation as 2-digit BCD data.
Write data Set the SP for a write operation as 4-digit BCD data. For data including 0.1 units, the least significant digit represents 0.1. Set the most significant digit to F for minus (–). The write operation commences on the ON rising-edge of the write request flag (Wd (n+2), bit 00).
Loop 1 executed bank number
Set the bank number currently executed for Loop 1 and Loop 2 as
1-digit BCD data. Executed bank numbers are from 1 to 8. If the value is set out of this range, the bank number reverts to the previous value (default value = 1).
Loop 2 executed bank number
---
Loop 1
STOP
---
Not used. Set to 0.
Bit set to 0 during temperature control of Loop 1 and set to 1 when the control stop is executed. This bit will not be available under the program mode with SW203-5 set to ON (same as the control stop).
Not used. Set to 0. n+3 n+4
03 to 01
00
15 to 00
15 to 00
Loop 2
STOP
Bit set to 0 during temperature control of Loop 2 and set to 1 when the control stop is executed. This bit will not be available under the program mode with SW203-5 set to ON (same as the control stop).
Not used. Set each bit to 0. ---
Write request
Turn this bit ON when writing the write data set with Wd (n+1) with the commands set to Wd (n).
Turn this bit OFF after the write complete flag (Wd (n+6), bit 08) turns ON.
Loop 1 PV Outputs the Loop 1 and Loop 2 PV (process value) as 4-digit BCD
Loop 2 PV data. For platinum resistance thermometer data, the least significant digit is 0.1. Set the most significant digit to F for minus (–). n+5 15 to 00 n+6 15 to 12
11
10 to 09
08
Read data Outputs the data read with the commands set with Wd (n). For data including 0.1 Units, the least significant digit represents 0.1.
Set the most significant digit to F for minus (–).
--Not used. Each bit is set to 0.
Write error Bit set to 1 when the write data exceeds the set permissible range.
The bit is automatically set to 0 on the OFF falling-edge of the write request flag (Wd (n+2), bit 00).
--Not used. Each bit is set to 0.
Write complete
Bit set to 1 when the write operation due to the instructions set with
Wd (n) ends normally. The bit is automatically set to 0 on the OFF falling-edge of the write request flag (Wd (n+2), bit 00).
40
Memory Allocation
Section 4-1
Input
I/O
n+6
Word
Address
Bit
07 to 01
00 n+7 15 to 12
11 to 08
07 to 02
01
00 n+8 Loop 1 n+9 Loop 2
15
14
13
12 to 09
08
07 to 05
04
03
02
01
00
Data item Data contents
---
Read complete
Not used. Each bit is set to 0.
Bit set to 1 when the read operation due to the commands set with
Wd (n) ends normally. The bit is set to 0 when the command is changed.
Outputs the bank number currently executed for Loop 1 and Loop
2 as 1-digit BCD data. Executed bank numbers are from 1 to 8.
Loop 1 executed bank number
Loop 2 executed bank number
---
SW2-2
SW2-1 Outputs the ON/OFF status of SW2-1 (switching memory contents).
0: Fixed
---
Sensor error
1: Normal
Not used. Set to 0.
Bit set to 1 if the sensor is not connected, a sensor wire is broken, or the input data exceeds the operational temperature range.
CT overflow Bit set to 1 when the detected heater current exceeds 5.5 A.
Loop 1/2 status data
---
STOP
Not used. Each bit is set to 0.
Outputs the ON/OFF status of SW2-2 (setting direction).
0: Data Setting Console
1: CPU Unit
---
Control output
AT
HB
AL1
AL2
Not used. Each bit is set to 0.
Bit set to 0 during temperature control and set to 1 when the control stop is executed.
Not used. Each bit is set to 0.
Bit set to 1 when the control output (transistor or voltage output) is ON. The bit is always 0 for current output.
Bit set to 1 during auto-tuning (AT).
Bit set to 1 if the detected heater current drops below the set heater burnout current value. (HB: heater burnout)
Bit set to 1 when the temperature enters the set
alarm range (Refer to page 25).
4-1-3 Table of Commands
The command codes shown below are set in bits (n Wd) 07 to 00 when the
SW2-1 (switching memory contents) on the front panel is set for normal memory allocations.
EEPROM Write/Read Command
Parameter
Set point 0
Command
Write
0 Yes
Read
Yes
Loop no.
Yes
Executed bank number 0 2 Yes Yes Yes
Bank no.
Yes
No
Actual data range
Write/Read data range
SV lower limit to SV upper limit
1 to 8
Default value
0
°
C
1
41
Memory Allocation
Section 4-1
Parameter
Alarm SV 1 (see note 4) 0
Command
Write
3 Yes
Read
Yes
Loop no.
Yes
Bank no.
Yes
Alarm SV 2 (see note 4)
Input shift value
Proportional band (see note 1)
Integral (reset) time (see note 1)
Derivative (rate) time
(see note 1)
SP lower limit
0
0
0
0
0
1
4
5
6
7
8
0
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Actual data range
Alarm mode
TC 1, 4, 5:
0
°
to 9999
°
C
Other TCs:
–999
°
to
9999
°
C
Pt 1, 4, 5:
0.0
°
to
999.9
°
C
Other Pts:
–99.9
°
to
999.9
°
C
–99.9
°
to
999.9
°
C
0.0
°
to
999.9
°
C
0 to 9999 s
0 to 9999 s
SP upper limit 1
Control period (see note
1 and 3)
1
Hysteresis (see note 2) 1
1
7
8
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Write/Read data range
0000 to
9999
F999 to
9999
0000 to
9999
F999 to
9999
F999 to
9999
0000 to
9999
Sensor measuring range lower limit to (SP upper limit value – 1 digit)
(SP lower limit + 1 digit) to sensor measuring range upper limit
1 to 99 s
Default value
0
°
C
0
°
C
0.0
°
40.0
20 s
C
°
240 s
40 s
C
TC: –200
Pt: –99.9
°
TC: 1,300
Pt: 450.0
°
°
C
°
C
C
C
Alarm hysteresis (see note 4)
Heater current monitor
(see note 3)
Heater burnout current
(see note 3)
Control output variable monitor
Auto-tuning start/stop
(see note 1)
Copy bank
Sensor-type monitor
Alarm 1 mode
Alarm 2 mode
1
1
1
2
2
2
2
2
2
9
A
B
0
1
2
3
4
5
Yes
No
Yes
No
Yes
Yes
No
Yes
Yes
Yes
Yes
Yes
Yes
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
0.0
°
to
999.9
°
C
0.0
°
to
999.9
°
C
0.0 to 5.6 A
0.0 to 5.0 A
0000 to
9999
0000 to
9999
0000 to
0056
0000 to
0050
0.8
0.2
---
0.0 A
0.0: No heater burnout detection, alarm signal OFF
5.0: No heater burnout detection, alarm signal ON
0.0% to
100.0%
0000 to
1000
---
°
°
C
C
AT start = 0001
AT stop = 0000
Run = 0001
0 to 9
0 to 9
Mode for Alarm SV 1/2 (0: no alarm)
---
---
Setting for
SW202
2
2
Note
Yes: Possible.
No: Not possible or not required.
1.
Only when advanced PID control is selected.
2.
Only when ON/OFF control is selected.
42
Memory Allocation
Section 4-1
3.
Does not apply to current output. A value of 5.6 (0056) for the heater current monitor indicates that the heater current value exceeds 5.6 A.
4.
Does not apply when Alarm Mode = 0
5.
Refer to
3-4 Parameter Displays and Settings
for details of the parameters.
6.
Thermocouple = TC
Platinum Resistance Thermometer = Pt
RAM Write Command
Parameter
Set point 4
Command
Write
0 Yes
Read
No
Loop no.
Yes
Executed bank number 4
Alarm SV 1 (see note 4) 4
Alarm SV 2 (see note 4) 4
Input shift value 4
Proportional band (see note 1)
Integral (reset) time (see note 1)
4
4
Derivative (rate) time
(see note 1)
SP lower limit
4
5
2 Yes
3 Yes
4 Yes
5 Yes
6 Yes
7 Yes
8 Yes
0 Yes
No
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Bank no.
Yes
No
Yes
Yes
Yes
Yes
Yes
Actual data range
SV lower limit to SV upper limit
1 to 8
Write/Read data range
Default value
0
°
C
1
0
°
C Alarm mode
TC 1, 4, 5:
0
°
to 9999
°
C
Other TCs:
–999
°
to
9999
°
C
Pt 1, 4, 5:
0.0
°
to
999.9
°
C
Other Pts:
–99.9
°
to
999.9
°
C
–99.9
°
to
999.9
°
C
0.0
°
to
999.9
°
C
0 to 9999 s
0000 to
9999
F999 to
9999
0000 to
9999
F999 to
9999
F999 to
9999
0000 to
9999
0
°
C
0.0
°
40.0
C
°
240 s
C
Yes
No
0 to 9999 s 40 s
TC: –200
°
C
Pt: –99.9
°
C
SP upper limit 5 1 Yes
7 Yes
No
No
Yes
Yes
No
No
Sensor measuring range lower limit to (SP upper limit value – 1 digit)
(SP lower limit + 1 digit) to sensor measuring range upper limit
1 to 99 s
TC: 1,300
°
C
Pt: 450.0
°
C
20 s Control period (see note
1 and 3)
5
Hysteresis (see note 2) 5 8 Yes No Yes Yes
Alarm hysteresis (see note 4)
Heater burnout current
(see note 3)
Alarm 1 mode
Alarm 2 mode
5
5
6
6
9 Yes
B Yes
4 Yes
5 Yes
No
No
No
No
Yes
Yes
Yes
Yes
No
No
No
No
0.0
°
to
999.9
°
C
0.0
°
to
999.9
°
C
0.0 to 5.0 A
0000 to
9999
0000 to
9999
0000 to
0050
0.0: No heater burnout detection, alarm signal OFF
5.0: No heater burnout detection, alarm signal ON
0 to 9
Mode for Alarm SV 1/2 (0: no alarm)
0.8
°
C
0.2
°
C
0.0 A
2
2
Yes: Possible.
No: Not possible or not required.
43
Data Flow
Note
Section 4-2
1.
Only when advanced PID control is selected.
2.
Only when ON/OFF control is selected.
3.
Does not apply to current output.
4.
Does not apply when Alarm Mode = 0
5.
Data written by the RAM write command will disappear when the power is turned OFF.
6.
Data cannot be read using the RAM write command.
7.
3-4 Parameter Displays and Settings
for details of the parameters.
4-2 Data Flow
Data Settings
Refer to
for the data flow in the Temperature Control Unit.
Before setting data with a user program or the Programming Console, turn
ON SW2-2 of the Unit to enable data setting from the CPU Unit. However, the executed bank number can be set with a user program or from the Programming Console regardless of the ON/OFF setting of SW2-2.
SW2-1 (switching memory contents) may be set in either the OFF (Fixed) or
ON (Normal) position, but care is required as the setting of this switch changes the stored data contents.
4-3 Programming
4-3-1 C200HX/HG/HE, C200HS, C200H
Example with SW2-1 with Fixed Memory Allocations
Description and Conditions
Example: The user program makes the following settings:
Loop 1 SP = 80
°
C
Loop 2 SP = 200
°
C
Loop 1 executed bank number = 1
Loop 2 executed bank number = 3
Conditions: C200H-TC001 (thermocouple)
SW203 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set OFF (Fixed) and SW2-2 set ON (C200H PC).
Sample Program
25315 10701
1 cycle ON
(C200H)
10700
Fixed
MOV (21)
#0080
100
Set #0080 for word 100 (Loop 1 SP).
MOV (21)
#0200
101
Set #0200 for word 101 (Loop 2 SP).
MOV (21)
#1300
102
Set #1300 for word 102 (executed bank number).
#1300
END (01)
Loop 2 executed bank number
Loop 1 executed bank number
Be sure to set the correct values for the Loop 1 and Loop 2 SP.
44
Programming
Section 4-3
The SV value is #0000 (0
°
C) if no data is set. If the executed bank number is set to a value out of the range from 1 to 8 the bank number reverts to the previous value (default value = 1).
Read monitored data into the program using Wd (n+3) to (n+9).
Reading Monitored Data
Example 1: Write with SW2-1 Set for Normal Memory Allocations
Description and Conditions
Example The user program makes the following settings:
Loop 1 SP = 200
°
C (Bank no. = 1)
Loop 2 SP = 250
°
C (Bank no. = 2)
Loop 1 executed bank number = 1
Loop 2 executed bank number = 2
Loop 1 heater burnout current value = 2.0 A
Loop 2 heater burnout current value = 2.5 A
Conditions C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109).
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
45
Programming
Sample Program
10701 10700
(C200H) Normal
25315 10701
1 cycle ON
(C200H)
23200
Normal
23201
10700
23202
23201
10608 Write complete
23203
46
23204
23203
10608
Write complete
23205
Next page
Section 4-3
DIFU (13)
23200
SW2-2 (10701) switch ON detection
(C200H PC)
23201
Program runs when operation is started or
SW2-2 turned ON.
MOV (21)
#1200
102
MOV (21)
#5100
100
MOV (21)
#0200
101
DIFD (14)
23203
S
KEEP(11)
23202
#1200
Loop 2 executed bank number
Loop 1 executed bank number
#5100
SP setting instruction
Bank number
Bit data: 0101
Loop 1
Write
Write data (200
°
C)
To start next data
R
MOV (21)
#6200
100
MOV (21)
#0250
101
DIFD (14)
23205
#6200
SP setting instruction
Bank number
Bit data: 0110
Loop 2
Write
Write data (250
°
C)
S
KEEP(11)
23204
To start next data
R
MOV (21)
#501B
100
MOV (21)
#0020
101
#501B
Write data (2A)
Heater burnout current value command
Bank number not required
Bit data: 0101
Loop 1
Write
Programming
23206
23205
10608
Write complete
23207
23208
10608
Write complete
23201
23203
23205
23207
Section 4-3
DIFD (14)
23207
S
KEEP(11)
23206
To start next data
R
MOV (21)
#601B
100
MOV (21)
#0025
101
#601B
Heater burnout current value command
Bank number not required
Bit data: 0101
Loop 2
Write
Write data (2.5A)
S
KEEP(11)
10200
R
Write request
DIFD (14)
23208
END (01)
47
Programming
Timing Chart
Section 4-3
1 cycle
25315
(1 cycle ON)
23201
23202
23203
23204
23205
23206
23207
10200
(Write request)
10608
(Write complete)
↑
: Point of Write command execution
In addition to the above, IR 23201 will turn ON for one cycle on the rising edge of SW2-2 (IR 10701). One cycle after IR 23208 turns ON, IR 10200 (write request) will turn ON.
Example 2: Read with SW2-1 Set for Normal Memory Allocations
Description and Conditions
Example: The following data is read from the indicated addresses:
Loop 1 PV: DM0000
Loop 1 control output variable: DM0001
Loop 2 heater current: DM0002
This read program is to be executed after writing the data with program example 1.
Conditions: C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: IR100 to IR109.
SW2-1 set ON (Normal) and SW2-2 set ON (C200H PC).
48
Programming
Sample Program
Section 4-3
25313
Normally ON
23209
(A)
23207
10608
Write complete
23300 10701 10700
(C200H)
Normal
23307
23301
Insert the program below before the END instruction in the program on
MOV (21)
103
DM0000
DIFD (14)
23300
S
Read Loop 1 PV from IR103 to DM 0000.
Read operation is not affected by SW2-1 and SW2-2 settings.
KEEP(11)
23209
Runs next Read command when final write complete is detected.
R
23301
23307 repeatedly executes the Read command when each Read Complete is detected.
23302
MOV (21)
#1020
100
DIFD (14)
23302
S
KEEP(11)
23303
#1020
Control output variable monitor command
Bank number not required
Bit data: to read data
0001
Wait for Read Complete
Loop 1
Read
R
10600
Read complete
23303
DIFD (14)
23304
Next page
49
Programming
23304
(B)
Section 4-3
23305
MOV (21)
105
DM0001
MOV (21)
#201A
100
DIFD (14)
23305
S
KEEP(11)
23306
Read data from IR105 to DM 0001.
Execute next Read command.
#201A
Heater Current
Monitor command
Bank number not required
Bit data 0010
Loop 2
Read
R
Wait for Read Complete to read data
10600
Read complete
23306
23307
DIFD (14)
23307
MOV (21)
105
DM0002
Read data from IR105 to DM 0002.
Change the above program as shown below if only reading is to be carried out.
Replace part (A) of the program with the following program.
10701 10700
(C200H) Normal
25315 10701 10700
1 cycle
(C200H)
ON
Normal
23200
DIFU (13)
23200
23301
SW2-2 (10701) switch ON detection (C200H PC)
Program runs when operation is started or SW2-2 turned ON
Add an END instruction (01) at position (B) of the program.
50
Programming
Timing Chart
Section 4-3
1 cycle
23301
23302
23303
23304
23305
23306
23307
Wd 105
(Read data)
10600
(Read complete)
1
2
: Point of Read command execution
: Point where data (1) is read.
: Point where data (2) is read.
4-3-2 CS Series
Example with Fixed Memory Allocations
Description and Conditions
Example: The user program makes the following settings:
Loop 1 SP = 80
°
C
Loop 2 SP = 200
°
C
Loop 1 executed bank number = 1
Loop 2 executed bank number = 3
Conditions: C200H-TC001 (thermocouple)
SW203 set to 2 (K).
Unit number set to 0 (allocated memory: CIO 2000 to CIO 2009).
SW2-1 set OFF (Fixed) and SW2-2 set ON (CPU Unit).
51
Programming
Sample Program
A20011 200701 200700
1 cycle ON CPU Unit Fixed
Section 4-3
MOV (021)
#0080
2000
Set #0080 for word 2000 (Loop 1 SP).
MOV (021)
#0200
2001
Set #0200 for word 2001 (Loop 2 SP).
MOV (021)
#1300
2002
END (001)
Set #1300 for word 2002 (executed bank number).
#1300
Loop 2 executed bank number
Loop 1 executed bank number
• Be sure to set the correct values for the Loop 1 and Loop 2 SP. The value is #0000 (0
°
C) if no data is set.
• If the executed bank number is set to a value out of the range from 1 to 8, the bank number reverts to the previous value (default value = 1).
Read monitored data into the program using Wd (n+3) to (n+9).
Reading Monitored Data
Example 1: Write Set for Normal Memory Allocations
Description and Conditions
Example The user program makes the following settings.
This example writes to EEPROM. To write to RAM, add 4 to the leftmost digit of the command.
Loop 1 SP = 200
°
C (Bank no. = 1)
Loop 2 SP = 250
°
C (Bank no. = 2)
Loop 1 executed bank number = 1
Loop 2 executed bank number = 2
Loop 1 heater burnout current value = 2.0 A
Loop 2 heater burnout current value = 2.5 A
Conditions C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: CIO 2000 to CIO 2009).
SW2-1 set ON (Normal) and SW2-2 set ON (CPU Unit).
52
Programming
Sample Program
20701 200700
CPU Unit Normal
A20011 200701 200700
1 cycle ON CPU Unit Normal
23200
23201
23202
23201
200608 Write complete
Next page
Section 4-3
DIFU (013)
2320
0
23201
SW2-2 (200701) switch ON detection (CPU Unit)
Program runs when operation is started or SW2-2 turned ON.
MOV (021)
#1200
2002
MOV (021)
#5100
2000
MOV (021)
#0200
2001
DIFU (014)
23203
KEEP(011)
23202
#1200
Loop 2 executed bank number
Loop 1 executed bank number
#5100
SP setting instruction
Bank number
Bit data: 0101
Loop 1
Write
Write data (200
°
C)
To start next data
53
Programming
23203
23204
23203
200608 Write complete
23205
23206
23205
200608
Write complete
23207
23208
200608
Write complete
23201
23203
23205
23207
54
Section 4-3
MOV (021)
#6200
2000
MOV (021)
#0250
2001
DIFD (014)
23205
S
KEEP(011)
23204
#6200
SP setting instruction
Bank number
Bit data:
0110
Loop 2
Write
Write data (250
°
C)
To start next data
R
MOV (021)
#501B
2000
MOV (021)
#0020
2001
#501B
Write data (2A)
Heater burnout current value command
Bank number not required
Bit data:
0101
Loop 1
Write
DIFD (014)
23207
S
KEEP(011)
23206
To start next data
R
MOV (021)
#601B
2000
MOV (021)
#0025
2001
#601B
Heater burnout current value command
Bank number not required
Bit data: 0101
Loop 2
Write
Write data (2.5A)
S
KEEP(011)
200200
R
Write request
DIFD (014)
23208
END (001)
Programming
Timing Chart
Section 4-3
1 cycle
A20011
(1 cycle ON)
23201
23202
23203
23204
23205
23206
23207
200200
(Write request)
200608
(Write complete)
↑
: Point of Write command execution
In addition to the above, CIO 23201 will turn ON for one cycle on the rising edge of SW2-2 (CIO 200701). One cycle after CIO 23208 turns ON, CIO
200200 (write request) will turn ON.
Example 2: Read Set for Normal Memory Allocations
Description and Conditions
Example: The following data is read from the indicated addresses:
Loop 1 PV: D0000
Loop 1 control output variable: D0001
Loop 2 heater current: D0002
This read program is to be executed after writing the data with program example 1.
Conditions: C200H-TC001 (thermocouple)
SW202 set to 2 (K).
Unit number set to 0 (allocated memory: CIO 2000 to CIO 2009.
SW2-1 set ON (Normal) and SW2-2 set ON (CPU Unit).
55
Programming
Sample Program
Section 4-3
(A)
CF113
Always ON
23209
23207
200608
Write complete
23300 200701 200700
CPU Unit
Normal
23307
23301
Insert the program below before the END instruction in the program on
MOV (021)
2003
D0000
DIFD (014)
23300
S
KEEP(011)
23209
Read Loop 1 PV from CIO 2003 to D0000.
Read operation is not affected by SW2-1 and SW2-2 settings.
Runs next Read command when final write complete is detected.
R
23301
23307 repeatedly executes the Read command when each Read Complete is detected.
23302
200600
Read complete
23303
MOV (021)
#1020
2000
DIFD (014)
23302
S
KEEP(011)
23303
#1020
Control output variable monitor command
Bank number not required
Bit data: to read data.
0001
Wait for Read Complete
Loop 1
Read
R
DIFD (014)
23304
Next page
56
Programming
23304
(B)
Section 4-3
23305
MOV (021)
2005
D0001
MOV (021)
#201A
2000
DIFD (014)
23305
S
KEEP(011)
23306
Read data from CIO 2005 to D0001.
Execute next Read command.
#201A
Heater Current
Monitor command
Bank number not required
Bit data 0010
Loop 2
Read
R
Wait for Read Complete to read data.
200600
Read complete
23306
23307
DIFD (014)
23307
MOV (021)
2005
D0002
Read data from CIO 2005 to D0002.
Change the above program as shown below if only reading is to be carried out.
Replace part (A) of the program with the following program.
200701 200700
CPU Unit Normal
A20011 200701 200700
1 cycle
ON
CPU Unit Normal
23200
DIFU (013)
23200
23300
SW2-2 (200701) switch
ON detection (CPU Unit)
Program runs when operation is started or SW2-2 turned ON
Add an END instruction (001) at position (B) of the program.
57
Programming
Timing Chart
Section 4-3
1 cycle
23301
23302
23303
23304
23305
23306
23307
Wd 2005
(Read data)
200600
(Read complete)
: Point of Read command execution
1
2
: Point where data (1) is read.
: Point where data (2) is read.
4-3-3 Operation Timing
The following descriptions apply to the C200HX/HG/HE, C200HS, C200H, and CS-series PCs.
Write Operation Timing
Command (Wd n)
Write data (Wd n+1)
Data (1) Data (2) Data (3) Data (4)
Write request
(Wd n+2), bit 00
ON
OFF
1,2,3...
Write complete
(Wd n+6), bit 08
ON
OFF
Approx.
140 ms
1.
The data is written to the Temperature Control Unit EEPROM when the
Write Request Flag turns ON.
2.
The Write Complete Flag turns ON when the data writing operation is completed. It takes approximately 140 ms to write the data.
3.
The Write Complete Flag automatically turns OFF when the Write Request
Flag turns OFF.
Check the Write Complete Flag is ON before turning OFF the Write Request Flag. If the Write Request Flag is set to OFF before the Write Com-
58
Programming
Section 4-3
plete Flag turns ON the Write Complete Flag will not subsequently turn
ON.
Temporarily turn the Write Request Flag OFF before executing the second and subsequent write operations. Writing is enabled on the ON rising edge of the Write Request Flag.
The Loop 1 and 2 executed bank number (Wd n+2) sets data directly. The data is written to the Temperature Control Unit RAM. If the value is set out of this range, the bank number reverts to the previous value (default value
= 1).
Timing for a Read Operation
1,2,3...
Command (n)
Read complete
(Wd n+6), bit 00
ON
OFF
Command (A) Command (B)
Read data
(Wd n+5)
Approx.
140 ms
Read data (A) Read data (B)
1.
The read data is output to Wd (n+5) approximately 140 ms after the Read command is executed.
2.
The read data is updated every 100 ms.
3.
When the Read command is modified, turn OFF the Read Complete Flag to execute the next read operation.
4-3-4 I/O Refresh
The following descriptions apply to the C200HX/HG/HE, C200HS, C200H, and CS-series PCs.
Temperature control cannot be performed properly unless the I/O refresh interval is at least 8 ms. Therefore, create programs that satisfy all of the following conditions.
• Set the cycle time to 8 ms min.
If the program processing time is short for the C200HX/HG/HE, C200HS, and C200H, use the CYCLE TIME instruction SCAN(18) to set a minimum cycle time.
If the program processing time is short for the CS-series PC, set the cycle time to a minimum value in the PC Setup.
• When using the I/O Refresh instruction IORF with the Unit, provide an interval of at least 8 ms between the end refreshes.
• Provide an interval of at least 8 ms between the I/O Refresh instructions.
Normal I/O refresh End refresh
8 ms min. (Cycle time)
Normal I/O refresh End refresh
8 ms min.
IORF I/O Refresh instruction
8 ms min.
IORF I/O Refresh instruction
8 ms min.
Normal I/O refresh End refresh
59
SECTION 5
Troubleshooting
This section provides possible errors and error remedies.
61
Error Detection
Section 5-1
5-1 Error Detection
When an error occurs in an input or in the Unit, details of the error are reported to the Data Setting Console and input relays.
Sensor Input Errors
Display
ser1 ser2 serr
Error name
Loop 1 sensor error
Loop 2 sensor error
Cold junction compensating circuit error
Output status after error
Control output:
The transistor output or voltage output turns OFF or the current output falls below 2 mA.
Alarm output:
The alarm is output assuming the input is
±
10%FS.
Control output:
The transistor output or voltage output turns OFF or the current output falls below 2 mA.
Alarm output turns OFF.
Cause
Reading is
±
10%FS out of sensor measurement range (i.e., 10%FS below the lower limit or 10%FS above the upper limit).
Broken or incorrect sensor wiring
Defective sensor
Defective Unit
SW203-4 is OFF (Loop 2 enabled) but no sensor connected to Loop 2
Abnormality in cold junction compensating circuit. Applies to thermocouple type only.
Remedy
Check the sensor wiring.
Replace the sensor.
Replace the Unit.
Correctly set switch
SW203-4.
Replace the Unit.
Data Setting Console
When a sensor error occurs, one of the codes above and the detected temperature are displayed alternately.
If a Loop 1 sensor error ser1
and a Loop 2 sensor error ser2
occur simultaneously, ser1
is displayed preferentially. Even if a sensor error is detected in one Loop, the other Loop continues to operate normally. Control operation restarts automatically five seconds after the cause of the error is corrected.
The bits shown in the table below are set to 1 when a relay input error occurs.
Wd (n+8), bit 14
Wd (n+9), bit 14
Loop 1 sensor error
Loop 2 sensor error
Both bits = 1 after a cold junction compensating circuit error.
CT Input Overflow
Display Error name Cause
ffff
CT input overflow The detected heater current exceeds 5.5 A.
Remedy
Check the CT and heater wiring.
The display shown in the table above will appear if the CT overflow error occurs when the heater current monitor is selected. The display returns to normal after the cause of the error is removed.
The bits shown in the table below are set to 1 when the CT overflow error occurs.
Wd (n+8), bit 13
Wd (n+9), bit 13
Loop 1 CT overflow
Loop 2 CT overflow
Heater Burnout Alarm
Display
HB indicator lit
Error name Cause
Heater burnout The detected heater current is below the heater burnout current value.
Remedy
Check the heater and heater wiring. Replace heater if necessary.
62
Error Detection
Temperature Alarm
EEPROM Error
Duplicate I/O Unit
Special I/O Unit Error
Section 5-1
Error displayed when an abnormality occurs in the loop currently being displayed.
The bits shown in the table below are set to 1 when a heater burnout alarm occurs.
Wd (n+8), bit 02
Wd (n+9), bit 02
Loop 1 heater burnout alarm
Loop 2 heater burnout alarm
Use one of the methods below to reset a heater burnout alarm.
• Turn ON the Special I/O Unit Restart Bit (AR 0100 to AR 0109 for the
C200HX/HG/HE, C200HS, C200H and A50200 to A50209 for a CS-series
PC) and then turn it OFF.
• Turn the PC power supply OFF then back ON.
• Set the heater burnout current limit to 00 then back to its original value.
Display
ALM1 indicator lit
Error name Cause
Temperature alarm 1 The temperature is in the alarm range set with Alarm SV 1.
Remedy
Check the temperature of the measured body.
Check the set SP value.
Error displayed when an abnormality occurs in the loop currently being displayed. No indicator is provided to show an ALM2 alarm.
The bits shown in the table below are set to 1 when a temperature alarm occurs.
Wd (n+8)
Wd (n+9)
Bit 01
Bit 00
Bit 01
Bit 00
Temperature alarm 1 Loop 1
Temperature alarm 2
Temperature alarm 1 Loop 2
Temperature alarm 2
Display Error name Output status after error
e111 EEPROM error
Control output:
The transistor output or voltage output is OFF or the current output is less than 2 mA.
Alarm output is OFF.
Cause
Defective
EEPROM
Remedy
Replace the Unit
The RUN indicator turns off when an EEPROM error occurs.
The unit number duplicates the number of another Special I/O Unit. SR 25415
(for C200HX/HG/HE, C200HS, C200H) or A40113 (for CS-series PC) will turn
ON when an Duplicate I/O Unit error occurs. Refer to AR0000 to AR0009 for the C200HX/HG/HE, C200HS, C200H or to A41100 to A41109 for the CSseries PC for the duplicated unit number. The CPU Unit will not operate during a duplicate I/O error.
Set the Unit number to a separate number.
I/O refresh not operating correctly between the CPU Unit and Temperature
Control Unit. Operation is not interrupted when a Special I/O Unit error occurs. Refer to AR 0000 to AR 0009 for the C200HX/HG/HE, C200HS,
C200H or to A41100 to A41109 for a CS-series PC for the unit number where the error occurred. After correcting the cause of the error, turn ON the Special
I/O Unit Restart Bit (AR 0100 to AR0109 for the C200HX/HG/HE, C200HS,
C200H; A50200 to A50209 for a CS-series PC) to restart operation.
63
Error Detection
RUN Indicator Unlit
No Data Setting Console
Display
Temperature Control Not
Performed
Section 5-1
The PC power supply is turned on but the RUN indicator is not lit. None of the errors described previously are detected. Replace the Unit.
No 24 VDC power supply is connected to the Temperature Control Unit input terminals A8 and A9.
• The connecting cable is disconnected.
• The connecting cable is broken.
• A circuit in the Data Setting Console is defective.
• A circuit in the Temperature Control Unit is defective.
After determining the cause of the error, correct the problem or replace the
Unit.
Temperature control will not be performed in either one of the following cases.
• SW203-5 on the rear panel is set to ON and the CPU Unit is in PRO-
GRAM mode.
• The Stop Bit (word n+2, bit 06 for loop 1 and bit 04 for loop 2) is ON.
Change to proper settings.
64
Appendix A
Specifications
General Specifications
Conforms to the CPU Unit specifications.
Item
Connectable temperature sensor (see note 1)
Current Transformer detection current
No. of input points (loops)
Temperature control mode
Setting/Indication accuracy
(see note 2, 3 and 4)
Influence of temperature:
For ambient temperature change from 0 to 23 to 55
°
C
Influence of voltage:
For change from
−
15% lower to
10% higher than rated voltage
C200H-TC00
@
C200H-TC10
@
Thermocouple (R, S, K, J, T, E, B, N, L, U) Platinum resistance thermometer (JPt100,
Pt100)
0.1 to 4.9 A (with a heater burnout detecting current difference of 0.5 A min.)
Indication accuracy:
±
5% FS
±
1 digit max.
Two points (two loops, each of which consists of a temperature sensor and a CT)
PID, ON/OFF (selectable with a switch on the rear panel)
(PID control with feed-forward circuitry with auto-tuning)
±
0.5% of set (designated) value or
±
2
°
C whichever larger
±
1 digit max.
±
0.5% of set (designated) value or
±
1
°
C whichever larger
±
1 digit max.
Thermocouples R and S
±
1% of set (designated) value or
±
10
°
C, whichever is larger,
±
1 digit max.
Other Thermocouples
±
1% of set (designated) value or
±
4
°
C, whichever is larger,
±
1 digit max.
Platinum Resistance Thermometer
±
1% of set (designated) value or whichever is larger,
CT Input
±
0.25 A
±
±
1 digit max.
1 digit max.
CT Input
±
0.25 A
±
1 digit max.
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F) (during ON/OFF control action)
0.0
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
0 to 9999 s (in units of 1 s)
±
2
°
C,
0 to 9999 s (in units of 1 s)
Hysteresis
Proportional band
Integral (reset) time
Derivative (rate) time
Control period
Sampling period
1 to 99 s (in units of 1 s)
500 ms
Output refresh period
Display refresh period
Input shift range
Alarm output setting range
No. of banks
500 ms
500 ms
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
–999
°
to 9,999
°
C/
°
F (in units of 1
°
C/
°
F)
8 banks
Internal current consumption 5 VDC, 0.33 A max.
External supply voltage
Dimensions (see note 4)
Weight
24 VDC
+10%
/
–15%
, 0.2 A min.
34.5 mm (W) x 130 mm (H) x 120.5 mm (D)
360 g
–99.9
°
to 999.9
°
C/
°
F (in units of 0.1
°
C/
°
F)
Note 1.
Set with the switch on the rear panel. See Appendix B Sensor Temperature Measurement Range for the measurable temperature range.
2.
The set value and designated value coincide with each other.
3.
The indication accuracy of thermocouples R and S at a temperature of 200
°
C max., that of thermocouples K and T at a temperature of –100
°
C max, and that of thermocouple U are all
±
4
°
C,
±
1 digit max. The indication accuracy of thermocouple B at a temperature of 400
°
C or below is not guaranteed.
4.
At an ambient temperature of 23
°
C.
5.
See Appendix D Dimensions.
65
Specifications
Appendix A
Output Characteristics
Open-collector Output (Pulse) C200H-TC
@
01
External supply voltage
Max. load voltage
Max. load current
Residual voltage when ON
Leakage current when OFF
24 VDC
+10%
/
–15%
24 VDC max.
100 mA max.
3 V max.
0.3 mA max.
Voltage Output (Pulse) C200H-TC
@
02
Output voltage
Max. load current
Current Output (Linear) C200H-TC
@
03
Output current
Permissible load impedance
Current value accuracy
12 VDC
40 mA (with short-protective circuit)
4 to 20 mA
600
Ω
max.
4
±
0.3 to 20
±
1 mA
66
Appendix B
Sensor Temperature Measurement Ranges
C200H-TC00
@
Thermocouple
Set the thermocouple type with the switch on the rear panel.
This switch is factory-set to 2 (K).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input
R
Platinum vs. platinum rhodium
13%
S
Platinum vs.
platinum rhodium
10%
K (CA)
Chromel vs. alumel
Range
°
C 0 to 1,700 0 to 1,700 –200 to
1,300
°
F
0 to 3,000 0 to 3,000 –300 to
2,300
Switch setting
0 1 2
J/L (IC)
Iron vs. constantan
–100 to
1,500
3/8
T/U (CC)
Copper vs. constantan
E (CRC)
Chromel vs. constantan
–100 to 850 –200 to 400 0 to 600
B
Platinum rhodium
30% vs. platinum rhodium 6%
100 to
1,800
–300 to 700 0 to 1,100 300 to
3,200
4/9 5 6
N
Nichrosil vs. nisil
0 to 1,300
0 to 2,300
7
C200H-TC10
@
Platinum Resistance Thermometer
OFF
ON
Set the platinum resistance thermometer type with the switch on the rear panel.
This switch is factory-set to OFF (JPt100).
The Data Setting Console can display the range from 10%FS below the lower limit to 10%FS above the upper limit.
Input JPt100 Pt100
Range
°
C
–99.9 to 450.0
–99.9 to 450.0
°
F
–99.9 to 800.0
–99.9 to 800.0
Switch setting
OFF ON
67
Appendix C
Heater Burnout Detection
Heater Burnout Detection System
The heater wiring is connected through the Current Transformer (CT). As a current flows through the heater wiring, an alternating current is induced in the CT which is dependent on the size of the current flowing. This induced current drops to zero if the heater burns out. The heater burnout alarm signal is output when the induced current is compared to the set current value.
Heater Burnout Alarm Precautions
• Turn ON the heater power supply and the input terminal 24-VDC power supply at the same time as or before the PC power supply. The heater burnout signal is output if the heater power supply or the input terminal 24-VDC power supply is turned ON after the PC power supply.
• Temperature Control Unit operation continues if a burned-out heater causes a heater burnout alarm. Control signal output continues according to the control parameters. Take measures to detect the heater burnout alarm signal to allow early repair.
• The heater burnout alarm is output when the control output is ON. Once the heater burnout alarm is output, it remains ON. Use one of the methods below to reset a heater burnout alarm.
• Turn ON the Special I/O Unit Restart Bit (AR 0100 to AR 0109 for the C200HX/HG/HE, C200HS, C200H and A50200 to A50209 for the CS1) and then turn it OFF.
• Turn the PC power supply OFF then back ON.
• Set the heater burnout current limit to 0.0 then back to its original value.
• Make sure that the current difference between normal operation and heater burnout is at least 0.5 A. Stable detection is difficult with a current difference less than 0.5 A.
• Heater burnout detection is not possible with the current output type (C200H-TC
@
03) or with 3-phase heaters.
• Set the heater burnout current to 0.0 when heater burnout detection is not required because the CT input wiring is not detected.
Determining the Heater Burnout Detection Current
• Determine the SV from the following equation:
SV =
Normal current value + heater burnout current
2
• If more than one heater is connected through the CT, take the heater burnout current as the value when the heater with the smallest current consumption is burned out. If all heaters consume equal current, take the heater burnout current as the value when any one heater is burned out.
• Make sure that the current difference between normal operation and heater burnout is at least 0.5 A. Stable detection is difficult with a current difference less than 0.5 A.
• Set the SV in the range between 0.1 A and 4.9 A. Heater burnout detection is not carried out if the SV is set to 0.0 A or 5.0 A. The alarm signal is always OFF if the SV is set to 0.0 or always ON if the SV is set to
5.0.
• The total heater current during normal operation should not exceed 5 A. If the current exceeds 5.5 A, a CT
Input Overflow error occurs and ffff
is displayed if the heater current monitor is selected.
Measure each current with the heater current monitor. In some cases the calculated current may differ from the actual measured value.
69
Heater Burnout Detection
Sample SV Calculations
Example 1 Using one 200 VAC, 800 W heater
Burnout current = 0 A
2
≤
4.9 A)
Example 2 Using three 100 VAC, 100 W heaters
Appendix C
Difference between normal and burnout current = 3 − 2 = 1 A (≤ 0.5 A)
Specifications
Heater Burnout Detection Characteristics
Heater burnout detection setting range
0.1 to 4.9 A (in units of 0.1 A) (see note 1)
Current difference required for heater burnout detection
0.5 A min. (normal time – burnout time)
Heater current monitor range
Monitor accuracy of input current
Min. detectable ON time
0.0 to 5.5 A
±
5% of FS
±
1 digit max.
200 ms (see note 2)
Note 1.
If the heater burnout detection setting value is set to 0.0 or 5.0 A, no heater burnout detection is possible. The alarm signal is turned OFF if the heater burnout detection setting value is set to 0.0 A and turned ON if it is set to 5.0 A.
2.
If the control output is turned ON for less than 200 ms, no heater burnout detection or heater current measurement is possible.
E54-CT1/CT3 Current Transformer
Max. continuous heater current
50 A
Dielectric strength
1,000 VAC (1 min)
Vibration resistance
Weight
Accessories (E54-CT3 only)
50 Hz (approx. 10G)
E54-CT1: approx. 11.5 g; E54-CT3: approx. 50 g
Contact: 2; Plug: 2
70
Heater Burnout Detection
Current Transformer Dimensions
E54-CT1
21
15
7.5
5.8 dia.
2.8
25
10.5
3
10
30
40
Two 3.5-dia. holes
E54-CT3
9
40
30
2.36 dia.
12 dia.
15
30
40
Two M3 holes with a depth of 4 mm
Appendix C
71
Heater Burnout Detection
Current Transformer Circuit Diagram
Control output
Heater
AC power supply
CT
To Temperature Control Unit
CT input terminal
To Temperature Control
Unit CT input terminal
(no polarity)
Heater cable
Current Transformer
Appendix C
72
Temperature Control Unit
Weight: 360 g
Unit Dimensions
Appendix D
Dimensions
130
34.5
20
100.5
120.5
131.5
11
Mounting Dimensions
Approx. 200
17
73
Dimensions
Data Setting Console
Weight: 120 g
Unit Dimensions
96
48
Mounting Dimensions
Panel Cutout
3
12 45
57
Clearance
44
91
Appendix D
92
+0.8
0
45
+0.6
0
Panel thickness 1 to 4 mm
Clearance of at least 150 mm
Allow a clearance of at least 150 mm behind the Data Setting Console when it is installed in the panel to allow cable connectors to be inserted. A clearance of 50 mm is sufficient if the rear panel can be opened.
74
A–B
alarm hysteresis
,
alarm mode setting
,
allocating memory
applications precautions
auto-tuning start/stop setting
,
bank number setting
,
C
command codes settings
EEPROM write/read command
,
RAM write command
,
compensating conductors specifications
Connector Terminal Block Converter Unit
,
control output variable monitor setting
,
control period setting
,
copy bank setting
,
cover removal and replacement
,
CT input overflow error
Current Transformer
D
data flow
data setting
,
operating procedure
,
Data Setting Console connecting cable and precautions
features
,
mounting
,
parameter and setting tables
physical features
data settings
derivative time setting
detecting errors
,
Duplicate I/O Unit
,
E
EEPROM error alarm
,
EEPROM write/read command
Index
command codes settings
,
error display
errors data setting
features
F–H
Heater Burnout Alarm
,
heater burnout current
heater burnout detection precautions and current ranges
,
hysteresis setting
I
I/O refresh
,
indicators
,
input shift value setting
input wiring
Platinum Resistance Thermometer
,
precautions
thermocouple
installation precautions
integral time setting
,
memory contents
,
M–O
operating environment precautions
operating in PROGRAM mode
,
Operation and Function Setting
,
operation timing
output wiring
circuit diagrams
,
connectors and cable
diagrams
,
precautions
P
PID control with feed-forward circuitry
precautions
,
75
76
applications
general
,
operating environment
safety
programming examples
,
proportional band setting
R
RAM write command command codes settings
,
read operation timing
,
refresh
I/O
,
Remote I/O Terminal
,
S
safety precautions
,
selecting allocated memory
,
sensors setting type
,
sensor-type setting
Set Value display upper and lower limits
,
setting and displaying parameters method
,
settings heater burnout current
,
source
Slave Rack number of mountable Units
,
Special I/O Unit error
specifications general, table
,
standby sequence
,
switch settings
,
switching memory contents
,
switching memory contents and setting direction
,
system configuration
T
temperature alarm
temperature measurements
Index
ranges
troubleshooting
CT input overflow error
data setting errors
,
duplicate I/O unit
EEPROM error
,
power supply
RUN Indicator Unlit
,
Special I/O Unit error
temperature alarm
U
Unit models
,
Unit components dimensions
,
Unit nomenclature
,
Revision History
A manual revision code appears as a suffix to the catalog number on the front cover of the manual.
Cat. No. W225-E1-05
Revision code
The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version.
Revision code
1
1A
2
3
04
05
Date
August 1993 Original production
Revised content
July 1995 Page 40: Note 1 corrected.
September 1996 Pages 35 to 39: Loop 1 STOP, Loop 2 STOP, and STOP data items added to the tables.
Pages 39 and 40: EEPROM Write/Read Command title added to table and the
RAM Write Command table added.
Page 48: 4-3-5 I/O Refresh added.
March 2000 Added precautions to beginning of manual and changed “C200H PC” to either
“PC” or “CPU Unit” throughout the manual.
Page 3: Added a table of applicable CPU Units.
Page 4: Modified number of units mountable on Slave Rack in the table.
Page 4: Added information on new functions.
Page 9: Added information on Stop Bits and Stop Flags.
Page 11: Changed screw tightening torque.
Pages 20, 21, 25: Changed descriptions of data setting.
Page 23: Added Stop Bit information to the Data Display note.
Page 30: Added Stop Bit information to Changing the Settings.
Page 34: Added memory allocation information for the CS1.
Page 45: Modified sample program for write request.
Page 49: Added programming examples for the CS1.
Page 53, 59: Changed SR bit and restart bit.
Page 53: Added information on cases where temperature control is not performed.
December 2001 Page xiii: Added Power Supply Units to WARNING sub-item.
Page 4: Added C200H-CPU-22-E to Applicable CPU Units table.
Page 15: Reversed A and B in Voltage/Current Output figure.
Pages 49 and 56: Changed 23208 to 23209.
December 2005 "CS1" changed to "CS" throughout manual in reference to OMRON PC Series.
Page xii: Safety precautions added.
Page xiv: Two precautions added toward top of page and three corrections/ additions made to existing precautions.
Page 65: Influence of temperature and influence of voltage specifications added, and note added.
77
OMRON Corporation
Control Devices Division H.Q.
Shiokoji Horikawa, Shimogyo-ku,
Kyoto, 600-8530 Japan
Tel: (81)75-344-7109/Fax: (81)75-344-7149
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
1 East Commerce Drive, Schaumburg, IL 60173
U.S.A.
Tel: (1)847-843-7900/Fax: (1)847-843-8568
OMRON ASIA PACIFIC PTE. LTD.
83 Clemenceau Avenue,
#11-01, UE Square,
Singapore 239920
Tel: (65)6835-3011/Fax: (65)6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120 China
Tel: (86)21-5037-2222/Fax: (86)21-5037-2200
Authorized Distributor:
Cat. No. W225-E1-05 Note: Specifications subject to change without notice.
This manual is printed on 100% recycled paper.
Printed in Japan
Download
Advertisement
Key features
PID with Feed-forward Circuitry
Two Temperature Control Loops
Heater Burnout Detection
Eight Banks of Data Settings
Data Setting Console
User Programs for Data Access
Frequently asked questions
The unit supports both thermocouples and platinum resistance thermometers.
It offers two control loops.
Three types of output specifications are available: transistor output (C200H-TC@@1), voltage output (C200H-TC@@2), and current output (C200H-TC@@3).
Heater burnout detection is achieved through a Current Transformer, allowing for quick detection with a minimum current difference of 0.5 A. The detection setting range is 0.1 to 4.9 A, enabling rapid problem correction.
The C200H-DSC01 Data Setting Console (sold separately) is used for inputting data and displaying process values (PV) and set values (SV). It has an easy-to-read display that can be panel-mounted.