Canadian Solar CSI Series Installation And Operation Manual

Add to My manuals
30 Pages

advertisement

Canadian Solar CSI Series Installation And Operation Manual | Manualzz

CANADIAN SOLAR INC.

Global Headquarters:

545 Speedvale Avenue, West Guelph, Ontario N1K 1E6, Canada

Tel: +1 519 837 1881

Sales Inquiries Email: [email protected]

Technical Inquiries Email: [email protected]

CANADIAN SOLAR (USA) , INC.

North America Headquarters:

3000 Oak Road, Ste 400, Walnut Creek, CA 94596

Tel: +1 888 998 7739

Sales Inquiries Email: [email protected]

Technical Inquiries Email: [email protected]

Europe, Middle East & Africa

Canadian Solar EMEA GmbH

Landsberger Strasse 94, 80339 Munich, Germany

Tel.: +49 89 5199689 0

E-mail: [email protected]

This manual is subject to change without prior notification. Copyright is reserved. Duplication of any part of this issue is prohibited without written permission.

Please adhere to the actual products in case of any discrepancies in this user manual.

CSI SERIES GRID-TIED PV Inverter

CSI-700TL1P-GI-FL

&

CSI-1KTL1P-GI-FL

CSI-1.5KTL1P-GI-FL

&

CSI-2KTL1P-GI-FL

CSI-2.5KTL1P-GI-FL

&

CSI-3KTL1P-GI-FL

INSTALLATION AND OPERATION MANUAL

VERSION 1.

1

Contents

1. Introduction ………………………………………………

1.1 Product Description

1.2 Packaging

…………………………………

…………………………………………

2. Safety Instructions

2.1 Safety Symbols

………………………………………

……………………………………

2.2 General Safety Instructions

2.3 Notice For Use

………………………

………………………………………

3. Overview ………………………………………………

3.1 Front Panel Display ………………………………

3.2 LED Status Indicator Lights

3.3 Keypad

………………………

……………………………………………

3.4 LCD

4. Installation

…………………………………………………

………………………………………………

4.1 Select Location for the Inverter …………………

4.2 Mounting the Inverter …………………………………

4.3 Electrical Connections ……………………………

4.3.1 Connect PV side of inverter ………………

4.3.2 Connect grid side of inverter

4.3.3 External ground connection

………………

………………

4.3.4 Max. overcurrent protection device (OCPD) …

4.3.5 Inverter monitoring connection

4.3.6 Electrical connection diagram

……………

…………

3

5

5

6

7

8

9

9

11

13

13

16

18

19

19

20

4.3.7 Meter Connection (optional)

4.3.8 CT connections (optional)

……………

………………

4.3.9 Logic interface connection (Only for UK)

5. Start & Stop ………………………………………………

5.1 Start the Inverter …………………………………

5.2 Stop the Inverter

6. Operation

…………………………………

………………………………………………

6.1 Main Menu

6.2 Information

6.2.1

……………………………………………

……………………………………………

Lock screen

……………………………………

23

23

23

24

24

24

26

20

21

22

7

7

8

3

4

5

Contents

6.3 Settings ………………………………………………

6.3.1 Set Time

6.3.2 Set Address

………………………………………

……………………………………

6.4 Advanced Info.

………………………………………

6.4.1 Alarm Message ………………………………

6.4.2 Running Message ……………………………

6.4.3 Version …………………………………………

6.4.4 Daily Energy ……………………………………

6.4.5 Monthly Energy and Yearly Energy

6.4.6 Daily Record

…………

……………………………………

6.4.7 Communication Data

6.4.8 Warning Message

6.5 Advanced Settings

6.5.1 Select Standard

…………………………

…………………………

…………………………………

………………………………

6.5.2 Grid ON/OFF

6.5.3 Clear Energy

…………………………………

………………………………

6.5.4 Reset Password

6.5.5 Power Control

…………………………………

………………………………

6.5.6 Calibrate Energy …………………………………

6.5.7 Special Settings

6.5.8 STD. Mode Settings

……………………………

………………………

6.5.9 Restore Settings

6.5.10 HMI Update

……………………………

…………………………………

6.5.11 Export Power Set ……………………………

6.5.12 Restart HMI …………………………………

6.5.13 Debug Parameter

6.5.14 DSP Update …………………………………

6.5.15 Power Parameter

…………………………

…………………………

7. Maintenance

8. Troubleshooting

………………………………………………

…………………………………………

9. Specifications ……………………………………………

10. Installation and commissioning checklist

……………

28

29

29

29

29

30

31

31

31

32

32

32

32

33

33

33

37

26

26

26

27

27

28

28

28

37

37

37

38

38

41

48

1. Introduction

1.1 Product Description

Canadian Solar 4G mini series single phase inverters integrate DRM and backflow power control function, thatcould suitable for smart grid requirement.

Mini Single phase 4G series inverter contain 6 models which are listed below:

CSI-700TL1P-GI-FL, CSI-1KTL1P-GI-FL, CSI-1.5KTL1P-GI-FL, CSI-2KTL1P-GI-FL,

CSI-2.5KTL1P-GI-FL, CSI-3KTL1P-GI-FL

LED lights

LCD display

4 buttons

Figure 1.1

Front side view

DC Switch(optional)

CT or Meter

Figure 1.2

a Bottom side view (0.7~3.0kW)

DC input RS 485 AC output

Figure 1.2

b Bottom side view (3.6kW)

.3.

1. Introduction

1.2 Packaging

When you receive the inverter, ensure that all the parts listed below are included:

1 2 3

.4.

4

Part #

1

2

3

4

7

8

5

6

9

5 6 7

Description

PV grid tie inverter

Wall/pole bracket

Locking screws

DC connector

AC connector

RJ45 connector (Only for UK)

WiFi / GPRS Stick ( Optional )

Manual

CT with cable ( Optional )

Table 1.1 Parts list

Number

1

1

2

1 pair for 0.7~3.0kW

2 pairs for 3.6kW

1

1

1

1

1

8

2.Safety Instructions

Improper use may result in potential electric shock hazards or burns. This manual contains important instructions that should be followed during installation and maintenance. Please read these instructions carefully before use and keep them for future reference.

2.1 Safety Symbols

Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed as follows:

WARNING:

WARNING symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.

NOTE:

NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter.

CAUTION:

CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety instructions, which if not correctly followed, could result in electric shock.

CAUTION:

CAUTION, HOT SURFACE symbol indicates safety instructions, which if not correctly followed, could result in burns.

2.2 General Safety Instructions

WARNING:

Only devices in compliance with SELV (EN 69050) may be connected to the

RS485 and USB interfaces.

WARNING:

Please don’t connect PV array positive(+) or negative(-) to ground, it could cause serious damage to the inverter.

WARNING:

Electrical installations must be done in accordance with the local and national electrical safety standards.

WARNING:

Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input.

.5.

2.Safety Instructions

WARNING:

To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the Inverter.

The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC

Article 690, Part II. All Canadian Solar single phase inverters feature an integrated DC switch.

CAUTION:

Risk of electric shock. Do not remove cover. There is no user serviceable parts inside. Refer servicing to qualified and accredited service technicians.

CAUTION:

The PV array (Solar panels) supplies a DC voltage when they are exposed to sunlight.

CAUTION:

Risk of electric shock from energy stored in capacitors of the Inverter. Do not remove cover for 5 minutes after disconnecting all power sources(service technician only). Warranty may be voided if the cover is removed without unauthorized .

CAUTION:

The surface temperature of the inverter can reach up to 75 ℃ (167 F).

To avoid risk of burns, do not touch the surface of the inverter while it’s operating.

Inverter must be installed out of the reach of children.

PV module used with inverter must have an IEC 61730 Class A rating.

.6.

2.3 Notice For Use

The inverter has been constructed according to the applicable safety and technical guidelines. Use the inverter in installations that meet the following specifications ONLY:

1. Permanent installation is required.

2. The electrical installation must meet all the applicable regulations and standards.

3. The inverter must be installed according to the instructions stated in this manual.

4. The inverter must be installed according to the correct technical specifications.

5. To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before

the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply

Main Switch (AC) must be switched off before the solar panel's DC isolator shall be

switched off.

3.1 Front Panel Display

3. Overview

Figure 3.1 Front Panel Display

3.2 LED Status Indicator Lights

There are three LED status indicator lights in the front panel of the inverter. Left LED:

POWER LED (red) indicates the power status of the inverter. Middle LED: OPERATION

LED (green) indicates the operation status. Right LED: ALARM LED (yellow) indicates the alarm status. Please see Table 3.1 for details

Light

POWER

OPERATION

ALARM

Status

ON

OFF

ON

OFF

FLASHING

ON

OFF

Description

The inverter can detect DC power

No DC power or low DC power

The inverter is operating properly.

The inverter has stopped to supply power.

The inverter is initializing.

Alarm or fault condition is detected.

The inverter is operating without fault or alarm.

Table 3.1 Status Indicator Lights

.7.

3. Overview

3.3 Keypad

There are four keys in the front panel of the Inverter(from left to right):

ESC, UP, DOWN and ENTER keys. The keypad is used for:

Scrolling through the displayed options (the UP and DOWN keys);

Access to modify the adjustable settings (the ESC and ENTER keys).

3.4 LCD

The two-line Liquid Crystal Display (LCD) is located on the front panel of the Inverter, which shows the following information:

Inverter operation status and data;

Service messages for operator;

Alarm messages and fault indications.

4. Installation

4.1 Select a Location for the Inverter

To select a location for the inverter, the following criteria should be considered:

Do not install in small closed spaces where air can not circulate freely. To avoid overheating, always make sure the flow of air around the inverter is not blocked.

Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting. Canadian Solar recommends inverter installed to avoid direct sunlight or raining.

To avoid over heating ambient air temperature must be considered when choosing the inverter installation location. Canadian Solar recommends using a sun shade minimizing direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.

Figure 4.1 Recommended Installation locations

.9.

.8.

4. Installation

Install vertically with a maximum incline of +/- 5 °.

If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.

When 1 or more inverters are installed in one location, a minimum 12inchs clearance should be kept between each inverter or other object. The bottom of the inverter should be 20inchs clearance to the ground.

4.2 Mounting the Inverter

Dimensions of wall bracket:

4. Installation

.10.

300mm 300mm 300mm

Figure 4.2 Inverter Mounting clearance

Visibility of the LED status indicator lights and the LCD located at the front panel of the inverter should be considered.

Adequate ventilation must be provided if the inverter is to be installed in a confined space.

NOTE:

Nothing should be stored on or placed against the inverter.

Figure 4.3 Inverter wall mounting

Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter.

The inverter shall be mounted vertically. The steps to mount the inverter are listed below:

1. According to the figure 4.2, select the mounting height of the bracket and mark the

mounting holes. For brick walls, the position of the holes should be suitable for the

expansion bolts.

Bracket

Suitable fixing screws

Figure 4.4 Inverter wall mounting

.11.

4. Installation

2.Make

sure the bracket is horizontal and the mounting holes (in Figure 4.4 )

are marked correctly . Drill the holes into the wall or pillar at your marks .

3. Use the suitable screws to fix the bracket to the wall.

WARNING:

The inverter must be mounted vertically.

4. Lift up the inverter (be careful to avoid body strain), and align the back bracket on the

inverter with the convex section of the mounting bracket. Hang the inverter on the

mounting bracket and make sure the inverter is secure (see Figure 4.5).

Locking screws

4. Installation

4.3 Electrical Connections

4.3.1 Connect PV side of inverter

The electrical connection of the inverter must follow the steps listed below:

1. Switch the Grid Supply Main Switch (AC) OFF.

2. Switch the DC Isolator OFF.

3. Assemble PV input connector to the Inverter.

Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter

Maximum 600Voc for

CSI-700TL1P-GI-FL, CSI-1KTL1P-GI-FL, CSI-1.5KTL1P-GI-FL,

CSI-2KTL1P-GI-FL, CSI-2.5KTL1P-GI-FL, CSI-3KTL1P-GI-FL

Please don’t connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter

Before connection, please make sure the polarity of the output voltage of PV array matches the “ DC+ ” and “ DC” symbols.

Figure 4.5 Wall Mount Bracket

5. Use M4*9 screws in accessory to lock the inverter to the mount bracket.

.12.

Figure 4.6 DC+ Connector Figure 4.7 DC- Connector

.13.

4. Installation

Please use approved DC cable for PV system.

Cable type

Cross section

Range

Recommended value

Industry generic PV cable

( model:PV1 F )

4.0~6.0

( 12~10AWG )

4.0

( 12AWG )

Table 4.1 DC cable

The steps to assemble the DC connectors are listed as follows:

I) Strip off the DC wire for about 7mm, Disassemble the connector cap nut.

Figure 4.8 Disassemble the Connector Cap nut

ii) Insert the wire into the connector cap nut and contact pin.

.14.

Figure 4.9 Insert the Wire into the Connector Cap nut and contact pin

4. Installation

iii) Crimp the contact pin to the wire using a proper wire crimper.

Crimping plier

Figure 4.10 Crimp the contact pin to the wire iv) Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector.

Figure 4.11 Connector with Cap nut Screwed on v) Then connect the DC connectors to the inverter. Small click will confirm connection.

Figure 4.12 Connect the DC Connectors to the Inverter

.15.

4. Installation

4.3.2 Connect grid side of inverter

2

For all AC connections, 2.5- 6mm 105 ℃ cable is required to be used. Please make sure the resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's recommended

2 to use 6mm cable.

WARNING:

There are symbols marked inside the connector , the Line wire of grid must be connected to “ L ” terminal; the Neutral wireof grid must be connected to “ N ” terminal; the Earth of grid must be connected to “ ” (see Figure 4.13).

Cable type

Industry generic grid cable

Cross section

Range

Recommended value

2.5~6.0mm

²

Table 4.2 Grid cable size

6mm ²

4. Installation

The steps to assemble the AC grid terminal connectors are listed as follows: a) Disassemble the AC connector. Strip the AC wires about 6mm.

Figure 4.15 Stripped AC Wires b) Fix the green and yellow wire to the ground terminal. Fix the red(or brown) wire to L

(line) terminal. Fix the blue wire to N(Neutral). Tight the screws on the connector.

Please try to pull out the wire to make sure the it’s well connected.

Figure 4.13 AC Grid Terminal Connector Inside

Each Canadian Solar Mini Single Phase Inverter is supplied with an AC grid terminal connector.

Figure 4.16 Connect Wires to the Terminal

c) Tighten up the cap on the terminal (see Figure 4.17).

Figure 4.14 AC Grid Terminal Connector

Figure 4.17 Tighten up the Cap on the Terminal

.17.

.16.

4. Installation

d) Connect the AC grid terminal connector to the inverter. Small click will confirm

connection.

Figure 4.18 Connect the AC Connector to the Inverter

Note: Connection for Split phase grid.

When connect to 208/220/240V split phase, please connect L1 to “L” terminal,

L2 to “N” terminal. Also connect earth to ground terminal.

4.3.3 External ground connection

An external ground connection is provided at the right side of inverter.

Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.

.18.

Figure4.19

Connect the external grounding conductor

4. Installation

4.3.4 Max. over current protection device (OCPD)

To protect the inverter's AC grid connection conductors, Canadian Solar recommends installing breakers that will protect against overcurrent. The following table defines OCPD ratings for the Canadian Solar mini single phase inverters.

Inverter

CSI-700TL1P-GI-FL

CSI-1KTL1P-GI-FL

CSI-1.5KTL1P-GI-FL

CSI-2KTL1P-GI-FL

CSI-2.5KTL1P-GI-FL

CSI-3KTL1P-GI-FL

Rated output

voltage(V)

Rated output

current (A)

220/230

220/230

220/230

220/230

220/230

220/230

3.2/3.0

4.5/4.3

6.8/6.5

9.1/8.7

11.4/10.9

13.6/13

Current for protection device (A)

10

10

10

15

15

20

Table 4.3 Rating of grid OCPD

4.3.5 Inverter monitoring connection

The inverter can be monitored via Wi-Fi or GPRS. All Canadian Solar communication devices are optional (Figure 4.20). For connection instructions, please refer to the Canadian

Solar Monitoring Device installation manuals.

Smart phone monitoring

GPRS monitoring

Internet

Wi-Fi monitoring

Router

Wi-Fi monitoring

PC monitoring

Wi-Fi box

Figure 4.20 Communication function

Web server

.19.

4. Installation

4.3.6 Electrical connection diagram

Refer to figure 4.21, which is a simple guidance for installing a solar system with PV inverter.

A DC isolator is required to be installed in the system between PV panels with inverter.

MAIN SWITCHBOARD

Consumers mains

(to grid)

Main switch

1

Solar supply main switch

1

Isolation device

Inverter with integral grid

Protection device

Solar

(PV) array

2

Isolation switch

Circuits not protected by

RCDs

Circuits Protected by RCDs

Figure 4.21 Guidance for a Simple Installation of an Inverter Solar Energy System

1. The RCD should be in parallel connection between the consumers mains and the solar supply.

2. More than one RCD may be used. Each RCD can protect one or more circuits.

4.3.7 Meter Connection(optional)

The inverter has intergrated export limitation functionality. inverter is divided into two types: single-direction meter, and dual-direction meter.

Therefore, the wiring method is divided into two cases.

The dual-direction meter corresponds to the meter in grid connection mode; the single-direction meter corresponds to the meter in load connection mode.

see Figure 4.22 and 4.23. After the inverter power on please set the corresponding configuration as sections 6.5.11.1.2 and 6.5.11.1.3.

Communication

5 6 7 8

A B

DDSD1352

220V~10(60)A

1

T1 T2 T3

1600 imp/kWh

MENU

L L ´ N N ´

Grid

Load

Figure 4.22 Meter in Load

.20.

4. Installation

Communication

5 6 7 8

A B

DDSD1352

220V~10(60)A

1

T1 T2 T3

1600 imp/kWh

MENU

L L ´ N N ´

Grid

Load

Figure 4.23 Meter in Grid

4.3.8 CT connections(optional)

This inverter has integrated export limitation functionality. To use this function, a CT must the live conductor on the grid side of the main incoming consumer unit. Use the directional flow indication arrow on the CT to ensure it is fitted in the correct orientation. The arrow should be pointing towards the grid, not the load. when the inverter power on, please set the corresponding configuration as sections 6.5.11.1.4.1 and 6.5.11.1.4.2.

Inverter

CT Input L N

CT

L N

Load

Figure 4.24 Direction of CT

L

N

Grid

.21.

4. Installation

4.3.9 Logic interface connection (Only for UK)

Logic interface is required by G98 and G99 standard that can be operated by a simple switch or contactor. When the switch is closed the inverter can operated normally. When the switch is opened, the inverter will reduce it’s output power to zero within 5s.

Pin5 and Pin6 of RJ45 terminal is used for the logic interface connection.

Please follow below steps to assemble RJ45 connector.

1. Insert the network cable into the communication connection terminal of RJ45.

(As shown in figure 4.25)

Figure 4.25 RJ45 communication connection terminals

2. Use the network wire stripper to strip the insulation layer of the communication cable.

According to the standard line sequence of figure 4.26 connect the wire to the plug of

RJ45, and then use a network cable crimping tool to make it tight.

Rj45 plug 1--8

Rj45 terminal

Correspondence between the cables and the stitches of plug, Pin5 and Pin6 of RJ45 terminal is used for the logic

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

Switch

_ input1 Switch

_ input2

DRM(logic interface) interface, other Pins are reserved.

Pin 1: Reserved; Pin 2: Reserved

Pin 3: Reserved; Pin 4: Reserved

Pin 5: Switch_input1; Pin 6: Switch_input2

Pin 7: Reserved; Pin 8: Reserved

Figure 4.26 Strip the insulation layer and connect to RJ45 plug

3. Connect RJ45 to DRM (l ogic interface ) .

After wire connection, please refer chapter 6.5.8.1 to enable the logic interface function.

5. Start & Stop

5.1 Start the Inverter

To start up the Inverter, it is important that the following steps are strictly followed:

1. Switch the grid supply main Switch (AC) ON first.

2. Switch the DC switch ON. If the voltage of PV arrays are higher than start up voltage,

the inverter will turn on. The red LED power will light.

3. When both the DC and the AC sides supply to the inverter, it will be ready to generate

power. Initially, the inverter will check both its internal parameters and the parameters

of the AC grid, to ensure that they are within the acceptable limits. At the same time,

the green LED will flash and the LCD displays the information of INITIALIZING.

4. After 30-300 seconds (depending on local requirement), the inverter will start to

generate power. The green LED will be on continually and the LCD displays

GENERATING.

WARNING:

Do not touch the surface when the inverter is operating. It may be hot and cause burns.

5.1.1 Inverter working status

When inverter working normally,there would be 5 status :

Generating:Inverter is working normally

LimByTemp: Inverter power limited by over ambient temperature.

LimByFreq: Inverter power limited by over grid frequency

LimByVg: Inverter power limited by over grid voltage

LimByVar: Inverter power limited by generating reactive power.

5.2 Stop the Inverter

To stop the Inverter, the following steps must be strictly followed:

1. Switch the Supply Main Switch (AC) OFF.

2. Wait 30 seconds. Switch the DC Switch OFF. All the LEDs of the inverter will be off in one

minute.

.22.

.23.

6. Operation

During normal operation, the display alternately shows the power and the operation status with each screen lasting for 10 seconds (see Figure 6.1). Screens can also be scrolled manually by pressing the UP and DOWN keys. Press the ENTER key to access to the Main Menu.

Pressing the

ESC key calls back the previous menu.

Power 3424W

01-01-2014 12:04

Start

5 sec UP/DOWN or auto-scroll

(10 sec)

Status: Generating

01-01-2014 12:04

Pressing the

ENTER key gives access to the main menu.

Main Menu

Information

UP/DOWN

Settings

UP/DOWN

Advanced Info.

UP/DOWN

Advanced settings

Figure 6.1 Operation Overview

6.1 Main Menu

There are four submenus in the Main Menu (see Figure 6.1):

1. Information

2. Settings

3. Advanced Info.

4. Advanced Settings

6.2 Information

The Canadian Solar Single Phase 4G Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.

.24.

6. Operation

Display

V_DC1 350.8V

I_DC1 5.1A

V_Grid 230.4V

I_Grid 8.1A

Status: Generating

Power: 1488W

Duration

10 sec

10 sec

10 sec

Description

V_DC1: Shows input 01 voltage value.

I_DC1: Shows input 01 current value.

V_Grid: Shows the grid's voltage value

I_Grid: Shows the grid's current value.

Status: Shows instant status of the Inverter.

Power: Shows instant output power value.

Grid Frequency

F_Grid 50.06Hz

10 sec F_Grid: Shows the grid's frequency value.

Total Energy

0258458 kwh

This Month: 0123kwh

Last Month: 0123kwh

Today: 15.1kwh

Yesterday: 13.5kwh

Inverter SN

00000000000000

Export_P: +0000W

Export_I: 00.0A

Work Mode: NULL

DRM Number: 08

Meter EnergyP

0000000 .

00k Wh

10 sec

10 sec

10 sec

10 sec

10 sec

10 sec

10 sec

Total generated energy value

This Month: Total energy generated this month.

Last Month: Total energy generated last month.

Today: Total energy generated today.

Yesterday: Total energy generated yesterday.

Display series number of the inverter.

Power of ERM.

Current of EPM.

Work Mode : The work mode of inverter .

DRM Number : Show the number 01 08 .

Meter EnergyP : The active power .

Table 6.1 Information list

.25.

6. Operation

6.2.1 Lock screen

Pressing the ESC key returns to the Main Menu. Pressing the ENTER key locks

(Figure 6.2(a)) or unlocks (Figure 6.2 (b)) the screen.

5.2 Stop the Inverter

(a) (b)

Figure 6.2 Locks and Unlocks the Screen of LCD

6.3 Settings

The following submenus are displayed when the Settings menu is selected:

1. Set Time

2. Set Address

6.3.1 Set Time

This function allows time and date setting. When this function is selected, the LCD will display a screen as shown in Figure 6.3.

NEXT=<ENT> OK=<ESC>

01-01-2016 16:37

Figure 6.3 Set Time

Press the UP/DOWN keys to set time and data. Press the ENTER key to move from one digit to the next (from left to right). Press the ESC key to save the settings and return to the previous menu.

6.3.2 Set Address

This function is used to set the address when muti inverters are connected to single monitor.

The address number can be assigned from “01”to “99”(see Figure 6.4). The default address number of Canadian Solar Single Phase Inverter is “01”.

6. Operation

YES=<ENT> NO=<ESC>

Set Address: 01

Figure 6.4 Set Address

Press the UP/DOWN keys to set the address. Press the ENTER key to save the settings.

Press the ESC key to cancel the change and return to the previous menu.

6.4 Advanced Info - Technicians Only

NOTE:

To access to this area is for fully qualified and accredited technicians only.

Enter menu “Advanced Info.” and “Advanced settings” ( need password ) .

Select “Advanced Info.” from the Main Menu. The screen will require the password as below

YES=<ENT> NO=<ESC>

Password:0000

Figure 6.5 Enter password

The default password is “0010". Please press “down” to move the cursor, press “up” to select the number.

After enter the correct password the Main Menu will display a screen and be able to access to the following information.

1. Alarm Message 2. Running Message 3.Version 4. Daily Energy 5. Monthly Energy

6. Yearly Energy 7. Daily Record 8. Communication Data 9 .

Warning Message

The screen can be scrolled manually by pressing the UP/DOWN keys. Pressing the ENTER key gives access to a submenu. Press the ESC key to return to the Main Menu.

6.4.1 Alarm Message

The display shows the 100 latest alarm messages (see Figure 6.6). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.

Alarm001: OV-G-V

Time: 27-11 Data: 7171

Figure 6.6 Alarm Message

.27.

.26.

6. Operation

6.4.2 Running Message

This function is for maintaince person to get running message such as internal temperature,

Standard NO. etc.

Screens can be scrolled manually by pressing the UP/DOWN keys.

6.4.3 Version

The screen shows the model version and the software version of the Inverter

(see Figure 6.7).

Model: 08

Software Version: D20001

Figure 6.7 Model Version and Software Version

6.4.4 Daily Energy

The function is for checking the energy generation for selected day.

YES=<ENT> NO=<ESC>

Select: 2015-0223

Figure 6.8 Select date for daily energy

Press DOWN key to move the cursor to day, month and year, press UP key to change the digit. Press Enter after the date is fixed.

2015-02-22: 051.3kWh

2015-02-23: 061.5kWh

Figure 6.9 Daily energy

Press UP/DOWN key to move one date from another.

6.4.5 Monthly Energy and Yearly Energy

The two functions are for checking the energy generation for selected month and Year

YES=<ENT> NO=<ESC>

Select: 201502

YES=<ENT> NO=<ESC>

Select: 20 15

Figure 6.10 Select month for monthly energy Figure 6.11 Select year for yearly energy

.28.

6. Operation

Press DOWN key to move the cursor, press UP key to change the digit.

Press Enter after the month/year is fixed.

2015-02: 0510kWh

2015-01: 0610kWh

2015: 0017513kWh

2014: 0165879kWh

Figure 6.12 Month energy

Press UP/DOWN key to move one date from another.

Figure 6.13 Yearly energy

6.4.6 Daily record

The screen shows history of changing settings. Only for maintance personel.

6.4.7 Communication Data

The screen shows the internal data of the Inverter (see Figure 6.14), which is for service technicians only.

01-05: 01 25 E4 9D AA

06-10: C2 B5 E4 9D 55

Figure 6.14 Communication Data

6.4.8 Warning Message

The display shows the 100 latest warn messages (see Figure 6.15). Screens can be scrolled manually by pressing the UP/ DOWN keys. Press the ESC key to return to the previous menu.

Msg000:

T: 00 00 00 : 00 D : 0000

Figure 6.15 Warning Message

6.5 Advanced Settings - Technicians Only

NOTE:

To access to this area is for fully qualified and accredited technicians only.

Please follow 6.4 to enter password to access this menu.

Select Advanced Settings from the Main Menu to access the following options:

1. Select Standard 2. Grid ON/OFF 3.Clear Energy 4. Reset Password

5. Power Control 6.Calibrate Energy 7.Special Settings 8 .

STD. Mode Settings

9 .

Restore Settings 10.HMI Update 11.Export Power Set 12.Restart HMI

13.Debug Parameter 14.DSP Update 15.Power Parameter

.29.

6. Operation

6.5.1 Selecting Standard

This function is used to select the grid's reference standard (see Figure 6.16).

YES=<ENT> NO=<ESC>

Standard:AS4777-02

Figure 6.16

Press the UP/DOWN keys to select the standard (AS4777-02,AS4777-15, VDE4105, VDE0126,

UL-240V-A, UL-208V-A, UL-240V, UL-208V, MEX-CFE, G83/2 (for 1-3.6kW models), G59/3

(for 4-5kW models), EN50438 DK, EN50438 IE, EN50438 NL and “User-Def” function).

Press the ENTER key to confirm the setting. Press the ESC key to cancel changes and returns to previous menu.

NOTE:

This function is for technicians use only.

Selecting the “User-Def” menu will access to the following submenu (see Figure 6.17),

OV-G-V1: 260V

OV-G-V1-T: 1S

Figure 6.17

NOTE:

The " User-Def" function can be only used by the service engineer and must be allowed by the local energy supplier.

Below is the setting range for “User-Def”. Using this function, the limits can be changed manually.

OV-G-V1: 240---270V OV-G-F1: 50.2-53Hz(60.2-64Hz)

OV-G-V1-T: 0.1---9S OV-G-F1-T: 0.1---9S

OV-G-V2: 240---300V OV-G-F2: 50.2-53Hz(60.2-64Hz)

OV-G-V2-T: 0.1---1S OV-G-F2-T: 0.1---9S

UN-G-V1: 170---210V UN-G-F1: 47-49.5Hz(56-59.8Hz)

UN-G-V1-T: 0.1---9S UN-G-F1-T: 0.1---9S

UN-G-V2: 110---210V UN-G-F2: 47-49Hz(56-59.8Hz)

UN-G-V2-T: 0.1---1S UN-G-F2-T: 0.1---9S

Startup-T : 10-600S Restore-T: 10-600S

.30.

6. Operation

NOTE:

This inverter inclding two level protections for voltage and frequency under user-def mode; please set the same value both level one and level two if the gird only have one level requriement, eg. Brazil...etc.

Press the UP/DOWN keys to scroll through items. Press the ENTER key to edit the highlighted item. Press the UP/DOWN keys again to change the setting. Press the ENTER key to save the setting. Press the ESC key to cancel changes and returns to the previous menu.

6.5.2 Grid ON/OFF

This function is used to start up or stop the power generation of Canadian Solar Single

Phase Inverter (see Figure 6.18).

Grid ON

Grid OFF

Figure 6.18 Set Grid ON/OFF

Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key to save the setting. Press the ESC key to return to the previous menu.

6.5.3 Clear Energy

Clear Energy can reset the history yield of inverter

These two functions are applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.

6.5.4 Reset Password

This function is used to set the new password for menu “Advanced info.” and “Advanced information” (see Figure 6.19).

YES=<ENT> NO=<ESC>

Password: 0000

Figure 6.19 Reset password

Enter the right password before set new password. Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the ENTER key to execute the setting.

Press the ESC key to return to the previous menu.

.31.

6. Operation

6.5.5 Power Control

Active and reactive power can be set through power setting button.

There are 5 item for this sub menu:

1. Set output power 2. Set Reactive Power 3. Out_P With Restore

4. Rea_P With Restore 5. Select PF Curve

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.

6.5.6 Calibrate Energy

Maintenance or replacement could clear or cause a different value of total energy. Use this function could allow user to revise the value of total energy to the same value as before. If the monitoring website is used the data will be synchronous with this setting automatically.

(see Figure 6.20).

YES=<ENT> NO=<ESC>

Energy:0000000kWh

Figure 6.20 Calibrate energy

Press the DOWN key to move the cursor, Press the UP key to revise the value. Press the

ENTER key to execute the setting. Press the ESC key to return to the previous menu.

6.5.7 Special Settings

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.

6.5.8 STD. Mode Settings

There are 5 setting under STD. Mode settings.

1. Working mode 2. Power Rate limit 3. Freq. Derate set 4. 10mins OV-G-V set.

5.Initial Settings

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from working properly.

.32.

6. Operation

6.5.8.1 Enable logic interface settings

When select G98 or G99 standard to use the logic interface function, please follow below settings to enable the DRM . DRM default setting is “OFF” , if DRM set “ON”, but the logic interface un-connected to the switch or the switch is open, the inverter HMI will display “Limit by DRM” and the inverter output power will be limited to zero.

1. Select Initial Settings

2. Select DRM and set it “ ON ”

6.5.9 Restore Settings

Restore setting could set all item in 6.5.7 special setting to default.

The screen shows as below :

Are you sure ?

YES=<ENT> NO=<ESC>

Figure 6.21 Restore Settings

Press the Enter key to save the setting after setting grid off .

Press the ESC key to return the previous mean .

6.5.10 HMI Update

This function is used for update the LCD program.

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.

6.5.11 Export Power Set

To access to this area is for fully qualified and accredited technicians only.

Please follow 6 .

4 to enter password to access this menu .

The default password is “0010". Please press “down” to move the cursor, press “up” to select the number .

Select EPM Settings from the Main Menu to access the following options:

1. Model Select 2.Set Backflow Power 3.Fail safe ON/OFF

.33.

6. Operation

6.5.11.1 Model Select

There are 4 settings in this menu as below:

1.OFF 2.Meter in Load 3.Meter in Grid 4.Current sensor

6.5.11.1.1 OFF

This function is used to shut down the Export Power Set.

ON=<ENT> CANCEL=<ESC>

OFF

Press the ENTER key to set d one.

Press the ESC key to the previous menu.

Figure 6.22

6.5.11.1.2 Meter in Load

The submenu is used to set meter in Load as shown as 4.3.7 Meter connection(optional).

ON=<ENT> CANCEL=<ESC>

Meter in Load

Press Enter key to save the setting.

6.5.11.1.3 Meter in Grid

Figure 6.23

The submenu is used to set meter in Grid as shown as 4.3.7 Meter connection(optional).

ON=<ENT> CANCEL=<ESC>

Meter in Grid

Figure 6.24

Press Enter key to save the setting.

6.5.11.1.4 Current sensor

The submenu is used to set current sensor as shown as 4.3.8 CT connection(optional).

There are 2 modes shown as below: 1.CT Sampling Ratio 2.CT Link test

ON=<ENT> CANCEL=<ESC>

Current Sensor

Figure 6.25

.34.

6. Operation

6.5.11.1.4.1 CT Sampling Ratio

This function is used for change CT Sampling Ratio if customer select different CT .

The default radio is 3000 : 1 .

-> CT Sampling Ratio

Figure 6.26 Set the CT Para of the EPM

YES=<ENT> NO=<ESC>

Ratio:3000:1

Figure 6.27

Press the UP/DOWN keys to set data.Press the ENTER key to set CT Para .

Press the ESC key to save the settings and return to the previous menu.

6.5.11.1.4.2 CT Link Test

Before pressing the CT Link Test menu, please check as follow:

1.

Load power ≥ 500W

2.Inverter should be set Grid Off

3.CT should be connected

4.EPM should be set ON

Press the ENTER key to show the screen of CT Link Test .it will show as below when the EPM was set ON :

CT Link State

Correct

Figure 6.28 CT Link State

Press the ESC key to the previous menu.

NOTE:

There are three states in the CT Link State.

“Error” means CT reverse connection. Please change CT direction

“Can not judge” means load power is not enough, it should be more than 500W.

“Correct” means CT has been connected correctly.

.35.

6. Operation

Inverter

CT Input L N

CT

×

×

CT

L N

Load

CT

Figure 6.29 CT loction

L

N

Grid

See figure 6.29. If CT test pass but inverter still can't achieve export power

(power is not controllable or always 0 power output).

Please check installation location of the CT.

6.5.11.2 Backflow Power

This submenu is used for set allowed power that inverter can generate to grid .

->Set Backflow Power YES=<ENT> NO=<ESC>

P_Backflow:-0001W

Figure 6.

30 Set the backflow p o wer Figure 6.31

Press the UP/DOWN keys to set data.Press the ENTER key to set backflow power

Then press DOWN keys to move the cursor, press UP to change the number.

Press the ESC key to save the settings and return to the previous menu.

6.5.11.3 Fail safe ON/OFF

This function is used to remind whether the fail safe function is ON or not.

The default setting is ON.

YES=<ENT> NO=<ESC>

Fail Safe Set:ON

Figure 6.32 Set the Fail Safe ON/OFF

Press the UP/DOWN keys to set ON/OFF.Press the ENTER key to set d one .

Press the ESC key to the previous menu.

.36.

6. Operation

ON: When CT is disconnected, the inverter will stop generate power and LCD show

"Fail Safe"

OFF: When CT is disconnected, the inverter will be limited to the power at the time CT is

disconnected. If restart, inverter will not limit output power.

6.5.12 Restart HMI

The function is used for restart the HMI .

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.

6.5.13 Debug Parameter

This function is used for manufacturer maintenance personnel only.

6.5.14 DSP Update

The function is used for update the DSP .

This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.

6.5.15 Power Parameter

This function is used for calibrate inverter output energy. It will not impact the energy count for inverter with RGM.

The screen shows :

YES=<ENT> NO=<ESC>

Power para : 1 .

000

Figure 6.33 Power Rate Limit

Press the Down key to move the cursor .

Press the Up key to change the digit .

Please press the Enter to save the setting and press the ESC key to return to the previous menu .

This setting is used for grid operator, don't change setting under this manual.

.37.

7. Maintenance

7.Maintenance

Canadian Solar Mini Single Phase 4G Inverter does not require any regular maintenance.

However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.

CAUTION:

Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter (refer to Section 5.2) and wait for a cool-down period before before any maintenance or cleaning operation.

The LCD and the LED status indicator lights can be cleaned with a damp cloth if they are too dirty to be read.

NOTE:

Never use any solvents, abrasives or corrosive materials to clean the inverter.

8. Troubleshooting

The inverter is designed in accordance with the most important international grid-tied standards and safety and electromagnetic compatibility requirements. Before delivering to the customer, the inverter has been subjected to several tests to ensure its optimal operation and reliability.

In case of failure, the LCD screen will display an alarm message. In this case, the inverter may stop feeding into the grid. The failure descriptions and their corresponding alarm messages are listed in Table 8.1:

8. Trouble Shooting

Alarm Message

No power

LCD show initializing all the time

OV-G-V01/02/03/04

Failure description

Inverter no power on LCD can not start-up

Over grid voltage

Solution

1.Check PV input connections

2.Check DC input voltage

(single phase >120V, three phase >350V)

3.Check if PV+/ is reversed

1.Check if the connector on main

board or power board are fixed.

2.Check if the DSP connector to

power board are fixed.

1.Resistant of AC cable is too high.

Change bigger size grid cable

2.Adjust the protection limit if it’s

allowed by electrical company.

UN-G-V01/02

OV-G-F01/02

UN-G-F01/02

G-IMP

Under grid voltage

Over grid frequency

Under grid frequency

High grid impedance

NO-GRID No grid voltage

OV-DC01/02/03/04

OV-BUS

UN-BUS01/02

GRID-INTF01/02

OV-G-I

IGBT-OV-I

DC-INTF

OV-DCA-I

IGFOL-F

IG-AD

Over DC voltage

Over DC bus voltage

Under DC bus voltage

Grid interference

Over grid current

Over IGBT current

DC input overcurrent

Grid current tracking fail

Grid current sampling fail

OV-TEM

INI-FAULT

DSP-B-FAULT

12Power-FAULT

1.Use user define function to adjust the

protection limit if it’s allowed by

electrical company.

1.Check connections and grid switch.

2.Check the grid voltage inside inverter

terminal.

1.Reduce the module number in series

1.Check inverter inductor connection

2.Check driver connection

1.Restart inverter

2.Change power board

1.Restart inverter

2.Identify and remove the string to the fault MPPT

2.Change power board

1.Restart inverter or contact installer.

Over Temperature

1.Check inverter surrounding ventilation.

2.Check if there’s sunshine direct on

inverter in hot weather.

Initialization system fault

Comm. failure between main and slave DSP

12V power supply fault

1.Restart inverter or contact installer.

PV ISO-PRO

01/02

PV isolation protection

1.Remove all DC input, reconnect and

restart inverter one by one.

2.Identify which string cause the fault and

check the isolation of the string.

.39.

.38.

8. Trouble Shooting

Alarm Message

ILeak-PRO

01/02/03/04

RelayChk-FAIL

DCinj-FAULT

Failure description

Leakage current protection

Relay check fail

High DC injection current

Solution

1.Check AC and DC connection

2.Check inverter inside cable connection.

1.Restart inverter or contact installer.

1.Restart inverter or contact installer.

Table 8.1 Fault message and description

NOTE:

If the inverter displays any alarm message as listed in Table 8.1; please turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5 minutes before restarting it (refer to Section 5.1 to start your inverter). If the failure persists, please contact your local distributor or the service center.

Please keep ready with you the following information before contacting us.

1. Serial number of Canadian Solar Single Phase Inverter;

2. The distributor/dealer of Canadian Solar Single Phase Inverter (if available);

3. Installation date.

4. The description of problem (i.e. the alarm message displayed on the LCD and the status

of the LED status indicator lights. Other readings obtained from the Information submenu

(refer to Section 6.2) will also be helpful.);

5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings

, etc.);

6. Your contact details.

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-700TL1P-GI-FL

900

600

200

60

50...500

11

17.2

1/1

700

800

800

220/230

3.2/3.0

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.2%

96.5%

>99.5%

310W*373H*160D (mm)

8.5kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

.41.

.40.

.42.

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-1KTL1P-GI-FL

1200

600

200

60

50...500

11

17.2

1/1

1000

1100

1100

220/230

4.5/4.3

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.2%

96.5%

>99.5%

310W*373H*160D (mm)

8.5kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-1.5KTL1P-GI-FL

1800

600

200

60

50...500

11

17.2

1/1

1500

1700

1700

220/230

6.8/6.5

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.2%

96.5%

>99.5%

310W*373H*160D (mm)

8.5kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

.43.

.44.

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-2KTL1P-GI-FL

2300

600

330

90

80...500

11

17.2

1/1

2000

2200

2200

220/230

9.1/8.7

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.2%

96.5%

>99.5%

310W*373H*160D (mm)

8.5kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-2.5KTL1P-GI-FL

3000

600

330

90

80...500

11

17.2

1/1

2500

2800

2800

220/230

11.4/10.9

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.5%

96.8%

>99.5%

310W*373H*160D (mm)

8.8kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

.45.

.46.

Model

Max. DC input power (Watts)

Max. DC input voltage (Volts)

Rated DC voltage (Volts)

Start-up voltage (Volts)

MPPT voltage range (Volts)

Max. input current (Amps)

Max short circuit input current (Amps)

MPPT number/Max input strings number

Rated output power (Watts)

Max. output power (Watts)

Max. apparent output power (VA)

Rated grid voltage (Volts)

Rated output current (Amps)

Power Factor (at rated output power)

THDi (at rated output power)

Rated grid frequency (Hertz)

Operating frequency range (Hertz)

Max.efficiency

EU efficiency

MPPT efficiency

Dimensions

Weight

Topology

Operating ambient temperature range

Ingress protection

Noise emission (typical)

Cooling concept

Max.operation altitude

Designed lifetime

Grid connection standard

Operating surroundings humidity

Connention

Display

Communication connections

Monitoring

Warranty Terms

CSI-3KTL1P-GI-FL

3500

600

330

90

80...500

11

17.2

1/1

3000

3300

3300

220/230

13.6/13

0.8leading~0.8lagging

<3%

50/60

47...52 or 57...62

97.5%

96.8%

>99.5%

310W*373H*160D (mm)

8.8kg

Transformerless

25 ℃...

60 ℃

IP65

<20 dBA

Natural convection

4000m

>20 years

En50438, G83/2, G98, G99, AS4777.2:2015,

VDE0126-1-1, IEC61727, VDE N4105

0...100% Condensing

Mc4 connector and Ip67 rated plug

LCD, 2×20 Z.

4 pins RS485 connector

WiFi or GPRS

5 Years STD (Extendable to 20 Years)

.47.

PROJECT NAME

LOCATION NUMBER

INSTALLATION AND 3 PHASE STRING INVERTERS

(KTL SERIES)

COMMISSIONING CHECKLIST

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Step No.

1

2

3

4

5

6

7

8

Content

Installation environment

Unpacking

Mounting bracket installation

Inverter installation

Serial number

Solar modules

DC input and

AC output connection

PV voltage

9 AC grid

.48.

10 Grounding cable www.canadiansolar.com

Details

Ensure installation site meets environmental and physical constraints.

Check inverter condition after unpacking.

Install inverter mounting bracket according to installation instructions in user manual. For allowable tilt angle refer to the installation manual.

Carefully install the inverter to the mounting bracket and ensure it is f irmly attached. Ensure the inverter has proper clearances and are properly ventilated.

Record the product serial numbers located on the side label.

Con f irm PV module installation completion.

Record the total power of the PV modules.

Switch off the DC and AC distribution unit, connect

DC to PV terminals of inverter, and connect AC to AC terminals of inverter. Ensure proper polarity and cable size. Torque to speci f ications.

Measure and record DC voltage. Ensure voltage and polarities are correct. Con f irm the voltages are within

5% tolerance to what was tested.

Measure and record AC voltage and frequency. Con f irm the

V

AC

voltages are within 5% tolerance to what was tested.

Ensure ground cable is f irmly attached to grounding lug.

Values / Notes

Please return completed form to [email protected]

Conclusion

[ ] Good [ ] Poor

[ ] Good [ ] Poor

[ ] Completed

Record Tilt Angle in Notes

[ ] Completed

Serial Numbers; attached list

[ ] Completed

Record kWp in Notes

[ ] Completed

Record Torque in Notes

[ ] Completed

Record V

DC

in Notes

[ ] Completed

Record V

AC

in Notes

[ ] Good [ ] Poor

.49.

PROJECT NAME

LOCATION NUMBER

INSTALLATION AND 3 PHASE STRING INVERTERS

(KTL SERIES)

COMMISSIONING CHECKLIST

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Step No.

Content Details

1

Communication cable (if function is used)

Connect the RS485 cable to the communication port.

Values / Notes Conclusion

[ ] Completed

2

Supply DC /

AC power

CSI-xx-KTL-G I :

1. Switch the grid supply main Switch (AC) ON f irst.

2. Switch the DC switch ON. If the voltages of PV arrays are higher than start up voltage, the inverter will turn on. The red LED power will be continuously lit.

3. When both the DC and the AC sides supply to the inverter, it will be ready to generate power. Initially, the inverter will check both its internal parameters and the parameters of the AC grid, to ensure that they are within the acceptable limits. At the same time, the green

LED will lash and the LCD displays the information of INITIALIZING.

.50.

www.canadiansolar.com

Please return completed form to [email protected]

[ ] Completed

Record LEDs status in Notes

.51.

PROJECT NAME

LOCATION NUMBER

INSTALLATION AND 3 PHASE STRING INVERTERS

(KTL SERIES)

COMMISSIONING CHECKLIST

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

Step No.

Content Details Values / Notes Conclusion

3 Waiting time

CSI-xx-KTL-G I : After 6 030 0 seconds (depending on local requirement), the inverter will start to generate power.

The green LED will be on continuously and the LCD displays the information of GENERATING.

[ ] Completed

Record LEDs status in Notes

4 Power generation After grid connection, record power output of inverter.

5

Date & Time setting

6

Communication setting (if avail.)

7 Machine version

8

9

10

Operating parameter

Testing

Completion

Set the current date and time using the front panel interface.

Set communication with a unique address for each inverter.

For maintenance and reference, please record the f irmware revisions if applicable.

Record operating parameters of the inverter.

Verify IEC62109 or the corresponding On-grid setting is selected.

De-rate inverter and attach de-rate sticker as required.

Open and close the DC breaker to conirm whether the inverter reboots and shuts down automatically.

Installation and commissioning is complete if no abnormality.

.52.

www.canadiansolar.com

Please return completed form to [email protected]

[ ] Completed

Record power in Notes

[ ] Completed

Record current date/time in Notes

[ ] Completed

Record address in Notes

[ ] Completed

Record with serial numbers

[ ] Completed

Record operating parameters in Notes

[ ] Reboot successful

[ ] Not rebooting

[ ] Good

[ ] Issues detected

.53.

PROJECT NAME

LOCATION NUMBER

INSTALLATION AND 3 PHASE STRING INVERTERS

(KTL SERIES)

COMMISSIONING CHECKLIST

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

System Owner:

Note site typical arrangements and variances

Inverter f irmware revision: DSP:

Address / Location:

Inverter model:

Number of inverters:

Output power*:

Grid: V Max: V Min:

Con f iguration: MPPT Individual

Monitoring: RS485:

PV module manufacturer:

Inverter mounting tilt:

Input DC voltage:

Frequency Max: Min:

MPPT Parallel

Ethernet:

PV model:

DC cable size: AC cable size:

Number of series connected modules in PV strings:

Number of PV strings in parallel per MPPT:

Total System size (DC Watts):

Insulation limit (K):

Reactive compensation:

Monitoring equipment and supplier:

Transformer ratings, supplier:

LCD:

PV start-up voltage:

+/- PF

*Specify de-rated power and add nameplate power in parenthesis

GENER AL COMMENTS / OBSERVATIONS:

.54.

www.canadiansolar.com

Please return completed form to [email protected]

.55.

PROJECT NAME

LOCATION NUMBER

INSTALLATION AND 3 PHASE STRING INVERTERS

(KTL SERIES)

COMMISSIONING CHECKLIST

Warning: This checklist is not a replacement for the user manual.

Please read the user manual prior to inverter site selection and installation.

16

17

18

19

20

21

12

13

14

15

8

9

10

11

6

7

4

5

2

3

Inverter serial numbers:

1

34

35

36

37

30

31

32

33

38

39

40

41

42

26

27

28

29

22

23

24

25

INSTALLER´S NAME

INSTALLER´S SIGNATURE

.56.

www.canadiansolar.com

COMPANY

DATE

Please return completed form to [email protected]

.57.

advertisement

Related manuals

Download PDF

advertisement