Canadian Solar CSI Series Installation And Operation Manual

Add to My manuals
42 Pages

advertisement

Canadian Solar CSI Series Installation And Operation Manual | Manualzz

CANADIAN SOLAR INC.

Global Headquarters:

545 Speedvale Avenue, West Guelph, Ontario N1 K 1 E6, Canada

Tel: +1 519 837 1881

Sales Inquiries Email: [email protected]

Technical Inquiries Email: [email protected]

CANADIAN SOLAR (USA), INC.

North America Headquarters:

3000 Oak Road, Ste 400, Walnut Creek, CA 94596

Tel: +1 888 998 7739

Sales Inquiries Email: [email protected]

Technical Inquiries Email: [email protected]

This manual is subject to change without prior notification. Copyright is reserved. Duplication of any part of this issue is prohibited without written permission.

Please adhere to the actual products in case of any discrepancies in this user manual.

$ ~

CanadianSolar

CSI Three Phase Inverter

(125kW)

Installation and Operation Manual

For U.S.

Ver 1.2

CANADIAN SOLAR INC.

~ ~

CanadianSolar

~ ~

CanadianSolar

Important notes

• Product specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate and up-to-date. Individuals reviewing this document and installers or service personnel are cautioned, however, that Canadian Solar reserves the right to make changes without notice and shall not be responsible for any damages, including indirect, incidental or consequential damages caused by reliance on the material presented including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the material provided in this document.

• Canadian Solar accepts no liability for customers' failure to comply with the instructions for correct installation and will not be held responsible for upstream or downstream systems Canadian Solar equipment has supplied.

• The customer is fully liable for any modifications made to the system; therefore, any hardware or software modification, manipulation, or alteration not expressly approved by the manufacturer shall result in the immediate cancellation of the warranty.

• Given the countless possible system configurations and installation environments, it is essential to verify adherence to the following:

• There is sufficient space suitable for housing the equipment.

• Airborne noise produced depending on the environment.

• Potential flammability hazards.

• Canadian Solar will not be held liable for defects or malfunctions arising from:

• Improper use of the equipment.

• Deterioration resulting from transportation or particular environmental conditions.

• Performing maintenance incorrectly or not at all.

• Tampering or unsafe repairs.

• Use or installation by unqualified persons.

• This product contains lethal voltages and should be installed by qualified electrical or service personnel having experience with lethal voltages.

Contents

~ ~

CanadianSolar

1. Introduction ···························································································································································· 4

1.1 Product Description ····················································································································· 4

1.2 Unpacking and storage ············································································································ 5

1.2.1 Storage ······························································································································ 6

2. Safety instructions ······································································································································· 7

2.1 Safety symbols ······························································································································ 7

2.2 General safety instructions ··································································································· 7

2.3 Notice for use ································································································································· 8

2.4 Protection Circuitry and Controls····························································································· 8

3. Installation ····························································································································································10

3.1 Environmental considerations ····························································································· 10

3.1.1 Select a location for the inverter ········································································ 10

3.1.2 Other environmental considerations ............................................................... 11

3.2 Product handling ························································································································ 12

3.3 Mounting the Inverter ··············································································································· 13

3.3.1 Wall mounting ··············································································································· 14

3.3.2 Rack mounting ······································································································ 15

3.4 Electrical Connections ··············································································································· 17

3.4.1 Grounding ··············································································································· 18

3.4.2 Connect PV side of inverter ···················································································· 20

3.4.3 Connect grid side of inverter ················································································· 23

4. Communication & Monitoring ············································································································ 26

4.1 RS485 and Ethernet communication connection ...................................................... 26

4.1.1 RS485 communication ································································································ 26

4.1.2 Ethernet communication ····························································································· 29

5. Commissioning ················································································································································ 30

5.1 Selecting the appropriate grid standard ········································································ 30

5.1.1 Verifying grid standard for country of installation ···································· 30

5.2 Changing the grid standard ··································································································· 30

5.2.1 Procedure to set the grid standard .................................................................. 30

5.3 Setting a custom grid standard ·························································································· 31

5.4 Preliminary checks ····················································································································· 32

5.4.1 DC Connections ············································································································ 32

5.4.2AC Connections ············································································································ 32

5.4.3 DC configuration ········································································································· 32

5.4.4AC configuration ······································································································ 34

6. Normal operation ······································································································································· 35

6.1 Start-up procedure .................................................................................................................. 35

6.2 Shutdown procedure ·················································································································· 35

6.3 Main Menu ······································································································································· 36

6.4 Information ······································································································································· 36

6.4.1 Lock screen

......................................................................................................... 38

~ ~

CanadianSolar

Contents

6.5 Settings ················································································································································ 38

6.5.1 Set Time ·················································································································· 38

6.5.2 Set Address ·················································································································· 38

6.6 Advanced Info- Technicians Only ······················································································· 39

6.6.1 Alarm Message ·················································································································· 39

6.6.2 Running Message ········································································································· 39

6.6.3 Version ································································································································· 40

6.6.4 Daily Energy ························································································································ 40

6.6.5 Monthly Energy ·················································································································· 40

6.6.6 Yearly Energy ····················································································································· 41

6.6.7 Daily Records ····················································································································· 41

6.6.8 Communication Data ··································································································· 41

6.6.9 Warning Message ············································································································ 41

6.7 Advanced Settings- Technicians Only ·············································································· 42

6.7.1 Selecting Standard ······································································································ 42

6.7.2 Grid ON/OFF ·················································································································· 44

6.7.3 Clear Energy ··················································································································44

6.7.4 Reset Password ·················································································································· 44

6.7.5 Power control ·················································································································· 45

6.7.6 Calibrate Energy·················································································································· 45

6.7.7 Special Settings ·················································································································· 45

6.7.8 STD Mode settings ········································································································· 46

6.7.9 Restore Settings ···············································································································57

6.7.10HMIUpdate ·····················································································································57

6.7.11 ExternaiEPMSet ·········································································································57

6.7.12RestartHMI ··················································································································58

6.7.13 Debug Parameter ·········································································································58

6.7.14 Fan Test ······························································································································58

6.7.15DSPUpdate ··················································································································59

6.7.16 Compensation Set ······································································································59

6.7.171/VCurve ···························································································································60

7. Maintenance ························································································································································· 61

7.1 Anti-PID Function ······························································································································ 61

7.2 Fan Maintenance ······························································································································ 62

7.3 Fuse Maintenance ··························································································································· 63

7.4 Surge Protection Device Maintenance ·············································································· 64

8. Troubleshooting ················································································································································ 65

8.1 Current Alarm ···································································································································· 65

8.2Aiarm History ···································································································································· 65

8.3 Error Messages ······························································································································ 65

9. Specifications ······················································································································································ 69

10. Appendices ························································································································································· 70

11. Installation and commissioning checklist ····································································· 72

1. Introduction ~ ~

CanadianSolar

1.2.1 Storage

If the inverter is not installed immediately, storage instructions and environmental conditions are below:

• Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the box.

• Store the inverter in a clean and dry place, free of dust and dirt. The storage temperature must be between -40 and 158 F (-40- 70C) and humidity should be between 0 to 100%, non-condensing.

• Do not stack more than two (2) inverters high on a single pallet. Do not stack more than 2 pallets high.

• Keep the box{es) away from corrosive materials to avoid damage to the inverter enclosure.

• Inspect the packaging regularly. If packing is damaged {wet, pest damages, etc.), repackage the inverter immediately.

• Store inverters on a flat, hard surface -- not inclined or upside down.

• After 100 days of storage, the inverter and carton must be inspected for physical damage before installing. If stored for more than 1 year, the inverter needs to be fully examined and tested by qualified service or electrical personnel before using.

• Restarting after a long period of non-use requires the equipment be inspected and, in some cases, the removal of oxidation and dust that has settled inside the equipment will be required.

~ ~

canadianSolar

2.

Safety Instructions

Improper use may result in electric shock hazards or burns. This product manual contains important instructions that are required to be followed during installation and maintenance.

Please read these instructions carefully before use and keep them in an easily locatable place for future reference.

2.1 Safety symbols

Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed below:

WARNING

Symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.

NOTE

Symbol indicates important safety instructions, which if not correctly followed, could result in damage to or the destruction of the inverter.

CAUTION, RISK OF ELECTRIC SHOCK

Symbol indicates important safety instructions, which if not correctly followed, could result in electric shock

CAUTION, HOT SURFACE

Symbol indicates safety instructions, which if not correctly followed, could result in burns.

2.2 General safety instructions

WARNING

Do not connect PVarray positive{+) or negative{-) to ground- doing so could cause serious damage to the inverter.

WARNING

Electrical installations must be done in accordance with local and national electrical safety standards.

WARNING

To reduce the risk of fire, branch circuit over-current protective devices {OCPD) are required for circuits connected to the Inverter.

CAUTION

The PV array {solar panels) supplies a DC voltage when exposed to light.

.7. .6.

DO NOT STACK

MORE 11-IAN 2 HIGH

Figure 1.3

3. Installation ~ ~

CanadianSolar

3.3.2 Rack mounting

The steps to mounted to the rack are listed below:

1. Select a location for the inverter

• With an NEMA4X protection rating,the inverter can be installed both outdoors and indoors.

• When the inverter is running, the temperature of the chassis and heat sink will be higher,

Do not install the inverter in a location that you accidentally touch.

• Do not install the inverter in a place where it is stored in a flammable or explosive material.

2. Installation angle

Please install the inverter vertically. If the inverter cannot be mounted vertically, it may be tilted backward to 15 degrees from vertical.

[ Vertical ] [ Backward ]

~ ~

CanadianSolar

3. Installation

3. Install mounting plate

1) Remove the bracket and fasteners from the packaging. Mark the position for hole, drilling according to the hole positions of the bracket.

Figure 3.11 Mark the position for hole

2) Drill the marked holes. It is recommended to apply anti-corrosive paint at the hole for corrosion protection.

Figure 3.9 Correct installation Angle

[ Inverted ]

Figure 3.12 Drill hole

®

Figure 3.10 Wrong installation Angle

®

. 14. .15 .

3. Installation ~ ~

CanadianSolar

3) Align the mounting plate with the holes, Insert the combination bolt {M1 OX40)through the mounting plate into the hole. Secure the bracket to the metal frame firmly with the supplied fastener. Torque the nut to 25.8ft-lbs {35N.m).

Figure 3.13 Construction bolt

4) Lift the inverter above the bracket and then slide down to make sure they match perfectly.

~ ~

CanadianSolar 3. Installation

3.4 Electrical Connections

Inverter design uses PV style quick-connect terminal. The top cover needn't be opened during DC electrical connection. The labels located the bottom of the inverter are described below in table 3.1. All electrical connections are suitable for local or national standard.

Parts Connection Cable size Torque

DC terminal

Ground terminal

PV strings

AC ground

12-10AWG

3-1 AWG

NA

7.4-8.9 ft-lbs

Grid terminal Grid 2-4/0AWG 7.4-14.6 ft-lbs

RS-485 terminal Communication cable 22-12AWG 0.44 ft-lbs

RJ45 terminal

COM terminal

DC surge protection device

Communication cable Network cable

Wi-Fi/Cellular stick NA

NA NA

NA

NA

NA

Table 3.1 Electrical connection symbols

The electrical connection of the inverter must follow the steps listed below:

1. Switch the Grid Supply Main Switch {AC) OFF.

2. Switch the DC Isolator OFF.

3. Connect the inverter to the grid.

4. Assemble PV connector and connect to the Inverter.

Figure 3.14 Mount the inverter

. 16. .17 .

3. Installation

3.4.3.2 Wiring procedure

~ ~

CanadianSolar

CAUTION

RISK OF ELECTRIC SHOCK. Prior to starting the wiring procedure, ensure that the three-pole circuit breaker is switched off and cannot be reconnected.

NOTE

Damage or destruction of the inverter's electronic components due to moisture and dust intrusion will occur if the enclosure opening is enlarged.

CAUTION

Risk offire if two conductors are connected to one terminal. If a connection of two conductors to a terminal is made, a fire can occur.

NEVER CONNECT MORE THAN ONE CONDUCTOR PER TERMINAL.

NOTE

Use M1 0 crimp terminals to connect to the inverter AC terminals.

The steps to assemble the AC grid terminals are listed as follows:

1) Strip the end of AC cable insulating jacket about 300mm then strip the end of each wire.

(as shown in figure 3.25)

~ ~

CanadianSolar

3. Installation

Figure 3.26 Remove the junction box cover

5) Insert the cable through the nut, sheath, and AC terminal cover. Connect the cable to the AC terminal block in turn, using a socket wrench. Tighten the screws on the terminal block.

The torque is 7.4-8.9 in-lbs (as shown in Figure 3.27).

PE

. 24.

Figure 3.25 StripAC cable

NOTE:

S2 (insulation stripping length) is 2mm-3mm longer than S1.

(OT cable terminal crimping area)

2) Strip the insulation of the wire past the cable crimping area of the OT terminal (M 10 terminal), then use a hydraulic crimp tool to crimp the terminal. The crimped portion of the terminal must be insulated with heat shrinkable tube or insulating tape.

3) Leave theAC breaker disconnected to ensure it does not close unexpectedly.

4) Remove the 4 screws on the inverter junction box and remove the junction box cover (Figure 3.26) .

Figure 3.27 wiring

.25.

5. Commissioning ~ ~

CanadianSolar

5.1 Selecting the appropriate grid standard

5.1.1 Verifying grid standard for country of installation

Canadian Solar inverters are used worldwide and feature preset standards for operating on any grid. Although the grid standard is set at the factory, it is essential the grid standard be verified for the country of installation before commissioning.

The menu for changing the grid standard or for creating a custom standard is accessible as described in Section 6.7 and below.

WARNING

Failure to set the correct grid standard could result in improper operation of the inverter, inverter damage or the inverter not operating at all.

5.2 Changing the grid standard

5.2.1 Procedure to set the grid standard

NOTE

This operation is for service technicians only. The inverter is customized according to the local grid standard before shipping. There should be no requirement to set the standard.

NOTE

The "User-Def" function can only be used by the service engineer.

Changing the protection level must be approved by the local utility.

1 ). From the main screen on the display, select ENTER. There are 4 sub-menu options, use the UP/DOWN arrows to highlight ADVANCED SETTINGS. Press enter to select. lmi.iiufdttm1

Settings

Figure 5.1

2). The screen will show that a password is required. The default password is "001 0", press the DOWN key to move cursor, press the UP key to change the highlighted digit.

I YES=<ENT> NO=<ESC>

Password: 0000

I

Figure 5.2

. 30.

~ ~

CanadianSolar

5. Commissioning

3). Use the UP/DOWN keys to highlight the SELECT STANDARD option. Press enter to select.

~-mm~·nmnmm

Grid ON/OFF

Figure 5.3

4). Select the grid standard for the country of installation.

I

YES=<ENT> NO=<ESC>

Standard:UL-600V

I

Figure 5.4

Press the UP or DOWN key to select the standard. Press the ENTER key to confirm the setting.

Press the ESC key to cancel changes and return to the previous menu.

UL-600V, R21 P3-600, ISONE600 are available for U.S. and Canada markets.

5.3 Setting a custom grid standard

WARNING

• Failure to set the correct grid standard could result in improper operation of the inverter, inverter damage or the inverter not operating at all.

• Only certified personnel should set the grid standard.

• Only set the grid configuration that is approved by your location and national grid standards.

1 ). Please refer to section 6.7 "Advanced Settings" for procedures to create a custom grid configuration for User-Def menu option.

.31 .

5. Commissioning ~ ~

CanadianSolar

5.4 Preliminary checks

WARNING

High Voltage.

AC and DC measurements should be made only by qualified personnel.

5.4.1 DC Connections

Verify DC connections.

1 ). Lightly tug on each DC cable to ensure it is fully captured in the terminal.

2). Visually check for any stray strands that may not be inserted in the terminal.

3). Check to ensure the terminal screws are the correct torque.

5.4.2 AC Connections

Verify AC connections.

1 ). Lightly tug on each AC cable to ensure it is fully captured in the terminal.

2). Visually check for any stray strands that may not be inserted in the terminal.

3). Check to ensure the terminal screws are the correct torque.

5.4.3 DC configuration

Verify DC configuration by noting the number of panels in a string and the string voltage.

5.4.3.1 VOC and Polarity

Measure VOC, and check string polarity. Ensure both are correct and VOC is in specification.

5.4.3.1.1 Check string voltage

To measure the open circuit voltage (VOC) and polarity of the individual strings, perform the following steps:

WARNING

When the fuse holders are closed, parallel strings on the same MPPT are connected together. If there is a voltage difference between the parallel strings such as different string lengths, current will flow between the parallel strings. Opening and closing the fuse holder in this instance is the same as opening and closing under load. Damage to equipment and /or injury to personnel may occur.

. 32.

1 ). Ensure that all fuse holders are open.

2). Connect the positive lead of the meter to the positive string cable of the string under test. Connect the negative lead of the meter to the negative string cable of the string under test.

~ ~

CanadianSolar 5. Commissioning

3). Measure the voltage present between the positive and negative wires of each string.

If the open circuit voltage of the string is near the maximum value accepted by the inverter, verify the string length. Low ambient temperatures cause an increase in the string voltage causing potential damage to the inverter.

4 ). Check the polarity of the string. All digital meters have a negative ("-")indicator that indicates when a voltage is negative; in this case a string connected in reverse polarity.

WARNING

Input voltages higher than the maximum value accepted by the inverter

(see "Specifications" in Section 9) may damage the inverter.

Although Canadian Solar inverters feature reverse polarity protection, prolonged connection in reverse polarity may damage these protection circuits and/or the inverter.

5.4.3.2 Leakage to ground

Measure leakage to ground to check for a DC ground fault.

5.4.3.2.1 Detection of leakage to ground

Canadian Solar inverters are transformer-less and do not have an array connection to ground.

Any measurement of a fixed voltage between ground and either the positive or negative string wiring indicates a leakage (ground fault) to ground and must be corrected prior to energizing the inverter or damage to the inverter may result.

To measure leakage to ground, perform the following steps:

1 ). Ensure that all fuse holders are open.

2). Ensure that neither negative nor positive DC conductors are connected to the ground strip.

3). Measure each string positive connection to ground.

4). Measure each string negative connection to ground.

5). Verify the voltage is "floating", not a consistent voltage to ground. Make sure you notice the units of the measurement. mV is not the same as V.

6). Do not close the fuse holder and connect the strings if a leakage to ground has been detected. Improper operation and damage to the inverter may result.

Once all DC tests have been completed, close the fuse holders.

.33 .

5. Commissioning ~ ~

CanadianSolar

5.4.4 AC configuration

Verify AC configuration.

5.4.4.1 Measure VAC and frequency

Measure VAC and verify voltage is within local grid standards.

1 ). Measure each phase to ground (L-G).

2). Measure phases to the other phases in pairs (L-L). PH A to PH B, PH B to PH C and

PH Cto PHA.

3). If the meter is equipped, measure the frequency of each phase to ground.

4 ). Ensure each measurement is within local grid standards and the inverter specifications as noted in Section 9 "Specifications".

5.4.4.2 Phase rotation test

A phase rotation test is recommended to ensure the phases have been connected in the appropriate order. Canadian Solar inverters do not require a specific phase rotation connection.

However, the local utility may require a specific phase rotation or a record of the phase configuration of the installation.

~ ~

CanadianSolar

6. Normal operation

6.1 Start-up procedure

To start-up the inverter, it is mandatory that the steps below are followed in the exact order outlined.

1 ). Ensure the commissioning checks in Section 5 have been performed.

2). Switch theAC switch ON.

3). Switch the DC switch ON. If the PV array (DC) voltage is higher than the inverter's start-up voltage, the inverter will turn on. The red DC POWER LED and LCD will be continuously lit.

4 ). Canadian Solar inverters are powered from the DC side. When the inverter detects DC power that is within start-up and operating ranges, the inverter will turn on. After turnon, the inverter will check internal parameters, sense and monitor AC voltage, hertz rate and the stability of the supply grid. During this period, the green OPERATION LED will flash and the LCD screen will show INITIALIZING. This tells the operator that the inverter is preparing to generate AC power.

5). After the locally mandated delay (300 seconds for IEEE-1547 compliant inverters), the inverter will start generating AC power. The green OPERATION LED will light continuously and the LCD screen will show GENERATING.

CAUTION

The inverter's surface temperature can reach up to 75•c (167° F). To avoid risk of burns, do not touch the surface when the inverter is in the operational mode. Additionally, the inverter must be installed out of the reach of children.

6.2

Shutdown procedure

To stop the inverter, it is mandatory that the steps below are followed in the exact order outlined.

1 ). Switch AC switch OFF.

2). Wait approximately 30 seconds (during this time, theAC side capacitors are dissipating energy). If the inverter has DC voltage above the start-up threshold, the red POWER

LED will be lit. Switch the DC switch OFF.

3). Confirm all LED's switch OFF (-one (1) minute).

CAUTION

Although the inverter DC disconnect switch is in the OFF position and all the LED's are OFF, operators must wait five (5) minutes after the DC power source has been disconnected before opening the inverter cabinet. DC side capacitors can take up to five (5) minutes to dissipate all stored energy .

. 35 . . 34.

6. Normal operation ~ ~

CanadianSolar

In normal operation, LCD screen alternatively shows inverter power and operation status

(see Figure 6.1 ). The screen can be scrolled manually by pressing the UP/DOWN keys.

Pressing the ENTER key gives access to Main Menu.

5sec

Status: Generating

01-01-2019 12:04

Pressing th r

ENTERkey gives access to the main menu.

Figure 6.1 Operation Overview

6.3 Main Menu

There are four submenus in the Main Menu (see Figure 6.1 ):

1. Information

2. Settings

3. Advanced Info.

4. Advanced Settings

6.4 Information

The Canadian Solar three Phase Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.

. 36.

~ ~

CanadianSolar

6. Normal operation

I

I

Display

VPV Total: 1000.0V

IPV_Total: +99.0A

VA: 345.7V

1_-A: 109.0A

V C: 345.0V

1_-C: 109.8A

Status: Generating

Power: 1488W

I

I

Duration

10 sec

Description

VPV _Total: Shows input voltage total.

IPV _Total: Shows input current total.

10 sec

10 sec

10 sec

V _A: Shows the grid's voltage value.

I_A: Shows the grid's current value.

V _ C: Shows the grid's voltage value.

I_C: Shows the grid's current value.

Status: Shows instant status of the Inverter.

Power: Shows instant output power value.

Rea Power: OOOVar

App -Power: VA

10 sec

Rea_Power: Shows the reactive power ofthe inverter.

App_Power: Shows the apparent power of the inverter.

Grid Frequency

F_Grid 50.06Hz

10 sec F _Grid: Shows the grid's frequency value.

Total Energy

0258458 kwh

This Month: 0123kwh

Last Month: 0123kwh

Today: 15.1kwh

Yesterday: 13.5kwh

Inverter SN

00000000000000

Work Mode: Volt-watt

DRM N0.:08

I_DC01: +05.0A

I_DC20: +05.2A

10 sec Total generated energy value.

10 sec

10 sec

This Month: Total energy generated this month.

Last Month: Total energy generated last month.

Today: Total energy generated today.

Yesterday: Total energy generated yesterday.

10 sec Display series number of the inverter.

10 sec

10 sec

Work Mode: Shows current working mode.

DRM NO.: Shows DRM Number.

I _DC01 :Shows input 01 current value.

I _DC02 :Shows input 02 current value.

...

I_DC20: Shows input 20 current value.

Table 6.1 Information list

.37 .

6. Normal operation ~ ~

CanadianSolar

6.4.1 Lock Screen

Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks

(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen. a

(a)

-":Ill

II:.-

(b)

Figure 6.2 Locks and Unlocks the Screen of LCD

6.5 Settings

The following submenus are displayed when the Settings menu is selected:

1.SetTime

2.Set Address

6.5.1 Set Time

This function allows time and date setting. When this function is selected, the LCD will display a screen as shown in Figure 6.3.

I NEXT=<ENT> OK=<ESC>I o1-o1-2019 16:37 1

Figure 6.3 Set Time

Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one digit to the next (from left to right). Press the ESC key to save the settings and return to the previous menu.

6.5.2 SetAddress

This function is used to set the address when muti inverters are connected to three monitor.

The address number can be assigned from "01 "to "99"(see Figure 6.4). The default address number of Canadian Solar Three Phase Inverter is "01 ".

I

YES=<ENT> NO=< ESC>

Set Address: 01

I

Figure 6.4 Set Address

Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.

Press the ESC key to cancel the change and return to the previous menu.

. 38.

~ ~

CanadianSolar 6. Normal operation

6.6Advanced Info- Technicians Only

NOTE:

To access to this area is for fully qualified and accredited technicians only.

Enter menu "Advanced Info." and "Advanced settings" Cneed password) .

Select "Advanced Info." from the Main Menu. The screen will require the password as below:

YES=<ENT>NO=<ESC>

Password :0000

Figure 6.5 Enter password

After enter the correct password the Main Menu will display a screen and be able to access to the following information.

1.Aiarm Message

2. Running message

3.Version

4. Daily Energy

5. Monthly Energy

6. Yearly Energy

7. Daily Records

&.Communication Data

9. Warning Message

The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.

6.6.1 Alarm Message

The display shows the 100 latest alarm messages (see Figure 6.6). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.

AlmOOO: OV-G-V

T:00-00 00:00 D:OOOO

Figure 6.6Aiarm Message

6.6.2 Running Message

This function is for maintaince person to get running message such as internal temperature,

Standard No.1 ,2,etc.

Screens can be scrolled manually by pressing the UP/DOWN keys.

.39 .

6. Normal operation ~ ~

CanadianSolar

6.6.3 Version

The screen shows the model version of the inverter. And the screen will show the software ver by pressing the UP and DOWN at the same time.( see Figure 6. 7).

Model: 08

Software Version: D20001

Figure 6. 7 Model Version and Software Version

6.6.4 Daily Energy

The function is for checking the energy generation for selected day.

YES=<ENT> NO=<ESC>

Select: 2019-01 -(!1]

Figure 6.8 Select date for daily energy

Press DOWN key to move the cursor to day, month and year, press UP key to change the digit.

Press Enter after the date is fixed.

I

2019-01-01: 051.3kWh

2019-01-01: 061.5kWh

I

Figure 6.9 Daily energy

Press UP/DOWN key to move one date from another.

6.6.5 Monthly Energy

The function is for checking the energy generation for selected month.

I YES=<ENT> NO=<ESC>

Select: 2019till

I

Figure 6.10 Select month for monthly energy

Press DOWN key to move the cursor to day and month, press UP key to change the digit.

Press Enter after the date is fixed.

2019-01: 051 OkWh

2019-01: 061 OkWh

Figure 6.11 Month energy

Press UP/DOWN key to move one date from another .

.40.

~ ~

CanadianSolar 6. Normal operation

6.6.6 Yearly Energy

The function is for checking the energy generation for selected year.

I

YES=<ENT> NO=< ESC>

Select: 20 IE

I

Figure 6.12 Select year for yearly energy

Press DOWN key to move the cursor to day and year, press UP key to change the digit.

Press Enter after the date is fixed.

I

2018:0017513kWh

2017:0165879kWh

Figure 6.13 Yearly energy

I

Press UP/DOWN key to move one date from another.

6.6. 7 Daily Records

The screen shows history of changing settings. Only for maintance personel.

6.6.8 Communication Data

The screen shows the internal data of the Inverter (see Figure 6.14), which is for service technicians only.

01-05:01 25 E4 9DAA

06-10: C2 85 E4 9D 55

Figure 6.14 Communication Data

6.6.9 Warning Message

The display shows the 100 latest warn messages (see Figure 6.15). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.

I

MsgOOO:

T:00-00 00:00 D:OOOO

I

Figure 6.15 Warning Message

.41.

6. Normal operation ~ ~

CanadianSolar

6. 7 Advanced Settings- Technicians Only

NOTE:

To access to this area is for fully qualified and accredited technicians only.

Please follow 6.4 to enter password to access this menu.

Select Advanced Settings from the Main Menu to access the following options:

1. Select Standard

2. Grid ON/OFF

3. Clear Energy

4. Reset Password

5. Power Control

6. Calibrate Energy

7. Special Settings

8. STD. Mode Settings

9. Restore Settings

10. HMI Update

11. External EPM set

12. Restart HMI

13. Debug Parameter

14.DSP Update

15.Compensation Set

16.1/VCurve

6. 7.1 Selecting Standard

This function is used to select the grid's reference standard (see Figure 6.16).

I

YES=<ENT> NO=<ESC>

Standard:UL-600V

I

Figure 6.16

Selecting the "User-Def" menu will access to the following submenu (see Figure 6.17),

I

-

OV-G-V1: 400V

I

OV-G-V1-T: 1.0S

Figure 6.17

Below is the setting range for "User-Def". Using this function, the limits can be changed manually. (These voltage values are the phase voltage)

.42.

~ ~

CanadianSolar 6. Normal operation

OV-G-V1: 300---480V

OV-G-V1-T: 0.0 1---9S

OV-G-V2: 300---490V

OV-G-V2-T: 0.01---1S

UN-G-V1: 173---336V

UN-G-V1-T: 0.01---9S

UN-G-V2: 132---319V

UN-G-V2-T: 0.01---1S

Startup-T: 1 0-600S

OV-G-F1: 50.2-63Hz

OV-G-F1-T: 0.01---9S

OV-G-F2: 51-63Hz

OV-G-F2-T: 0.01---9S

UN-G-F1: 47-59.5Hz

UN-G-F1-T: 0.01---9S

UN-G-F2: 47-59Hz

UN-G-F2-T: 0.01---9S

Restore-T: 1 0-600S

Table 6.2 Setting ranges for User-Def (L-N)

NOTE

The initial value of the User-Def standard is for reference only. It does not represent a correct value suitable for use.

Setting value

Vup-Limit1

Time1

Vup-Limit2

Time2

Vdw-Limit1

Time1

Vdw-Limit2

Time2

Fup-Limit1

Time1

Fup-Limit2

Time2

Fdw-Limit1

Time1

Fdw-Limit2

Time2

600V Rated (L-L) 600V Rated (L-N)

660<V<720

1S

V~720

381<V<415

1S

V~415

0.16S

360~V<528

2S

0.16S

207~V<304

2S

V<360

0.16S

V<207

0.16S

60.5Hz < F <62Hz 60.5Hz < F <62Hz

2S 2S

F>62Hz

0.16S

F>62Hz

0.16S

57Hz< F < 59.5Hz 57Hz< F < 59.5Hz

2S 2S

57Hz< F

0.16S

57Hz< F

0.16S

Table 6.3 Baseline Inverter Settings

.43 .

6. Normal operation ~ ~

CanadianSolar

6.7.2 Grid ON/OFF

This function is used to start up or stop the power generation of Canadian Solar Three Phase

Inverter (see Figure 6.18).

GridON

Grid OFF

Figure 6.18 Set Grid ON/OFF

Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key to save the setting. Press the ESC key to return to the previous menu.

6.7.3 Clear Energy

Clear Energy can reset the history yield of inverter

A

These two functions are applicable by maintenance personnel only, wrong

6.7.4 Reset Password

This function is used to set the new password for menu "Advanced info." and "Advanced information" (see Figure 6.19).

I

YES=<ENT> NO=<ESC>

Password: 0000

I

Figure 6.19 Set new password

Enter the right password before set new password. Press the DOWN key to move the cursor,

Press the UP key to revise the value. Press the ENTER key to execute the setting.

Press the ESC key to return to the previous menu.

~ ~

CanadianSolar 6. Normal operation

6. 7.5 Power Control

Active and reactive power can be set through power setting button.

There are 5 item for this sub menu:

1. Set output power

2. Set Reactive Power

3. Out_P With Restore

4. Rea_P With Restore

5. Select PF Curve

A

This function is applicable by maintenance personnel only, wrong operation

6. 7.6 Calibrate Energy

Maintenance or replacement could clear or cause a different value of total energy. Use this function could allow user to revise the value of total energy to the same value as before. If the monitoring website is used the data will be synchronous with this setting automatically.

(see Figure 6.20).

YES=<ENT> NO=<ESC>

Energy:OOOOOOOkWh

Figure 6.20 Calibrate energy

Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the

ENTER key to execute the setting. Press the ESC key to return to the previous menu.

6.7.7 Special Settings

A

This function is applicable by maintenance personnel only, wrong operation

.44. .45 .

6. Normal operation ~ ~

CanadianSolar

6.7.8 STD Mode Settings

£

This section is applicable to maintenance personnel only.

Selecting "STD Mode. Settings" displays the sub-menu shown below:

1. Working Mode Set

2. Power Rate Limit

3. Freq Derate Set

4. 1Om ins Voltage Set

5. Power Priority

6. Initial Settings

7. Voltage PCC Set

6. 7 .8.1 Working Mode Set

There are TWO situations with different grid standards selected.

6. 7.8.1.1 With UL Standard selected

NOTE

The following modes are for "UL-600V".

Canadian Solar inverters have Seven working modes:

1. NULL

2. Volt-watt

3. Volt-Var

4. Fixed-PF

5. Reac-power

6. Power-PF

7. VgWatt-UL

Based on UL 1741 SA, working mode 1,3,4, 7 can be used by grid operator.

~ ~

CanadianSolar 6. Normal operation

1.NULL

Description: Inverter is not under any working mode.

2. Volt-Watt (Not Required)

Description: Inverter will change the active output power based on voltage change.

Note: This Setting is NOT required by UL 17 41 SA Standards.

A

This function is for maintenance personnel only, wrong operation

3. Volt-Var (Default)

Description: Inverter will change the reactive output power based on voltage change.

Q1, cap

02=03=0

Q4, ind

---------

~~

------

i~

--

~~~~

-

i ....

J_

Figure 6.21 Volt-VAR curve for Q (V)

Default Settings for UL 1741 SA:

Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%

Rated 600V Grid

V1 :(277-346V) Default 303V V2: (277-346V) Default 340V

V3:(346-415V) Default 349V V4: (346-415V) Default 381V

Voltage1 : 303V

I Voltage2: 340V

Figure 6.22 Volt-VAR

I

.46. .47 .

6. Normal operation ~ ~

CanadianSolar

4.Fixed-PF

Description: Inverter will output power with fixed power factor.

Setting Range: -0.8 to +0.8

Default value is PF = 1 under-excited

Q/Po under-excited

YES=<ENT> NO=<ESC>

Power Factor:+1. 00

Figure 6.23 Fixed-PF

!

1.0 P/Po

·-..

.. ____

Ill over-excited

----

---

IV over-excited

Figure 6.24 PF Range

5. Reac-power (Not Required)

Description: Inverter will generate reactive power based on changing output power.

Note: This Setting is NOT required by UL 1741 SA Standards.

A

This function is for maintenance personnel only, wrong operation

6. P-factor (Not Required)

Description: Inverter will change power factor based on changing output power.

Note: This Setting is NOT required by UL 1741 SA Standards.

A

This function is for maintenance personnel only, wrong operation

~ ~

CanadianSolar 6. Normal operation

7.VgWatt-UL

Description: Inverter will change the active output power based on voltage change.

Note: This is the Volt-Watt Setting for UL 1741 SA Standards.

100% of

Input

Power

0

Vmin Vnom Vstart

Figure 6.25 Volt-Watt characteristic

Vstop

ACVolt

Vmax

Default Settings for UL 1741 SA:

Rated 600V Grid

V1 :less than V2

V2:1ess than Vstart

V3 (Vstart): (346-415V) Default381V

V4 (Vstop): (381-450V) Default415V

P1:100% P2:100% P3: 100% P4:0%

I

Voltage1 : 318V

P-Limit1: 100%

Figure 6.26 VgWatt-UL

I

.48. .49.

6. Normal operation ~ ~

CanadianSolar

6. 7 .8.1.2 With Rule21 Standard selected

NOTE

The following modes are for "R21 P3-600".

Canadian Solar inverters have Ten working modes:

1. NULL

2. Volt-watt

3. Volt-Var

4. Fixed-PF

5. Reac-power

6. Power-PF

7. VgWatt-UL

Based on Rule21, working mode 1 ,2,3,4 can be used by grid operator.

NOTE

The other three working mode"P1-V-Watt", "P1-V-Var" and

"P1-V-P&V-Q" are NOT applicable for settings.

1.NULL (Mode Reset)

Description: Inverter is not under any working mode.

2. Volt-Watt

Description: Inverter will change the active output power based on voltage change.

Note: This is the Volt-Watt Setting for Rule21 Standards.

Full Power Production Real Power

Capabilities Zone Reduction Zone

100% r---------------~~

Active Power as%of

Nameplate

50%

No Real Power

Production Zone

11 0% % Voltage 0% 106% 108%

Figure 6.27 Volt-Watt characteristic

. 50.

~ ~

CanadianSolar 6. Normal operation

Default Settings for Rule21 Standards:

Rated 600V Grid

V1 :less than Vstart

V2 (Vstart): (346-415V) Default 367V

V3 (Vstop): (381-450V) Default 381V

V4: larger than Vstop

P1 :100% P2:100% P3: 0% P4:0%

3. Volt-Var

Description: Inverter will change the reactive output power based on voltage change.

Q1, cap

Q2=Q3=0

Q4, ind ---------

~~ i~:

-----i~ - ~n _ o _ ~ i ....

J

_ 4 ________ _

Figure 6.28 Volt-VAR curve for Q (V)

Default Settings for Rule21 Standard:

Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%

Rated 600V Grid

V1 :(277-346V) Default 318V

V3:(346-415V) Default 357V

V2: (277-346V) Default 335V

V4: (346-415V) Default 370V

I

Voltage1 : 318V

Voltage2: 335V

Figure 6.29 Volt-VAR

I

4.Fixed-PF

Description: Inverter will output power with fixed power factor.

Setting Range: -0.8 to +0.8

Default value is PF

=

1

.51 .

6. Normal operation ~ ~

CanadianSolar under-excited

Q/Pn under-excited

YES=<ENT>NO=<ESC>

Power Factor: +1. 00

Figure 6.30 Fixed-PF f 1,0 P/Pn

~--

Ill over-excited

-----

___

..

---

IV over-excited

Figure 6.31 PF Range

5. Reac-power (Not Required)

Description: Inverter will generate reactive power based on changing output power.

Note: This Setting is NOT required by Rule21 Standards.

A

This function is for maintenance personnel only, wrong operation

6. P-factor (Not Required)

Description: Inverter will change power factor based on changing output power.

Note: This Setting is NOT required by Rule21 Standards.

A

This function is for maintenance personnel only, wrong operation

7.VgWatt-UL (Not Required)

Description: Inverter will change the active output power based on voltage change.

Note: This Setting is NOT required by Rule21 Standards.

A

This function is for maintenance personnel only, wrong operation

~ ~

CanadianSolar 6. Normal operation

8. Enable both Volt-Var and Volt-Watt modes

Description: Rule21 requires both Volt-var and Volt-watt modes can be enabled.

To set both modes (Volt-var in high priority)

Step 1: Select and set Volt-watt mode at first.

Step 2: Enter "Working Mode" again and select and set Volt-var mode then.

Step 3: To check the priority, a new mode will appear as "V-Q & V-P" which indicates (Q) Volt-var is in high priority.

YES=<ENT> NO=<ESC>

Work Mode : V-Q & V-P

Figure 6.32 Work Mode

To set both modes (Volt-watt in high priority)

Step 1: Select and set Volt-var mode at first.

Step 2: Enter "Working Mode" again and select and set Volt-watt mode then.

Step 3: To check the priority, a new mode will appear as "V-P & V-Q" which indicates (P) Volt-watt is in high priority.

YES=<ENT> NO=<ESC>

Work Mode : V-P & V-Q

Figure 6.33 Work Mode

To reset dual-mode or exit the dual-mode situation

Step 1: Select "Null" mode at first.

Step 2: Enter "Working Mode" again. Redo above dual-mode setting steps to reset OR set other modes to exit dual-mode situation.

NOTE

To check the Volt-watt and Volt-var priority, simply enter the working modes.

V-Q&V-P indicates Volt-Var First V-P&V-Q indicates Volt-Watt First

. 52. .53.

6. Normal operation ~ ~

CanadianSolar

6. 7 .8.2 Power Rate Limit

This function is used for change Power Ramp-up rate. When inverter start up or input string

MPPT changes, inverter power ramp-up rate is limited in this menu.

The default setting is stop (disable).

The setting range from 10% to 600%, means inverter power change rate per minute.

Values are not allowed to change. If they are set, they may not conform to the UL 1741 SA standard.

I

Power Rate:016%

RateP _Sts-US:STOP

Figure 6.34 Power Rate Limit

I

6.7.8.3 Freq Derate Set

This setting is applicable when UL Standards are selected.

There are 5 derate modes in this menu. When operating under standard UL-17411imits, modes 00 to 03 are disabled. Mode 04 is used for UL 1741 SA frequency derating setting.

Mode 08 is used for RULE21 Freq-watt setting. This sets the f start and f stop point.

Mode 04:

I

Derate Mode: 04

OV-F-Start: 60. 20Hz

Figure 6.35 Freq Derate Set

I

. 54.

100% of

Available

Power

~ ,;d

F'eq"e"cy o L----------------r-----------r----------~--------~ f min f nom f start f stop f max

Figure 6.36 Freq-Watt characteristic

Over frequency load shedding Fstart range 60-62Hz, default setting 60.2Hz

Fstop can set the scope: 61-64Hz, the default setting 62Hz.

Press the Enter key to select the mode or frequency.

Press Up/Down to set. Press ESC to save the settings .

~ ~

CanadianSolar 6. Normal operation

Mode 08:

This setting is used to control real power based on the frequency excursion

This setting is applicable when Rule21 Standards are selected.

1

-

Start Freq: 60.50Hz

WGradient: 040%

Figure 6.37 Freq-Watt (1)

I

Start Freq: This is the frequency that active power reduction starts.

WGradient: This is the active power reduction rate in terms ofthe frequency.

Stop Freq: This is the frequency that stops the correction cycle.

Hysteresis: This indicates whether hysteresis is enabled.

Reduced

Power f stop f start

~

·;·"'

Hysteresis

Figure 6.38 Freq-Watt (2) f

This function is for maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.

.55.

6. Normal operation ~ ~

CanadianSolar

6.7.8.4 1Om ins Voltage Set

This function is disabled and not used for the US.

A

This function is for maintenance personnel only, wrong operation

6. 7 .8.5 Power Priority

This setting is used to set the priority between Active Power Control (Watt) and

Reactive Power Control (Var).

I

YES=<ENT> NO=<ESC>

Select: Var First

I

Figure 6.39 Power Priority

Two options are available: Watt First and Var First.

A

This function is for maintenance personnel only, wrong operation

6.7.8.61nitial Settings

In initial settings it will reset each work mode from 6.5.8.1 to 6.5.8.4 back to default.

I

Work Mode Default

Power Rate Default

Figure 6.40 Initial Settings

I

6. 7 .8. 7 Voltage PCC Set

Set the voltage at the PCC point.

This setting is required by RULE 21 requirements.

PCC: Point of Common Coupling, the point where a Local EPS is connected to an Area EPS.

A

This function is for maintenance personnel only, wrong operation

~ ~

CanadianSolar 6. Normal operation

6.7.9 Restore Settings

There are 5 items in initial setting submenu.

Restore setting could set all item in 6.5.7 special setting to default.

The screen shows as below:

Are you sure? I

YES=<ENT>NO=<ESC>

I

Figure 6.41 Restore Settings

Press the Enter key to save the setting after setting grid off.

Press the ESC key to return the previous mean.

6.7.10 HMI Update

£

This section is applicable to maintenance personnel only.

Selecting "Updater" displays the sub-menu shown below:

HMI Current Ver.: 02

YES=<ENT>NO=<ESC>

Figure 6.42

Updater is for updating LCD firmware. Press the ENTER key to start the process.

Press the ESC key to return to the previous menu.

6.7.11 External EPM Set

This function is turned on when the EPM is external.

YES=<ENT> NO=<ESC>

Fail Safe Set: ON

Figure 6.43 Set the Fail Safe ON/OFF

. 56. .57.

. 58.

6. Normal operation ~ ~

CanadianSolar

6.7.12 Restart HMI

The function is used for restart the HMI.

A

This function is applicable by maintenance personnel only, wrong operation

6. 7.13 Debug Parameter

£

This section is applicable to maintenance personnel only.

Debug Parameter as shown as below:

-+S16DAT1: +0000

S16DAT2: +0000

S16DAT3: +0000

S16DAT4: +0000

S16DAT5: +0000

S16DAT6: +0000

S16DAT7: +0000

S16DAT8: +0000

Figure 6.44

Press the UP/DOWN keys to scroll through items. Press the ENTER key to select.

Press the DOWN key to scroll and press the UP key to change the value.

Press the ENTER key to save the setting. Press the ESC key to cancel. changes and return to the previous menu.

6.7.14 FANTest

£

This section is applicable to maintenance personnel only.

~ ~

CanadianSolar 6. Normal operation

Selecting "Fan Test" displays the sub-menu shown below:

I

Are you sure?

I

YES=<ENT>NO=<ESC~

Figure 6.45

Fan Test is a factory test function. Press the ENTER key to start the test.

Press the ESC key to return to the previous menu.

6. 7.15 DSP Update

The function is used for update the DSP.

A

This function is applicable by maintenance personnel only, wrong operation

6. 7.16 Compensation Set

This function is used to calibrate inverter output energy and voltage. It will not impact the energy count for inverter with RGM.

Two sections are included: Power Parameter and Voltage Parameter.

The screen shows:

YES=<ENT>NO=<ESC>

Power para: 1. 000

Figure 6.46 Power Rate Limit

Press the Down key to move the cursor.

Press the Up key to change the digit.

Please press the Enter to save the setting and press the ESC key to return to the previous menu.

A

This setting is used for grid operators, do not change this setting unless

.59.

6. Normal operation ~ ~

CanadianSolar

6.7.171/VCurve

This function is used to scan the 1/V characteristic curves of each PV strings.

1

-

Set 1/V Curve

1/V Curve Scan

Figure 6.47 1/V Curve

I

6.7.17.1 Set 1/V Curve

This setting can set the scanning voltage start point and the voltage interval.

Start_ V: 850V lntervai_V: 010V

Figure 6.48 Set 1/V Curve

Start_ V: The start voltage of the IIV scan. (Adjustable from 850V-1 OOOV)

Interval_ V: The scanning voltage intervai.(Adjustable from 001V-1 OOV)

In total, 60 data points can be scanned.

The max scanning range is from 850-1450V.

6. 7.17 .2 IIV Curve Scan

Press "ENT" to start the 1/V curve scan.

Scanning ... 01

Figure 6.49 1/V Curve Scan (1)

After it is completed, the screen will display "Scan OK" and then enter the following section.

Select String No.: 01

Figure 6.50 1/V Curve Scan (2)

I

01 850V: o2::::S60V:

9.56A

9.44A I

Figure 6.51 1/V Curve Scan (3)

.60.

~ ~

CanadianSolar 7. Maintenance

Canadian Solar Three Phase Inverter does not require any regular maintenance. However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.

CAUTION:

Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter (refer to Section

6.2) and wait for a cool-down period before before any maintenance or cleaning operation.

The LCD and the LED status indicator lights can be cleaned with a damp cloth if they are too dirty to be read.

NOTE:

Never use any solvents, abrasives or corrosive materials to clean the inverter.

7.1 Anti-PI D Function

CSI-125KTL-GS-E integrates optional Anti-PID module and it can recover the

PID effect during night thus protect the PV system from degradation.

CSI-125KTL-GS-E

Figure 7.1

The Anti-PID module repairs the PID effect of the PV model at night. When operating, the inverter LCD screen displays" PID-repairing" information, and the red light is on.

TheAnti-PID function is always ON whenAC is applied.

If maintenance is required and turn off the AC switch can disable the Anti-PID function.

WARNING:

The PID function is automatic. When the DC bus voltage is lower than 260Vdc, the PID module will start creating 650 Vdc between PV- and ground.

No need any control or settings

.61.

8. Troubleshooting ~ ~

CanadianSolar

Alarms

No Information

(Blank Screen)

• Input voltage low/missing

• Polarity reversed

• Main board damaged

Initializing

(Inverter stuck in this mode)

OV-G-V: Over

Grid Voltage

UN-G-V: Under

Grid Voltage

Cause

• Inverter is waiting for driving signal

• Inverter detects grid voltage as too high

• Inverter detects grid voltage as too low

Solution

Test- DC switch OFF

• Check PV connections

• Check polarity

• Check voltage >860V

Test- DC Switch ON

• Check voltage >860V

• If DC voltage is "0" replace inverter

Test- DC switch OFF

• Check PV connections

• Check polarity

• Check voltage >860V

Test- DC Switch ON

• Check voltage >860V

• A cable may have been damaged or loosened in shipping replace inverter

Test- DC switch OFF

• CheckAC at the inverter

• If AC measures high, adjust upper limit with permission from utility

Test- DC Switch ON, full power

• CheckAC at inverter test points

• Compare with LCD

•lfAC measures high, cables between inverter and interconnect are too small

• Check ampacity and voltage drop calculations

Test- DC switch OFF

• CheckAC at the inverter test points

• If AC measures low, adjust lower limit with permission from utility

• Check LCD voltage reading, may be a bad measurement circuit

Test- DC Switch ON

• Check grid standard

• Replace inverter

~ ~

CanadianSolar 8. Troubleshooting

Alarms

OV-G-F: Over

Grid Frequency

NO-GRID

Cause

•Inverter detects grid

Frequency as too high

• Inverter does not detect the grid

Solution

Test- DC switch OFF

• Check frequency at the inverter test points

• If Frequency measures high, adjust upper limit with permission from utility

• Check LCD reading, may be a bad measurement circuit

Test - DC Switch ON

• Check grid standard

• Replace inverter

Test- DC switch OFF

• CheckAC at the inverter test points

• L-L, L-GND

• Check LCD reading, may be a bad measurement circuit

Test - DC Switch ON

• Check grid standard

• Replace inverter

OV-DC: DC voltage is too high

OV-BUS: DC

BUS voltage is too high

UN-BUS: DC

BUS voltage is too low

•Inverter detects High DCV

•Inverter detects High

DCV on internal bus

• Inverter detects low DCV on internal bus

Test- DC switch OFF

• Check DC at the inverter test points

• If DCV is high, too many panels in the string

Test - DC Switch ON

• Check LCD reading, may be a bad measurement circuit

• Replace inverter

Test

• Measure DC and AC voltages

• Compare with LCD

• Replace Inverter

• Internal damage

• Wire came loose during shipping

Test

• Measure DC and AC voltages

• Compare with LCD

• Replace Inverter

• Internal damage

• Wire came loose during shipping

. 66. .67 .

8. Troubleshooting ~ ~

CanadianSolar

Alarms

GRID-INTF:

Grid unstable

IN I-PRO:

Initialization

Protection

Cause

• Inverter detects grid instability, internal fault current high

• Master and Slave DSP have different values

Solution

Test- With DC Switch OFF

• MeasureAC voltage

• TestAe line forTHD

• Test- With DC Switch ON

TestAe line forTHD

• Multiple inverters/turn one off

• Impedance matching adjustment or box

• Internal damage

• Wire came loose in shipping

Reset Inverter

• DC switch OFF

• Wait until alllights/LCD turn off

• DC switch ON

• Replace inverter

TEM-PRO:

Temperature

Protection

GROUND-PRO:

Ground

Protection

• Inverter detects high ambient temperature >60C

• Inverter detects low DC insulation resistance

Inspect installation

• Check heatsink for obstructions/ventilation

• Is inverter in direct sunshine

• Measure ambient temperature near inverter

• lftemp is in range replace inverter

Inspect installation

• Reset inverter

• Note weather conditions when alarm occurs

• Measure insulation resistance

• If normal, measure in SAME weather as alarm

• Physically check cables

• Replace inverter

Table 8.1 Fault messages and descriptions

~ ~

CanadianSolar

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPTvoltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Max. efficiency

EU efficiency

MPPT efficiency

Dimensions (W*H*D)

Weight

Topology

Self consumption (night)

Operating ambient temperature range

Relative humidity

Ingress protection

Noise emission

Cooling concept

Max.operation altitude

Compliance

DC connection

AC connection

Display

Communication connections

OTAupdate

Warranty

9. Specifications

CSI-125KTL-GS-E

187000

1500

950

900

860 ... 1450

150

300

1120

125000

125000

125000

3/PE-600

120

0.81eading-0.81agging

<3%

60

99.1%

98.6%

99.9%

1176*713.5*315 (mm) /46.3*28.1*12.4 (inch)

84kg /185.21b

Transformerless

< 3W (without anti-PID)

-25"C ... +60"C

0-100%

NEMA4X/IP65

S55dB(A)

Fan cooling

4000m

UL 1741, UL 1741SA, Rule 21, UL 1998,

UL 16998, IEEE 1547,FCC Part 15 (Class A& B),

CAN/CSAC22.2107.1-1,Rule21 Phaes 11&111

MC4

OT Terminal connectors ( Max.185mm• )

LCD

RS485/Ethernet

Yes

10 years standard (extend to 20 years)

.69 . . 68.

PROJECT NAME. ____________________________________________________ _

LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - - -

NUMBER __________________ __

INSTALLATION AND

COMMISSIONING CHECKLIST

.S

1!

CanadianSolar

3 PHASE STRING INVERTERS

(KTL SERIES)

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Values I Notes No. Content

Installation environment

2 Unpacking

3

Mounting bracket installation

4

Inverter installation

5 Serial number

6 Solar modules

7

DC input and

AC output connection

8 PVvoltage

9 AC grid

10 Grounding cable

. 72. www.canadiansolar.com

Details

Ensure installation site meets environmental and physical constraints.

Check inverter condition after unpacking.

Install inverter mounting bracket according to installation instructions in user manual. For allowable tilt angle refer to the installation manual.

Carefully install the inverter to the mounting bracket and ensure it is irmly attached. Ensure the inverter has proper clearances and are properly ventilated.

Record the product serial numbers located on the side label.

Conirm PV module installation completion.

Record the total power of the PV modules.

Switch off the DC and AC distribution unit, connect

DC to PV terminals of inverter, and connect AC to AC terminals of inverter. Ensure proper polarity and cable size. Torque to speciications.

Measure and record DC voltage. Ensure voltage and polarities are correct. Conirm the voltages are within

5% tolerance to what was tested.

Measure and record AC voltage and frequency. Conirm the

VAc voltages are within 5% tolerance to what was tested.

Ensure ground cable is irmly attached to grounding lug.

Please return completed form to [email protected]

Conclusion

[I

Good

[I

Poor

[I

Good

[I

Poor

[ ] Completed

Record Tilt Angle in Notes

[ ] Completed

Serial Numbers; attached list

[ ] Completed

Record kWp in Notes

[ I Completed

Record Torque in Notes

[ I Completed

Record \{,c in Notes

[ ] Completed

Record Xcin Notes

[I Good [I Poor

.73 . e

<(

"'

~

C/l

.L

Cii u

PROJECT NAME. ____________________________________________________ _

LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -

NUMBER __________________ _

INSTALLATION AND

COMMISSIONING CHECKLIST

.S

1!

CanadianSolar

3 PHASE STRING INVERTERS

(KTL SERIES)

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Values I Notes Conclusion No. Content

Communication cable (iffunction is used)

Details

Connect the RS485 cable to the communication port.

CSI-xx-KTL-CT:

1. Switch on the DC switch irst. The LCD and "Power" LED indicator will be green lighted. The "Run" LED will be off.

The "Grid" LED will be lashing. The "Fault" LED will be lashing and the inverter begins self-checking. Initially,

"GridV.Outlimit" and "GridF.Outlimit" will be displayed, then the inverter will switch to "Standby" mode.

2. Switch on the AC switch. The Grid faults will clear automatically. In "Standby" mode, the "Power" LED is solid green, the "Run" LED is off, the "Grid" LED is solid green and the "Fault" LED is off.

2

Supply DC I

AC power

CSI-xx-KTL-GS:

1. Switch the grid supply main Switch (AC) ON irst.

2. Switch the DC switch ON. If the voltages of PV arrays are higher than start up voltage, the inverter will turn on. The red LED power will be continuously lit.

3. When both the DC and the AC sides supply to the inverter, it will be ready to generate power. Initially, the inverter will check both its internal parameters and the parameters of the AC grid, to ensure that they are within the acceptable limits. At the same time, the green

LED will lash and the LCD displays the information of INITIALIZING .

[ ] Completed

[ ] Completed

Record LEOs status in Notes

[ ] Completed

Record LEOs status in Notes

. 74. www.canadiansolar.com Please return completed form to [email protected]

.75.

PROJECT NAME. ____________________________________________________ _

LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -

NUMBER __________________ _

INSTALLATION AND

COMMISSIONING CHECKLIST

.S

1!

CanadianSolar

3 PHASE STRING INVERTERS

(KTL SERIES)

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Values I Notes Conclusion No. Content

3 Waiting time

Details

CSI-xx-KTL-CT: A standard 5 minute delay is required before the inverter generates any power to the grid.

In normal operation mode, the "Power", "Run", and

"Grid" LEOs are solid green and the" Fault" LED is off.

CSI-xx-KTL-GS:After 30-180 seconds (depending on local requirement), the inverter will start to generate power.

The green LED will be on continuously and the LCD displays the information of GENERATING.

4 Power generation After grid connection, record power output of inverter.

5

Date & Time setting

6

Communication setting (if avail.)

7 Machine version

8

9

10

Operating parameter

Testing

Completion

Set the current date and time using the front panel interface.

Set communication with a unique address for each inverter.

For maintenance and reference, please record the irmware revisions if applicable.

Record operating parameters of the inverter.

Verify IEEE1547 or UL 1741 setting is selected.

De-rate inverter and attach de-rate sticker as required.

Open and close the DC breaker to conirm whether the inverter reboots and shuts down automatically.

Installation and commissioning is complete if no abnormality.

.76. www.canadiansolar.com Please return completed form to [email protected]

[ ] Completed

Record LEOs status in Notes

[ ] Completed

Record LEOs status in Notes

[ ] Completed

Record power in Notes

[ ] Completed

Record current date/time in Notes

[ ] Completed

Record address in Notes

[ ] Completed

Record with serial numbers

[ ] Completed

Record operating parameters in Notes

[ ] Reboot successful

[ ] Not rebooting

[I Good

[ ]Issues detected

.77.

PROJECT NAME. ____________________________________________________ _

LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -

NUMBER __________________ _

INSTALLATION AND

COMMISSIONING CHECKLIST

System Owner: ____________________________________________________________ __

.S

1!

CanadianSolar

3 PHASE STRING INVERTERS

(KTL SERIES)

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Address I Location:

Inverter model:

Note site typical arrangements and variances

Inverter irmware revision: DSP:

LCD:. __________________________ ___

Number of inverters: Inverter mounting tilt:

Output power*: Input DC voltage: -------------------------Insulation limit (K): PV start-up voltage:

Grid: V Max: ________ V Min: ______ __ Frequency Max: ________ Min: ______________ __ Reactive compensation: _________________ +1- PF

---------------------

Coniguration: MPPT Individual MPPT Parallel __________________________ _

Monitoring: RS485:

Ethernet: -------------------------------

Monitoring equipment and supplier:

PV module manufacturer:

PV model: -------------------------------

DC cable size: ------------------AC cable size: ------------------------------

Number of series connected modules in PV strings:

Transformer ratings, supplier:

Number of PV strings in parallel per MPPT:

Total System size (DC Watts): -------------------------------------------------

*Specify de-rated power and add nameplate power in parenthesis

GENERAL COMMENTS I OBSERVATIONS:

.78. www.canadiansolar.com

.79.

Please return completed form to [email protected]

PROJECT NAME. ____________________________________________________ _

LOCATION

NUMBER __________________ __

INSTALLATION AND

COMMISSIONING CHECKLIST

.S

1!

CanadianSolar

3 PHASE STRING INVERTERS

(KTL SERIES)

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Inverter serial numbers:

8

9

6

7

10

4

5

2

3

11 ·--------------------------------------------------------------------------·

12 ·--------------------------------------------------------------------------·

13

14

15

16

17 ·--------------------------------------------------------------------------·

18

19

20

22

23

24

25

26

27

28

29

30

37

38

39

31 ·--------------------------------------------------------------------------·

32

33

34

35

36

40

21 ·--------------------------------------------------------------------------·

41 ·--------------------------------------------------------------------------·

42

INSTALLER'S NAME

INSTALLER'S SIGNATURE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -

. 80. www.canadiansolar.com

COMPANY ____________________________________________________ ___

DATE ____________________________________________________________ ___

Please return completed form to [email protected]

.81 .

advertisement

Related manuals

Download PDF

advertisement