Graco 308504C H 2 O PRO Continuous Flow System Owner's Manual

Add to My manuals
48 Pages

advertisement

Graco 308504C H 2 O PRO Continuous Flow System Owner's Manual | Manualzz

INSTRUCTIONS-PARTS LIST

This manual contains important warnings and information.

READ AND KEEP FOR REFERENCE.

INSTRUCTIONS

H

2

O PRO

Continuous Flow System

100 psi (7 bar) Maximum Working Air and Fluid Pressure

Part No. 237–928

Waterborne Voltage Block

For use with Graco PRO 5500wb and PRO

3500wb guns when electrostatically spraying conductive, waterborne fluids that meet at least one of the following conditions of nonflammability:

1. The fluid has a flash point above 140 F

(60 C) and a maximum organic solvent concentration of 20%, by weight, as determined in accord with the Standard Method of Testing for Flash Point by the Pensky-

Martens Closed Tester, ASTM D93.

2. The fluid does not sustain burning characteristics in accordance with the Standard

Method for Sustained Burning of Liquid

Mixtures by the Setaflash Apparatus,

ASTM D4206.

U.S. Patent No. 5,526,986

308–504

Rev. C

Supersedes B

GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440–1441

COPYRIGHT 1995, GRACO INC.

Graco Inc. is registered to I.S. EN ISO 9001

Table of Contents

Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Voltage Block Component Identification

Sequence of Operation

. . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . .

7

10

Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Warning Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Ventilate the Spray Booth

Fluid Supply Unit

. . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . . . .

Air Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Leveling the Voltage Block . . . . . . . . . . . . . . . . . .

Remote Terminal Strip . . . . . . . . . . . . . . . . . . . . . .

Interlock the Gun Turbine Air Supply . . . . . . . . .

Connect the Hoses

Ground the System.

. . . . . . . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . .

Check the System Grounding . . . . . . . . . . . . . . .

13

13

14

16

16

12

12

12

12

12

12

Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fluid Voltage Discharge and Grounding

Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pressure Relief Procedure . . . . . . . . . . . . . . . . . .

Emergency Fluid Shutoff

Operating Checklist

. . . . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . . . .

18

18

20

20

20

Voltage Block Startup Procedure

Operating the Voltage Block

. . . . . . . . . . . .

. . . . . . . . . . . . . . . . .

Flushing and Shutdown . . . . . . . . . . . . . . . . . . . .

21

22

23

Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cycle Counting . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TSL System Maintenance . . . . . . . . . . . . . . . . . .

Drain and Flush the TSL System

PTFE Tubing Replacement

. . . . . . . . . . . .

. . . . . . . . . . . . . . . .

Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Isolator Service . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Accumulator Service . . . . . . . . . . . . . . . . . . . . . . .

24

27

27

27

28

28

29

29

34

Voltage Block Assembly Parts . . . . . . . . . . . . . . . .

Accumulator Assembly Parts

Isolator Assembly Parts

. . . . . . . . . . . . . . . . .

. . . . . . . . . . . . . . . . . . . . . .

Air Logic Schematic and Parts . . . . . . . . . . . . . . . .

38

42

44

46

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

The Graco Warranty and Disclaimers . . . . . . . . . .

Graco Phone Number . . . . . . . . . . . . . . . . . . . . . . . .

47

47

48

48

2 308–504

Warning Symbol

WARNING

This symbol alerts you to the possibility of serious injury or death if you do not follow the instructions.

Symbols

Caution Symbol

CAUTION

This symbol alerts you to the possibility of damage to or destruction of equipment if you do not follow the instructions.

WARNING

FIRE AND EXPLOSION HAZARD

Improper grounding, poor air ventilation, open flames, or sparks can cause a hazardous condition and result in a fire or explosion.

Electrostatic equipment must be used only by trained, qualified personnel who understand the requirements stated in this instruction manual.

Ground the equipment, personnel in or close to the spray area, the object being sprayed, and all other electrically conductive objects in the spray area. See Ground the System on page 16.

Provide fresh air ventilation to avoid the buildup of toxic vapors. Interlock the automatic gun air supply to prevent operation of the power supply unless the ventilating fans are on. See Ventilate the Spray Booth on page 12.

Only use this equipment to spray non-flammable, waterborne fluids, as defined on the front cover of this manual.

Only flush, purge, or clean the electrostatic, waterborne spray system with non-flammable fluids, as defined on the front cover of this manual.

Do not flush the system with the gun electrostatics turned on.

Use only non-sparking tools to clean residue from the booth and hangers.

Extinguish all open flames or pilot lights in the spray area.

Keep the spray area free of debris, including solvent, rags, and gasoline.

Do not store any flammable fluids in the spray area.

Do not turn on or off any light switch in the spray area while operating or if fumes are present.

Do not smoke in the spray area.

Do not operate a gasoline engine in the spray area.

Warnings are continued on the next page.

308–504 3

ELECTRIC SHOCK HAZARD

WARNING

Improper grounding or an improper setup and usage of the voltage block system can cause a hazardous condition and result in an electric shock or other serious injury.

Ground the equipment, personnel in or close to the spray area, the object being sprayed, and all other electrically conductive objects in the spray area. See Ground the System on page 16.

The components of the voltage block system that are charged with high voltage when the spray gun is operating are inside the voltage block enclosure to make these components inaccessible to personnel and prevent electric shock. The enclosure door must be closed when any gun connected to the system is operating. The enclosure door has a switch that moves the isolator to discharge the voltage if the door is opened, which helps prevent personnel from making contact with the components when they are charged with high voltage. Do not tamper with or bypass the door switch or other safety devices.

The automatic gun air supply must be interlocked with the voltage block system to shut off the turbine air supply whenever the enclosure door is opened.

Only use the red-colored Graco electrically conductive gun air hose with this system. Do not use the black or grey-colored Graco air hoses.

The areas of the Graco waterborne fluid hose that are accessible to the personnel must be covered by the conductive, grounded hose layer. The area on the hose that is not covered by the conductive hose layer must be inside the voltage block system enclosure.

Install only one continuous Graco waterborne fluid hose between the voltage block system and the spray gun. Do not splice hoses together.

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 when instructed to discharge the voltage; before cleaning, flushing, or servicing the system; before approaching the gun; and when opening the voltage block enclosure door.

Do not touch the gun electrode or come within 4 inches (101.6 mm) of the nozzle during gun operation until the Fluid Voltage Discharge and Grounding Procedure , page 18, has been completed.

Do not enter a high voltage or hazardous area until all high voltage equipment has been discharged.

If there is any static sparking while using the equipment, stop spraying immediately . Identify and correct the problem.

Follow the warnings and instructions in the spray gun manual.

PRESSURIZED EQUIPMENT HAZARD

Spray from the gun, hose leaks, or ruptured components can splash fluid in the eyes or on the skin and cause a serious injury.

Do not stop or deflect fluid leaks with your hand, body, glove, or rag.

Follow the Pressure Relief Procedure on page 20 whenever you: are instructed to relieve the pressure; stop spraying; clean, check, or service the equipment; and install or clean the fluid nozzles.

Tighten all the fluid connections before each use.

Check the hoses, tubes and couplings daily. Replace worn, damaged, or loose parts immediately.

Permanently coupled hoses cannot be repaired; replace the entire hose.

Warnings are continued on the next page.

4 308–504

WARNING

EQUIPMENT MISUSE HAZARD

INSTRUCTIONS

Equipment misuse can cause the equipment to rupture, malfunction, or start unexpectedly and result in a serious injury.

Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system.

This equipment is for professional use only.

Read all the instruction manuals, tags, and labels before operating the equipment.

Use the equipment only for its intended purpose. If you are uncertain about usage, call your Graco distributor.

Do not alter or modify this equipment. Use only genuine Graco parts and accessories.

Check the equipment daily. Repair or replace worn or damaged parts immediately.

Do not exceed the maximum working pressure of the lowest rated system component. This equipment has a 100 psi (7 bar) maximum working air and fluid pressure .

Do not lift pressurized equipment.

Use fluids that are compatible with the equipment wetted parts. See the Technical Data section of all the equipment manuals. Read the fluid manufacturer’s warnings. Do not use MEK or any ketone solvent mixture to flush the system.

Route the hoses away from traffic areas, sharp edges, moving parts, and hot surfaces. Do not expose Graco hoses to temperatures above 180 F (82 C) or below –40 F (–40 C).

Do not use the hoses to pull equipment.

Comply with all applicable local, state, and national fire, electrical, and other safety regulations.

TOXIC FLUID HAZARD

Hazardous fluids or toxic fumes can cause a serious injury or death if splashed in the eyes or on the skin, swallowed, or inhaled.

Know the specific hazards of the fluid you are using. Read the fluid manufacturer’s warnings.

Store hazardous fluid in an approved container. Dispose of the hazardous fluid according to all local, state, and national guidelines.

Wear appropriate protective clothing, gloves, eyewear, and respirator.

MOVING PARTS HAZARD

Moving parts can pinch or amputate fingers. Keep clear of moving isolator parts.

308–504 5

6 308–504

Voltage Block Component Identification

20 Fluid Pressure Air Pilot Regulator

The air pilot regulator is used to adjust the pressure setting of the fluid regulator (2) at the voltage block fluid outlet.

72

20

A B C

Fig. 1

05316

See Fig. 1. Refer to Fig. 2 and 3.

A Fill/Run Button

The Fill/Run Button is pressed to initially fill the accumulators (74) or restart operation after a period when spraying had stopped or the door has been opened.

B Flush/Reset Button

The Flush/Reset Button has the following uses:

To reset the air logic assembly (99) components when initially starting the system or when the air logic was shut down due to air supply depressurization.

To pressurize the accumulators (74) to prepare to flush the system.

To prepare to empty the accumulators (74) and depressurize the voltage control fluid section before shutting down the system.

To stop the filling process.

C Optional kV Display (purchased separately)

The kV display, part no. 238–095, is an accessory that can be added to the voltage block to provide a system voltage reading.

72 Fluid Pressure Gauge

The gauge shows the air pilot regulator (20) pressure, which controls the fluid regulator (2) pressure.

See Fig. 2

YY Remote Terminal Strip

The remote terminal strip provides 8 ports for sending input or output signals to operate the system remotely.

See page 13.

ZZ Optional Pneumatic Counter Kit (purchased separately)

The pneumatic counter kit, part no. 238–026, counts the number of isolator cycles for maintenance tracking.

99 Air Logic Assembly

The air logic assembly is mounted inside, on the enclosure door. It receives and sends signals that enable the voltage block to operate properly. No adjustments to the air logic assembly are necessary. Do not alter components or connections.

Fig. 2

ZZ

YY

99

05826

308–504 7

Voltage Block Component Identification

13 22 90 91 76 77 53

75

103

74

43

106

D

2

SIDE 1 SIDE 2

Fig. 3

See Fig. 3

D Graco Waterborne Fluid Hose (purchased separately)

A Graco waterborne fluid hose must be used between the voltage block fluid regulator (2) outlet and the spray gun. This fluid hose consists of three layers (see

Fig. 5, page 15):

Inner Hose Layer: is a PTFE tube.

Conductive Hose Layer: covers the PTFE tube.

Outer Hose Jacket: is a protective polyethylene hose cover.

If a hose failure occurs, where the high voltage arcs through the PTFE core, the voltage will be discharged to ground through the conductive hose layer. When properly installed, the hose is grounded through its connection to the enclosure. All areas of the fluid hose that are accessible to personnel must be covered by the conductive hose layer.

05815A

2 Fluid Regulator

The voltage block fluid regulator regulates the fluid pressure to the gun. The setting is adjusted with the air pilot regulator (20–see Fig. 1). A small air bleed hole constantly bleeds the pilot air for fluid control accuracy.

13 Air Inlet Quick-disconnect

The connector for the voltage block air supply hose.

The quick-disconnect allows for quick disconnection of the air line to shutdown the system in an emergency.

22 Voltage Block Air Pressure Regulator

This air regulator is used to adjust air pressure to the voltage block components.

8 308–504

Voltage Block Component Identification

See Fig. 3

43 Voltage Bleed Resistor

The voltage bleed resistor completely bleeds off the voltage from the gun in about 30 seconds after the gun trigger is released. The actual time depends on the hose length.

76 Full Level Switch

When the accumulator (74) is filling, the full level switch sets the maximum amount of fluid the accumulator will allow. To reduce the number of times the accumulator has to refill and decrease the wear on the equipment, set the full level at the highest setting.

53 Door Switch

When the enclosure door is opened, the door switch signals the isolator (75) to ground the fluid in the voltage block and bleed off the high voltage.

77 Low Level Switch

When the fluid in the accumulator (74) reaches this switch and the gun is triggered, the Voltage Block will begin supplying fluid to the spray gun from the second accumulator and will also refill the accumulator that is low on fluid.

90 TSL Pump

The TSL pump circulates the TSL through the isolator

(75) fluid block and seals.

74 Accumulator

The accumulator is a container inside the voltage block enclosure (106). It fills with fluid from the fluid supply unit and supplies that fluid to the spray gun. The accumulator has a full level switch (76) and low level switch (77) for the fluid.

91 TSL Container

The TSL container contains throat seal liquid (TSL) to lubricate the isolator (75) rod and seals.

103 Fluid Inlet Connector

The connector for the voltage block fluid supply hose.

75 Isolator

The isolator can move up or down on the isolator rod.

The position the isolator is in depends on which operating phase the voltage block is in.

106 Enclosure

The enclosure houses the internal components of the voltage block and helps prevent personnel from coming in contact with the components when they are charged with high voltage.

Spraying Position: is the upward position of the isolator. This position isolates the waterborne fluid in the accumulator (74) (which is connected to the isolator) from the fluid supply (which is at ground) and enables the fluid to be sprayed electrostatically.

See Fig. 4, page 15

25 Ground Lug

The ground lug is used to ground the voltage block by connecting the main ground wire (123) between the lug and a true earth ground.

Fill Position: is the downward position of the isolator. In this position, the valve in the isolator rod opens so the accumulator (74) can be refilled by the fluid supply.

123 Main Ground Wire

The ground wire is connected between the ground lug

(25) and a true earth ground.

308–504 9

Sequence of Operation

The following charts show the sequence of how the system or voltage block operates during various operation modes. The charts do not cover how to actually operate the system or voltage block. For operating instructions, see the Operation section.

NOTE: Refer to Fig. 3, page 8.

Key:

Vented – accumulator is filling

Pressurized – accumulator is dispensing fluid

Air Blocked – accumulator piston is holding its current position, it is neither filling or dispensing.

FILL/RUN

FILL Sequence

Operation

1.

Accumulator 1 starts filling

Isolator 1

Position down

2.

Accumulator 1 is full down

3.

Accumulator 1 dispenses to Accumulator 2 up

4.

Accumulator 2 is full up

5.

Accumulator 1 starts refilling down

6.

Accumulator 1 is full up

7.

System is ready to spray up

Accumulator 1 Isolator 2

Position vented up vented pressurized pressurized vented pressurized pressurized up down down up down down

Accumulator 2 pressurized pressurized vented air blocked air blocked air blocked air blocked

RUN Sequence

Operation Isolator 1

Position up 1.

Accumulator 1 dispenses to spray gun

2.

Accumulator 1 is empty down

3.

Accumulator 2 dispenses to spray gun while Accumulator 1 starts refilling down

4.

Accumulator 1 is full down

5.

Accumulator 1 dispenses to spray gun and refills Accumulator 2 up

6.

Accumulator 2 is full up

Accumulator 1 Isolator 2

Position pressurized down vented vented vented pressurized pressurized up up up down down

Accumulator 2 air blocked pressurized pressurized pressurized vented air blocked

7.

Operation continues with the Run Sequence, steps 2 to 6, until the operator stops spraying

10 308–504

Sequence of Operation

FLUSH/RESET

FLUSH

Sequence– through gun

Operation Isolator 1

Position

1.

Both accumulators dispense to spray gun

2.

Both accumulators are empty

3.

Water supply flushes through the system until clear fluid is seen

4.

Voltage block remains in this mode until the fill sequence is activated up down down down

Accumulator 1 Isolator 2

Position pressurized pressurized pressurized pressurized down down down down

Accumulator 2 pressurized pressurized pressurized pressurized

Paint Saver

This operation sequence pushes the fluid in the accumulator back into the fluid supply to help save fluid. Refer to page 23.

Paint Saver

Sequence

Operation Isolator 1

Position down 1.

Both accumulators dispense their fluid back to the depressurized fluid supply or to a container

2.

Both accumulators are empty

3.

Remains in this mode until the enclosure door is closed and the

Fill/Run button is pressed.

down down

Accumulator 1 Isolator 2

Position pressurized down pressurized pressurized down down

Accumulator 2 pressurized pressurized pressurized

308–504 11

Installation

IMPORTANT:

Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system. The instructions in this manual are based on a typical system, where one of these Graco guns would be used.

Electrically interlock the gun air supply with the ventilators to prevent operation of the electrostatic power supply unless the ventilating fans are on.

WARNING

ELECTRIC SHOCK HAZARD

Installing and servicing this equipment requires access to parts which could cause an electric shock or other serious injury if the work is not performed properly.

Check and follow all local, state, and national codes regarding air exhaust velocity requirements. High velocity air exhaust will decrease the operating efficiency of the electrostatic system. The minimum allowable air exhaust velocity is 60 ft./min. (19 linear meters/min.).

Fluid Supply Unit

Do not install or service this equipment unless you are trained and qualified.

Comply with all local, state, and national codes for the installation of electrical apparatus in a

Class , Group D, Hazardous Location.

Comply with all applicable local, state, and national fire, electrical, and other safety regulations.

WARNING

COMPONENT RUPTURE HAZARD

To reduce the risk of serious injury due to component rupture, do not exceed the maximum working pressure of the lowest rated system component. This equipment has a

100 psi (7 bar) maximum air and fluid working pressure .

Warning Signs

Mount the warning sign, part no. 186–118 (included with the PRO 5500wb automatic gun or PRO 3500wb hand-held gun), in the spray area where it can easily be seen and read by all operators. Read the warning and instruction labels on the enclosure. Additional warning labels and signs are available at no charge.

Ventilate the Spray Booth

Follow the installation instructions in the manual for your fluid supply unit. It is recommended that the fluid be filtered with a 60 mesh filter.

Air Supply

The air supply must be filtered and dry for the voltage block to operate properly. At a minimum, use a 40 micron filter. A Graco air filter, part no. 106–148, is available.

WARNING

TOXIC FLUID HAZARD

Provide fresh air ventilation to avoid the buildup of toxic vapors. The gun air supply must be interlocked with the ventilators to prevent operation of the electrostatic power supply unless the ventilating fans are on.

Leveling the Voltage Block

The voltage block must be level to ensure proper alignment of the door latches and for system stability.

Loosen the jam nut (86) and adjust the leg leveler (12) until the voltage block is level. See the parts drawing on page 38.

12 308–504

Installation

Remote Terminal Strip

The remote terminal strip is mounted on the inside of the clear plastic cover that covers the air logic assembly. See Fig. 2, page 7. There are 8 ports available to connect to for sending or receiving air signals to operate the system remotely from an external control, such as a PLC (programmable logic controller) system.

Use polyethylene, 5/32 in. (4 mm) O.D., tubing for connection to the terminal strip ports. This tubing is available from Graco in 100 ft. (30.5 m) lengths. The chart below shows the part numbers and colors.

#4 FLUID PRESSURE: Accepts an input air signal from an external source that duplicates the air pressure setting from the air pilot regulator on the voltage block door, which controls the fluid regulator.

#5 READY TO FLUSH: Sends an output air signal to an external controller or indicator to signal when both of the accumulators have dispensed the fluid and are in their empty position, ready for water flushing.

Tubing Part No.

054–730

054–731

054–732

054–733

054–734

Color

Natural (clear)

Blue

Red

Yellow

Black

#6 READY TO SPRAY: Sends an output air signal to an external controller or indicator to signal when both of the accumulators are full and have actuated their full level switches.

#7 DOOR OPEN: Sends an output air signal to an external controller or indicator to signal when the door switch is activated “open” and it is an unsafe condition for spraying.

NOTE: See page 46 for the air logic assembly schematic.

The 8 ports are labeled in the air logic circuit as:

#1 FILL/RUN: Accepts an input air signal (minimum

60 psi [4.1 bar]) from an external source that duplicates the FILL/RUN button on the voltage block door.

#8 VOLTAGE DUMP: Accepts an input air signal from an external source that duplicates the door open switch operation that sends both of the isolators down to immediately ground out the high voltage charge of the fluid.

Interlock the Gun Turbine Air Supply

#2 FLUSH/RESET: Accepts an input air signal (minimum 60 psi [4.1 bar]) from an external source that duplicates the FLUSH/RESET button on the voltage block door.

#3 QUICK DUMP: Accepts an input air signal (minimum 60 psi [4.1 bar]) from an external source that duplicates the function of opening the voltage block door to initiate the “paint saver” option. In order for this function to operate, the installation must also be set up to activate color change valves to close the paint inlet line and open a dump valve line.

WARNING

ELECTRIC SHOCK HAZARD

If the PRO 5500wb Automatic Gun is being used, the turbine air supply must be interlocked with the voltage block system to shut off the turbine air supply anytime the voltage block door is opened. The remote terminal strip must be used to interlock the turbine air supply and the voltage block door, by using the door open port (see description of port #7, above).

To reduce the risk of an electric shock, do not tamper with or bypass the air line interlock.

308–504 13

Connect the Hoses

Installation

3. Connect the gun air supply line(s) as instructed in the gun manual.

WARNING

ELECTRIC SHOCK HAZARD

To reduce the risk of an electric shock:

Install only one continuous Graco waterborne fluid hose between the voltage block and the spray gun. Do not splice hoses together.

The areas of the waterborne fluid hose that are accessible to personnel during normal operation must be covered by the outer hose jacket (FF).

See Fig. 5.

WARNING

ELECTRIC SHOCK HAZARD

To reduce the risk of an electric shock or other serious injury, you must use the red Graco Electrically Conductive Air

Hose for a hand-held gun’s air supply hose or for an automatic gun’s turbine air hose, and you must connect the hose ground wire to a true earth ground. Do not use the black or grey-colored Graco air hoses.

NOTE: If multiple automatic gun operation is needed, contact your Graco representative for ordering requirements for the Multiple Gun Fluid Manifold Kit, part no. 237–965, for the PRO 5500wb Automatic

Guns.

WARNING

ELECTRIC SHOCK HAZARD

The Multiple Gun Fluid Manifold Kit can only be used with automatic guns. Regulations applying to this type of equipment prohibit the use of multiple hand-held guns.

Graco Electrically Conductive Air Hose Part Numbers

100 psi (7 bar) Maximum Working Pressure

Conductive SST wire braid for grounding; polyurethane tube and cover; 0.315 inch I.D.; 1/4 npsm(f) x 1/4 npsm(f) left-hand thread; the hose is color-coded red

Part No.

235–068

235–069

235–070

235–071

235–072

235–073

235–074

Length

6 ft. (1.8 m)

15 ft. (4.6 m)

25 ft. (7.6 m)

36 ft. (11.0 m)

50 ft. (15.2 m)

75 ft. (23.0 m)

100 ft. (30. 5 m)

4. Loosen the fluid hose ferrule nut (8) and hose compression nut (AA). See Fig. 5.

1. Connect the air supply hose between the air supply and the air inlet quick-disconnect (13). See

Fig. 4.

5. Install the Graco waterborne fluid supply hose through the fluid hose port (P) in the enclosure and into the fluid regulator fitting (49). See Fig. 4 and 5.

2. Connect the fluid supply hose between the grounded fluid supply and the 3/8 npsm voltage block fluid inlet (103). Use a 5/16 in. (7.9 mm) or

3/8 in. (9.5 mm) I.D. hose for minimal pressure drop.

6. Hand-tighten the hose compression nut (AA) securely. See Fig. 5.

NOTE: The two hose ferrules (BB & CC) must be orientated as shown in Fig. 5, with the taper of the solid ferrule (BB) facing toward the fluid regulator (2) and the taper of the split ferrule (CC) facing away from the fluid regulator.

Graco Waterborne Fluid Hoses Part Numbers

100 psi (7 bar) Maximum Working Pressure

0.25 in. (6.35 mm) I.D.; PTFE

Spray Gun Model Hose Part No.

Length

Manual PRO

3500wb Spray Gun

Automatic PRO

5500wb Spray Gun

237–924

237–925

237–926

237–920

237–921

237–922

25 ft. (7.6 m)

36 ft. (11.0 m)

50 ft. (15.2 m)

25 ft. (7.6 m)

36 ft. (11.0 m)

50 ft. (15.2 m)

7. The hose ferrule nut (8) grounds the conductive layer (DD) of the Graco waterborne fluid hose and provides strain relief for the hose. See Fig. 5.

Tighten the hose ferrule nut securely.

8. Connect the other end of the fluid hose to the gun fluid inlet. Read the instructions on fluid hose connection in your gun manual.

14 308–504

KEY-Fig. 4

N True Earth Ground

P Enclosure Fluid Hose Port

13 Voltage Block Air Inlet (quick-disconnect)

22 Voltage Block Air Regulator

25 Ground Lug

Installation

49 Fluid Regulator Nut

103 Voltage Block Fluid Inlet

119 Main Ground Wire Clamp

123 Main Ground Wire

22

106

25

13

123

119

N

103

2

49

P

05318

Fig. 4

KEY-Fig. 5

AA Hose Compression Nut

BB Hose Ferrule

CC Hose Ferrule

DD Conductive Hose Layer

EE Inner Hose Layer

FF Outer Hose Jacket

8 Hose Ferrule Nut

2 Fluid Regulator

49 Fluid Regulator Fitting

106 Voltage Block Enclosure

The areas of the waterborne fluid hose that are accessible to personnel during normal operation must be covered by the outer hose jacket (FF).

The portion of the inner hose layer (EE) that is not covered by the outer hose jacket (FF) must be inside the enclosure (106).

2

Fig. 5

49 BB CC 8 FF

AA EE DD

106

05375

308–504 15

Ground the System

See Fig. 4

Installation

2.

Fluid Supply: Ground the fluid supply by connecting a ground wire and clamp. See your fluid supply instruction manual for grounding instructions.

WARNING

FIRE, EXPLOSION, AND ELECTRIC

SHOCK HAZARD

When operating the electrostatic gun, any ungrounded objects in the spray area (such as people, containers, tools, etc.) can become electrically charged.

Improper grounding can result in static sparking, which can cause a fire, explosion, or electric shock. Follow the grounding instructions below.

The following grounding instructions are minimum requirements for a basic electrostatic, waterborne system. Your system may include other equipment or objects which must be grounded. Check your local electrical code for detailed grounding instructions for your area and type of equipment. Your system must be connected to a true earth ground.

3.

Gun Air Supply Hose or Turbine Air Supply on the PRO 5500wb Automatic Gun: You must use the red-colored Graco electrically conductive gun air hose . Do not use the black or grey-colored

Graco air hoses. Ground the hose by connecting the air hose ground wire to a true earth ground.

4.

Graco PRO 5500wb or PRO 3500wb

Spray Gun: Ground the gun by connecting the grounded red-colored Graco electrically conductive air hose to the gun. Check the electrical grounding of the gun as instructed in the spray gun manual.

5.

Graco Waterborne Fluid Hose: The hose must be properly grounded as instructed on page 14 and in the spray gun manual.

1.

Voltage Block: Connect one end of the main ground wire (123), which is included with the system, to the ground lug (25) on the outside of the voltage block enclosure. Connect the other end of the ground wire to a true earth ground (N).

6.

All persons entering the spray area: Their shoes must have conductive soles, such as leather, or personal grounding straps must be worn. Rubber or plastic soles are not conductive.

Do not disconnect or tamper with the internal ground wire connections (W) inside the voltage block enclosure. They should be connected as shown in Fig. 6.

W

7.

Object being sprayed: Keep the workpiece hangers clean and grounded at all times. Contact points must be sharp points or knife edges.

8.

The floor of the spray area: The floor must be electrically conductive and grounded. Do not cover the floor with cardboard or any non-conductive material which would interrupt grounding continuity.

W

Fig. 6

9.

All electrically conductive objects or devices in the spray area: They must be properly grounded.

05822A

Check the System Grounding

After grounding the system , check the resistance between the exterior of the voltage block enclosure and a true earth ground. The resistance must be less than 20 ohms.

16 308–504

Notes

308–504 17

Operation

WARNING

ELECTRIC SHOCK HAZARD

The voltage block door switch helps to prohibit personnel from making contact with the enclosed voltage block components before the system voltage is discharged. To reduce the risk of an electric shock, do not tamper with or bypass the voltage block door switch.

For Manual Spray Guns

1. Turn off the gun electrostatics. If the PRO 3500wb is being used, turn the ES lever on the gun to the

OFF position.

2. Wait at least 30 seconds for the voltage to discharge through the voltage block bleed resistor. If the voltage block has the optional kV meter, wait until the meter registers zero kV before proceeding.

IMPORTANT: Only use the Graco PRO 5500wb automatic gun or PRO 3500wb hand-held gun with this system. The instructions in this manual are based on a typical system, where one of these Graco guns would be used.

NOTE: When the voltage block is used with a 60 kV

Graco spray gun, the typical “actual” voltage on the voltage block system is in the 45 to 55 kV range when the gun tip is at least 1 ft. (305 mm) away from a grounded object.

Fluid Voltage Discharge and Grounding

Procedure

WARNING

ELECTRIC SHOCK HAZARD

The voltage block is charged with high voltage until the voltage is discharged.

Contact with the charged components of the isolation system or spray gun will cause an electric shock. To avoid an electric shock, follow the Fluid Voltage Discharge and Grounding

Procedure : when instructed to discharge the voltage, before cleaning, flushing, or servicing the system equipment, before approaching the gun, and before opening the voltage block door.

3. Touch the electrode of the gun with a grounded rod to make sure that the voltage has been discharged. If an arc is seen, verify that the electrostatics are turned off or see Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding.

4. Cleaning or typical adjustments of the gun, such as air cap positioning or cleaning, can be made after completing step 3. Before doing further service, such as gun or voltage block servicing, complete steps 5 and 6.

5. Unscrew the voltage block door latches to bring the isolators down and ground the high voltage charge of the fluid.

6. Touch the wire connector (R) of the fluid regulator with a grounded rod to make sure that the voltage has been discharged. See Fig. 7. If an arc is seen, see Troubleshooting , page 25, or your gun instruction manual for other possible problems.

Resolve the problem before proceeding.

NOTE: After service is complete and the doors are closed, the FILL/RUN button must be pressed to restart operation.

NOTE:

The metal enclosure of the H

2

O PRO voltage block is always grounded if properly connected to a true earth ground by the main ground wire.

An accessory grounding rod, part no. 210–084, is available to discharge any voltage remaining on a system component. Contact your Graco representative to order it.

Fig. 7

R

05816

18 308–504

Operation

Fluid Voltage Discharge and Grounding

Procedure (continued)

For Automatic Spray Guns

1. Turn off the gun electrostatics to all the spray guns connected to the voltage block.

2. Unscrew the voltage block door latches to bring the isolators down and ground the high voltage charge of the fluid.

3. Touch the wire connector (R) of the fluid regulator with a grounded rod to make sure that the voltage has been discharged. See Fig. 7. If an arc is seen, see Troubleshooting , page 25, or your gun instruction manual for other possible problems.

Resolve the problem before proceeding.

4. If servicing the spray gun(s), touch the electrode of the gun with a grounded rod to make sure that the voltage has been discharged. If an arc is seen, verify that the electrostatics are turned off or see

Troubleshooting , page 25, or your gun instruction manual for other possible problems. Resolve the problem before proceeding.

NOTE: After service is complete and the doors are closed, the FILL/RUN button must be pressed to restart operation.

308–504 19

Pressure Relief Procedure

Operation

Emergency Fluid Shutoff

Use this procedure if rapid fluid depressurization is needed, such as in the case of a hose leak.

WARNING

PRESSURIZED EQUIPMENT HAZARD

The system pressure must be manually relieved to prevent the system from starting or spraying accidentally. To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure whenever you: are instructed to relieve the pressure, stop spraying, check or service any of the system equipment, or install or clean the spray nozzle.

1. Disconnect the air line from the voltage block quick-disconnect air inlet. The air pressure will bleed off to zero.

2. Turn the fluid supply unit off. The accumulator pistons will slowly rise until the fluid and air pressures are both at zero.

Operating Checklist

Check the following list daily, before starting to operate the system, to help ensure safe, efficient operation.

1. Follow the Fluid Voltage Discharge and

Grounding Procedure , page 18.

____ 1. Be sure all the operators are properly trained to safely operate an electrostatic, waterborne, air spray system as instructed in this manual and the gun manual.

2. Shut off the fluid supply to the voltage block.

____ 2. Be sure all the operators are trained how to properly relieve system pressure as instructed at left and in the gun manual.

3. Shut off the air supply to the voltage block. The shut-off device must bleed the air out of the system.

____ 3. Be sure all the operators are trained how to properly discharge the voltage as instructed on page 18.

4. Trigger the gun(s) to relieve the pressure in the fluid lines.

5. For automatic guns, shut off any other air supplies to the spray gun(s). Use bleed-type shut-off valves to relieve the pressure in the air lines.

____ 4. Be sure the system is thoroughly grounded and the operator and all persons entering the spray area are properly grounded. See

Ground the System , page 16.

____ 5. Be sure the ventilation fans are operating properly.

NOTE: After service is complete and the doors are closed, press the FLUSH/RESET button, then press the FILL/RUN button to restart operation.

____ 6. Be sure all the debris, including flammable liquids and rags, is removed from the spray area.

20 308–504

Operation

Voltage Block Startup Procedure

1. Install and ground the system as instructed in the

Installation section.

6. Repeatedly push the manual switch button near the TSL pump (90) until all air is purged out through the tubing. Refer to Fig. 3, page 8.

2. Remove the TSL containers (91) and fill them about 1/2 full with the TSL provided. Refer to Fig.

3, page 8.

3. If adjusting the position of the accumulator full level switch (76), be sure to push the switch bracket (AB) fully to the left and hold it in place until the screws (39) are tight. See Fig. 8.

CAUTION

Make sure that the fluid inlet pressure is a minimum of 5 psi (0.35 bar) lower than the set operating pressure of the voltage block or the accumulators will fill during step 6.

7. Connect a water supply to the voltage block.

AB

76

8. Set the fluid outlet pressure to the gun by adjusting the air pilot regulator (20) on the front cover of the voltage block. See Fig. 10.

39

NOTE: The voltage block fluid inlet pressure will affect the accumulators fill time only.

Fig. 8 05894

4. If using a hand-held gun, remove the air cap from the gun.

5. With the voltage block door open, turn on the air to the voltage block. Set the air pressure between 80 to 100 psi (5.6 to 7 bar).

The air inlet pressure is set with the air regulator

(22) installed at the voltage block air inlet. See Fig.

9.

NOTE: Be sure to turn on the air to the voltage block before pressing the FLUSH/RESET button or the system components will not operate.

9. Trigger the gun until all the air is purged through the voltage block and fluid lines.

10. If desired, check the voltage block operation or check for fluid leaks with water before connecting the paint line. Close the door and press the FILL/

RUN button (A) to fill and dispense the accumulators. See Fig. 10. Press the FLUSH/RESET button

(B), and dispense all water out of the accumulators.

11. Shut off the water supply, and connect the paint supply line.

12. Trigger the gun until the water is purged and paint starts to dispense from the gun nozzle.

13. Press the FILL/RUN button (A) to fill the accumulators.

CAUTION

Do not set the air pressure to the voltage block below 60 psi (4.2 bar) or the voltage block will not operate properly.

14. Wipe off the fluid nozzle, and install the air cap.

15. Follow the procedure Operating the Voltage

Block , page 22, to begin spraying.

Fig. 9

22

05323 Fig. 10

20

A B

05314

308–504 21

Operating the Voltage Block

Operation

NOTE: Be sure to turn on the air to the voltage block before pressing the FLUSH/RESET button or the system components will not operate.

WARNING

FIRE, EXPLOSION AND ELECTRIC

SHOCK HAZARD

To reduce the risk of fire, explosion, and electric shock:

Only use this equipment to spray non-flammable, waterborne fluids as defined on the front cover of this manual.

The voltage block door must be closed when any gun connected to the system is operating. Do not tamper with or bypass the door switch or other safety devices.

CAUTION

Do not set the air pressure to the voltage block below 60 psi (4.2 bar) or the voltage block will not operate properly.

2. Press the FLUSH/RESET button (B) to reset the air logic components. See Fig. 10, page 21.

3. Set the voltage block fluid pressure for the desired fluid flow through the gun. Set the fluid pressure with the regulator knob (20) on the voltage block door.

WARNING

COMPONENT RUPTURE HAZARD

To reduce the risk of component rupture, which can cause serious injury, do not exceed the maximum working pressure of the lowest rated system component. This equipment has a 100 psi (7 bar) maximum working air and fluid pressure .

4. Turn on the fluid supply to the voltage block.

NOTE: The voltage block fluid inlet pressure will affect the accumulators fill time only.

5. Press the FILL/RUN button (A) to fill the accumulators.

6. Open the gun air supply.

1. Turn on the air to the voltage block. Set the air pressure between 80 to 100 psi (5.6 to 7 bar).

The air inlet pressure is set with the air regulator

(22) installed at the voltage block air inlet. See Fig.

9, page 21.

7. Follow the gun operation instructions in the gun manual. Use the same spraying technique you would use without the voltage block to coat the workpiece.

22 308–504

Flushing and Shutdown

WARNING

FIRE AND EXPLOSION HAZARD

To reduce the risk of fire and explosion:

Only flush, purge, or clean the electrostatic, waterborne spray system with non-flammable fluids, as defined on the front cover of this manual.

Do not flush the system with the gun electrostatics turned on.

Operation

General Flushing and Shutdown

NOTE: Before flushing, make sure the fluid inlet pressure is a minimum of 5 psi (0.35 bar) lower than the voltage block air pressure regulator (22) setting or the accumulators will fill during the flush cycle. Refer to

Fig. 9, page 21.

1. Follow the Fluid Voltage Discharge and

Grounding Procedure on page 18.

2. Shut off the fluid supply. Trigger the gun until the fluid pressure is relieved.

3. If using a hand-held gun, remove the air cap from the gun.

WARNING

ELECTRIC SHOCK HAZARD

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 when shutting down the system to ensure the voltage is discharged and avoid serious injury from an electric shock.

4. Change the fluid supply to water or the appropriate flushing material. Do not use MEK or related ketone mixtures.

5. Press the FLUSH/RESET button.

6. Turn off the air supply to the gun, except the air to actuate the gun trigger if it is an automatic gun. If the automatic gun has an air pilot regulator, the pilot air must also be left on.

WARNING

PRESSURIZED EQUIPMENT HAZARD

To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 20 when you stop spraying and whenever you are instructed to relieve the pressure.

7. Make sure the gun electrostatics are turned off.

8. Trigger the gun to dispense the fluid out of the voltage block until the fluid section is completely flushed.

NOTE: After the accumulators empty, the first isolator will connect to the water supply.

To save the fluid in the accumulator, follow the Paint

Saver Option procedure, below. For general gun flushing and shutdown, follow the General Flushing and Shutdown procedure, at right.

Paint Saver Option

To save fluid at shutdown:

1. Follow the Fluid Voltage Discharge and

Grounding Procedure on page 18.

2. Depressurize the fluid supply to the voltage block.

3. Open the voltage block door latch enough to actuate the door switch, which will send both the isolators down and allow the fluid in the accumulators to be pushed back to the fluid supply.

4. Continue with the General Flushing and Shutdown procedure.

9. Shut off the fluid supply. Trigger the gun until the fluid pressure is relieved.

10. Do not purge the system with air; leave water in the fluid lines until you operate the system again.

11. Shut off the air supply to the enclosure.

12. Wipe the gun clean. If the gun air cap was removed, wipe off the fluid nozzle and install the air cap.

13. Make sure that the voltage block door is closed and that the main ground wire is connected between the enclosure ground lug and a true earth ground before operating the system again.

308–504 23

Troubleshooting

WARNING

ELECTRIC SHOCK HAZARD

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock.

First, check the system for any visible faults or errors to help isolate whether the spray gun, fluid hose or voltage block has failed.

1. Check that all of the air and fluid tubes and hoses are properly connected.

2. Check that the valves and controls are properly set for operation. Refer to the Operation procedures.

WARNING

PRESSURIZED EQUIPMENT HAZARD

To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 20 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure.

Problem: Voltage Loss

A loss of spraying voltage can be caused by a problem with the spray gun, fluid hose, or voltage block, since all of the system components are electrically connected through the conductive, waterborne fluid.

Before troubleshooting or servicing the voltage block itself, determine which component in the system is most likely causing a problem. Possible causes include:

Spray Gun

Fluid leakage

Dielectric breakdown at the fluid hose connection or fluid packings

Not enough air pressure for the turbine

Faulty power supply

Excessive overspray on gun surfaces

Fluid in the air passages

Waterborne Fluid Hose

Dielectric failure of hose (pin-hole leak through

PTFE layer)

Air gap in the fluid column between the gun and isolated fluid supply

Voltage Block

Fluid leakage

Dielectric breakdown of hoses, seals, or connections

Isolators not functioning properly

3. Check that the spray gun power supply and voltage block have sufficient air pressure.

4.

PRO 3500wb Gun Only: Check that the spray gun

ES lever is in the ON position and that the gun ES indicator light comes on. If the ES indicator light does not come on, remove the spray gun for service.

5. Check that the voltage block door is closed and that any safety interlocks are engaged and working properly.

6. To eliminate air gaps in the fluid column, spray enough fluid to purge the air out between the voltage block and the spray gun. An air gap in the fluid hose can break the electrical continuity between the spray gun and the fluid in the voltage block accumulators and cause a low voltage reading on the optional kV meter connected to the voltage block accumulators.

7. Check the spray gun cover and barrel for accumulated overspray. Excessive overspray can create a conductive path back to the grounded gun handle.

Install a new gun cover and clean the exterior of the barrel.

8. Inspect the entire system for any visible fluid leakage, paying special attention to the following areas:

Packing area of the spray gun

Fluid hose: check for leakage or any bulges in the outer jacket, which may indicate an internal leak

Internal voltage block components

If you still have no voltage, separate the spray gun and hose from the voltage block and check them for problems as instructed in the spray gun manual.

The optional kV Probe and Meter, part no. 236–003, is recommended to measure voltage levels at key points in the system.

Follow the troubleshooting chart for more detailed checking of the voltage block.

24 308–504

Troubleshooting

Problem

Voltage loss*

Cause

Voltage block enclosure door is not closed

Voltage block is in the end of the flush mode and the fluid is connected to a grounded fluid supply

Waterborne fluid hose has a pin-hole leak through the PTFE ing dielectric failure

layer, caus-

Fluid is leaking at the gun fluid hose connection

Excessive fluid overspray on the outside of the gun barrel, shroud, or gun cover

Excessive waterborne fluid leaking into the TSL recirculating return line

Solution

Close the door.

Push the FILL/RUN button.

Check for leakage or any bulges in the outer jacket, which may indicate an internal leak. Inspect the end of the hose connected to the voltage block. Look for cuts or nicks. Make sure the hose is properly stripped; see the spray gun manual for hose stripping dimensions. Restrip or replace the hose.

Remove the hose at the gun connection. Clean and dry the gun barrel I.D.

and the hose O.D. Lubricate the hose

O.D. and o-rings with dielectric grease and reinstall them.

Clean the outside of the gun barrel or shroud. Replace the gun cover.

Flush and refill the TSL lines and container with clean TSL. See Service . If the problem reoccurs quickly, replace the isolator seals with the seal kit.

Replace the seals as necessary.

Fluid is leaking on the components inside the voltage block

Air in the fluid line to the gun (can cause low voltage reading on the optional voltage block kV meter)

Gun electrostatics (turbine air or gun

ES lever) not turned off

Trigger the gun until the air is purged out through the gun nozzle.

Turn off the gun electrostatics.

Voltage is still present at the gun or fluid regulator after following the Fluid Voltage Discharge and Grounding Procedure

Did not wait long enough for the voltage to discharge through the voltage bleed resistor

Air pocket in the fluid lines

Faulty bleed resistor

Wait the 30 second time period before making contact with the gun or internal voltage block components.

Purge the air out of the fluid lines.

Check for loose wire connection or replace the bleed resistor if necessary.

* Normal spraying voltage is 45 to 55 kV.

308–504 25

Troubleshooting

Problem

TSL container level is rising

TSL container level is dropping

TSL, TSL tubing, or TSL container color changing to color of waterborne fluid

TSL not circulating

Fluid leak at isolator rod seam

PTFE leaking fluid hose connections are

Cause

Waterborne fluid is leaking into the

TSL lines

TSL is leaking or slowly evaporating with use

This is normal unless the kV level is dropping (see Voltage Loss , page

25)

Cartridge seals worn allowing excessive fluid into the TSL ports

TSL circulating pump seals worn

Check valve(s) in TSL tubing line(s) failed

Air restrictor to TSL pump closed too far

Retaining collar nut has loosened causing loss of spring pressure

Rod o-ring is worn or damaged

Fitting nut is not tight

Fitting threads are stripped

Cylinder restrictors misadjusted or plugged

Solution

Replace the isolator seals with the seal kit. See Service.

Refill the TSL container or replace the TSL seals.

No action necessary. The dirty TSL can be pumped out and refilled as necessary.

Replace the isolator seals with the seal kit.

Replace TSL pump seals with the pump fluid seal repair kit.

Replace check valve(s) and tubing if necessary with TSL tube repair kit.

Open the adjustment screw on the restrictor 1/2 turn and test with the manual pump actuator.

Re-tighten the collar. Secure the collar with its retaining screw. See

Service .

Replace the o-ring and cartridge seals with the replacement seal kit.

See Service .

Hand-tighten the nut. Hand-tighten only; do not use tools.

Replace the fitting. Install the new hose or nut assembly as needed.

Adjust air cylinder exhaust port for speed adjustment of about 2 seconds per stroke.

Isolator air cylinder moving too slow or too fast (normal speed is approximately 2 seconds per stroke)

Isolator cylinder is not operating properly

Accumulator fills past the full setting switch

Air leak at fluid regulator pilot air fitting

Voltage block air pressure set below

60 psi (4.2 bar); recommended pressure is 65–95 psi (4.5–6.6 bar)

Switch position is not adjusted properly

Constant air exhaust from small hole in pilot air fitting is normal and used for pressure control accuracy.

Set air to proper pressure. See

Operation .

Re-adjust the switch position.

No action necessary.

26 308–504

Maintenance

Cycle Counting

A Pneumatic Cycle Counter Kit, part no. 238–026, is available to count the number of isolator cycles for maintenance tracking.

If the Cycle Counter Kit is not installed, time how long one voltage block cycle takes during normal operation.

Use the following formulas to convert the voltage block cycles to production hours:

2. Inspect the condition of the TSL fluid in the sight glass and in the TSL container (91) daily. Refer to

Fig. 11, page 29. Signs of TSL contamination include:

Discoloration of the TSL

Rise in the TSL level in the tank

Gradual reduction of the spraying voltage.

Fluid Seal Time in Hours =

(15,000 x Cycle Time in minutes) 60

TSL Change Time in Hours =

(4000 x Cycle Time in minutes) 60

3. To help ensure that only fresh TSL enters the seal area, change the TSL every 4000 cycles or sooner if it appears to be contaminated. Follow the Drain and Flush the TSL System instructions, page 28.

TSL System Maintenance

To prolong the life of the isolator and to avoid expensive repairs and downtime, perform the following maintenance:

4. Once a week, manually check the operation of the

TSL pump (90). Refer to Fig. 11. The isolator must be in the down position* and the voltage block must be pressurized for the pump to operate. Operate the TSL pump by pressing the button on the pump. Watch the sight glass in the TSL line to see if the fluid is moving.

1. Replace the isolator seals every 15,000 voltage block cycles, or every four months, whichever comes first. See page 29.

* The isolator will automatically stop in the down position when the voltage block door is opened.

308–504 27

Drain and Flush the TSL System

Maintenance

3. Remove the TSL return tube (E) from the TSL pump (90) fitting.

WARNING

ELECTRIC SHOCK HAZARD

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock.

4. Drain both tubes (A, E) into a waste container.

5. If the TSL container (91) still appears dirty after draining it, remove the TSL container and clean it with non-flammable fluids, which are defined on the front cover of this manual.

6. Reinstall the TSL container and TSL tubes.

WARNING

PRESSURIZED EQUIPMENT HAZARD

To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 20 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure.

1. Follow the General Flushing and Shutdown procedure on page 23.

7. Disconnect the tube (L) from the tube connector

(M). Place the end of the tube into a waste container and fill the TSL container with TSL fluid (part no. 206–995).

8. Turn on the air inlet pressure to the voltage block.

9. Press the button on the TSL pump (90) to manually activate it and flush the remaining TSL out of the pump and into the waste container. When the TSL tubes are purged of contaminated TSL and air, reconnect the tube (L) to the connector (M).

NOTE: As part of the General Flushing and Shutdown , the Fluid Voltage Discharge and Grounding

Procedure , page 18, and the Pressure Relief Procedure , page 20, should have been completed. Do not proceed until you have followed those procedures.

2. Remove the TSL container outlet tube (A) from the fluid block (330) fitting. See Fig. 11, page 29.

PTFE

Tubing Replacement

The PTFE flared tube assembly (101) will fatigue over time. To prevent failure during operation, replace the tube assembly after dispensing about 50,000 gal.

(189,250 liters) of fluid or after about 6,000 hours of operation. If a cycle counter is used, replace the tube assembly every 70,000 cycles.

28 308–504

Isolator Service

WARNING

ELECTRIC SHOCK HAZARD

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock.

Service

4. Disconnect the two air tubes from the air cylinder connectors (B). Mark or tag the tubes so it is apparent which connector they attach to for reassembly.

5. Disconnect the two PTFE isolator elbows.

fluid tubes (C) from the

6. Remove the screw (305), and disconnect the ground wire from the air cylinder. Reinstall the screw to avoid losing it.

WARNING

PRESSURIZED EQUIPMENT HAZARD

To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 20 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure.

7. Disconnect the TSL return tube (E) from the fluid block (330) fitting.

8. Remove the four 3/8” screws (97), and remove the isolator assembly (75) from the enclosure (106).

9. Take the isolator to a clean service bench.

90 L M A 91

NOTE: An Isolator Seal Kit, part no. 237–977, is available. It includes the o-rings (302, 306, 308, 309,

319) and seals (320) for the seal cartridges.

Isolator Disassembly

1. Follow the General Flushing and Shutdown procedure on page 23.

NOTE: As part of the General Flushing and Shutdown , the Fluid Voltage Discharge and Grounding

Procedure , page 18, and the Pressure Relief Procedure , page 20, should have been completed. Do not proceed until you have followed those procedures.

Follow the steps below to remove either one or both of the isolators.

2. Remove the TSL container outlet tube (A) from the fluid block (330) fitting. See Fig. 11. Drain the TSL from the TSL container (91) into a waste container.

3. Remove the TSL container and clean it with nonflammable fluids, which are defined on the front cover of this manual. The remaining TSL system components will be flushed after the isolator service is completed.

B

305

330

E

C

106

Fig. 11

75 97 101

05817A

308–504 29

Service

Isolator Disassembly (continued)

10. Remove the retainer screw (343) from the bottom support (331). See Fig. 12.

19. While holding the parts over a waste container, pull the isolator rod (334) out of the fluid block (330).

Be careful not to nick or scratch the rod surfaces.

20. Remove the isolator rod o-ring (319).

11. Remove the spring retainer collar (336).

12. Rotate the fluid tube (335) until the ground electrode (337) is accessible. Remove the screw (338) and ground electrode (337).

21. Remove both seal cartridges (332, 333), the high voltage electrode (326), plug (325), and o-ring

(306) from the fluid block (330).

13. Pull the fluid tube (335) out of the bottom support

(331). Remove the plug (325) and o-ring (306).

14. Remove the bottom support (331) by removing the four screws (318) that fasten it to the mounting brackets (324).

CAUTION

Be careful not to nick or scratch the cartridges (332,

333) surfaces when removing o-rings and seals.

Note the o-ring and seal sizes and positions as they are removed to ensure they are reinstalled correctly.

15. Loosen the screw (307) holding the cover retainer

(328), and rotate the cover retainer off of the cylinder rod cover (327).

22. Remove all the o-rings (302, 308, 309) from both seal cartridges (332, 333).

16. Push the cylinder rod cover (327) up until the air cylinder rod (G) is accessible. Unscrew the cylinder rod from the adapter in the fluid block (330).

23. Use a dental pick to remove the wiping seals (320) from both seal cartridges (332, 333). Be careful not to scratch the cartridges surfaces.

17. Remove the plastic screw (304) holding the isolator rod (334).

18. Slide the fluid block (330) [with the isolator rod still in place] off the metal guide rod (321).

24. Thoroughly clean and inspect all the parts. Inspect the fluid tube (335) and isolator rod (334) for nicks, grooves, and high voltage burn marks on sealing and wiping surfaces. Inspect the guide rod bearings (312) for wear. Replace all the parts that appear to be worn or damaged.

Continue on page 32

30 308–504

Service

311

324

305

318

307

328

330

F

Fig. 12

Apply lubricant.

Torque to 15 in-lbs (1.7 N S m).

Torque to 8 in-lbs (0.9 N S m).

Tighten securely, until bottomed out.

304

329

G

320*

332

309*

302*

320*

327

326

325

306*

321

Lips face down

Lips face up

* Included in Kit 237–977

320

308*

325

306*

335

331

343

313

336

333

320

334

319*

337

338

05818A

308–504 31

Service

Isolator Assembly

NOTE: Parts that are marked with an asterisk (*) are included with the Isolator Seal Kit, part no. 237–977.

11. Secure the bottom support (331) to the mounting bracket (324) with the four screws (318). Tighten the screws to 15 in-lbs (1.7 N m).

1. Lubricate the new seals (320*) and install them into the cartridges (332, 333), orientated as shown in Fig. 12, page 31. Make sure the seals sit straight in the cartridge and that the seal quad-ring is in place.

12. Install the spring (313) into the retainer collar

(336), and screw the collar into the bottom support

(331) until the collar bottoms out. Secure the collar with the retainer screw (343).

2. Lubricate the new o-rings (302*, 308*, 309*) and install them in the grooves on the cartridges (332,

333) in the order shown in Fig. 12.

13. Secure the isolator assembly (75) into the enclosure (106), using the four 3/8” screws (97). See

Fig. 11, page 29.

14. Plug the TSL container (91) outlet tube, then fill the TSL container (91) with fresh TSL.

3. Install the o-ring (306*), plug (325), and high voltage electrode (326) in the fluid block (330).

Tighten the plug and the electrode until they bottom out.

15. Connect the two air tubes to the air cylinder connectors (B).

4. Carefully install the seal cartridges (332, 333) into the fluid block (330). Tighten the cartridges until they bottom out.

16. Connect the two PTFE isolator elbows.

fluid tubes (C) to the

5. Install the o-ring (319*) on the end of the isolator rod (334).

CAUTION

Tighten the tube retaining nuts by hand only to avoid damaging them.

6. Slide the tapered end of the isolator rod (334) through the seal cartridges (332, 333) in the fluid block (330).

17. Remove the screw (305). Connect the ground wire to the air cylinder, and secure the wire with the screw.

7. Place the cylinder rod cover (327) in the locating groove (F). Do not fasten the cover with the retainer (328) and screw (307) yet.

18. Remove the plug from the TSL container outlet tube (A), and connect the tube to the fluid block

(330) fitting.

8. Slide the fluid block (330) onto the metal guide rod

(321). Push the isolator rod (334) into the counterbore in the top support (329), and secure the rod with the plastic screw (304). Tighten the screw to 8 in-lbs (0.9 N m).

19. Connect the TSL return tube (E) to the fluid block

(330) fitting.

20. Disconnect the tube (L) from the tube connector

(M). Place the end of the tube into a waste container and fill the TSL container.

9. Push the fluid block (330) partially down to slide the cylinder rod cover (327) up and tighten the air cylinder rod (G). Tighten the rod until it bottoms out.

21. Turn on the air inlet pressure to the voltage block.

10. Slide the cylinder rod cover (327) down and secure the cover with the retainer (328) and screw (307).

Tighten the screw to 8 in-lbs (0.9 N m).

22. Press the button on the TSL pump (90) to manually activate it and flush the remaining TSL out of the pump and into the waste container. When the TSL tubes are purged of contaminated TSL and air, reconnect the tube (L) to the connector (M).

32 308–504

Notes

308–504 33

Accumulator Service

WARNING

ELECTRIC SHOCK HAZARD

Follow the Fluid Voltage Discharge and Grounding Procedure on page 18 before checking or servicing the system to ensure the voltage is discharged and avoid serious injury from an electric shock.

Service

4. Disconnect the air pilot tube from the fluid regulator air pilot connector (48).

5. Loosen the hose ferrule nut (8).

6. Loosen (but do not remove) the hose compression nut (AA) connecting the gun fluid supply hose to the fluid regulator outlet. Pull the hose out of the fitting.

7. Remove the four top plastic screws (54) that secure the accumulator (74) to the mounting plate

(X) in the enclosure.

WARNING

PRESSURIZED EQUIPMENT HAZARD

To reduce the risk of an injury from accidental spray from the gun, splashing fluid, or moving parts, follow the Pressure Relief Procedure on page 20 before checking or servicing any part of the system and whenever you are instructed to relieve the pressure.

8. Remove the accumulator (74) from the mounting plate (X).

9. Remove the four thread caps (225) and cap plugs

(224). See Fig. 14.

10. Loosen the four hex nuts (213) evenly.

11. Remove the four 12.6” screws (212), washers

(204), and high voltage shields (223).

Signs of accumulator piston seal failure include a noticeable and repeated spitting of fluid while spraying

(indicating that air is entering into the fluid stream) or a visible amount of fluid in the top air exhaust line that is exiting through the enclosure bottom.

NOTE: An Accumulator Seal Kit, part no. 237–976, is available. It includes the o-rings (211) and u-cups (208,

214).

Accumulator Disassembly

1. Follow the General Flushing and Shutdown procedure on page 23.

12. Tap the end blocks (216, 217) off of the cylinder

(219).

13. Remove the piston assembly (221, 222, 214 from the cylinder (219).

1 , 220)

14. Remove the u-cups (208, 214 2 ) and o-rings (201,

202, 211). Clean and inspect the parts. Replace all the parts that are worn or damaged.

Continue on page 36

H

NOTE: As part of the General Flushing and Shutdown , the Fluid Voltage Discharge and Grounding

Procedure , page 18, and the Pressure Relief Procedure , page 20, should have been completed. Do not proceed until you have followed those procedures.

Follow the steps below to remove either one or both of the accumulators.

X

J

8

54

74

2. Disconnect the exhaust air tube from the top accumulator fitting (H). See Fig. 13.

AA

3. Disconnect the fluid hose nut (J) from the fluid inlet flared hose end.

48

NOTE: Follow steps 4 to 6 to disconnect the fluid regulator (2), which is connected to accumulator #2, from the system. If disconnecting accumulator #1 only, disconnect the fluid tube from the accumulator outlet fitting and continue with step 7.

34 308–504

Fig. 13

2

05320A

Service

217

225

202

213

210

211*

219

201

223

222

*214 1

220

*208

221

215

*214 2

212

202

224

Fig. 14

Install the u-cups (214 1 the piston (220).

, 214 2 ) with the lips facing to the outside of

Install the piston assembly (221, 222, 214 1 , 220) into the end of the cylinder (219) with the internal chamfer. The cylinder end with the chamfer must face toward the upper end block (217).

Apply lubricant to the seal contact surfaces.

Do not use lubricant on the o-rings (202) that are in the cap plugs (224).

Torque to 15 ft-lbs (20.25 N S m).

Torque to 15 in-lbs (1.7 N S m).

Apply dielectric lubricant to the o-ring.

* Included in Kit 237–976

05296

308–504 35

201

211*

216

204

Service

Accumulator Assembly

NOTE:

Parts that are marked with an asterisk (*) are included with the Accumulator Seal Kit, part no.

237–976.

Lubricate the o-rings and u-cups as directed in Fig.

14, page 35. Do not use lubricant on the o-rings

(202) that are in the cap plugs (224).

1. Install the u-cup (214 1* ) on the air side of the piston (220) with the lips of the u-cup facing up, away from the piston, as shown in Fig. 14. Using a blunt instrument, carefully press around all sides of the u-cup lips until it is completely engaged in the piston (220) groove. Lightly lubricate the outside edge of the u-cup.

9. Place the upper end block (217) on the end of the cylinder (219) with the internal chamfer.

10. Install the o-rings (201) and high voltage shields

(223) into the upper end block (217).

11. Place the lower end block (216) on the other end of the cylinder. Make sure the eight o-rings (201) stay correctly placed in the end blocks.

12. Secure the end blocks (216, 217) with the washers

(204), screws (212), and nuts (213). Tighten the screws oppositely and evenly to 15 ft-lbs (20.25

N m).

13. Install the o-rings (202) into the thread caps (225) and onto the grooves on the cap plugs (224).

2. Secure the piston extension (222) to the piston

(220) with the four screws (215). Tighten the screws to 15 in-lbs (1.7 N m).

3. Install the piston assembly (221, 222, 214 1 , 220) into the end of the cylinder (219) with the internal chamfer. Make sure the fluid side of the piston faces down into the cylinder. See Fig. 14.

14. Apply dielectric grease to the o-rings (202) in the thread caps (225). Do not apply grease to the o-rings (202) on the cap plugs (224).

15. Install the thread caps (225) and cap plugs (224).

16. Add 0.7 oz. (20 cc) of TSL into the top end (piston rod end) of the accumulator. Remove the top air fitting for easier access if necessary.

4. Push the piston assembly to the the bottom of the cylinder until the bottom edge of the piston (220) is exposed.

5. Install the u-cup (214 2 *) on the piston (220) with the lips of the u-cup facing down away from the piston, as shown in Fig. 14. Using a blunt instrument, carefully press around all sides of the u-cup lips until it is completely engaged in the piston

(220) groove. Lightly lubricate the outside edge of the u-cup.

17. Secure the accumulator (74) to the mounting plate

(X) with the four plastic screws (54). See Fig. 13, page 34. Tighten the screws until they are snug; do not over-tighten them.

18. Reconnect the Graco waterborne fluid hose as instructed on page 14.

19. Connect the exhaust air tube to the top accumulator fitting (H). See Fig. 13, page 34.

6. Install the new piston rod u-cup (208*) with the u-cup lips facing toward the piston (220). Lightly lubricate the outside edge of the u-cup.

NOTE: If installing accumulator #1, connect the fluid tube to the accumulator outlet fitting.

7. Install the two new o-rings (211*) into the end blocks (216, 217). Lightly lubricate the o-rings.

20. Connect the fluid hose nut (J) to the fluid inlet flared hose end.

8. Install the eight o-rings (201) into the grooves in the end block (216, 217) ports. Apply dielectric grease to the o-rings.

21. Connect the air pilot tube to the fluid regulator air pilot connector (48).

36 308–504

Notes

308–504 37

Parts

Part No. 237–928

Waterborne Voltage Block

21

22

See DETAIL B, below, and page 46 for replaceable air logic assembly parts

53

65 57

Ref.

31

24

29

25

60

73

17

7

9

51 52

79

11

13

61

16

31

71

72

20

103

83

34

18

6

68

38

15

48

106

10 8

100

DETAIL A

44

120

14

86

12

46

30

35

59

58

See page 40 for parts. See

DETAIL A for tube parts.

** NOTE: The washers (80) are installed for grounding continuity. Install them in the location shown, not next to the nuts (56).

DETAIL B

99 110 93

**80

56

113 107 101

38 308–504

05819

Part No. 237–928

Waterborne Voltage Block

NOTE: Parts for the voltage block assembly are continued on the next page.

Parts

Ref.

No.

Part No.

Description

6

7

8

290–098 WARNING LABEL

101–390 LOCK WASHER

185–549 HOSE FERRULE

9 185–548 NUT, 5/8–24

10 185–547 FERRULE HOUSING

11 208–536 AIR LINE COUPLING

12 110–544 LEG LEVELER

13 169–970 AIR LINE FITTING, quick-disconnect

14 109–570 WASHER

15 113–348 LOCK WASHER

16 156–971 SHORT NIPPLE

17 154–636 WASHER

18 112–308 NUT, regulator panel

20 110–438 AIR REGULATOR, self relieving, 0–100 psi (0–7 bar)

21 110–436 AIR PRESSURE GAUGE

22 111–804 AIR REGULATOR, self relieving, 0–125 psi (0–8.5

bar)

24 106–086 HEX JAM NUT

25 104–029 GROUND LUG

29 100–732 LOCK WASHER

30 100–731 WASHER

31 104–641 FITTING, 3/8 npt(f) x

3/4–20 unef–2a

34 100–527 WASHER

35 100–307 HEX NUT

38 100–056 HEX JAM NUT

44 113–078 SCREW

46 113–080 SCREW RETAINER

48 113–058 CONNECTOR, 5/32 x 1/4 npt(m)

51 113–069 90 ELBOW, 1/4 npt(f)

52 113–068 CONNECTOR, 5/32 x 1/8 npt(m)

53 113–067 PNEUMATIC SWITCH

56 113–127 NUT

57 113–128 STANDOFF; 3/4” (19 mm)

58 113–129 CAP SCREW, 1/4–20 x

1.25”

59 113–130 WASHER

60 290–089 LABEL, air inlet, max.

pressure

61 290–090 LABEL, fluid inlet, max.

pressure

Qty.

1

4

4

4

1

4

16

4

1

2

2

3

2

2

2

4

1

4

1

1

1

1

1

1

1

1

4

1

1

1

4

1

2

1

1

1

Ref.

No.

Part No.

Description

65 113–179 CONNECTOR, 1/4 npt(m), for 1/4” O.D. tube

68 113–062 UNION

71 113–268 BUSHING

72 113–060 FLUID PRESSURE

GAUGE; 0–100 psi (0–7 bar)

73 113–061 PUSH SWITCH

79 113–150 STANDOFF; 1–1/4”

(32 mm)

80 100–985 WASHER

83 100–333 CAP SCREW

86 100–338 JAM NUT

93 113–154 AIR LOGIC COVER

99 113–167 AIR LOGIC ASSEMBLY

100 113–170 ADAPTER NUT

101 113–181 FLARED TUBE ASSY.,

15.5” (394 mm)

103 190–715 BULKHEAD FITTING,

3/8–18.6 special form straight pipe thread

106 190–721 VOLTAGE BLOCK

ENCLOSURE

107 113–180 FLARED TUBE ASSY., 23”

(584 mm)

110 190–712 AIR LOGIC STANDOFF

113 113–182 FLARED TUBE ASSY., 5.5”

(139.7 mm)

120 190–734 PEDESTAL

Qty.

1

1

2

4

1

2

1

1

1

1

1

4

12

4

1

2

4

1

Replacement Danger and W arning labels, tags and cards are available at no cost.

AIR LOGIC TUBING

Use polyethylene, 5/32 in. (4 mm) O.D., tubing. This tubing is available from Graco in 100 ft. (30.5 m) lengths. The chart below shows the part numbers and colors.

Tubing Part No.

Color

054–730

054–731

Natural (clear)

Blue

054–732

054–733

Red

Yellow

054–734 Black

308–504 39

Parts

Part No. 237–928

Waterborne Voltage Block

91

52

90

88

34

32

114

104

105

96

39

98

39

116

*117

*1

129

87 27

34

32

109

76

39

77

39

74

See parts on page 42

94

] 122

19

42

43

41

50

49

42

54

97

75

See parts on page 44 95

Isolator 2

A

37

121

92

Isolator 1

115

Accumulator 1

36 111 102

47

48

Accumulator 2

] The other cable end connects to the ground lug (25) inside the enclosure (106).

Tapered end of the check valve (1) must face up.

2

05820A

40 308–504

Parts

Part No. 237–928

Waterborne Voltage Block

Ref.

No.

Part No.

Description

1*

2

– CHECK VALVE

236–281 FLUID REGULATOR,

3–100 psi (0.2–7 bar)

4* 206–995 TSL FLUID, 1 qt. (0.95 liter) bottle (not shown)

19 110–620 SCREW, nylon

27 101–816 MACHINE SCREW

32 110–823 MACHINE SCREW

34 100–527 WASHER

36 100–268 MACHINE SCREW

37 100–166 HEX NUT

39 103–774 MACHINE SCREW

40* – TSL TUBING (not shown)

41 113–135 CRUSH RING

42 113–075 WASHER

43 190–410 BLEED RESISTOR

47 113–071 90 _ ELBOW, 1/4 npt(f)

48 113–058 CONNECTOR, male, 5/32 x 1/4 npt

49 113–081 TUBE ADAPTER, male,

1/4 npt(m), for 3/8” O.D.

tube

50 113–070 REDUCER NIPPLE,

3/8–1/4 npt(m)

52 113–068 CONNECTOR, male, 5/32 x 1/8 npt

54 113–125 CAP SCREW, 3/8–16 x 2”

74 237–929 ACCUMULATOR, see page

42 for parts

75 237–930 ISOLATOR ASSY., see page 44 for parts

76 113–123 FULL LEVEL SWITCH

77 113–124 LOW LEVEL SWITCH

87 113–174 TSL PUMP SWITCH

88 113–175 SWITCH BRACKET

90 l 113–143 TSL PUMP

91 113–144 TSL RESERVOIR, 1.5 qt.

(1.4 liters)

92 113–151 TUBE ADAPTER 90 _

ELBOW, 3/8 npt(f), for 3/8”

O.D. tube

94 113–155 BLEED RESISTOR

CLAMP

95 113–152 TUBE ADAPTER, 3/8 npt(f), for 1/2” O.D. tube

Qty.

2

1

1

4

2

1

2

1

2

1

8

2

2

2

2

2

2

2

1

1

3

2

16

8

16

1

2

14

2

4

Ref.

No.

Part No.

Description

96 113–166 BLOCKING EXHAUST

VALVE

97 113–126 CAP SCREW, 3/8–16 x 1”

98 113–165 EXHAUST VALVE

102 190–714 RESISTOR FITTING,

10–24 unc–2b x 1/4–18 npt(m)

104 191–971 SWITCH BRACKET

105 190–719 SWITCH BRACKET NUT,

10–24 unc–2b

109 190–733 ACCUMULATOR ROD

GUIDE

111 237–937 WIRE ASSY., regulator to bleed resistor

112 237–939 WIRE ASSY., component to ground (not shown–refer to Fig. 6, page 16)

114 113–212 PUSH-IN TUBE UNION

115 113–169 TUBE ADAPTER, 3/8 npt(m), for 1/2” O.D. tube

ADAPTER

116 112–698 SWIVEL ELBOW,

1/8 npt(m)

117* – BARB FLUID

CONNECTOR

118 113–190 HOSE CLAMP (not shown)

119 113–191 CABLE CLAMP (not shown)

121 181–328 NUT

122 237–938 WIRE ASSY., bleed resistor to ground

123 237–569 WIRE ASSY, 25 ft. (7.6 m)

(not shown)

124 237–968 TOOL KIT, Includes items

124a & 124b (not shown),

Required to install pump seal repair kit, part no.

237–969.

124a 113–226 S PUMP ASSY. TOOL

124b 113–227 S PUMP O-RING TOOL

129 113–894 CLAMP, tube

Qty.

* These parts are available to order as part of a TSL

Tube Repair Kit, part no. 238–024. The kit also includes ref. no. 310, listed on page 45.

l A pump fluid seal repair kit, part no. 237–969, is available.

1

2

1

2

4

8

1

1

1

1

16

2

6

2

1

8

1

1

2

1

2

7

308–504 41

Parts

Item 74: Part No. 237–929

Accumulator Assembly

225

202

213

210

203

217

226

207

209

{ 208

221

215

{

218

211

211 {

219

201

223

214 {

201

205

206

216

222

{ 214

220

Install the u-cups (214) with the lips facing to the outside of the piston (220).

Install the piston assembly (222, 214, 220) into the end of the cylinder (219) with the internal chamfer. The cylinder end with the chamfer must face toward the upper end block (217).

Apply lubricant to the seal contact surfaces.

42 308–504

204

226

207

209

212

202

224

05280

Do not use lubricant on the o-rings (202) that are in the cap plugs (224).

Apply anaerobic pipe sealant on the threads.

Torque to 15 ft-lbs (20.25 N S m).

Torque to 15 in-lbs (1.7 N S m).

Apply dielectric lubricant to the o-ring.

Parts

Item 74: Part No. 237–929

Accumulator Assembly

Ref.

No.

Part No.

Description

201 722–834 O-RING, Viton r

202 188–555 O-RING, Viton

203 113–058 CONNECTOR, 5/32 x

1/4 npt

204 109–570 WASHER

205 113–135 CRUSH RING

206 113–074 TUBE ADAPTER 90 _ elbow, 3/8 npt(m), for 1/2”

O.D. tube

207 113–075 WASHER

208 { – U-CUP, urethane

209 113–164 CAP SCREW, 3/8–16 x 1.5”

210 113–066 WASHER

211 { – O-RING, Viton

212 113–140 CAP SCREW, 1/2–13 x

12.625”

213 113–141 HEX NUT, 1/2”

Qty.

4

8

8

1

4

1

1

4

2

4

4

1

4

Ref.

No.

Part No.

Description

214 { – U-CUP, hytrel & Viton

215 108–630 MACHINE SCREW, 10–24 x 0.75”

216 190–693 LOWER END BLOCK

217 190–694 UPPER END BLOCK

218 190–695 SHOULDER PIN

219 190–696 CYLINDER

220 190–697 PISTON

221 190–698 PISTON ROD

222 190–699 PISTON EXTENSION

223 190–700 HIGH VOLTAGE SHIELD

224 190–701 CAP PLUG

225 190–702 THREAD CAP

226 190–703 SUPPORT BLOCK

{ These parts are available to order as part of an

Accumulator Seal Kit, part no. 237–976.

Qty.

2

4

4

4

4

1

1

4

1

1

3

1

1

308–504 43

Parts

Item 75: Part No. 237–930

Isolator Assembly

318

347

346

311 345

304

346

305

329

324

318

316

307

328

327

330

344

322

323

Apply anaerobic pipe sealant on the threads.

Apply lubricant.

Torque to 15 in-lbs (1.7 N S m).

Torque to 8 in-lbs (0.9 N S m). raisin

310*

320 }

332

309 }

302 }

320 }

326

325

306 }

310*

314

315

321

Tighten securely, until bottomed out.

Lips face down

Lips face up

320 }

308 }

333

320 }

334

319 }

337

338

325

306 }

335

331

343

313

336

05813A

44 308–504

Parts

Item 75: Part No. 237–930

Isolator Assembly

Ref.

No.

Part No.

Description

302 } – O-RING, Viton r

304 112–325 THUMB SCREW, 1/4–20 nc x 1”

305 111–788 CAP SCREW, 1/4–20 unc–3a x 0.75”

306 } – O-RING, Viton

307 110–620 SCREW, 10–24 unc–2a x 0.5”

308 }

309 }

O-RING, Viton

O-RING, Viton

310* 113–213 BARBED HOSE FITTING

311 113–131 AIR CYLINDER

313 113–136 COMPRESSION SPRING

314 113–135 CRUSH RING

315 113–074 TUBE ADAPTER 90 _ elbow, 3/8 npt(m), for 1/2”

O.D. tube

316 113–134 JAM NUT, 1–1/4 uns–2b

318 113–126 CAP SCREW, 3/8–16 x 1”

319 }

320 }

O-RING, CV75

WIPING SEAL, lubrithane

& Viton r

321 190–636 GUIDE ROD

322 190–637 AIR CYLINDER ADAPTER

323 190–638 CAP PLUG

324 190–639 MOUNTING BRACKET

325 190–640 GROUND PLUG

326 190–641 HIGH VOLTAGE

ELECTRODE

Qty.

2

2

1

1

1

1

1

8

1

4

4

1

1

1

1

3

2

2

1

1

1

1

Ref.

No.

Part No.

Description

327 190–717 CYLINDER ROD COVER

328 190–718 COVER RETAINER

329 190–642 TOP SUPPORT

330 239–017 FLUID BLOCK

331 190–644 BOTTOM SUPPORT

332 190–645 TOP SEAL CARTRIDGE

333 190–646 BOTTOM SEAL

CARTRIDGE

334 190–647 ISOLATOR ROD

335 190–689 FLUID TUBE

336 238–085 SPRING RETAINER

337 190–691 GROUND ELECTRODE

338 103–310 MACHINE SCREW, 8–32 unc–2a x 1/4”

343 100–609 MACHINE SCREW, 1/4–20 unc–2a x 0.375”

344 187–959 WARNING LABEL

345 238–770 BRACKET ASSY., Isolator

346 113–058 CONNECTOR, male, 5/32 x 1/4 npt

347 113–184 ELBOW ADAPTER

Qty.

1

1

1

1

1

1

1

1

1

1

1

1

1

1

1

2

1

} These parts are available to order as part of an Iso lator Seal Kit, part no. 237–977.

* This part (along with items 1, 4, 40, and 117) is included in TSL Tube Repair Kit 238–024, which may be purchased separately .

308–504 45

46 308–504

Air Logic Schematic and Parts

RED

RED

05327

AA

BB

Dimensions

Measurements, inches (mm)

AA

53.625

(1362)

BB

49.625

(1260)

CC

37.50

(953)

DD

51.0

(1295)

Width*

17.0

(432)

* Width at the widest point of the voltage block assembly

CC

DD

05332

Technical Data

Category

Maximum Working Pressure

Air Pressure Operating Range

Fluid Pressure Operating Range

Maximum Voltage

Fluid Specification

Accumulator Capacity

Maximum Fluid Temperature

Weight

Air Inlet

Fluid Inlet

Wetted Parts

Sound Pressure at 80 psi (5.6 bar) {

Data

100 psi (7 bar)

60–100 psi (4.2–7 bar)

0–100 psi (0–7 bar)

60 kV

For use with Graco PRO 5500wb t and PRO 3500wb t guns when electrostatically spraying conductive, waterborne fluids that meet at least one of the following conditions of non-flammability:

D The fluid has a flash point above 140 _ F (60 _ C) and a maximum organic solvent concentration of 20%, by weight, as determined in accord with the Standard Method of Testing for Flash Point by the

Pensky-Martens Closed Tester, ASTM D93.

D The fluid does not sustain burning characteristics in accordance with the Standard Method for Sustained Burning of Liquid Mixtures by the

Setaflash Apparatus, ASTM D4206.

100 oz. (3 liters)

120 _ F (49 _ C)

257.0 lbs. (115.65 kg)

1/4 npt(f) quick-disconnect

3/8–18 npsm (R3/8–19) compound thread

304 SST, PTFE r , PEEK, Viton r , Epoxy, Acetal

74.6 Db(A)

{ Sound pressure was measured per a time weighted average over a 4 minute complete dispense/refill cycle.

PTFE and Viton r

308–504 47

The Graco Warranty and Disclaimers

WARRANTY

Graco warrants all equipment manufactured by it and bearing its name to be free from defects in material and workmanship on the date of sale by an authorized Graco distributor to the original purchaser for use. As purchaser’s sole remedy for breach of this warranty, Graco will, for a period of twelve months from the date of sale, repair or replace any part of the equipment proven defective. This warranty applies only when the equipment is installed, operated and maintained in accordance with Graco’s written recommendations.

This warranty does not cover, and Graco shall not be liable for, any malfunction, damage or wear caused by faulty installation, misapplication, abrasion, corrosion, inadequate or improper maintenance, negligence, accident, tampering, or substitution of non–Graco component parts. Nor shall Graco be liable for malfunction, damage or wear caused by the incompatibility with Graco equipment of structures, accessories, equipment or materials not supplied by Graco, or the improper design, manufacture, installation, operation or maintenance of structures, accessories, equipment or materials not supplied by Graco.

This warranty is conditioned upon the prepaid return of the equipment claimed to be defective to an authorized Graco distributor for verification of the claim. If the claimed defect is verified, Graco will repair or replace free of charge any defective parts. The equipment will be returned to the original purchaser transportation prepaid. If inspection of the equipment does not disclose any defect in material or workmanship, repairs will be made at a reasonable charge, which charges may include the costs of parts, labor and transportation.

DISCLAIMERS AND LIMITATIONS

The terms of this warranty constitute purchaser’s sole and exclusive remedy and are in lieu of any other warranties (express or implied), including warranty of merchantability or warranty of fitness for a particular purpose , and of any non–contractual liabilities, including product liabilities, based on negligence or strict liability. Every form of liability for direct, special or consequential damages or loss is expressly excluded and denied. In no case shall Graco’s liability exceed the amount of the purchase price.

Any action for breach of warranty must be brought within two (2) years of the date of sale.

EQUIPMENT NOT COVERED BY GRACO WARRANTY

Graco makes no warranty, and disclaims all implied warranties of merchantability and fitness for a particular purpose , with respect to accessories, equipment, materials, or components sold but not manufactured by Graco. These items sold, but not manufactured by Graco (such as electric motor, switches, hose, etc.) are subject to the warranty, if any, of their manufacturer.

Graco will provide purchaser with reasonable assistance in making any claim for breach of these warranties.

Manual

Change Summary

Graco Phone

Number

TO PLACE AN ORDER , contact your Graco distributor, or call this number to identify the distributor closest to you: 1–800–367–4023 Toll Free

Assembly

Changed

237–928

237–930

Part

Status

Ref.

No.

1

Part No.

Name

Quantity changed to 2

Old

New

– Check Valve

104 190–716

191–971

Bracket

129 113–894 Clamp Added

Deleted 312 113–132 Bearing

Old

New

330 190–643

239–017

Fluid Block

Old

New

345 –

238–770

Bracket Assy.

Miscellaneous Changes: Added TSL System maintenance information.

Sales Offices: Atlanta, Detroit, Los Angeles

Foreign Offices: Belgium, Canada, England, Korea, Switzerland, France, Germany, Hong Kong, Japan

GRACO INC. P.O. BOX 1441 MINNEAPOLIS, MN 55440–1441

PRINTED IN U.S.A. 308–504 July 1995 Revised January 1997

48 308–504

advertisement

Related manuals

advertisement