Premium PLCs
TSX 57/PCX 57
Processors
Implementation Manual Volume 1
TSX DM 57 xxF eng
2
Document Set
At a Glance This documentation is made up of 5 Volumes: l Volume 1 l l l
Racks/Supplies/Processors
Implementation/Diagnostics/Maintenance l Standards and operating conditions l Process supply
Volume 2 l l Discrete interfaces l Safety
Volume 3 l l Counting l Movement commands
Volume 4 l l Communication l Network and bus interfaces
Volume 5 l l
Analog
Weighing
Document Set
TSX DM 57 xxF
3
Document Set
4
TSX DM 57 xxF
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Part I
Premium and Atrium PLC stations . . . . . . . . . . . . . . . . . 17
Chapter 1
Introduction to Premium and Atrium PLC stations . . . . . . . . . 19
Chapter 2
General introduction to the components of a PLC station . . . 23
General introduction to TSX P57 processors . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
General introduction to PCX 57 processors . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
General introduction to TSX PSY power supply modules . . . . . . . . . . . . . . . . . . 28
General introduction to Process and AS-i TSX SUP and TSX 1021/1051 power
General introduction to the TSX REY X Bus extension module . . . . . . . . . . . . . 31
General introduction to TSX DEY/DSY/DMY input/output modules . . . . . . . . . . 32
General introduction to TSX CTY/CCY counting modules . . . . . . . . . . . . . . . . . 34
Introduction to TSX CAY axis control modules . . . . . . . . . . . . . . . . . . . . . . . . . . 35
General introduction to TSX CFY step by step control modules . . . . . . . . . . . . . 37
General introduction to TSX SCY/ETY communication . . . . . . . . . . . . . . . . . . . 38
General introduction to the AS-i bus interface module: TSX SAY. . . . . . . . . . . . 42
General introduction to the TSX ISPY weighing module. . . . . . . . . . . . . . . . . . . 43
General introduction to the TSX FAN ventilation module . . . . . . . . . . . . . . . . . . 44
General introduction to the TSX PAY emergency stop monitoring module. . . . . 45
Chapter 3 General introduction to the different configurations of a PLC
station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
5
6
Different types of PLC stations with Atrium processors. . . . . . . . . . . . . . . . . . . . 51
Chapter 4
Operating Standards and Conditions . . . . . . . . . . . . . . . . . . . 55
Operating conditions and environmental conditions to be avoided . . . . . . . . . . . 57
Part II
TSX RKY.. standard and extendable racks . . . . . . . . . . . 65
Chapter 5
Introduction to TSX RKY .. standard/extendable racks.. . . . . 67
Standard and extendable TSX RKY racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Chapter 6 TSX RKY.. standard and extendable racks : installation/
mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Connection of the ground to a TSX RKY rack . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Chapter 7
TSX RKY.. standard and extendable racks: functions . . . . . . 85
Building a PLC station with Premium processor . . . . . . . . . . . . . . . . . . . . . . . . . 86
The principle of addressing two racks at the same address . . . . . . . . . . . . . . . . 93
Installing power supplies, processors and other modules . . . . . . . . . . . . . . . . . . 96
Chapter 8
TSX RKY Racks: accessories . . . . . . . . . . . . . . . . . . . . . . . . . . 99
TSX CBY..0K X Bus extension cable (II
≥
02) . . . . . . . . . . . . . . . . . . . . . . . . . . 100
TSX CBY 1000 X Bus extension cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Positioning of line terminators on a station using a Premium processor . . . . . . 105
Positioning of line termination on a station using a Atrium processor . . . . . . . . 106
TSX RKA 02 protective cover for unoccupied positions . . . . . . . . . . . . . . . . . . 107
Chapter 9
Ventilation module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Rules for installing racks fitted with ventilation modules . . . . . . . . . . . . . . . . . . 118
Chapter 10
X Bus extension module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
X Bus extension module: physical description . . . . . . . . . . . . . . . . . . . . . . . . . 125
X Bus extension module: maximum distances according to module type. . . . . 130
Topology of a PLC station with extension module . . . . . . . . . . . . . . . . . . . . . . 137
Managing a power supply module fitted with an X Bus extension module . . . . 139
Part III
TSX P57 Premium processors . . . . . . . . . . . . . . . . . . . 141
Chapter 11
TSX P57 processors: introduction . . . . . . . . . . . . . . . . . . . . . 143
Physical description of TSX P57 processors. . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Chapter 12
TSX P57 processors: installation . . . . . . . . . . . . . . . . . . . . . . 151
Mounting/Removing a PCMCIA memory extension card on a TSX P57 processor
Processing on insertion/extraction of a PCMCIA memory card on a Premium PLC
Standard and Backup memory cards for PLCs . . . . . . . . . . . . . . . . . . . . . . . . . 159
File type Memory Card: TSX MRP DS 2048 P . . . . . . . . . . . . . . . . . . . . . . . . . 162
Chapter 13
TSX P57 processors: diagnostics. . . . . . . . . . . . . . . . . . . . . . 163
Precautions to be taken when replacing a TSX P57 processor . . . . . . . . . . . . 166
Changing the RAM memory backup battery on TSX P57 . . . . . . . . . . . . . . . . . 167
7
8
Changing the battery of a RAM memory Type 1 PCMCIA card on the TSX P57170
Changing the TSX MRP 2048 P memory card's battery . . . . . . . . . . . . . . . . . . 172
What happens after you press the processor RESET button . . . . . . . . . . . . . . 174
Chapter 14
TSX P57 103 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
General characteristics of TSX P 57 103 processors . . . . . . . . . . . . . . . . . . . . 181
Chapter 15
TSX P57 153 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
General characteristics of TSX P57 153 processors . . . . . . . . . . . . . . . . . . . . . 183
Chapter 16
TSX P57 203 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
General characteristics of TSX P57 203 processors . . . . . . . . . . . . . . . . . . . . . 185
Chapter 17
TSX P57 253 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
General characteristics of TSX P57 253 processors . . . . . . . . . . . . . . . . . . . . . 187
Chapter 18
TSX P57 2623 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
General characteristics of TSX P57 2623 processors . . . . . . . . . . . . . . . . . . . . 189
Chapter 19
TSX P57 2823 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
General characteristics of TSX P57 2823 processors . . . . . . . . . . . . . . . . . . . . 191
Chapter 20
TSX P57 303 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
General characteristics of TSX P57 303 processors . . . . . . . . . . . . . . . . . . . . . 193
Chapter 21
TSX P57 353 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
General characteristics of TSX P57 353 processors . . . . . . . . . . . . . . . . . . . . . 195
Chapter 22
TSX P57 3623 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
General characteristics of TSX P57 3623 processors . . . . . . . . . . . . . . . . . . . . 197
Chapter 23
TSX P57 453 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
General characteristics of TSX P57 453 processors . . . . . . . . . . . . . . . . . . . . . 199
Chapter 24
TSX P57 4823 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
General characteristics of TSX P57 4823 processors . . . . . . . . . . . . . . . . . . . . 201
Chapter 25
Premium TSX P57 processor: general characteristics . . . . 203
Electrical characteristics of TSX P57 processors . . . . . . . . . . . . . . . . . . . . . . . 204
Devices which can be connected to or built into the processor . . . . . . . . . . . . . 206
Defining and counting application-specific channels . . . . . . . . . . . . . . . . . . . . . 207
Chapter 26
Processor performance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 209
MAST task cycle time: program processing Ppt . . . . . . . . . . . . . . . . . . . . . . . . 211
MAST task cycle time: input/output internal processing . . . . . . . . . . . . . . . . . . 213
Example of the calculation of cycle times of a MAST task under the following
Part IV
Atrium PCX 57 processors . . . . . . . . . . . . . . . . . . . . . . 221
Chapter 27
PCX 57 Processors: introduction . . . . . . . . . . . . . . . . . . . . . . 223
Physical description of PCX 57 processors. . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Dimensions of PCX 57 processor cards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 228
The different components of a PCX 57 card . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Chapter 28
PCX 57 Processors: installation . . . . . . . . . . . . . . . . . . . . . . . 231
Physical installation of the PCX 57 processor in the PC . . . . . . . . . . . . . . . . . . 233
Logical installation of the PCX 57 processor on the X Bus . . . . . . . . . . . . . . . . 234
How to configure the PCX 57 processor address on the X Bus . . . . . . . . . . . . 238
How to configure the processor’s standard I/O address on the ISA bus. . . . . . 240
How to install the PCX 57 processor card in the PC . . . . . . . . . . . . . . . . . . . . . 243
Integrating a PCX 57 processor into an X Bus section . . . . . . . . . . . . . . . . . . . 245
How to install/remove the memory extension card on the PCX 57 processor . 248
Processing on insertion/extraction of a PCMCIA memory card on a PCX 57 PLC
Memory cards for PCX 57 processors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Precautions to be taken when replacing a PCX 57 processor . . . . . . . . . . . . . 251
Chapter 29
PCX 57 processors: Diagnostics . . . . . . . . . . . . . . . . . . . . . . 253
Description of PCX 57 processor LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
Changing the PCX 57 RAM memory backup battery . . . . . . . . . . . . . . . . . . . . 256
Changing the PCX 57 RAM memory PCMCIA card battery . . . . . . . . . . . . . . . 259
What happens after you press the processor RESET button . . . . . . . . . . . . . . 261
How the PCX 57 behaves after an action on the PC . . . . . . . . . . . . . . . . . . . . 262
Finding errors via the processor status LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . 263
Chapter 30
PCX 57 203 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 265
General characteristics of the PCX 57 203 processor . . . . . . . . . . . . . . . . . . . 265
9
10
Chapter 31
PCX 57 353 processor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267
General characteristics of the PCX 57 353 processor . . . . . . . . . . . . . . . . . . . . 267
Chapter 32
Atrium PCX 57 CPU: general characteristics . . . . . . . . . . . . 269
Electrical characteristics of PCX 57 processors . . . . . . . . . . . . . . . . . . . . . . . . 270
Devices which can be connected to or built into the processor . . . . . . . . . . . . . 271
Defining and Counting Application-specific channels . . . . . . . . . . . . . . . . . . . . 272
Part V
TSX PSY… supply modules . . . . . . . . . . . . . . . . . . . . . . 275
Chapter 33
TSX PSY… supply modules: introduction. . . . . . . . . . . . . . . 277
Chapter 34
TSX PSY … supply modules: installation . . . . . . . . . . . . . . . 283
Installation/mounting TSX PSY … supply modules . . . . . . . . . . . . . . . . . . . . . . 284
Rules for connecting TSX PSY supply modules . . . . . . . . . . . . . . . . . . . . . . . 285
Connecting alternating current power supply modules . . . . . . . . . . . . . . . . . . . 287
Connecting direct current power supply modules from a floating 24 or 48 VDC direct
Connecting direct current power supply modules from an alternating current network
Sensor and pre-actuator power supply servo control . . . . . . . . . . . . . . . . . . . . 294
Chapter 35
TSX PSY … supply modules: diagnostics. . . . . . . . . . . . . . . 299
Back-up battery on TSX PSY ... power supply modules . . . . . . . . . . . . . . . . . . 301
What happens after pressing the RESET button on a power supply module . . 303
Chapter 36
TSX PSY … supply modules : auxiliary functions . . . . . . . . 305
Alarm relay on TSX PSY supply modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
Chapter 37 TSX PSY power supply modules: breakdown of power
consumption and power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 311
Breakdown of power consumption for selection of the power supply module . 312
Consumption breakdown of analog/counting/movement control modules . . . . 317
Consumption breakdown of communication modules. . . . . . . . . . . . . . . . . . . . 318
Consumption breakdown (other modules) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 320
Chapter 38
TSX PSY 2600 power supply module . . . . . . . . . . . . . . . . . . . 321
Characteristics of the TSX PSY 2600 power supply module . . . . . . . . . . . . . . 321
Chapter 39
TSX PSY 5500 power supply module . . . . . . . . . . . . . . . . . . . 323
Characteristics of the TSX PSY 5500 power supply module . . . . . . . . . . . . . . 323
Chapter 40
TSX PSY 8500 power supply module . . . . . . . . . . . . . . . . . . . 325
Characteristics of the TSX PSY 8500 power supply module . . . . . . . . . . . . . . 325
Chapter 41
TSX PSY 1610 power supply module . . . . . . . . . . . . . . . . . . . 327
Characteristics of the TSX PSY 1610 power supply module . . . . . . . . . . . . . . 327
Chapter 42
TSX PSY 3610 power supply module . . . . . . . . . . . . . . . . . . . 329
Characteristics of the TSX PSY 3610 power supply module . . . . . . . . . . . . . . 329
Chapter 43
TSX PSY 5520 power supply module . . . . . . . . . . . . . . . . . . . 331
Characteristics of the TSX PSY 5520 power supply module . . . . . . . . . . . . . . 331
Part VI
Process and AS-i supply . . . . . . . . . . . . . . . . . . . . . . . . 333
Chapter 44
Process and AS-i supply: introduction . . . . . . . . . . . . . . . . . 335
General introduction to Process and AS-i power supply modules . . . . . . . . . . 336
Physical description of TBX SUP 10 supply block . . . . . . . . . . . . . . . . . . . . . . 337
Physical description of the TSX SUP 1011 supply module . . . . . . . . . . . . . . . . 338
Physical description of TSX 1021/1051 supply modules. . . . . . . . . . . . . . . . . . 339
Physical description of the TSX SUP A02 supply module. . . . . . . . . . . . . . . . . 340
Description of TSX SUP 1101/A05 supply blocks . . . . . . . . . . . . . . . . . . . . . . . 341
Chapter 45
Process and AS-i suppliers: installation . . . . . . . . . . . . . . . . 347
TBX SUP 10 dimensions/mounting/connections. . . . . . . . . . . . . . . . . . . . . . . . 348
Dimensions/mounting Process and AS-i supply modules . . . . . . . . . . . . . . . . . 350
TSX SUP 1101/A05 supply block dimensions/mounting. . . . . . . . . . . . . . . . . . 354
Chapter 46
Process supply modules: connections . . . . . . . . . . . . . . . . . 357
11
12
Connection of TSX SUP 1011/1021 power supplies . . . . . . . . . . . . . . . . . . . . . 358
Connection of TSX SUP 1051 power supplies . . . . . . . . . . . . . . . . . . . . . . . . . 360
Connection of TSX SUP 1101 power supplies . . . . . . . . . . . . . . . . . . . . . . . . . 362
Chapter 47
Connecting AS-i supply modules. . . . . . . . . . . . . . . . . . . . . . 365
Connection of TSX SUP A02 power supply modules . . . . . . . . . . . . . . . . . . . . 366
Connecting TSX SUP A05 supply modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . 368
Chapter 48
Process and AS-i supply module characteristics. . . . . . . . . 373
Electrical characteristics of process supply modules: TBX SUP 10 and TSX SUP
Electrical characteristics of process supply modules: TSX SUP 1021/1051/1101
Electrical characteristics of AS-i supply modules: TSX SUP A02/A05 . . . . . . . 378
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 383
Saf Information
§
General electrical safety
General points This manual is meant to be used by people who are qualified in the technology needed to work with and maintain the products described therein. It contains the required information which is adequate to conform with the proper use of the products. However, those who wish to make more "advanced" use of our products may find it necessary to consult our nearest distributor in order to obtain additional information.
The manual's contents are not binding and in no way restrict or infringe on the clauses of the guarantee.
User qualifications
Only qualified persons are authorized to use, work with or maintain these products.
The interference of non-qualified persons or failure to observe the security setpoints contained in this manual, or attached to the devices, can endanger the safety of such persons, or irretrievably damage the equipment. The following persons can be designated as " qualified persons ": l l at application design level, design office personnel who are familiar with automation security concepts (e.g., a design engineer, etc.), as far as the use of the devices is concerned, people who are familiar with the l installation, connection and starting of automatic devices (for example, a fitter or cable installer during the installation phase, an operating technician, etc.) as far as operating is concerned, persons familiar with using and managing l automatic devices (for example an operator, etc.) as far as preventive or corrective maintenance is concerned, persons trained and qualified in regulating or repairing automatic devices (for example an operating technician, an after-sales service technician, etc.).
13
TSX DM 57 xxF
Safety Information
Electrical and thermal properties
Details of the electrical and thermal characteristics of the devices can be found in the associated technical manuals (operating manuals, service instructions).
14
TSX DM 57 xxF
About the Book
At a Glance
Document Scope This manual describes the installation of the Premium range of PLCs and their main accessories:
It is made up of 6 sections: l l l l l l
1 General introduction to a TSX P57 PLC station and a PCX 57 PLC station,
2 Standard and extendable TSX RKY racks ,
3 TSX P57 Premium Processors,
4 PCX 57 Atrium Processors,
5 TSX PSY power supply modules,
6 Process and AS-i Power Supplies.
Validity Note The updated version of this manual takes the new processors into account.
User Comments We welcome your comments about this document. You can reach us by e-mail at
TSX DM 57 xxF
15
About the Book
16
TSX DM 57 xxF
Premium and Atrium PLC stations
I
At a Glance
Aim of this Part
What's in this
Part?
The Part gives a general introduction to the Premium TSX P57 PLC station and the
Atrium PCX 57 PLC station.
This part contains the following chapters:
Chapter
1
2
3
4
Chapter Name
Introduction to Premium and Atrium PLC stations
General introduction to the components of a PLC station
General introduction to the different configurations of a PLC station
Operating Standards and Conditions
Page
17
TSX DM 57 xxF
TSX P57/PCX 57 stations
18
TSX DM 57 xxF
Introduction to Premium and
Atrium PLC stations
1
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter gives a general introduction to TSX P57 and PCX 57 PLC stations.
This chapter contains the following topics:
Topic
TSX P57 PLC station
PCX 57 PLC station
Page
TSX DM 57 xxF
19
Introduction to Premium and Atrium PLC stations
TSX P57 PLC station
General
Illustration
Premium TSX P57 automated platform processors manage the entire PLC station, which is made up of "Discrete" input/output modules, analog input/output modules and application-specific modules. These can be distributed over one or several racks connected to the X Bus or the field bus.
Example of a TSX P57 PLC station:
7
5 6
Number table
1 2 3 4
Description according to the addresses in the diagram above:
4
5
6
7
Number
1
2
3
Description
Double format power supply module.
Processor module.
X Bus extension module.
Input/output module.
Standard format power supply module.
Processor module.
TSX RKY rack.
20
TSX DM 57 xxF
Introduction to Premium and Atrium PLC stations
PCX 57 PLC station
General
Illustration
Atrium PCX 57 coprocessors are built into a PC and manage an entire PLC station composed of the same input/output modules as the Premium processors (i.e.
"Discrete", analog, application and communication modules). These modules can be distributed over one or more racks connected to the X Bus.
Example of a PCX 57 PLC station:
4
3
2
1
Number table Description according to the addresses in the diagram above:
3
4
Number
1
2
Description
Coprocessor.
Supply module.
Input/output modules.
TSX RKY rack.
TSX DM 57 xxF
21
Introduction to Premium and Atrium PLC stations
22
TSX DM 57 xxF
General introduction to the components of a PLC station
2
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to provide an overview of the different components which may make up a PLC station.
This chapter contains the following topics:
Topic
General introduction to TSX P57 processors
General introduction to PCX 57 processors
General introduction to TSX RKY racks
General introduction to TSX PSY power supply modules
General introduction to Process and AS-i TSX SUP and TSX 1021/1051 power supply modules
General introduction to the TSX REY X Bus extension module
General introduction to TSX DEY/DSY/DMY input/output modules
General introduction to TSX CTY/CCY counting modules
Introduction to TSX CAY axis control modules
General introduction to TSX CFY step by step control modules
General introduction to TSX SCY/ETY communication
General introduction to the AS-i bus interface module: TSX SAY
General introduction to the TSX ISPY weighing module
General introduction to the TSX FAN ventilation module
General introduction to the TSX PAY emergency stop monitoring module
Page
23
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to TSX P57 processors
General points Each PLC station is provided with a processor, chosen according to: l l l l its integration type: integration on rack or integration in a PC, the processing power necessary: number of discrete I/Os, analog I/Os, etc., memory capacity, processing type: sequential or sequential + process control.
See
TSX P57 Premium processors, p. 141.
Table of different sequential and rack-insertable processor format types:
Processor
Standard format processors: l l
TSX P57 103,
TSX P57 153.
Illustration
Double format processors: l l l l l
TSX P57 203,
TSX P57 253,
TSX P57 303,
TSX P57 353,
TSX P57 453.
24
TSX DM 57 xxF
General introduction to the components of a PLC station
Illustration Processor l l l l
Double format processors with on-board
Ethernet:
TSX P57 2623,
TSX P57 2823,
TSX P57 3623,
TSX P57 4823.
TSX DM 57 xxF
25
General introduction to the components of a PLC station
General introduction to PCX 57 processors
General points
Illustration
Installed on the ISA bus of an industrial or office PC running in a Windows 95 or NT environment, they are used to control a PLC station.
Also, installation of a communication driver enables transparent communication between the host PC and the processor, without the need for another programming terminal.
There are two types of sequential Atrium PCX 57 processor that can be integrated in a PC: l l
PCX 57 203,
PCX 57.353.
See
Atrium PCX 57 processors, p. 221.
Illustration of a PCX 57 processor:
PCX 57 203/353
26
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to TSX RKY racks
General points
Examples
Two families of racks are offered: l Standard racks 6, 8 and 12 positions: l they are used to build a PLC station which is limited to a single rack,
Extendable racks 4, 6, 8 and 12 positions: they are used to make up a PLC station that can contain up to: l a maximum of 16 racks if the station is made up of racks with 4, 6, or 8 positions, l a maximum of 8 racks if the station is made up of racks with 12 positions.
See
TSX RKY.. standard and extendable racks, p. 65.
The following illustration shows the standard 6-position TSX RKY rack:
The following illustration shows the extendable 12-position TSX RKY rack:
X Bus
TSX DM 57 xxF
27
General introduction to the components of a PLC station
General introduction to TSX PSY power supply modules
General points
Illustration l l
Each rack requires a power supply module (See TSX PSY… supply modules,
p. 275) defined according to the distributed network (alternating or direct current)
and the power required for the rack.
There are two types of modules: standard format power supply module, double format power supply module.
The following illustration shows the two formats for TSX PSY power supply modules: standard format supply module for alternating or direct current network double format supply module for alternating or direct current network
28
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to Process and AS-i TSX SUP and TSX 1021/1051 power supply modules
Process power supply modules
Illustration
A wide range of power supply units and modules is offered to meet your needs in the best possible way. Controlled by Premium TSX/PCX PLCs and designed to supply the peripherals of an automation system with 24 VDC, they can all be mounted on a Telequick AM1-PA mounting board and some can be mounted on a
AM1-DP200 / DE 200 central DIN rail.
See
Process and AS-i supply, p. 333.
The following illustration shows the various types of TSX SUP and TSX 1021/1051 process power supply modules:
24 VDC / 1A 24 VDC / 1A 24 VDC / 2A
24 VDC / 5A
24 VDC / 10A
TSX DM 57 xxF
29
General introduction to the components of a PLC station
AS-i power supply module
They are designed to supply 30 VDC to components connected to the AS-i field bus.
Illustration:
30 VDC AS-i / 2.4 A 30 VDC AS-i / 5A and 24 VDC
30
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to the TSX REY X Bus extension module
General This module allows the extension of two bus segments from the rack supporting the processor, up to a maximum distance of 250 meters. Each extended segment is able to support racks distributed along the X Bus to a maximum length of 100 meters.
See
X Bus extension module, p. 123.
Illustration: TSX REY X Bus extension module
TSX DM 57 xxF
31
General introduction to the components of a PLC station
General introduction to TSX DEY/DSY/DMY input/output modules
Discrete inputs/ outputs
A wide range of discrete input/output modules are available to meet your needs in the best possible way. These modules differ from one another in their:
Characteristics
modularity type of inputs type of outputs type of connectors
Description
8, 16, 28, 32 or 64 channels.
l l modules with direct current inputs (24VDC,
48VDC), modules with alternating current inputs
(24VAC, 48VAC, 110VAC, 240VAC).
l l l modules with relay outputs, modules with direct current (24VDC / 0.1A -
0.5A - 2A, 48VDC / 0.25A - 1A) static outputs, modules with alternating current (24VAC /
130VAC / 1A, 48VAC / 240 VAC / 2A) static outputs.
screw terminal blocks and HE10 connectors allow the connection of sensors and preactuators via the TELEFAST 2 prewiring system.
Illustration:
HE10 connector Screw terminal block connector
64 I/64 O 32 I/32 O 28 I/O (16+12 O) 16 I
32 I
8 I - 16 I
8 O - 16 O
32
TSX DM 57 xxF
Analog inputs/ outputs
General introduction to the components of a PLC station
The range of analog input and output modules can meet your main needs. These modules differ from one another in their:
Characteristics modularity performance and range of signals offered type of connectors
Description
4, 8, 16 channels.
voltage/current, thermoelectric couple, multirange (thermoelectric couple, heat probe, voltage/current).
screw terminal blocks or 25-pin SUB D connectors allow the connection of the sensors via the TELEFAST 2 prewiring system.
Example: 25-pin SUB D connectors
Example: screw terminal block connectors
TSX DM 57 xxF
33
General introduction to the components of a PLC station
General introduction to TSX CTY/CCY counting modules
General points
Illustration
Premium and Atrium PLCs offer main counting functions (down-counting, upcounting, up/down counting) from the application-specific "counting" modules.
Three modules are offered: l a 2-channel module and a 4-channel module for the incremental encoder, with a maximum reading frequency of 40 kHz, l a 2-channel module for: l l incremental encoder, with a maximum reading frequency of 500 kHz, absolute SSI series encoder, with a maximum reading frequency of 2 MHz.
Illustration of different types of TSX CTY/CCY counting modules:
2-channel module 4-channel module
2-channel module (incremental encoder/absolute series encoder).
34
TSX DM 57 xxF
General introduction to the components of a PLC station
Introduction to TSX CAY axis control modules
General points Using the application-specific "axis control" modules, Premium PLCs can be used to manage movement control applications, driven by servomotors and with an analog value speed setpoint (+/- 10V).
Five modules are offered:
Module
2-channel module
2-channel module
4-channel module
4-channel module
3-channel module characteristics allows controlled positioning with two independent, linear, limited axes.
allows controlled positioning with two independent, circular, infinite axes.
allows controlled positioning with four independent, linear, limited axes.
allows controlled positioning with four independent, circular axes.
allows positioning on 2 or 3 synchronized axes (linear interpolation).
TSX DM 57 xxF
35
General introduction to the components of a PLC station
Illustration Illustration of different types of TSX CAY axis control modules:
2-channel module 4-channel module
3-channel module
36
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to TSX CFY step by step control modules
General points
Illustration
Using application-specific "step by step command" modules, Premium and Atrium
PLCs can be used to manage movement control modules, controlled by translators with a frequency speed setpoint.
l l
Two modules are offered: a 1-channel module which is used to control a translator, a 2-channel module which is used to control two translators,
Illustration of different types of TSX CFY modules:
1-channel 2-channel
TSX DM 57 xxF
37
General introduction to the components of a PLC station
General introduction to TSX SCY/ETY communication
General points Different modes of communicationcan be used with Premium PLCs: l TSX processor communication on the terminal port: these have two terminal ports (TER) and (AUX), a non-insulated RS 485 serial link, UNI-TELWAY or character mode protocol.
l
These terminal ports can be used to connect: l a programming terminal and/or an operator dialog console (UNI-TELWAY master mode), l the station to a multipoint UNITELWAY link (master or slave UNI-TELWAY l mode), a printer or a terminal in character mode.
Note: the communication protocol, as defined in the configuration, is identical for both ports.
PSX processor communication on the terminal port: these have one terminal port (TER), a non-insulated RS 485 serial link, UNI-
TELWAY or character mode protocol.
As with TSX processors, these can be used to connect: l l l l a programming terminal or an operator dialog console (UNI-TELWAY master mode), the station to a multipoint UNITELWAY link (master or slave UNI-TELWAY l mode), l a printer or a terminal in character mode.
Master FIPIO communication, built-in to some processors ,
TSX P57x53 and PCX P57 353 processors feature as standard a master FIPIO link, used to provide remote operation (maximum 15 kms) of devices such as:
- discrete I/Os,
- analog I/Os,
- speed drives,
- operation and supervising stations,
- devices,
- etc.
Communication by means of PCMCIA cards which can be built into the processor or the application-specific communication module TSX SCY
21601 : the processors and the application-specific communication module TSX
SCY 21601 have a slot which is used for accommodating an extended type III
PCMCIA communication card,
Communication via application-specific modules :
TSX SCY 2160 module:
This module, which can be integrated in all TSX/PCX Premium PLC station racks, has: l a built-in communication channel (1), multiprotocol (UNITELWAY, Modbus/
Jbus, character mode), isolated RS 485 serial link,
38
TSX DM 57 xxF
General introduction to the components of a PLC station l a slot (2) for receiving an extended PCMCIA type III format communication card.
TSX ETY 110/4102/PORT/5102 module: l l
Module enabling communication in an Ethernet multi-network architecture with a communication channel providing two types of connection: connection to an ETHWAY network, connection to an TCP_IP network.
PCMCIA cards PCMCIA type III format communication cards (See TSX P57 processors:
Illustrations The following table illustrates the different modes of communication:
Illustration Description
TER and AUX ports on TSX processors.
TER ports on PCX processors.
TSX DM 57 xxF
39
General introduction to the components of a PLC station
Illustration Description
FIPIO link on TSX processors.
FIPIO link on PCX processors.
Built-in Ethernet links for TSX
P57 ••23 processors.
40
TSX DM 57 xxF
TSX DM 57 xxF
Illustration
General introduction to the components of a PLC station
Description
Communication by means of
PCMCIA cards which can be built in to the processor or the module.
Communication via application-specific module
TSX SCY 21601: l 1: built-in communication channel, l 2: slot for PCMCIA card.
Communication via application-specific module
TSX ETY 110.
41
General introduction to the components of a PLC station
General introduction to the AS-i bus interface module: TSX SAY
General points
Illustration
This is a module which is used to connect an AS-i bus to a Premium TSX/PCX PLC station.
This master module manages and coordinates bus access. It transmits data to all slaves and receives data from them.
Illustration of the TSX SAY 100 module:
42
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to the TSX ISPY weighing module
General
Illustration
Using the TSX ISPY 101 and TSX ISPY 101 application-specific "weighing" modules, TSX Premium PLCs can be used to manage weighing applications: dosage, multi-product dosage, grading, flow control, weight totalizer, etc.
This module offers a measurement input for a maximum of 8 sensors, 2 rapid discrete outputs and a serial link for a displayed report.
Illustration of the TSX ISPY 100/101 module:
TSX DM 57 xxF
43
General introduction to the components of a PLC station
General introduction to the TSX FAN ventilation module
General
Illustration
Depending on the rack modularity (4, 6, 8 or 12 positions), one, two or three ventilation modules can be installed above each rack to help cool the different modules by forced convection.
l l
These ventilation units should be used in the following scenarios:
Ambient temperature in the 25°C...60°C range ,
Ambient temperature in the 60°C70°C range .
Three types of ventilation module are offered: l l ventilation module with 110 VAC power supply, ventilation module with 220 VAC power supply, l ventilation module with 24 VDC supply,
See
Illustration of the TSX FAN ventilation module:
44
TSX DM 57 xxF
General introduction to the components of a PLC station
General introduction to the TSX PAY emergency stop monitoring module
General points These are modules with built-in safety device, designed to control machine emergency stop circuits with the utmost safety.
These modules are used to cover safety functions up to category 4 according to the
EN 954-1 standard.
l l
Two modules are offered:
1 module consisting of 12 inputs and 2 outputs,
1 module consisting of 12 inputs and 4 outputs.
Illustration of the TSX PAY module:
TSX DM 57 xxF
45
General introduction to the components of a PLC station
46
TSX DM 57 xxF
General introduction to the different configurations of a PLC station
3
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter gives a general introduction to the different configurations which are possible for TSX and PCX PLC stations.
This chapter contains the following topics:
Topic
Different types of Premium PLC stations
Different types of PLC stations with Atrium processors.
Page
TSX DM 57 xxF
47
General introduction to the different configurations of a PLC station
Different types of Premium PLC stations
General points
TSX P57 10 station
The choice of rack (standard or extendable) and processor type defines the maximum capacities of a TSX Premium PLC station.
l the TSX P57 stations are composed of TSX P57 103 and 153 single format processors and TSX P57 203/253/2623/2823/303/353/3623/453/4823 double format processors.
Without X Bus extension module:
Station with standard rack:
1 rack, 6, 8 or 12 positions.
Station with extendable racks:
2 racks 12 positions or,
4 racks 4, 6 or 8 positions, maximum length of
X Bus: 100 meters
With X Bus extension module:
Principal X Bus segment
X Bus
≤
100m
Processor
Remote X Bus segment
Remote X bus
≤ 250 meters
X Bus
≤ 100m
Station with extendable racks:
2 racks 12 positions or,
4 racks 4, 6 or 8 positions
2 possible remotes, maximum length of a remote: 250 meters, maximum length of the X Bus segments: 100 meters.
48
TSX DM 57 xxF
General introduction to the different configurations of a PLC station
TSX 57 20/30/40 station
Without X Bus extension module:
Station with standard rack:
1 rack, 6, 8 or 12 positions.
Station with extendable racks:
8 racks 12 positions or,
16 racks 4, 6 or 8 positions, maximum length of
X Bus: 100 meters
100 meters max.
TSX DM 57 xxF
49
General introduction to the different configurations of a PLC station
With X Bus extension module:
Principal X Bus segment
Remote X bus
≤
250 meters
Segment 1 remote from X Bus
X Bus
≤ 100m
X Bus
≤
100m
Processor
Station with extendable racks:
8 racks 12 positions or,
16 racks 4, 6 or 8 positions
2 possible remotes, maximum length of a remote: 250 meters, maximum length of the X Bus segments: 100 meters.
Remote X bus
≤
250 meters
X Bus
≤
100m
Segment 2 remote from X Bus
50
TSX DM 57 xxF
General introduction to the different configurations of a PLC station
Different types of PLC stations with Atrium processors.
General points
PCX 57 203 station
By selecting the PCX 57 203 or 353 processor type, you set the maximum capacities of a Premium PCX PLC station.
This type of station, with the processor integrated in a PC, will be controlled with extendable racks.
Without X Bus extension module:
Extendable racks
TSXRKY •• EX
PCX 57203
X1
PC
Station with extendable racks:
2 racks 12 positions or,
4 racks 4, 6 or 8 positions, maximum length of X Bus (X1+X2): 100 meters.
With X Bus extension module:
Segment 1 remote from X Bus
X Bus
≤ 100 m
X2
PCX 57353
PC
Segment 2 remote from X Bus
Station with extendable racks:
2 racks 12 positions or,
4 racks 4, 6 or 8 positions,
2 possible remotes, maximum length of a remote: 250 meters – X1, maximum length of the X Bus segments: 100 meters.
TSX DM 57 xxF
51
General introduction to the different configurations of a PLC station
PCX 57 353 station
Without X Bus extension module:
PC
PCX 57353
X1
Station with extendable racks:
8 racks 12 positions or,
16 racks 4, 6 or 8 positions, maximum length of X Bus (X1+X2): 100 meters
Extendable racks
TSXRKY •• EX
X2
52
TSX DM 57 xxF
TSX DM 57 xxF
General introduction to the different configurations of a PLC station
With X Bus extension module:
Segment 1 remote from X Bus
X Bus
≤ 100m remote X Bus
≤ 250m-X1
PCX 57353
X Bus
≤ 100m
Segment 2 remote from X Bus
Station with extendable racks:
8 racks 12 positions or,
16 racks 4, 6 or 8 positions, two possible remotes, maximum length of a remote: 250 meters – X1 maximum length of the X Bus segments: 100 meters remote X Bus
≤
250m-X1
Principal X Bus segment
53
General introduction to the different configurations of a PLC station
54
TSX DM 57 xxF
Operating Standards and
Conditions
4
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This chapter deals with the operating standards and conditions of TSX Premium
PLCs.
This chapter contains the following topics:
Topic
Standards and Certification
Operating conditions and environmental conditions to be avoided
Premium PLC protection processing
Page
55
TSX DM 57 xxF
Operating Standards and Conditions
Standards and Certification
General Premium TSX/PMX/PCX PLCs have been developed to conform to the principal national and international standards for industrial electronic PLC equipment.
l Programmable PLCs: specific requirements: functional characteristics, resistance, safety etc.
l
IEC 61131-2, CSA 22.2 N° 142, UL 508
Merchant navy requirements of the major international organisations:
ABS, BV, DNV, GL, LROS, RINA, RRS, CCS etc.
l l
Adhering to European Directives:
Low Voltage: 73/23/EEC amendment 93/68/EEC
Electromagnetic Compatibility: 89/336/EEC amendments 92/31/EEC and 93/68/
EEC
Electric qualities and self-extinguishability of insulating materials: UL 746C, UL
94 l Danger Zones Cl1 Div2 CSA 22.2 N° 213
"THIS EQUIPMENT IS SUITABLE FOR USE IN CLASS I, DIVISION 2,
GROUPS A, B, C AND D OR NON-HAZARDOUS LOCATIONS ONLY"
WARNING: "EXPLOSION HAZARD - DO NOT DISCONNECT WHILE CIRCUIT
IS LIVE UNLESS AREA IS KNOWN TO BE NON-HAZARDOUS"
56
TSX DM 57 xxF
Operating Standards and Conditions
Operating conditions and environmental conditions to be avoided
Operating temperature/ hygrometry/ altitude
Data table:
Ambient temperature when operative
Relative humidity
Altitude
0°C to +60°C (IEC 1131-2 = +5°C to +55°C)
10% to 95% (without condensation)
0 to 2000 meters
Power supply voltages
Data table:
Voltage
Frequency
Brown-outs
Harmonic rate
Residual ripple included nominal 24 VDC 48 VDC 100 to 240VAC 100...120/200...240 VAC limit 19 to 30 VDC 19...60VDC (1) 90 to 264 VAC 90 to 140/190 to 264VAC nominal limit duration repetition
-
≤
1
µσ
≥
1
σ
-
-
-
≤
1
µσ
≥
1
σ
-
50/60 Hz
47/63 Hz
≤
1/2
π e
ριοδ
≥
1
σ
10%
50/60 Hz
47/63 Hz
≤
1/2
π e
ριοδ
≥
1
σ
10%
5% 5% -
(1) Possible up to 34 VDC, limited to 1 hour every 24 hours.
For TSX PSY 1610 and TSX PSY 3610 power supplies, and when using relay output modules, this scope is reduced to 21.6V...26.4V.
TSX DM 57 xxF
57
Operating Standards and Conditions
Human and material safety
Data table:
Test Designation
Dielectric rigidity and
Isolation resistance *
Norms
IEC 61131-2
UL 508
CSA 22-2 N°142
IEC 60950
Maintaining ground connections*
IEC 61131-2
UL 508
CSA 22-2 N°142
Leakage Current *
Enclosures for protection * IEC 61131-2
CSA 22-2 N°142
IEC 60950
Impact Resistance
CSA 22-2 N°142
IEC 60950
CSA 22-2 N°142
IEC 60950
Legend
*: Tests required by EC directives
Levels
24 - 48 V Power supply
100 -220 V Power supply
< 48V Discrete I/Os
> 48V Discrete I/Os
> 10 M
Ω
< 0.1
Ω
/ 30 A / 2 min
< 3.5 mA fixed device
IP 20
Drop / 1.3 m / 500 g Sphere
1500 Vrms
2000 Vrms
500 Vrms
2000 Vrms
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
58
TSX DM 57 xxF
Operating Standards and Conditions
Resistance of devices to power supply L.F. turbulence
Data table:
Test Designation
Voltage and frequency
Variation *
Continuous voltage variation *
Harmonic 3 *
Momentary
Interruptions *
Voltage peaks and troughs *
Norms
EN 50082-1
EN 50082-1
IEC 61131-2
IEC 61131-2
IEC 61131-2
Levels
Un 15% / Nf 5% 30 min x 2
Un 20% / Nf 10% 5 s x 2
0.85 Un - 1.2 Un 30 + 30 min
+ 5% ripple maximum
10% Un
0° / 5 min - 180° / 5 min
AC 10 ms
DC 1 ms
Un-0-Un; Un / 60s 3 cycles separated by 10 s
Un-0-Un; Un / 5s 3 cycles separated by 1 to 5 s
Un-0.9-Un; Un / 60s 3 cycles separated by 1 to 5 s
Legend
Un: Nominal Voltage Nf: Nominal Frequency Ud: Power-on detection level
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
TSX DM 57 xxF
59
Operating Standards and Conditions
Resistance to
H.F. turbulence
Data table:
Test Designation
Amortized oscillatory wave *
Norms
IEC 61131-2
IEC 61000-4-12
Fast transients (bursts)
*
EN 50082-1
IEC 61000-4-4
Hybrid shockwave IEC 61000-4-5
Electrostatic Discharge
*
IEC 61131-2
IEC 61000-4-2
Electromagnetic Field * EN 50082-2
IEC 61000-4-3
Conduit Turbulence * EN 50082-2
IEC 61000-4-6
Levels
AC / DC 1 kV SM
24 V Discrete I/Os 1 kV SM
AC / DC Power Supply 2 kV WM / CM
48 V > Discrete I/Os 2 kV CM other ports 1 kV CM
AC / DC Power Supply 2 kV WM / 1 kV SM
AC Discrete I/Os 2 kV WM / 1 kV SM
DC Discrete I/Os 2 kV WM / 0.5 kV SM
Shielded Cable 1 kV CM
6 kV contact
8 kV air
10 V/m, 80MHz - 2 GHz
Sinusoidal modulation amplitude 80% / 1kHz
10 V 0.15 MHz - 80 MHz
Sinusoidal modulation amplitude 80% / 1kHz
Legend
SM: Serial mode CM: Common Mode WM: Wire Mode
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
60
TSX DM 57 xxF
Operating Standards and Conditions
Electromagnetic
Emissions
Data table:
Test Designation
Conduction Limits *
Norms
EN55022/55011
EN50081-2
Emission Limits *(1) EN55022/55011
EN50081-2
Levels
Class A
150 kHz - 500 kHz quasi-peak 79 dB mV
average 66 dB mV
500 kHz -30 kHz quasi-peak 73 dB mV
average 60 dB mV
Class A d = 10 m
30 kHz -230 kHz quasi-peak 30 dB mV/m
230 kHz -1 kHz quasi-peak 37 dB mV/m
Legend
(1) This test is carried out outside the casing, with the devices secured to a metallic grill and wired as shown in the TSX DG KBL• Manual.
*: Tests required by EC directives
Note: The devices must be installed and wired according to the directions in the
TSX DG KBL• manual.
TSX DM 57 xxF
61
Operating Standards and Conditions
Resistance to climatic variation
Data table:
Test Designation
Dry heat
Cold
Norms
IEC60068-2-2 Bd
IEC60068-2-1 Ad
Levels
60°C / 16h (E.O)
40°C / 16h (E.F)
0°C / 16h
Continuous humid heat IEC60068-2-30 Ca 60°C / 93% Hr /96h (E.O)
40°C / 93% Hr /96h (E.F)
Cyclical humid heat
Cyclical temperature variations
IEC60068-2-30 Db (55°C E.O / 40°C E.F); - 25°C / 93-95% Hr
2 cycles: 12 o' clock - 12h o' clock
IEC60068-2-14 Nb 0°C; -60°C / 5 Cycles: 6 o'clock-6 o'clock
(E.O.)
0°C; -40°C / 5 Cycles: 6 o'clock-6 o'clock
(E.F)
Temperature Rise IEC61131-2
UL508
CSA22-2 N°142
Ambient temperature: 60°C
Legend
E.O: Device open E.F: Device closed Hr: Relative Humidity
Resistance to mechanical constraints
Data table:
Test Designation
Sinusoidal vibrations
Half-sinus shocks
Standards Levels
IEC60068-2-6 Fc 3 Hz - 100 Hz / 1 mm amplitude / 0.7 Gn
Endurance: rf / 90 min / axis (Q limit) < 10
3 Hz - 150 Hz / 1.5 mm / 2 Gn
Endurance: 10 cycles (1 octave / min)
IEC60068-2-27 Ea 15 Gn x 11 ms 3 shocks / direct. / axis
Legend rf: Resonance Frequency Q: Amplification Coefficient
62
TSX DM 57 xxF
Operating Standards and Conditions
Resistance to climatic variation
Data table:
Test Designation
Dry heat whilst inoperative
Cold whilst inoperative
Humid heat whilst inoperative
Thermal shocks whilst inoperative
Standards
IEC60068-2-2 Bb
Levels
70°C / 96h
IEC60068-2-1 Ab -25°C / 96h
IEC60068-2-30 dB 60°C; - 25°C / 93-95% Hr
2 cycles: 12 o' clock - 12h o' clock
IEC60068-2-14 Na -25°C; -70°C / 2 Cycles: 3 o'clock - 3 o'clock
Resistance to mechanical constraints
Data table:
Test Designation
Flat free drop
Free drop from controlled position
Random free drop (conditioned material)
Standards Levels
IEC60068-2-32 Ed 10 cm / 2 drops
IEC60068-2-31 Ec 30° or 10 cm / 2 drops
IEC60068-2-32
Method 1
1 m / 5 drops
TSX DM 57 xxF
63
Operating Standards and Conditions
Premium PLC protection processing
General points TSX/PMX/PCX PLCs in the Premium range meet AP (all-climate processing) processing requirements.
For installations used in industrial production workshops or in environments which come under the title HP (processors in heat and humidity) processing, the Premium
PLCs must be inserted into a protection casing (minimum IP54 as outlined by standards IEC 60664 and NF C 20 040).
Premium PLCs have an IP20 protection index. They can thus be installed without a protection casing in restricted-access areas which do not exceed Pollution Degree
2 (control room free of machines or any activity creating dust).
The PCX card is designed for integration into a host PC. The host device must therefore conform to the IP20 protection index.
Note: For a rack to conform to the IP20 protection index, the unoccupied module slots must be protected by a TSX RKA 02 protection cover.
64
TSX DM 57 xxF
TSX RKY.. standard and extendable racks
II
At a Glance
Aim of this Part
What's in this
Part?
This part deals with TSX RKY..
standard and extendable racks.
This part contains the following chapters:
Chapter
5
6
9
10
7
8
Chapter Name
Introduction to TSX RKY .. standard/extendable racks.
TSX RKY.. standard and extendable racks : installation/ mounting
TSX RKY.. standard and extendable racks: functions
TSX RKY Racks: accessories
Ventilation module
X Bus extension module
Page
TSX DM 57 xxF
65
TSX RKY.. standard and extendable racks
66
TSX DM 57 xxF
Introduction to TSX RKY .. standard/extendable racks.
At a Glance
Aim of this
Chapter
What's in this
Chapter?
l l
This Chapter deals with: general points regarding TSX RKY racks, the physical description of these racks.
This chapter contains the following topics:
Topic
Standard and extendable TSX RKY racks
Standard rack: description
Extendable rack: description
5
Page
TSX DM 57 xxF
67
Introduction to TSX RKY .. standard/extendable racks.
Standard and extendable TSX RKY racks
General points TSX RKY racks form the base unit of Premium PLCs.
These racks serve the following functions: l Mechanical function: they are used to mount a set of modules for a PLC station (i.e. supply modules, l processors, discrete/analog input/output modules, application-specific modules).
They can be mounted in cabinets, machine frames or on panels.
Electrical function: l l the racks have a built-in bus, called X Bus, which distributes: the required supply for each module on the same rack, service signals and data for the whole PLC station when this is made up of several racks.
Note: two families of racks are offered in several modularities (4, 6, 8 and 12 positions): l l standard racks , extendable racks .
Standard racks They are used to make up a PLC station which is limited to a single rack.
This table presents the different standard racks :
Designation
TSX RKY 6
Illustration
6-position rack
68
TSX DM 57 xxF
TSX DM 57 xxF
Designation
TSX RKY 8
Illustration
8-position rack
Introduction to TSX RKY .. standard/extendable racks.
TSX RKY 12 12-position rack
69
Introduction to TSX RKY .. standard/extendable racks.
Extendable racks They are used to make up a PLC station which can have: l l a maximum of 8 TSX RKY 12 EX racks, a maximum of 16 TSX RKY 4EX/6EX/8EX racks.
These racks are distributed on a bus called X Bus, whose maximum length is limited to 100 meters.
A bus extension cable assures rack-to-rack bus continuity.
For applications which require a greater distance, a Bus X extension module allows the extension of two X bus segments from the rack which is supporting the processor to a maximum distance of 250 meters.
This table presents the different extendable racks :
Designation
TSX RKY 4EX
Illustration
4-position rack
TSX RKY 6EX 6-position rack
70
TSX DM 57 xxF
TSX DM 57 xxF
Designation
TSX RKY 8EX
Illustration
8-position rack
Introduction to TSX RKY .. standard/extendable racks.
TSX RKY 12EX 12-position rack
71
Introduction to TSX RKY .. standard/extendable racks.
Standard rack: description
At a Glance
Illustration
They are used to make up a PLC station which is limited to a single rack.
Standard rack
1
3
4
9
6
7
6
8
6
5
2
Description
72
The following table describes the different elements of a standard rack.
6
7
2
3
4
5
Number
1
Description l l
Metal sheet which: l supports the X-Bus electronic card, and protects against EMI and ESD interference.
supports the modules, maintains the rack’s physical rigidity.
Holes to be used as anchor-points for module pins.
Female 48-pin 1/2 DIN connectors for connecting each module to the rack.
When racks are delivered, these connectors are protected by covers, which must be removed before modules are installed.
The connector on the farthest left marked PS is always dedicated to the rack supply module. The other connectors marked 00 to ..
are for receiving all the other module types.
Screw-holes for the module-mounting screws.
Guide-hole to assist in mounting the supply module.
As supply modules have a projecting part on the back, this module cannot be mounted in any other position.
Holes for mounting the rack onto a support. These holes can take M6 screws.
Slot to hold the label for the rack address.
TSX DM 57 xxF
Introduction to TSX RKY .. standard/extendable racks.
Number
8
9
Description
Slot to hold the label for the station network address.
Ground terminals for grounding the rack.
TSX DM 57 xxF
73
Introduction to TSX RKY .. standard/extendable racks.
Extendable rack: description
At a Glance
Illustration
They are used to form a PLC station which can be made up of several racks.
Extendable rack
1
3
4
10
8
5
6
9
6
11
7
6
2
Description
74
The following table describes the different elements of an extendable rack.
6
7
2
3
4
5
Number
1
Description l l
Metal sheet which: l supports the X-Bus electronic card, and protects against EMI and ESD interference.
supports the modules, maintains the rack’s physical rigidity.
Holes to be used as anchor-points for module pins.
Female 48-pin 1/2 DIN connectors for connecting each module to the rack.
When racks are delivered, these connectors are protected by covers, which must be removed before modules are installed.
The connector on the farthest left marked PS is always dedicated to the rack supply module. The other connectors marked 00 to ..
are for receiving all the other module types.
Screw-holes for the module-mounting screws.
Guide-hole to assist in mounting the supply module.
As supply modules have a projecting part on the back, this module cannot be mounted in any other position.
Holes for mounting the rack onto a support. These holes can take M6 screws.
Slot to hold the label for the rack address.
TSX DM 57 xxF
Number
8
9
10
11
Introduction to TSX RKY .. standard/extendable racks.
Description
Slot to hold the label for the station network address.
Ground terminals for grounding the rack.
Microswitch for coding the rack address (extendable racks only).
Female 9-pin SUBD connectors for extending the X-Bus to another rack
(extendable rack only).
TSX DM 57 xxF
75
Introduction to TSX RKY .. standard/extendable racks.
76
TSX DM 57 xxF
TSX RKY.. standard and extendable racks : installation/ mounting
At a Glance
Aim of this
Chapter
What's in this
Chapter?
l l
This chapter deals with: rack installation, mounting these racks.
This chapter contains the following topics:
Topic
Installing racks
Mounting and fixing racks
Connection of the ground to a TSX RKY rack
6
Page
TSX DM 57 xxF
77
TSX RKY.. standard and extendable racks: installation/mounting
Installing racks
Introduction The mounting TSX RKY • • racks requires certain installation rules to be followed.
Rack installation rules: description l l
1 As the different modules (e.g. supply, processors, discrete I/O, etc.) are cooled by natural convection, it is compulsory in order to facilitate ventilation (See
to install the different racks horizontally and vertically .
2 If several racks are installed in the same cabinet, you are advised to comply with the following advice on layout: l leave at least 150 mm between two racks placed on top of each other, to allow l room for cable troughs and help air circulation.
you are advised to install the devices which generate heat (eg transformers, process supply, power contacts, etc.) above the racks, l leave at least 100 mm on each side of a rack to allow room for cabling and to help air circulation.
78
TSX DM 57 xxF
Illustration
TSX RKY.. standard and extendable racks: installation/mounting
The following illustration shows the rules for installation a Greater than or equal to 50 mm .
1 Installation or casing.
2 Trough or cable tray.
TSX DM 57 xxF
79
TSX RKY.. standard and extendable racks: installation/mounting
Overall rack dimensions: illustrations
The following illustrations show the overall dimensions of
TSX RKY 4EX
TSX RKY• • racks.
160 mm (1)
200 mm (2)
187.9 mm
TSX RKY 6/6EX
261.6 mm
TSX RKY 8/8EX
335.3 mm
TSX RKY 12/12EX
482.6 mm
( 1 ) With screw terminal block modules.
( 2 ) Maximum depth for all types of modules and their associated connectors.
80
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: installation/mounting
Mounting and fixing racks
Introduction l l
TSX RKY •• and TSX RKY••EX racks can be mounted: on a 35 mm wide DIN mounting rail using M6x25 screws, on a Telequick mounting grid or on a panel.
The rules for installation (See
Installing racks, p. 78) are to be always followed,
whatever the type of mounting.
Mounting on 35 mm wide DIN mounting rail
Fixing with four M6x25 screws + washers and AF1-CF56
1
/
4
turn sliding nuts.
Diagram illustrating the mounting
Mounting on a panel
( 1 ) TSX RKY 4EX
( 2 ) TSX RKY6 and TSX RKY 6EX
( 3 ) TSX RKY8 and TSX RKY 8EX
( 4 ) TSX RKY 12 and TSX RKY 12EX
Plan of screw-holes (dimensions in mm):
4 fixing holes
(1)
TSX DM 57 xxF
(1) the diameter of the fixing holes must be sufficient to take M6 screws.
( 1 ) The diameter of the fixing holes must be such as to allow M6 screws.
a and b see table.
81
TSX RKY.. standard and extendable racks: installation/mounting
Mounting on an
AM1-PA
Telequick mounting grid
Fix the rack using four M6x25 screws + washers and AF1-EA6 clips nuts.
Plan of screw-holes (dimensions in mm): the following table presents mounting characteristics according to the different TSX
RKY racks:
Racks
TSX RKY 4EX
TSX RKY 6/6EX
TSX RKY 8/8EX a
170.4 mm
244.1 mm
317.8 mm
TSX RKY 12/12EX 465.1 mm b
187.9 mm
261.6 mm
335.3 mm
482.6 mm
Depth
16 mm
16 mm
16 mm
16 mm
Note: Maximum tightening torque for fixing screws: 2.0.N.m.
82
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: installation/mounting
Connection of the ground to a TSX RKY rack
Grounding racks Functional grounding of the racks is guaranteed by the back, which is made of metal.
This means that the PLCs can be guaranteed to conform to environmental norms; assuming, however, that the racks are fixed to a metal support that is correctly connected to ground. The different racks which can make up a TSX P57 PLC station must be mounted either on the same support or on different supports, as long as the latter are correctly interlinked.
For people’s safety, in every case, each rack’s grounding terminal must be linked to the protective ground.
For this, use a green/yellow wire of with a minimum section of 2.5 mm
2
and of the shortest length possible.
Illustration: support connected to the ground yellow/green wire linked to the ground
Note: The PLC’s internal 0V is linked to the ground connection. The ground connection itself being linked to ground.
Maximum lightning moment on the ground connection screw: 2.0 N.m.
TSX DM 57 xxF
83
TSX RKY.. standard and extendable racks: installation/mounting
84
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: functions
7
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This chapter describes the different functions of the TSX RKY..
standard and extendable racks .
This chapter contains the following topics:
Topic
Building a PLC station with Premium processor
Building a PLC station with Atrium processor
PLC station rack addressing
The principle of addressing two racks at the same address
Module addresses
Installing power supplies, processors and other modules
Page
TSX DM 57 xxF
85
TSX RKY.. standard and extendable racks: functions
Building a PLC station with Premium processor
Introduction It is possible to build a PLC station with TSX P57 processor using: l l standard racks (See
Standard racks, p. 68): TSX RKY 6/8/12,
extendable racks (See
Extendable racks, p. 70): TSX RKY 4EX/6EX/8EX/12EX.
Standard racks can be used to build a TSX P57 PLC station limited to a single rack.
Building using standard racks
Building using extendable racks: TSX RKY
4EX/6EX/8EX/
12EX
Extendable racks can be used to build a PLC station that contains a maximum of:
Station
For a TSX 57 10 station
For a TSX 5720, 5730 or 5740 station
Number of racks l l l l
2 TSX RKY 12EX racks,
4 TSX RKY 4EX/6EX/8EX racks.
8 TSX RKY 12EX racks,
16 TSX RKY 4EX/6EX/8EX racks.
86
TSX DM 57 xxF
Diagram
TSX RKY.. standard and extendable racks: functions
TSX DM 57 xxF l l
(1) The same station can contain 4, 6, 8 and 12 position racks that are linked by
X Bus extension cables (See TSX CBY..0K X Bus extension cable (II ≥ 02),
(2) The X Bus must have a line termination (See Line terminator TSX TLYEX,
p. 104) (labeled 2) fitted at each end.
87
TSX RKY.. standard and extendable racks: functions
Note: the cumulative length of all the TSX CBY ..0K cables used in a PLC station must never exceed 100 meters. For applications which require a distance of more than 100 meters between racks, an extension module allows the extension of two
X bus segments from the rack supporting the processor, to a maximum distance of
250 meters, each X bus segment having a maximum distance of 100 meters.
X Bus extension cable
Racks are connected by means of TSX CBY ..
0K X Bus extension cables which are connected to the 9-pin SUB D connectors situated on the right and left of each extendable rack.
Note: As the idea of in and out does not exist at the level of the 9-pin SUB D connector, a cable can enter or leave using either the right or left-hand connector.
Line termination The two racks situated at the ends of the chain must always be fitted with a TSX TL
YEX line termination on the unused 9-pin SUB D connectors, labeled A/ and /B .
88
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: functions
Building a PLC station with Atrium processor
At a Glance It is possible to build a PLC station with PCX 57 processor using extendable racks:
TSX RKY 4EX/6EX/8EX/12EX.
Building using extendable racks
Extendable racks can be used to build a PLC station that contains a maximum of:
Station
For a PCX 57 203 station
For a PCX 57 353 station
Number of racks l l l l
8 TSX RKY 12EX racks,
16 TSX RKY 4EX/6EX/8EX racks.
8 TSX RKY 12EX racks,
16 TSX RKY 4EX/6EX/8EX racks.
Diagram:
TPCX 57 203
X1
PC
X2
TSX DM 57 xxF
89
TSX RKY.. standard and extendable racks: functions l l
(1) The same station can contain 4, 6, 8 and 12 position racks that are linked by
X Bus extension cables (See TSX CBY..0K X Bus extension cable (II ≥ 02),
(2) The X Bus must have a line termination (See Line terminator TSX TLYEX,
p. 104) (labeled 2) fitted at each end.
Note: the cumulative length (X1+X2) of all the TSX CBY..0K cables used in a PLC station must never exceed 100 meters. For applications which require a distance of more than 100 meters between racks, an extension module allows the extension of two X bus segments from the rack which is supporting the PCX 57 processor virtually, to a maximum distance of 250 meters, each X bus segment having a maximum distance of 100 meters.
X Bus extension cable
Racks are connected by means of TSX CBY••0K X Bus extension cables which are connected to the 9-pin SUB D connectors situated on the right and left of each extendable rack and at the top of the front panel of the processor.
Note: As the idea of in and out does not exist at the level of the 9-pin SUB D connector, a cable can enter or leave using either the right or left-hand connector.
Line termination At manufacture, the equivalent of the line terminator /A is built in to the processor and, due to this, the processor forms a termination of the X bus. The extendable rack located at the end of the chain therefore must always have a TSX TLY line terminator, labeled /B on its unused 9-pin SUB D connector.
Note on the PCX
57 processor
By default, the PCX 57 processor is equipped to be mounted as the start of the X bus, and thus, the line termination /A is built-in to it in the form of a removable daughterboard.
If an application requires the integration of the processor inside a Bus X section, a mechanical kit is supplied with the processor to satisfy this requirement.
l l
This mechanical kit is in the form of: a daughterboard which is mounted in place of the line termination A/, a shield equipped with a 9-pin SUB D connector for connecting an X Bus TSX
CBY••0K cable and a cable for connection to the daughterboard.
90
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: functions
PLC station rack addressing
Introduction Two cases can occur for PLC station rack addressing: l l
PLC station built from a standard rack (See
PLC station built from extendable racks (See
Station built from a standard rack
The station is always limited to a single rack, thus the rack address is implicit and has a value of 0 (no microswitches).
Station built from extendable racks
For each station rack an address must be assigned. This address is coded using 4 microswitches found on the rack.
Microswitches 1 to 3 are used to code the address of the rack on the X Bus X (0 to
7), microswitch 4 is used to code two racks (4, 6 or 8 positions) on the same address.
This latter functionality is managed by the PL7 Junior or PL7 Pro software version V
3.3
or above.
Diagram showing the microswitch
TSX DM 57 xxF
Table of rack addresses
Rack addresses
Position of the micro-switches
Note: On delivery, microswitches 1, 2 and 3 are in the ON position (address 0).
91
TSX RKY.. standard and extendable racks: functions
Assigning addresses to different racks
Address 0: l l
this address is always assigned to the rack which supports: the TSX P57 processor physically, the PCX 57 processor virtually.
This rack can be located in any position in the chain.
Addresses 1 to 7: they can be assigned in any order to all the other extendable racks in the station.
Note: the rack address coding must be done before mounting the power supply module.
CAUTION
Address conflict
If, through a mistake, two or more racks are unintentionally positioned at the same address (other than address 0), then the racks concerned as well as all their modules show a fault. Having correctly addressed the racks with faulty addresses, it is necessary to switch off and then switch on the racks concerned.
Failure to follow this precaution can result in injury or equipment damage.
This note only applies to racks with references TSX RKY..EX
If two or more racks are at address 0, the rack supporting the processor does not show a fault.
92
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: functions
The principle of addressing two racks at the same address
Illustration The following diagram shows the principle of addressing two racks at the same address.
1 single rack
TSX RKY 12EX on the same address
2 single racks
TSX RKY 8EX on the same address
2 racks
TSX RKY 6EX on the same address
Microswitch 4 2 racks
TSX RKY 4EX on the same address
TSX DM 57 xxF
Note: take into account the following notes: l l l
TSX RKY 12EX racks cannot have a second rack at the same address.
TSX RKY 8EX/6EX/4EX racks can be intermixed.
Two TSX RKY 8EX/6EX/4EX racks at the same address will not necessarily be linked one after the other. The order of physical distribution is not important.
93
TSX RKY.. standard and extendable racks: functions
Module addresses
At a Glance
Module addressing on standard racks
For all standard and extendable racks, the module address is geographical and will depend upon the position of the module on the rack. The address of each position is indicated under each connector - the connector with address PS is always dedicated to the rack power supply.
l l
Several addressing cases are possible: module addressing on standard racks (See
module addressing on extendable racks (See
l l l for a TSX RKY 6: use addresses 00 to 04, for a TSX RKY 8: use addresses 00 to 06, for a TSX RKY 12: use addresses 00 to 10.
Module addressing on extendable racks
The address of a module will depend upon the position of microswitch 4: l microswitch 4 in the ON position, the modules will have addresses (00 to x), according to the rack type, l microswitch 4 in the OFF position, the modules will have addresses (08 to y), according to the rack type. This functionality is only managed by the PL7 Junior or PL7 Pro software version V 3.3
or above.
the following table shows the addresses in relation to the position of microswitch 4:
Position of microswitch 4
TSX RKY 4EX racks
TSX RKY 6EX racks
TSX RKY 8EX racks
TSX RKY 12EX racks
ON
00 to 02
00 to 04
00 to 06
00 to 10
OFF
08 to 10
08 to 12
08 to 14 unusable
94
TSX DM 57 xxF
Illustration
TSX RKY.. standard and extendable racks: functions
Diagram showing the module addresses on rack TSX RKY 8EX
Micro-switch 4 Module addresses
Note: the shaded addresses are only accessible using PL7 Junior or PL7 Pro software version V 3.3
or above
TSX DM 57 xxF
95
TSX RKY.. standard and extendable racks: functions
Installing power supplies, processors and other modules
Installation on a standard or extendable rack with address 0 and with a
Premium processor
The rack with address 0 must have a power supply module and the processor module. Premium PLCs have two types of power supply (standard format or double format), the position of the processor will depend upon the type of power supply used.
l l
Using a standard format power supply module: the power supply module automatically occupies position PS, the single format processor module is installed in position 00 (preferred position) or in position 01, if position 00 is unavailable.
Illustration l l the double format processor module is installed in positions 00 and 01 (preferred positions) or in positions 01 and 02, if position 00 is unavailable, other modules are installed starting from position 01, 02 or 03 depending on the installation of the processor.
Illustration
96
Using a double format power supply module: l l the power supply module automatically occupies position PS, the single format processor module is always installed in position 01.
Illustration l l the double format processor module is installed in positions 01 and 02, other modules are installed starting from position 02 or 03 depending on the type of processor.
TSX DM 57 xxF
TSX RKY.. standard and extendable racks: functions
Illustration
Installation on an extendable rack with address 0 and with an
Atrium processor
The PCX 57 processor, which is built in to the PC, occupies a virtual position on the rack with address 0. This virtual position should be unoccupied. Premium PLCs have two types of power supply (standard and double format), the unoccupied position will depend upon the type of power supply used.
Using a standard format power supply module: l l the power supply module automatically occupies position PS, position 00, the virtual slot for the processor, must be unoccupied, l the other modules are installed starting at position 01.
Illustration
Using a double format power supply module: l l l the power supply module automatically occupies the positions PS and 00, position 01, the virtual location of the processor, must be unoccupied, the other modules are installed starting from position 02.
Illustration
TSX DM 57 xxF
97
TSX RKY.. standard and extendable racks: functions
Installation on an extendable rack with address 1 to
7, regardless of processor type
Each rack must be equipped with a power supply module, either standard or double format.
Using a standard format power supply module: l l the power supply module automatically occupies position PS, the other modules are installed starting from position 00.
Illustration
Using a double format power supply module: l l the power supply module automatically occupies positions PS and 00, the other modules are installed starting at position 01.
Illustration
98
TSX DM 57 xxF
TSX RKY Racks: accessories
8
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this chapter is to show the different accessories which go with TSX RKY..
racks..
This chapter contains the following topics:
Topic
TSX CBY..0K X Bus extension cable (II ≥ 02)
TSX CBY 1000 X Bus extension cable
Line terminator TSX TLYEX
Positioning of line terminators on a station using a Premium processor
Positioning of line termination on a station using a Atrium processor
TSX RKA 02 protective cover for unoccupied positions
Labeling
Compatibility with the installed base
Page
99
TSX DM 57 xxF
TSX RKY Racks: accessories
TSX CBY..0K X Bus extension cable (II ≥ 02)
At a Glance These cables of predetermined length are used to chain TSX RKY..EX
extendable racks and to transport the different X Bus signals.
When a PCX 57 processor is used, they can also be used to connect the PC’s builtin processor and the first rack in the station.
They are equipped at each end with male 9-pin SUB D connectors, which connect to the female 9-pin SUB D connector on the extendable rack or the PCX 57 processor.
Station with a TSX processor capable of being integrated in the rack
100
Station with a PCX processor capable of being integrated in a PC
TSX DM 57 xxF
TSX RKY Racks: accessories
Important :
The cumulative length of all the cables used in a PLC station is limited to 100 meters.
CAUTION
Insertion and extraction l l l l
Insertion and extraction of a TSX CBY0K cable must only be done with all the station’s elements switched off (racks, PC, etc.)
The minimum bend radius of the X bus cable must be:
40mm for a static application,
80mm for a dynamic application.
Failure to follow this precaution can result in injury or equipment damage.
Different cable types available
To suit different users, several cable lengths are available.
Summary table of different cable types
Product reference
TSX CBY 010K (II
≥
02)
TSX CBY 030K (II
≥
02)
TSX CBY 050K (II
≥
02)
TSX CBY 120K (II
≥
02)
TSX CBY 180K (II
≥
02)
TSX CBY 280K (II
≥
02)
TSX CBY 380K (II
≥
02)
TSX CBY 500K (II
≥
02)
TSX CBY 720K (II
≥
02)
TSX CBY 1000K (II
≥
02)
Lengths
1 meter
3 meters
5 meters
12 meters
18 meters
28 meters
38 meters
50 meters
72 meters
100 meters
TSX DM 57 xxF
101
TSX RKY Racks: accessories
TSX CBY 1000 X Bus extension cable
At a Glance For X Bus lengths less than 100 meters but different from those available as cables with connectors, always use a TSX CBY 1000 cable.
This cable must have TSX CBY K9 connectors fitted at both ends by the user. The assembly procedure is described in the instructions supplied with the cable and the l l l connectors.
For implementation of these cables the following elements are required:
1 TSX CBY 1000 cable,
1 set of two TSX CBY K9 9-pin connectors,
1 TSX CBY ACC10 kit.
1 TSX CBY 1000 cable,
This cable must include one 100-meter reel of cable and two testers to check the cable once the various connections have been made.
Illustration:
Reel
Testers
1 set of two TSX
CBY K9 9-pin connectors l l l l l l
For each connector this set must include:
1 connector body,
1 set of contacts,
1 internal screening cap,
1 external screening cap,
1 ferrule,
1 plastic cover with 2 fixing screws.
Illustration:
102
TSX DM 57 xxF
1 TSX CBY
ACC10 kit
TSX RKY Racks: accessories l l l l
This kit must include:
2 crimping tools and a contact extractor to be used in case of errors,
1 digital ohmmeter,
1 pair of scissors,
1 pair of wire strippers.
Illustration:
Crimping tools
TSX DM 57 xxF
103
TSX RKY Racks: accessories
Line terminator TSX TLYEX
Introduction
At a Glance
When extendable racks (See TSX RKY.. standard and extendable racks: functions,
p. 85) are used, the X Bus must be fitted with a line terminator at each end.
A line terminator is made up of a 9-pin SUB D connector and a cover containing the adaptation components. It is mounted on the 9-pin SUB D 9 connector belonging to the extendable rack at the end of the line.
Illustration:
104
TSX TLYEX line terminations are sold in twos and marked A/ and /B . The bus must be fitted with a terminator A/ at one end and a terminator /B at the other end in no predefined (See Positioning of line terminators on a station using a Premium
CAUTION
Insertion or extraction
Insertion or extraction of a line terminator must only be done with all the station’s racks switched off.
Failure to follow this precaution can result in injury or equipment damage.
TSX DM 57 xxF
TSX RKY Racks: accessories
Positioning of line terminators on a station using a Premium processor
Positioning on a
PLC station containing several TSX
RKY..EX extendable racks
Diagram showing the principle:
Positioning on a
PLC station containing a single TSX
RKY..EX extendable rack
Diagram showing the principle:
Note: When a single extendable rack is used, a line terminator must always be mounted on each of the rack’s 9-pin SUB D connectors.
TSX DM 57 xxF
105
TSX RKY Racks: accessories
Positioning of line termination on a station using a Atrium processor
At a Glance At manufacture, the equivalent of the line terminator /A is built in to the processor and, due to this, the processor forms a termination of the X bus. The extendable rack located at the end of the chain therefore must always have a TSX TLY EX line terminator labeled /B fitted on its unused 9-pin SUB D connector.
Principle diagram:
PC
PCX57
OK NOK
Special case.
When no devices are connected to the X Bus, the TSX TLYEX line terminator /B must be installed on the X Bus connector of the PCX 57 processor.
Illustration:
OK NOK
PCX57
106
TSX DM 57 xxF
TSX RKY Racks: accessories
TSX RKA 02 protective cover for unoccupied positions
At a Glance If a position on a rack is unoccupied, it is advisable to mount a TSX RKA 02 cover designed for this in this position.
This cover is mounted and fixed on the rack like a module with a reduced depth.
TSX RKA 02 covers are sold in indivisible quantities of five.
Illustration
TSX DM 57 xxF
107
TSX RKY Racks: accessories
Labeling
Labeling of module positions on the rack
When the module is in place on the rack, it masks the address of the position, which is printed on the rack.
Due to this and in order to be able to identify the module’s position quickly, each rack is delivered with a page of sticky labels which allow you to label the position of each module.
This sticky label is stuck on the upper part of the module when it is in place on the rack.
Illustration: example of processor module labeling
Label position
Page of labels:
PS
07
00
08
01
09
020 03
10 11
04
12
05
13
06
14
108
TSX DM 57 xxF
Rack labeling
TSX RKY Racks: accessories l l
Each rack is delivered with a set of snap out labels so that for each rack you can label: the address of the rack in the station, the network address of the station when the station is connected to a communication network.
Therefore each rack has two slots where these addresses can be placed.
Illustration:
Network address of the station
Rack address in station
TSX DM 57 xxF
109
TSX RKY Racks: accessories
Compatibility with the installed base
Summary table
2 terminators
TSX TLY (•• 01)
TSX CBY..OK (••
01) cables
Terminators
TSX TLY A+B (••
03)
TSX RKY..E rack(s)
This table gives the compatibility with the installed base in relation to old and new references:
Configuration already in place with
TSX RKY..E
TSX CBY..OK (••
01)
TSX TLY (•• 01)
YES
Previous references
New references
TSX RKY..E
TSX CBY..OK (••
01)
TSX TLYEX A+B (••
03)
TSX RKY..E
TSX CBY..OK (••
02)
TSX CBY 1000
TSX TLYEX A+B (••
03)
TSX RKY..EX
TSX CBY..OK (••
02)
TSX CBY 1000
TSX TLYEX A/+/B
NO NO NO
YES
YES
YES
YES
YES
YES
NO
YES
YES
NO
NO
NO
TSX CBY..OK (••
02) or CBY 1000 cables
TSX RKY..EX rack(s)
Terminators
TSX TLYEX A/+/B
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
110
Note: in a PLC station, the TSX TLY line terminator torque must be to the same index.
•• corresponds to the product version.
TSX DM 57 xxF
Ventilation module
9
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the ventilation module and its installation.
This chapter contains the following topics:
Topic
Ventilation module: general introduction
Ventilation module: physical description
Ventilation module: dimensions
Ventilation module: mounting
Rules for installing racks fitted with ventilation modules
Ventilation module: connections
Ventilation module: characteristics
Page
TSX DM 57 xxF
111
Ventilation module
Ventilation module: general introduction
At a Glance The ventilation modules which are installed above the TSX P57 PLC station racks force air convection in order to make uniform the ambient temperature inside the casing and thus eliminate the various hot spots which may exist.
Note: A temperature probe built into each module informs the user when the ambient temperature has reached its maximum value.
ventilation module:
Use of ventilation modules
The use of these modules is recommended in the following cases: l Ambient temperature in the 25°C...60°C range: the life of the various components of the TSX Premium PLC is increased (MTBF increased by 25%).
l Ambient temperature in the 60°C...0.70°C range: the ambient temperature being limited to 60°C without ventilation, forced ventilation makes it possible to lower the temperature inside the modules by 10°C, which brings the internal temperature of the modules back to the equivalent of 60°C at ambient temperature.
112
TSX DM 57 xxF
Ventilation module
Different module types
Three ventilation modules are available, adapted to the main supply networks: ventilation module with 24 VDC, 110 VAC or 220 VAC power supply.
According to the rack modularity (4, 6, 8 or 12 positions), 1, 2 or 3 ventilation modules are to be fitted above each rack: l l l
12-position racks TSX RKY 12/12EX: 3 ventilation modules,
8-position racks TSX RKY 8/8EX: 2 ventilation modules,
4 and 6-position racks TSX RKY 4EX/6/6EX: 1 ventilation module.
Illustration:
TSX RKY 12/12EX
TSX RKY 8/8EX
TSX RKY 4EX/6/6EX
TSX DM 57 xxF
113
Ventilation module
Ventilation module: physical description
Illustration Descriptive diagram:
Table of labels This table gives you descriptions according to the labels:
2
3
Label
1
4
Description
Terminal block for connecting: l l the module power supply, the supply for the temperature probe and the associated LED or preactuator. Each terminal can receive one 1.5mm
2
wire without a wire end ferrule, or two 1mm
2
wires with wire end ferrules.
Terminal for connecting the module to the ground.
Holes for fixing the module (M4 x 12 screws). If these modules are used with
TSX Premium PLCs, the ventilation modules must be fixed on an AM1-ED
...
35 x 15 mounting rail .
Louvered slats which send air to the front.
114
TSX DM 57 xxF
Ventilation module
Ventilation module: dimensions
Ventilation module alone
Illustrative diagram (dimensions in millimeters):
Ventilation module + rack
Rear view Right-hand view
Illustrative diagram (dimensions in millimeters):
Front view
(1) with screw terminal block module,
(2) maximum depth for all types of modules and their associated connectors.
Characteristics table:
Racks
TSX RKY 4EX
TSX RKY 6/6EX
TSX RKY 8/8EX
TSX RKY 12/12EX
Number of positions
4
6
8
12 a
187.9 mm
261.6 mm
335.3 mm
482.6 mm
TSX DM 57 xxF
115
Ventilation module
Ventilation module: mounting
General points The ventilation modules associated with TSX/PCX Premium PLC’s must be mounted on 35mm wide and 15mm deep mounting rails (type AM1-ED ...
) in order to compensate for the thickness of the rack (See
Mounting and fixing racks, p. 81).
Diagram:
Support
Mounting rail
35x15
Ventilation module
Premium TSX PLC
116
TSX DM 57 xxF
Mounting position
Mounting position for ventilation modules according to rack-type:
Ventilation module
6 position racks (TSX RKY 6/6EX) 8 position racks (TSX RKY 8/8EX)
12 position racks (TSX RKY 12/12EX) 4 position racks (TSX RKY 4EX)
TSX DM 57 xxF
117
Ventilation module
Rules for installing racks fitted with ventilation modules
Illustration Principle diagram: see
118 a = 50 mm b = 30 mm
1 Installation or casing.
2 Trough or cable tray.
TSX DM 57 xxF
Ventilation module
Ventilation module: connections
Connecting the power supply to the ventilation module
Illustration:
Note: If several ventilation modules of the same type are used, a common power supply should be used for all ventilation modules.
Connecting the power supply to the temperature probe
The temperature probe can be supplied either by direct or alternating current and connected to a signaling LED, a PLC input, etc .
Diagram:
TSX DM 57 xxF
Direct current supply
Alternating current supply
Note: If several ventilation modules are used, the probe contacts are set up in series.
119
Ventilation module
Illustration:
Ventilation module 1
Ventilation module 2
Ventilation module 3
(1) 24/28V direct or 110/220V alternating.
120
TSX DM 57 xxF
Ventilation module
Ventilation module: characteristics
Table of
Characteristics
Reference
Table of ventilation module characteristics:
TSX FAN D2 P TSX FAN A4P TSX FAN A5P
Supply voltage Nominal
Limit
Current consumed at nominal voltage
Temperature probe
Power supply voltage
Outage power
(on resistive load)
Deactivation
Status
No. of modules per rack
24 VDC
20..27.6 VDC
180 mA
110 VAC
90120 VAC
180 mA
direct 24/28 VDC or alternating 110/220 VAC
220 VAC
180260 VAC
100 mA
1 A at 24 VDC / 10,000 operations
1 A at 48 VDC / 30,000 operations
1 A at 110 VDC / 30,000 operations
0.5 A at 220 VDC / 10,000 operations
Temperature>= 75°C +/- 5°C l l l
0.5 A at 220 VDC / 10,000 operations
Temperature>= 75°C +/- 5°C
1 module on 4 and 6-position racks (TSX RKY 4EX/6/6EX),
2 modules on 8-position racks (TSX RKY 8/8EX),
3 modules on 12-position racks (TSX RKY 12/12EX).
TSX DM 57 xxF
121
Ventilation module
122
TSX DM 57 xxF
X Bus extension module
10
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to introduce the X Bus extension module and its installation.
This chapter contains the following topics:
Topic
X Bus extension module: introduction
X Bus extension module: physical description
X Bus extension module: installation
X Bus extension module: configuration
X Bus extension module: maximum distances according to module type
X Bus extension modules: connections
X Bus extension module: diagnostics
Topology of a PLC station with extension module
Managing a power supply module fitted with an X Bus extension module
Page
TSX DM 57 xxF
123
X Bus extension module
X Bus extension module: introduction
General
Example of topology
Module consumption
124
The Premium PLC X Bus makes it possible to connect 8 racks with 12 positions
(TSX RKY 12EX) or 16 racks with 4, 6 or 8 positions (TSX RKY 4EX/6EX/8EX), distributed along a maximum length of 100 meters.
If applications require greater distances between racks, the Bus X extension module
(TSX REY 200) makes it possible to greatly increase this distance whilst maintaining the characteristics and performance which are inherent in a PLC station which is only made up of a single X Bus segment without extension module.
The system consists of: l an X Bus extension module (TSX REY 200) called "Master" located on the rack with address 0 (rack supporting the processor) and on the main X Bus segment.
This module has two channels which allow the two X Bus segments to be extended up to a maximum distance of 250 meters, l l one or two TSX REY 200 modules called "Slave", each located on a rack on the extended bus segments, each of the slave modules is connected to the master module by a TSX CBRY
2500 cable fitted with TSX CBRY K5 connectors.
Illustration:
Remote X bus segment Main X bus segment
X bus
≤
100m
Remote X Bus
TSX REY 200
Master
≤ 250m
X
≤ 100m slave
TSX REY 200
Processor
Remote X Bus
≤
250m
TSX REY 200 slave
X bus
≤ 100m
Remote X bus segment
Consumption on 5VDC power supply: 500 mA
Dissipated power: 2.5 W.
TSX DM 57 xxF
X Bus extension module: physical description
Illustration Descriptive diagram:
X Bus extension module
Table of labels Description table according to number:
2
3
Label
1
Description
Display block made up of 6 LEDs: l l l l l l
RUN
ERR
I/O LED: indicates an error external to the module,
MST
CH0
CH1
LED: indicates the operating status of the module,
LED: indicates an error within the module,
LED: indicates the status of the master or slave function of the module,
LED: indicates the operating status of channel 0,
LED: indicates the operating status of channel 1,
Connector for linking channel 0 of the module.
Connector for linking channel 1 of the module.
TSX DM 57 xxF
125
X Bus extension module
X Bus extension module: installation
Introduction
Installation of a master module on the TSX P57 station l l l
There are several different cases when installing an X Bus extension module: installation of a master module on the TSX P57 station, installation of a master module on the PCX 57 station, installation of a slave module.
The master module must be installed: l on the rack which supports the processor (rack with address 00), this rack being located on the main X Bus segment, l in any position on this rack apart from those positions which are dedicated to the power supply and processor modules.
Constraint: the 00 position of rack with address 0 is prohibited to all modules including the processor module, only a double format power supply is allowed to occupy this position.
The table below indicates the various scenarios according to the format of the power supply module and the processor:
Illustration Scenario
Rack with address 0 with single format power supply module and processor: l l l l power supply module in position PS, processor must be in position 01, position 00 is always unoccupied,
TSX REY 200 module in one of the available positions in the rack.
l l l
Rack with address 0 with double format power supply module and single format processor: power supply module in positions PS and 00, processor must be in position 01,
TSX REY 200 module in one of the available positions in the rack.
Address rack 0 with single format power supply module and double format processor: l l l l power supply module in position PS, processor must be in positions 01 and 02, position 00 is always unoccupied,
TSX REY 200 module in one of the available positions in the rack.
126
TSX DM 57 xxF
Scenario l l l
Rack with address 0 with double format power supply module and processor: power supply module in positions PS and 00, processor must be in positions 01 and 02,
TSX REY 200 module in one of the available positions in the rack.
Illustration
X Bus extension module
Installing a master module on a PCX 57 station
As with a TSX P57 station, the master module must be installed: l on the rack which supports the processor virtually (rack with address 0), this rack being located on the main X Bus segment, l in any position on this rack apart from the position dedicated to the power supply module and that which is virtually occupied by the processor.
Constraint:
The 00 position of the rack with address 0 is prohibited to all modules, only a double format power supply module is allowed to occupy this position. The virtual position of the processor (unoccupied position) must always be position 01.
The table below indicates the various scenarios according to the format of the power supply module and the processor:
Scenario
Rack with address 0 with single format power l l supply: l l power supply module in position PS, virtual position of the processor must be position 01
(position always unoccupied), position 00 is always unoccupied,
TSX REY 200 module in one of the available positions in the rack.
Illustration
Rack with address 0 with double format power supply module: l l power supply module in position PS, virtual position of the processor must be position 01
(position always unoccupied), l TSX REY 200 module in one of the available positions in the rack.
TSX DM 57 xxF
127
X Bus extension module
Installation of a slave module
The slave module can be installed on one of the racks of the bus extension segment and in any position on this rack apart from the one which is dedicated to the power supply module.
The table below indicates the various scenarios according to the format of the power supply module and the processor:
Illustration Scenario
Rack with address 0 with single format power supply: l l power supply module in position PS,
TSX REY 200 module in one of the available positions in the rack.
Rack with address 0 with double format power supply module: l l power supply module in positions PS and 00,
TSX REY 200 module in one of the available positions in the rack.
128
TSX DM 57 xxF
X Bus extension module
X Bus extension module: configuration
General points The configuration of the module as a master or slave is automatic: l if the module is installed on the rack with address 0, it will automatically be l declared as master, if the module is installed on a rack with an address other than 0, it will automatically be declared as slave.
Illustration
Note: If 2 racks are declared at address 0, the master module must be located on l l l the rack supporting the "low" module addresses, as indicated in the figure below.
"Low" module addresses: addresses 0 to 6 on TSX RKY 8EX, addresses 0 to 4 on TSX RKY 6EX, addresses 0 to 2 on rack TSX RKY 4EX,
Example: 2 TSX RKY 8EX racks at address 0.
TSX DM 57 xxF
Microswitch 4 located on the rack
Note: If two racks are declared at address 0, the rack supporting the "high" address l l l modules cannot receive a slave extension module.
"High" address modules: addresses 8 to 14 on rack TSX RKY 8EX, addresses 8 to 12 on rack TSX RKY 6EX, addresses 8 to 10 on rack TSX RKY 4EX.
129
X Bus extension module
X Bus extension module: maximum distances according to module type
General points The figure below summarizes the maximum distances authorized for the different X l l
Bus segments and X Bus extensions: for each X Bus segment (X1, X2 or X3): maximum length 100 meters, for each X Bus extension (XD1 or XD2): maximum length 250 meters,
Illustration:
Main X Bus segment (X1)
TSX REY 200
Master
X Bus
≤ 100m
Remote X Bus ≤ 250m
XD1
Main X Bus segment (X2)
X Bus
X Bus
<= 100 m
≤ 100m
Slave
TSX REY 200
Processor
XD2
Remote X Bus
≤
250m
TSX REY 200
Slave
X Bus
≤
100m
Main X bus segment (X3)
Taking this into account, the maximum distance possible between the processor and the remote modules is 350 meters.
This distance of 350 meters is only possible for single discrete input/output modules.
The following illustrations indicate the restrictions in relation to module type.
Note: Extension is prohibited for communication modules TSX SCY •••/TSX
ETY•••/TSX IBY •••/TSX PBY •••. These modules must be located on the main segment of the X Bus X1
130
TSX DM 57 xxF
X Bus extension module
Safety and single discrete I/O modules
Illustration:
≤ 250
≤ 350m
X Bus
≤
100m
Single discrete I/O modules:
TSX DEY.../TSX DSY... and TSX PAY… safety modules
Exception: TSX DEY 16FK
Mixed discrete I/
O, analog, applicationspecific and bus sensor/actuator modules
Illustration:
≤ 175 m
Modules:
TSX DMY… discrete mixed and TSX DEY 16FK discrete single,
TSX AEY.../TSX ASY... analog,
TSX ISPY.../TSX CTY...TSX CAY.../TSX
CFY…applications
TSX SAY 100 bus sensors/actuators.
≤ 175 m
X Bus
≤ 100m
TSX DM 57 xxF
131
X Bus extension module l l l l l l l
Note: for the following modules:
TSX DEY 16 FK with PV index
≥
06,
TSX DMY 28FK / 28RFK,
TSX AEY 810/1614,
TSX ASY 410 with PV index
≥
11,
TSX ASY 800,
TSX CTY 2C
TSX CAY 22/42/33, maximum distance authorized (extension cable and X Bus cable length): 225 meters.
Communication modules
Illustration:
CAUTION
Extension prohibited
Modules must be located on the main X Bus segment.
Failure to follow this precaution can result in injury or equipment damage.
Modules:
TSX SCY… communication
TSX ETY… network
TSX IBY…/TSX PBY field bus
Extension prohibited!
NO
132
TSX DM 57 xxF
X Bus extension module
X Bus extension modules: connections
General points
Connecting accessories l l
To extend the X Bus, you must use: the kit TSX CBRY 2500 made up of a reel of cable, 250 meters in length, the set of connectors TSX CBRY K5.
You must fit the cable with connectors at both ends. The procedure for mounting the connectors on the cable is described in the instructions supplied with the set of connectors TSX CBRT K5.
Installing an X Bus extension requires, therefore, the following elements:
1 TSX CBRY 2500 kit including 1 cable, 250 meters long, supplied on a reel.
1 set of 5 connectors TSX CBRY K5, which allows you to fit 2 extension cables, leaving you with one connector as a spare.
TSX DM 57 xxF
133
X Bus extension module
Connecting principles
Illustration:
M ain X Bus segment
TSX REY 200
Master
Remote X bus (XD2) ≤ 250m
TSX CBRY 2500+TSX CBRY K5
(Cable + connector)
Channel 0
R emote X Bus segment
Channel 0
TSX REY 200
Slave
Processor
Channel 0
Channel 1
Remote X bus (XD2)
≤
250m
TSX CBRY 2500+TSX CBRY K5
(Cable + connector)
TSX REY 200
Slave
R emote X Bus segment
Note: Each X Bus segment must have a A/ and B/ line terminator (See Line
terminator TSX TLYEX, p. 104)at each end.
134
TSX DM 57 xxF
X Bus extension module
X Bus extension module: diagnostics
By signaling
LEDs
The TSX REY 200 module display panel, located on the front panel of the module, is used for diagnostics on the extension system.
Illustration: display panel
Module functioning as master
(positioned on the rack with address 00)
Diagnostics table:
LED status
ERR RUN
F N/A
Mst I/O
N/A N/A
Off
Off
Off
Off
On
On
On
On
On
On
On
On
Off
Off
Off
On
Module status Comments
CH0 CH1
N/A N/A Fault
On
Off
On
Off
Off
On
On
Off
OK
OK
OK
Fault
No communication with the processor
Channel 0 active
Channel 1 inactive
Channel 0 inactive
Channel 1 active
Channel 0 active
Channel 1 active
Channel 0 inactive
Channel 1 inactive
Legend:
On: on
Off: switched off
F: flashing
N/A: Not applicable
TSX DM 57 xxF
135
X Bus extension module
Module functioning as slave (positioned on a rack with address other than 00)
Diagnostics table:
LED status
ERR RUN
F N/A
Mst
N/A
I/O
N/A
Off
Off
On
On
Off
Off
Off
On
Module status Comments
CH0 CH1
N/A N/A Fault
On
Off
Off
Off
OK
Fault
No communication with the processors
Channel 0 active
Channel 0 inactive
Legend:
On: on
Off: switched off
F: flashing
N/A: not determined
136
TSX DM 57 xxF
X Bus extension module
Topology of a PLC station with extension module
TSX P57 station Illustration:
Main X Bus segment
Remote X Bus ≤ 250 m
TSX REY 200
Master
X Bus
≤ 100m
Segment 1 of remote X Bus
X Bus
≤ 100m
TSX REY 200
Slave
Processor
Remote X Bus ≤ 250 m
TSX REY 200
Slave
X Bus
≤ 100m
Segment 2 of remote X Bus
Maximum station capacity: l With TSX P57 10 processors: l l
2 TSX RKY 12 EX racks,
4 TSX RKY 4EX/6EX/8EX racks.
l With TSX P57 20/30/40 processors: l l
8 TSX RKY 12 EX racks,
16 TSX RKY 4EX/6EX/8EX racks.
TSX DM 57 xxF
137
X Bus extension module
PCX 57 station Illustration:
Main X Bus segment
Remote X bus ≤ (250m-X1)
Host PC
TSX REY 200
Master
PCX 57 processor
X Bus
L=X1
Virtual position of the processor
Remote X bus
≤
(250m-X1)
Segment 1 of remote X Bus
X Bus
≤ 100m
TSX REY 200
Slave
X Bus L =
TSX REY 200
Slave
X Bus
≤ 100m
Segment 2 of remote X Bus
Main X Bus segment
Maximum station capacity: l With TSX P57 10 processors: l 2 TSX RKY 12 EX racks, l l 4 TSX RKY 4EX/6EX/8EX racks.
With TSX P57 30 processors: l 8 TSX RKY 12 EX racks, l 16 TSX RKY 4EX/6EX/8EX racks.
Note: In every case, the length of X Bus extension segments is defined in relation to the location of the processor. This maximum distance is 250 meters. In the special case of the PCX 57 processor, when it is located in the PC, the extension distance of the X Bus segments in relation to the rack with address 0, is equal to
250 meters minus the distance (X1) between the processor and rack with address
0. Main X Bus segment = (X1+X2)
≤
100 meters.
138
TSX DM 57 xxF
X Bus extension module
Managing a power supply module fitted with an X Bus extension module
General
CAUTION
Use of a module
All use of an X Bus extension module (TSX REY 200) in an installation makes management of the installation or the machine subject to all the racks configured in the application being present.
In order to do this, an application check must be carried out to make sure that all the application racks are present by testing the bit %MWxy
MOD 2 X6 (explicit exchanges) on at least one module on each rack.
This test allows the racks to be cleared of all incorrect declarations in the rack addressing and, in particular, if two racks bear the same address by mistake.
This test only comes into play after the installation has completely restarted (switched on, installation modified, processor RESET, configuration changed).
Failure to follow this precaution can result in injury or equipment damage.
TSX DM 57 xxF
139
X Bus extension module
140
TSX DM 57 xxF
TSX P57 Premium processors
III
At a Glance
Aim of this Part
What's in this
Part?
The aim of this part is to describe the TSX P57 Premium processors and their implementation.
This part contains the following chapters:
20
21
22
17
18
19
Chapter
11
12
13
14
15
16
23
24
25
26
Chapter Name
TSX P57 processors: introduction
TSX P57 processors: installation
TSX P57 processors: diagnostics
TSX P57 103 processor
TSX P57 153 processor
TSX P57 203 processor
TSX P57 253 processor
TSX P57 2623 processor
TSX P57 2823 processor
TSX P57 303 processor
TSX P57 353 processor
TSX P57 3623 processor
TSX P57 453 processor
TSX P57 4823 processor
Premium TSX P57 processor: general characteristics
Processor performance
Page
TSX DM 57 xxF
141
TSX P57 Premium processors
142
TSX DM 57 xxF
TSX P57 processors: introduction
11
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this chapter is to introduce the TSX P57 processors.
This chapter contains the following topics:
Topic
General introduction
Physical description of TSX P57 processors
Real-time clock
Page
TSX DM 57 xxF
143
TSX P57 processors: introduction
General introduction
Introduction
General points
A wide range of TSX P57 processors of different levels of performance and specifications are available to meet your various requirements.
TSX P57 sequential processors can be integrated into TSX RKY... racks (See
Standard and extendable TSX RKY racks, p. 68).
l l l l
List of TSX P57 processors:
TSX P57 103, TSX P57 153 processor,
TSX P57 203, TSX P57 253, TSX P57 2623, TSX P57 2823 processor,
TSX P57 303, TSX P57 353, TSX P57 3623 processor
TSX P57 453, TSX P57 4823 processor.
Note: Processors from families 20, 30 and 40 have built-in process control functions.
Illustration TSX P57 standard format in TSX RKY 6EX rack:
144
TSX DM 57 xxF
TSX P57 processors: introduction
Functions l l l
Premium TSX P57 processors manage a complete PLC station which is made up of: discrete input/output modules, analog input/output modules, application-specific modules (i.e. counting, axis control, step by step control, communication, etc.), which can be distributed over one or more racks connected to the X Bus.
l l l l
The application is designed using PL7 Junior or PL7 Pro running Windows. This offers: four programming languages: Grafcet, Ladder, Structured Text and List, a multitask software structure: Master, Fast, Event processing, a change function for programs being executed, etc.
Table of TSX P57 processors
Type
TSX P57 103
TSX P57 153
TSX P57 203
TSX P57 253
TSX P57 2623
TSX P57 2823
TSX P57 303
TSX P57 353
TSX P57 3623
TSX P57 453
TSX P57 4823
All processors in the TSX P57 range can be found in the following table.
Physical format
Single
Single
Double
Double
Double
Double
Double
Double
Double
Double
Double
1024
1024
1024
2048
2048
Maximum number of discrete I/Os
512
512
1024
1024
1024
1024
Maximum memory size
96K16
96K16
208K16
224K16
208K16
224K16
464K16
480K16
464K16
688K16
688K16
-
X
-
X
-
X
-
X
-
X
X
Built-in master
FIPIO link
Built-in Ethernet link
-
-
X
X
-
-
-
-
X
-
X
Legend:
X available.
- : unavailable.
TSX DM 57 xxF
145
TSX P57 processors: introduction
Physical description of TSX P57 processors
Illustration These diagrams label the different components of a TSX P57 processor module
(standard or double):
146
Processeur format standard :
TSX P57 103/153
Processeur double format :
TSX P57 203/253/303/353/453
6
7
4
8
5
2
3
9
1
Processeur double format avec Ethernet embarqué :
TSX P57 2623/2823/3623/4823
TSX DM 57 xxF
Description
TSX P57 processors: introduction
This table describes the components of a processor module
Number
1
2
3
4
5
6
7
8
9
Function
Display panel containing four or five LEDs.
Recessed RESET button which when pressed causes a cold startup.
l Processor working normally: cold startup in STOP or RUN mode, depending on the procedure defined at configuration.
l Processor error: forced startup in STOP mode.
Terminal port ( TER Connector (8-pin mini-DIN)): this is used to connect an FTX type or PC compatible terminal, or to connect the PLC to the UNI-TELWAY bus through the TSX P ACC 01 insulation unit.
This connector is used to supply 5V to the peripheral which is linked to it
(limited by the available current provided by the power supply).
Terminal port ( AUX Connector (8-pin mini-DIN)): this is used to connect a peripheral with its own power supply (terminal, operator dialog console or printer (no voltage is supplied to this connector)).
Slot for a type 1 PCMCIA memory extension card.
If there is no memory card, this slot is fitted with a cover which must be kept in place; as the processor will stop if it is removed .
Slot for a type 3 PCMCIA card. This slot can accept either of the following: l l a memory extension card, a communication card allowing the processor to be connected to a
FIPWAY, FIPIO Agent, UNI-TELWAY or serial link communication channel.
If there is no card, this slot is fitted with a cover.
9-pin SUB D connector for connecting a FIPIO bus master. This connector is only present on TSX P57 •53 processors.
RJ 45 connector for connecting to the Ethernet network. This connector is only present on TSX P57 •23 processors.
The ETY PORT display panel comprising 6 LEDs.
Note: The ( TER ) and ( AUX ) connectors propose master UNI-TELWAY communication mode at 19200 bauds by default and can be configured for slave
UNI-TELWAY or ASCII character mode.
TSX DM 57 xxF
147
TSX P57 processors: introduction
Real-time clock
At a Glance l l
Each processor (TSX P57 or PCX 57) has a savable real-time clock which manages: the current date and time, the date and time of when the application last stopped.
The date and time are managed even when the processor is switched off, on condition that: l the TSX P57 processor is mounted on the rack with its power supply module in place and is equipped with a back-up battery, l the PCX 57 processor is equipped with a back-up battery.
Current date and time the processor keeps the current date and time up to date in the system words
%SW49 to %SW53. This data is coded in BCD.
System words Most significant byte
%SW49 00
%SW50
%SW51
%SW52
%SW53
Seconds (0 to 59)
Hours (0 to 23)
Month (1 to 12)
Century (0 to 99)
Least significant byte
Days of the week from 1 to 7
(1 for Monday and 7 for Sunday)
00
Minutes (0 to 59)
Days of the month (1 to 31)
Year (0 to 99)
Note: %SW49 is read-only.
148
TSX DM 57 xxF
Accessing the date and time
TSX P57 processors: introduction l l
The date and time can be accessed: via the processor debug screen, via the program: l l read: system words %SW49 to %SW53, if the system bit %S50 = 0, immediate update: write system words %SW50 to %SW53, if the system bit
%S50 = 1, l incremental update: the system word %SW59 is used to change the date and time, field by field, from the current value, if the system bit %S59 = 1, or is used to carry out a global increment/decrement.
Bit value table: bit0 = 1 globally increments of the days of the week from 1 to 7 (1 for Monday 7 for
Sunday) bit8 = 1 globally decrements of the days of the week from 1 to 7 (1 for Monday 7 for Sunday) bit1 =1, increments the seconds bit2 =1, increments the minutes bit9 =1, decrements the seconds bit10 =1, decrements the minutes bit3 =1, increments the hours bit4 =1, increments the days bit5 =1, increments the months bit6 =1, increments the years bit7 =1, increments the centuries bit11 bit12 bit13 bit14 bit15
=1, decrements the hours
=1, decrements the days
=1, decrements the months
=1, decrements the years
=1, decrements the centuries
(1) all fields are updated.
Note: The processor does not automatically manage the change between winter and summer time.
TSX DM 57 xxF
149
TSX P57 processors: introduction
The date and time of when the application last stopped
The date and time of when the application last stopped are stored in BCD in the system words %SW54 to %SW58.
System words
%SW54
%SW55
%SW56
%SW57
%SW58
Most significant byte
Seconds (0 to 59)
Hours (0 to 23)
Least significant byte
00
Minutes (0 to 59)
Month (1 to 12)
Century (0 to 99)
Days of the month (1 to 31)
Year (0 to 99)
Day of the week (from 1 to 7) Reason for the last application stop l l to access the date and time of the last application stop: read the system words %SW54 to %SW58, to find the reason for the last application stop: read the least significant byte of the system word %SW58 (value saved in BCD).
Table of %SW58 system words:
%SW58 = 1
%SW58 = 2
%SW58 = 4
%SW58 = 5
%SW58 = 6 application switched to STOP mode, application stopped due to a software error, power outage or power supply RESET button has been pressed stop due to hardware fault application stopped due to HALT instruction
150
TSX DM 57 xxF
TSX P57 processors: installation
12
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the installation of TSX P57 processor modules and the
PCMCIA extension card.
This chapter contains the following topics:
Topic
Positioning the processor module
How to mount processor modules
Mounting/Removing a PCMCIA memory extension card on a TSX P57 processor
Processing on insertion/extraction of a PCMCIA memory card on a Premium
PLC
Standard and Backup memory cards for PLCs
Application + files type memory cards
File type Memory Card: TSX MRP DS 2048 P
Page
151
TSX DM 57 xxF
TSX P57 processors: installation
Positioning the processor module
Introduction l l
There are two scenarios for the positioning of a processor module on a rack: positioning a standard format processor module, positioning a double format processor module.
Positioning a standard format processor module
A standard format processor module is always installed on the TSX RKY..
rack with address 0 and in position 00 or 01 according to whether the rack is equipped with a standard or double format power supply module.
Rack with standard format power supply module: TSX PSY 2600/1610.
In this case, the processor module will be placed in position 00 (preferred position) or position 01. If the latter, position 00 must be unoccupied.
Illustration
Rack with double format power supply module: TSX PSY 3610/5500/5520/
8500.
In this case, the processor will be placed in position 01, as the power supply module occupies two positions (PS and 00).
Illustration
152
TSX DM 57 xxF
Positioning a double format processor module
TSX P57 processors: installation
A double format processor module is always installed on the TSX RKY..
rack with address 0 and in positions 00 and 01 or 01 and 02 according to whether the rack is equipped with a standard or double format power supply module.
Rack with standard format power supply module: TSX PSY 2600/1610.
In this case, the processor module will be installed in positions 00 and 01 (preferred position) or in positions 01 and 02. If the latter, position 00 must be unoccupied.
Illustration
Rack with double format power supply module: TSX PSY 3610/5500/5520/
8500.
In this case, the processor will be placed in positions 01 and 02, as the power supply module occupies two positions (PS and 00).
Illustration
Note: The rack on which the processor is installed always has address 0.
TSX DM 57 xxF
153
TSX P57 processors: installation
How to mount processor modules
Introduction Mounting and removing processor modules is identical to mounting and removing other modules apart from the fact that it must not be done when power is switched on .
Note: when extracting/inserting modules with the power on, the terminal block or
HE10 connector must be disconnected. You must also take care to shut off the sensor/preactuator supply if this is over 48V.
Installing a processor module onto a rack
Carry out the following steps:
Step
1
2
Action
Place the pins at the back of the module into the centering holes on the lower part of the rack (number 1, see diagram 1).
Swivel the module to bring it into contact with the rack (number 2).
Illustration
3 Fix the processor module to the rack by tightening the screw on the upper part of the module (number 3).
154
Note: the mounting of processor modules is identical to the mounting of other modules.
Note: Maximum tightening torque: 2.0N.m.
TSX DM 57 xxF
Grounding modules
TSX P57 processors: installation
CAUTION
Install with power off
A processor module must always be mounted with the rack power supply switched off.
Failure to follow this precaution can result in injury or equipment damage.
Processor modules are grounded using metal plates at the rear of the module. When the module is in place, these metal plates are in contact with the metal of the rack.
This ensures the link with the ground connection.
Illustration
Ground connection contacts
TSX DM 57 xxF
155
TSX P57 processors: installation
Mounting/Removing a PCMCIA memory extension card on a TSX P57 processor
At a Glance l l
The Premium range offers two memory extension cards: the Type 1 PCMCIA card for application, data and symbol storage,
The Type 3 PCMCIA card for application data only.
Note: A clip is needed to insert a Type 1 PCMCIA memory card into its slot on the
TSX P57 processor.
Note: The Type 3 PCMCIA memory card must be inserted and extracted from its slot whilst the power is off.
Mounting the clip on the Type 1 memory card
Carry out the following steps:
Step Action
1 Place the end of the memory card
(opposite end to the connector) between the arms of the clip.
The markers (in the form of a triangle) on both the clip and the card label must be facing same way.
Illustration
Diagram 1
2 Slide the memory card into the clip until it stops. The card is now firmly attached to the clip.
Diagram 2
Markers locating device with one edge connector markers locating device with 2 edges clip
156
TSX DM 57 xxF
Mounting the memory cards
TSX P57 processors: installation
Carry out the following steps to install the memory card into the processor:
Step
1
2
3
Action
Remove the protective cover from the respective slot by unlocking it and then pulling it forwards out of the PLC.
Place the PCMCIA card (with clip if Type 1) into the now empty slot. Slide the whole thing in until the card can go no further, then press the clip to connect the card.
For a Type 3 memory card, fix the card onto the processor with 2 fixing screws.
Illustration
TSX DM 57 xxF l l
Note: When inserting the Type 1 PCMCIA card into its slot, check that the edges are correctly positioned:
1 edge on top,
2 edges at the bottom.
Note: If the program contained in the Type 1 PCMCIA memory card contains the
RUN AUTO option, the processor will automatically restart in RUN mode after the card has been inserted.
157
TSX P57 processors: installation
Processing on insertion/extraction of a PCMCIA memory card on a Premium
PLC
General
Type 1 memory extension card
The front panels of Premium PLC processors have removable covers to prevent the accidental intrusion of objects which could damage the connector.
The cover for slot 0 (Type 1 PCMCIA memory slot) must be in place for PLC operation to take place when the memory card and clip are absent.
The extraction (or absence) of the cover or memory card and clip causes the PLC to stop without saving the application context. Module outputs switch to fallback mode.
Inserting the cover or memory card with clip will cause the PLC to perform a cold start.
CAUTION
RUN AUTO option
If the program contained in the PCMCIA memory card includes the
RUN AUTO option, the processor will automatically restart in RUN after the card is inserted.
Failure to follow this precaution can result in injury or equipment damage.
Type 3 memory extension card
The Type 3 PCMCIA memory card should be inserted into slot 1 of the processor while the PLC power is off . Ignoring this warning could cause the processor to malfunction.
158
TSX DM 57 xxF
TSX P57 processors: installation
Standard and Backup memory cards for PLCs
Standard memory cards
BACKUP type memory cards l l
There are 2 types of standard memory cards: saved RAM memory extension card,
Flash Eprom memory extension card.
Saved RAM memory extension card: used particularly when generating and debugging an application program. It is used for all application transfer and modification services when online.
The memory is saved by a removable battery integrated in the memory card.
See Changing the battery of a RAM memory Type 1 PCMCIA card on the TSX P57,
Flash Eprom memory extension card: used when the application program debugging has finished. It allows only a global transfer of the application and avoids the problems associated with battery backups.
When previously loaded with the application program, this card can be used to reload the application program into the processor’s internal RAM memory without the need to use a programming terminal.
This card can only be used when the application is solely in the processor’s internal
RAM memory and if the entire size (program + constants) is less than 32 Kwords.
TSX DM 57 xxF
159
TSX P57 processors: installation
Product references for standard and
Backup extension memory cards
The following table shows the compatibility of the cards with the processors:
Product references
TSX MRP
032P
TSX MRP
064P
TSX MRP
0128P
TSX MRP
0256P
TSX MRP
0512P
TSX MFP
032P
TSX MFP
064P
TSX MFP
0128P
TSX MFP
BAK032P
Type/Capacity Processor compatibility
TSX P57 103 TSX P57 2•3/2•23
PCX 57 2•3
RAM/32K16
RAM/64K16
RAM/128K16
RAM/256K16
RAM/512K16
Yes
Yes
No
No
No
Flash Eprom/
32K16
Flash Eprom/
64K16
Yes
Yes
Flash Eprom/
128K16
No
BACKUP/32K16 Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
TSX P57 3•3/3623
TSX P57 4•3/4823
PCX 57 353
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Note: Memory capacity: K16=Kwords (16 bit word).
160
TSX DM 57 xxF
TSX P57 processors: installation
Application + files type memory cards
General These memory cards, as well as a conventional application storage area, also have: l for all cards, a file zone for archiving data by program.
l
Application examples: l automatic storage of application data and remote consultation by modem link, l storage of manufacturing formulas, for some cards, a zone for storing the client application symbol database. This symbol database is compressed so that it fits easily into the area which is allocated to it (128K16).
There are two types of memory card: l saved RAM application + files memory extension card. The memory is saved by a removable battery built into the memory card, l Flash Eprom application + files memory extension card. In this instance, the data storage area is in saved RAM which implies that this type of card must be equipped with a back-up battery.
Product references for application + files extension memory cards
The following table shows the compatibility of the cards with the processors:
Product references
TSX MRP 232 P
TSX MRP 264 P
TSX MRP 2128 P
TSX MRP 3256 P
TSX MRP 3384P
Technology type
RAM
RAM
RAM
RAM
RAM
TSX MRP 512 P RAM
Type/Capacity
Application area
32K16
64K16
128K16
256K16
384K16
512K16
TSX MFP 232 P Flash Eprom 32K16
TSX MFP 264 P Flash Eprom 64K16
File area
(RAM type)
128K16
128K16
128K16
640K16
(5x128K16)
640K16
-
128K16
128K16
Processor compatibility
Symbol area
(RAM type)
TSX
P57 1•3
TSX P57
2•3/2•23
TSX P57
3•3/3623
TSX P57
453/4823
-
-
128K16
128K16 yes yes no no yes yes yes yes (1) yes yes yes yes yes yes yes yes
-
256K16
-
no no yes yes yes (1) yes yes yes (1) yes (2) yes yes yes yes yes yes yes
TSX DM 57 xxF
(1) The usable application size is limited to 160K16 which conforms to the characteristics of this processor.
(2) The usable application size is limited to 384K16 which conforms to the characteristics of this processor, the size of the symbol area is limited to 128K16.
161
TSX P57 processors: installation
File type Memory Card: TSX MRP DS 2048 P
At a Glance
Compatibility
This card is used for archiving application data.
Application examples: l l storage of manufacturing formulas, making a library.
The TSX MRP DP 2048 P card has a Saved RAM capacity of 4 Mb. Saving is carried out by a removable battery built into the memory card.
The TSX MRP DS 2048 P memory card must be used in one of the following l l l l l processors:
TSX P57 203 and TSX P57 2623,
TSX P57 253 and TSX P57 2823,
TSX P57 303 and TSX P57 3623,
TSX P57 353,
TSX P57 453 and TSX P57 4823.
162
TSX DM 57 xxF
TSX P57 processors: diagnostics
13
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with diagnostics for TSX P57 processors.
This chapter contains the following topics:
Topic
Viewing
Precautions to be taken when replacing a TSX P57 processor
Changing the RAM memory backup battery on TSX P57
Changing the battery of a RAM memory Type 1 PCMCIA card on the TSX P57
Changing the TSX MRP 2048 P memory card's battery
What happens after you press the processor RESET button
Page
Finding errors using processor state LEDs
Non blocking errors
Blocking errors
Processor or system errors
TSX DM 57 xxF
163
TSX P57 processors: diagnostics
Viewing
At a Glance There are five display LEDs on the front panel of the processor for a quick diagnostic of the status of the PLC controller.
Illustration
Description
RUN
(green)
ERR
(red)
The following table describes the role of each LED
LED flashing
LED on.
I/O
(red)
LED off.
LED status not important
TER
(yellow)
FIP
(yellow)
Description self-testing in progress.
reset (for processor versions
≥
4.0).
reset (for processors version <4.0).
blocking software fault.
164
TSX DM 57 xxF
RUN
(green)
ERR
(red)
I/O
(red)
TSX P57 processors: diagnostics
TER
(yellow)
FIP
(yellow)
Description fault on Bus X (for processor versions ≥ 4.0).
fault on Bus X (for processor version <4.0).
hardware fault or fault on BusX. In this case, do a reset.
If the three LEDs are still on after the reset, then it is a hardware fault.
PLC working normally, run the program.
processor or system fault
I/O fault from a module or channel or a configuration error.
terminal port link active. The intensity of the flashing depends on the traffic.
FIPIO bus link active. The intensity of the flashing depends on the traffic.
PLC not configured (application absent, not valid or incompatible).
normal state, no internal fault.
normal state, no I/O fault.
inactive link.
inactive link.
Note: l the FIP LED is only present on TSX P57 •53 and TSX P57 •823 processors.
TSX DM 57 xxF
165
TSX P57 processors: diagnostics
Precautions to be taken when replacing a TSX P57 processor
Important
CAUTION
Replacing a processor
If the TSX P57 processor is being replaced by another processor which is not blank (the processor has already been programmed and contains an application), the power for all the PLC station’s control units must be switched off.
Before restoring power to the control units, check that the processor contains the required application.
Failure to follow this precaution can result in injury or equipment damage.
166
TSX DM 57 xxF
TSX P57 processors: diagnostics
Changing the RAM memory backup battery on TSX P57
At a Glance
Installing the battery
This battery, which is in the TSX PSY … power supply module (See Supply
modules: description, p. 280), ensures that the internal RAM memory of the
processor and the real-time clock are saved in case of a voltage power outage. It is delivered in the same packaging as the power supply module and must be installed by the user.
Carry out the following steps:
Step
1
2
3
Action
Open the access flap on the front of the power supply module.
Place the battery in its slot, taking care to respect polarities as marked on the module.
Close the access flap.
Illustration
TSX DM 57 xxF
167
TSX P57 processors: diagnostics
Changing the battery
The battery can be changed every year as a preventative measure or when the
LED is lit.
To do this, use the same procedure as for installation, and carry out the following steps:
Step
1
2
3
4
Action
Open the access flap for the battery.
Remove the defective battery from its slot.
Put the new battery into place.
Close and lock the access flap.
BAT
Illustration
168
If there is a power outage while the battery is being changed, the processor ensures the RAM memory is saved, as it has its own offline independent save function.
Note: so as not to forget to change the battery, you are advised to note the date of the next change in the space provided on the inside of the flap.
TSX DM 57 xxF
TSX P57 processors: diagnostics
How often must the battery be changed?
Period of battery backup
The length of time during which the battery ensures backup of the processor’s internal RAM memory and the real-time clock depends on two factors: l the percentage of time for which the PLC is switched off and therefore the battery is being used, l the ambient temperature when the PLC is switched off.
Summary table:
Ambient temperature when inoperative
Backup time PLC off for 12 hours per day
≤
30°C
5 years
PLC off for 1 hour per day
5 years
40°C 50°C
3 years
60°C
2 years 1 year
5 years
4.5 years 4 years
Independent saving by the processor
The processors have their own offline independent save function to save the processor’s internal RAM memory and the real-time clock, which allows the removal of: l the battery, the power supply or the TSX P57 processor.
The backup time depends on the ambient temperature.
Assuming that the processor was switched on previously, the guaranteed time varies in the following way:
Ambient temperature when switching off
Backup time
20°C
2h
30°C 40°C 50°C
45mn 20mn 8mn
TSX DM 57 xxF
169
TSX P57 processors: diagnostics
Changing the battery of a RAM memory Type 1 PCMCIA card on the TSX P57
Introduction
How to change the battery
RAM memory PCMCIA cards (TSX MRP etc.) must have a battery (reference TSX
BAT M01) which needs to be changed.
Carry out the following steps:
5
6
8
9
Step
1
2
3
4
7
Action
Remove the card from its slot by pulling the clip forwards out of the PLC.
Separate the PCMCIA card from its clip by pulling the two components (card and clip) in opposite directions.
Hold the PCMCIA card so you can access the battery slot. This is at the end of the card without the connector.
Unlock the battery holder, which is at the end of the card without the connector.
To do this, press the lock towards the bottom of the card (the opposite direction to the write protection micro-switch) while pulling towards the back (see illustration).
Remove the battery and holder unit from its slot (see illustration).
Swap the defective battery for an identical 3V battery. Polarities must be observed by placing the + labels on the holder and the battery on the same side.
Place the battery and holder unit back in its slot, then lock it. To do this, carry out the removal procedure in reverse.
Fix the PCMCIA card into its clip.
Put the card with its clip back into the PLC.
Illustration
Write protection
Lock
Battery slot
6
Number
170
TSX DM 57 xxF
Battery life See the following table:
PCMCIA card stored in normal conditions (-20°C to 70°C)
PCMCIA card fitted in an operating PLC (0°C to 60°C)
TSX P57 processors: diagnostics
12 months
36 months
Note: During operation, the processor’s ERR LED flashes if the PCMCIA card battery is defective.
TSX DM 57 xxF
171
TSX P57 processors: diagnostics
Changing the TSX MRP 2048 P memory card's battery
At a Glance
How to change the battery
The TSX MRP 2048 P memory extension card must have a battery (product ref. TSX
BAT M01) in order to ensure data is saved.
Carry out the following steps:
Step
1
2
Action
Remove the card from its slot by pulling the clip forwards out of the PLC.
Open the PCMCIA card clip.
172
3
4
Hold the PCMCIA card so you can access the battery slot. This is at the end of the card without the connector.
Unlock the battery flap located at the edge of the card. To do this press the lock towards the top of the card (the opposite direction to the write protection microswitch.
TSX DM 57 xxF
Step
5
TSX P57 processors: diagnostics
Action
Take off the battery flap. To do this, slightly rotate the socket as shown in the diagram. Take the card out of its slot.
Battery slot
Lock
Write protection
Battery life
Markers
6
7
8
9
Swap the defective battery for an identical 3V battery. It is essential to respect the polarities as detailed on the memory card label.
Replace and then lock the battery hatch. To do this, carry out the removal procedure in reverse.
Close the PCMCIA card clip.
Put the card with its clip back into the PLC.
See the following table:
PCMCIA card stored in normal conditions.
PCMCIA card fitted in an operating PLC (0°C to 60°C)
12 months
36 months
TSX DM 57 xxF
173
TSX P57 processors: diagnostics
What happens after you press the processor RESET button
General All processors have a RESET button on their front panel, which when pressed, causes a cold start of the PLC, in RUN or in STOP mode (starting in RUN or in STOP mode is defined at configuration), on the application contained in the memory card
(or in the internal RAM)…
RESET following a processor fault
As soon as a processor fault appears, the alarm relay on rack 0 (with TSX 57 processor) is deactivated (open contact) and the module outputs switch to fallback position or are maintained in the current state depending on the selection made in configuration. Pressing the RESET button causes the PLC, forced into STOP, to cold start.
Note: When the RESET button is pressed, and during the PLC cold start, the terminal link is deactivated.
174
TSX DM 57 xxF
TSX P57 processors: diagnostics
Finding errors using processor state LEDs
General
Error detection
The state LEDs situated on the processor enable the user to be informed about the operating mode of the PLC but on possible errors. l l l
Errors detected by the PLC concerned: circuits constituting the PLC and/or its modules: internal errors, the process controlled by the PLC or the cabling of the process: external errors, functioning of the application executed by the PLC: internal or external errors.
Detecting errors is carried out during start-up (autotest) or during functioning (this is the case for most hardware errors), during exchanges with modules or during the execution of a program instruction.
Certain "serious" errors require the PLC to be restarted, others are controlled by the user who decides on the behavior to adopt according to the desired level of application function.
l l l
There are three types of error: non blocking, blocking, processor or system error.
TSX DM 57 xxF
175
TSX P57 processors: diagnostics
Non blocking errors
General
Non blocking errors linked to inputs/outputs
176
This concerns an anomaly, provoked by an input/output error on the X bus, on the
FIPIO bus or by the execution of an instruction. It can be processed by the user program and does not change the PLC state.
i i l l l
The identification of a non blocking error linked to the inputs/outputs is signaled by: the I/O state LED of the processor is lit, the I/O state LEDs of the faulty modules are lit, (on X bus and FIPIO bus), the bits and error words associated to the channel: l Inputs/Outputs on X bus:
%Ixy.i.ERR bit = 1 indicates a faulty channel (implicit exchanges), l
%Mwxy.i.2 words indicate the type of channel error (explicit exchanges),
Inputs/Outputs on FIPIO bus:
%I\p.2.c\m.v.ERR bit = 1 indicates a faulty channel (implicit exchanges), l
%MW\p.2.c\m.v.2 words indicate the type of channel errors (explicit exchanges), bits and error words associated with the module: l Module on X bus:
%Ixy.MOD.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%MWxy.MOD.2 words indicate the type of channel error (explicit exchanges), l l Module on FIPIO bus:
%I\p.2.c\0.MOD.ERR bit = 1 indicates a faulty channel (implicit exchanges),
%MW\p.2.c\0.MOD.2 words indicate the type of channel error (explicit exchanges), system bits:
%S10: I/O error (on X bus or FIPIO bus),
%S16: I/O error (on X bus and FIPIO bus) in the task in progress,
%S40 à %S47: I/O error in racks at addresses 0 to 7 on the X bus.
Diagnostics table:
Errors Status LED i
RUN ERR I/O i To
System bits
%S10 i i To
To
%S16
%S40 to
%S47
Input/output error: channel supply fault, channel disjointed, module not conforming to configuration, out of service, module supply fault.
Error on input/output in a task.
Error on inputs/outputs at rack level
(%S40: rack 0, %S47: rack 7)
Legend:
To: Lit LED,
I: State not determined.
TSX DM 57 xxF
TSX P57 processors: diagnostics
Non blocking errors linked to program execution
The indication of a non blocking error linked to program execution is signaled by setting to state 1 of one or several system bits %S15, %S18, %S20.
The test and setting to state 0 of the system bits are controlled by the user.
Diagnostics table:
Status LED
RUN ERR
To
To i i i i
I/O
To i i
System bits
%S15=1
%S18=1
%S20=1
Errors
Character string manipulation error.
Capacity overrun, error on floating point or division by 0.
Index overflow.
Legend:
To: Lit LED,
I: State not determined.
Note: The program diagnostics function, accessible through the PL7 Pro software, enables certain non blocking errors linked to the program execution, to be turned into blocking errors. The nature of the error is indicated in the system word %SW
125.
TSX DM 57 xxF
177
TSX P57 processors: diagnostics
Blocking errors
General These errors, provoked by the application program, disable its execution but do not cause system errors. On such an error, the application stops immediately and goes to HALT state (the tasks are all stopped in their current instruction).
l l
There are two possibilities for restarting the application: by the command INIT through the PL7 Junior or PL7 Pro software, by the processor RESET button.
The application is thus in a preliminary state: the data has its preliminary values, the tasks are stopped at the end of the cycle, the input image is updated and the outputs are commissioned in fallback position, the RUN command enables application restart.
The indication of a blocking error is signaled by the state LEDs (ERR and RUN) flashing and according to the nature of the error by the setting to 1 of one or several of the system bits %S11 and %S26. The nature of the error is indicated in the system word %SW 125.
Diagnostics table:
C
C
State LEDs
RUN ERR
C
C
C
C
C
C
Legend:
C: blinking i: not determined i i i i
I/O
System Bits Errors
%S11=1 Watchdog overrun
%S26=1 Overrun of the grafcet activity table
Step, Grafcet not resolved
Executing the HALT instruction
Executing a non resolved JUMP
178
TSX DM 57 xxF
TSX P57 processors: diagnostics
Processor or system errors
General
Diagnostics of processor errors:
These serious faults on either processor (hardware or software), or on X bus cabling no longer ensure that the system will function correctly. They cause the PLC to restart in ERREUR which requires a cold restart. The next cold restart will be forced into STOP to avoid the PLC falling back into error.
Diagnostics table:
State LEDs
RUN
E
ERR
To
I/O
To
E
E
C
To
C
To
System word
%SW124
H’80’
H’81’
Errors
System watchdog error or error on X bus cabling
Cabling error on X bus
System code error, unforeseen error
Overrun of the system task batteries
Overrun of the PL7 task batteries
Legend:
To: on
C: blinking
E: not determined
When the PLC has stopped in error, it is no longer able to communicate with a diagnostics device. The information relating to the errors is only accessible after a cold restart (see system word %SW124). In general, the information is not used by the user, only the information H’80’ and H’81’ can be used to diagnose a cabling error on the X bus.
TSX DM 57 xxF
179
TSX P57 processors: diagnostics
180
TSX DM 57 xxF
TSX P57 103 processor
14
General characteristics of TSX P 57 103 processors
TSX P 57 103 processors
The following table gives the general characteristics of the TSX P 57 103 processor.
Reference TSX P 57 103
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (1)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O
Applications (counting, axis, etc.)
Maximum number of connections
Built-in UNI-TELWAY (terminal port,
Ethernet)
Network (ETHWAY, FIPWAY, Modbus
Plus)
Master FIPIO (built-in)
Third party field bus
AS-i field bus
Savable real-time clock
1
-
-
2 yes
2
4
21
27 fixed
512
24
8
1
181
TSX P57 103 processor
Reference TSX P 57 103
Memory capacity
Application structure
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Master task
Fast task
Application code execution time for a 1K instruction
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
System overhead
MAST task
FAST task fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
32K16
64K16
-
128K16
1
1
32
0.66 ms
0.95 ms
0.85 ms
1.18 ms
1.5 ms
0.8 ms
182
TSX DM 57 xxF
TSX P57 153 processor
15
General characteristics of TSX P57 153 processors
TSX P 57 153 processors
The following table gives the general characteristics of the TSX P 57 153 processor.
Reference TSX P 57 153
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks 2
Maximum number of TSX RKY 4EX/6EX/8EX racks 4
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
21
27
I/O profile (1)
Maximum number of channels
Maximum number of connections
In-rack discrete I/O
In-rack analog I/O
Applications (counting, axis, etc.) 8
Built-in UNI-TELWAY (terminal port)
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet) fixed
512
24
1
1
Master FIPIO (built-in)
Third party field bus
AS-i field bus
Savable real-time clock
63
-
2 yes
183
TSX P57 153 processor
Reference TSX P 57 153
Memory capacity
Application structure
Application code execution time for a 1K instruction
System overhead
Processor internal RAM
PCMCIA memory card
(maximum capacity)
Master task
Application area
Symbol Zone
File area
Fast task
Event processing (1 has priority)
Internal RAM 100% Boolean
65% Boolean + 35% digital
PCMCIA card
MAST task
100% Boolean
65% Boolean + 35% digital without using the FIPIO bus using the FIPIO bus
FAST task
32K16
64K16
-
128K16
1
1
32
0.66 ms
0.95 ms
0.85 ms
1.18 ms
1.5 ms
3.1 ms
0.8 ms fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
184
TSX DM 57 xxF
TSX P57 203 processor
16
General characteristics of TSX P57 203 processors
TSX P 57 203 processors
The following table gives the general characteristics of the TSX P 57 203 processor.
Reference TSX P 57 203
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX
8
16
86 with TSXRKY 4EX, 6EX, 8EX 110
I/O profile (1)
Maximum number of channels
Maximum number of connections
In-rack discrete I/O
In-rack analog I/O fixed
1024
Applications (counting, axis, etc.)
Built-in UNI-TELWAY (terminal port)
1
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet)
1
80
24
Savable real-time clock
Master FIPIO (built-in)
Third party field bus
AS-i field bus
-
1
4 yes
185
TSX P57 203 processor
Reference TSX P 57 203
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Master task
Fast task
Application code execution time for a 1K instruction
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
System overhead
MAST task
FAST task
48K16
160K16
256K16
640K16 channel
0+
2048K16 channel 1
1
1
64
0.21 ms
0.28 ms
0.27 ms
0.40 ms
1 ms
0.35 ms fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
186
TSX DM 57 xxF
TSX P57 253 processor
17
General characteristics of TSX P57 253 processors
TSX P57 253 processor
The following table gives the general characteristics of the TSX P 57 253 processor.
Reference TSX P57 253
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (1)
Maximum number of channels
Maximum number of connections
In-rack discrete I/O
In-rack analog I/O
8
16
86
110
Applications (counting, axis, etc.) 24
Built-in UNI-TELWAY (terminal port)
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet) fixed
1024
80
1
1
Savable real-time clock
Master FIPIO (built-in)
Third party field bus
AS-i field bus
127
1
4 yes
187
TSX P57 253 processor
Reference TSX P57 253
Memory capacity
Processor internal RAM
PCMCIA memory card
(maximum capacity)
Application area
Symbol Zone
File area
Application structure
Application code execution time for a 1K instruction
System overhead
Master task
Fast task
Event processing (of which 1 has priority)
Internal RAM 100% Boolean
PCMCIA card
MAST task
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital without using the FIPIO bus using the FIPIO bus
FAST task
64K16
160K16
256K16
640K16 channel
0+
2048K16 channel 1
1
1
64
0.21 ms
0.28 ms
0.27 ms
0.40 ms
1 ms
1.2 ms
0.35 ms fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
188
TSX DM 57 xxF
TSX P57 2623 processor
18
General characteristics of TSX P57 2623 processors
TSX P 57 2623 processors
The following table gives the general characteristics of the TSX P 57 2623 processor.
Reference TSX P 57 2623
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (1)
Maximum number of channels
Maximum number of connections
In-rack discrete I/O
In-rack analog I/O
8
16
86
110
Applications (counting, axis, etc.) 24
Built-in UNI-TELWAY (terminal port)
Network (embedded ETHWAY,
FIPWAY, Modbus Plus, Ethernet) fixed
1024
80
1
1
Savable real-time clock
Master FIPIO (built-in)
Third party field bus
AS-i field bus
-
1
4 yes
189
TSX P57 2623 processor
Reference TSX P 57 2623
Memory capacity
Processor internal RAM
PCMCIA memory card
(maximum capacity)
Application area
Symbol Zone
File area
Application structure
Master task
Fast task
Application code execution time for a 1K instruction
System overhead
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
MAST task
FAST task
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
48K16
160K16
256K16
640K16 channel 0 +
2048K16 channel 1
1
1
64
0.21 ms
0.28 ms
0.27 ms
0.40 ms
1 ms
0.35 ms
190
TSX DM 57 xxF
TSX P57 2823 processor
19
General characteristics of TSX P57 2823 processors
TSX P57 2823 processor
The following table gives the general characteristics of the TSX P 57 2823 processor.
Reference TSX P57 2823
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (1)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O
Applications (counting, axis, etc.)
Maximum number of connections
Built-in UNI-TELWAY (terminal port)
Network (embedded ETHWAY,
FIPWAY, Modbus Plus, Ethernet)
Master FIPIO (built-in)
Third party field bus
AS-i field bus
Savable real-time clock
127
1
4 yes
1
1
8
16
86
110 fixed
1024
80
24
191
TSX P57 2823 processor
Reference TSX P57 2823
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
System overhead
Master task
Fast task
Application code execution time for a 1K instruction
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
MAST task without using the FIPIO bus using the FIPIO bus
FAST task fixed I/O profile (1): the number of discrete I/Os, and application-specific and analog channels can be accumulated
64K16
160K16
256K16
640K16 channel 0
+
2048K16 channel 1
1
1
64
0.21 ms
0.28 ms
0.27 ms
0.40 ms
1 ms
1.2 ms
0.35 ms
192
TSX DM 57 xxF
TSX P57 303 processor
20
General characteristics of TSX P57 303 processors
TSX P57 303 processor
The following table gives the general characteristics of the TSX P 57 303 processor.
Reference TSX P57 303
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (2)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O
Applications (counting, axis, etc.)
Maximum number of connections
Built-in UNI-TELWAY (terminal port)
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet)
Master FIPIO (built-in)
Third party field bus
AS-i field bus
Savable real-time clock
1
3
-
2
8 yes
8
16
86
110 fixed
1024
128
32
193
TSX P57 303 processor
Reference TSX P57 303
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Master task
Fast task
Application code execution time for a 1K instruction
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
System overhead
MAST task
FAST task
64K16/80K16(1)
384K16
256K16
640K16 channel 0
+ 2048K16 channel 1
1
1
64
0.15 ms
0.21 ms
0.22 ms
0.32 ms
1 ms
0.25 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog channels can be accumulated.
194
TSX DM 57 xxF
TSX P57 353 processor
21
General characteristics of TSX P57 353 processors
TSX P57 353 processor
The following table gives the general characteristics of the TSX P 57 353 processor.
Reference TSX P57 353
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX
8
16
86 with TSXRKY 4EX, 6EX, 8EX 110
I/O profile (2)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O fixed
1024
Maximum number of connections
Applications (counting, axis, etc.)
Built-in UNI-TELWAY (terminal port)
1
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet)
3
128
32
Master FIPIO (built-in)
Third party field bus
Savable real-time clock
AS-i field bus
127
2
8 yes
195
TSX P57 353 processor
Reference TSX P57 353
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Application code execution time for a 1K instruction
System overhead
Master task
Fast task
Event processing (of which 1 has priority)
Internal RAM 100% Boolean
PCMCIA card
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
MAST task without using the FIPIO bus using the FIPIO bus
FAST task
80K16/96K16(1)
384K16
256K16
640K16 channel 0
+ 2048K16 channel 1
1
1
64
0.15ms
0.21ms
0.22ms
0.32ms
1 ms
1 ms
0.25 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog channels can be accumulated.
196
TSX DM 57 xxF
TSX P57 3623 processor
22
General characteristics of TSX P57 3623 processors
TSX P57 3623 processor
The following table gives the general characteristics of the TSX P 57 3623 processor.
Reference TSX P57 3623
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
8
16
86
110
I/O profile (2)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O fixed
1024
128
Applications (counting, axis, etc.) 32
Maximum number of connections
Built-in UNI-TELWAY (terminal port)
1
Network (embedded ETHWAY,
FIPWAY, Modbus Plus, Ethernet)
3
Master FIPIO (built-in)
Third party field bus
Savable real-time clock
AS-i field bus
-
2
8 yes
197
TSX P57 3623 processor
Reference TSX P57 3623
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Application code execution time for a 1K instruction
System overhead
Master task
Fast task
Event processing (of which 1 has priority)
Internal RAM 100% Boolean
PCMCIA card
MAST task
FAST task
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
80K16/96K16(1)
384K16
256K16
640K16 channel
0 + 2048K16 channel 1
1
1
64
0.15 ms
0.21 ms
0.22 ms
0.32 ms
1 ms
0.25 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
fixed I/O profile (2): the number of discrete I/Os, and application-specific and analog channels can be accumulated.
198
TSX DM 57 xxF
TSX P57 453 processor
23
General characteristics of TSX P57 453 processors
TSX P57 453 processor
The following table gives the general characteristics of the TSX P 57 453 processor.
Reference TSX P57 453
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks 8
Maximum number of TSX RKY 4EX/6EX/8EX racks 16
Maximum number of slots with TSXRKY 12EX 86 with TSXRKY 4EX, 6EX, 8EX 110
I/O profile (2)
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O flexible
2048
256
64 Applications (counting, axis, etc.)
Maximum number of connections
Built-in UNI-TELWAY
(terminal port)
1
Network (ETHWAY, FIPWAY,
Modbus Plus, Ethernet)
4
Master FIPIO (built-in)
Third party field bus
127
2
Savable real-time clock
AS-i field bus 8 yes
199
TSX P57 453 processor
Reference TSX P57 453
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Application code execution time for a 1K instruction
System overhead
Master task
Fast task
Event processing (of which 1 has priority)
Internal RAM 100% Boolean
PCMCIA card
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
MAST task
FAST task
96K16/176K16(1)
512K16
256K16
640K16 channel 0
+ 2048K16 channel
1
1
1
64
0.07ms
0.11ms
0.07ms
0.11ms
1 ms
0.20 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
flexible I/O profile (2): the maximum number of discrete I/Os, and applicationspecific and analog channels cannot be accumulated. These area distributed according to a formula.
200
TSX DM 57 xxF
TSX P57 4823 processor
24
General characteristics of TSX P57 4823 processors
TSX P57 4823 processor
The following table gives the general characteristics of the TSX P 57 4823 processor.
Reference TSX P57 4823
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
I/O profile (2)
8
16
86
110
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O
Applications (counting, axis, etc.)
Maximum number of connections
Built-in UNI-TELWAY (terminal port) 1
Network (embedded ETHWAY,
FIPWAY, Modbus Plus, Ethernet)
4
FIPIO master (built-in), number of devices
127 flexible
2048
256
64
Third party field bus
AS-i field bus
Savable real-time clock
2
8 yes
201
TSX P57 4823 processor
Reference TSX P57 4823
Memory capacity
Processor internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Application code execution time for a 1K instruction
System overhead
Master task
Fast task
Event processing (of which 1 has priority)
Internal RAM 100% Boolean
PCMCIA card
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
MAST task
FAST task
96K16/
176K16(1)
512K16
256K16
640K16 channel 0 +
2048K16 channel 1
1
1
64
0.07ms
0.11ms
0.07ms
0.11ms
1 ms
0.19 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
flexible I/O profile (2): the maximum number of discrete I/Os, and applicationspecific and analog channels cannot be accumulated. These area distributed according to a formula.
202
TSX DM 57 xxF
Premium TSX P57 processor: general characteristics
25
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to introduce the characteristics of devices that can be used when installing a TSX 57 station.
This chapter contains the following topics:
Topic
Electrical characteristics of TSX P57 processors
Devices which can be connected to or built into the processor
Defining and counting application-specific channels
Page
203
TSX DM 57 xxF
Premium TSX P57 processor: general characteristics
Electrical characteristics of TSX P57 processors
General
Power consumption
As the processors can be fitted with certain devices which do not have their own power supply, the consumption of these devices must be taken into account when establishing a global breakdown of power consumption.
l l l l l
Devices without their own power supply which can be connected to the terminal port: l adjustment terminal: T FTX 117 ADJUST , l TSX P ACC01 unit for connecting to the UNI-TELWAY bus.
Devices without their own power supply which can be built into the processor: l PCMCIA communication cards TSX FPP 10/20,
PCMCIA communication card TSX SCP 111/112/114,
PCMCIA communication card TSX MBP 100,
PCMCIA modem card TSX MDM 10.
This table shows the consumption of the TSX PSY supply module at 5VDC:
Processor + PCMCIA memory card
TSX P57 103
TSX P57 153
TSX P57 203
TSX P57 253
TSX P57 2623
TSX P57 2823
TSX P57 303
TSX P57 353
TSX P57 3623
TSX P57 453
TSX P57 4823
Typical consumption
440 mA
530 mA
750 mA
820 mA
1110 mA
1180 mA
1000 mA
1060 mA
1360 mA
1080 mA
1440 mA
Maximum consumption
610 mA
740 mA
1050 mA
1140 mA
1450 mA
1540 mA
1400 mA
1480 mA
1800 mA
1510 mA
1910 mA
204
TSX DM 57 xxF
Dissipated power
Premium TSX P57 processor: general characteristics
This table states the dissipated power for TSX P57 processors:
Processor + PCMCIA memory card
TSX P57 103
TSX P57 153
TSX P57 203
TSX P57 253
TSX P57 2623
TSX P57 2823
TSX P57 303
TSX P57 353
TSX P57 3623
TSX P57 453
TSX P57 4823
typical
2.2 W
2.7 W
3.8 W
4.1 W
5.6 W
5.9 W
5.0 W
5.3 W
6.8 W
5.4 W
7.2 W
maximum
3.1 W
3.7 W
5.3 W
5.7 W
7.4 W
7.8 W
7.0 W
7.4 W
9.1 W
7.6 W
9.7 W
TSX DM 57 xxF
205
Premium TSX P57 processor: general characteristics
Devices which can be connected to or built into the processor
Tables of consumption and dissipated power
Consumption:
Consumption at 5VDC from the power supply module TSX
PSY …
Devices without their own power supply which can be connected to the terminal port (TER)
TFTX 117 ADJUST
TSXPACC01
PCMCIA communication card which can be built into the processor
TSXFPP10
TSXFPP20
TSXSCP111
TSXSCP112
TSXSCP114
TSXMBP100
TSXMDM10
Typical
310mA
150mA
330 mA
330 mA
140 mA
120 mA
150 mA
220 mA
195 mA
Maximum
340 mA
250 mA
360 mA
360 mA
300 mA
300 mA
300 mA
310 mA
-
Dissipated power:
Dissipated power
Devices without their own power supply which can be connected to the terminal port (TER)
PCMCIA communication card which can be built into the processor
TFTX 117 ADJUST
TSXPACC01
TSXFPP10
TSXFPP20
TSXSCP111
TSXSCP112
TSXSCP114
TSXMBP100
TSXMDM10
Typical
1.5 W
0.5 W
1.65 W
1.65 W
0.7 W
0.6 W
0.75 W
1.1 W
0.975 W
Maximum
1.7 W
1.25 W
1.8 W
1.8 W
1.5 W
1.5 W
1.5 W
1.55 W
-
206
TSX DM 57 xxF
Premium TSX P57 processor: general characteristics
Defining and counting application-specific channels
Summary table Applications:
Application
Counting
Movement control
Module/card
TSXCTY2A
TSXCTY2C
TSXCTY4A
TSXCAY21
Applicationspecific channels
Yes
Yes
Yes
Yes
Number
TSXCAY41
TSXCAY22
TSXCAY42
Yes
Yes
Yes
TSXCAY33 Yes 3
TSXCSY84 Yes
32
Step by step control TSXCFY11 Yes 1
4
2
4
2
2
4
2
2
2
0(*)
Weighing
Communication Serial link
TSXCFY21
TSXISPY100
TSXSCP11. in the processor
TSXSCP11. in the
TSXSCY21.
Yes
Yes
No
Yes
Modem
FIPIO agent
TSXSCP11. in the
TSXSCY21.
TSXSCY 21 (built-in channel)
TSXMDM10
Master FIPIO Built into the processor
Yes
Yes
Yes
TSXFPP10 in the processor No
No
1
1
1
1
0(*)
0(*)
(*) Although these channels are application-specific, they should not be taken into account when calculating the maximum number of application-specific channels which can be supported by the processor.
Note: Only channels configured from PL7 Junior or PL7 Pro software can be counted.
TSX DM 57 xxF
207
Premium TSX P57 processor: general characteristics
208
TSX DM 57 xxF
Processor performance
26
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter describes processor performance.
This chapter contains the following topics:
Topic
MAST task cycle time: introduction
MAST task cycle time: program processing Ppt
MAST task cycle time: input/output internal processing
Example of the calculation of cycle times of a MAST task under the following conditions
FAST task cycle time
Event response time
Page
TSX DM 57 xxF
209
Processor performance
MAST task cycle time: introduction
Explanatory diagram
The following diagram describes the MAST task cycle time:
Program processing
I.P
on input
I.P
on output cycle time
IP = internal
MAST CYCLE TIME = Program processing time (Ppt) + input/output internal processing time (Ipt):
210
TSX DM 57 xxF
Processor performance
MAST task cycle time: program processing Ppt
Definition of Ppt program processing time
Ppt = Application code execution time (Apcet) + Grafcet overhead time (OtG7).
Application code execution time
(Apcet)
Apcet = sum of the times of each instruction carried out by the application program in each cycle.
The execution time of each instruction as well as the type of application which was used to check them are given in the PL7 reference manual.
Processors
The table opposite gives the execution times in milliseconds (ms) for a 1K instruction
(1024 instructions):
Application code execution time Apcet (1)
Internal RAM
100% Boolean
0.66 ms
65% Boolean +
35% numerical
0.95 ms
PCMCIA card
100% Boolean
0.83 ms
65% Boolean +
35% numerical
1.18 ms TSX P57 103
TSX P57 153
TSX P57 2•3/2•23
TPCX 57 203
TSX P57 3•3/3623
TPCX 57 353
TSX P57 453/4823
0.21 ms
0.15 ms
0.28 ms
0.21 ms
0.27 ms
0.22 ms
0.40 ms
0.32 ms
0.11 ms 0.07 ms 0.11 ms 0.07 ms
(1) with all the instructions executed in each PLC cycle.
TSX DM 57 xxF
211
Processor performance
Grafcet overhead time (OtG7)
OtG7 = GFT + (AST x number of simultaneous active steps) + (OTT x number of transitions occurring simultaneously).
Summary table:
Processors
TSX P57 103
TSX P57 153
TSX P57 2•3/2•23
TPCX 57 203
TSX P57 3•3/3623
TPCX 57,353
TSX P57 453/4823
GFT: Grafcet time
AST: active step time
OTT: occurring transition time
GFT
0.243 ms
0.075 ms
0.047 ms
0.039 ms
AST
0.088 ms
0.029 ms
0.018 ms
0.015 ms
OTT
0.359 ms
0.109 ms
0.069 ms
0.058 ms
212
TSX DM 57 xxF
Processor performance
MAST task cycle time: input/output internal processing
Definition of input and output internal processing time
(Ipt)
Ipt =
MAST task overhead system time (Mtost)
+
max [receiving communication system Time (rcomT); management time on input of implicit I/O %I (mTi%I)]
+
max [sending communication system Time (scomT); management time on output of implicit I/O %Q (Mto%Q)]
MAST task overhead system time (Mtost)
Summary table:
Processors
TSX 57 103
TSX 57 153
TSX P57 203 / 2623
TPCX 57 203
TSX P57 253 / 2823
TSX P57 303 / 3623
TSX P57 353
TPCX 57 353
TSX P57 453 / 4823
Time without FIPIO application Time with FIPIO application
1.5 ms -
1.5 ms
1 ms
3.1 ms
-
1 ms
1 ms
1 ms
1 ms
1.2 ms
-
1 ms
1 ms
TSX DM 57 xxF
213
Processor performance
Management
Time on input/ output of implicit
I/O %I and %Q mTi%I = 60 micro seconds + sum of the IN times of each module.
mTo%Q = 60 micro seconds + sum of the OUT times of each module.
Management time on input (IN) and on output (OUT) for each module:
Type of module Management time
8 channel discrete inputs
On input (IN)
27
µ s
27
µ s 16 channel discrete inputs
(all modules except TSX DEY 16FK)
32 channel discrete inputs
64 channel discrete inputs
48 µ s
96
µ s
29 µ s Fast discrete inputs (8 channels used)
(module TSX DEY 16FK/TSXDMY 28FK)
Fast discrete inputs (16 channels used)
(module TSX DEY 16FK/TSXDMY 28FK/
28RFK)
37
µ s
8 channel discrete outputs
16 channel discrete outputs
32 channel discrete outputs
64 channel discrete outputs
Analog inputs (in groups of 4 channels)
Analog outputs (4 channels)
Counting (TSX CTY 2A/4A), by channel
Counting (TSX CTY 2C), by channel
26
µ s
33
µ s
47
µ s
94
µ s
84
µ s
59
µ s
55
µ s
65
µ s
Step by step control (TSX CFY ..
), by channel 75
µ s
Axis control (TSX CAY ..
), by channel 85
µ s
On output (OUT)
-
-
-
-
16 µ s
22
µ s
15
µ s
20
µ s
30
µ s
60
µ s
-
59
µ s
20
µ s
21
µ s
20
µ s
22
µ s
Total (IN+OUT)
27
µ s
27
µ s
48 µ s
96
µ s
45 µ s
59
µ s
41
µ s
53
µ s
77
µ s
154
µ s
84
µ s
118
µ s
75
µ s
86
µ s
95
µ s
107
µ s
Note: Discrete input/output module times are given in the theory that all channels of the module are assigned to the same task.
Example: using module TSX DEY 32 D2 K l if the 32 channels are assigned to the same task, use the "32 channel discrete inputs" time, l if only 16 channels are assigned to the same task, use the "16 channel discrete inputs" time and not the "32 channel discrete input" time divided by 2.
214
TSX DM 57 xxF
Processor performance
Communication system time l l
Communication (except telegram) is made during MAST task "Internal Processing" phases: on input for receiving messages (rcomT), on outputs for sending messages (scomT).
The MAST task cycle time is therefore affected by communication traffic.
Communication time through each cycle varies considerably according to: l traffic generated by the processor: the number of simultaneously active communication EF, l traffic generated from other devices to the processor or for which the processor ensures a traffic routing function like the master.
This time only occurs in the cycles where there is a new message to be managed.
Examples of communication system time
Terminal connected to PL7 Junior software and open animation table
Processors
TSX P57 103 / 153
TSX P57 2•3/2•23
TPCX 57 203
TSX P57 3•3/3623
TPCX 57 353
TSX P57 453 / 4823
Average time per cycle
2.5 ms
2 ms
1.3 ms
1 ms
Maximum time per cycle
3.5 ms
2.5 ms
1.8 ms
1.5 ms
1 OF SEND_RQ (mirror request, 100 characters)
Instruction execution time: 0.5 ms (for a TSX P57 203 processor), to be included in the application code execution time for cycles where the EF is executed in real-time.
TSX DM 57 xxF
215
Processor performance
Communication system time
Data table:
Processors
TSX P57 103 / 153
TSX P57 2•3/2•23
TPCX 57 203
TSX P57 3•3/3623
TPCX 57 353
TSX P57 453 / 4823
Sending time
800
µ s
220
µ s
150
µ s
120
µ s
Receiving time
800
µ s
220
µ s
150
µ s
120
µ s
Note: These times cannot be combined in the same cycle. Transmission occurs in the same cycle as instruction execution as long as communication traffic remains light, but the reply is not received in the same cycle.
216
TSX DM 57 xxF
Processor performance
Example of the calculation of cycle times of a MAST task under the following conditions
Introduction l l l l l l l l l
An application with the following characteristics:
TSX P57 203 processor,
Execution of a program in PLC internal RAM,
10 K instructions: 65% Boolean + 35% numerical,
1 OF communication type SEND_REQ,
128 discrete inputs distributed over: 7 TSX DEY 16D2 modules + 1 TSX DEY
16FK module,
80 discrete outputs distributed over: 5 TSX DSY 16T2 modules,
32 analog inputs distributed over: 2 TSX AEY 1600 modules,
16 analog outputs distributed over: 4 TSX ASY 410 modules,
2 counting channels distributed over: 1 TSX CTY 2A module.
Calculation of the different times l l
Application code execution time (APCET): without communication OF: 10 x 0.28 = 2.8 ms with 1 OF of SEND_REQ type communication (execution of an EF = 2 ms) =
(10x0.28) + 2 = 4.8 ms
Overhead system time (Ost) = 1ms
Input and output management time for implicit I/O %I and %Q:
Module product references
TSX DEY 16D2
Module type
TSX DEY 16 FK
16 channel discrete inputs
16 channel discrete inputs (fast inputs)
TSX DSY 16T2
TSX AEY 1600
TSX ASY 410
16 channel discrete outputs
Analog inputs
Analog outputs
TSX CTY 2A Counting
Total management time
Number of modules Input management time (IN)
7 238 micro seconds
1
5
2 (32 channels)
4 (16 channels)
1 (2 channels)
37 micro seconds
165 micro seconds
672 micro seconds
236 micro seconds
110 micro seconds
1458 micro seconds
Output management time (OUT)
-
22 micro seconds
100 micro seconds
-
236 micro seconds
40 micro seconds
398 micro seconds
Input management time: Imt%I = 60 microseconds + 1458 microseconds = 1518 microseconds = 1.52 ms.
Output management time: Omt%Q = 60 microseconds +398 microseconds = 458 microseconds = 0.46 ms.
TSX DM 57 xxF
217
Processor performance
Communication system time: l l
Sending a request: scomT = 0.22 ms,
Receiving the reply: rcomT = 0.22 ms.
Cycle time without execution of the communication OF
TcyM = Apcet + Most + Imt%I + Omt%Q
= 2.8 ms +1 ms + 1.52 ms + 0.46 ms = 5.78 ms
Cycle time with execution of the communication OF and sending of the request
McyT = Apcet + Texec EF + Most +Imt%I + Omt%Q + scomT
= 2.8 ms + 2 ms + 1 ms + 1.52 ms + 0.46 ms + 0.22ms = 8 ms
Cycle time with reception of reply
Mcyt = Apcet + Texec EF + Most +Imt%I + Omt%Q + rcomT
= 2.8 ms + 2 ms + 1 ms + 1.52 ms + 0.46 ms + 0.22ms = 8 ms
218
TSX DM 57 xxF
Processor performance
FAST task cycle time
Definition FAST cycle time = Program processing time (Ppt) + input and output internal processing time (Ipt).
Definition of Ppt program processing time
Ppt = Application code execution time relative to the FAST (Apcet).
Application code execution time: see Application code execution time (Apcet),
Definition of input and output internal processing time
(Ipt)
Ipt = FAST task overhead system time + input and output management time for implicit I/O %I and %Q.
FAST task overhead system time (FosT)
Processors
TSX P57 103
PCX 57 203
TSX P57 2•3/2•23
TSX P57 3•3/3623
PCX 57 353
TSX P57 453 / 4823
FAST task overhead system time
0.8 ms
0.6 ms
0.2 ms
Input and output management time for implicit I/O %I and %Q: see MAST task cycle
time: input/output internal processing, p. 213.
TSX DM 57 xxF
219
Processor performance
Event response time
General
Processors
TSX P57 103
PCX 57 203
TSX P57 2•3/2•23
TSX P57 3•3/3623
PCX 57 353
TSX P57 453/4623
Definition: time between an edge on an event input and the corresponding edge on an output positioned by the program in the event task.
Example: program with 100 Boolean instructions and input module TSX DEY 16 FK
Response time
Module TSX DSY 08T22
Minimum Typical
1.2 ms 1.3 ms
Maximum
2.8 ms
Module TSX DSY 32T2K
Minimum
1.9 ms
Typical
2.4 ms
Maximum
4.2 ms
1 ms
0.7 ms
1.1 ms
0.8 ms
2.2 ms
0.8 ms
1.8 ms
1.5 ms
2.2 ms
1.9 ms
3.7 ms
2.1 ms
220
TSX DM 57 xxF
Atrium PCX 57 processors
IV
At a Glance
Aim of this Part
What's in this
Part?
The aim of this Part is to describe PCX 57 processors and their installation.
This part contains the following chapters:
Chapter
27
28
29
30
31
32
Chapter Name
PCX 57 Processors: introduction
PCX 57 Processors: installation
PCX 57 processors: Diagnostics
PCX 57 203 processor
PCX 57 353 processor
Atrium PCX 57 CPU: general characteristics
Page
TSX DM 57 xxF
221
Atrium PCX 57 processors
222
TSX DM 57 xxF
PCX57 Processors : introduction
27
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to introduce PCX 57 processors.
This chapter contains the following topics:
Topic
General introduction
Physical description of PCX 57 processors
Real-time clock
Dimensions of PCX 57 processor cards
The different components of a PCX 57 card
Page
TSX DM 57 xxF
223
Processeurs PCX 57 : présentation
General introduction
At a Glance Integrated into a host PC (1) running Windows 95/98/2000 or Windows NT with a
16-bit ISA bus, PCX 57 processors manage, using PL7 Junior or PL7 Pro software, a complete PLC station made up of racks, discrete input/output modules, analog input/output modules and application modules, which can be distributed over one or more racks connected to an X Bus.
Note: The PCX 57 processor communicates with the PC in which it is installed via the 16-bit ISA bus. To do this, a communication driver ( ISAWAY 95/98/2000 or
ISAWAY NY must be installed.
Illustration
PCX 57 processor
Characteristics of the host PC
Host PC
Two types of processor are available to meet your different requirements: l PCX 57 203 processor: a processor with specifications and performance identical to the TSX P57 203 processor, l PCX 57 353 processor: a processor with specifications and performance identical to the TSX P57 353 processor.
l l l
To support a PCX 57 processor, the host PC must: operate under Windows 95/98 or Windows NT, have a 16-bit 8 MHz ISA bus, have two standard slots available on the ISA bus (consecutive and 20.32mm apart), of sufficient height and width.
As the shape of the PCX 57 processor card is exactly the same as the shape of l a 16-bit ISA PC card, the host PC must respond to ISA norms (signals, power supply, etc.).
Note: (1) the term "host PC" means a Schneider Group industrial PC or any other office PC that has the characteristics defined above.
224
TSX DM 57 xxF
Processeurs PCX 57 : présentation
Physical description of PCX 57 processors
Illustration This diagram labels the different components of a PCX 57 processor module
Description
4
5
2
3
6
This table describes the components of a processor module:
Number
1
Function
RUN, TER, BAT, I/O and FIP LEDs for signaling (the FIP LED is only present on the TPCX 57 353 model).
Slot for a PCMCIA type 1 memory extension card.
Micro-switches for coding the module’s position on the rack.
Micro-switches for coding the rack address on the X Bus.
Slot for a PCMCIA type 3 communication card.
Female 9-pin SUB D connector used to extend the X Bus to an extendable rack.
TSX DM 57 xxF
225
Processeurs PCX 57 : présentation
Number
7
8
9
10
11
12
13
14
Function
Terminal port ( TER Connector (8-pin mini-DIN)): this is used to connect an FTX type or PC compatible terminal, or to connect the PLC to the UNI-TELWAY bus through the TSX P ACC 01 insulation unit. This connector is used to supply 5V to the peripheral which is linked to it (limited by the available current provided by the PC’s power supply).
Recessed RESET button which leads to a cold startup of the PLC, when it is activated.
l Processor working normally: cold startup in STOP or RUN mode, according to the procedure defined in the configuration, l Processor error: forced startup in STOP mode.
The RESET button must be pressed using a non-conductive object.
ERR LED.
Male 9-pin SUB D connector for linking up to a master FIPIO bus. This connector is only present on TSX P57 353 processors.
16-bit ISA connector, used for linking up to the host PC.
Micro-switches for coding the PCX 57 processor address on the ISA bus (I/O space).
Contacts for selecting the interrupt (IRQ ..
), used by the processor on the ISA bus.
Slot for a battery which ensures that the processor’s internal RAM memory is saved.
Note: The TER terminal port offers master UNI-TELWAY communication mode by default, and can be configured for slave UNI-TELWAY or ASCII character mode.
226
TSX DM 57 xxF
Processeurs PCX 57 : présentation
Real-time clock
At a Glance PCX 57 processors have a real-time clock.
See
Real-time clock, p. 148 in the
TSX P57 Premium processor section.
TSX DM 57 xxF
227
Processeurs PCX 57 : présentation
Dimensions of PCX 57 processor cards
Diagrams The various following diagrams show the dimensions, in millimeters, of PCX 57 processor cards.
249
228
Note: A PCX 57 processor uses two slots on the PC ISA bus. These slots must be adjacent and 20.32mm apart.
TSX DM 57 xxF
Processeurs PCX 57 : présentation
The different components of a PCX 57 card
Illustration This diagram shows the various components which make up a PCX 57 processor card
1
3
4
2 5
6
Table of components and their descriptions
The following table gives the names and descriptions of the various components which make up the PCX 57 processor card:
Address Element
1 PCX 57 processor card
2 battery
3
4 line terminator removable cover
Description associated with a mechanical sub-assembly used to house a PCMCIA type 3 communication card.
the battery (See Changing the PCX 57 RAM memory
backup battery, p. 256 ) ensures the processor RAM
memory is saved, and it should be mounted in the appropriate slot on the processor card.
TSX TLYEX /B (See Line terminator TSX TLYEX,
a removable cover for a PCMCIA communication card specific to the PCX 57 processor.
TSX DM 57 xxF
229
Processeurs PCX 57 : présentation
Address Element
5 shield
6 daughterboard
Description shield equipped with a 9-pin SUB D connector to link a
TSX CBY..0K (See TSX CBY..0K X Bus extension cable
(II
≥
02), p. 100 ) X Bus extension cable, and a cable for
linking to the PCX 57 processor. This accessory is for connecting the PCX 57 processor inside a section of the
X Bus.
interfaces between the above shield and the PCX 57 processor card. This accessory should be used with the above shield. It is fitted instead of the A/ line terminator which is built into the processor as standard.
l l
Note: In addition to the components given above, the following are provided with the PCX 57 card: diskettes containing the ISAWAY drivers and OFS software package, instructions for installing the PCX 57 processor.
230
TSX DM 57 xxF
PCX 57 Processors : installation
28
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the installation of PCX 57 processors and the PCMCIA extension card.
This chapter contains the following topics:
Topic
Precautions to be taken during installation
Physical installation of the PCX 57 processor in the PC
Logical installation of the PCX 57 processor on the X Bus
Operations to be carried out before installation
How to configure the PCX 57 processor address on the X Bus
How to configure the processor’s standard I/O address on the ISA bus
How to install the PCX 57 processor card in the PC
Integrating a PCX 57 processor into an X Bus section
How to install/remove the memory extension card on the PCX 57 processor
Processing on insertion/extraction of a PCMCIA memory card on a PCX 57
PLC
Memory cards for PCX 57 processors
Precautions to be taken when replacing a PCX 57 processor
Page
231
TSX DM 57 xxF
Processeurs PCX 57 : installation
Precautions to be taken during installation
General You are advised to limit charges of static electricity, which can cause significant l l l damage to electronic circuits. To do this the following rules should be observed: l hold the card by the edges. Do not touch the connectors or any of the circuits that are visible, l do not take the card out of its protective anti-static packaging before you are ready to install it in the PC, ground yourself during handling, if possible, do not put the card on a metal surface, avoid unnecessary movements, as static electricity is generated by clothing, carpets and furniture.
232
TSX DM 57 xxF
Processeurs PCX 57 : installation
Physical installation of the PCX 57 processor in the PC
General
Illustration
The PCX 57 processor physically occupies two consecutive slots, slots 1 and 2, on the ISA bus but only uses one of them, slot 1, electrically. Slot 2 is used by the
PCMCIA communication card.
Diagram showing the principle:
Note: two PCX 57 processors can be installed in the same PC.
TSX DM 57 xxF
233
Processeurs PCX 57 : installation
Logical installation of the PCX 57 processor on the X Bus
Logical installation on the X Bus
The PCX 57 processor logically occupies the same slot as a TSX P57 processor
(rack with address 0, position 00 or 01).
The TSX RKY••EX rack with address 0 must have a power supply module and the position which is normally taken up by a TSX P57 processor will be unoccupied
(virtual slot for the PCX 57 processor).
Premium PLCs have two types of power supply (standard and double format). The unoccupied position on the rack with address 0 will be depend upon the type of power supply used.
Note: l The slot corresponding to the PCX 57 processor address (physically free on the l rack) must not be used by another module.
The X Bus address (See How to configure the PCX 57 processor address on
the X Bus, p. 238) must be configured using the micro-switches on the
processor card, so that the PCX 57 processor is aware of its address on the X
Bus.
Using a standard format power supply module l l l
In this case, the installation rule for the rack with address 0 is as follows: the power supply module automatically occupies position PS, position 00, the virtual slot for the processor, must be unoccupied, the other modules are installed starting at position 01.
234
TSX DM 57 xxF
TSX DM 57 xxF
Processeurs PCX 57 : installation
The following diagram shows the module installation rule when a single format power supply module is used.
TSX RKY••EX rack at address x
Rack address: 00
Address position: 00
TSX RKY••EX rack at address y
TSX RKY••EX rack at address 0
235
Processeurs PCX 57 : installation
Using a double format power supply module
In this case, the installation rule for the rack with address 0 is as follows: l l the power supply module automatically occupies positions PS and 00, position 01, the virtual slot for the processor, must be unoccupied, l the other modules are installed starting from position 02.
The following diagram shows the module installation rule when a single format power supply module is used.
TSX RKY••EX rack at address x
Rack address: 0
Address position: 01
TSX RKY••EX rack at address 0
TSX RKY••EX rack at address y
236
TSX DM 57 xxF
Processeurs PCX 57 : installation
Operations to be carried out before installation
General Certain operations must be performed before a processor card is installed in the PC: l l l l if necessary, insert the battery into the slot provided (See
RAM memory backup battery, p. 256),
Changing the PCX 57 if necessary, insert the PCMCIA memory card (See How to install/remove the
memory extension card on the PCX 57 processor, p. 248),
configure the address of the processor on the X Bus (See How to configure the
PCX 57 processor address on the X Bus, p. 238),
configure the processor’s standard I/O address on the ISA bus (See How to
configure the processor’s standard I/O address on the ISA bus, p. 240).
TSX DM 57 xxF
237
Processeurs PCX 57 : installation
How to configure the PCX 57 processor address on the X Bus
General points
Illustration
This address must be the same as the one which will be configured in the configuration screen of the PL7 Junior or PL7 Pro software. This configuration is carried out using micro-switches found on the processor card.
Rack address: the processor’s virtual slot is always situated on the rack with address 0.
Processor position: the virtual position of the processor will depend upon the type l l of power supply installed on the rack: single format power supply: virtual position of processor = 00, double format power supply: virtual position of processor = 01.
l l
Default configuration: rack address = 0, module position = 00.
Explanatory diagrams:
Coding
Value processor, here: 00
Coding address rack, here: 0
PCX
ADD
RACK
ADD
238
TSX DM 57 xxF
TSX DM 57 xxF
Processeurs PCX 57 : installation
Position of the RACK ADD micro-switches in relation to the rack address:
Rack 0 1 2 3 4 5 6 7
Position of the microswitches
PCX ADD
Addresses not used
Position of the PCX ADD micro-switches in relation to the processor’s position on the rack:
Position of the processeur
00 01
Position of the microswitches
PCX ADD
239
Processeurs PCX 57 : installation
How to configure the processor’s standard I/O address on the ISA bus
General points The PCX 57 processor uses: l l eight consecutive addresses in the ISA bus’s I/O space, an interrupt (IRQ ..
).
Before configuring the PCX 57 processor, it is a good idea to establish an I/O space and an available IT in the PC using the standard utilities under Windows 95/98 or
Windows NT.
When the available resources are determined, PCX 57 is configured as follows: l l the standard address of the PCX 57 processor on the ISA bus is configured, the interrupt used by the processor on the ISA bus is configured (IRQ ..
).
CAUTION
Bad configuration
A bad configuration can lead to the PC malfunctioning.
Failure to follow this precaution can result in injury or equipment damage.
Configuring the standard address of the
PCX 57 processor on the
ISA bus
This configuration is carried out using the 6 micro-switches located near the PCX
57’s ISA connector. They represent from left to right the bits with addresses SA9 to
SA4.
The address H‘220’ is configured by default.
Note: This address must be the same as the one which will be configured in the configuration screen of the ISAWAY driver.
240
TSX DM 57 xxF
Processeurs PCX 57 : installation
Illustration: the PCX 57 card and its micro-switches which are used to configure the address
Example of PCX
57 address coding on the
ISA bus
This table shows various address codings
Switch
Coding of the address
H’000’
H’110’
H’220’
H’330’
E
F
C
D
8
9
To
B
6
7
4
5
2
3
0
1
9 8
0 0
0 1
1 0
1 1
7 6 5 4
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0
1 0 1 1
1 1 0 0
1 1 0 1
1 1 1 0
1 1 1 1
3 2 1 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
0 0 0 0
TSX DM 57 xxF
241
Processeurs PCX 57 : installation
Illustration: coding using the micro-switches
Configuring the interrupt used by the processor on the ISA bus
(IRQ..)
This is configured using a jack-plug which should be placed over the interrupt to be selected. IRQ 10 is selected by default.
Illustration: PCX 57 card with micro-switches which are used to configure the IRQ.
242
TSX DM 57 xxF
Processeurs PCX 57 : installation
How to install the PCX 57 processor card in the PC
Preliminary conditions
Preliminary addressing operations (See Operations to be carried out before
installation, p. 237) must be performed.
DANGER
When installing the processor in the PC, the PC must always be switched off.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
Procedure to be followed
The following table describes the procedure for installing the processor card in the
PC:
Step
1
Action
Once the PC’s electrical power supply has been switched off, remove the computer casing and find two free adjacent ISA slots.
As an installation constraint, the PC must conform to the following standard:
PC
Emplacement ISA 1
Emplacement ISA 2
2
3
4
Remove the protective covers and fixing screws already in place which correspond to the available slots.
Install the card in the planned free slots.
Fix the card to the PC by tightening the fixing screws you removed previously.
TSX DM 57 xxF
243
Processeurs PCX 57 : installation
Step
5
6
Action
Place the casing back on the computer again and replace all the cables and accessories which had to be switched off: l X Bus cable and /B line terminator TSX TLYEX
Warning: The processor switches to a blocking fault, if the line terminator /B is not installed: l on the PCX 57 processor, if this is not linked to a rack by a TSX CBY ..
X
Bus cable. . In this case, a /B line terminator (See Line terminator TSX
TLYEX, p. 104 ) must be installed on the processor’s X Bus output.
l l on the available connector of the last rack of the station, if the PCX 57 processor is linked to a rack by a TSX CBY ..
X Bus cable. . In this case, a
/B line terminator must be installed.
This device is used to show that the X Bus has not been adapted.
FIPIO Bus cable and PCMCIA communication card, if necessary.
l l
Switch the PC on and start installing the various software packages: l ISAWAY driver which corresponds to the OS installed: WINDOWS 95/98 or
Windows NT, (see the service instructions provided with the processor),
OFS data server if used,
PL7 Junior or PL7 Pro software if used.
244
TSX DM 57 xxF
Processeurs PCX 57 : installation
Integrating a PCX 57 processor into an X Bus section
General
Illustration
As standard, the PCX 57 processor is equipped to be built into the start of the X Bus line, and for this reason it has a built-in A/ line terminator.
If you want to integrate the processor into an X Bus section, the module is supplied with two accessories which make this possible: l l l a shield equipped with: a 9-pin SUB D connector for linking up a TSX CBY• X Bus cable, a cable for connecting the 9-pin SUB D connector to the processor card, l a daughterboard equipped with two connectors which interface between the
PCX 57 card and the 9-pin SUB D connector of the aforementioned shield. This daughterboard is fitted instead of the A/ line terminator, mounted on the PCX 57 card as standard.
Shield and daughterboard:
Shield
Daughterboard
TSX DM 57 xxF
245
Processeurs PCX 57 : installation
Installation procedure
Carry out the following steps
Step
1
Action
Remove the A/ line terminator from its slot on the processor.
Illustration
2 Fit the daughterboard in place of the A/ line terminator.
3 Once the processor card is in place in the PC, fix the shield in the available slot situated immediately to the left of the processor card, as indicated in the diagram below.
4 Connect the cable to the connector of the daughterboard which was installed in step 2
246
TSX DM 57 xxF
Example of the topology of a
PCX 57 station with the processor integrated in an X
Bus section
Diagram
Host PC
PCX 57
PCX 57
Processeurs PCX 57 : installation
Note: In this example, as the PCX 57 processor is no longer integrated at the start of the line, the TSX TLY EX A/ and /B line terminators must be installed on each of the racks situated at the end of the lines.
TSX DM 57 xxF
247
Processeurs PCX 57 : installation
How to install/remove the memory extension card on the PCX 57 processor
Principle Perform the following steps to install the memory card on the PCX 57 processor:
2
3
Step
1
Action
Place the PCMCIA card in its allocated slot.
Slide it in until it can go no further.
Position the card in the PC with the power turned off.
Illustration
CAUTION
Installation precautions
The memory extension card must be installed on the processor card with the power switched off and before the latter is installed in the PC.
Failure to follow this precaution can result in injury or equipment damage.
Explanatory diagram:
248
Note: If the program in the PCMCIA memory cartridge contains the RUN AUTO option, the processor will automatically restart in RUN mode after the cartridge is inserted and the PC is turned on.
TSX DM 57 xxF
Processeurs PCX 57 : installation
Processing on insertion/extraction of a PCMCIA memory card on a PCX 57 PLC
General
CAUTION
Insertion/Extraction
It is forbidden to insert or extract the PCMCIA memory card into or from a PCX 57 when it is powered-up. These actions, although they will not damage the processor or any other device, cause random processor behavior and thus, correct operation cannot be guaranteed.
Failure to follow this precaution can result in injury or equipment damage.
CAUTION
RUN AUTO option
If the program contained in the PCMCIA memory card includes the
RUN AUTO option, the processor will automatically restart in RUN mode after the card is inserted and the PC is switched on.
Failure to follow this precaution can result in injury or equipment damage.
TSX DM 57 xxF
249
Processeurs PCX 57 : installation
Memory cards for PCX 57 processors
General See
Standard and Backup memory cards for PLCs, p. 159 andApplication + files
250
TSX DM 57 xxF
Processeurs PCX 57 : installation
Precautions to be taken when replacing a PCX 57 processor
Important
CAUTION
Replacing a processor
If the PCX 57 processor is being replaced by another processor which is not blank (i.e. the processor has already been programmed and contains an application), you must cut the power to all of the PLC station’s control units.
Before restoring power to the control units, check that the processor contains the required application.
Failure to follow this precaution can result in injury or equipment damage.
TSX DM 57 xxF
251
Processeurs PCX 57 : installation
252
TSX DM 57 xxF
PCX 57 processors: Diagnostics
29
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with PCX 57 processor diagnostics.
This chapter contains the following topics:
Topic
Description of PCX 57 processor LEDs
Changing the PCX 57 RAM memory backup battery
Changing the PCX 57 RAM memory PCMCIA card battery
What happens after you press the processor RESET button
How the PCX 57 behaves after an action on the PC
Finding errors via the processor status LEDs
Page
TSX DM 57 xxF
253
PCX 57 processors: Diagnostics
Description of PCX 57 processor LEDs
Labeling of the
LEDs
Six LEDs (RUN, TER, BAT, I/O, FIP and ERR) found on the processor card enable fast diagnostics of the status of the PLC station.
Due to the small amount of space available on the shield, only the ERR LED is visible when the PC housing the processor is closed.
To make it more user-friendly, the state of the RUN, I/O, ERR and FIP LEDs is displayed via a utility in the task bar in Windows 95/98 or Windows NT on the PC with the processor card. This functionality is only available when the host PC is running (ISAWAY driver installed)
254
TSX DM 57 xxF
Description
TSX DM 57 xxF
PCX 57 processors: Diagnostics
The following table describes the role of each LED:
Display
LED
BAT
(red)
RUN
(green)
TER
(yellow)
I/O
(red)
FIP
(yellow)
ERR
(red) l l l
battery missing, battery flat, battery the wrong way round, wrong type of battery.
l
PLC running normally, program executing.
-
PLC in STOP mode or blocked by software error.
running normally.
input/output errors coming from a module, a channel or a configuration error.
terminal port link active.
The rate of flashing is relative to the amount of traffic.
link not active.
X Bus error (1).
normal state, no internal error.
processor or system error.
l l
PLC not configured: application missing, invalid or incompatible,
PLC error: processor or system error.
FIPIO bus link active.
The rate of flashing is relative to the amount of traffic.
l l l l
PLC not configured
(application missing, invalid or incompatible),
PLC blocked by a software error, memory card battery error,
X Bus error (1).
link not active.
normal state, no internal error.
Note: l (1) an X Bus error is indicated by simultaneous flashing of the ERR and I/O
LEDs.
l the FIP LED is only present on TPCX P57 353 processor.
255
PCX 57 processors: Diagnostics
Changing the PCX 57 RAM memory backup battery
Introduction This battery on the PCX 57 processor module ensures that the processor internal
RAM memory and the real-time clock are saved in the event of a power outage. It is delivered in the same packaging as the processor and must be installed by the user.
Note: With a PCX 57 processor, there is no point in putting a battery into the rack power supply which usually houses the processor (rack with address 0).
Installing the battery for the first time
To install the battery, carry out the following:
Step
1
2
3
Action
Remove the cover by squeezing the sides.
Put the battery in its slot taking care to observe polarities.
Replace the cover which keeps the battery in its slot.
Changing the battery
The battery can be changed every year as a preventative measure or when the BAT
LED is lit. However the LED is not visible when the PC is closed, but you have a
%S68 system bit (0 = backup battery OK) which can be used by the application program to generate an alarm to warn that the battery needs changing.
To change the battery, carry out the following:
6
7
4
5
8
9
2
3
Step
1
Action
Switch the PC off.
Disconnect the different cables linked to the processor.
Open the PC.
Take the card out of its slot.
Remove the cover.
Remove the defective battery from its slot.
Put in the new battery, observing the polarities.
Replace the cover.
Put the card back in its slot, close the PC, connect external components and switch on.
256
TSX DM 57 xxF
Illustration
PCX 57 processors: Diagnostics
CAUTION
Precaution to be taken when changing the battery
Changing the battery should not exceed the stated limit for the PC being switched off. Exceeding this limit may cause data in RAM memory to be lost.
Failure to follow this precaution can result in injury or equipment damage.
The following diagram shows how the battery is installed:
1: cover
2: battery
TSX DM 57 xxF
257
PCX 57 processors: Diagnostics
How often must the battery be changed?
Period of battery backup
The length of time during which the battery ensures backup of the processor’s internal RAM memory and the real-time clock depends on two factors: l the percentage of time for which the PLC is switched off and as a result the battery is being used, l the ambient temperature when the PLC is switched off.
Summary table:
Ambient temperature when inoperative
Backup time PLC off for 12 hours per day
≤
30°C
5 years
PLC off for 1 hour per day
5 years
40°C 50°C
3 years
2 years
5 years
60°C
1 year
4.5 years 4 years
Independent saving by the processor
The processors have their own offline independent save function to save the processor internal RAM memory and the real-time clock, which allows the removal of: l the PCX 57 processor battery.
The backup time depends on the ambient temperature.
Assuming that the processor was switched on previously, the guaranteed time varies in the following way:
Ambient temperature when switching off
Backup time
20°C
2h
30°C 40°C 50°C
45mn 20mn 8mn
258
TSX DM 57 xxF
Changing the PCX 57 RAM memory PCMCIA card battery
PCX 57 processors: Diagnostics
Introduction
How to change the battery
RAM memory PCMCIA cards (TSX MRP etc.) must have a battery (reference TSX
BAT M01) which needs to be changed.
Carry out the following steps:
4
5
Step
1
2
3
6
7
Action
Take the card out of its slot.
Hold the PCMCIA card so you can access the battery slot. This is at the end of the card without the connector.
Unlock the battery holder, which is at the end of the card without the connector.
To do this press the lock towards the bottom of the card (the opposite direction to the write protection micro-switch) while pulling towards the back.
Remove the battery and holder unit from its slot.
Swap the defective battery for an identical 3V battery. Polarities must be observed by placing the + labels on the holder and the battery on the same side.
Place the battery and holder unit back in its slot, then lock it. To do this, carry out the removal procedure in reverse.
Put the memory card back in its allocated slot on the PCX 57 card.
Illustration Principle diagram:
Write protection
Lock
Battery slot
Number
TSX DM 57 xxF
259
PCX 57 processors: Diagnostics
Battery life See the following table:
PCMCIA card stored in normal conditions (-20°C to 70°C)
PCMCIA card fitted in an operating PLC (0°C à 60°C).
12 months
36 months
Note: During operation, the processor’s ERR LED flashes if the PCMCIA card battery is defective.
260
TSX DM 57 xxF
PCX 57 processors: Diagnostics
What happens after you press the processor RESET button
General All processors have a RESET button on their front panel, which when pressed, causes a PLC cold start, in RUN or in STOP mode (1), in the application contained on the memory card (or in internal RAM).
RESET following a processor fault
As soon as a processor fault appears, the alarm relay on rack 0 (2) is deactivated
(open contact) and the module outputs switch to fallback position or are maintained in the current state depending on the selection made at configuration. Pressing the
RESET button causes the PLC, forced into STOP mode, to cold start.
(1) Start in RUN or in STOP mode is defined at configuration.
(2) With the PCX 57 processor, this relay is not controlled.
Note: When the RESET button is pressed, and during the PLC cold start, the terminal link is deactivated.
TSX DM 57 xxF
261
PCX 57 processors: Diagnostics
How the PCX 57 behaves after an action on the PC
General The following table describes the different actions on the PC and what implications they have for the PCX 57:
Action on the PC
Switching off/on
Micro-outages on the network supplying the
PC
Pressing the RESET button
PC’s software RESET
(CTRL ALT DEL)
PCX 57 behavior warm restart if the application environment has not changed
As the PCX 57 does not have a filtering mechanism for microoutages, every micro-outage not filtered by the PC’s internal power supply causes a warm restart of the PCX 57, if the application environment has not changed generally, and subject to the PC’s RESET button activating the
RSTDRV signal on the ISA bus, pressing the PC RESET button causes a warm restart of the PCX 57, if the application environment has not changed.
these actions have no effect on the current state of the PCX 57 processor (if the PCX 57 processor is in RUN, it stays in , etc.) and does not cause a warm restart or cold restart
Note: A PC software blockage has no effect on the current state of the PCX 57 processor (identical behavior to a PC software RESET).
262
TSX DM 57 xxF
Finding errors via the processor status LEDs
General See: l l l
Finding errors using processor state LEDs, p. 175,
l
Processor or system errors, p. 179.
PCX 57 processors: Diagnostics
TSX DM 57 xxF
263
PCX 57 processors: Diagnostics
264
TSX DM 57 xxF
PCX 57 203 processor
30
General characteristics of the PCX 57 203 processor
PCX 57 203 processor
The following table gives the general characteristics of the PCX 57 203 processor.
Reference PCX 57 203
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks
Maximum number of TSX RKY 4EX/6EX/8EX racks 16
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
87
111
Maximum number of channels
In-rack discrete I/O
In-rack analog I/O
8
1024
80
Application (counting, axis, etc.) 24
1 Maximum number of connections
Built-in UNI-TELWAY (terminal port)
Network (ETHWAY, FIPWAY,
Modbus+)
Master FIPIO (built-in)
Third party field bus
AS-i field bus
Savable real-time clock
1
-
1
4 yes
265
PCX 57 203 processor
Reference PCX 57 203
Memory capacity
Application structure
Savable internal RAM
PCMCIA memory card
(maximum capacity)
Application area
Symbol Zone
File area
Master task
Fast task
Application code execution time for a 1K instruction
Event processing (of which 1 has priority)
Internal RAM
PCMCIA card
100% Boolean
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
System overhead
MAST task
FAST task
48K16
160K16
-
128K16 or 640K16
1
1
64
0.21 ms
0.28 ms
0.27 ms
0.40 ms
1 ms
0.35 ms
266
TSX DM 57 xxF
PCX 57 353 processor
31
General characteristics of the PCX 57 353 processor
PCX 57 353 processor
The following table introduces the general characteristics of the PCX 57 353 processor.
Reference PCX 57 353
TSX DM 57 xxF
Maximum configuration
Functions
Maximum number of TSX RKY 12EX racks 8
Maximum number of TSX RKY 4EX/6EX/8EX racks 16
Maximum number of slots with TSXRKY 12EX with TSXRKY 4EX, 6EX, 8EX
87
111
Maximum number of channels
Maximum number of connections
In-rack discrete I/O
In-rack analog I/O
1024
128
Application (counting, axis, etc.) 32
Built-in UNI-TELWAY (terminal port)
1
Network (ETHWAY, FIPWAY,
Modbus+)
FIPIO master (built-in), number of devices
3
127
Third party field bus
AS-i field bus
2
8
267
PCX 57 353 processor
Reference PCX 57 353
Memory capacity
Savable real-time clock
Savable internal RAM
PCMCIA memory card (maximum capacity)
Application area
Symbol Zone
File area
Application structure
Master task
Fast task
Event processing (of which 1 has priority)
100% Boolean Application code execution time for a 1K instruction
Internal RAM
PCMCIA card
65% Boolean + 35% digital
100% Boolean
65% Boolean + 35% digital
System overhead
MAST task
FAST task yes
80K16 or 96K16 (1)
384K16
-
128K16 or 640K16
1
1
64
0.15 ms
0.21 ms
0.22 ms
0.32 ms
1 ms
0.25 ms
(1) 1 st
figure when the application is in internal RAM, 2 nd
figure when the application is in card memory.
268
TSX DM 57 xxF
Atrium PCX 57 CPU: general characteristics
32
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to introduce you to the characteristics of devices that can be used when installing a PCX 57 station.
This chapter contains the following topics:
Topic
Electrical characteristics of PCX 57 processors
Devices which can be connected to or built into the processor
Defining and Counting Application-specific channels
Processor performance
Page
269
TSX DM 57 xxF
Atrium PCX 57 CPU: general characteristics
Electrical characteristics of PCX 57 processors
General
Feature of PCX
57 processors
Power consumption
As the processors can be fitted with certain devices which do not have their own power supply, the consumption of these devices must be taken into account when establishing a global breakdown of power consumption.
l l l l l
Devices without their own power supply which can be connected to the terminal port: l adjustment terminal: T FTX 117 ADJUST , l unit TSX P ACC01 for connecting to the UNI-TELWAY bus.
Devices without their own power supply which can be built into the processor: l PCMCIA communication cards TSX FPP 10/20,
PCMCIA communication card TSX SCP 111/112/114,
PCMCIA communication card TSX MBP 100,
PCMCIA modem card TSX MDM 10.
PCX 57 processors have their own 5VDC power supply, which is generated from the host PC’s 12 VDC power supply. As a result of this, the 12 VDC power supply from the host PC must have sufficient power to accommodate a PCX 57 processor.
This table shows consumption of the host PC at 12VDC:
Typical consumption Maximum consumption Processor + PCMCIA memory card
TPCX P57 203
TPCX P57 353
400 mA
550 mA
560 mA
770 mA
Dissipated power
This table states the dissipated power for PCX 57 processors:
Typical consumption Maximum consumption Processor + PCMCIA memory card
TPCX P57 203
TSX P57 353
4,8W
6,6W
6,72W
9,24W
270
TSX DM 57 xxF
Atrium PCX 57 CPU: general characteristics
Devices which can be connected to or built into the processor
Tables of consumption and dissipated power
Consumption:
Consumption at 12VDC from host PC
Devices without their own power supply which can be connected to the terminal port (TER)
TFTX 117 ADJUST
TSXPACC01
Typical
144 mA
69 mA
PCMCIA communication card which can be built into the processor
TSXFPP10
TSXFPP20
TSXSCP111
153 mA
153 mA
65 mA
TSXSCP112
TSXSCP114
TSXMBP100
TSXMDM10
56 mA
69 mA
102 mA
90 mA
Maximum
157 mA
116 mA
167 mA
167 mA
139 mA
139 mA
139 mA
144 mA
-
Dissipated power:
Dissipated power
Devices without their own power supply which can be connected to the terminal port (TER)
PCMCIA communication card which can be built into the processor
TFTX 117 ADJUST
TSXPACC01
TSXFPP10
TSXFPP20
TSXSCP111
TSXSCP112
TSXSCP114
TSXMBP100
TSXMDM10
Typical
1.7 W
0.8 W
1.8 W
1.8 W
0.8 W
0.7 W
0.8 W
1.2 W
1.1 W
Maximum
1.9 W
1.4 W
2.0 W
2,0W
1.7 W
1.7 W
1.7 W
1.7 W
-
TSX DM 57 xxF
271
Atrium PCX 57 CPU: general characteristics
Defining and Counting Application-specific channels
Summary table
272
Applications:
Application Module/card
Counting TSXCTY2A
TSXCTY2C
TSXCTY4A
CCY 1128
Movement commands TSXCAY21
TSXCAY41
TSXCAY22
TSXCAY42
Step by step control
Weighing
Communication Serial link
TSXCAY33
CSY 84
TSXCFY11
TSXCFY21
Yes
Yes
TSXISPY100 / TSXISP101 Yes
TSXSCP11. in the processor
No
TSXSCP11. in the
TSXSCY21.
TSXSCP11. in the
TSXSCY21.
TSXSCY 21 (built-in channel)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Applicationspecific channels
Yes
Yes
Modem
FIPIO agent
TSXMDM10
Master FIPIO Built into the processor
Yes
TSXFPP10 in the processor No
No
Number
1
1
1
1
0(*)
0(*)
(*) Although these channels are application-specific, they should not be taken into account when calculating the maximum number of application-specific channels which can be supported by the processor.
1
2
3
32
2
0(*)
2
4
2
4
4
1
2
2
Note: Only channels configured from PL7 Junior or PL7 Pro software can be counted.
TSX DM 57 xxF
Processor performance
General See
Processor performance, p. 209:
Atrium PCX 57 CPU: general characteristics
TSX DM 57 xxF
273
Atrium PCX 57 CPU: general characteristics
274
TSX DM 57 xxF
TSX PSY… supply modules
V
At a Glance
Aim of this Part
What's in this
Part?
The aim of this Part is to describe the TSX PSY … supply modules and their installation.
38
39
40
41
42
43
This part contains the following chapters:
Chapter
33
34
35
36
37
Chapter Name
TSX PSY… supply modules: introduction
TSX PSY … supply modules: installation
TSX PSY … supply modules: diagnostics
TSX PSY … supply modules : auxiliary functions
TSX PSY power supply modules: breakdown of power consumption and power
TSX PSY 2600 power supply module
TSX PSY 5500 power supply module
TSX PSY 8500 power supply module
TSX PSY 1610 power supply module
TSX PSY 3610 power supply module
TSX PSY 5520 power supply module
Page
TSX DM 57 xxF
275
TSX PSY… supply modules
276
TSX DM 57 xxF
TSX PSY… supply modules: introduction
33
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to introduce the TSX PSY … supply modules .
This chapter contains the following topics:
Topic
General introduction
Supply modules: description
Page
TSX DM 57 xxF
277
TSX PSY…supply modules : introduction
General introduction
At a Glance
Auxiliary functions of supply modules
TSX PSY… supply modules are designed to supply each TSX RKY… rack and its modules. The supply module is chosen according to the distribution network (direct or alternating current) and the power required (standard or double format model).
l l
There are several types of supply modules: supply modules for an alternating current network , supply modules for a direct current network .
l l l l
Each supply module has auxiliary functions: a display panel, an alarm relay, a slot for a battery for saving the data in the processor’s RAM memory, a recessed button which, when pressed, simulates a power-supply outage, and launches a warm restart of the application, l a 24 VDC sensor supply (only on models supplied from an alternating current network).
Supply modules for an alternating current network
The following table displays the types of supply module according to their format:
Standard format model Double format model
TSX PSY 2600
100...240 VCA
TSX PSY 5500
100...120 VCA
TSX PSY 8500
200...240 VCA
278
TSX DM 57 xxF
TSX PSY…supply modules : introduction
Supply modules for a direct current network
The following table displays the types of supply module according to their format:
Standard format model Double format model
TSX PSY 1610
24 VCC non-insulated
TSX PSY 3610
24 VCC non-insulated
TSX PSY 5520
24...48 VCC insulated
TSX DM 57 xxF
279
TSX PSY…supply modules : introduction
Supply modules: description
At a Glance
Illustration l l
The supply models take the form of: standard format modules, for TSX PSY 2600 and TSX PSY 1610 modules, double format modules for TSX PSY 5500/3610/5520/8500 modules.
These illustrations label the different components of a standard supply module and a double format supply module:
Standard format Double format
280
TSX DM 57 xxF
Description
TSX PSY…supply modules : introduction
This table describes the components of a supply module:
6
7
3
4
Number Function
1 Display block containing: l l l an a
OK
BAT
LED (green), lit if the voltages are present and correct,
LED (red), lit when the battery is defective or missing, a 24V LED (green), lit when the voltage sensor is present. This LED is only present on alternating current supply modules TSX PSY 2600/5500/8500.
2 Recessed RESET button which, when pushed, triggers a warm restart of the application.
Slot for a battery which ensures the processor’s internal RAM memory is saved.
Flap for protecting the front panel of the module.
5
8
Screw terminal block for linking up to: l l l the supply network, the alarm relay contact, the sensor supply for alternating current supply modules TSX PSY 2600/
5500/8500.
Hole for a cable-tightening clip to go through.
Fuse located under the module protecting: l l the 24VR voltage on the direct current supply module TSX PSY 3610, the primary voltage on the direct current supply module TSX PSY 1610,
Note: on the TSX PSY 2600/5500/5520/8500 supply modules, the primary voltage protection fuse is inside the module and cannot be accessed.
110/220 voltage selector, only present on alternating current supply modules
TSX PSY 5500/8500. On delivery, the selector is set to 220.
TSX DM 57 xxF
281
TSX PSY…supply modules : introduction
282
TSX DM 57 xxF
TSX PSY … supply modules: installation
34
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the installation of TSX PSY … power supply modules .
This chapter contains the following topics:
Topic
Installation/mounting TSX PSY … supply modules .
Rules for connecting TSX PSY supply modules
Connecting alternating current power supply modules
Connecting direct current power supply modules from a floating 24 or 48 VDC direct current network
Connecting direct current power supply modules from an alternating current network
Sensor and pre-actuator power supply servo control
Definition of protection devices at the start of a line
Page
283
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Installation/mounting TSX PSY … supply modules .
Mounting
Installation
The mounting of the TSX PSY… power supply module is identical to the mounting of processor modules and, in general terms, the same as the mounting of other modules (see
How to mount processor modules, p. 154).
This table describes the principles of installing power supply modules:
Type of supply module
Standard format:
TSX PSY 2600/1610
Description installed in the first slot in each TSX RKY rack and occupy the PS position.
Illustration
Double format:
TSX PSY 3610/5500/
5520/8500 installed in the first two slots in each TSX RKY rack and occupy the PS and 00 positions.
Note: Each supply module is provided with a locating device that only allows the module to be installed in the slot designated above.
Note: the TSX PSY 8500 supply module does not provide 24VR voltage. Because of this, a rack fitted with this supply module will not be able to accommodate some modules, such as relay output and weighing modules
284
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Rules for connecting TSX PSY supply modules
General points
Illustration
The TSX PSY ••• power supply modules on each rack are equipped with a nonremovable terminal block, protected by a flap, which is used to connect the power supply, the alarm relay, the protection ground and, for alternating current supplies, the supply of the 24 VDC sensors.
This screw terminal block is equipped with captive clamp screws which can connect a maximum of 2 wires with a cross-sectional area of 1.5mm
2
with wire end ferrules, or one wire with a cross-sectional area of 2.5mm
2
(maximum tightening torque on screw terminal: 0.8N.m).
The wires come out vertically towards the bottom. These wires can be kept in place with a cable-clip.
This diagram shows the screw terminal block:
TSX DM 57 xxF
Supply
24V sensors
Alarm relay
Network ~
110-220V
Protection ground
PE
Alarm relay
24V network (1)
Protection ground
PE
Alternating current supply
TSX PSY 2600/5500/8500
Direct current supply
TSX PSY 1610/3610/5520
(1) 24...48VAC for the TSX PSY 5520 supply module.
285
Alimentations TSX PSY ... : installation
Warning
286
CAUTION
Positioning the voltage selector
For the power supply modules TSX PSY 5500/8500, position the voltage selector according to the voltage power used (110 or 220 VAC).
Failure to follow this precaution can result in injury or equipment damage.
Provide a protection device and switchgear upstream of the PLC station.
When selecting protection devices, the user should take into account the signaling currents which are defined in the characteristics tables for each supply module.
Note: As direct current supply modules TSX PSY 1610/2610/5520 have a strong signaling current, it is not advisable to use them on direct current networks which protect flood-back current limits.
When a power supply module is connected to a direct current network, it is mandatory to limit the length of the supply cable in order to prevent transmission loss.
l TSX PSY 1610 supply module: l length limited to 30 meters (60 meters there and back) with copper wires and l a 2.5mm
2
cross-section, length limited to 20 meters (40 meters there and back) with copper wires and a 1.5mm
2
cross-section.
l TSX PSY 3610 and TSX PSY 5520 supply modules: l length limited to 15 meters (30 meters there and back) with copper wires and a 2.5mm
2
cross-section, l length limited to 10 meters (20 meters there and back) with copper wires and a 1.5mm
2
cross-section.
Linking several PLCs supplied by a permissible direct current network not connected to ground.
The 0V and physical ground are linked internally in the PLCs, in the network cabling accessories and in some control consoles.
For specific applications which use a "floating" installation, special measures should be taken with connections. These depend on the method used for installation.
In this case, it is mandatory to use insulated direct current power supplies. Please contact us when you are defining the electrical installation.
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Connecting alternating current power supply modules
Connecting a single-rack PLC station
Illustration:
Alternating network 100-240 V
Supply control
Pre-actuators
Sensor supply for sensors on the rack (2)
TSX PSY ..00
Q: general section switch,
KM: circuit contactor-breaker,
(1) insulating connector bar for finding grounding faults
(2) available current: l l
0.6 A with a TSX PSY 2600 (See
TSX PSY 2600 power supply module, p. 321)
power supply module,
0.8 A with a TSX PSY 5500 (See
TSX PSY 5500 power supply module, p. 323)
power supply module, l 1.6 A with a TSX PSY 8500 (See power supply module,
TSX PSY 8500 power supply module, p. 325)
Note: Protective fuses: alternating current power supply modules TSX PSY
2600/5500/8500 are fitted during manufacture with a protective fuse. This fuse, in series with the L input, is located inside the module and cannot be accessed.
TSX DM 57 xxF
287
Alimentations TSX PSY ... : installation
Illustration: Connecting a
PLC station made up of several racks
Alternating network 100-240 V
Supply control pre-actuators
Sensor supply for sensors on the rack (2)
TSX PSY ..00
Supply control pre-actuators
Sensor supply for sensors on the rack (2)
TSX PSY ..00
288
Note: If there are several PLC stations supplied by the same network, the principles of connection are identical.
Q: general section switch,
KM: circuit contactor-breaker,
(1) insulating connector bar for finding grounding faults
(2) available current: l l
0.6 A with a TSX PSY 2600 (See
TSX PSY 2600 power supply module, p. 321)
power supply module,
0.8 A with a TSX PSY 5500 (See
TSX PSY 5500 power supply module, p. 323)
power supply module, l 1.6 A with a TSX PSY 8500 (See power supply module,
TSX PSY 8500 power supply module, p. 325)
Note: Protective fuses: alternating current power supply modules TSX PSY
2600/5500/8500 are fitted during manufacture with a protective fuse. This fuse, in series with the L input, is located inside the module and cannot be accessed.
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Connecting direct current power supply modules from a floating 24 or 48 VDC direct current network
Warning
Illustration
In the case of floating mounting (not linked to ground) used for specific applications and in particular in Marine Applications , an insulated TSX PSY 5520 (24/48 VDC) supply module must be selected.
Diagram showing the principle:
Alternating network low voltage
Pre-actuator supply control
Rack 0
TSX PSY 5520
Battery charger
Battery
Pre-actuator supply control
Rack x
TSX PSY 5520
Insulation tester
TSX DM 57 xxF
24 VDC floating network for supplying the sensors, actuators and discrete input/output modules
Note: A device can continually measure the level of insulation of the 24 VDC (or
48 VDC) in relation to the ground, and can give an alert when the level of insulation is abnormally low.
The input/output modules in the Premium range are insulated.
289
Alimentations TSX PSY ... : installation
Connecting direct current power supply modules from an alternating current network
Non-insulated power supply modules TSX
PSY 1610/3610
Connecting a single-rack PLC station with a ground-referenced network:
Alternating network 100-240 V
Supply control pre-actuators
TSX PSY ..10
Supply for sensors/ pre-actuators
Q: General section switch,
KM: Circuit contactor-breaker,
(1): External shunt provided with the power supply module,
(2): Insulating connector bar for finding grounding faults. In this case, it is necessary to switch off the supply in order to disconnect the network from the ground,
(3): Optional use of a process power supply module (See Process and AS-i supply,
(4): Protective fuse, (4 A, with time-delay) only necessary with the TSX PSY 3610 power supply module.
The TSX PSY 1610 power supply module is fitted during manufacture with a protective fuse located under the module and in series on the 24V input (3.5 A, 5x20 time-delay fuse).
290
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Connecting a multi-rack PLC station with a ground-referenced network:
Alternating network 100-240 V
Supply control pre-actuators
TSX PSY ..10
Supply sensors/ pre-actuators
Supply control pre-actuators
TSX PSY ..10
TSX DM 57 xxF
Q: General section switch,
KM: Circuit contactor-breaker,
(1): External shunt provided with the power supply module,
(2): Insulating connector bar for finding grounding faults. In this case, it is necessary to switch off the supply in order to disconnect the network from the ground,
(3): Optional use of a process power supply module,
(4): Protective fuse, (4 A, with time-delay) only necessary with the TSX PSY 3610 power supply module.
The TSX PSY 1610 power supply module is fitted during manufacture with a protective fuse located under the module and in series on the 24V input (3.5 A, 5x20 time-delay fuse).
291
Alimentations TSX PSY ... : installation
Note: If there are several PLC stations supplied by the same network, the principles of connection are identical.
TSX PSY 5520 isolated power supply module
Connecting a single-rack PLC station with a ground-referenced network:
Alternating network 100-240 V
Supply control pre-actuators
TSX PSY 5520
Supply for sensors/ pre-actuators
Q: General section switch,
KM: Circuit contactor-breaker,
(1): Insulating connector bar for finding grounding faults,
(2): Optional use of a process power supply.
Note: Protective fuse: the TSX PSY 5520 power supply modules are fitted during manufacture with a protective fuse. This fuse, in series with the 24/48V input, is located inside the module and cannot be accessed.
292
TSX DM 57 xxF
Alimentations TSX PSY ... : installation
Connecting a multi-rack PLC station with a ground-referenced network:
Alternating network 100-240 V
Supply control pre-actuators
TSX PSY 5520
Supply for sensors/ pre-actuators
Supply control pre-actuators
TSX PSY 5520
TSX DM 57 xxF
Q: General section switch,
KM: Circuit contactor-breaker,
(1): Insulating connector bar for finding grounding faults,
(2): Optional use of a process power supply.
Note: Protective fuse: the TSX PSY 5520 power supply modules are fitted during manufacture with a protective fuse. This fuse, in series with the 24/48V input, is located inside the module and cannot be accessed.
Note: If there are several PLC stations supplied by the same network, the principles of connection are identical.
293
Alimentations TSX PSY ... : installation
Sensor and pre-actuator power supply servo control
How to set up servo control
It is recommended that servo control of the different power supplies is set up in the following sequence:
Step Action
1 Switch on the power supply to the PLC and the inputs (sensors), using the contactor
KM (see diagram (See
TSX PSY 5520 isolated power supply module, p. 292 )).
2 If the PLC is in RUN mode and running on AUTO, switch on the output power supply
(pre-actuators), using the contactor KA. This is controlled by the alarm relay contact in each power supply.
Safety standards Before restarting the installation following a stop (caused by a power outage or an emergency stop), safety standards require authorization to be given by the operator.
The MANU/AUTO switch makes it possible to force outputs from a terminal, when the PLC is in STOP mode.
Example 1 PLC station supplied by alternating current:
Emergency stop
Supply pre-actuators
Run
Man.
Auto alarm relay contact alarm relay contact (1)
294
KA: contact controlled by alarm relay from supply module in AUTO run mode.
(1) When the PLC station is composed of several racks: set all the "alarm relay" contacts in series
(RAL0, RAL1, RAL2, etc.).
TSX DM 57 xxF
Example 2
Alimentations TSX PSY ... : installation
PLC station supplied by direct current:
Emergency stop
Supply pre-actuators
Run
Supply sensors
Auto alarm relay contact
Man.
alarm relay contact (1)
KA: contact controlled by alarm relay from supply module in AUTO run mode.
(1) When the PLC station is composed of several racks: set all the "alarm relay" contacts in series
(RAL0, RAL1, RAL2, etc.).
TSX DM 57 xxF
295
Alimentations TSX PSY ... : installation
Definition of protection devices at the start of a line
Introduction
Selecting a line circuit breaker
You are advised to mount a protection device, such as circuit-breaker and fuse, at the start of the line on the supply network.
The following information can be used to define the minimum caliber of the circuit breaker and the fuse for a given power supply module.
l l l
To select the caliber of the circuit breaker, the following three characteristics, which are given for each supply module, should be taken into account.
the nominal input current: I rms , signaling current: the It .
I ,
The minimum caliber for the circuit breaker should be selected as follows: l l l caliber of circuit breaker IN > the supply I max. circuit breaker I > the supply signal I ,
rms, circuit breaker It at point A on the curve > the supply It .
Illustration: characteristics provided by the circuit breaker manufacturer.
Thermal zone
Magnetic zone
Selecting the line fuse
When selecting the caliber of the line fuse, the two following characteristics, which are given for each power supply, should be taken into account: l l the nominal input current:
I
2 t.
I rms ,
The minimum caliber for the fuse is selected as follows:
296
TSX DM 57 xxF
TSX DM 57 xxF
Alimentations TSX PSY ... : installation l l fuse caliber IN > 3 x the supply I rms ,
I
2 t of the fuse > 3 x I
2 t of the power supply.
Reminder of the characteristics of I rms , signal I , It and I
2 t for each power supply module
I
TSX module
I rms at 24VDC at 48VDC
PSY 2600 PSY 5500 PSY
8500
-
at 100VAC 0.5A
at 24VAC 0.3A
-
-
1.7A
0.5A
-
-
1.4A
0.5A
I signa l (1) at 24VDC at 48VDC
-
at 100VAC 37A at 24VAC 75A
-
-
38A
38A
-
-
30A
60A
It
2 t at 24VDC at 48VDC
-
at 100VAC 0.034As
at 24VAC 0.067As
at 24VDC -
-
-
0.11As
0.11As
-
-
-
0.15As
0.15As
at 48VDC at 100VAC at 24VAC
0.63A
2 s
2.6A
2 s
4A
2 s
2A
2 s
15A
2 s
8A
2 s
-
-
-
-
0.2As
-
PSY
1610
1.5A
-
-
-
100A
-
PSY
3610
2.7A
-
-
-
150A
-
-
-
0.5As
-
-
-
12.5A
2 s 20A 2 s 50A 2 s
-
-
55A
2 s
-
-
-
-
-
7As
6As
PSY
5520
3A
1.5A
-
-
15A
15A
-
(1) Values at initial power-up and at 25°C.
297
Alimentations TSX PSY ... : installation
298
TSX DM 57 xxF
TSX PSY … supply modules: diagnostics
35
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the diagnostics of TSX PSY … supply modules .
This chapter contains the following topics:
Topic
Display on TSX PSY supply modules
Back-up battery on TSX PSY ... power supply modules
Power supply failure to rack other than rack 0
What happens after pressing the RESET button on a power supply module
Page
TSX DM 57 xxF
299
TSX PSY … supply modules: diagnostics
Display on TSX PSY supply modules
Introduction
Description
Each supply module has a display panel containing: l three LEDs (OK, BAT, 24V) for the alternating current supply modules TSX PSY l
2600/5500/8500, two LEDs (OK, BAT) for the direct current supply modules TSX PSY 1610/3610/
5520.
The following table describes the various LEDs and their functions:
Display LED Description
OK LED (green) l on when operating normally, l off when the output voltage is below the thresholds.
BAT LED (red) l off when operating normally, l on if battery is missing, flat, the wrong way round or the wrong type.
24V LED
(green) l l on when operating, off if the sensor 24V voltage delivered by the supply is no longer present.
RESET pushbutton
Pressing this button activates a sequence of service signals identical to: l l a power outage, when pressed, powering up, when released.
The application takes these actions (pressing and releasing) to mean a warm restart (See
FAST task cycle time, p. 219 ).
Sensor supply The alternating current supply modules TSX PSY 2600/5500/8500 have a built-in power supply which delivers a voltage of 24VDC for supplying the sensors.
This sensor power supply can be accessed via the module’s screw connection terminal block.
CAUTION
Parallelization
This supply module cannot be set in parallel with an external supply module.
Failure to follow this precaution can result in injury or equipment damage.
300
Note: The "24 VDC sensor supply module" output for the TSX PSY 8500 module is a VLSV-(very low safety voltage) type This ensures the user’s safety.
TSX DM 57 xxF
TSX PSY … supply modules: diagnostics
Back-up battery on TSX PSY ... power supply modules
At a Glance Each power supply module has a slot for the installation of a battery which supplies the internal RAM memory of the processors in order to save the data when the PLC is switched off.
This battery is delivered in the same packaging as the power supply module. When inserting it, you must respect the polarities.
Note: If a PCX 57 processor which can be integrated into a PC is being used, the back-up battery is built into the processor and its characteristics are the same as those described below.
Data on the backup battery
Battery characteristics: thyonile lithium chloride battery, 3.6V/0.8 Ah, 1/2AA size.
Spare part product reference: TSX PLP 01.
Period for which data is stored: the data storage time depends on two factors: l the percentage of time for which the PLC is switched off and as a result the battery is being used, l the ambient temperature when the PLC is switched off.
Table of the ambient temperatures when switched off:
Ambient temperature when inoperative
Backup time PLC off for 12 hours per day
PLC off for 1 hour per day
≤
30°C 40°C 50°C 60°C
5 years 3 years
2 years
1 year
5 years 5 years
4.5 years
4 years
Monitoring the battery status: when the power is on, it monitors the status of the battery. If there are problems, the user is informed visually by the BAT (red) LED which lights up. If this happens, the battery must be changed immediately. The
%S68 system bit gives the status of the backup battery (0 = battery OK).
Changing the battery: the battery can be changed when the power supply module is on, or immediately after switching it off. In the latter case, the time for intervention is limited.
The backup time depends on the ambient temperature. Assuming that the processor was switched on previously, the guaranteed time varies in the following way.
Ambient temperature when switching off
Backup time
20°C 30°C
2h 45mn
40°C 50°C
20mn 8mn
TSX DM 57 xxF
301
TSX PSY … supply modules: diagnostics
Power supply failure to rack other than rack 0
General
Limit of failure period
All the channels on this rack are seen as in error by the processor, but the other racks are not affected. The values of the inputs in error are no longer updated in the application memory and are reset to zero in a discrete input module, unless they have been forced, when they are maintained at the forcing value.
If the failure period is less than 10 ms for alternating current power supplies or less than 1 ms direct current power supplies, the failure is not detected by the program, which will run as normal.
302
TSX DM 57 xxF
TSX PSY … supply modules: diagnostics
What happens after pressing the RESET button on a power supply module
General The power supply module of each rack has a RESET button on its front panel, which when pressed triggers an initialization sequence of the modules on the rack it is supplying.
When this action takes place in a power supply module in the rack supporting the
TSX P57 processor (rack 0), it causes a warm restart.
Special case with the PCX 57 processor
In this case, the processor is not physically present on the rack at address 0, so pressing the RESET button on the rack power supply module does not cause the application to warm restart, nevertheless the modules present on the rack are reinitialized.
TSX DM 57 xxF
303
TSX PSY … supply modules: diagnostics
304
TSX DM 57 xxF
TSX PSY … supply modules : auxiliary functions
36
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the auxiliary functions of TSX PSY … supply modules .
This chapter contains the following topics:
Topic
Alarm relay on TSX PSY supply modules
Characteristics of the alarm relay contact
Page
TSX DM 57 xxF
305
TSX PSY … supply modules : auxiliary functions
Alarm relay on TSX PSY supply modules
Introduction The alarm relay located in each supply module has a potential free contact, which can be accessed on the module’s screw connection terminal block.
Illustration:
Connection terminal block
Ral
Alarm relay of the module situated on the rack supporting the processor
(rack 0)
When operating normally, with the PLC in RUN mode, the alarm relay is activated and its contact is closed (state 1). Whenever the application is stopped, even partially, when a "blocking" error appears, when there are incorrect output voltages or power disappears, the relay falls back and its associated contact opens (state 0).
Illustration:
PLC in RUN mode
PLC in STOP mode or faulty
Alarm relay
306
Operation alarm relay rack 0 appearance of a
PLC blocking error or incorrect voltages
Note: When a PCX 57 processor, which can be integrated into a PC, is being used, the supply module alarm relay is not managed and is therefore always open.
If this function is absolutely imperative for the proper operation of the installation, the alarm relay of the power supply module can be replaced by the use of an alarm relay output on the X Bus or the FIPIO bus. In order to achieve this, this output should be: l a relay output,
TSX DM 57 xxF
TSX PSY … supply modules : auxiliary functions l l configured with fallback to 0 (default configuration), initialized at state 1 when the application program starts executing.
When configured in this way, the relay output will behave in the same way as the alarm relay controlled by a TSX P57 processor.
Alarm relay for modules on the other racks
(1 to 7)
Once the module has been switched on and if the output voltages are correct, the alarm relay is activated and the contact is closed (state 1).
If the power disappears, or if the output voltages are incorrect, the relay falls back
(state 0).
These modes of operation allow these contacts to be used in fail-safe external circuits, as, for example, the automatic control of pre-actuator supplies, or the transmission of information.
TSX DM 57 xxF
307
TSX PSY … supply modules : auxiliary functions
Characteristics of the alarm relay contact
Characteristics Relay alarm contact.
Voltage limit when in use
Alternating current
Direct current (possible up to 34V for 1hr in every 24hrs)
Thermal current 3 A
Alternating current load Resistive load AC
12
Voltage
Power
~24V ~48V
50VAC (5) 50VAC (6)
110VAC (4)
Inductive AC14 and AC15
Voltage
Power
~24V ~48V
24VAC (4) 10VAC (10)
24VAC (8)
19..0.264 V
10...30 V
~110V
110VAC (6)
220VAC (4)
~110V
10VAC (11)
50VAC (7)
110VAC (2)
~220V
220VAC
(6)
~220V
10VAC
(11)
50VAC (9)
110VAC
(6)
220VAC
(1)
Direct current load Resistive DC12
Inductive load
DC13
(L/R=60ms)
Voltage
Power
Voltage
Power
24V (direct)
24 W (6)
40 W (3)
24V (direct)
10 W (8)
24 W (6)
1mA/5V
Response time
Type of contact
Built-in protection
Minimum switchable load
Activation
Deactivation
< 10 ms
< 10 ms
Normally open
Against overloading and short circuits
Against inductive over-voltage in
~
None, a fast-blow fuse must be fitted
Against direct current inductive over-voltage
None, compulsory installation – in parallel to the terminals of each pre-actuator - of a RC circuit or
MOV (ZNO) peak limiter, appropriate to the voltage in use
None, a discharge diode must be fitted to the terminals of each pre-actuator.
308
TSX DM 57 xxF
TSX PSY … supply modules : auxiliary functions
Insulation (test voltage) Contact/ground 2000 V rms-50/60Hz-1mn (on modules TSX PSY 2600/5500/1610/
3610/5520
3000 V rms-50/60Hz-1mn (on module TSX PSY 8500)
> 10MOhms under 500 VDC Resistance of insulation
(1) 0.1 x 7
6
operations (10) 1.5 x 10
6
operations
(2) 0.15 x 8
6
operations (10) 2 x 10
6
operations
(3) 0.3 x 9
6
operations (10) 3 x 10
6
operations
(4) 0.5 x 10
6
operations (10) 5 x 10
6
operations
(5) 0.7 x 10
6
operations (11) 10 x 10
6
operations
(6) 1 x 10
6
operations
TSX DM 57 xxF
309
TSX PSY … supply modules : auxiliary functions
310
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption and power
37
At a Glance
Aim of this
Chapter
What's in this
Chapter?
The aim of this Chapter is to provide a breakdown of power consumption and power for the selection of the power supply module.
This chapter contains the following topics:
Topic
Breakdown of power consumption for selection of the power supply module
Processor consumption breakdown
I/O module consumption breakdown
Consumption breakdown of analog/counting/movement control modules
Consumption breakdown of communication modules
Consumption breakdown (other modules)
Page
311
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption and power
Breakdown of power consumption for selection of the power supply module
General points The power needed to supply a rack depends on the type of modules installed on it.
It is therefore necessary to perform a consumption report in order to define the supply module to be mounted on the rack (standard or double format module).
Reminder of the outputs available with each power supply module
Summary table:
Total output included)(1)
(all outputs
(4b)
Standard format
TSX PSY
1610
TSX PSY
2600
30 W
(30 W)
26W
(30 W)
Double format
TSX PSY
3610
TSX PSY
5520
50 W
(55) W
50 W
(55 W)
15 W 25 W 35 W 35 W
TSX PSY
5500
50 W
(55 W)
TSX PSY 8500
77W at 60°C
85W at 55°C, 100W with a TSX FAN
35 W 75 W Power available on 5 VDC output (1 b)
Power available on 24 VR output (2 b)
15 W
Power available on 24VDC output (sensors supply on the front panel terminal block)
(3 b) not supplied
15 W
12 W
19 W not supplied
19 W not supplied
19 W
19 W not supplied
38 W
(1) The values in brackets correspond to the maximum values which can be supported for 1 minute every 10 minutes. These values should not be taken into account when calculating the breakdown of power consumption.
WARNING
Establishing the power breakdown
When the power breakdown is established, the total power consumed on each output (5 VDC, 24 VR and 24 VS) must not exceed the total output of the module.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
312
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption
Note: The TSX PSY 8500 supply module does not have a 24 VR output for supplying some modules at 24VDC. Therefore, the following provisions and preparations must be made for all racks which have this type of power supply: l the relay output modules TSX DSY 08R .
/ 16R .
and the weighing module TSX
ISP Y 100 cannot be installed on these racks, l the TSX ASY 800 analog output modules should be configured using an external power supply (maximum of 3 modules per rack).
Breakdown of power
Table of power breakdown:
2
3
Rack number:
1 Power required at 5VDC output:
4
Power required at 24VR output:
Power required at 24VS output:
Total power required:
.........x10
-3
Ax5V
.........x10
-3
Ax24V
.........x10
-3
Ax24V
=................W
=................W
=................W
=................W
WARNING
Calculated power
The calculated power should be compared with the power of the supply modules in the table below.
l power required on each output – available power on each output: 1l
1a, 2-2a, 3-3a.
sum of the power required on each output – total power available: 4-
4a.
Failure to follow this precaution can result in death, serious injury, or equipment damage.
TSX DM 57 xxF
313
TSX PSY power supply modules: breakdown of power consumption and power
Processor consumption breakdown
Table 1 This table shows the typical consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Rack number:
Module type
Processor +
PCMCIA memory card
Product references No.
Consumption in mA (typical value) (1)
At 5VDC At 24VR
TSX P57 103
TSX P57 153
TSX P57 203
TSX P57 2623
TSX P57 253
TSX P57 2823
TSX P57 303
TSX P57 3623
TSX P57 353
TSX P57 453
TSX P57 4823
Module
440
530
750
1110
820
1180
1000
1360
1060
1080
1440
Total Module Total
Total
At 24VS (2)
Module Total
(1) Module consumption is given for 100% of inputs or outputs in state 1.
(2) If using a 24V (direct) external sensor supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.
314
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption
I/O module consumption breakdown
Table 2 This table shows the typical consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Rack number:
Module type Product references No.
Consumption in mA (typical value) (1)
At 5VDC At 24VR
Module Total Module Total
At 24VS (2)
Module Total
Carried forward
Discrete input
TOR outputs
TSX DEY 08D2
TSX DEY 16A2
TSX DEY 16A3
TSX DEY 16A4
TSX DEY 16A5
TSX DEY 16D2
TSX DEY 16D3
TSX DEY 16FK
TSX DEY 32D2K
TSX DEY 32D3K
TSX DEY 64D2K
TSX DSY 08R4D
TSX DSY 08R5
TSX DSY 08R5A
TSX DSY 08S5
TSX DSY 08T2
TSX DSY 08T22
TSX DSY 08T31
TSX DSY 16R5
TSX DSY 16S4
TSX DSY 16S5
TSX DSY 16T2
TSX DSY 16T3
TSX DSY 32T2K
TSX DSY 64T2K
55
80
80
80
80
80
80
250
135
140
155
55
55
55
125
55
55
55
80
220
220
80
80
140
155
80
70
80
135
80
135
135
75
160
275
315
TSX DM 57 xxF
315
TSX PSY power supply modules: breakdown of power consumption and power
Rack number:
Discrete Inputs/
Outputs
Total
TSX DMY 28FK
TSX DMY 28RFK
300
300
75
75
(1) Module consumption is given for 100% of inputs or outputs in state 1.
(2) If using a 24V (direct) external sensor supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.
316
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption
Consumption breakdown of analog/counting/movement control modules
Table 3 This table shows the typical consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Rack number:
Module type Product references No.
Consumption in mA (typical value) (1)
At 5VDC At 24VR
Module Total Module Total
At 24VS (2)
Module Total
Carried forward
Analog
Counting
Axis control
Step by step control
Grand total
TSX AEY 414
TSX AEY 420
TSX AEY 800
TSX AEY 810
TSX AEY 1600
TSX AEY 1614
TSX AEY 410
TSX AEY 800 (3)
TSX CTY 2A
TSX CTY 2C
TSX CTY 4A
TSX CAY 21
TSX CAY 22
TSX CAY 33
TSX CAY 41
TSX CAY 42
TSX CSY 84
TSX CFY 11
TSX CFY 21
660
500
270
475
270
300
990
200
280
850
330
1100
1100
1500
1500
1500
1800
510
650
300
30
15
36
15
15
30
30
30
50
100
TSX DM 57 xxF
(1) Module consumption is given for 100% of inputs or outputs in state 1.
(2) If using a 24V (direct) external sensor supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.
(3) If using a 24VR (direct) external power supply, the consumption of 300mA on the internal 24VR should not be taken into account when selecting the rack power supply.
317
TSX PSY power supply modules: breakdown of power consumption and power
Consumption breakdown of communication modules
Table 4 This table shows the typical consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Rack number:
Module type Product references No.
Consumption in mA (typical value) (1)
At 5VDC
Module Total
At 24VR
Module Total
At 24VS (2)
Module Total
Carried forward
Communication TSX ETY 110 (3)
(4)
TSX ETY 120 (3)
(4)
TSX ETY 210 (3)
(4)
TSX ETY 4102/PORT/
5102
TSX IBY 100
TSX PBY 100
TSX SAY 100
TSX SAY 1000
TSX SCY 21601
TSX SCP 111
TSX SCP 112
TSX SCP 114
TSX FPP 10
TSX FPP 200
TSX JNP 112
TSX JNP 114
TSX MBP 100
TSX MDM 10
Grand total
800
1200
800
1200
800
1200
360
330
330
120
150
220
195
350
140
120
150
500
400
110
100
(1) Module consumption is given for 100% of inputs or outputs in state 1,
318
TSX DM 57 xxF
TSX PSY power supply modules: breakdown of power consumption
(2) if using a 24V (direct) external sensor power supply, the consumption on this output should not be taken into account when selecting the power supply for the rack,
(3) without remote power feed (RJ45),
(4) with remote power feed (AUI).
TSX DM 57 xxF
319
TSX PSY power supply modules: breakdown of power consumption and power
Consumption breakdown (other modules)
Table 5 This table shows the typical consumption of each module and can be used to calculate the consumption per rack and on each output depending on the modules installed:
Rack number:
Module type Product references No.
Consumption in mA (typical value) (1)
At 5VDC At 24VR
Module Total Module Total
Carried forward
Weighing
Emergency stop backup
TSX ISPY 100/101
TSX PAY 262
Remote X bus
TSX PAY 282
TSX REY 200
Other (devices without their own power supply which can be connected to the terminal port)
TSX P ACC01
T FTX 117 (adjust)
150
150
150
500
150
310
145
At 24VS (2)
Module Total
Grand total
(1) Module consumption is given for 100% of inputs or outputs in state 1,
(2) If using a 24V (direct) external sensor power supply, the consumption on this output should not be taken into account when selecting the power supply for the rack.
320
TSX DM 57 xxF
TSX PSY 2600 power supply module
38
Characteristics of the TSX PSY 2600 power supply module
Characteristics The TSX PSY 2600 module is a single format alternating current power supply module.
Reference TSX PSY 2600
TSX DM 57 xxF
Primary Nominal voltage (V) ~
Voltage limits (V) ~
100...240
85...264
Nominal and limit frequencies
Apparent power
Nominal current consumption: Irms
Initial power-up at 25°C (1)
I
I signal
2 t on locking
50-60/47-63Hz
50 VA
≤ 0.5A to 100V
≤
0.3A to 240V
≤
37A to 100V
≤ 75A to 240V
0.63A
2 s to 100V
2.6A
2 s to 240V
It on locking
Accepted length of micro-power outages
Integrated phase protection
0.034 As at 100V
0.067 As at 240V
≤
10ms via internal, non-accessible fuse
321
TSX PSY 2600 power supply module
Reference TSX PSY 2600
322
Secondary Total output
5VDC output
24VR output (24V relay) (2)
24VS output (24V sensor)
Protection of output from
Power dissipation
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
26W
5.1V
5A
25W
24VDC
0.6A
15W
24VDC
0.5A
12W overloading/short circuits/over-voltages
10W
Auxiliary functions
Alarm relay yes (1 contact closed, free from potential on terminal block)
Display
Back-up battery yes, via LED on front panel yes (status monitored via LED on front panel of module)
Conformity to the norms
Insulation
IEC 1131-2
Dielectric resistance (50/60Hz-
1mn)
Resistance of insulation
Primary/secondary
Primary/ground
2000 Vrms
2000 Vrms
24VDC output/ground -
Primary/secondary
Primary/ground
≥
100 MOhms
≥
100 MOhms
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.
(2) 24V direct current output for supplying relays of "relay output" modules.
TSX DM 57 xxF
TSX PSY 5500 power supply module
39
Characteristics of the TSX PSY 5500 power supply module
Characteristics The TSX PSY 5500 module is a double format alternating current power supply module.
Reference
TSX DM 57 xxF
Primary Nominal voltage (V) ~
Voltage limits (V) ~
Nominal and limit frequencies
100..120/
200..240
85..140/190..264
50-60/47-63Hz
Apparent power
Nominal current consumption: Irms
Initial power-up at 25°C (1)
I
I signal
2 t on locking
150 VA
≤ 1.7A to 100V
≤
0.5A to 240V
≤
38A to 100V
≤ 38A to 240V
4A 2 s to 100V
2A
2 s to 240V
It on locking
Accepted length of micro-power outages
Integrated phase protection
0.11 As at 100V
0.11 As at 240V
≤
10ms via internal, non-accessible fuse
323
TSX PSY 5500 power supply module
Reference
324
Secondary Total output
5VDC output
24VR output (24V relay) (2)
24VS output (24V sensor)
Protection of output from
Power dissipation
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
50W
5.1V
7A
35W
24VCC
0.8A
19W
24VCC
0.8A
19W overloading/short circuits/over-voltages
20W
Auxiliary functions
Alarm relay yes (1 contact closed, free from potential on terminal block)
Display
Back-up battery yes, via LED on front panel yes (status monitored via LED on front panel of module)
Conformity to the norms
Insulation
IEC 1131-2
Dielectric resistance (50/60Hz-
1mn)
Resistance of insulation
Primary/secondary
Primary/ground
2000 Vrms
2000 Vrms
24VDC output/ground -
Primary/secondary
Primary/ground
≥ 100 MOhms
≥
100 MOhms
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.
(2) 24V direct current output for supplying relays of "relay output" modules.
TSX DM 57 xxF
TSX PSY 8500 power supply module
40
Characteristics of the TSX PSY 8500 power supply module
Characteristics The TSX PSY 8500 module is a double format alternating current power supply module.
Reference
TSX DM 57 xxF
Primary Nominal voltage (V) ~
Voltage limits (V) ~
Nominal and limit frequencies
100..120/
200..240
85..140/170..264
50-60/47-63Hz
Apparent power
Nominal current consumption: Irms
Initial power-up at 25°C (1)
I
I signal
2 t on locking
150 VA
≤
1.4A to 100V
≤
0.5A to 240V
≤ 30A to 100V
≤
60A to 240V
15A
2 s to 100V
8A
2 s to 240V
It on locking
0.15 As at 100V
0.15 As at 240V
Accepted length of micro-power outages
Integrated phase protection
≤ 10ms via internal, non-accessible fuse
325
TSX PSY 8500 power supply module
Reference
326
Secondary Total output
5VDC output
24VR output (24V relay) (3)
24VS output (24V sensor)
Protection of output from
Power dissipation
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
Nominal current
Power (typical)
77/85/100W (2)
5.1V
15A
75W not supplied not supplied not supplied
24VDC
1.6A
38W overloading/short circuits/over-voltages
20W
Auxiliary functions
Alarm relay yes (1 contact closed, free from potential on terminal block)
Display
Back-up battery yes, via LED on front panel yes (status monitored via LED on front panel of module)
Conformity to the norms
Insulation
IEC 1131-2
Dielectric resistance (50/60Hz-
1mn)
Resistance of insulation
Primary/secondary
Primary/ground
3000 Vrms
3000 Vrms
24VDC output/ground 500 Vrms
Primary/secondary
Primary/ground
≥
100 MOhms
≥
100 MOhms
(1) These values should be taken into account when starting up several devices at the same time, or for dimensioning the protection systems.
(2) 77W at 60°C, 85W at 55°C, 100W at 55°C, if the rack is fitted with ventilation modules.
(3) 24V direct current output for supplying relays of "relay output" modules.
TSX DM 57 xxF
TSX PSY 1610 power supply module
41
Characteristics of the TSX PSY 1610 power supply module
Characteristics The TSX PSY 1610 module is a single format non-isolated direct current power supply module.
Reference TSX PSY 1610
TSX DM 57 xxF
Primary Nominal voltage (not isolated) 24 VDC
Voltage limits (including ripple) (1) (possible up to 34V for 1hr in every 24hrs)
19.2 to 30 VDC
Nominal input current: Irms at 24VDC
Initial power-up at 25°C (2) I signal
≤
1.5 A
≤
100A at 24V DC
I 2 t on locking
12.5 A
It on locking
0.2 As
Accepted length of micro-power outages
Integrated input protection
≤
1ms via 5x20 time delay fuse, 3.5A
2 s
327
TSX PSY 1610 power supply module
Reference TSX PSY 1610
Secondary Total output (typical)
5VDC output Nominal voltage:
Nominal current
Power (typical)
24VR output (24VDC relay) (3) Nominal voltage:
30 W
5V
3A
15W
Built-in output protection against (4)
Nominal current
Power (typical)
Overloading
Short circuits
Over-voltage
U network – 0.6V
0.6 A
15 W yes yes yes
10W Power dissipation
Auxiliary functions
Alarm relay
Display yes (1 contact closed, free from potential on terminal block) yes, via LED on front panel
Back-up battery yes (status monitored via LED on front panel of module)
Conformity to the norms IEC1131-2
(1) With the supply of "relay output" modules, the limit range is reduced to
21.6V26.4V.
(2) These values should be taken into account when starting up several devices at the same time, and for dimensioning the protection systems.
(3) 24V direct current output for supplying relays of "relay output" modules.
(4) The 24VR output voltage, which cannot be accessed by the user, is protected by a fuse which is located under the module (5x20, 4A, Medium type).
328
TSX DM 57 xxF
TSX PSY 3610 power supply module
42
Characteristics of the TSX PSY 3610 power supply module
Characteristics The TSX PSY 3610 module is a double format non-insulated direct current supply module.
Reference
TSX DM 57 xxF
Primary Nominal voltage 24 VDC
Voltage limits (including ripple) (1) (possible up to 34V for 1hr in every 24hrs)
19.2 to 30 VDC
Nominal input current: Irms at 24VDC
Initial power-up at 25°C (2) I signal
≤
2.7 A
≤ 150A at 24V DC
20 A
2 s I
2 t on locking
It on locking
0.5 As
Accepted length of micro-power outages
Integrated input protection no
≤
1ms
329
TSX PSY 3610 power supply module
Reference
Secondary Total output (typical)
5VDC output Nominal voltage:
Nominal current
Power (typical)
Nominal voltage:
50 W
5.1V
7A
35W
24VR output (24V relay) (3)
Nominal current
Power (typical)
Overloading
Short circuits
Over-voltage
U network – 0.6V
0.8 A
19 W yes Built-in output protection against
(4) yes yes
15W Power dissipation
Auxiliary functions
Alarm relay
Display yes (1 contact closed, free from potential on terminal block) yes, via LED on front panel
Back-up battery yes (status monitored via LED on front panel of module)
Conformity to the norms IEC1131-2
(1) With the supply of "relay output" modules, the limit range is reduced to
21.6V26.4V.
(2) These values should be taken into account when starting up several devices at the same time, and for dimensioning the protection systems.
(3) 24V direct current output for supplying relays of "relay output" modules.
(4) The 24VR output voltage, which cannot be accessed by the user, is protected by a fuse which is located under the module (5x20, 4A, Medium type).
330
TSX DM 57 xxF
TSX PSY 5520 power supply module
43
Characteristics of the TSX PSY 5520 power supply module
Characteristics The TSX PSY 5520 module is a double format insulated direct current power supply module.
Reference
TSX DM 57 xxF
Primary Nominal voltage
Voltage limits (including ripple)
Nominal input current: Irms
Initial power-up at 25°C (1)
I
I signal
2 t on locking
24..0.48 VDC
19.2 to 60VDC
≤ 3 A at 24V DC
≤
1.5A at 48V DC
≤
15A at 24V DC
≤ 15 A at 48V DC
50 A 2 s at 24VDC
55 A
2 s at 48VDC
It on locking
Accepted length of micro-power outages
Built-in protection of + input
7 As at 24VDC
6 As at 48VDC
≤
1ms by internal, non-accessible fuse module
331
TSX PSY 5520 power supply module
Reference
332
Secondary Total output (typical)
5VDC output Nominal voltage:
Nominal current
Power (typical)
24VR output (24VDC relay) (2) Nominal voltage:
50 W
5.1V
7A
35W
Nominal current
Power (typical)
Built-in output protection against Overloading
Short circuits
Over-voltage
24 V
0.8 A
19 W yes
Power dissipation
Auxiliary functions
Alarm relay
Display yes (1 contact closed, free from potential on terminal block) yes, via LED on front panel yes yes
20W
Back-up battery yes (status monitored via LED on front panel of module)
Conformity to the norms IEC1131-2
Insulation Dielectric resistance
Resistance of insulation primary/secondary primary/ground primary/secondary primary/ground
2000 Vrms-50/
60Hz-1mn
2000 Vrms-50/
60Hz-1mn
≥
10 MOhms
≥ 10 MOhms
(1) These values should be taken into account when starting up several devices at the same time, and for dimensioning the protection systems.
(2) 24VDC output for supplying the relays of the "relay output" modules.
TSX DM 57 xxF
Process and AS-i supply
VI
At a Glance
Aim of this Part
What's in this
Part?
This Part describes Process and AS-i supply and their installation.
This part contains the following chapters:
Chapter
44
45
46
47
48
Chapter Name
Process and AS-i supply: introduction
Process and AS-i suppliers: installation
Process supply modules: connections
Connecting AS-i supply modules
Process and AS-i supply module characteristics
Page
TSX DM 57 xxF
333
Process and AS-i supply
334
TSX DM 57 xxF
Process and AS-i supply: introduction
44
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter introduces Process and AS-i supply.
This chapter contains the following topics:
Topic
General introduction to Process and AS-i power supply modules
Physical description of TBX SUP 10 supply block
Physical description of the TSX SUP 1011 supply module
Physical description of TSX 1021/1051 supply modules
Physical description of the TSX SUP A02 supply module
Description of TSX SUP 1101/A05 supply blocks
Physical description of the support board
Process supply: auxiliary functions
AS-i supply module: dedicated features
Page
TSX DM 57 xxF
335
Process and AS-i supply: introduction
General introduction to Process and AS-i power supply modules
General A wide range of power supply units and modules is offered to meet your needs in the best possible way: l TBX SUP 10 and TSX SUP 1..1 process power supply units and modules, designed to supply 24 VDC to a PLC system periphery, and driven by PLCs (TSX
Micro and Premium). This periphery being composed of sensors, pre-actuators, encoders, operator dialog terminals, regulators, LEDs, push-buttons, pneumatic actuators, etc. . This 24 V power supply can be delivered using a 100/240 V, 50/ l
60 Hz AC network.
The power supply modules TBX SUP 10 and TSX SUP 1011 can also be connected to a 125 VDC network.
The AS-i power supply units and modules TSX SUP A02 and A05 designed to supply 30 VDC to the components connected to an AS-i field bus. This power supply is distributed over the same wires as those used for data exchange.
The attachment mode for these products has been specially designed to respond to the specific mounting distances and specifications of TSX Micro and TSX Premium
PLCs, and TBX products.
l l
All the products are mounted: on a Telequick AM1-PA mounting plate, on a central DIN rail AM1-DP200/DE200, except for the high-power power supply blocks TSX SUP 1101 and TSX SUP A05.
336
TSX DM 57 xxF
Physical description of TBX SUP 10 supply block
Illustration Diagram and numbers:
Process and AS-i supply: introduction
Number table
3
4
1
2
The following table shows the numbers and their corresponding descriptions from the diagram above:
2
3
Numbers
1
4
Description
LED showing power-up of module.
Screw terminal block for supply voltage wiring.
Identification label for the wire terminals.
Wings for fixing the module.
TSX DM 57 xxF
337
Process and AS-i supply: introduction
Physical description of the TSX SUP 1011 supply module
Illustration Diagram and numbers:
Number table
338
The following table shows the numbers and their corresponding descriptions from the diagram above:
5
6
3
4
Numbers Description
1 Support board for fixing the supply module directly onto the AM1-DE200 / DP200
DIN mounting track or the AM1-PA Telequick perforated board.
2 Display block with: l a 24 V LED (green): lit if the established internal and output voltages are correct, l a LSH LED (orange) "power optimization mode": lit if the power supply is running in parallelization mode with power optimization.
Flap for protecting the terminal block.
Screw terminal block for connection: l l to the AC/DC supply network, to 24 VDC output.
Hole for the cable-tightening clip to go through.
"NOR/LSH" switch placed at the back of the module to control the power optimization system.
l l
NOR position: normal operation without power optimization (default position),
LSH position: operation with power optimization with supply running in parallel.
Note: Access to the switch requires the module to be removed from the support board.
TSX DM 57 xxF
Process and AS-i supply: introduction
Physical description of TSX 1021/1051 supply modules
Illustration Diagram and numbers:
1
2
3
Number table
TSX DM 57 xxF
4
5
6
7
The following table shows the numbers and their corresponding descriptions from the diagram above:
5
6
3
4
Numbers Description
1 Support board for fixing the supply module directly onto the AM1-DE200 / DP200
DIN mounting track or the AM1-PA Telequick perforated board.
2 Display block with: l l a 24 V LED (green): lit if the internal and output voltages are correct, a LSH LED (orange) only on TSX SUP 1021 "power optimization mode": lit if the power supply is running in parallelization mode with power optimization.
Flap for protecting the terminal block.
Screw terminal block for connection: l l to the AC/DC supply network, to 24 VDC output.
Hole for the cable-tightening clip to go through.
7
110/220 V voltage selector. On delivery, the selector is set at 220.
"NOR/LSH" switch placed at the back of the module to control the power optimization system. This switch is only present on the TSX SUP 1021 module.
l l
NOR position: normal operation without power optimization (default position),
LSH position: operation with power optimization with supply running in parallel.
Note: Access to the switch requires the module to be removed from the support board.
339
Process and AS-i supply: introduction
Physical description of the TSX SUP A02 supply module
Illustration Diagram and numbers:
Number table The following table shows the numbers and their corresponding descriptions from the diagram above:
5
6
3
4
Numbers
1
2
Description
Support board for fixing the supply module directly onto the AM1-DE200 /
DP200 DIN mounting rail or the AM1-PA Telequick board.
Display block with: l an AS-i LED (green): lit if the internal and output voltages are correct,
Flap for protecting the terminal block.
Screw terminal block for connection: l l to an alternating supply network, from AS-i 30 VDC output.
Hole for the cable-tightening clip to go through.
110/220 V voltage selector. On delivery, the selector is set at 220.
340
TSX DM 57 xxF
Description of TSX SUP 1101/A05 supply blocks
Illustration Diagram and numbers:
Process and AS-i supply: introduction
Number table
3
4
5
The following table shows the numbers and their corresponding descriptions from the diagram above:
6
7
Numbers
1
2
Description
Display block with an ON LED (orange): lit if power supply is running.
Display block with: l l a 24 V LED (green): lit if 24 VDC output voltage is present and correct, an AS-i LED (green): lit if the AS-i 30 VDC output voltage is present and correct. This LED is only present on the TSX SUP A05.
Flap for protecting terminal blocks.
Screw terminal block for connection to alternating supply network.
Screw terminal block for connecting AS-i 24 VDC and 30 VDC output voltage to TSX SUP A05.
Holes for the cable-tightening clip to go through.
Four fixing holes for M6 screws.
TSX DM 57 xxF
341
Process and AS-i supply: introduction
Physical description of the support board
Introduction
Illustration
Each TSX SUP 10.1 and TSX SUP A02 supply module is delivered mounted on a support board. This is used to fix the supply module: the DIN AM1-DE200 or AM1-
DP200 profile, or to a Telequick AM1-PA perforated mounting plate.
Each support board can take: either a TSX SUP 1021, TSX SUP 1051 or TSX SUP
A02 module, or one or two TSX SUP 1011 modules.
Diagram and numbers:
Information
Table
The following table shows the numbers and their corresponding descriptions from the diagram above:
3
4
Number
1
2
Description
Three 5.5 mm diameter holes for fixing the board onto a panel or an AM1-PA perforated board with a mounting distance of 140 mm (mounting distance for
TSX 37 PLCs).
Four 6.5 mm diameter holes for fixing the board onto a panel or an AM1-PA perforated board with a mounting distance of 88.9 mm (mounting distance for
TSX 57 PLCs).
Two M4 holes for fixing TSX SUP 1011/1021/1051/A02 supply module(s).
Windows designed to ink pins situated at the bottom and at the back of the module.
342
TSX DM 57 xxF
Process and AS-i supply: introduction
Note:
• each of these supply modules can also be mounted on a TSX RKY••• rack in place of another module, except in position PS. This must only be used by a TSX PSY••• supply module for supplying rack modules.
• the following operations require the module to be removed from the support board:
- positioning the "NOR/LSH" switch onto "LSH",
- mounting the board onto a panel or AM1-PA perforated board,
- mounting the module onto a TSX RKY••• rack.
TSX DM 57 xxF
343
Process and AS-i supply: introduction
Process supply: auxiliary functions
Parallelization mode with power optimization
The aim of parallelization is to use two modules with the same product reference in order to provide an output current which is greater than the maximum allowed by a single supply. The total current is the sum of the currents provided by all the supplies put together.
Power optimization is a system within the supply which is designed to distribute currents equally between parallel supplies. The resulting advantage is that the life of products is significantly extended, linked with distributed power consumption.
Dedicated supply features:
TSX SUP 1011/1021 supply
Power optimization mode is obtained by positioning the NOR/LSH switch at the rear of the modules onto LSH. To access the switch, the support board must be removed. When the orange LED (LSH) is lit, the mode is in operation.
The current provided by two parallel supplies is limited to: l l
2A with 2 TSX SUP 1011 suppliers,
4A with 2 TSX SUP 1021 suppliers.
Using this mode means output voltage can vary slightly: 24V + or - 5% instead 24 V + or - 3% in normal mode.
When sharing loads, the power imbalance can reach a maximum of
25%.
A specific connection (See Connection of TSX SUP 1011/1021
power supplies, p. 358 ) is required for these types of modules.
TSX SUP 1051/1101 supply
Power optimization mode does not require a switch on these supply modules. A specific connection must be made for the TSX SUP 1051
(See
Connection of TSX SUP 1051 power supplies, p. 360 ) module
and the TSX SUP 1101 (See Connection of TSX SUP 1101 power
The maximum current provided by two parallel supplies is limited to: l l
10A with 2 TSX SUP 1051 suppliers,
20A with 2 TSX SUP 1101 suppliers.
Using this mode will lead to no loss of output voltage:
When sharing loads, the power imbalance can reach a maximum of
15%.
344
TSX DM 57 xxF
Process and AS-i supply: introduction
Redundancy/
Safety on TSX
SUP 1011/1021 suppliers
Principle:
To ensure that the currents required for the application are available, even in the event of failure of one of the suppliers.
To do this, the two suppliers are run in parallel by setting up the necessary connections (see
Connection of TSX SUP 1011/1021 power supplies, p. 358).
The suppliers are configured in power optimization mode.
Example: provide 1A with redundancy from 2 TSX SUP 1011 suppliers.
Fuse
Discrete inputs 1 and 2 on the PLC indicate the failure of one or other of the power supplies.
Load
Note: TSX SUP 1051 and 1101 suppliers are not equipped with a serial diode, which is required for the redundancy function.
TSX DM 57 xxF
345
Process and AS-i supply: introduction
AS-i supply module: dedicated features
General The simultaneous transmission of information and power down the same cable means that data transmission needs to be filtered in relation to supply.
This is why AS-i supply module has a built-in decoupling filter which supports the maximum direct current provided by the power supply. A standardized impedance is introduced into the power supply in relation to the frequency of information transmission.
346
TSX DM 57 xxF
Process and AS-i suppliers: installation
45
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the installation of Process and AS-i supply modules.
This chapter contains the following topics:
Topic
TBX SUP 10 dimensions/mounting/connections
Dimensions/mounting Process and AS-i supply modules
TSX SUP 1101/A05 supply block dimensions/mounting
Summary of fixing methods
Page
TSX DM 57 xxF
347
Process and AS-i suppliers: installation
TBX SUP 10 dimensions/mounting/connections
Dimensions/ mounting
Illustration:
Connections
The TBX SUP 10 supply block must be mounted in an upright position to allow for the best possible natural air convection within the block.
It can be mounted on a panel, an AM1-PA Telequick perforated board or AM1-
DE200 / DP200 mounting rail.
Illustration:
348
(1) External protection fuse on phase: 1A time delay 250V if single supply block.
Note: Primary: if the module is supplied with a 100/240V alternating current, the phase and the neutral wire must be taken into account when wiring. On the other hand, if the module is supplied with a 125 V direct current, polarities do not need to be taken into account.
Secondary: the terminal, with 0V potential, must be connected to the ground as soon as the supply module starts to provide output.
TSX DM 57 xxF
Process and AS-i suppliers: installation
DANGER
Personnel safety
For personnel safety, the module ground terminal must be connected to the protective ground with a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
TSX DM 57 xxF
349
Process and AS-i suppliers: installation
Dimensions/mounting Process and AS-i supply modules
At a Glance Each power supply module is delivered with a support which allows it to be mounted directly on a DIN (AM1-D••••) mounting rail or TELEQUICK (AM1-PA) mounting plate. l l
The support is able to receive:
1 or 2 TSX SUP 1011 power supply modules,
1 TSX SUP 1021/1051/A02 power supply module.
Note: When using the TELEQUICK mounting plate, it is necessary to remove the module.
1 module
TSX SUP 1011
2 modules
TSX SUP 1011
1 module
TSX SUP 1021/
1051/A02
350
TSX DM 57 xxF
Dimensions
Process and AS-i suppliers: installation
The illustration below shows the dimensions of the modules and support and the overall dimensions for each type of mounting system.
SUP 1011
SUP 1021/
1051/A02
Mounting support
Mounting on an
AM1-D mounting rail
Dimensions in millimeters
TSX SUP 1011/1021/1051/A02 power supply modules can be mounted in different ways:
Mounting on an AM1-DE200 or AM1-DP200 mounting rail or on an AM1-PA board
Each supply module is delivered fixed to a support which can be mounted in this way.
TSX DM 57 xxF
(1) 147.2mm (AM1-DE200)
139.7mm (AM1-DP200)
Carry out the following steps:
Step
1
2
3
Action
Remove the module from its support.
Mount the support, using 3 M6x25 screws, onto the AM1-D••• mounting rails equipped with AF1-CF56 1/4 turn sliding nuts.
Mount the module on its support.
351
Process and AS-i suppliers: installation
Mounting on an
AM1-PA board
(2) 136.7 mm (AM1-PA)
Carry out the following steps:
Step
1
2
3
Action
Remove the module from its support.
Mount the support onto the AM1-PA board.
Mount the module on its support.
Removing the module
Carry out the following steps:
Step
1
2
Action
Loosen the screw on the upper part of the module in order to separate it from the support.
Rotate the module in order to free the lower pins from the support.
Illustration:
Support
Support
352
TSX DM 57 xxF
Process and AS-i suppliers: installation
Mounting on an
AM1-ED••• mounting rail
Carry out the following steps:
Step
1
2
3
Action
Remove the module from its support.
Mount the support, using 3 M6x25 screws, onto the AM1-ED••• mounting rails equipped with AF1-CF56 1/4 turn sliding nuts.
Mount the module on its support.
Mounting on a
TSX RKY••• rack
TSX SUP 1011/1021/1051/A02 power supply modules can be mounted in any position on the TSX RKY•• rack, except for the PS position reserved for the power supply module of the rack. In this case, the support is not used and must be removed.
The support delivered with the supply module is not used and must be removed; the module is in this case mounted in the same way as the other modules (e.g.: processor (see
How to mount processor modules, p. 154).
Note: The power supply module of the TSX PSY••• rack must be in the PS position in order to supply power to the modules in the rack.
TSX DM 57 xxF
353
Process and AS-i suppliers: installation
TSX SUP 1101/A05 supply block dimensions/mounting
Introduction
Mounting on a panel
TSX SUP 1101 and TSX SUP A05 supply blocks can be mounted on a panel, an
AM1-PA board, or DIN rail.
Screw-hole layout (dimensions in millimeters):
4 fixing holes (1)
(1) The diameter of the fixing holes must be sufficient to take M6 screws.
Mounting on an
AM1-PA
Telequick mounting grid
Fix the supply block with 4 M6 x 25 screws + washers and AF1-EA6 clips nuts
(dimensions in millimeters):
354
TSX DM 57 xxF
Process and AS-i suppliers: installation
Mounting on 35 mm wide DIN mounting rail
Fix the supply block using 4 M6 x 25 screws + washers and AF1-CF6
1
/
4
turn sliding nuts (dimensions in millimeters):
TSX DM 57 xxF
355
Process and AS-i suppliers: installation
Summary of fixing methods
Summary table of mounting methods
The following table lists a summary of the different methods available for mounting
Process and AS-i supply modules:
Supply module product reference
AM1-PA
Telequick board
AM1-DE200/
DP200 central
DIN rail
AM1-ED DIN rail with 88.9 mm spacing (TSX 57
PLC)
X
X
TSX 57 rack
TSX RKY••
TBX SUP
10
TSX SUP
1011
X
X
X
X
TSX SUP
1021
X
X
X
X
TSX SUP
1051
X
X
X
X
TSX SUP
1101
X
X
TSX SUP
A02
X
X
X
X
TSX SUP
A05
X
X
356
TSX DM 57 xxF
Process supply modules: connections
46
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the connection of Process supply modules.
This chapter contains the following topics:
Topic
Connection of TSX SUP 1011/1021 power supplies
Connection of TSX SUP 1051 power supplies
Connection of TSX SUP 1101 power supplies
Page
TSX DM 57 xxF
357
Process and AS-i supply modules: connections
Connection of TSX SUP 1011/1021 power supplies
Illustration Connection diagram:
Normal connection
Parallelization
Module 1
Module 2
Fu=External safety fuse
on phase (Fu): 250 V 4A time delay.
(1) 100...240VAC on TSX SUP 1011
100...120/200..240VAC on TSX SUP 1021
(2) 125 VDC, only on TSX SUP 1011.
358
TSX DM 57 xxF
Process and AS-i supply modules: connections
Connection rules Primary: if the module is supplied with a 100/240V AC power supply, it is necessary to observe wiring requirements for the phase and neutral when connecting the module. However, if the module is powered by a 125 VDC supply, it is not necessary to respect the polarities.
l an operating voltage
≥
600 V AC with a cross-section of 1.5 mm
2
for connection to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module must be connected to the protective earth using a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
The power supply terminal is protected by a flap which allows access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cable-clip.
Secondary: to comply with isolation requirements for a 24 V SELV isolated voltage, the following wiring is used: l an operating voltage
≥
300 V AC with a cross-section of 2.5 mm
2
for the 24 V outputs and the ground.
TSX DM 57 xxF
359
Process and AS-i supply modules: connections
Connection of TSX SUP 1051 power supplies
Illustration Connection diagram:
Normal connection Parallelization
Module 1
Fu=External safety fuse on phase
(Fu): 250V 4A time delay
Module 2
360
TSX DM 57 xxF
Process and AS-i supply modules: connections
Connection rules Primary: observe the rules concerning phase and neutral when wiring.
l an operating voltage
≥
600 VAC with a cross-section of 1.5 mm
2
for connection to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module must be connected to the protective earth using a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
The power supply terminal is protected by a flap which allows access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cable-clip.
Secondary: to comply with isolation requirements for a 24 V SELV isolated voltage, the following wiring is used: l an operating voltage
≥
300 V AC with a cross-section of 2.5 mm
2
for the 24 V outputs and the ground.
TSX DM 57 xxF
361
Process and AS-i supply modules: connections
Connection of TSX SUP 1101 power supplies
Illustration 1 Normal connection diagram: input terminal output terminal
AC network connection
200..240V
AC network connection
100..120V
24 VDC output connection.
362
TSX DM 57 xxF
Illustration 2
Process and AS-i supply modules: connections
Parallel connection diagram (parallelization): input terminals output terminals
Module 1
Module 2
(1) Connection for a 100...120 VAC power supply.
(2) External safety fuse on phase (Fu): 250 V 6.3A time delay.
TSX DM 57 xxF
363
Process and AS-i supply modules: connections
Connection rules Primary: Observe the rules concerning phase and neutral when wiring.
l an operating voltage
≥
600 V AC with a cross-section of 1.5mm
2
or 2.5mm
2
for connection to the mains,
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module must be connected to the protective earth using a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
The power supply terminal is protected by a flap which allows access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cable-clip.
Secondary: To comply with isolation requirements for a 24 V SELV isolated voltage, the following wiring is used: l l an operating voltage
≥
300 V AC with a cross-section of 2.5 mm
2
for the 24 V outputs and the ground.
Wire the two 24V terminals in parallel, or distribute the load over the two 24V outputs when the total current to be supplied is greater than 5A.
364
TSX DM 57 xxF
Connecting AS-i supply modules
47
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter deals with the connection of AS-i supply modules.
This chapter contains the following topics:
Topic
Connection of TSX SUP A02 power supply modules
Connecting TSX SUP A05 supply modules
General precautions
Page
TSX DM 57 xxF
365
Connecting AS-i supply modules
Connection of TSX SUP A02 power supply modules
Illustration Connection diagram:
(1) Shielded AS-i cable screen if environment is disturbed.
Fu=External safety fuse on phase (Fu): 250 V 4A time delay.
Connection synoptic
The TSX SUP A02 power supply module is designed to supply the AS-i bus, and the connected slaves (30 VDC/2.4A).
AS-i Master
366
TSX DM 57 xxF
Connecting AS-i supply modules
Connection rules Primary: observe the rules concerning phase and neutral when wiring.
DANGER
Safety of personnel
To ensure the safety of personnel, the ground terminal of the module must be connected to the protective earth using a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
The power supply terminal is protected by a flap which allows access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cable-clip.
To comply with isolation requirements for a 24 V SELV isolated voltage, the following wiring is used: l an operating voltage
≥
600 VAC with a cross-section of 1.5 mm
2
for connection to the mains, l an operating voltage
≥
300 VAC with a cross-section of 2.5 mm
2
for the 24 V outputs and the ground.
It is necessary to use a shielded cable for the AS-i bus only in cases where the installation is subject to very high levels of disturbance in terms of EMC (Electro
Magnetic Compatibility).
TSX DM 57 xxF
367
Connecting AS-i supply modules
Connecting TSX SUP A05 supply modules
Illustration Connection diagram:
Input terminal
(1)
Output terminal
(3)
Connection overview
Connection to alternating network
200..240 V
Connection to an alternating network
100...120 V
Direct output connection 24V and 30 V AS-i
(1) Connection if supply is from 100120V alternating current network.
(2) External protection fuse on phase (Fu): 6.3A time delay 250 V.
(3) Shielded AS-i cable screen in case of disrupted surroundings.
The TSX SUP A05 supply module is designed to supply the AS-i bus, including the slaves which are connected to it (30V/5A output). It also has an auxiliary supply (24
VDC/7A) for sensors/actuators which consume large amounts of current. For this, a black AS-i ribbon cable is used.
Principle diagram:
AS-i master
368
TSX DM 57 xxF
Rules of connection
Connecting AS-i supply modules
Primary: observe the rules concerning phase and neutral when wiring.
l an operating voltage
≥
600 V AC with a cross-section of 1.5mm
2
or 2.5mm
2
for connection to the mains,
DANGER
Safety of personnel
For personnel safety, the module ground terminal must be connected to the protective ground with a green/yellow wire.
Failure to follow this precaution will result in death, serious injury, or equipment damage.
The "AC power supply network" and "24V and 30 V DC output" AS-i terminals are protected by a flap allowing access to the wiring terminals. The wires come vertically out of the power supply at its base. These wires can be kept in place with a cableclip.
Secondary: to comply with isolation requirements for a 24 V SELV isolated voltage, the following wiring is used: l an operating voltage
≥
300 V AC with a cross-section of 2.5mm
2
for the 24 V outputs and the ground, l connect the two 24V terminals in parallel, or distribute the load over the two 24V outputs when the total current to be provided is greater than 5A.
Using a shielded cable for the AS-i bus is only necessary if the installation is overly disrupted in terms of EMC (Electro Magnetic Compatibility).
Given the large current that this supply module provides, its position on the bus is very important.
If the supply module is placed at one of the ends of the bus, it will provide a nominal current (e.g. 5A) for the whole bus. The fall in voltage at the end of the bus is therefore proportional to the 5A.
If it is positioned in the middle of the bus, the voltage drop at the ends is proportional to only 2.5A, assuming that the consumption for both sections of the bus is the same.
TSX DM 57 xxF
369
Connecting AS-i supply modules
Supply
AS-i
2.5 A 2.5 A
If there is no slave which consumes large amounts of power, it would be better to place the supply module in the middle of the installation. Conversely, if the installation has one or several large power consumers, it would be wise to place the supply module close to them.
Note: Where there are large power consumer actuators (contactor, solenoid coils etc.) the TSX SUP A05 supply module can provide the auxiliary 24 VDC, insulated from the AS-i line.
370
TSX DM 57 xxF
Connecting AS-i supply modules
General precautions
Introduction
Important
Rule 1
Rule 2
While installing the yellow AS-i cable, it is essential to place it in a cable track which is separate from the power cables. It is also advisable to place it flat and not twisted.
This will help make the two AS-i cable wires as symmetrical as possible.
Installing the AS-i cable on a surface connected to the electric potential of the machine (for example, the housing) complies with the requirements of the EMC
(Electro Magnetic Compatibility) directive.
The end of the cable, or the ends in the case of a bus with a star-formation , must l l be protected either: by connecting it (them) to a T-derivation, by not allowing them to come out of their last connection point.
It is important to distribute power effectively on the AS-i bus, so that each device on the bus is supplied with sufficient voltage to enable it to operate properly. To do this, certain rules must be followed.
Select the caliber of the supply module adapted to the total consumption of the ASi segment. Available calibers are 2.4A (TSX SUP A02) and 5A (TSX SUP A05).
A caliber of 2.4A is generally sufficient based on an average consumption of 65mA per slave for a segment made up of a maximum of 31 slaves.
To minimize the effect of voltage falls and reduce the cost of the cable, you must determine the best position of the supply module on the bus, as well as the minimum size of cable appropriate for distributing power.
The voltage fall between the master and the last slave on the bus must not exceed
3V. For that purpose, the table below gives the essential points for selecting the cross-sectional measurement of the AS-i cable.
Table of characteristics:
Cross-section measurement of AS-i cable
Linear resistance
0.75 mm
2
1.5 mm
2
Voltage fall for 1A over 100 meters
52 milli Ohms/meter 27 milli Ohms/ meter
5.2V
2.7V
2.5 mm
2
16 milli Ohms/ meter
1.6V
TSX DM 57 xxF
371
Connecting AS-i supply modules
The cable which can be used for most applications is the cable with a cross-section of 1.5 mm
2
. This is the standard AS-i bus model (the cable is offered in the
SCHNEIDER catalog).
Smaller cables can be used when sensors consume very little power.
Note: The maximum length of all the segments making up the AS-i bus without a relay is 100 meters. The lengths of cables which link a slave to a passive distribution box must be taken into account.
372
TSX DM 57 xxF
Process and AS-i supply module characteristics
48
At a Glance
Aim of this
Chapter
What's in this
Chapter?
This Chapter presents the different electrical characteristics of Process and AS-i supply modules in a table.
This chapter contains the following topics:
Topic
Electrical characteristics of process supply modules: TBX SUP 10 and TSX
SUP 1011
Electrical characteristics of process supply modules: TSX SUP 1021/1051/
1101
Electrical characteristics of AS-i supply modules: TSX SUP A02/A05
Physical environmental characteristics
Page
373
TSX DM 57 xxF
Process and AS-i supply module characteristics
Electrical characteristics of process supply modules: TBX SUP 10 and
TSX SUP 1011
Table of
Characteristics
The following table describes the electrical characteristics of supply modules: TBX
SUP 10 and TSX SUP 1011:
Process supply TBX SUP 10 24V/1A TSX SUP 1011 24V/
1A
374
Primary
Nominal input voltage
Input limit voltage
Network frequency
Nominal input current (U=100V)
Maximum call current (1) to 100 V to 240 V
Maximum It on trigger (1)
Maximum I trigger (1)
2 t on to 100 V to 240 V to 100 V to 240 V
Power factor
Harmonic (3)
Full load efficiency
Secondary
Output (2)
Nominal output current (2)
V
V
Hz
On
On
On
As
As
A
2 s
A 2 s
% alternating 100240 direct 125 alternating 90264 direct 88156
47...63
0.4
3
30
0.03
0.07
2 alternating 100240 direct 125 alternating 85264 direct 105156
47...63/360...440
0.4
37
75
0.034
0.067
0.63
2 2.6
0.6
0.6
10% (Phi=0°and 180°) 10% (Phi=0°and
180°)
>75 >75
W
On
24
1
26(30)
1.1
TSX DM 57 xxF
TSX DM 57 xxF
Process supply
Process and AS-i supply module characteristics
TBX SUP 10 24V/1A TSX SUP 1011 24V/
1A
Output voltage/ accuracy at 25°C
Residual ripple (peak to peak)
Maximum HF noise (peak to peak)
V mV
Accepted length of micro-power outages (3)
Protection against Short circuits and overloads mV ms
24+/-5%
240
24+/-3%
150
240
≤ 10 in AC
≤
1 in DC continuous automatic reset cuts off at U>36
240
≤ 10 in AC
≤
1 in DC fallback to 0 and automatic reset after fault has disappeared cuts off at U>36 Overvoltages
V
Parallelization
Serialization
Power dissipation no no
8 yes with power optimization yes
18
(1) Values on initial power-up at 25°C. These elements are to be taken into account on start-up for the dimensioning of protection devices.
(2) Output power and current for an ambient temperature of 60°C. Input value in ( )
= output in a ventilated cabinet or within a temperature range of 0+40°C.
(3) A nominal voltage for a repetition period of 1Hz.
375
Process and AS-i supply module characteristics
Electrical characteristics of process supply modules: TSX SUP 1021/1051/1101
Table of
Characteristics
Process supply
The following table describes the electrical characteristics of supply modules: TSX
SUP 1021/1051/1101:
TSX SUP 1021 24V/2A TSX SUP 1051
24V/5A
TSX SUP 1101
24V/10A
Primary
Nominal input voltage
Input limit voltage
Network frequency
Nominal input current (U=100V)
Maximum call current (1)
Maximum It on trigger (1)
Maximum I
2 t on trigger (1) to 100 V to 240 V to 100 V to 240 V to 100 V to 240 V
Power factor
Harmonic 3
Full load efficiency
Secondary
%
Output (2)
Nominal output current (2)
W
On
Output voltage (0°C-60°c) V
Residual ripple (peak to peak)
Maximum HF noise (peak to peak) mV mV mV
Accepted length of micro-power outages (3) ms
Start-up time on resisting load s
On
On
As
As
A
2 s
A
2 s
V
V
Hz
On
53(60)
2.2
24+/-3%
150
240
<=10
<1 alternating 100..0.120/200..0.240
alternating 85...132/170...264
47...63/360...440
0.8
2.4
<30
<30
0.06
0.03
4
51
51
0.17
0.17
8.6
4
0.6
10% ( ϕ
=0° and 180°)
>75
8.6
0.52
>80
120
5
200
376
5
75
51
0.17
0.17
8.5
8.5
0.5
240
10
24+/-1%
TSX DM 57 xxF
Process supply
Process and AS-i supply module characteristics
TSX SUP 1021 24V/2A TSX SUP 1051
24V/5A
TSX SUP 1101
24V/10A
Protection against
Parallelization
Serialization
Power dissipation
Short circuits and overloads
Overvoltages
V fallback to 0 and automatic reset after fault has disappeared cuts off at U>36 current limit cuts off at U>32 yes with power optimization yes
18 30 60
(1) Values on initial power-up at 25°C. These elements are to be taken into account on start-up for the dimensioning of protection devices.
(2) Output power and current for an ambient temperature of 60°C. Input value in ( )
= output in a ventilated cabinet or within a temperature range of 0+40°C.
(3) A nominal voltage for a repetition period of 1Hz.
TSX DM 57 xxF
377
Process and AS-i supply module characteristics
Electrical characteristics of AS-i supply modules: TSX SUP A02/A05
Table of
Characteristics
References
The following table describes the electrical characteristics of supply modules: TSX
SUP A02/A05:
TSX SUP A02
30V AS-i / 2.4A
TSX SUP A05 24V/7 AS-i & 30V AS-i/5A
Primary
Nominal input voltage
Input limit voltage
V
V
Network frequency
Nominal input current (U=100V)
Maximum call current (1) to 100 V to 240 V
Maximum It on trigger (1)
Maximum I trigger (1)
2 t on to 100 V to 240 V to 100 V to 240 V
Power factor
Harmonic 3
Full load efficiency
Secondary
Output
Peak nominal current
30 V AS-i output
%
W
On
24 V output On
As
As
A
2 s
A
2 s
Hz
On
On
On alternating 100..0.120/
200..0.240
alternating 85...132/
170...264
47...63/360...440
1.3
30
30
0.06
0.03
4
4
0.6
10% (Phi=0°and 180°)
>75 alternating 100..0.120/200..0.240
alternating 85...132/170...264
47...63/360...440
5
50
50
0.17
0.17
8.5
8.5
0.51
10% (Phi=0°and 180°)
>80
72(84) (2)
2.4(2.8) (2)
-
230 (3)
5 (3)(4)
7 (3)(4)
378
TSX DM 57 xxF
References TSX SUP A02
30V AS-i / 2.4A
Process and AS-i supply module characteristics
TSX SUP A05 24V/7 AS-i & 30V AS-i/5A
Output voltage
Global variation (-10°C to +60°C)
Ripple (from 10 to 500 kHz)
V
V mV
30(AS-i)
29.5 to 31.6
50
24
+/-3%
200
30(AS-i)
29.5 to 31.6
50
Ripple (from 0 to 10 kHz)
Start-up time on resisting load mV s
Length of micro power outages (5) ms
Protection against Short circuits and overloads
Overvoltages
V
Power dissipation W
300
<2 (where C=15000 micro Farads
≤
10 fallback to 0 and automatic reset after fault has disappeared cuts off at U>36
240 300
<2 (where C= 15000 micro Farads) current limit on each output cuts off at U>36
24 60
(1) Values on initial power-up at 25°C. These elements are to be taken into account on start-up for the dimensioning of protection devices.
(2) Output and output current for an ambient temperature of 60°C. Input value () = surge output.
(3) Output and output current for a maximum ambient temperature of 55°C, if product index II = 01 (60°C if product index II > 01).
(4) distribution of current for each output (See Chart of available currents on 30 V
AS-i and 24 V output from the TSX SUP A05 supply block., p. 380).
(5) Acceptable period at nominal voltage for a repetition period of 1 Hz.
TSX DM 57 xxF
379
Process and AS-i supply module characteristics
Chart of available currents on 30 V
AS-i and 24 V output from the
TSX SUP A05 supply block.
The maximum power which can be delivered by the supply block is 230 W. If consumption is 5 A on the 30 V AS-i, possible flow on 24 V output is no greater than
3 A (see chart below).
Chart:
380
TSX DM 57 xxF
Process and AS-i supply module characteristics
Physical environmental characteristics
Table of characteristics
Connection to screw terminals
The following table describes the electrical characteristics of Process and AS-i supply modules:
Process and AS-i supply blocks/modules mm
2
TBX SUP 10
1 terminal per output
1 x 2.5
TSX SUP 1011/1021
TSX SUP 1051/1101
TSX SUP A02/A05
1011/1021/1051/A02: 1 output terminal
1101 : 2 terminals/output
A05: 2 terminals/output (24 VDC)
1 terminal/output (30 VDC AS-i)
2 x 1.5 with adapter or 1 x 2.5
maximum capacity per terminal
Temperature:
Storage
Operating
°C
°C
Relative humidity
Cooling
User safety
%
%
V eff
V eff
V eff
-25 to +70
+5 to +55
-25 to +70
0 to +60 (TSX SUP 1011/1021/1051/
1101
-10 to +60 (TSX SUP A02/A05) (1)
5-95
By natural convection
Very Low Voltage Safety (EN 60950 and IEC 1131-2)
50/60Hz-1 mm
1500
1500
500
3500
2200
500
Dielectric strength:
Primary/secondary
Primary/ground
Secondary/ground
Insulation resistance
Primary/secondary
Primary/ground
Leakage current
Electrostatic uploading immunity
Fast electric surge
Electromagnetic field influence
Rejected electromagnetic disturbances
Shock wave
Mega Ohms
Mega Ohms
≥
100
≥
100
I ≤ =3.5 mA (EN 60950)
6 kV per contact/8 KV in the air
(complies with IEC 1000-4-2)
2 kV (serial mode and common mode on input and output)
10 V/m (80MHz to 1GHz)
(comply with FCC 15-A et EN 55022 class A
Test conditions: nominal U and I, resisting load, cable: 1 meter horizontally, 0.8 meters vertically
Input: 4kV MC, 2kV MS Outputs: 2kV MF, 0.5 kV MS
(complies with IEC 1000-4-5)
TSX DM 57 xxF
381
Process and AS-i supply module characteristics
Process and AS-i supply blocks/modules
Vibration (2)
Degree of protection
MTBF at 40°C
Length of life at 50°C
TBX SUP 10 TSX SUP 1011/1021
TSX SUP 1051/1101
TSX SUP A02/A05
1 mm 3 Hz to 13.2 Hz 1g 57 Hz to 150 Hz (2g TSX SUP A02/
A05)
(complies with IEC 68-2-6, FC test)
IP 20.5
100 000
IP 20.5, terminal IP 21.5
30 000 (at nominal voltage and 80% of nominal power)
H
H
(1) -10°C +55°C for TSX SUP A05 supply module with product index II=01.
-10°C +60°C for TSX SUP A05 supply module with product index II > 01.
(2) complies with IEC 68-2-6, FC test with module or block mounted on a board or panel.
382
TSX DM 57 xxF
Index
A
Addressing two racks at the same address,
B
Breakdown of power consumption
TSX PSY power supply modules, 312
Building a PCX 57 PLC station with a TSX
Building a TSX P57 PLC station with TSX
C
Changing the battery on the TSX P57, 167
Changing the PCX 57 battery, 256
Changing the PCX 57 PCMCIA card battery,
Changing the Type 1 PCMCIA card battery on the TSX P57, 170
Changing the Type 3 PCMCIA card battery on the TSX P57, 172
Characteristics of AS-i supply modules, 378
Characteristics of Process supply modules,
Configuring the PCX 57 processor address,
Configuring the processor’s address, 240
Connecting racks to the ground, 83
TSX DM 57 xxF
A C
Connecting TSX PSY supply modules, 287,
Connecting TSX SUP A05 supply modules,
Connecting ventilation modules, 119
Connection of TSX SUP 1011/1021 power supplies, 358
Connection of TSX SUP 1051 power supplies, 360
Connection of TSX SUP 1101 power supplies, 362
Connection of TSX SUP A02 power supply modules, 366
D
Description of PCX 57 processors, 225
Description of TBX SUP 10 supply block,
Description of the support board, 342
Description of the TSX SUP 1011 supply module, 338
Description of the TSX SUP A02 supply module, 340
Description of TSX 1021/1051 supply modules, 339
Description of TSX SUP 1101/A05 supply blocks, 341
Dimensions of PCX 57 processor cards, 228
383
Index
E
Environment characteristics of AS-i supply modules, 381
Extendable rack
F
Finding errors using the processor state
G
General characteristics of the PCX 57 203 processor, 265
General characteristics of the PCX 57 353 processor, 267
General introduction to PCX 57 processors,
General introduction to Process and AS-i power supply modules, 336
General introduction to Process and AS-i
TSX SUP and TSX 1021/1051 power supply modules, 29
General introduction to the AS-i bus interface module
General introduction to the TSX FAN ventilation module, 44
General introduction to the TSX ISPY weighing module, 43
General introduction to the TSX P57, 144
General introduction to the TSX PAY emergency stop monitoring module, 45
General introduction to the TSX REY X Bus extension module, 31
General introduction to TSX CFY step by step control modules, 37
General introduction to TSX CTY/CCY counting modules, 34
General introduction to TSX DEY/DSY/DMY input/output modules, 32
General introduction to TSX P57 processors,
384
General introduction to TSX PSY power supply modules, 28
General introduction to TSX PSY supply modules, 278
General introduction to TSX RKY racks, 27
General introduction to TSX SCY/ETY communication, 38
H
How the PCX 57 behaves after an action on the PC, 262
I
Installation/mounting TSX PSY supply modules, 284
Installing a PCX 57 in the PC, 243
Installing the PCX 57
Installing the PCX 57 processor, 233
Integrating a PCX 57 into an X Bus section,
Introduction to PCX 57 processors, 224
Introduction to TSX CAY axis control modules, 35
L
Line terminator TSX TLYEX, 104
Logical installation of the PCX 57 processor on the X Bus, 234
M
MAST cycle time, 210, 211, 213, 217
Module installation on a rack, 96
Mounting processor modules, 154
Mounting/Removing a PCMCIA card on TSX
TSX DM 57 xxF
N
O
P
Physical description of TSX P57 processors,
PLC station rack addressing, 91
PLC station topology, extension module, 137
Positioning of line termination, 106
Positioning of line terminators, 105
Positioning the processor module, 152
Power supply servo control, 294
Precautions to be taken when installing a
Precautions to be taken when replacing a
Processing on insertion/extraction of a
PCMCIA memory card on a PCX 57 PLC,
Processing on insertion/extraction of a
PCMCIA memory card on a Premium PLC,
R
Rack power supply failure, 302
Rules for connecting to TSX PSY supply modules, 285
Rules for installing racks with ventilation modules, 118
TSX DM 57 xxF
Index
S
Standard rack
T
TSX CBY 1000 X Bus extension cable, 102
TSX CBY..0K X Bus extension cable, 100
TSX MRP DS 2048 P Memory Card, 162
TSX P 57 103 characteristics, 181
TSX P57 153 characteristics, 183
TSX P57 203 characteristics, 185
TSX P57 253 characteristics, 187
TSX P57 2623 characteristics, 189
TSX P57 2823 characteristics, 191
TSX P57 303 characteristics, 193
TSX P57 353 characteristics, 195
TSX P57 3623 characteristics, 197
TSX P57 453 characteristics, 199
TSX P57 4823 characteristics, 201
TSX P57 electrical characteristics, 204
TSX PSY supply modules
TSX RKA 02 protective cover, 107
TSX RKY Racks
TSX SUP 10 dimensions/mounting/ connection, 348
V
Ventilation module
introduction, 112 mounting, 116
W
What happens after pressing the RESET button on a power supply module, 303
What happens after you press the processor
385
Index
X
X Bus extension module
X Bus extension modules
386
TSX DM 57 xxF