advertisement
![Canadian Solar CSI Series Installation And Operation Manual | Manualzz Canadian Solar CSI Series Installation And Operation Manual | Manualzz](http://s2.manualzz.com/store/data/065152584_1-069ce5b11f53475f04ca664a6e3c4ca3-360x466.png)
CANADIAN SOLAR INC.
Global Headquarters:
545 Speedvale Avenue, West Guelph, Ontario N1 K 1 E6, Canada
Tel: +1 519 837 1881
Sales Inquiries Email: [email protected]
Technical Inquiries Email: [email protected]
CANADIAN SOLAR (USA), INC.
North America Headquarters:
3000 Oak Road, Ste 400, Walnut Creek, CA 94596
Tel: +1 888 998 7739
Sales Inquiries Email: [email protected]
Technical Inquiries Email: [email protected]
This manual is subject to change without prior notification. Copyright is reserved. Duplication of any part of this issue is prohibited without written permission.
Please adhere to the actual products in case of any discrepancies in this user manual.
$ ~
CanadianSolar
CSI Three Phase Inverter
(125kW)
Installation and Operation Manual
For U.S.
Ver 1.2
CANADIAN SOLAR INC.
~ ~
CanadianSolar
~ ~
CanadianSolar
Important notes
• Product specifications are subject to change without notice. Every attempt has been made to make this document complete, accurate and up-to-date. Individuals reviewing this document and installers or service personnel are cautioned, however, that Canadian Solar reserves the right to make changes without notice and shall not be responsible for any damages, including indirect, incidental or consequential damages caused by reliance on the material presented including, but not limited to, omissions, typographical errors, arithmetical errors or listing errors in the material provided in this document.
• Canadian Solar accepts no liability for customers' failure to comply with the instructions for correct installation and will not be held responsible for upstream or downstream systems Canadian Solar equipment has supplied.
• The customer is fully liable for any modifications made to the system; therefore, any hardware or software modification, manipulation, or alteration not expressly approved by the manufacturer shall result in the immediate cancellation of the warranty.
• Given the countless possible system configurations and installation environments, it is essential to verify adherence to the following:
• There is sufficient space suitable for housing the equipment.
• Airborne noise produced depending on the environment.
• Potential flammability hazards.
• Canadian Solar will not be held liable for defects or malfunctions arising from:
• Improper use of the equipment.
• Deterioration resulting from transportation or particular environmental conditions.
• Performing maintenance incorrectly or not at all.
• Tampering or unsafe repairs.
• Use or installation by unqualified persons.
• This product contains lethal voltages and should be installed by qualified electrical or service personnel having experience with lethal voltages.
Contents
~ ~
CanadianSolar
1. Introduction ···························································································································································· 4
1.1 Product Description ····················································································································· 4
1.2 Unpacking and storage ············································································································ 5
1.2.1 Storage ······························································································································ 6
2. Safety instructions ······································································································································· 7
2.1 Safety symbols ······························································································································ 7
2.2 General safety instructions ··································································································· 7
2.3 Notice for use ································································································································· 8
2.4 Protection Circuitry and Controls····························································································· 8
3. Installation ····························································································································································10
3.1 Environmental considerations ····························································································· 10
3.1.1 Select a location for the inverter ········································································ 10
3.1.2 Other environmental considerations ............................................................... 11
3.2 Product handling ························································································································ 12
3.3 Mounting the Inverter ··············································································································· 13
3.3.1 Wall mounting ··············································································································· 14
3.3.2 Rack mounting ······································································································ 15
3.4 Electrical Connections ··············································································································· 17
3.4.1 Grounding ··············································································································· 18
3.4.2 Connect PV side of inverter ···················································································· 20
3.4.3 Connect grid side of inverter ················································································· 23
4. Communication & Monitoring ············································································································ 26
4.1 RS485 and Ethernet communication connection ...................................................... 26
4.1.1 RS485 communication ································································································ 26
4.1.2 Ethernet communication ····························································································· 29
5. Commissioning ················································································································································ 30
5.1 Selecting the appropriate grid standard ········································································ 30
5.1.1 Verifying grid standard for country of installation ···································· 30
5.2 Changing the grid standard ··································································································· 30
5.2.1 Procedure to set the grid standard .................................................................. 30
5.3 Setting a custom grid standard ·························································································· 31
5.4 Preliminary checks ····················································································································· 32
5.4.1 DC Connections ············································································································ 32
5.4.2AC Connections ············································································································ 32
5.4.3 DC configuration ········································································································· 32
5.4.4AC configuration ······································································································ 34
6. Normal operation ······································································································································· 35
6.1 Start-up procedure .................................................................................................................. 35
6.2 Shutdown procedure ·················································································································· 35
6.3 Main Menu ······································································································································· 36
6.4 Information ······································································································································· 36
6.4.1 Lock screen
......................................................................................................... 38
~ ~
CanadianSolar
Contents
6.5 Settings ················································································································································ 38
6.5.1 Set Time ·················································································································· 38
6.5.2 Set Address ·················································································································· 38
6.6 Advanced Info- Technicians Only ······················································································· 39
6.6.1 Alarm Message ·················································································································· 39
6.6.2 Running Message ········································································································· 39
6.6.3 Version ································································································································· 40
6.6.4 Daily Energy ························································································································ 40
6.6.5 Monthly Energy ·················································································································· 40
6.6.6 Yearly Energy ····················································································································· 41
6.6.7 Daily Records ····················································································································· 41
6.6.8 Communication Data ··································································································· 41
6.6.9 Warning Message ············································································································ 41
6.7 Advanced Settings- Technicians Only ·············································································· 42
6.7.1 Selecting Standard ······································································································ 42
6.7.2 Grid ON/OFF ·················································································································· 44
6.7.3 Clear Energy ··················································································································44
6.7.4 Reset Password ·················································································································· 44
6.7.5 Power control ·················································································································· 45
6.7.6 Calibrate Energy·················································································································· 45
6.7.7 Special Settings ·················································································································· 45
6.7.8 STD Mode settings ········································································································· 46
6.7.9 Restore Settings ···············································································································57
6.7.10HMIUpdate ·····················································································································57
6.7.11 ExternaiEPMSet ·········································································································57
6.7.12RestartHMI ··················································································································58
6.7.13 Debug Parameter ·········································································································58
6.7.14 Fan Test ······························································································································58
6.7.15DSPUpdate ··················································································································59
6.7.16 Compensation Set ······································································································59
6.7.171/VCurve ···························································································································60
7. Maintenance ························································································································································· 61
7.1 Anti-PID Function ······························································································································ 61
7.2 Fan Maintenance ······························································································································ 62
7.3 Fuse Maintenance ··························································································································· 63
7.4 Surge Protection Device Maintenance ·············································································· 64
8. Troubleshooting ················································································································································ 65
8.1 Current Alarm ···································································································································· 65
8.2Aiarm History ···································································································································· 65
8.3 Error Messages ······························································································································ 65
9. Specifications ······················································································································································ 69
10. Appendices ························································································································································· 70
11. Installation and commissioning checklist ····································································· 72
1. Introduction ~ ~
CanadianSolar
1.2.1 Storage
If the inverter is not installed immediately, storage instructions and environmental conditions are below:
• Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the box.
• Store the inverter in a clean and dry place, free of dust and dirt. The storage temperature must be between -40 and 158 F (-40- 70C) and humidity should be between 0 to 100%, non-condensing.
• Do not stack more than two (2) inverters high on a single pallet. Do not stack more than 2 pallets high.
• Keep the box{es) away from corrosive materials to avoid damage to the inverter enclosure.
• Inspect the packaging regularly. If packing is damaged {wet, pest damages, etc.), repackage the inverter immediately.
• Store inverters on a flat, hard surface -- not inclined or upside down.
• After 100 days of storage, the inverter and carton must be inspected for physical damage before installing. If stored for more than 1 year, the inverter needs to be fully examined and tested by qualified service or electrical personnel before using.
• Restarting after a long period of non-use requires the equipment be inspected and, in some cases, the removal of oxidation and dust that has settled inside the equipment will be required.
~ ~
canadianSolar
2.
Safety Instructions
Improper use may result in electric shock hazards or burns. This product manual contains important instructions that are required to be followed during installation and maintenance.
Please read these instructions carefully before use and keep them in an easily locatable place for future reference.
2.1 Safety symbols
Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed below:
WARNING
Symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.
NOTE
Symbol indicates important safety instructions, which if not correctly followed, could result in damage to or the destruction of the inverter.
CAUTION, RISK OF ELECTRIC SHOCK
Symbol indicates important safety instructions, which if not correctly followed, could result in electric shock
CAUTION, HOT SURFACE
Symbol indicates safety instructions, which if not correctly followed, could result in burns.
2.2 General safety instructions
WARNING
Do not connect PVarray positive{+) or negative{-) to ground- doing so could cause serious damage to the inverter.
WARNING
Electrical installations must be done in accordance with local and national electrical safety standards.
WARNING
To reduce the risk of fire, branch circuit over-current protective devices {OCPD) are required for circuits connected to the Inverter.
CAUTION
The PV array {solar panels) supplies a DC voltage when exposed to light.
.7. .6.
DO NOT STACK
MORE 11-IAN 2 HIGH
Figure 1.3
3. Installation ~ ~
CanadianSolar
3.3.2 Rack mounting
The steps to mounted to the rack are listed below:
1. Select a location for the inverter
• With an NEMA4X protection rating,the inverter can be installed both outdoors and indoors.
• When the inverter is running, the temperature of the chassis and heat sink will be higher,
Do not install the inverter in a location that you accidentally touch.
• Do not install the inverter in a place where it is stored in a flammable or explosive material.
2. Installation angle
Please install the inverter vertically. If the inverter cannot be mounted vertically, it may be tilted backward to 15 degrees from vertical.
[ Vertical ] [ Backward ]
~ ~
CanadianSolar
3. Installation
3. Install mounting plate
1) Remove the bracket and fasteners from the packaging. Mark the position for hole, drilling according to the hole positions of the bracket.
Figure 3.11 Mark the position for hole
2) Drill the marked holes. It is recommended to apply anti-corrosive paint at the hole for corrosion protection.
Figure 3.9 Correct installation Angle
[ Inverted ]
Figure 3.12 Drill hole
®
Figure 3.10 Wrong installation Angle
®
. 14. .15 .
3. Installation ~ ~
CanadianSolar
3) Align the mounting plate with the holes, Insert the combination bolt {M1 OX40)through the mounting plate into the hole. Secure the bracket to the metal frame firmly with the supplied fastener. Torque the nut to 25.8ft-lbs {35N.m).
Figure 3.13 Construction bolt
4) Lift the inverter above the bracket and then slide down to make sure they match perfectly.
~ ~
CanadianSolar 3. Installation
3.4 Electrical Connections
Inverter design uses PV style quick-connect terminal. The top cover needn't be opened during DC electrical connection. The labels located the bottom of the inverter are described below in table 3.1. All electrical connections are suitable for local or national standard.
Parts Connection Cable size Torque
DC terminal
Ground terminal
PV strings
AC ground
12-10AWG
3-1 AWG
NA
7.4-8.9 ft-lbs
Grid terminal Grid 2-4/0AWG 7.4-14.6 ft-lbs
RS-485 terminal Communication cable 22-12AWG 0.44 ft-lbs
RJ45 terminal
COM terminal
DC surge protection device
Communication cable Network cable
Wi-Fi/Cellular stick NA
NA NA
NA
NA
NA
Table 3.1 Electrical connection symbols
The electrical connection of the inverter must follow the steps listed below:
1. Switch the Grid Supply Main Switch {AC) OFF.
2. Switch the DC Isolator OFF.
3. Connect the inverter to the grid.
4. Assemble PV connector and connect to the Inverter.
Figure 3.14 Mount the inverter
. 16. .17 .
3. Installation
3.4.3.2 Wiring procedure
~ ~
CanadianSolar
CAUTION
RISK OF ELECTRIC SHOCK. Prior to starting the wiring procedure, ensure that the three-pole circuit breaker is switched off and cannot be reconnected.
NOTE
Damage or destruction of the inverter's electronic components due to moisture and dust intrusion will occur if the enclosure opening is enlarged.
CAUTION
Risk offire if two conductors are connected to one terminal. If a connection of two conductors to a terminal is made, a fire can occur.
NEVER CONNECT MORE THAN ONE CONDUCTOR PER TERMINAL.
NOTE
Use M1 0 crimp terminals to connect to the inverter AC terminals.
The steps to assemble the AC grid terminals are listed as follows:
1) Strip the end of AC cable insulating jacket about 300mm then strip the end of each wire.
(as shown in figure 3.25)
~ ~
CanadianSolar
3. Installation
Figure 3.26 Remove the junction box cover
5) Insert the cable through the nut, sheath, and AC terminal cover. Connect the cable to the AC terminal block in turn, using a socket wrench. Tighten the screws on the terminal block.
The torque is 7.4-8.9 in-lbs (as shown in Figure 3.27).
PE
. 24.
Figure 3.25 StripAC cable
NOTE:
S2 (insulation stripping length) is 2mm-3mm longer than S1.
(OT cable terminal crimping area)
2) Strip the insulation of the wire past the cable crimping area of the OT terminal (M 10 terminal), then use a hydraulic crimp tool to crimp the terminal. The crimped portion of the terminal must be insulated with heat shrinkable tube or insulating tape.
3) Leave theAC breaker disconnected to ensure it does not close unexpectedly.
4) Remove the 4 screws on the inverter junction box and remove the junction box cover (Figure 3.26) .
Figure 3.27 wiring
.25.
5. Commissioning ~ ~
CanadianSolar
5.1 Selecting the appropriate grid standard
5.1.1 Verifying grid standard for country of installation
Canadian Solar inverters are used worldwide and feature preset standards for operating on any grid. Although the grid standard is set at the factory, it is essential the grid standard be verified for the country of installation before commissioning.
The menu for changing the grid standard or for creating a custom standard is accessible as described in Section 6.7 and below.
WARNING
Failure to set the correct grid standard could result in improper operation of the inverter, inverter damage or the inverter not operating at all.
5.2 Changing the grid standard
5.2.1 Procedure to set the grid standard
NOTE
This operation is for service technicians only. The inverter is customized according to the local grid standard before shipping. There should be no requirement to set the standard.
NOTE
The "User-Def" function can only be used by the service engineer.
Changing the protection level must be approved by the local utility.
1 ). From the main screen on the display, select ENTER. There are 4 sub-menu options, use the UP/DOWN arrows to highlight ADVANCED SETTINGS. Press enter to select. lmi.iiufdttm1
Settings
Figure 5.1
2). The screen will show that a password is required. The default password is "001 0", press the DOWN key to move cursor, press the UP key to change the highlighted digit.
I YES=<ENT> NO=<ESC>
Password: 0000
I
Figure 5.2
. 30.
~ ~
CanadianSolar
5. Commissioning
3). Use the UP/DOWN keys to highlight the SELECT STANDARD option. Press enter to select.
~-mm~·nmnmm
Grid ON/OFF
Figure 5.3
4). Select the grid standard for the country of installation.
I
YES=<ENT> NO=<ESC>
Standard:UL-600V
I
Figure 5.4
Press the UP or DOWN key to select the standard. Press the ENTER key to confirm the setting.
Press the ESC key to cancel changes and return to the previous menu.
UL-600V, R21 P3-600, ISONE600 are available for U.S. and Canada markets.
5.3 Setting a custom grid standard
WARNING
• Failure to set the correct grid standard could result in improper operation of the inverter, inverter damage or the inverter not operating at all.
• Only certified personnel should set the grid standard.
• Only set the grid configuration that is approved by your location and national grid standards.
1 ). Please refer to section 6.7 "Advanced Settings" for procedures to create a custom grid configuration for User-Def menu option.
.31 .
5. Commissioning ~ ~
CanadianSolar
5.4 Preliminary checks
WARNING
High Voltage.
AC and DC measurements should be made only by qualified personnel.
5.4.1 DC Connections
Verify DC connections.
1 ). Lightly tug on each DC cable to ensure it is fully captured in the terminal.
2). Visually check for any stray strands that may not be inserted in the terminal.
3). Check to ensure the terminal screws are the correct torque.
5.4.2 AC Connections
Verify AC connections.
1 ). Lightly tug on each AC cable to ensure it is fully captured in the terminal.
2). Visually check for any stray strands that may not be inserted in the terminal.
3). Check to ensure the terminal screws are the correct torque.
5.4.3 DC configuration
Verify DC configuration by noting the number of panels in a string and the string voltage.
5.4.3.1 VOC and Polarity
Measure VOC, and check string polarity. Ensure both are correct and VOC is in specification.
5.4.3.1.1 Check string voltage
To measure the open circuit voltage (VOC) and polarity of the individual strings, perform the following steps:
WARNING
When the fuse holders are closed, parallel strings on the same MPPT are connected together. If there is a voltage difference between the parallel strings such as different string lengths, current will flow between the parallel strings. Opening and closing the fuse holder in this instance is the same as opening and closing under load. Damage to equipment and /or injury to personnel may occur.
. 32.
1 ). Ensure that all fuse holders are open.
2). Connect the positive lead of the meter to the positive string cable of the string under test. Connect the negative lead of the meter to the negative string cable of the string under test.
~ ~
CanadianSolar 5. Commissioning
3). Measure the voltage present between the positive and negative wires of each string.
If the open circuit voltage of the string is near the maximum value accepted by the inverter, verify the string length. Low ambient temperatures cause an increase in the string voltage causing potential damage to the inverter.
4 ). Check the polarity of the string. All digital meters have a negative ("-")indicator that indicates when a voltage is negative; in this case a string connected in reverse polarity.
WARNING
Input voltages higher than the maximum value accepted by the inverter
(see "Specifications" in Section 9) may damage the inverter.
Although Canadian Solar inverters feature reverse polarity protection, prolonged connection in reverse polarity may damage these protection circuits and/or the inverter.
5.4.3.2 Leakage to ground
Measure leakage to ground to check for a DC ground fault.
5.4.3.2.1 Detection of leakage to ground
Canadian Solar inverters are transformer-less and do not have an array connection to ground.
Any measurement of a fixed voltage between ground and either the positive or negative string wiring indicates a leakage (ground fault) to ground and must be corrected prior to energizing the inverter or damage to the inverter may result.
To measure leakage to ground, perform the following steps:
1 ). Ensure that all fuse holders are open.
2). Ensure that neither negative nor positive DC conductors are connected to the ground strip.
3). Measure each string positive connection to ground.
4). Measure each string negative connection to ground.
5). Verify the voltage is "floating", not a consistent voltage to ground. Make sure you notice the units of the measurement. mV is not the same as V.
6). Do not close the fuse holder and connect the strings if a leakage to ground has been detected. Improper operation and damage to the inverter may result.
Once all DC tests have been completed, close the fuse holders.
.33 .
5. Commissioning ~ ~
CanadianSolar
5.4.4 AC configuration
Verify AC configuration.
5.4.4.1 Measure VAC and frequency
Measure VAC and verify voltage is within local grid standards.
1 ). Measure each phase to ground (L-G).
2). Measure phases to the other phases in pairs (L-L). PH A to PH B, PH B to PH C and
PH Cto PHA.
3). If the meter is equipped, measure the frequency of each phase to ground.
4 ). Ensure each measurement is within local grid standards and the inverter specifications as noted in Section 9 "Specifications".
5.4.4.2 Phase rotation test
A phase rotation test is recommended to ensure the phases have been connected in the appropriate order. Canadian Solar inverters do not require a specific phase rotation connection.
However, the local utility may require a specific phase rotation or a record of the phase configuration of the installation.
~ ~
CanadianSolar
6. Normal operation
6.1 Start-up procedure
To start-up the inverter, it is mandatory that the steps below are followed in the exact order outlined.
1 ). Ensure the commissioning checks in Section 5 have been performed.
2). Switch theAC switch ON.
3). Switch the DC switch ON. If the PV array (DC) voltage is higher than the inverter's start-up voltage, the inverter will turn on. The red DC POWER LED and LCD will be continuously lit.
4 ). Canadian Solar inverters are powered from the DC side. When the inverter detects DC power that is within start-up and operating ranges, the inverter will turn on. After turnon, the inverter will check internal parameters, sense and monitor AC voltage, hertz rate and the stability of the supply grid. During this period, the green OPERATION LED will flash and the LCD screen will show INITIALIZING. This tells the operator that the inverter is preparing to generate AC power.
5). After the locally mandated delay (300 seconds for IEEE-1547 compliant inverters), the inverter will start generating AC power. The green OPERATION LED will light continuously and the LCD screen will show GENERATING.
CAUTION
The inverter's surface temperature can reach up to 75•c (167° F). To avoid risk of burns, do not touch the surface when the inverter is in the operational mode. Additionally, the inverter must be installed out of the reach of children.
6.2
Shutdown procedure
To stop the inverter, it is mandatory that the steps below are followed in the exact order outlined.
1 ). Switch AC switch OFF.
2). Wait approximately 30 seconds (during this time, theAC side capacitors are dissipating energy). If the inverter has DC voltage above the start-up threshold, the red POWER
LED will be lit. Switch the DC switch OFF.
3). Confirm all LED's switch OFF (-one (1) minute).
CAUTION
Although the inverter DC disconnect switch is in the OFF position and all the LED's are OFF, operators must wait five (5) minutes after the DC power source has been disconnected before opening the inverter cabinet. DC side capacitors can take up to five (5) minutes to dissipate all stored energy .
. 35 . . 34.
6. Normal operation ~ ~
CanadianSolar
In normal operation, LCD screen alternatively shows inverter power and operation status
(see Figure 6.1 ). The screen can be scrolled manually by pressing the UP/DOWN keys.
Pressing the ENTER key gives access to Main Menu.
5sec
Status: Generating
01-01-2019 12:04
Pressing th r
ENTERkey gives access to the main menu.
Figure 6.1 Operation Overview
6.3 Main Menu
There are four submenus in the Main Menu (see Figure 6.1 ):
1. Information
2. Settings
3. Advanced Info.
4. Advanced Settings
6.4 Information
The Canadian Solar three Phase Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
. 36.
~ ~
CanadianSolar
6. Normal operation
I
I
Display
VPV Total: 1000.0V
IPV_Total: +99.0A
VA: 345.7V
1_-A: 109.0A
V C: 345.0V
1_-C: 109.8A
Status: Generating
Power: 1488W
I
I
Duration
10 sec
Description
VPV _Total: Shows input voltage total.
IPV _Total: Shows input current total.
10 sec
10 sec
10 sec
V _A: Shows the grid's voltage value.
I_A: Shows the grid's current value.
V _ C: Shows the grid's voltage value.
I_C: Shows the grid's current value.
Status: Shows instant status of the Inverter.
Power: Shows instant output power value.
Rea Power: OOOVar
App -Power: VA
10 sec
Rea_Power: Shows the reactive power ofthe inverter.
App_Power: Shows the apparent power of the inverter.
Grid Frequency
F_Grid 50.06Hz
10 sec F _Grid: Shows the grid's frequency value.
Total Energy
0258458 kwh
This Month: 0123kwh
Last Month: 0123kwh
Today: 15.1kwh
Yesterday: 13.5kwh
Inverter SN
00000000000000
Work Mode: Volt-watt
DRM N0.:08
I_DC01: +05.0A
I_DC20: +05.2A
10 sec Total generated energy value.
10 sec
10 sec
This Month: Total energy generated this month.
Last Month: Total energy generated last month.
Today: Total energy generated today.
Yesterday: Total energy generated yesterday.
10 sec Display series number of the inverter.
10 sec
10 sec
Work Mode: Shows current working mode.
DRM NO.: Shows DRM Number.
I _DC01 :Shows input 01 current value.
I _DC02 :Shows input 02 current value.
...
I_DC20: Shows input 20 current value.
Table 6.1 Information list
.37 .
6. Normal operation ~ ~
CanadianSolar
6.4.1 Lock Screen
Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks
(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen. a
(a)
-":Ill
II:.-
(b)
Figure 6.2 Locks and Unlocks the Screen of LCD
6.5 Settings
The following submenus are displayed when the Settings menu is selected:
1.SetTime
2.Set Address
6.5.1 Set Time
This function allows time and date setting. When this function is selected, the LCD will display a screen as shown in Figure 6.3.
I NEXT=<ENT> OK=<ESC>I o1-o1-2019 16:37 1
Figure 6.3 Set Time
Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one digit to the next (from left to right). Press the ESC key to save the settings and return to the previous menu.
6.5.2 SetAddress
This function is used to set the address when muti inverters are connected to three monitor.
The address number can be assigned from "01 "to "99"(see Figure 6.4). The default address number of Canadian Solar Three Phase Inverter is "01 ".
I
YES=<ENT> NO=< ESC>
Set Address: 01
I
Figure 6.4 Set Address
Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.
Press the ESC key to cancel the change and return to the previous menu.
. 38.
~ ~
CanadianSolar 6. Normal operation
6.6Advanced Info- Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Enter menu "Advanced Info." and "Advanced settings" Cneed password) .
Select "Advanced Info." from the Main Menu. The screen will require the password as below:
YES=<ENT>NO=<ESC>
Password :0000
Figure 6.5 Enter password
After enter the correct password the Main Menu will display a screen and be able to access to the following information.
1.Aiarm Message
2. Running message
3.Version
4. Daily Energy
5. Monthly Energy
6. Yearly Energy
7. Daily Records
&.Communication Data
9. Warning Message
The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.
6.6.1 Alarm Message
The display shows the 100 latest alarm messages (see Figure 6.6). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.
AlmOOO: OV-G-V
T:00-00 00:00 D:OOOO
Figure 6.6Aiarm Message
6.6.2 Running Message
This function is for maintaince person to get running message such as internal temperature,
Standard No.1 ,2,etc.
Screens can be scrolled manually by pressing the UP/DOWN keys.
.39 .
6. Normal operation ~ ~
CanadianSolar
6.6.3 Version
The screen shows the model version of the inverter. And the screen will show the software ver by pressing the UP and DOWN at the same time.( see Figure 6. 7).
Model: 08
Software Version: D20001
Figure 6. 7 Model Version and Software Version
6.6.4 Daily Energy
The function is for checking the energy generation for selected day.
YES=<ENT> NO=<ESC>
Select: 2019-01 -(!1]
Figure 6.8 Select date for daily energy
Press DOWN key to move the cursor to day, month and year, press UP key to change the digit.
Press Enter after the date is fixed.
I
2019-01-01: 051.3kWh
2019-01-01: 061.5kWh
I
Figure 6.9 Daily energy
Press UP/DOWN key to move one date from another.
6.6.5 Monthly Energy
The function is for checking the energy generation for selected month.
I YES=<ENT> NO=<ESC>
Select: 2019till
I
Figure 6.10 Select month for monthly energy
Press DOWN key to move the cursor to day and month, press UP key to change the digit.
Press Enter after the date is fixed.
2019-01: 051 OkWh
2019-01: 061 OkWh
Figure 6.11 Month energy
Press UP/DOWN key to move one date from another .
.40.
~ ~
CanadianSolar 6. Normal operation
6.6.6 Yearly Energy
The function is for checking the energy generation for selected year.
I
YES=<ENT> NO=< ESC>
Select: 20 IE
I
Figure 6.12 Select year for yearly energy
Press DOWN key to move the cursor to day and year, press UP key to change the digit.
Press Enter after the date is fixed.
I
2018:0017513kWh
2017:0165879kWh
Figure 6.13 Yearly energy
I
Press UP/DOWN key to move one date from another.
6.6. 7 Daily Records
The screen shows history of changing settings. Only for maintance personel.
6.6.8 Communication Data
The screen shows the internal data of the Inverter (see Figure 6.14), which is for service technicians only.
01-05:01 25 E4 9DAA
06-10: C2 85 E4 9D 55
Figure 6.14 Communication Data
6.6.9 Warning Message
The display shows the 100 latest warn messages (see Figure 6.15). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.
I
MsgOOO:
T:00-00 00:00 D:OOOO
I
Figure 6.15 Warning Message
.41.
6. Normal operation ~ ~
CanadianSolar
6. 7 Advanced Settings- Technicians Only
NOTE:
To access to this area is for fully qualified and accredited technicians only.
Please follow 6.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard
2. Grid ON/OFF
3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9. Restore Settings
10. HMI Update
11. External EPM set
12. Restart HMI
13. Debug Parameter
14.DSP Update
15.Compensation Set
16.1/VCurve
6. 7.1 Selecting Standard
This function is used to select the grid's reference standard (see Figure 6.16).
I
YES=<ENT> NO=<ESC>
Standard:UL-600V
I
Figure 6.16
Selecting the "User-Def" menu will access to the following submenu (see Figure 6.17),
I
-
OV-G-V1: 400V
I
OV-G-V1-T: 1.0S
Figure 6.17
Below is the setting range for "User-Def". Using this function, the limits can be changed manually. (These voltage values are the phase voltage)
.42.
~ ~
CanadianSolar 6. Normal operation
OV-G-V1: 300---480V
OV-G-V1-T: 0.0 1---9S
OV-G-V2: 300---490V
OV-G-V2-T: 0.01---1S
UN-G-V1: 173---336V
UN-G-V1-T: 0.01---9S
UN-G-V2: 132---319V
UN-G-V2-T: 0.01---1S
Startup-T: 1 0-600S
OV-G-F1: 50.2-63Hz
OV-G-F1-T: 0.01---9S
OV-G-F2: 51-63Hz
OV-G-F2-T: 0.01---9S
UN-G-F1: 47-59.5Hz
UN-G-F1-T: 0.01---9S
UN-G-F2: 47-59Hz
UN-G-F2-T: 0.01---9S
Restore-T: 1 0-600S
Table 6.2 Setting ranges for User-Def (L-N)
NOTE
The initial value of the User-Def standard is for reference only. It does not represent a correct value suitable for use.
Setting value
Vup-Limit1
Time1
Vup-Limit2
Time2
Vdw-Limit1
Time1
Vdw-Limit2
Time2
Fup-Limit1
Time1
Fup-Limit2
Time2
Fdw-Limit1
Time1
Fdw-Limit2
Time2
600V Rated (L-L) 600V Rated (L-N)
660<V<720
1S
V~720
381<V<415
1S
V~415
0.16S
360~V<528
2S
0.16S
207~V<304
2S
V<360
0.16S
V<207
0.16S
60.5Hz < F <62Hz 60.5Hz < F <62Hz
2S 2S
F>62Hz
0.16S
F>62Hz
0.16S
57Hz< F < 59.5Hz 57Hz< F < 59.5Hz
2S 2S
57Hz< F
0.16S
57Hz< F
0.16S
Table 6.3 Baseline Inverter Settings
.43 .
6. Normal operation ~ ~
CanadianSolar
6.7.2 Grid ON/OFF
This function is used to start up or stop the power generation of Canadian Solar Three Phase
Inverter (see Figure 6.18).
GridON
Grid OFF
Figure 6.18 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key to save the setting. Press the ESC key to return to the previous menu.
6.7.3 Clear Energy
Clear Energy can reset the history yield of inverter
A
These two functions are applicable by maintenance personnel only, wrong
6.7.4 Reset Password
This function is used to set the new password for menu "Advanced info." and "Advanced information" (see Figure 6.19).
I
YES=<ENT> NO=<ESC>
Password: 0000
I
Figure 6.19 Set new password
Enter the right password before set new password. Press the DOWN key to move the cursor,
Press the UP key to revise the value. Press the ENTER key to execute the setting.
Press the ESC key to return to the previous menu.
~ ~
CanadianSolar 6. Normal operation
6. 7.5 Power Control
Active and reactive power can be set through power setting button.
There are 5 item for this sub menu:
1. Set output power
2. Set Reactive Power
3. Out_P With Restore
4. Rea_P With Restore
5. Select PF Curve
A
This function is applicable by maintenance personnel only, wrong operation
6. 7.6 Calibrate Energy
Maintenance or replacement could clear or cause a different value of total energy. Use this function could allow user to revise the value of total energy to the same value as before. If the monitoring website is used the data will be synchronous with this setting automatically.
(see Figure 6.20).
YES=<ENT> NO=<ESC>
Energy:OOOOOOOkWh
Figure 6.20 Calibrate energy
Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the
ENTER key to execute the setting. Press the ESC key to return to the previous menu.
6.7.7 Special Settings
A
This function is applicable by maintenance personnel only, wrong operation
.44. .45 .
6. Normal operation ~ ~
CanadianSolar
6.7.8 STD Mode Settings
£
This section is applicable to maintenance personnel only.
Selecting "STD Mode. Settings" displays the sub-menu shown below:
1. Working Mode Set
2. Power Rate Limit
3. Freq Derate Set
4. 1Om ins Voltage Set
5. Power Priority
6. Initial Settings
7. Voltage PCC Set
6. 7 .8.1 Working Mode Set
There are TWO situations with different grid standards selected.
6. 7.8.1.1 With UL Standard selected
NOTE
The following modes are for "UL-600V".
Canadian Solar inverters have Seven working modes:
1. NULL
2. Volt-watt
3. Volt-Var
4. Fixed-PF
5. Reac-power
6. Power-PF
7. VgWatt-UL
Based on UL 1741 SA, working mode 1,3,4, 7 can be used by grid operator.
~ ~
CanadianSolar 6. Normal operation
1.NULL
Description: Inverter is not under any working mode.
2. Volt-Watt (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by UL 17 41 SA Standards.
A
This function is for maintenance personnel only, wrong operation
3. Volt-Var (Default)
Description: Inverter will change the reactive output power based on voltage change.
Q1, cap
02=03=0
Q4, ind
---------
~~
------
i~
--
~~~~
-
i ....
J_
Figure 6.21 Volt-VAR curve for Q (V)
Default Settings for UL 1741 SA:
Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%
Rated 600V Grid
V1 :(277-346V) Default 303V V2: (277-346V) Default 340V
V3:(346-415V) Default 349V V4: (346-415V) Default 381V
Voltage1 : 303V
I Voltage2: 340V
Figure 6.22 Volt-VAR
I
.46. .47 .
6. Normal operation ~ ~
CanadianSolar
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1 under-excited
Q/Po under-excited
YES=<ENT> NO=<ESC>
Power Factor:+1. 00
Figure 6.23 Fixed-PF
!
1.0 P/Po
·-..
.. ____
Ill over-excited
----
---
IV over-excited
Figure 6.24 PF Range
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL 1741 SA Standards.
A
This function is for maintenance personnel only, wrong operation
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL 1741 SA Standards.
A
This function is for maintenance personnel only, wrong operation
~ ~
CanadianSolar 6. Normal operation
7.VgWatt-UL
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for UL 1741 SA Standards.
100% of
Input
Power
0
Vmin Vnom Vstart
Figure 6.25 Volt-Watt characteristic
Vstop
ACVolt
Vmax
Default Settings for UL 1741 SA:
Rated 600V Grid
V1 :less than V2
V2:1ess than Vstart
V3 (Vstart): (346-415V) Default381V
V4 (Vstop): (381-450V) Default415V
P1:100% P2:100% P3: 100% P4:0%
I
Voltage1 : 318V
P-Limit1: 100%
Figure 6.26 VgWatt-UL
I
.48. .49.
6. Normal operation ~ ~
CanadianSolar
6. 7 .8.1.2 With Rule21 Standard selected
NOTE
The following modes are for "R21 P3-600".
Canadian Solar inverters have Ten working modes:
1. NULL
2. Volt-watt
3. Volt-Var
4. Fixed-PF
5. Reac-power
6. Power-PF
7. VgWatt-UL
Based on Rule21, working mode 1 ,2,3,4 can be used by grid operator.
NOTE
The other three working mode"P1-V-Watt", "P1-V-Var" and
"P1-V-P&V-Q" are NOT applicable for settings.
1.NULL (Mode Reset)
Description: Inverter is not under any working mode.
2. Volt-Watt
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for Rule21 Standards.
Full Power Production Real Power
Capabilities Zone Reduction Zone
100% r---------------~~
Active Power as%of
Nameplate
50%
No Real Power
Production Zone
11 0% % Voltage 0% 106% 108%
Figure 6.27 Volt-Watt characteristic
. 50.
~ ~
CanadianSolar 6. Normal operation
Default Settings for Rule21 Standards:
Rated 600V Grid
V1 :less than Vstart
V2 (Vstart): (346-415V) Default 367V
V3 (Vstop): (381-450V) Default 381V
V4: larger than Vstop
P1 :100% P2:100% P3: 0% P4:0%
3. Volt-Var
Description: Inverter will change the reactive output power based on voltage change.
Q1, cap
Q2=Q3=0
Q4, ind ---------
~~ i~:
-----i~ - ~n _ o _ ~ i ....
J
_ 4 ________ _
Figure 6.28 Volt-VAR curve for Q (V)
Default Settings for Rule21 Standard:
Q1: (0-60%) Default +30% Q4: (-60%-0%) Default -30%
Rated 600V Grid
V1 :(277-346V) Default 318V
V3:(346-415V) Default 357V
V2: (277-346V) Default 335V
V4: (346-415V) Default 370V
I
Voltage1 : 318V
Voltage2: 335V
Figure 6.29 Volt-VAR
I
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF
=
1
.51 .
6. Normal operation ~ ~
CanadianSolar under-excited
Q/Pn under-excited
YES=<ENT>NO=<ESC>
Power Factor: +1. 00
Figure 6.30 Fixed-PF f 1,0 P/Pn
~--
Ill over-excited
-----
___
..
---
IV over-excited
Figure 6.31 PF Range
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
A
This function is for maintenance personnel only, wrong operation
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
A
This function is for maintenance personnel only, wrong operation
7.VgWatt-UL (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by Rule21 Standards.
A
This function is for maintenance personnel only, wrong operation
~ ~
CanadianSolar 6. Normal operation
8. Enable both Volt-Var and Volt-Watt modes
Description: Rule21 requires both Volt-var and Volt-watt modes can be enabled.
To set both modes (Volt-var in high priority)
Step 1: Select and set Volt-watt mode at first.
Step 2: Enter "Working Mode" again and select and set Volt-var mode then.
Step 3: To check the priority, a new mode will appear as "V-Q & V-P" which indicates (Q) Volt-var is in high priority.
YES=<ENT> NO=<ESC>
Work Mode : V-Q & V-P
Figure 6.32 Work Mode
To set both modes (Volt-watt in high priority)
Step 1: Select and set Volt-var mode at first.
Step 2: Enter "Working Mode" again and select and set Volt-watt mode then.
Step 3: To check the priority, a new mode will appear as "V-P & V-Q" which indicates (P) Volt-watt is in high priority.
YES=<ENT> NO=<ESC>
Work Mode : V-P & V-Q
Figure 6.33 Work Mode
To reset dual-mode or exit the dual-mode situation
Step 1: Select "Null" mode at first.
Step 2: Enter "Working Mode" again. Redo above dual-mode setting steps to reset OR set other modes to exit dual-mode situation.
NOTE
To check the Volt-watt and Volt-var priority, simply enter the working modes.
V-Q&V-P indicates Volt-Var First V-P&V-Q indicates Volt-Watt First
. 52. .53.
6. Normal operation ~ ~
CanadianSolar
6. 7 .8.2 Power Rate Limit
This function is used for change Power Ramp-up rate. When inverter start up or input string
MPPT changes, inverter power ramp-up rate is limited in this menu.
The default setting is stop (disable).
The setting range from 10% to 600%, means inverter power change rate per minute.
Values are not allowed to change. If they are set, they may not conform to the UL 1741 SA standard.
I
Power Rate:016%
RateP _Sts-US:STOP
Figure 6.34 Power Rate Limit
I
6.7.8.3 Freq Derate Set
This setting is applicable when UL Standards are selected.
There are 5 derate modes in this menu. When operating under standard UL-17411imits, modes 00 to 03 are disabled. Mode 04 is used for UL 1741 SA frequency derating setting.
Mode 08 is used for RULE21 Freq-watt setting. This sets the f start and f stop point.
Mode 04:
I
Derate Mode: 04
OV-F-Start: 60. 20Hz
Figure 6.35 Freq Derate Set
I
. 54.
100% of
Available
Power
~ ,;d
F'eq"e"cy o L----------------r-----------r----------~--------~ f min f nom f start f stop f max
Figure 6.36 Freq-Watt characteristic
Over frequency load shedding Fstart range 60-62Hz, default setting 60.2Hz
Fstop can set the scope: 61-64Hz, the default setting 62Hz.
Press the Enter key to select the mode or frequency.
Press Up/Down to set. Press ESC to save the settings .
~ ~
CanadianSolar 6. Normal operation
Mode 08:
This setting is used to control real power based on the frequency excursion
This setting is applicable when Rule21 Standards are selected.
1
-
Start Freq: 60.50Hz
WGradient: 040%
Figure 6.37 Freq-Watt (1)
I
Start Freq: This is the frequency that active power reduction starts.
WGradient: This is the active power reduction rate in terms ofthe frequency.
Stop Freq: This is the frequency that stops the correction cycle.
Hysteresis: This indicates whether hysteresis is enabled.
Reduced
Power f stop f start
~
·;·"'
Hysteresis
Figure 6.38 Freq-Watt (2) f
This function is for maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
.55.
6. Normal operation ~ ~
CanadianSolar
6.7.8.4 1Om ins Voltage Set
This function is disabled and not used for the US.
A
This function is for maintenance personnel only, wrong operation
6. 7 .8.5 Power Priority
This setting is used to set the priority between Active Power Control (Watt) and
Reactive Power Control (Var).
I
YES=<ENT> NO=<ESC>
Select: Var First
I
Figure 6.39 Power Priority
Two options are available: Watt First and Var First.
A
This function is for maintenance personnel only, wrong operation
6.7.8.61nitial Settings
In initial settings it will reset each work mode from 6.5.8.1 to 6.5.8.4 back to default.
I
Work Mode Default
Power Rate Default
Figure 6.40 Initial Settings
I
6. 7 .8. 7 Voltage PCC Set
Set the voltage at the PCC point.
This setting is required by RULE 21 requirements.
PCC: Point of Common Coupling, the point where a Local EPS is connected to an Area EPS.
A
This function is for maintenance personnel only, wrong operation
~ ~
CanadianSolar 6. Normal operation
6.7.9 Restore Settings
There are 5 items in initial setting submenu.
Restore setting could set all item in 6.5.7 special setting to default.
The screen shows as below:
Are you sure? I
YES=<ENT>NO=<ESC>
I
Figure 6.41 Restore Settings
Press the Enter key to save the setting after setting grid off.
Press the ESC key to return the previous mean.
6.7.10 HMI Update
£
This section is applicable to maintenance personnel only.
Selecting "Updater" displays the sub-menu shown below:
HMI Current Ver.: 02
YES=<ENT>NO=<ESC>
Figure 6.42
Updater is for updating LCD firmware. Press the ENTER key to start the process.
Press the ESC key to return to the previous menu.
6.7.11 External EPM Set
This function is turned on when the EPM is external.
YES=<ENT> NO=<ESC>
Fail Safe Set: ON
Figure 6.43 Set the Fail Safe ON/OFF
. 56. .57.
. 58.
6. Normal operation ~ ~
CanadianSolar
6.7.12 Restart HMI
The function is used for restart the HMI.
A
This function is applicable by maintenance personnel only, wrong operation
6. 7.13 Debug Parameter
£
This section is applicable to maintenance personnel only.
Debug Parameter as shown as below:
-+S16DAT1: +0000
S16DAT2: +0000
S16DAT3: +0000
S16DAT4: +0000
S16DAT5: +0000
S16DAT6: +0000
S16DAT7: +0000
S16DAT8: +0000
Figure 6.44
Press the UP/DOWN keys to scroll through items. Press the ENTER key to select.
Press the DOWN key to scroll and press the UP key to change the value.
Press the ENTER key to save the setting. Press the ESC key to cancel. changes and return to the previous menu.
6.7.14 FANTest
£
This section is applicable to maintenance personnel only.
~ ~
CanadianSolar 6. Normal operation
Selecting "Fan Test" displays the sub-menu shown below:
I
Are you sure?
I
YES=<ENT>NO=<ESC~
Figure 6.45
Fan Test is a factory test function. Press the ENTER key to start the test.
Press the ESC key to return to the previous menu.
6. 7.15 DSP Update
The function is used for update the DSP.
A
This function is applicable by maintenance personnel only, wrong operation
6. 7.16 Compensation Set
This function is used to calibrate inverter output energy and voltage. It will not impact the energy count for inverter with RGM.
Two sections are included: Power Parameter and Voltage Parameter.
The screen shows:
YES=<ENT>NO=<ESC>
Power para: 1. 000
Figure 6.46 Power Rate Limit
Press the Down key to move the cursor.
Press the Up key to change the digit.
Please press the Enter to save the setting and press the ESC key to return to the previous menu.
A
This setting is used for grid operators, do not change this setting unless
.59.
6. Normal operation ~ ~
CanadianSolar
6.7.171/VCurve
This function is used to scan the 1/V characteristic curves of each PV strings.
1
-
Set 1/V Curve
1/V Curve Scan
Figure 6.47 1/V Curve
I
6.7.17.1 Set 1/V Curve
This setting can set the scanning voltage start point and the voltage interval.
Start_ V: 850V lntervai_V: 010V
Figure 6.48 Set 1/V Curve
Start_ V: The start voltage of the IIV scan. (Adjustable from 850V-1 OOOV)
Interval_ V: The scanning voltage intervai.(Adjustable from 001V-1 OOV)
In total, 60 data points can be scanned.
The max scanning range is from 850-1450V.
6. 7.17 .2 IIV Curve Scan
Press "ENT" to start the 1/V curve scan.
Scanning ... 01
Figure 6.49 1/V Curve Scan (1)
After it is completed, the screen will display "Scan OK" and then enter the following section.
Select String No.: 01
Figure 6.50 1/V Curve Scan (2)
I
01 850V: o2::::S60V:
9.56A
9.44A I
Figure 6.51 1/V Curve Scan (3)
.60.
~ ~
CanadianSolar 7. Maintenance
Canadian Solar Three Phase Inverter does not require any regular maintenance. However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.
CAUTION:
Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter (refer to Section
6.2) and wait for a cool-down period before before any maintenance or cleaning operation.
The LCD and the LED status indicator lights can be cleaned with a damp cloth if they are too dirty to be read.
NOTE:
Never use any solvents, abrasives or corrosive materials to clean the inverter.
7.1 Anti-PI D Function
CSI-125KTL-GS-E integrates optional Anti-PID module and it can recover the
PID effect during night thus protect the PV system from degradation.
CSI-125KTL-GS-E
Figure 7.1
The Anti-PID module repairs the PID effect of the PV model at night. When operating, the inverter LCD screen displays" PID-repairing" information, and the red light is on.
TheAnti-PID function is always ON whenAC is applied.
If maintenance is required and turn off the AC switch can disable the Anti-PID function.
WARNING:
The PID function is automatic. When the DC bus voltage is lower than 260Vdc, the PID module will start creating 650 Vdc between PV- and ground.
No need any control or settings
.61.
8. Troubleshooting ~ ~
CanadianSolar
Alarms
No Information
(Blank Screen)
• Input voltage low/missing
• Polarity reversed
• Main board damaged
Initializing
(Inverter stuck in this mode)
OV-G-V: Over
Grid Voltage
UN-G-V: Under
Grid Voltage
Cause
• Inverter is waiting for driving signal
• Inverter detects grid voltage as too high
• Inverter detects grid voltage as too low
Solution
Test- DC switch OFF
• Check PV connections
• Check polarity
• Check voltage >860V
Test- DC Switch ON
• Check voltage >860V
• If DC voltage is "0" replace inverter
Test- DC switch OFF
• Check PV connections
• Check polarity
• Check voltage >860V
Test- DC Switch ON
• Check voltage >860V
• A cable may have been damaged or loosened in shipping replace inverter
Test- DC switch OFF
• CheckAC at the inverter
• If AC measures high, adjust upper limit with permission from utility
Test- DC Switch ON, full power
• CheckAC at inverter test points
• Compare with LCD
•lfAC measures high, cables between inverter and interconnect are too small
• Check ampacity and voltage drop calculations
Test- DC switch OFF
• CheckAC at the inverter test points
• If AC measures low, adjust lower limit with permission from utility
• Check LCD voltage reading, may be a bad measurement circuit
Test- DC Switch ON
• Check grid standard
• Replace inverter
~ ~
CanadianSolar 8. Troubleshooting
Alarms
OV-G-F: Over
Grid Frequency
NO-GRID
Cause
•Inverter detects grid
Frequency as too high
• Inverter does not detect the grid
Solution
Test- DC switch OFF
• Check frequency at the inverter test points
• If Frequency measures high, adjust upper limit with permission from utility
• Check LCD reading, may be a bad measurement circuit
Test - DC Switch ON
• Check grid standard
• Replace inverter
Test- DC switch OFF
• CheckAC at the inverter test points
• L-L, L-GND
• Check LCD reading, may be a bad measurement circuit
Test - DC Switch ON
• Check grid standard
• Replace inverter
OV-DC: DC voltage is too high
OV-BUS: DC
BUS voltage is too high
UN-BUS: DC
BUS voltage is too low
•Inverter detects High DCV
•Inverter detects High
DCV on internal bus
• Inverter detects low DCV on internal bus
Test- DC switch OFF
• Check DC at the inverter test points
• If DCV is high, too many panels in the string
Test - DC Switch ON
• Check LCD reading, may be a bad measurement circuit
• Replace inverter
Test
• Measure DC and AC voltages
• Compare with LCD
• Replace Inverter
• Internal damage
• Wire came loose during shipping
Test
• Measure DC and AC voltages
• Compare with LCD
• Replace Inverter
• Internal damage
• Wire came loose during shipping
. 66. .67 .
8. Troubleshooting ~ ~
CanadianSolar
Alarms
GRID-INTF:
Grid unstable
IN I-PRO:
Initialization
Protection
Cause
• Inverter detects grid instability, internal fault current high
• Master and Slave DSP have different values
Solution
Test- With DC Switch OFF
• MeasureAC voltage
• TestAe line forTHD
• Test- With DC Switch ON
TestAe line forTHD
• Multiple inverters/turn one off
• Impedance matching adjustment or box
• Internal damage
• Wire came loose in shipping
Reset Inverter
• DC switch OFF
• Wait until alllights/LCD turn off
• DC switch ON
• Replace inverter
TEM-PRO:
Temperature
Protection
GROUND-PRO:
Ground
Protection
• Inverter detects high ambient temperature >60C
• Inverter detects low DC insulation resistance
Inspect installation
• Check heatsink for obstructions/ventilation
• Is inverter in direct sunshine
• Measure ambient temperature near inverter
• lftemp is in range replace inverter
Inspect installation
• Reset inverter
• Note weather conditions when alarm occurs
• Measure insulation resistance
• If normal, measure in SAME weather as alarm
• Physically check cables
• Replace inverter
Table 8.1 Fault messages and descriptions
~ ~
CanadianSolar
Model
Max. DC input power (Watts)
Max. DC input voltage (Volts)
Rated DC voltage (Volts)
Start-up voltage (Volts)
MPPTvoltage range (Volts)
Max. input current (Amps)
Max short circuit input current (Amps)
MPPT number/Max input strings number
Rated output power (Watts)
Max. output power (Watts)
Max. apparent output power (VA)
Rated grid voltage (Volts)
Rated output current (Amps)
Power Factor (at rated output power)
THDi (at rated output power)
Rated grid frequency (Hertz)
Max. efficiency
EU efficiency
MPPT efficiency
Dimensions (W*H*D)
Weight
Topology
Self consumption (night)
Operating ambient temperature range
Relative humidity
Ingress protection
Noise emission
Cooling concept
Max.operation altitude
Compliance
DC connection
AC connection
Display
Communication connections
OTAupdate
Warranty
9. Specifications
CSI-125KTL-GS-E
187000
1500
950
900
860 ... 1450
150
300
1120
125000
125000
125000
3/PE-600
120
0.81eading-0.81agging
<3%
60
99.1%
98.6%
99.9%
1176*713.5*315 (mm) /46.3*28.1*12.4 (inch)
84kg /185.21b
Transformerless
< 3W (without anti-PID)
-25"C ... +60"C
0-100%
NEMA4X/IP65
S55dB(A)
Fan cooling
4000m
UL 1741, UL 1741SA, Rule 21, UL 1998,
UL 16998, IEEE 1547,FCC Part 15 (Class A& B),
CAN/CSAC22.2107.1-1,Rule21 Phaes 11&111
MC4
OT Terminal connectors ( Max.185mm• )
LCD
RS485/Ethernet
Yes
10 years standard (extend to 20 years)
.69 . . 68.
PROJECT NAME. ____________________________________________________ _
LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - - -
NUMBER __________________ __
INSTALLATION AND
COMMISSIONING CHECKLIST
.S
1!
CanadianSolar
3 PHASE STRING INVERTERS
(KTL SERIES)
Warning: This checklist is not a replacement for the user manual.
Please read the user manual prior to inverter site selection and installation.
Values I Notes No. Content
Installation environment
2 Unpacking
3
Mounting bracket installation
4
Inverter installation
5 Serial number
6 Solar modules
7
DC input and
AC output connection
8 PVvoltage
9 AC grid
10 Grounding cable
. 72. www.canadiansolar.com
Details
Ensure installation site meets environmental and physical constraints.
Check inverter condition after unpacking.
Install inverter mounting bracket according to installation instructions in user manual. For allowable tilt angle refer to the installation manual.
Carefully install the inverter to the mounting bracket and ensure it is irmly attached. Ensure the inverter has proper clearances and are properly ventilated.
Record the product serial numbers located on the side label.
Conirm PV module installation completion.
Record the total power of the PV modules.
Switch off the DC and AC distribution unit, connect
DC to PV terminals of inverter, and connect AC to AC terminals of inverter. Ensure proper polarity and cable size. Torque to speciications.
Measure and record DC voltage. Ensure voltage and polarities are correct. Conirm the voltages are within
5% tolerance to what was tested.
Measure and record AC voltage and frequency. Conirm the
VAc voltages are within 5% tolerance to what was tested.
Ensure ground cable is irmly attached to grounding lug.
Please return completed form to [email protected]
Conclusion
[I
Good
[I
Poor
[I
Good
[I
Poor
[ ] Completed
Record Tilt Angle in Notes
[ ] Completed
Serial Numbers; attached list
[ ] Completed
Record kWp in Notes
[ I Completed
Record Torque in Notes
[ I Completed
Record \{,c in Notes
[ ] Completed
Record Xcin Notes
[I Good [I Poor
.73 . e
<(
"'
~
C/l
.L
Cii u
PROJECT NAME. ____________________________________________________ _
LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -
NUMBER __________________ _
INSTALLATION AND
COMMISSIONING CHECKLIST
.S
1!
CanadianSolar
3 PHASE STRING INVERTERS
(KTL SERIES)
Warning: This checklist is not a replacement for the user manual.
Please read the user manual prior to inverter site selection and installation.
Values I Notes Conclusion No. Content
Communication cable (iffunction is used)
Details
Connect the RS485 cable to the communication port.
CSI-xx-KTL-CT:
1. Switch on the DC switch irst. The LCD and "Power" LED indicator will be green lighted. The "Run" LED will be off.
The "Grid" LED will be lashing. The "Fault" LED will be lashing and the inverter begins self-checking. Initially,
"GridV.Outlimit" and "GridF.Outlimit" will be displayed, then the inverter will switch to "Standby" mode.
2. Switch on the AC switch. The Grid faults will clear automatically. In "Standby" mode, the "Power" LED is solid green, the "Run" LED is off, the "Grid" LED is solid green and the "Fault" LED is off.
2
Supply DC I
AC power
CSI-xx-KTL-GS:
1. Switch the grid supply main Switch (AC) ON irst.
2. Switch the DC switch ON. If the voltages of PV arrays are higher than start up voltage, the inverter will turn on. The red LED power will be continuously lit.
3. When both the DC and the AC sides supply to the inverter, it will be ready to generate power. Initially, the inverter will check both its internal parameters and the parameters of the AC grid, to ensure that they are within the acceptable limits. At the same time, the green
LED will lash and the LCD displays the information of INITIALIZING .
[ ] Completed
[ ] Completed
Record LEOs status in Notes
[ ] Completed
Record LEOs status in Notes
. 74. www.canadiansolar.com Please return completed form to [email protected]
.75.
PROJECT NAME. ____________________________________________________ _
LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -
NUMBER __________________ _
INSTALLATION AND
COMMISSIONING CHECKLIST
.S
1!
CanadianSolar
3 PHASE STRING INVERTERS
(KTL SERIES)
Warning: This checklist is not a replacement for the user manual.
Please read the user manual prior to inverter site selection and installation.
Values I Notes Conclusion No. Content
3 Waiting time
Details
CSI-xx-KTL-CT: A standard 5 minute delay is required before the inverter generates any power to the grid.
In normal operation mode, the "Power", "Run", and
"Grid" LEOs are solid green and the" Fault" LED is off.
CSI-xx-KTL-GS:After 30-180 seconds (depending on local requirement), the inverter will start to generate power.
The green LED will be on continuously and the LCD displays the information of GENERATING.
4 Power generation After grid connection, record power output of inverter.
5
Date & Time setting
6
Communication setting (if avail.)
7 Machine version
8
9
10
Operating parameter
Testing
Completion
Set the current date and time using the front panel interface.
Set communication with a unique address for each inverter.
For maintenance and reference, please record the irmware revisions if applicable.
Record operating parameters of the inverter.
Verify IEEE1547 or UL 1741 setting is selected.
De-rate inverter and attach de-rate sticker as required.
Open and close the DC breaker to conirm whether the inverter reboots and shuts down automatically.
Installation and commissioning is complete if no abnormality.
.76. www.canadiansolar.com Please return completed form to [email protected]
[ ] Completed
Record LEOs status in Notes
[ ] Completed
Record LEOs status in Notes
[ ] Completed
Record power in Notes
[ ] Completed
Record current date/time in Notes
[ ] Completed
Record address in Notes
[ ] Completed
Record with serial numbers
[ ] Completed
Record operating parameters in Notes
[ ] Reboot successful
[ ] Not rebooting
[I Good
[ ]Issues detected
.77.
PROJECT NAME. ____________________________________________________ _
LOCATION - - - - - - - - - - - - - - - - - - - - - - - - - - -
NUMBER __________________ _
INSTALLATION AND
COMMISSIONING CHECKLIST
System Owner: ____________________________________________________________ __
.S
1!
CanadianSolar
3 PHASE STRING INVERTERS
(KTL SERIES)
Warning: This checklist is not a replacement for the user manual.
Please read the user manual prior to inverter site selection and installation.
Address I Location:
Inverter model:
Note site typical arrangements and variances
Inverter irmware revision: DSP:
LCD:. __________________________ ___
Number of inverters: Inverter mounting tilt:
Output power*: Input DC voltage: -------------------------Insulation limit (K): PV start-up voltage:
Grid: V Max: ________ V Min: ______ __ Frequency Max: ________ Min: ______________ __ Reactive compensation: _________________ +1- PF
---------------------
Coniguration: MPPT Individual MPPT Parallel __________________________ _
Monitoring: RS485:
Ethernet: -------------------------------
Monitoring equipment and supplier:
PV module manufacturer:
PV model: -------------------------------
DC cable size: ------------------AC cable size: ------------------------------
Number of series connected modules in PV strings:
Transformer ratings, supplier:
Number of PV strings in parallel per MPPT:
Total System size (DC Watts): -------------------------------------------------
*Specify de-rated power and add nameplate power in parenthesis
GENERAL COMMENTS I OBSERVATIONS:
.78. www.canadiansolar.com
.79.
Please return completed form to [email protected]
PROJECT NAME. ____________________________________________________ _
LOCATION
NUMBER __________________ __
INSTALLATION AND
COMMISSIONING CHECKLIST
.S
1!
CanadianSolar
3 PHASE STRING INVERTERS
(KTL SERIES)
Warning: This checklist is not a replacement for the user manual.
Please read the user manual prior to inverter site selection and installation.
Inverter serial numbers:
8
9
6
7
10
4
5
2
3
11 ·--------------------------------------------------------------------------·
12 ·--------------------------------------------------------------------------·
13
14
15
16
17 ·--------------------------------------------------------------------------·
18
19
20
22
23
24
25
26
27
28
29
30
37
38
39
31 ·--------------------------------------------------------------------------·
32
33
34
35
36
40
21 ·--------------------------------------------------------------------------·
41 ·--------------------------------------------------------------------------·
42
INSTALLER'S NAME
INSTALLER'S SIGNATURE - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
. 80. www.canadiansolar.com
COMPANY ____________________________________________________ ___
DATE ____________________________________________________________ ___
Please return completed form to [email protected]
.81 .
advertisement