This manual provides information for the assembly, wiring, configuration and maintenance of the AB_AI module.

SE-M556-USR

Publication Date (3/2020)

Read carefully the information contained in this manual before assembly, installation and use of the equipment. www.schneider-electric.com

20/03/2020

Change Control

User Manual – AB_AI

Rev Date

01 20-03-2020 Initial edition

Description

General Information

The Saitel platform and all its components have been developed in accordance to the requirements for a quality management system, complying with the ISO 9001:2015 Norm.

Document nº:

Revision/Date:

File:

Retention period:

SE-M556-USR

01 / 20-03-2020

AB_AI – User Manual_EN_01.pdf

Permanent throughout its validation period + 3 years after its cancellation.

Reference Documents

User Manual

Easergy Builder User Manual

HUe User Manual

HU_A User Manual

HU_B User Manual

HU_AF User Manual

Easergy Builder User Manual

Document Code

FTE-MSS-S856

SE-M588-USR

SE-M551-USR

SE-M552-USR

SE-M503-USR

FTE-MSS-S856 webAPP User Manual webTool user manual

EOL Instructions

FTE-WPP-S856

FTE-MSW-S856

FTE-EOLI-M555

Software Version in this Manual

The information in this manual is valid for the software versions listed below. This information is also valid for later versions, although some parameters may change slightly:

Module

Baseline

Baseline

Baseline

Easergy Builder Tool

AB_AI software

RTU Software

Module

HUe

HU_A/HU_AF

HU_B

Core

AB_AI.bin

Version

11.06.08_7061

11.04.18_6825

02.03.01

1.5.9.1

01.07.07

Pag 2

R&D Digital Seville

User Manual – AB_AI

Content

20/03/2020

1 SAFETY & HEALTH .................................................................................................. 4

2 GENERAL DESCRIPTION OF AB_AI .................................................................... 15

3 PHYSICAL MOUNTING & INSTALLING ................................................................ 20

4 CONFIGURATION & MAINTENANCE .................................................................... 26

5 TECHNICAL SPECIFICATIONS TABLE ................................................................ 52

R&D Digital Seville

Pag 3

20/03/2020

1 Safety & Health

User Manual – AB_AI

Pag 4

R&D Digital Seville

User Manual – AB_AI

Content

20/03/2020

1 SAFETY & HEALTH .................................................................................................. 4

I NTRODUCTION ........................................................................................................ 6

I NFORMATION OF S AFETY ................................................................................. 6

P RESENTATION ................................................................................................ 6

I NTRODUCTION TO S AFETY ....................................................................................... 7

S YMBOLS AND L ABELS ON THE E QUIPMENT ............................................................. 8

I NSTALLATION , S ETUP AND O PERATION ................................................................... 8

E ARTHING ............................................................................................................. 10

E LECTRICAL S AFETY ...................................................................................... 10

F UNCTIONAL E ARTH (EMC) ............................................................................ 11

H ANDLING E LECTRONIC C OMPONENTS .................................................................. 11

T ECHNICAL S PECIFICATIONS FOR S AFETY .............................................................. 12

P ROTECTIVE E LEMENTS ................................................................................. 12

E NVIRONMENTAL C ONDITIONS ........................................................................ 12

S TORAGE C ONDITIONS ................................................................................... 12

T ECHNICAL L ABEL ................................................................................................. 13

P ACKING AND U NPACKING ..................................................................................... 13

D ECOMMISSIONING AND D ISPOSAL ....................................................................... 13

R&D Digital Seville

Pag 5

20/03/2020

Introduction

User Manual – AB_AI

Information of Safety

Important information

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain it. In this manual you can find different types of messages associated with situations that have different level of risk for people and / or for the equipment.

This symbol indicates "DANGER" or "WARNING". This symbol informs of an electrical risk that will cause personal injuries if the instructions are not followed.

This symbol is associated to a safety alert. It is used to warn of possible personal injury hazards. The user must follow all instructions or messages associated to this symbol to avoid possible injuries.

DANGER

DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.

WARNING

WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.

NOTICE

NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this signal word.

To Keep in Mind

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

A qualified person is who fulfill with requirements in paragraph 1.2.

Presentation

This manual provides information for a safe handling, commissioning and testing. This Safety chapter also includes descriptions of the labels on the equipment.

Documentation for equipment ordered from Schneider Electric is dispatched separately from manufactured goods and may not be received at the same time. Therefore, this guide is provided to ensure that printed information which may be present on the equipment is fully understood by the recipient.

The technical data in this safety guide is typical only, see the technical data section of the user manual for specific details of a particular equipment.

R&D Digital Seville

Pag 6

User Manual – AB_AI 20/03/2020

Before carrying out any work on the equipment the user should be familiar with the contents of this Safety chapter and the ratings on the equipment’s rating label.

THE SAFETY SECTION MUST BE READ BEFORE STARTING ANY WORK ON

THE EQUIPMENT.

Introduction to Safety

The information in this section is intended to get that equipment is properly installed and handled in order to maintain it in safety conditions. It is assumed that everyone who will be associated with the equipment will be familiar with the contents of that Safety section.

When electrical equipment is in operation, dangerous voltages will be present in certain parts of the equipment. Failure to observe warning notices, an incorrect or improper use may endanger personnel and equipment and also cause personal injury or physical damage.

WARNING

Before working with the terminal of connection, the device must be turned off and disconnected of the feeding.

Proper and safe operation of the equipment depends on appropriate shipping and handling, proper storage, installation and commissioning, and on careful operation, maintenance and servicing. For this reason only qualified personnel may work on or operate the equipment.

Qualified personnel are individuals who:

• Are familiar with the installation, commissioning, and operation of the equipment and of the system to which it is being connected.

• Have read and understood the information on the device and its user manual.

• Are able to safely perform switching operations in accordance with accepted safety engineering practices and are authorized to energize and de-energize equipment and to isolate, ground, and label it.

• Are trained in the care and use of safety apparatus in accordance with safety engineering practices.

• Are trained in emergency procedures (first aid).

It is necessary to consider that the documentation of the device collects the instructions for its installation, set up and operation. However, the manuals could not cover all the possible circumstances neither include specific information on all the details.

In case of questions or specific problems, contact with his office of sales Schneider Electric or with the center of attention to the customer and request the necessary information.

R&D Digital Seville

Pag 7

20/03/2020

Symbols and Labels on the Equipment

User Manual – AB_AI

Before the equipment is installed or commissioned, the user must understand the following symbols, which may be used on the equipment or referred to in the user documentation:

Table 1 – Symbols

Symbol Associated Text Description

Possibility of electric chock

Caution, read the manual.

Possibility of electric chock

Protective earth connection

IEC symbol associated to a DANGER or

WARNING message indicating that there is an electrical risk. Failure to follow these instructions could cause damage to people or death.

Symbol associated with a risk alert. The user must read the manual before handling the equipment.

ANSY symbol associated to a DANGER or

WARNING message indicating that there is an electrical risk. Failure to follow these instructions could cause damage to people or death.

Associated symbol to the protective ground

connection. See paragraph 1.5.1 in this manual.

CE Mark

Electronic device.

Special instructions must be follow for discard it.

Compliant with

RoHS.

Direct Voltage

This symbol indicates that the equipment has been developed in compliance with all applicable European Directives.

This symbol indicates that, at the end of its life, this module must be discarded according to the

WEEE Directive (Waste Electrical and Electronic

Equipment).

The equipment has been designed and manufactured according to RoHS Directive

(Restriction of Hazardous Substances).

Symbol of direct voltage (V

DC

).

Alternate Voltage Symbol of alternate voltage (V

AC

).

Installation, Setup and Operation

There are several acquisition blocks in Saitel DR that use high voltages (> 50 V). The user is responsible to check that the characteristics of each device are adapted and convenient for his installation. The user should read the instructions of installation before proceeding to the use or maintenance of the devices.

Not following these instructions can be dangerous for the people and the devices.

DANGER

Devices that handle dangerous tensions are marked with a sticker on the front label (size: 12,5 mm). This label must be visible all the time while the module is installed on the DIN rail.

Pag 8

R&D Digital Seville

User Manual – AB_AI

The following products handle dangerous tensions:

20/03/2020

• HU_AF: Advanced head unit with acquisition (P/N M503xx3x0x and P/N M503xx4x0x). For other part numbers, depending on the voltage handled by the equipment connected to the digital outputs (voltage > 50 V), this module must be marked with an electric risk label. It will not be marked on factory.

• HU120: High-performance CPU with acquisition (P/N M590xx000x).

• AB_DI : Digital inputs module (P/N: M55520000x, M55530000x and M55540000x).

• AB_DIDO : Input and output digital module (P/N M5722x000x, M5723x000x and M5724x000x).

For other part numbers, depending on the voltage handled by the equipment connected to the digital outputs (voltage > 50 V), this module must be marked with a electric risk label. It will not be marked on factory.

• AB_AC : Direct measurements module (P/N M562x0000x).

• AB_DO : This module does not handle high voltages, it will not be marked at the factory. This module must be marked to inform about the risk when some equipment that manage voltage higher than 50 V are connected to digital outputs.

It is recommended to install the RTU inside a cabinet with a key. This cabinet only should be opened by a qualified person.

WARNING

If this type of cabinet isn't available, a barrier must be installed in order to avoid an accidental contact with these dangerous elements. This barrier only should can be removed using a special tool.

If the barrier has to be removed in order to access to equipment, personnel responsible for the task must be sure that the barrier is installed again when the task is finished.

While the RTU is accessible for a user, all people must follow all instructions to prevent electrical risk or discharges.

Not following these instructions can give like result that the device do not work properly or even can damage to the people or devices .

An electrical risk symbol with enough size must be included on the cabinet’s door or on the barrier .

The following image shows an example:

Figure 1 – Barrier of protection for elements with dangerous voltages.

INFORMATION

Terminals will not be accessible to the user directly once it has made the installation of the device. The cabinet will have to remain closed with key or the screen of installed protection.

The cabinet or installation must have a general switch placed just in the cable entry of the

installation (see paragraph 1.7.1)

R&D Digital Seville

Pag 9

20/03/2020 User Manual – AB_AI

For the cleaning of the device it is only necessary using a dry cloth by the surface when it detects excessive presence of dust or any element deposited on the surface.

WARNING

Don’t use a liquid products of cleanliness due to the presence of active parts.

Because of the variety of uses of the product, the managers of the application and use of this device of control will have to take the measures to ensure the fulfillment of all the requests of security and provision of each application. The requests do reference to the applicable laws, regulations, codes and standard.

Earthing

WARNING

Before energizer the device, it has to be placed to earth properly such as it indicates in sections

1.5.1 and 1.5.2.

When installing the device, ground is the first thing that should be connected and the last one that should be disconnected.

Saitel can need put to earth for two distinct needs:

• For purposes of electrical safety (Protective Earth, PE).

• Improve the behavior in EMC and derive perturbations to earth (functional Earth).

Electrical Safety

Only qualified personnel, with knowledge about hazards associate with electrical equipment is allowed to install Saitel DR. In general, the installation will be following IEC 61010-1 recommendations in order to be compliant with this norm.

The DIN rail must be installed on a metallic surface. This metallic surface must have available an M4 screw marked with this symbol. The ground of the cabinet or installation must be connected to this screw, according to the norm IEC 61010-1 .

Saitel DR modules have a metallic enclosure offering protection for isolation faults. Earthing is done by the metal rail fixing clip.

WARNING

All devices with high voltage must be disconnected before dismount a module from the DIN rail.

A dedicated connection with green/yellow wire should be used to assure electric continuity to the installation protective earth. Section of these wires must be enough in order to support 25 A

(ground bonding test).

Figure 2 – Yellow and Green cable for earthing.

The design and installation of the cabinet is responsible for compliance with all the existing international and national electrical codes concerning protective grounding of any device.

Pag 10

R&D Digital Seville

User Manual – AB_AI 20/03/2020

WARNING

According to Electrical Safety:

• The screw for ground must be exclusive for this use.

• The power voltage must be supplied by a power supply that offers double or reinforced insulation against dangerous voltages.

Functional Earth (EMC)

In this case the main rule is that the connection has to do with wires of the lower possible length to the screen or connection of put to earth nearer. In this case the section of the driver is not notable, is more, it advises that the use of flat wires or flexible conductive bands for a good behavior EMC.

INFORMATION

The DIN rail must have terminals of earthing (of yellow and green color) necessary to connect the terminals of PE (if it is present).

Figure 3 – Terminal for functional earth (EMC).

All Saitel DR modules with power or polarization connector have an exclusive terminal for earthing

EMC. These modules are HU120, HUe, HU_B, HU_A, HU_AF, XU, AB_DO, AB_DIDO and

AB_SER with external polarization.

Figure 4 – Example of earthing for EMC.

Handling Electronic Components

Saitel is susceptible to receive electrostatic discharges during the handling. It is necessary to take the usual measures to minimize this risk, since serious damage to the equipment can be caused, which may not be detected immediately but which may affect the reliability of the product.

WARNING

The enclosure ONLY should be removed when is strictly necessary , because this action has a risk for the equipment:

• Before removing the enclosure, the operator must be equipotential with the equipment.

• Avoid touching the electronic. The board must be always manipulated for the edges.

• If the equipment has to be passed between two persons, both must be equipotential.

• Put the module always on an antistatic surface or on a surface equipotential with you.

• During the storage and transport, the module will remain in the packaging.

R&D Digital Seville

Pag 11

20/03/2020 User Manual – AB_AI

Not following these instructions can give like result that the device do not work properly or even can damage to the people or devices.

Technical Specifications for Safety

Protective Elements

The cabinet's engineering and installation must include a general automatic switch next to the cables' input in the cabinet; once the door is opened, high voltages must be interrupted inside. This switch must be located at a place which is not accessible by a third person while the operator is using the boards in the cabinet.

Moreover, the installation will incorporate a circuit breaker of 5A next to the cabinet protecting it from possible overcurrent in the power supply.

Both switches will be labeled with the symbol O as "Off" and I as “On”.

WARNING

The connection / disconnection switch must be installed in a fixed element (for example the wall of the cabinet) and it mustn’t break any earthing wire.

Environmental Conditions

The protection degree of the device is IP20.

WARNING

This equipment has been designed ONLY for indoor use.

If it is necessary for his use in some external surroundings, it has to mount in a cabinet or specific accommodation that contributes a degree of protection IP54, protected against the dust and water.

The electronic cards of the modules will be able to be tropicalized or no according to the option of setting chosen. The tropicalized used is the AVR80, of the company ABchimie. It can consult all the technical information of this type of finishing in http://www.abchimie.com/ .

Other data to take into account about the environmental are:

• Altitude until 2000 m.

• Operation temperature range: Between -40 ºC and 70 ºC. (IEC 60068-2-1 and IEC 60068-2-2).

• Maximum relative humidity of 95%. (IEC 60068-2-30)

• Degree of pollution II. (IEC 61010-1)

• Overvoltage transitory until levels of Category II. (IEC 61010-1)

Storage Conditions

The continuous exhibition to some high levels of humidity during the storage can cause damages to the electronic components and reduce the useful life of the device.

We recommend that, in the enclosure of storage, the relative humidity do not exceed 50%.

Once that the Saitel devices have been unpacked, recommend that they are energized inside the three following months. When it installs an electrical device, it has to leave sufficient time for the acclimatization to the temperature acclimatize of the environment, before the activation. Once the equipment has been unpacked, it is recommended that it be energized within the following three months.

Pag 12

R&D Digital Seville

User Manual – AB_AI

Technical Label

Each Saitel product includes a technical label with the following information:

Figure 5 – Technical label.

20/03/2020

INFORMATION

On the “Technical data” zone, you can see relevant information about the input and output voltage in the module. Any voltage greater than 50 V must be consider as a high voltage.

Packing and Unpacking

All Saitel modules are packaged separately in their own carton box and shipped inside outer packaging. Use special care when unpacking the device. Don’t use force.

The design revision and manufacturing options can be determined using the P/N included in the packaging label on packaging.

After unpacking the device, inspect it visually to be sure it is in proper mechanical condition.

If the product needs to be shipped, the original packaging must be used, including foams and the carton box. If the original packaging is no longer available, make sure that the packaging used is according to ISO 2248 specifications for a drop height 1 m.

Decommissioning and Disposal

When the product is marked with this symbol, it means that, at the end of its life cycle, you mustn't dispose the product together with habitual residues. To avoid the possible damage to the environment or to the human health that represents the uncontrolled elimination of residues, please, separate the battery (if there is one) of the other elements, and each one must be recycled according to the local regulation .

R&D Digital Seville

Pag 13

20/03/2020 User Manual – AB_AI

Pag 14

R&D Digital Seville

User Manual – AB_AI

2 General Description of AB_AI

20/03/2020

R&D Digital Seville

Pag 15

20/03/2020

Content

User Manual – AB_AI

2 GENERAL DESCRIPTION OF AB_AI .................................................................... 15

S AITEL DR P LATFORM ........................................................................................... 17

AB_AI F EATURES ................................................................................................. 17

I NTERFACES .......................................................................................................... 18

H ARDWARE A RCHITECTURE ................................................................................... 19

Pag 16

R&D Digital Seville

User Manual – AB_AI

Saitel DR Platform

20/03/2020

Saitel DR is a hardware platform by Schneider Electric. It consists of a set of equipment which have been specifically designed for real-time control and automation applications. Saitel DR is a high-technology platform which serves Schneider Electric’s business areas.

On this hardware platform, the Baseline Software Platform is installed. This software is used in

Saitel families (Saitel DP and Saitel DR) and other Schneider Electric products.

Other features identifying Saitel DR are:

• A DIN rail is used for the mechanical installation.

• The communication between the controls units integrated in a distributed system is mainly established by Ethernet.

• The terminal blocks for field-connection are completely built into acquisition blocks.

Figure 6 – Saitel DR.

Saitel DR’s design has been optimized to meet the most demanding requirements of multiple sectors:

• Safety and reliability requirements for power, gas and water supply, as well as sewage treatment plants, etc.

• Compliance with electric safety, electromagnetic compatibility, and environmental standards.

• Centralized monitoring and control of geographically-distributed systems which support hierarchical data acquisition and sharing networks.

• Local monitoring and control with data sharing capabilities of plant-distributed equipments.

• Quick troubleshooting, including the possibility of using programmable automation execution.

WARNING

Please note Saitel DR does not support hot-swapping, that is, module replacements during operation.

AB_AI Features

The main features of this module are:

• 8 analog inputs using 2 removable terminal blocks. Each terminal allows connecting 4 signals.

• The information is processed before transmitting it to the HU, to do so, it uses a high-resolution sigma-delta converter.

• Processing of information includes:

R&D Digital Seville

Pag 17

20/03/2020 User Manual – AB_AI o Digital filtering. o Scaling to engineering units. o Range limits detection. o Value change detection. o Zero value cancellation

• The module is synchronized via a message received from the HU.

• 4 LED indicators are available on the front side.

The diagram below illustrates the functional blocks integrated in the AB_AI module:

Figure 7 – Functional block diagram

Analog Inputs

The AB_AI has two terminal blocks labeled as B1 and B2 which allow the connection of 8 analog inputs (4 per terminal block). The main features of these inputs are:

• Differential type.

• By default, all signals are ready for voltage, but they can be configured for currents using an external resistor (250 Ω ).

• 8-channel multiplexing.

• 16-bits sigma-delta converter.

• Accuracy better than 0.1% at 25 ºC.

• Protections against overvoltage.

Interfaces

Following interfaces are available in this module:

• 2 removable terminal block to connect one analog input.

• 4 LED indicators.

Figure 8 – AB_AI Module

Pag 18

R&D Digital Seville

User Manual – AB_AI

Hardware Architecture

The following P/N describes all available ordering options for this module:

Figure 9 – AB_AI P/N description.

The following figure illustrates the AB_AI hardware blocks diagram:

Figure 10 – AB_AI - Hardware block diagram

20/03/2020

Indicators

There are 4 LED indicators on the module’s front panel which provide information about the module and the features

Analog Inputs (B1 and B2)

There are 4 analog inputs in each terminal. The first 8 pins (from left to right) are related to 4 analog inputs and the last one is used for ground connection.

R&D Digital Seville

Pag 19

20/03/2020 User Manual – AB_AI

3 Physical Mounting & Installing

Pag 20

R&D Digital Seville

User Manual – AB_AI

Content

20/03/2020

3 PHYSICAL MOUNTING & INSTALLING ................................................................ 20

ITB INSTALLATION ................................................................................................. 22

H ANDLING ...................................................................................................... 22

L OCATION IN THE ITB ..................................................................................... 22

P OWER S UPPLY R EQUIREMENTS .................................................................... 22

M OUNTING P ROCEDURE ................................................................................. 22

W IRING AB_AI ...................................................................................................... 23

W IRING R ECOMMENDATIONS .......................................................................... 24

A NALOG I NPUT C ONNECTION .......................................................................... 24

LED I NDICATORS ................................................................................................... 25

R&D Digital Seville

Pag 21

20/03/2020

ITB installation

User Manual – AB_AI

Handling

DANGER

Depending on the devices connected to the module AB_AI, could exist hazard of electric chock, electric arc or burns. For any of these cases, follow these instructions:

• Only qualified operator should install this equipment. Such work should be performed only after reading this entire set of instructions and checking the technical characteristics of the device.

• NEVER work alone.

• Turn off all power supplying this equipment before working on or inside it. Consider all sources of power, including the possibility of back feeding.

• Always use a properly rated voltage sensing device to confirm that all power is off.

• Start by connecting the device to the protective ground and to the functional ground.

• Screw tight all terminals, even those not in use.

Failure to follow these instructions will result in death or serious injury .

To avoid electrostatic damage, the following precautions must be strictly followed:

• Do not touch the bus connector pins.

• If unused, keep the modules in the antistatic bag.

WARNING

Electrostatic discharges may damage semi-conducive devices within the module.

Location in the ITB

Saitel DR modules cannot be placed at any position in the ITB. Some of them, such as the head unit, the termination (TU or BT), the expansion (XU) and the communications module (AB_SER) must be installed in a specific position in the ITB.

All AB_AI modules will always be placed between two termination blocks. The type of termination block will depend on the row position within the ITB (HU, TU, XU or BT).

Power Supply Requirements

The main power is supplied by the HU through the bus. The maximum power requirement for each

AB_AI module is:

• Main power supply : Basic consumption

1

Mounting Procedure

WARNING

It is important to assure that handling is always done while the ITB elements are unpowered.

All Saitel DR modules have a DIN-rail bracket at the rear side that allows mounting on a DIN rail.

1 Basic consumption and Maximum current per signal values are indicated in the technical specifications table at the end of this manual.

Pag 22

R&D Digital Seville

User Manual – AB_AI

Figure 11 – Mount bracket on DIN rail.

20/03/2020

The mounting procedure is described below:

• Switch off the power supply.

• Attach the module’s rear bracket on the upper DIN rail.

• Press the lower front panel gently until a click confirms that the bracket is fit on the rail.

• Verifying the module is anchored firmly to the rail, although lateral movement is possible.

Figure 12 – Saitel DR module on a DIN rail.

The module is dismounted from the DIN rail as follows:

• Switch off the power supply.

• If necessary, disconnect the bridge(s) connecting the module to the system bus.

• Holding the module by the front panel, push the upper metal tab downward. The user can also pull the tab down using for example a screwdriver as shown in the next figure.

• Figure 13 – Remove module.

• Pressing the tab, remove the module from the lower DIN rail.

• Once detached, the module can be removed easily.

Wiring AB_AI

The AB_AI analog inputs are differential, so there is no common terminal. Each terminal block includes 4 pairs of signals which correspond to the 4 analog inputs.

R&D Digital Seville

Pag 23

20/03/2020 User Manual – AB_AI

INFORMATION

Current inputs require a 250Ω resistor and a 0.1% precision between the two input terminals.

This figure illustrates the pins arrangement in the AB_AI screw terminals:

Figure 14 – B1 and B2 terminal blocks wiring.

Wiring Recommendations

The following table shows several wiring recommendations for signals and polarization:

Type of wire

Analog inputs 7 mm

2.5 mm²

13 AWG

0.5 Nm Copper

Analog Input Connection

Both B1 and B2 have 4 terminals for signals. The field inputs are voltage-free NO (Normally open) contacts.

Figure 15 – B1 and B2 terminal blocks wiring.

The 8 signals wiring in each terminal block is described below:

Figure 16 – Analog inputs wiring.

Pag 24

R&D Digital Seville

User Manual – AB_AI 20/03/2020

LED Indicators

The AB_AI module has the following indicators on the front panel:

Figure 17 – LED indicators.

LED

Run

AB_AI LED provide the following information to the operator:

Table 1 - AB_AI - LED indicators meaning

Status Description

Module working properly.

Module not in acquisition mode.

Out R

Fail

Mnt

A signal is out of range.

Signals are in range.

Module not configured or in abnormal state.

No fault has been detected in configuration or hardware.

Failure in EEPROM.

The module is in maintenance (Flashing, addressing, ...)

The module is in operation.

Recommended action

The module wasn’t included into the configuration, the module doesn't have an address or according to the loaded configuration, the type of the module is wrong.

Check the range of the signals

Check the configuration loaded in the HU. The module must be addressed and with the correct type (AB_AI).

R&D Digital Seville

Pag 25

20/03/2020 User Manual – AB_AI

4 Configuration & Maintenance

Pag 26

R&D Digital Seville

User Manual – AB_AI

Content

20/03/2020

4 CONFIGURATION & MAINTENANCE .................................................................... 26

ITB CONFIGURATION .............................................................................................. 28

AB_AI C ONFIGURATION ........................................................................................ 30

I NFORMATION OF L OCAL A CQUISITION ............................................................. 31

AB_AI SIGNALS .............................................................................................. 32

L OCAL A CQUISITION C OORDINATES ................................................................ 32

I NFORMATION IN THE T ABLE A NALOG .............................................................. 33

S IGNAL C ALIBRATION ............................................................................................ 34

S IGNAL C ALIBRATION U SING A B ASIC HU ........................................................ 34

S IGNAL C ALIBRATION U SING A HU_A OR HU_AF ............................................ 36

S IGNAL C ALIBRATION U SING A HU E ................................................................ 37

M AINTENANCE OF M ODULE VIA WEB ..................................................................... 39

W EB A PP V S W EB T OOL .................................................................................. 39

U SING W EB A PP ............................................................................................. 39

U SING W EB T OOL ........................................................................................... 45

F IRMWARE U PDATE ............................................................................................... 49

R&D Digital Seville

Pag 27

20/03/2020

ITB configuration

User Manual – AB_AI

INFORMATION

To perform the operations described in this chapter, the user must be familiar with the Easergy

Builder tool. Otherwise, please refer to the tool's manual.

In the Workspace of Easergy Builder, create a new RTU using button or pressing right button of the mouse in an empty area of the rtus tree:

Figure 18 – Adding a new RTU.

Pressing button next to the graphical ITB, you can add, remove or change the I/O modules included on the default configuration.

The user needs understand some basic concepts about Saitel DR before configuring the acquisition:

• An ITB is a set of acquisition blocks connected to a CPU (HU).

• An Acquisition Block or AB is a Saitel DR input/output module.

• Each acquisition block is allocated to a unique address in the ITB, the Node Number; this number identifies both the module and its type.

• The procedure AAP (Automatic Addressing Procedure) is performed by the operator every time an AB module is added, deleted, replaced or moved inside the ITB. It can be launched manually or automatically depending on the configuration switches of the HU

(consult user manual of the HU).

Figure 19 – ITB.

Pag 28

R&D Digital Seville

User Manual – AB_AI 20/03/2020

The number between parentheses next to each module's name is the node number. You can select an AB and use buttons to change its physical position.

When “ Auto Address ” box is checked (by default), if you reorder, add or delete an AB, all addresses are automatically recalculated matching their physical position in the rail. Address number 1 is assigned to the AB closest to the HU module (for HU_AF or HU_BI, address number 1 will be attached to the HU itself).

If “ Auto Address ” box is unchecked, modules will retain the allocated address, ignoring any changes made. If rechecked, the following message will appear:

Figure 20 – Auto Address.

Select an AB (click on the AB image) and use button to remove it. Use button to add a new

AB. Select the type of AB in the following window:

Figure 21 – Adding an AB module.

If “ Auto Address ” is checked, you can add several AB at one time. This window allows selecting the quantity of modules to be added. If “ Auto Address ” in unchecked, you only can add one AB each time and you have to select the address to be assigned.

To create a new configuration, select RTU in the tree and pulse right button of the mouse or use

button.

Figure 22 – Adding a configuration.

R&D Digital Seville

Pag 29

20/03/2020 User Manual – AB_AI

If the field " Create acquisition points defined in the RTU " is marked, all points of the local acquisition of the acquisition blocks included in the default acquisition configuration associated with the RTU will be included in coreDb.

For example, if a HUe has an ITB with an AB_AI module, if " Create acquisition points defined in the RTU ", 8 analog inputs signals will be included in the Analog table.

Finally, the new configuration will appear in the RTUs tree.

Access to the configuration edition clicking on the configuration name in the tree:

Figure 23 – Configuration edition

Double click on the claq Device open the window to configure/modify the ITB.

Selecting the module AB_AI, you can configure each field signal

Figure 24 – Changing the ITB configuration.

Other buttons in this window are explained in the user manual of Easergy Builder.

AB_AI Configuration

The local acquisition Device for Saitel DR is named “claq”. The main functionality of the Local

Acquisition Device Controller is supporting the communication between the inputs and the outputs managed by the acquisition blocks and coreDb points.

The first step to configure the acquisition settings is to assure that the ITB in the graphical interface is according to the system. Each module must be addressed according its position in the ITB.

R&D Digital Seville

Pag 30

User Manual – AB_AI 20/03/2020

INFORMATION

The graphical interface does not take into account if the ITB is assembled in one or multiple rows. The modules should always be added in the adequate order, regardless the number of

TU-XU modules that we have installed.

Figure 25 – Configuring local acquisition for Saitel DR.

Information of Local Acquisition

The following figure shows the relationship between the field information received by the AB_AI module and the related points in coreDb:

Figure 26 – Field signals and points in coreDb.

R&D Digital Seville

Pag 31

20/03/2020

AB_AI signals

User Manual – AB_AI

The following figure shows the configuration panel when the ITB is composed by an HUe and one

AB_AI module with address 1:

Figure 27 – AB_AI field signals.

Select the module in the ITB and all its field signals are shown (marked in red).

The first position of each row corresponds with the signal’s description (AI_PNT_1 ... AI_PNT_8).

In coreDb, each signal will be identified using its coordinate. (see paragraph 3.2.2).

Each signal has the following associated information:

• EMin : Minimum value expressed in field units (from -32768 to 32767).

• EMax : Maximum value expressed in field units (from -32768 to 32767).

• Rng : Voltage range expressed in engineering units (0/5 V, -5/5 V, 0/20 mA, -20/20 mA, and

4/20 mA).

• Filt : Mobile measuring filter (expressed as a percentage value, 0 - total filtering and 100 - no filtering).

• Zero : Zero cancellation (expressed in scaled values)

Local Acquisition Coordinates

Each digital input is identified in coreDb by a name (it is stored in the field Description), but this name is only used for information purpose. coreDb uses the signal’s coordinate in order to identify a field signal.

A claq coordinate is a numerical identifier of 10 digits with the following structure:

1XXXYYZZZZ

Where:

• 1 : First digit of the coordinate. In local acquisition signals, it must always be 1.

• XXX : Number that identifies the acquisition block. For the HUe signals, it will always be 000.

For the rest of the ABs, this number will correspond with the address of the module.

Pag 32

R&D Digital Seville

User Manual – AB_AI

• YY : Type of signal. For digital input could be: o 02: Simple digital input. o 03: Count. o 07: Double digital input.

20/03/2020

• ZZZZ : Position of the signal in the module.

Information in the Table Analog

Each AB_AI signal is associated to a coreDb register in the analog table using its claq coordinate as source:

Figure 28 – Information of analogical inputs in CoreDb.

These points and other diagnostic points (D001_COMM_DIAG and D001_HW_DIAG) can be created automatically when the module is included in the ITB, but they can be created manually using the claq’s wizard.

In order to include a point manually, please create a new point, select claq as Source Device, click right-button on the field Source Device and select Launch Point wizard:

Figure 29 – Point wizard.

R&D Digital Seville

Pag 33

20/03/2020 User Manual – AB_AI

Select the module in which it wants to create these points and then select the point to be created.

Only not created point will be shown in the list.

The following point can be added for a AB_AI module:

• Status, Source Coordinates: o Diagnostics point:

 COMM_DIAG: Status of the communication with the HU. 0  “Communication

FAIL”, 1  “Communication OK”.

 HW_DIAG: Hardware diagnostic. 0  No problem detected, 1  Problem detected in the hardware.

• Analog, Source Coordinates: o Analog Inputs: Analog inputs, depend on the configuration performed.

Signal Calibration

The AB_AI analog inputs are calibrated in factory. Nevertheless, the user may calibrate each signal to meet the environment requirements.

INFORMATION

• The user must assure that the calibration device is similar to the device recommended by

Schneider Electric, in particular the calibrator Fluke 725. The device should be able to generate voltages ranging from 0V to 10V with a precision lower than 0.1%.

• Signal calibration can be performed in the field, while the ITB is under a normal data acquisition state. During calibration, all modules will operate normally, except for the module under calibration.

The calibration method depends on the HU type which controls the ITB. If the CPU is an advanced

HU (HU_A, HU_AF), Saitel Webtool is used to calibrate. If the CPU is a Hue, Saitel WebApp is used. When the CPU module is a basic HU (HU_B), the calibration process is performed using the console.

The calibration is done separately for each channel.

Signal Calibration Using a Basic HU

1. The user needs to connect the PC to the HU module through the CON port (console channel).

For further details about the connection, please refer to the CPU manual.

2. For each analog input, the user must execute the “claqCalAi N C” command, where N refers tclao the AB_AI module's number within the ITB (can be obtained by entering the “claqShow” command in the console) and C refers to the signal number within the module, where

1<=C<=8.

3. After executing the calibration command, for example on the 2 nd signal of the B1 terminal block

(signal 2) of the module number 1, the following message will appear:

4. When the calibrator is connected to terminals AI2+ (red cable) and AI2- (black cable), the system will wait for it to supply 0V. Then, the user needs to press any key. Subsequently, the system asks the user to wait while specific calculations are made.

5. Once a 0V level is registered, the system requests a 5V level voltage to be injected and to press any key:

Pag 34

R&D Digital Seville

User Manual – AB_AI 20/03/2020

6. The system will repeat the operations and calculations for this voltage level. Once finished, it will display a message to inform that the analog input has been calibrated:

The calibration values depend on the signal range assigned in the configuration tool (see section

3.2).

For example, if the input 1 of the AB_AI module, which is in the position 1, is configured in the range 0/20 mA, the messages exchanged with the user during the calibration process are:

In the case of calibrating current inputs, it will be necessary to place a 250Ω resistor between the positive and the negative pin, so that by injecting current with the calibrator, the voltage between the two input terminals is lower than 5V.

Factory calibration values can be restored individually for each signal at any time. To do so, execute the “claqRestCalAi N C” command, where N refers to the module number and C refers to the signal number in the module. For example, to restore the factory values for the previous signal

(input 1), follow the procedure below:

R&D Digital Seville

NOTICE

• It should be noted that even if the signal is configured for current (0/20 mA), the factory calibration is done for voltage values, and these are the retrieved values. Therefore, the resistor tolerances, which convert current to voltage, are not calibrated.

• Schneider Electric recommends a 250 Ω resistor with 0.1% tolerance in order to maximize the resolution of the analog to digital converter

Pag 35

20/03/2020

Signal Calibration Using a HU_A or HU_AF

User Manual – AB_AI

If the CPU is a HU_A or HU_AF, to calibrate AB_AI, Saitel WebTool must be used.

In WebTool, go to Bins section and click on “claq”. You will see a table with the correspondent signals.

Figure 30 – Saitel WebTool Menu.

For example, following picture shows a tab corresponding to an AB_AI module.

Figure 31 – Claq Device in Saitel WebTool.

To calibrate a specific AB_AI module, press “Calibrate” button on the table. Then, the following screen appears:

Figure 32 – AB_AI module calibration.

Each input must be calibrated separately, by pressing the “Start” button which is associated to each signal in the “Calibration” column.

Pag 36

R&D Digital Seville

User Manual – AB_AI

When calibration starts, the following message is shown:

20/03/2020

When the calibrator is connected to terminals AI1+ (red cable) and AI1- (black cable), the system will wait for the calibrator to supply 0 V. Then, press “Ok”. Subsequently, the system asks the user to wait while the input is calibrated for 0 V.

Then, the following message is shown:

As described for the previous step, supply 5 V through the calibrator and then press “Ok”. The system will start the calibration for this voltage level.

When the operation finishes, the following message will appear:

The calibration values depend on the signal range assigned in Easergy Builder.

Factory calibration values can be restored at any time for individual signals. To do so, press the

“Restore” button associated to the channel in the table. You will be prompted to confirm or cancel the operation.

Signal Calibration Using a HUe

If the CPU is a HUe, to calibrate AB_AI, Saitel WebApp must be used. The recommended web browser is Google Chrome (version 67.0.3396.99).

In WebApp, go to Maintenance section and click in “Acquisition”. You will see a table with the correspondent signals. If the permissions set for the user allows it, these points van be calibrated.

Figure 33 – Saitel WebApp Menu.

R&D Digital Seville

Pag 37

20/03/2020 User Manual – AB_AI

For example, following picture shows a tab corresponding to a AB_AI module. All its signals are displayed with the value and quality information.

Figure 34 – AB_AI module calibration.

To start the calibration of an analog input, just click on the “calibrate” button for the signal to calibrate. A window will pop with the instruction that the user must follow. Please take into account that if the point has no good quality or it is blocked, calibration will not start.

Press “Yes” to continue or “No” to cancel the process.

If the analog point cannot be calibrated, following message will be shown:

Pag 38

R&D Digital Seville

User Manual – AB_AI

Maintenance of Module via WEB

20/03/2020

WebApp Vs WebTool

WebApp and Webtool are remote user interfaces for consulting, monitoring and maintenance tasks. Once the username and password have been entered, you can access to the main window and, depending on the web tool, several sections are available.

INFORMATION

WebApp has been designed to work only with cybersecurity brick. At now, it can be used only with HUe. HU_A and HU_AF use Webtool, while HU_B doesn’t allow a remote connection using a webserver.

When use WebApp, the following message is shown previously to access the tool:

Figure 35 – Disclaimer information.

Please, read this information and take it into account.

In this manual, only the information about AB_AI is shown. For more information about these tools, please, consult the user manual for each one.

Using WebApp

Saitel WebApp has an access control that allows differentiating the users who are able to connect.

To get the window access, please write https://< CPU IP address> in the navigation address bar.

Figure 36 – Access screen

Write the Username and Password in orfer to access the webAppp’s mains window:

R&D Digital Seville

Pag 39

20/03/2020 User Manual – AB_AI

Home tab

This screen contains 5 menus:

• Home

• Monitoring & Control

• Diagnostic

• Maintenance

• Settings

Select Home in the main toolbar and the following information is shown.

Figure 37 – Home view.

Pag 40

R&D Digital Seville

User Manual – AB_AI 20/03/2020

Some of this information can be filled in by the user.

• Device Information . It is possible to add the names of the operators who have used or configured the equipment or a specific custom note that can be viewed each time a connection is established to this RTU. This information can be changed using button “Edit”, next to “Device information”.

• Location . The GPS coordinates for the RTU location (place, latitude, longitude, and altitude) should be entered here by the installer. Location is not set automatically. The image must be included manually by clicking button on the map.

• Image associated to the RTU. It could be useful to include a location map corresponding to the

GPS coordinates. Use button on the graphic zone to do it.

• Notes . This zone allows the user to include notes that are shown to other users. Use button

too add new notes.

• Factory information : This zone shows the manufacturer, model and the version of the software loaded on the HU module. Using button next to the text “Factory Information”, it is also possible to include an image of the particular RTU or CPU for identification purposes.

This screen contains other menus:

• Monitoring & Control

• Diagnostic

• Maintenance

• Settings

This manual only includes relevant information for AB_AI. For more information about webApp, please, consult the webApp user manual.

Monitoring and Control

This menu is used to monitor and control the information regarding to system status and coreDb points.

Select “Monitoring & control  System information” and the following information the system is displayed or not depending on whether the corresponding monitoring point was included or not in coreDb. In the following image, for each data, the supervision point that must be included in coreDb is indicated in a blue square.

R&D Digital Seville

Pag 41

20/03/2020

Figure 38 – Monitoring and Control view – System information

User Manual – AB_AI

Please take into account that the correspondent supervision points must be installed, otherwise, you will see a warning like the one in the example above (PLC information not available).

For an AB_AI module, the showed points are the followings:

Figure 39 – Monitoring and Control – Status.

Figure 40 – Monitoring and Control – Analog.

Pag 42

R&D Digital Seville

User Manual – AB_AI 20/03/2020

For all types of points, each page has the same format. If the user locks the signal and click in in the “value” column, the value of the correspondent signal can be changed.

If the user locks the signal and click in in the “quality” column, the value of the correspondent signal can be changed.

Each code of quality bit has a different meaning. See next tables to know the description of each one.

Table 2 - Local quality bits

Values (Hexadecimal) Description

0x00000000 OK

R&D Digital Seville

Pag 43

20/03/2020 User Manual – AB_AI

Values (Hexadecimal) Description

0x00000001 There has been an overflow

0x00000002

0x00000004

There has been a carry on a counter or a roll-over.

There has been a counter adjustment.

0x00000008

0x00000010

0x00000020

0x00000040

Excessive changes in a digital input.

Locked Point (blocked)

Point manually replaced (manual)

The point has not yet been written into the database (No refresh)

0x00000080

0x00000100

0x00000200

0x00000400

0x00000800

0x00001000

Invalid value (Error)

The value of the item has exceeded Highest Limit Alarm.

The value of the item has exceeded High Limit Alarm.

The value of the point has fallen down of Low Limit Alarm.

The value of the point has fallen down of Lowest Limit Alarm.

Invalid time.

Table 3 - Quality bits from the Device

Values (Hexadecimal) Description

0x00000000

0x00010000

0x00020000

0x00040000

0x00080000

0x00100000

0x00200000

0x00400000

0x00800000

0x10000000

OK

There has been an overflow.

There has been a carry on a counter or a roll-over.

There has been a counter adjustment.

Excessive changes in a digital input.

Locked Point.

Point manually replaced.

The point has not yet been written into the database.

Invalid value.

Invalid time.

NOTICE

If more than one error is detected for a signal, the hexadecimal value monitored for quality bits will result from the sum of all. For example:

0x00000001 indicates that an overflow has occurred and 0x00000002 indicates that there has been a carry on a counter or a roll-over. The value 0x00000003 would appear monitored.

Pag 44

R&D Digital Seville

User Manual – AB_AI 20/03/2020

Using WebTool

Saitel Webtool is the tool used for maintenance and monitoring of Saitel RTUs which is supplied with the baseline software platform. The values of all the coreDb signals in real-time can be monitored through the Saitel Webtool as well as the quality data related to these values.

Saitel Webtool has an access control that allows differentiating the users who are able to connect.

To get the window access, please write https://< CPU IP address> in the navigation address bar.

If the browser has been correctly configured, and the remote equipment is connected to the PC, the login window will prompt:

Figure 41 – Login window of Saitel Webtool.

Once the username and the password are introduced in the login window, the main workspace is displayed:

Figure 42 – Initial screen of Saitel Webtool.

This window shows:

• Information about the user who opened the session (Login: admin).

• Button “Exit” in order to close the current session.

• It is possible to select the language through the field “Language”.

• The main menu is located on the left side of the screen. Each button gives access to all the information of the RTU: o Information: General information about the CPU configuration.

R&D Digital Seville

Pag 45

20/03/2020 User Manual – AB_AI o Monitoring: Gives access to the coreDb tables and the values for each register and field.

o Bins: Gives access to the devices that have been configured in the RTU.

o Network configuration: Gives information about the physical devices and rooters.

Information

Clicking Information on the main menu, you can see general information about the system.

The following real-time information can be monitored on this menu:

• System’s Configuration

• Hardware Status

• Synchronization Status

• Software Versions

• Figure 43 – Information section

Monitoring

The top area of the screen includes the following information for any signal type (go to “Monitoring

 Status”, “Monitoring  Command”, “Monitoring  Analog” or “Monitoring  Setpoint”):

For each kind of modules, the information will be included in different tables. In the case of the

AB_AI module, the information for the acquisition points can be found in the Status and Analog screen.

In the status table, two signals are automatically created.

 COMM_DIAG: CPU diagnosis communication variable. 0 the module cannot communicate with the CPU. 1 the module is communicating properly with the CPU.

 HW_DIAG: Auto diagnosis hardware variable. 0 the module is correct. 1 the module has some hardware problem.

Figure 44 – Status monitoring screen.

Pag 46

R&D Digital Seville

User Manual – AB_AI 20/03/2020

In the analog table, the analog acquisition points can be monitored.

Figure 45 – Analog monitoring screen.

The information available for all types of signals is the following:

• Point name: Signal's name in coreDb.

• Value: Current value of the signal. This value is retrieved from the signal’s source and it is updated in Saitel Webtool according to the refresh period specified in the RT field.

• QF: Current quality flags of the value displayed for this signal

NOTICE

If the value of the quality bit associated to the signal is “Unrefreshed” (0x00000040) or “Invalid”

(0x00000080), the signal value will be “???”.

Clinking in “Set”, the value and the quality flag can be modified.

Figure 46 – Set Value screen.

R&D Digital Seville

Pag 47

20/03/2020 User Manual – AB_AI

Each code of quality bit has a different meaning. See next tables to know the description of each one.

Table 4 - Local quality bits

0x00000000

0x00000001

0x00000002

0x00000004

0x00000008

0x00000010

0x00000020

0x00000040

0x00000080

0x00000100

0x00000200

0x00000400

0x00000800

0x00001000

Values (Hexadecimal) Description

OK

There has been an overflow

There has been a carry on a counter or a roll-over.

There has been a counter adjustment.

Excessive changes in a digital input.

Locked Point (blocked)

Point manually replaced (manual)

The point has not yet been written into the database (No refresh)

Invalid value (Error)

The value of the item has exceeded Highest Limit Alarm.

The value of the item has exceeded High Limit Alarm.

The value of the point has fallen down of Low Limit Alarm.

The value of the point has fallen down of Lowest Limit Alarm.

Invalid time.

Table 5 - Quality bits from the Device

Values (Hexadecimal) Description

0x00000000

0x00010000

0x00020000

OK

There has been an overflow.

There has been a carry on a counter or a roll-over.

Pag 48

R&D Digital Seville

User Manual – AB_AI

0x00040000

0x00080000

0x00100000

0x00200000

0x00400000

0x00800000

0x10000000

There has been a counter adjustment.

Excessive changes in a digital input.

Locked Point.

Point manually replaced.

The point has not yet been written into the database.

Invalid value.

Invalid time.

20/03/2020

NOTICE

If more than one error is detected for a signal, the hexadecimal value monitored for quality bits will result from the sum of all. For example:

0x00000001 indicates that an overflow has occurred and 0x00000002 indicates that there has been a carry on a counter or a roll-over. The value 0x00000003 would appear monitored.

Firmware Update

Once the ITB is configured, the HU module (HU_A or HU_B) already knows the type of acquisition blocks that are been installed and their corresponding addresses.

To update the software of the AB_AI module, you need:

• A console connection with the HU.

• AB_AI module must be correctly addressed and working fine in the ITB (LED Run must be blinking).

• AB_AI.bin file with the new version. This file must be available in the flash folder of the HU. If not, you can contact Schneider Electric in order to ask for it. Use an SFTP client and transfer this binary file into the HU flash folder.

The console tool can be executed using any commercial tool for serial or SSH connection. In this manual, PuTTy software is used.

Open a serial connection as follow:

Figure 47 – Putty configuration.

R&D Digital Seville

Pag 49

20/03/2020 User Manual – AB_AI

SSH connection via Ethernet can be used too. More information about the console use in the HU user manual. In the following picture, HUe is used as CPU:

Figure 48 – SSH connection.

INFORMATION

If the baseline includes the cybersecurity brick, you need to login in the console with Installer .

No other user has permissions to execute this operation. Please, consult the HU user manual for more information.

If the file AB_AI.bin is available in the flash folder, use one of the following commands to upgrade the software of AB_AI modules:

Table 6 – Upgrading AB_AI software.

Module

All modules

By position

AB_AI

File

*.bin

Command claqUpgrade “all”

Description

It updates all the acquisition AB addressed in the ITB. You need to use the adequate file for each block.

AB_AI.bin claqUpgrade “<position>” It updates the module AB_AI with the <position> address.

AB_AI.bin claqUpgrade “all AB_AI” It updates all the AB_AI modules installed in the ITB.

INFORMATION

Console commands are case-sensitive, and quotation marks must be included.

Pag 50

R&D Digital Seville

User Manual – AB_AI 20/03/2020

After running the command, the console will show some messages indicating the process status.

Finally, if no problem is found, we will have updated the firmware of the modules.

R&D Digital Seville

Pag 51

20/03/2020 User Manual – AB_AI

5 Technical Specifications Table

Pag 52

R&D Digital Seville

User Manual – AB_AI

Features

Hardware

Software

Signal type.

Input type

Converter

Differential

Voltage from factory

Current, using an external resistor ( 250 Ω )

16-bits sigma-delta

Accuracy

Input impedance

Better than 0.1% at 25 ºC

200 kΩ

Voltage tolerance in common mode > 15 V

Field connection. Terminal / Flat ribbon.

Consumption

Weight

Dimensions

Protection

0.6 W

427 g

129 x 94 x 60 mm

Overvoltage

Processing

Common mode rejection ratio.

Parameterization

Digital filtering.

Scaling to engineering units.

Range limits detection.

Value change detection.

Zero value cancellation.

90 dB

Configurable range by channel:

• ±5 V

DC

/ 0 - 5 V

DC

.

• ±20 mA / 0 - 20 mA / 4 - 20 mA

Ordering Options

20/03/2020

CE Mark

Standards, Directives and harmonized norms.

RoHS

Environmental tests

R&D Digital Seville

LVD – Low Voltage Directive

EMC – Electromagnetic Compatibility

RoHS 2

WEEE – Waste Electrical and Electronic

Equipment

Directive 2011/65/UE

Cold - EN 60068-2-1:2007

Dry heat - EN 60068-2-2:2007

Damp heat - EN 60068-2-30:2005

Directive 2014/35/UE

Directive 2014/30/UE

Directive 2011/65/EU, according to RD 219/2013

Directive 2012/19/UE according to RD 110/2015

Verification of Lead, Cadmium, Mercury, Chrome and Bromine

-20ºC during 16h (100h)

+80ºC during 16h (100h)

25-60ºC with 95%RH during 24h

Pag 53

20/03/2020

EMC Directive

Tests according to

Emission

Immunity

User Manual – AB_AI

EN 60870-2-1 (1996)

IEC/TS 61000-6-5 (2015)

Radiated emissions

EN 55022:2006 + A1:2007

Conducted emissions

EN 55022:2006 + A1:2007

Electrostatic discharges (ESD)

EN 61000-4-2:2009

Radiated, radio-frequency, electromagnetic field

EN 61000-4-3:2006 + A2:2010

Fast transients common mode

EN61000-4-4:2012

Surges, line to line and line to ground

EN 61000-4-5:2006

From 30 to 1000 MHz (Class A)

From 0.15 to 30 MHz (Class A)

By air ±8 kV and by contact ±6 kV (Level 3)

From 80 to 2700 MHz (Level 3).

Power port: ±4 kV, 5kHz.

Communications ports: ±4 kV 5kHz and 2.5kHz.

I/O ports: ±4 kV 5kHz (Level 4).

Power: ±4 kV symmetric and asymmetric (Level 4)

Power: ±4 kV, 5kHz.

Communications: ±4 kV CM, ±2 kV DM (Level 4).

I/O: ±4 kV CM, ±2 kV DM

RF common mode

EN 61000-4-6:1996 + A1:2001

Power frequency magnetic field

EN 61000-4-8:2010.

Power frequency common mode disturbances

EN 61000-4-16:1998

Damped Oscillatory wave

EN 61000-4-18:2007 + A1:2010

10 V

RMS

0.15-80MHz 80% AM (Level 3).

100 A/m, 1000 A/m 3s (Level 4).

30V 50Hz, 300V 50Hz 1s (Level 4).

Power, Communications and I/O:

1kV DM, 2.5kV CM (Level 4), (f=1MHz)

Pag 54

R&D Digital Seville

User Manual – AB_AI

Index of Figures

20/03/2020

Figure 1 – Barrier of protection for elements with dangerous voltages. ....................................................................... 9

Figure 2 – Yellow and Green cable for earthing. ........................................................................................................ 10

Figure 3 – Terminal for functional earth (EMC). ......................................................................................................... 11

Figure 4 – Example of earthing for EMC. ................................................................................................................... 11

Figure 5 – Technical label. .......................................................................................................................................... 13

Figure 6 – Saitel DR. .................................................................................................................................................. 17

Figure 7 – Functional block diagram........................................................................................................................... 18

Figure 8 – AB_AI Module ............................................................................................................................................ 18

Figure 9 – AB_AI P/N description. .............................................................................................................................. 19

Figure 10 – AB_AI - Hardware block diagram ............................................................................................................ 19

Figure 11 – Mount bracket on DIN rail. ....................................................................................................................... 23

Figure 12 – Saitel DR module on a DIN rail. .............................................................................................................. 23

Figure 13 – Remove module. ..................................................................................................................................... 23

Figure 14 – B1 and B2 terminal blocks wiring. ........................................................................................................... 24

Figure 15 – B1 and B2 terminal blocks wiring. ........................................................................................................... 24

Figure 16 – Analog inputs wiring. ............................................................................................................................... 24

Figure 17 – LED indicators. ........................................................................................................................................ 25

Figure 18 – Adding a new RTU. ................................................................................................................................. 28

Figure 19 – ITB. .......................................................................................................................................................... 28

Figure 20 – Auto Address. .......................................................................................................................................... 29

Figure 21 – Adding an AB module. ............................................................................................................................. 29

Figure 22 – Adding a configuration. ............................................................................................................................ 29

Figure 23 – Configuration edition ................................................................................................................................ 30

Figure 24 – Changing the ITB configuration. ............................................................................................................. 30

Figure 25 – Configuring local acquisition for Saitel DR. ............................................................................................ 31

Figure 26 – Field signals and points in coreDb. ........................................................................................................ 31

Figure 27 – AB_AI field signals. .................................................................................................................................. 32

Figure 28 – Information of analogical inputs in CoreDb. ............................................................................................ 33

Figure 29 – Point wizard. ............................................................................................................................................ 33

Figure 30 – Saitel WebTool Menu. ............................................................................................................................. 36

Figure 31 – Claq Device in Saitel WebTool. ............................................................................................................... 36

Figure 32 – AB_AI module calibration. ....................................................................................................................... 36

Figure 33 – Saitel WebApp Menu. .............................................................................................................................. 37

Figure 34 – AB_AI module calibration. ....................................................................................................................... 38

Figure 35 – Disclaimer information. ............................................................................................................................ 39

Figure 36 – Access screen ......................................................................................................................................... 39

Figure 36 – Home view. .............................................................................................................................................. 40

Figure 38 – Monitoring and Control view – System information ................................................................................. 42

R&D Digital Seville

Pag 55

20/03/2020 User Manual – AB_AI

Figure 39 – Monitoring and Control – Status. ............................................................................................................. 42

Figure 36 – Monitoring and Control – Analog. ............................................................................................................ 42

Figure 41 – Login window of Saitel Webtool. ............................................................................................................. 45

Figure 42 – Initial screen of Saitel Webtool. ............................................................................................................... 45

Figure 43 – Information section .................................................................................................................................. 46

Figure 44 – Status monitoring screen. ........................................................................................................................ 46

Figure 45 – Analog monitoring screen. ....................................................................................................................... 47

Figure 46 – Set Value screen. .................................................................................................................................... 47

Figure 47 – Putty configuration. .................................................................................................................................. 49

Figure 48 – SSH connection. ...................................................................................................................................... 50

Pag 56

R&D Digital Seville

User Manual – AB_AI

Index of Tables

20/03/2020

Table 1 - AB_AI - LED indicators meaning ................................................................................................................. 25

Table 2 - Local quality bits .......................................................................................................................................... 43

Table 3 - Quality bits from the Device ........................................................................................................................ 44

Table 4 - Local quality bits .......................................................................................................................................... 48

Table 5 - Quality bits from the Device ........................................................................................................................ 48

Table 6 – Upgrading AB_AI software. ........................................................................................................................ 50

R&D Digital Seville

Pag 57

20/03/2020

Glossary

A

A : Ampere.

AAP : Automatic Addressing Procedure.

AB : Saitel DR Acquisition Block.

AB_AC : Direct measurements Acquisition Block.

AB_AI : Analog Inputs Acquisition Block.

AB_AO : Analog Outputs Acquisition Block.

AB_DI : Digital Inputs Acquisition Block.

AB_DIDO: Digital Inputs and Outputs Acquisition Blocks.

AB_DO: Digital Outputs Acquisition Blocks.

AB_MIO: Multiple Inputs and Outputs Acquisition Block.

AB_SER: Communication module for expansion.

AC: Alternate Current.

AI: Analog Input.

AO: Analog Output.

AWG: American Wire Gauge .

B

Bps : Bits per second .

C

ºC: Celsius degree.

COM: Puerto de comunicaciones.

CPU: Central Processing Unit.

CTS: Clear to Send.

D

DC : Direct Current.

DI : Digital Input.

DIN : Deutsches Institut für Normung.

DO : Digital Output.

DRAM : Dynamic Random Access Memory.

E

EMC: ElectroMagnetic Compatibility.

EPROM : Erasable Programmable Read Only Memory

Pag 58

User Manual – AB_AI

R&D Digital Seville

User Manual – AB_AI

F

FTP : File Transfer Protocol.

G g : Gram.

GPS : Global Positioning System.

H

HU : Head Unit. Saitel DR CPU.

HU_A : Saitel DR Advanced Head Unit.

HU_AF : Saitel DR Advanced Head Unit with acquisition.

HU_B : Saitel DR Basic Head Unit.

HUe : Saitel DR High-Performance Head Unit.

Hz : Hertz.

I

IED : Intelligent Electronic Device.

I/O : Input / Output.

IRIG : Inter Range Instrumentation Group.

IRIG-B : Mode B of the standard IRIG.

ISO 9001 : International standard for Quality Systems.

ITB : Intelligent Terminal Block.

K

KB : Kilobyte. kHz : Kilohertz.

L

LAN : Local Area Network.

LED: Light Emitting Diode.

M mA: Milliampere.

MHz: Megahertz.

MB: Megabyte.

Mbps: Megabits per second. m : Meter. mm: Millimeter. ms : Millisecond.

R&D Digital Seville

Pag 59

20/03/2020

20/03/2020

N

N/A : Non-Application.

P

PC : Personal Computer.

PPS : Pulses per Second.

PS : Power Supply.

PWR : Power.

R

RAM : Random Access Memory.

RS-232 : Communication standard.

RS-485 : Multipoint differential Bus.

RTDB : Real Time DataBase.

RTS : Request To Send.

RTU : Remote Terminal Unit.

Rx : Reception

S s : Second.

SCADA : Supervisory Control And Data Acquisition.

SNTP : Simple Network Time Protocol.

SRAM : Static Random Access Memory.

T

TCP/IP : Transmission Control Protocol/Internet Protocol.

TFTP : Trivial File Transfer Protocol.

TU : Terminal Unit.

Tx : Transmission.

V

VAC : Volt of Alternate Current.

VDC : Volt of Direct Current.

W

W : Watt.

X

XU: Expansion Unit.

Pag 60

User Manual – AB_AI

R&D Digital Seville

Schneider Electric

C/ Charles Darwin s/n

Parque Científico y Tecnológico de la Cartuja

Seville, Spain

©2020 All rights reserved. The information contained in this document is confidential and is owned by Schneider Electric. It cannot be copied or distributed in any way, unless there is express written authorization by Schneider Electric.

Although this information was verified at the time of publication, may be subject to change without notice.

SE-M556-USR-01 03/2020

R&D Digital Seville

Printed in:

Monday, April 6, 2020