Below you will find brief information for Quantum 140 CPU Series, Quantum 140 NOE Series. This user manual outlines the comprehensive steps for configuring TCP/IP communication within your industrial control system using Unity Pro. It covers essential setup procedures for Ethernet networks, including IP addressing, messaging, and advanced features like I/O scanning for periodic data exchange, Global Data for real-time variable synchronization, SNMP for network management, and bandwidth monitoring. This guide ensures efficient and reliable operation of Quantum PLCs with diverse Ethernet devices.
Advertisement
Advertisement
Quantum with Unity Pro
TCP/IP Configuration
User Manual
eng
2
Document Set
Document Set
Presentation
This package contains the following manuals: l l l l l l
Quantum and Premium Communication Architecture Reference Manual
140 EIA 921 00 Quantum AS-i-Bus Interface Module User Manual
Quantum TCPIP/IP Configuration User Manual
Quantum Modbus Plus Network Modules
Quantum Ethernet Network Modules User Manual
140 ESI 062 10 Quantum ASCII Interface Module User Manual
3
Document Set
4
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Ethernet - General Information . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 2
Start Communication with Unity Pro . . . . . . . . . . . . . . . . . . . . 15
2.1
Add a new network to the Communication folder . . . . . . . . . . . . . . . . . . . . . . . . 18
2.2
Link between Configuration and Communication . . . . . . . . . . . . . . . . . . . . . . . . 23
Chapter 3
Software Settings for Ethernet Communication . . . . . . . . . . . 25
3.1
Selecting the Quantum NOE Ethernet Module . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.2
3.3
Quantum NOE Ethernet Messaging Configuration . . . . . . . . . . . . . . . . . . . . . . . 30
3.4
Quantum NOE I/O Scanner Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
5
6
3.5
Planning the Global Data (Publish / Subscribe) System . . . . . . . . . . . . . . . . . . . 38
Quantum NOE Global Data Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
3.6
3.7
Address Server Configuration / Faulty Device Replacement . . . . . . . . . . . . . . . . 64
Quantum NOE Address Server Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
3.8
Quantum NOE Bandwidth Monitor Configuration . . . . . . . . . . . . . . . . . . . . . . . . 71
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Safety Information
§
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will
result in death, serious injury, or equipment damage.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
7
Safety Information
PLEASE NOTE
Electrical equipment should be serviced only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. This document is not intended as an instruction manual for untrained persons.
© 2003 Schneider Electric All Rights Reserved
8
About the Book
At a Glance
Document Scope
This documentation describes hardware and software installation procedures for the
TCP/IP bus.
This documentation is valid for Unity Pro from version 1.0.
Validity Note
The data and illustrations found in this documentation are not binding. We reserve the right to modify our products in line with our policy of continuous product development. The information in this document is subject to change without notice and should not be construed as a commitment by Schneider Electric.
Related
Documents
Title of Documentation
Quantum Hardware Reference Manual
Quantum Discrete and Analog I/O Reference Manual
Quantum Experts and Communication Reference Manual
Grounding and Electromagnetic Compatibility of PLC Systems
User Manual
Quantum and Premium Communication Architecture Reference
Manual
Reference Number
UNY USE 10010V10E
UNY USE 10010V10E
UNY USE 10010V10E
UNY USE 10010V10E
Part of this package
Note: The above mentioned documentations are only available in online form at this time.
9
About the Book
Product Related
Warnings
Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have any suggestions for improvements or amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical, including photocopying, without express written permission of
Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this product. For reasons of safety and to ensure compliance with documented system data, only the manufacturer should perform repairs to components.
When controllers are used for applications with technical safety requirements, please follow the relevant instructions.
Failure to use Schneider Electric software or approved software with our hardware products may result in injury, harm, or improper operating results.
Failure to observe this product related warning can result in injury or equipment damage.
User Comments
We welcome your comments about this document. You can reach us by e-mail at
10
Ethernet - General Information
1
Ethernet and 802.3
General description
Ethernet was introduced in 1980 as Ethernet 1 and developed by the DEC, Intel and
Xerox companies. This Ethernet later formed the basis of the 802.3-LAN from IEEE, that was published as the ISO standard in 1990.
Since 1990, Ethernet products have been produced almost exclusively according to the 802.3 standard.
The topology of an Ethernet corresponds to that of a bus system. However, the physical cabling can be made in point to point form. Hubs/Switches form the logical bus of the Ethernet from a physical point.
11
Ethernet - General Information
Framework formats
Ethernet-LAN und 802.3-LAN haben unterschiedliche Rahmenformate. The different formats are shown below.
Ethernet frame format
Preamble Destination
8 Bytes 6 Bytes
Source
6 Bytes
Protocol
2 Bytes
Data
n Bytes
FCS
4 Bytes
Preamble
8 Bytes
SFD
1 Bytes
802.3-frames (MAC frame format)
Dest.
Source Length
6 Bytes 6 Bytes 2 Bytes
DSAP
1 Byte
Logical Link Control
SSAP CTL
1 Byte 1 (2) Byte
FCS
DATA and PAD
Field n Bytes 4 Bytes
The following table contains a description of the frame parameters for Ethernet and
802.3.
Parameter Description
Preamble Identifies the prefix of an Ethernet / 802.3 frame.
Used for synchronizing the destination.
SFD The SFD field has the bit pattern 10101011 and identifies the start of the frame.
Destination Target address of the destination
Source
Length
Protocol
DSAP
Address of origin of the sender
Gives the number of bytes in the LLC (Logical Link Control) data field (not with Ethernet frames).
Specifies the protocol used (not for 802.3 frames).
(Destination Service Access Point)
Destination address (SAP) for destinations. The DSAP identifies the transfer interface to the next highest protocol (e.g. E0h=IPX).
SSAP
CTL
Data
(Source Service Access Point)
Destination address (SAP) for sources. The SSAP identifies the transfer interface to the next highest protocol (e.g. E0h=IPX).
(Control Field)
The CTL field is 2 bytes long if the frame contains sequential number. In all other cases it is 1 byte long.
(Also Data and PAD Field)
Logging the data to be transferred. Since every Ethernet frame must be a minimum of 64 bytes long, and 18 bytes are used by the MAC Header and Trailer, the minimum length of the data section is 46 bytes. If the useful load of the frame is less than 46 bytes, the frame is padded out to fill the prescribed length (padding).
FCS (Frame Check Sequence)
The checksum is formed in the CRC procedure (CRC=Cyclic Redundancy Check). Frames with invalid checksums are rejected.
12
Ethernet - General Information
LAN Addresses
IPv4 and IPv6
The Internet Protocol (IP) is the lowest layer in an Internet. The IP is defined in RFC
791. The Transmission Control Protocol (TCP) is set on the IP. The applications refer to this.
With networks that work with the TCP/IP protocol, and also on the internet, every PC can be identified via a numerical address. An IP address (Ipv4 standard) consists of four numbers separated by points, that can each be a value between 0 and 255. A typical IP address is "192.168.000.123". User PCs that access the internet via a
Provider also receive an IP address: It is always the same static IP address, or a new dynamic IP address every time a connection is made.
The IPv4, developed 20 years ago, uses a 32 bit address system, which theoretically allows up to four billion IP addresses. However in practice, a large part of these adresses cannot be used with group formation and other mechanisms.
The new IPv6 functions with a 128 bit system, an address space, which generally cannot be configured. This significantly increases the number of available IP numbers. Further advantages of the new IP address space include greater security, better support for real-time applications and a higher router capacity. IPv6 should be established by 2005. Backward compatibility with software and network components, which use the IPv4 standard, is to remain guaranteed according to the
IETF (Internet Engineering Task Force).
Subnet mask
IP addresses are 32 bit numbers (IPv4) that consists of two components, the power supply and the computer. There are three different types of IP network classes,
Class-A, Class-B and Class-C.
The subnet mask determines the size of a network. The combination of the subnet mask and the IP addresses results in the combination composition of the subnets and the number of possible network nodes in the subnet. A part of the IP address is therefore defined as the Subnet. This is defined via the Subnet mask.
Gateway address
The Gateway address determines, where the data packets are to be sent. This can depend on the local network card or a Gateway (Router) in the local subnet.
13
Ethernet - General Information
Cabling
Type
10BaseT
100BaseT
1000BaseT
10BaseF
There are different ways to create Ethernet LANs. They differ considerably in the type of cable and method of connection.
The following table shows the most common types of cabling.
Description
Twisted Pair
The most heavily used form of Ethernet is the 10xBaseT. 10BaseT was developed in 1986 as shielded cables. A constant development has occurred since then. The standard today is the 100BaseT. The first character in the label stands for the transmission speed in MBits/s.
A disadvantage of the 10xBaseT is the low maximum extension of the network. Only a maximum expansion of 205 m between two stations can be achieved. A station can be situated 100 m from the hub. The distance between two hubs can be 5 m.
Fiber Optic
Connection of Ethernet components using fiber optic cables.
The distance between the fiber optic module and hub can be up to 500 m.
14
Start Communication with
Unity Pro
2
At a Glance
Introduction
What's in this
Chapter?
This chapter presents how to start the configuration of an Ethernet network within
Unity Pro.
This chapter contains the following sections:
Section
2.1
2.2
Topic
How to configure the communication
Unity Soft Communication Links
Page
15
Start Communication with Unity Pro
16
2.1
Start Communication with Unity Pro
How to configure the communication
Overview
Overview
What's in this
Section?
This section describes how to configure the communication.
This section contains the following topics:
Topic
Add a new network to the Communication folder
Configure Network
Properties of a network
Delete an existing network folder
Page
17
Start Communication with Unity Pro
Add a new network to the Communication folder
Add a new network to the
Communication folder
After starting a new application, the Communication folder under Station tree branches the Network folder and the Routing table folder (only on Premium platform). These two folders are empty. Under the Network folder, the user can insert the networks by menu. A click on the right mouse-button above Network pops up a contextual menu. The user selects the type of network he wants to add. For easier use, a network name will be suggested with the prefix of the network type
(Ethernet_1 or ModbusPlus_1). By choosing a new network the next available number for the network is chosen automatically like e.g. Ethernet_1 then Ethernet_2 and so on. At any moment, the user may rename any NetLink.
The user can also attach a comment that describes each configured network. The
OK button adds the network as subfolder.
The names of network nodes are also called NetLink. These are the names of logical networks.
Station
Configuration
Derived Data Types
Derived FB Types
Variables & FB instances
Communication
Networks
Program
New Network
Station
Configuration
Derived Data Types
Derived FB Types
Variables & FB instances
Communication
Networks
Ethernet_1
Program
Animation Tables
Operator Screens
Documentation
1
Add Network
Network Comment
List of available Networks :
Ethernet
Ethernet_1
2
OK Cancel Help
18
Start Communication with Unity Pro
Configure Network
Configure
Network
On the network folder, by a double-clicking action or by the Open item on contextual menu, the editor of the corresponding communication screen is opened in order to set the specific network services.
The figure shows the contextual menu to start network properties
Station
Configuration
Derived Data Types
Modbus+_1
Derived FB Types
Open
Variables & FB instances
Communication
Export
Delete Del
Networks
Add user directory
Ethernet_1
Add Hyperlink
Program
Animation Tables
Zoom out
Operator Screens
Properties Alt+Enter
Documentation
Properties of a network
Properties of a network
The contextual menu proposes the user to see again the properties of a configured network. Here, the user can change the NetLink name and the associated comment.
The figure shows the Ethernet property window
Station
Configuration
Derived Data Types
Properties Network Ethernet_1
Derived FB Types
Variables & FB instances
Communication
Network Comment
List of available Networks :
Ethernet
Networks
Ethernet_1s_1
Program
Export
Animation Tables
Operator Screens
Delete Del
Add user directory
Documentation
Add Hyperlink
Zoom out
Properties Alt+Enter
Change Name :
Ethernet_1
OK Cancel
19
Start Communication with Unity Pro
Delete an existing network folder
Delete an existing network folder
With a right-mouse-click above the network folder, a contextual menu appears. Here the user is able to delete the network configuration. In this case, the subfolder of the network will also be removed in application browser.
Station
Configuration
Derived Data Types
Derived FB Types
Variables & FB instances
Communication
Delete Network...
Remove this Network ?
Ethernet_1
OK Cancel
Networks
Ethernet_1
Note: If this removed network was previously attached to a communication module, this module loses its link and it will work with its default parameters.
20
2.2
Start Communication with Unity Pro
Unity Soft Communication Links
At a Glance
Overview
What's in this
Section?
This section presents the principle of communication implementation and describes the relationship between software configuration of networks and the hardware configuration of the network controllers.
This section contains the following topics:
Topic
Communication Configuration Principle
Link between Configuration and Communication
Link between data and communication
Page
21
Start Communication with Unity Pro
Communication Configuration Principle
Introduction
Configuration
The configuration of communication links between different devices with Unity Soft l l l includes three different configuration parts.
Configuration of the Network Controller
Configuration of the Logical Network
Configuration of Network Variables
The Communication Configuration supports the "Free Mode" of Unity Soft. That means the user can first configure the module and then the Communication or the user can configure the communication and then the module.
This will be provided through a NetLink that must be selected in the module configuration. The network variables including in the VAR folder are linked with a group name that defines an IP domain over Internet network.
The illustration shows the three parts involved in communication configuration:
STATION
VAR
COMM
two rk
Gr ou ps
o f ne bl var ia es
Network
Variables
GROUP NAME ca l
Lo gi net wo rk s
Network
Parameters
CONF
NET LINK
Ne tw or k m fig ur con od ul at io e ns
Module
Parameters
VAR
Data base
COMM
Data base
CONF
Data base
22
Start Communication with Unity Pro
Link between Configuration and Communication
NetLinks
During Unity Pro application design, the NetLinks are created and inserted on subfolder Communication under Network. These are the names of logical networks.
Under configuration folder, on the communication module node included in the current station, the list of existing NetLinks is proposed to select and attach one network to one module. Only the NetLink that can be managed by this module, are displayed in the list box on module configuration screen. No NetLink can be edited and created here (no edit box), but this list contains at least the No_Link field.
The following figure shows the window for the Ethernet link for the Quantum NOE module.
UNITY-Station
Variables
Communication
Network
Modbus+_A
Ethernet_1
Ethernet_2
Configuration
0 : X Bus
0 : PremiumDrop
0 : TSX RKY 12EX ef
5:
6:
2:
3:
0:
1:140 CPU 534
4: 140 NOE 771 11
1.4 : SubsetENETLF
ENETFE
Overview
General
Please choose a Network
No Link
No Link
ETHERNET_1
Attaching a
NetLink to a
Module
When a network is attached to a module, the icon of the corresponding node is changed and the network editor displays the address of the module in the rack .
The Icon in the Network folder indicates whether the link is attached to a module or not:
Icon when no communication module is attached to the NetLink
Icon when a communication module has been attached to the NetLink
23
Start Communication with Unity Pro
Link between data and communication
Network
Variables and
Groupes
Structural view
Station
Configuration
Derived Data Types
Derived FB Types
Variables
Communication
Networks
Ethernet_plant
Ethernet_PLC
Program
Animation Tables
Operator Screens
Documentation
The groups of Ethernet network variables are created in the Ethernet network communication folders. An IP domain determines a group. In Unity Pro, one network can support only one group.
In Data Editor, the list of all current groups is provided to select in which group each
Ethernet network variables is included. Nevertheless, the group field is also a free entry editing box, in order to give a group name not yet defined in communication folder. The build step checks this link.
The illustration shows corresponding fields in Communication configuration and the
Data Editor:
Ethernet_PLC
Global data configuration
Health time out 300
Distribution period 2 ms scan
Group address 239
.
255
.
255
.
255
Group name Group_1
Ethernet_plant
Messaging IO Scanning Address Server
Global data configuration
Health time out 250
Distribution period 5 ms scan
SNMP
Global data
Group address
Bandwidth
239 .
255 .
255 .
255
Group name Group_2
Data Editor
Variables
Filter
DDT Types Function Blocks
Name
GD_MW500
GD_MW893
X_temperature
Valve12
X_Counter
P_x1
Name *
Type
Array[1...3] %MW500
Array[1...10
Address
%MW893
Int
Valve
Int
Int
%MW22
%MW381
%MW100
%MW200
DFB Types
Value Global...
0 SUB
0 PUB
0
0
PUB
SUB
0
100
SUB
NO
EDT DDT IODDT
Group
Group_1 1
Group_2
Enet ID
7
Group_1
Group_1
Group_2
8
7
10
Ethernet
010
Data Editor
Ethernet
24
Software Settings for Ethernet
Communication
3
At a Glance
Introduction
What's in this
Chapter?
This chapter contains all information required for configuring Ethernet communication software settings.
This chapter contains the following sections:
Section
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
Topic
Selecting the Ethernet Module
IP Configuration
Messaging
I/O Scanner Configuration
Global Data Configuration
SNMP Configuration
Address Server Configuration
Bandwidth Monitor Configuration
Page
25
Software Settings
26
Software Settings
3.1
Selecting the Ethernet Module
Selecting the Quantum NOE Ethernet Module
General description
After configuring Ethernet communication (see: Add a new network to the
Communication folder, p. 18) the Ethernet module parameters can be configured.
When you select the model family, all the corresponding communication module configuration options are displayed automatically. The module services allow the following settings to be made.
Table of module service configuration options:
Setting
No
Yes
Web
Description
Setting deactivated
Setting activated. Parameters are set using the Unity Pro menu window.
Setting activated. Parameters are set using the configured NOE Web pages.
Unity Pro menu window deactivated.
Not available for every model family.
Note: The availability of the displayed settings depends on the selected model family and can vary.
The screen shot shows an example of the menu window of the Ethernet module
NOE 771 x1 (TCP/IP 10/100 Regular connection).
ETHERNET_1
Model Family
TCP/IP 10/100 Regular Connection
Module IP Address
IP Address
0 . 0 . 0 . 0
Subnetwork Mask
0 . 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0 . 0 . 0 . 0
Module Utilities
YES Access Control
YES
YES
I/O Scanning
Global Data
YES
YES
SNMP
Address Server
Parameter description
Parameter
Model family
Slot
Module services
IP address of the module
Description
Quantum NOE Ethernet Module settings
Not used
For module service configuration options, see above.
Overview of the IP address parameter set.
27
Software Settings
After selecting the model family TCP/IP 10/100 Regular Connection, the following mask appears. The image also displays the activated module services.
ETHERNET_1
Model Family
TCP/IP 10/100 Regular Connection
Module IP Address
IP Address
0
. 0 . 0 . 0
Subnetwork Mask
0
. 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0
. 0 . 0 . 0
Module Utilities
YES
Access Control
YES
I/O Scanning
YES
Global Data
YES
SNMP
YES
Address Server
IP Confugration
Access Control
IP Address Configuration
Configured
I/O Sanning
IP adress
Subnetwork mask
Gateway address
From a server
WEB Configurator
Ethernet configuration
Ethernet II
139
. 124 . 10 . 14
255 . 255 . 0 . 0
139 . 124 . 10 . 1
802.3
Global Data SNMP Address Server Bandwidth
Note: The availability of the displayed register depends on the selected model family and can vary.
After selecting the Yes option in module services, the tab corresponding to the module is activated.
28
Software Settings
3.2
IP Configuration
IP Configuration
General description
The IP configuration tab enables you to configure the IP address settings. The settings are activated after the connection to the hardware and the configuration is downloaded to the PLC in the Quantum NOE Ethernet module.
The diagram shows the IP configuration for the Quantum NOE Ethernet model family.
ETHERNET_1
Model Family
TCP/IP 10/100 Regular Connection
Module IP Address
IP Address
0 . 0 . 0 . 0
Subnetwork Mask
0 . 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0 . 0 . 0 . 0
Module Utilities
YES Access Control
YES
YES
YES
YES
I/O Scanning
Global Data
SNMP
Address Server
IP Confugration
Access Control
IP Address Configuration
Configured
I/O Sanning
IP adress
Subnetwork mask
Gateway address
From a server
WEB Configurator
Ethernet configuration
Ethernet II
139 . 124 . 10 . 14
255 . 255 . 0 . 0
139 . 124 . 10 . 1
802.3
Global Data SNMP Address Server Bandwidth
Description of the selection properties
Selection
Configured
Client / Server
Description
Activate the IP address, Subnet mask and Gateway address. The data is activated after the configuration is downloaded to the PLC.
The Quantum NOE Ethernet module receives its IP address parameter through a BOOTP server on startup.
Web configuration
The IP address parameter settings are made on the embedded
Web page of the Quantum NOE Ethernet module.
Ethernet configuration
Select the default protocol as Ethernet or 802.3.
29
Software Settings
3.3
Messaging
Quantum NOE Ethernet Messaging Configuration
Introduction
Ethernet Messaging gives the user the opportunity to send and receive Ethernet messages. Data traffic is handled by the Client / Server procedure.
The illustration shows the Ethernet Messaging dialog box.
ETHERNET_1
Model Family
TCP/IP 10/100 Regular Connection
Module IP Address
IP Address
0 . 0 . 0 . 0
Subnetwork Mask
0 . 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0 . 0 . 0 . 0
Module Utilities
YES
Access Control
YES I/O Scanning
YES
YES
Global Data
SNMP
YES
Address Server
IP Configuration
Access Control
I/O Scanning Global Data SNMP Address Server
8
9
10
11
12
3
4
5
1
2
6
7
Connection configuration
Access
Slave IP Address
139.124.10.11
100.32.0.12
100.32.0.11
100.32.0.10
100.32.0.14
139.124.10.12
139.124.10.13
100.32.0.12
100.32.0.18
100.32.0.10
139.124.10.15
Bandwidth
Parameter description
Setting
Connection configuration
Access
Slave IP address
Description
Activates general data transfer
Activates data transfer between specific nodes.
Defines the node for the Ethernet Messaging procedure.
30
Software Settings
3.4
I/O Scanner Configuration
At a Glance
Introduction
What's in this
Section?
This chapter contains a description of the I/O Scanner configuration.
This section contains the following topics:
Topic
I/O Scanner Concepts
Quantum NOE I/O Scanner Configuration
Page
31
Software Settings
I/O Scanner Concepts
Overview
Introduction
I/O Scan List
The following information describes how to configure the I/O scanner.
The NOE 771 0x, -x1 and CPU 651 x0 modules provide an I/O scanner. It will be configured with the Schneider Electric programming packages or directly by using the internal NOE I/O Scanner Web site (NOE 771 0x and -x1 only). In both ways, the user can configure data and transfer it between network nodes without using the
MSTR instruction.
The I/O Scanner is a feature of the NOE module, which allows repeated reading and/or writing to Input/Output devices.
The I/O scan list is a configuration table that identifies the targets with which repetitive communication is authorized. The list contains enough information to enable each target to construct the MODBUS message addressed to the specified remote device and to designate where on the local controller the input and output data are to be mapped at the end of the scan. While the controller is running, the
NOE module transfers data to and from the controller’s registers and coils as indicated by the I/O scan list.
The user configures the I/O scan list with the Schneider Electric programming packages. There can be multiple instances of the I/O scan list (Peer Cop restrictions apply). The individual scan lists for each module are identified by the Quantum backplane slot number where the NOE is installed.
32
Software Settings
I/O Scanner
Definitions
Note: Health bits run differently.
l l
I/O Scanner health bits run left to right.
Global Data health bits run right to left.
The following table lists and defines the terms that are used to describe the I/O
Scanner operation.
Term
Scan List
Definition
The list of input and/or output devices that the NOE module is configured to scan.
Specific Input Input to the controller, on the backplane where the NOE resides.
Specific
Output
Output from the controller, on the backplane where the NOE resides.
Peer Cop
Ethernet I/O
Scanner
Legacy I/O Scanner support to upgrade MODBUS Plus I/O applications to
Ethernet.
Provides high performance cyclic communication service to the controller.
Quantum Status
Word
Information
For a better diagnostic of the Quantum CPU status, the programmer has the possibility to analyze the Quantum status words.
For detailed information refer to Quantum System Objects in the Unity Pro
Reference Manual.
Health Bits
Peer Cop and
Enhanced
MODBUS/TCP
Scanners
The following bits contain the health status for the Quantum I/O Scanner and/or the
Global Data.
l %SW139
Global Data and I/O Scanning utility load l %SW160 to %SW167 l
Device operating status determined by I/O Scanning
%SW168 to %SW171
Operating status of Global Data
For detailed information refer to Quantum System Words in the Unity Pro Reference
Manual.
The NOE 771 0x and -x1 module’s design provides you with the ability to configure its MODBUS I/O Scanner as either a Peer Cop or Enhanced MODBUS scanner. The determination as to which scanner is used depends on the programming package that is installed on your system.
33
Software Settings
Peer Cop I/O
Scanner
Features
The following table lists the characteristics of the Peer Cop based MODBUS I/O
Scanner.
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Output Words
Timeout Value
Input TimeOutState
IP Address
Remote Register Reference
Destination ID
Operation through a MODBUS Plus to
Ethernet bridge
Value
64
500
500
Global Setting (20 ms to 2 s in 20 ms increments
Global Setting (Zero or Hold)
Derived from MODBUS address (must be on
NOE’s subnet)
Not configurable - 400001 is used
Not settable, set to 0
Not supported
Enhanced
MODBUS I/O
Scanner
Features
The following table lists the characteristics of the Enhanced MODBUS I/O Scanner.
Parameter
Max. No. of Devices
Max. No. of Input Words
Max. No. of Input Words
Timeout Value
Input TimeOutState
IP Address
Destination ID
Operation through a MODBUS Plus to
Ethernet bridge
Operation through a MODBUS bridge
Value
64 or 128
4,000
4,000
Individual Setting (10 ms to 2 s in 10 ms increments
Global Setting (Zero or Hold)
IPv4 Address
Not settable, set to 0
Not supported
Supported
34
I/O Scanner
Support
Software Settings
The following table summarizes the permissible mix of I/O scanners and NOE modules per CPU.
Quantum CPU Type
140 CPU 311 10
140 CPU 434 12A
140 CPU 534 14A
140 CPU 651 50
140 CPU 651 60
140 CPU 671 60
6
6
6
6
6
No. of NOEs Supported
2
35
Software Settings
Quantum NOE I/O Scanner Configuration
Introduction
The I/O scanner offers the possibility to retrieve periodic data from Ethernet input/ output modules. This is carried out according to the Master / Slave procedure, whereby the Quantum NOE module represents the Master.
The screen shot shows the I/O scanner tab
IP Configuration Access Control
I/O Scanning
I/O Scanner configuration
Health Block : (%I / %IW)
Global Data
%IW0
SNMP Address Server Bandwidth
Slave IP
Address
7
8
5
6
9
1
2
3
4
139.124.10.81
139.124.10.82
139.124.10.83
139.124.10.84
139.124.10.85
139.124.10.86
Unit ID
255
0
100
255
28
255
255
Health
Timeout
(ms)
1500
0
65535
20000
100
0
1500
Repetitive rate (ms)
RD
Master
Object
RD
Slave
Index
100 %MW22 %MW0
80 %MW100 %MW1
60 %M76 %MW1
240 %M488 %MW0
0 %MW3 %MW0
0
%M640
%MW0
60
RD length
Last value
(input)
1 Maintain
2 Set to 0
0 Set to 0
1 Maintain
2 Maintain
1
Set to 0
Maintain
Set to 0
WR
Maste
Object
WR
Slave
Index
%MW20 %MW1
%MW77 %MW0
%M0 %MW0
%MW37 %MW1
%M248 %MW0
%M111 %MW1
Parameter description
Parameter
Slave IP address
Description
IP address of the input/output module
Unit ID
Specific ID of the input/output module
Health timeout (ms)
Time frames. After the time has run out the node can no longer send.
Rep rate (ms)
RD ref. master
RD ref. slave
RD length
Time after which the data can be periodically scanned.
Destination address in the controller for read periods. The read is carried out in words.
Source address of the input/output address for the read period.
Number of words to read
Last value (input)
WR ref. master
WR ref. slave
WR length
Description
Status of the inputs in the event of an error.
Source address in the controller for write periods. The write is carried out in words.
Destination address of the input/output address for the write period.
Number of words to write.
Infotext
36
Software Settings
3.5
Global Data Configuration
At a Glance
Introduction
What's in this
Section?
This chapter contains a description about Global Data configuration.
This section contains the following topics:
Topic
Planning the Global Data (Publish / Subscribe) System
Quantum NOE Global Data Configuration
Page
37
Software Settings
Planning the Global Data (Publish / Subscribe) System
Overview
Global Data service is a real time Publisher/Subscriber mechanism providing the most efficient data exchange for PLC application coordination.
Devices supporting Global Data are arranged in a distribution group for the purpose of application variable exchange and synchronization. Each Global Data device can publish up to one network (application) variable and subscribe up to 64 network
(application) variables.
The Quantum NOE’s embedded Global Data Configuration Web page provides a configuration screen to determine which and how many application variables are exchanged with this service. After configuration, the exchanges between all stations belonging to the same distribution group are done automatically.
The Global Data service uses %MW (4x registers) for Global Data exchanges.
Key Features of
Global Data
The main features for Global Data are: l l l
One publisher and many subscribers
A device can publish one network variable of up to 512 %MW words (4x registers)
A device can subscribe of up to 64 network variables of up to 2048 %MW words l l l l
(4x registers)
A device subscribes to the complete network variable
One distribution group per network IP address
Application defined publication rate
Up to 64 Global Data Network variables (numbered from 1 to 64) can be part of the data distribution group l
A NOE has only one multicast address; consequently, it can only publish and subscribe inside the group l A device can participate in several distribution groups by using multiple NOEs in the rack
Global Data has an advantage over Client / Server services when more than one subscriber is receiving the same data since only one transaction is necessary for all l l subscribers to receive the data.
This advantage offers two benefits:
Reduce overall network traffic
Ensure tighter synchronization of multiple subscribers
38
Software Settings
Planning Your
System
Configuration
The Global Data (Publish / Subscribe) utility is a powerful function incorporated into the NOE product line. Implementing Global Data requires a configuration that spans many PLCs throughout the system. Therefore, we recommend preplanning your installation before implementation. Work spent on preplanning saves time and money by reducing errors and unnecessary debugging time. Preplanning also serves as an aid to ensuring consistency throughout the system.
Go to paper before computer.
We offer the following table to help with your system planning. The table below is a graphic representation of a recommended configuration table for system planning, which we call the Global Data Planning Spreadsheet. You may create your own table using the format below or you may download a Microsoft Excel
TM
spreadsheet template which is available on the Schneider public Web site.
Here is the graphic representation of the Global Data Planning Spreadsheet.
Parameter
Checking
Variable ID
Symbol
1.
Length
(Registers)
Device Number Variable
Public.
Status
1
2
...
64
VALVE_STATUS
VALVE_CONTROL
PUMP_CONTROL
20
10
50
1
PUB
SUB
SUB
2
SUB
NONE
PUB
...
3
NONE
PUB
NONE
OK
OK
OK
Group IP Address
Multicast Filtering Enabled
Default 4x Address for Health
Distribution Period
Health Timeout
Data Zone
Device Publication Status:
Total Publication Size per Node:
Total Subscription Size per Node:
239.255.255.0
OFF
400100
10
1000
400200
OK
20
60
OK
50
20
OK
10
0
1. Entries or changes to the symbol (description) do NOT affect or change a variable or the system. The Symbol used in the Quantum product line has no relation to the Concept / Unity product line symbol.
39
Software Settings
Table of Global Data Limits
Parameter
Maximum number of publish variables per device
Limit
1
Maximum size for the publish variable
Maximum number of subscription variables per device 64
(63 if this device is publishing)
Maximum size for the subscripe variables per device
512 Registers = 512 Words (16 bits) =
1024 Bytes
2048 registers = 2048 Words (16 bits) =
4096 Bytes
Note: We recommend that you consider the following when planning.
l
10 to 20% Increase margin for growth
We suggest that you allow for a percentage increase in growth of any variable, l a 10 to 20% increase allowance should be sufficient.
Add at end
We recommend that you add variables at the end of the configuration because variables added at the end of the configuration do not affect the existing application address. Therefore, you avoid changing the existing addresses in your configuration, which can be a time consuming process.
Table of Global Data Planning Spreadsheet
Parameter
Parameter Checking
Variable Id
Symbol
Length Words (Registers)
Device Number
Variable Public. Status
Device Publication Status
Description
Reserved
Represents the Data ID on the NOE’s Global Data Configuration Web page
Symbolic name for Global Data exchange.
Length of Global Data information. Number of %MW words (4x registers).
Number of devices for the Global Data network. Of up to 64.
Automatic information of the correct publication status of the Global Data network.
Only by using the Microsoft Excel
TM
spreadsheet. Information per symbol.
Automatic information of the correct publication status of the Global Data network.
Only by using the Microsoft Excel
TM
spreadsheet. Information per device.
Total Publication Size per Node Publication size for the specific node. The maximum publication size is 512 words
(registers) per node
Total Subscription Size per
Node
Group IP Address Enabled
Subscription size for the specific node. The maximum subscription size is 2048 words (registers) per node
IP address for multicast networking. Identifies the stations distribution group. The address range is from 224.0.0.0 to 239.255.255.255
Multicast Filtering Enabled A check box for Ethernet switches that support multicast filtering.
40
Parameter
Default Address for
Health%MW (4x register)
Distribution Period
Health Timeout
Data Zone
Software Settings
Description
%MW (4x register) address for the Health bits. This is the memory area where the
Health bits are stored. It has the size of 4 words (registers).
Is the minimum number of controller scan times before an update will occur.
Is the maximum time between received subscriptions before a subscription is declared unhealthy (faulty). The value is measured in milliseconds and can be set to a value that ranges from 50 through 1000 ms (increase in units of 50 ms)
The starting address for the data. This are the registers where the data information are stored.
41
Software Settings
Quantum NOE Global Data Configuration
Introduction
Global data configuration is carried out in the network configuration as well as the data editor.
The variables for the Publish/Subscribe procedure are configured in the data editor.
The screen shot shows the network configuration Global data configuration settings.
ETHERNET_1
Model Family
TCP/IP 10/100 Regular connection
Module IP Address
IP-Adresse
0 . 0 . 0 . 0
Subnetwork Mask
0 . 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0 . 0 . 0 . 0
Module Utilities
YES Access Control
YES
YES
I/O Scanning
Global Data
YES
YES
SNMP
Address Server
IP Configuration Access Control
Global data configuration
I/O Scanning
HealthTimeout 1000 ms
Global Data
SNMP Address Server
Group address 239 . 10 . 10 . 10
Bandwidth
Diistribution period 10 scan Group name plantgrp
Health bit block (%I / %WIW) %IW1
Multicast Filtering
Parameter
Health timeout
Group address
Distribution time
Group name
Status bit block
Multicast filtering
Parameter description
Description
After this time period has run out, the data received becomes invalid.
Class D Multicast IP address. All nodes in the global data procedure use the same Multicast address for distributing or receiving data. The address range is: 224.0.0.0 to
239.255.255.255.
Time after which the data is received or sent. Minimum scan time of the PLC.
Logical name. Defines the varibale allocation to different communication configurations in the variablen editor.
Address for retrieving the status information of the global data procedure.
Activates an Ethernet switch on connection that supports Multicast filtering.
42
Software Settings
The screen shot shows an image of the data editor.
Variables
Filter
DDT Types
Function Blocks DFB Types
Name
Name
VALVE_STATUS
VALVE_CONTROL
PUMP_STATUS
*
Type
ARRAY[0..19] OF Word
ARRAY[0..9] OF Word
ARRAY[0..99] OF Word
EDT
Address
%MW200
%MW220
%MW230
Global ...
PUB
SUB
SUB
DDT
Group plantgrp plantgrp plantgrp
IODDT
2
3
Enet ID
1
Parameter description
Parameter
Name
Type
Address
Enet
Group
Enet ID
Description
Variables ID
Variable type
Variable address
Type of Global Data Variable. Options: No/Publish/Subscribe
Group name for allocating the variables of the existing network description. When creating the different Ethernet networks, a logical connection is arranged here between the network and the variable declaration.
Ethernet ID. Representation of the administrative order.
43
Software Settings
3.6
SNMP Configuration
At a Glance
Introduction
This chapter contains a description about how to configure a Simple Network
Management Protocol (SNMP).
Note: Simple Network Management Protocol (SNMP) is not supported by the
CPU 651 x0 modules.
What's in this
Section?
This section contains the following topics:
Topic
SNMP
ASN.1 Naming Scheme
Configuring a NOE with SNMP
Configuring a NOE with TFE Private MIB
Quantum NOE SNMP Configuration
Page
44
Software Settings
SNMP
Overview
This following information describes the Simple Network Management Protocol
(SNMP), which is configured on your NOE.
Introduction
Manager/Agent
Paradigm
Network management software allows a network manager to l l l
Monitor and control network components
Isolate problems and find their causes
Query devices such as a host computer, routers, switches, and bridges to determine their status l Obtain statistics about the networks to which they attach
Network management software follows the conventional client-server model.
To avoid confusion with other network communication protocols that use the client/ server terminology, network management software uses the following terms: l Manager
For the client application that runs on the manager’s computer l Agent
For the application that runs on a network device
The manager uses conventional transport protocols (e.g., TCP or UDP) to establish communication with the agent. Managers and agents then exchange requests and responses according to the network management protocol.
Simple Network
Management
Protocol
Your NOE module is configured with the Simple Network Management Protocol
(SNMP), which is the standard protocol used to manage a local area network (LAN).
SNMP defines exactly how a manager communicates with an agent.
The SNMP defines the format of the requests that a manager sends to an agent and the format of the replies that the agent returns to the manager.
The MIB
The Private MIB
Each object SNMP has access to has to be defined and given a unique name. Both the manager and agent program must agree on the names and the meanings of the fetch and store operations. The set of all objects SNMP can access is known as a
Management Information Base (MIB).
Schneider obtained a private MIB, Groupe_Schneider (3833). Under the Groupe
Schneider private MIB is a Transparent Factory Ethernet (TFE) private MIB. The
Transparent Factory SNMP embedded component controls the Schneider private
MIB function.
45
Software Settings
Choosing a
SNMP Manager
If you have a SNMP Manager already working, you may continue to use that SNMP
Manager. If you are selecting a SNMP Manager, there are many SNMP Managers on the market, and you may use any of these managers. You must use a SNMP
Version 1 compliant manager.
If you do not currently use a SNMP Manager in your organization and are evaluating
SNMP Managers for purchase, then we recommend that you consider the HiVision‚ with the ConnexView Add-On developed for use with Schneider Automation PLCs.
Please contact your Schneider Electric sales office for availability and pricing of
HiVision‚ and ConnexView‚.
46
Using a SNMP
Manager
Software Settings
2
3
4
The process for obtaining a SNMP Manager
Step
1
Action
Get Schneider
.mib
file from the NOE Web page.
You are going to find the
.mib
file as a packed file under /wwwroot/
SchneiderTFE.zip on your NOE module.
Compile
.mib
file in the compiler that comes with the NOE.
Load compiled
.mib
file to the SNMP manager.
When you are done, you will see the Schneider private MIB manager in your manager.
The process is simple.
Get file
Compile file
Load file into your manager
47
Software Settings
More SNMP
Information
SNMP and related subjects are well documented on Web sites and in many books l l
As of this writing, a useful description appears on Microsoft’s Technet pages.
Browse to http://www.microsoft.com/technet. Use the Search function to find
"Network Management for Microsoft Networks Using SNMP."
Use an Internet search engine to search for a SNMP introduction, a SNMP l tutorial, and other topics on SNMP.
The SNMP FAQ from the news group comp.protocols.snmp
appear on many
.com
and
.org
Web pages. Search for the combination of l
" comp.protocols.snmp
" and "
FAQ
."
A list of print books about SNMP appears in the SNMP FAQs. In addition, a search of most online retail book sites will yield a substantial list of titles.
ASN.1 Naming Scheme
ASN.1 Overview
Abstract Syntax Notation One (ASN.1) is a formal language for abstractly describing messages to be exchanged between distributed computer systems.
48
An Example
Software Settings
Objects in a MIB are defined with the ASN.1 naming scheme that assigns each object a long prefix that guarantees that the name will be unique. For example, an integer that counts the number of IP datagrams that a device has received is named: iso.org.dod.internet.mgmt.mib.ip.ipinReceives.
The following figure depicts the ASN.1 Naming Scheme example.
iso (1) org (3) dod (6) internet (1)
directory (1)
mgmt (2)
experimental (3)
mib (2)
system
(1) interfaces
(2)
ip (4)
address translation
(3) ipForwarding (1) ipDefaultTTL (2)
ipinReceives (3)
l l l
This object name is represented in an SNMP message by assigning each part an l l l l l integer. So, the above message would appear as 1.3.6.1.2.2.4.3.
Each integer has the following meaning.
1 = ISO (International Organization for Standardization)
3 = identified organization — one of branches under the ISO root
6 = U. S. Department of Defense (DOD) — one of the children under branch1.3
1 = the Internet subtree under 1.3.6
2 = the mgm branch — (one of seven) of the Internet subtree. It is managed by the Internet Assigned Numbers Authority, and includes the standard MIBs
2 = mib-2(1) group of managed objects
4 = ip — the mib-2(1) IP group (one of 11)
3 = ipinReceives — the MIB object
49
Software Settings
Configuring a NOE with SNMP
The Object
Identifier (OID)
SNMP Protocol
Data Units
In the ASN.1 Naming Scheme example, the MIB object identified by the notation
1.3.6.1.2.2.4.3 is referred to as the Object Identifier or OID. All OIDs can be envisioned as part of a tree structure which begins at the root (ISO) and branches out with each subtree identified by an integer.
SNMP uses Protocol Data Units (PDUs) to carry the requests and responses, between the manager and the agents, for the information contained in an OID.
As the following figure shows, the SNMP message is the innermost part of a typical network transmission frame.
IP
Header
Local
Network
Header
UDP
Header
SNMP
Message
Local
Network
Trailer
Version Community
GetRequest, SetRequest, or Trap PDU
The PDUs within the SNMP initiate the communication between the manager and the agents. l l l
The SNMP installed on your NOE module uses the following three PDUs.
GetRequest
SetRequest
Trap
GetRequest PDU
The GetRequest (shortened to Get) PDU is used by the SNMP manager to retrieve the value of one or more objects (OIDs) from an agent.
SetRequest PDU
The SetRequest (shortened to Set) PDU is used by the SNMP manager to assign a value to one or more objects (OIDs) residing in an agent.
Trap PDU
The Trap PDU is used by the agent to alert the manager that a predefined event has occurred.
50
Version &
Community
Identifiers
What Can Be
Configured
Software Settings
The version identifies the version number of the SNMP software being used by the manager and the agent. Your NOE supports Version 1 of the SNMP. The community is an identifier that you assign to your SNMP network. If community names for the manager and the agent do not agree, the agent will send an authentication failure trap message to the manager. If the community names and version number agree, the SNMP PDU will be processed.
Your NOE module can be configured to send an authentication trap to two SNMP managers if it receives a community name in a Get/Set request that does not match the configured name. Also, you can configure the SysContact and SysLocation via the configuration page in the module’s Embedded Web pages. After making changes in the SNMP Configuration Web page and to set those changes, reboot the module using hot swap.
51
Software Settings
Configuring a NOE with TFE Private MIB
Introduction
A MIB, a Management Information Base, is an element used in network management. Network management services are based on the need to monitor and to manage: l l l
Performance
Fault occurrences
Security
Each MIB contains a finite number of objects. Manage your MIB with a management station running an SNMP management application. The management application uses GETs and SETs to retrieve system information and to set system environment variables.
Note: The TFE private MIB is available only in the 140 NOE 771 -01, -11 and 140
NWM 100 00, the Transparent Factory / Real Time modules.
The 140 NOE 771 -00 and -10, the Transparent Factory modules, use the previous
MIB.
Schneider
Private MIB
Schneider Automation obtained a Private Enterprise Number (PEN) from the
Internet Assigned Numbers Authority (IANA). That number represents a subtree in the SNMP MIB, a number that is a unique identifier used for Groupe Schneider.
The object identifier for the root of the Groupe Schneider subtree is
1.3.6.1.4.1.3833
and represents a path to the subtree as follows: iso(1) org(3) dod(6) internet(1) private(4) enterprise(1)
GroupeSchneider(3833)
Transparent_Factory_Ethernet(1)
Under the GroupeSchneider private MIB is a Transparent Factory Ethernet (TFE) private MIB, Transparent_Factory_Ethernet(1).
52
Software Settings
TFE Private MIB
The Transparent Factory SNMP-embedded component controls the Schneider private MIB function. The Schneider private MIB, and associated services, perform
Network Management on all components of the system. The Transparent Factory private MIB provides the data to manage the main Transparent Factory communication services for all the communication components of the Transparent
Factory architecture (ETYs, NOEs, third party toolkit, ENTs, M1Es). The
Transparent Factory private MIB does not define the specific management applications and policies.
53
Software Settings
The diagram below illustrates the Schneider Electric (Groupe_Schneider (3833) private enterprise MIB subtree.
54
The Groupe_Schneider (3833) subtree is the root of Groupe Schneider's private
MIB in the Structure of Management Information (SMI) used by SNMP and defined in RFC-1155, which is a specification that defines the structure and identification of management information for TCP/IP-based Internets.
Software Settings
Transparent
Factory Ethernet
Subtree
The Transparent_Factory_Ethernet (1) subtree defines groups that support the
Transparent Factory Ethernet services and devices.
Service
Switch (1)
Port502_Messaging (2)
I/O_Scanning (3)
Global_Data (4)
Web (5)
Address_Server (6)
Equipment_Profiles (7)
Description
Subtree defines a brand of switches labeled:
ConneXium switches private MIB
Subtree defines objects for managing explicit client / server communications supporting applications, such as HMI, SCADA, or programming tools
Subtree defines objects for managing I/O device communications that use the I/O Scanner mechanism with the MB/TCP protocol
Subtree defines objects for managing the application coordination service using a publish / subscribe protocol
Subtree defines objects for managing the activity of the embedded Web servers
Subtree defines objects for managing the activity of the
BOOTP and (or) DHCP servers
Subtree identifies objects for each type of device in
Transparent Factory Ethernet's product portfolio
Device subtrees, or groups, will be defined for the following devices: l l l l l
Premium(1)
Quantum(2)
Generic_Device(3)
M1E(4)
ENT(5)
As devices are added to Schneider's catalog, Schneider's private MIB will be extended in the following manner: l
If needed, a Transparent Factory, communication-service object will be added for the new device in the corresponding Equipment_Profiles(7) subtree. As many l objects as needed can be added to this subtree.
If needed, a new branch will be added at the same level as
Transparent_Factory_Ethernet(1). This subtree will be created for productspecific objects (such as the ATV58 object under the IndustrialControl-
Products (3) subtree)
When a new device is created, a corresponding object description is created in the
ASN.1 format. The ASN.1 file(s) are then given to producers of SNMP manager software for inclusion in their products.
55
Software Settings
Port502
Messaging
Subtree
The Port502_Messaging (2) subtree, or group, provides connection management and data flow services. The following list describes the function of each object.
Service port502Status(1) port502SupportedProtocol(2) port502IpSecurity(3): port502MaxConn(4) port502LocalConn(5) port502RemConn(6) port502IpSecurityTable(7) port502ConnTable(8) port502MsgIn(9) port502MsgOut(10) port502MsgOutErr(11) port502AddStackStat(12) port502AddStackStatTable(13)
Description
Indicates the status of the service (Idle, Operational)
Indicates the supported protocols (MODBUS, Xway)
Indicates the status of the Port502 IP Security service
(enabled/disabled)
Indicates the maximum TCP connection number supported by the Port502 entity
Indicates the TCP connection number currently opened by the local Port502 entity
Indicates the TCP connection number currently opened by the remote entity to the local Port502 entity
Indicates a table containing the number of unsuccessful TCP connection open tries from a remote TCP entity
Indicates a table containing Port502 TCP specific information (MsgIn, MsgOut)
Indicates the total number of Port502 messages received from the network
Indicates the total number of Port502 messages sent from the network
Indicates the total number of error messages built by the Port502 messaging entity and sent to the network
Indicates the support of additional port502 stack statistics
1 - Disabled
2 - Enabled
Indicates additional stack statistics for Port502
(optional)
56
I/O Scanning
Subtree
Software Settings
The I/O_Scanning (3) subtree, or group, contains the objects related to I/O Scanning device management and associated MODBUS communications on Port502.
Service ioScanStatus(1) ioScanMaxDevice(2) ioScanPolledDevice(3) ioScanTransSend(4) ioScanGlbHealth(5) ioScanDeviceTable(6)
Description
Indicates the global status of the I/O Scanning service
1 - Idle
2 - Operational
3 - Stopped
Indicates the maximum number of devices supported by the I/O Scanning entity
Indicates the number of devices currently polled by the
I/O Scanning entity
Indicates the total number of transactions sent by the I/
O Scanning entity
Indicates the global status of health for the I/O Scanning service
2 - OK: Every remote I/O device is responding
4- Warning: At least one remote I/O device is not responding
Displays a table containing information on each remote devices polled by the I/O Scanning entity
57
Software Settings
Global Data
Subtree
The Global_Data (4) subtree, or group, contains the objects related to the Global
Data service.
Service glbDataStatus(1) glbDataMaxPub(2) glbDataMaxSub(3) glbDataPub(4) glbDataSub(5) glbDataPubErr(6) glbDataSubErr(7) glbDataGlbSubHealth(8) glbDataPubTable(9) glbDataSubTable(10)
Description
Indicates the global status of the Global Data service
1 - Idle
2 - Operational
3 - Stopped
Indicates the maximum number of published variables configured by the Global Data entity
Indicates the maximum number of subscribed variables configured by the Global Data entity
Indicates the total number of publications sent to the network
Indicates the total number of subscriptions received from the network
Indicates the total number of publication errors detected by the local entity
Indicates the total number of subscription errors detected by the local entity
Indicates the global status of health for the Global Data subscribed variables
2 - OK: The health status of all subscribed variables are
OK
4 - Warning: At least one subscribed variable has a health fault
Displays a table containing information on each published variable (the number of publications, the source IP address, the number of errors)
Displays a table containing information on each subscribed variable (the number of subscriptions, the source IP address, the number of errors, Health)
58
Web Subtree
Software Settings
The Web (5) subtree, or group, contains the objects related to the Web server service.
Service webStatus(1) webPassword (2) webSuccessfullAccess (3)
webFailedAttempts (4)
Description
Indicates the global status of the Web service
1 - Idle
2 - Operational
Indicates a switch to enable or disable the use of Web passwords
1 - Disabled
2 - Enabled
Indicates the total number of successful accesses to the Web site
Indicates the total number of unsuccessful accesses to the Web site
Address Server
Subtree
The Address_Server (6) subtree, or group, contains the objects related to the
Address Server service. The Address Server can be either a BOOTP server or a
DHCP server.
Service addressServerStatus(1)
Description
Indicates the global status of the addressServer service
1 - Idle
2 - Operational
59
Software Settings
Equipment
Profile Subtree
The Equipment_Profiles (7) subtree contains a set of common objects.
Service profileProductName(1) profileVersion(2) profileCommunicationServices
(3) profileGlobalStatus(4) profileConfigMode(5) profileRoleName(6) profileBandwidthMgt(7) profileBandwidthDistTable(8) profileLedDisplayTable(9) profileSlot(10) profileCPUType(11)
Description
Displays the commercial name of the communication product in a string form (for example: 140 NOE 771 11)
Displays the software version of the communication product in a string form (for example: Vx.y or V1.1)
Displays a list of the communication services supported by the profile (Port502Messaging, I/O scanning Messaging, Global Data, Web, and Address
Server)
Indicates the global status of the communication module
1 - nok
2 - ok
Indicates the IP configuration mode of the communication module
1 - Local: The IP configuration is created locally
2 - dhcpServed: The IP configuration is created by a remote DHCP server
Indicates the role name for the IP address management if it exists (Empty string if there is none)
Indicates the status of Bandwidth Management
1 - Disabled
2 - Enabled
Indicates the CPU time distribution between Global
Data, Port502 Messaging, I/O Scanning
Displays a table giving the name and the state of each module’s LEDs
Indicates the position of the communication module inside the rack if there is one. If there is no rack, the profileSlot value will be zero
Indicates that if the CPU type exists, this variable identifies the host for which that communication module is a part. If there is no host, the string is empty
profileTrapTableEntriesMax(12)
Indicates the maximum numbers of entries in the Trap
Table. This entry equals the number of possible remote managers
profileTrapTable(13)
Displays a table allowing you to enable or disable the private traps for each of the communication services
60
Service profileSpecificId(14) profileIpAddress(15) profileIpNetMask(16) profileIpGateway(17) profileMacAddress(18)
Software Settings
Description
Indicates a unique Profile Specific Identification inside the equipmentProfile object of the Schneider
Transparent Factory MIB. (For example the PLC
Premium family is 100)
Indicates the IP address of the SNMP agent
Indicates the subnet mask associated with the IP address of the SNMP agent. The value of the mask is an IP address with all the network bits set to 1 and all the host bits set to 0
Indicates the default Gateway IP address of the SNMP agent
Indicates the Ethernet media-dependent address of the SNMP agent
Private Traps and MIB Files
Traps are used to signal Status Changes to the manager. Using traps helps to avoid adding traffic.
The four status changes signaled by the trap are for the: l l l l
LEDs
Communication Ports
I/O Scanning Health Values
Global Data Health
The following list describes the characteristics of private traps, which means that l l they can: l Send messages to the two managers whose IP addresses are configured in the
SNMP configuration (either the PL7 or the Web page)
Use the community name given to this configuration
Enable or disable each of the Transparent Factory Ethernet Private MIB groups:
Switch (1), Port502_Messaging (2), I/O_Scanning (3), Global_Data (4), Web (5),
Address_Server (6), and Equipment_Profiles (7)
Private traps are described in the MIB ASN.1 description, which is contained in a
.mib
text file.
61
Software Settings
Quantum NOE SNMP Configuration
Introduction
The SNMP settings described are entered in the following mask.
The screen shot shows an image of the SNMP configuration.
IP Configuration Access Control
IP Address Managers
I/O Scanning Global Data
SNMP Address Server
Bandwidth
IP-Adress-Manager1 139 . 150 . 33 . 10 IP-Adress-Manager2 139 . 150 . 90 . 20
Agent
Location (SysLocation) MyLocation
Contact (SysContact) MyContact
Community names
Set public
Get public
Trap public
Security
SNMP manager
Enable "Authentification Failure" trap
Parameter description
Parameter
IP address manager1
IP address manager2
Location (SysLocation)
Contact (SysContact
SNMP manager
Setting
Getting
Trap
Activate "Authentication error" trapping device
Description
IP Address (Computer) of the SNMP responsibility
Alternative IP Address (Computer) of the SNMP responsibility, e.g. substitute.
Information about module location
Information about the system administrator
Reserved
Security setting for rights to modify the configuration.
(Public/Secret)
Security setting for rights to view the configuration settings. (Public/Secret)
Security setting for rights to receive SNMP information. (Public/Secret)
Message for faulty login.
62
Software Settings
3.7
Address Server Configuration
At a Glance
Introduction
What's in this
Section?
This chapter contains a description about the Quantum NOE Address Server configuration.
This section contains the following topics:
Topic
Address Server Configuration / Faulty Device Replacement
Quantum NOE Address Server Configuration
Page
63
Software Settings
Address Server Configuration / Faulty Device Replacement
Overview
The Address Server provides 2 capabilities:
1. Standard BOOTP Server Behavior
Enter the MAC Address and IP Configuration. The NOE BOOTP server will provide the IP configuration when the device sends a BOOTP request.
2. Faulty Device Replacement (FDR) Behavior
Enter the Role Name or the MAC Address of the device. The device will send its
Role Name or the MAC Address with its DHCP request. With the DHCP response from the NOE, the device will receive its IP Configuration, plus the name and location of a configuration file.
The next step for a FDR-compliant device is to download its configuration from the NOE.
Consult your Schneider Automation Sales Representative for the current list of
FDR-Compliant devices.
The Address Server in the NOE supports both modes at the same time. You select a mode by entering either the MAC Address or the Role Name in the Address
Server Node Configuration page. You may enter only one or the other, but not both.
The Faulty Device Replacement capability allows automatic configuration of FDRcompliant devices.
Identifying a Role
Name
Inherent in the discussion of Faulty Device Replacement is the idea of a Role Name.
A Role Name is a logical name that the user assigns to a device, a logical name that has a meaning within the application.
Some examples of a Role Name might be: l ENT_6 (6th Momentum ENT in your application) l OUTPUT_VALVE_2 (2nd Output Valve in your application)
Role Names are case sensitive.
64
Faulty Device
Replacement
Role Name
Software Settings
The Faulty Device Replacement service offers a method of handling device replacement without disrupting the system nor interrupting service. Should a device l l l fail, replacing that device is easy. When the new device is physically connected to the network, the system (including the new device) is able to
Provide the replacement device with the IP address of the previous device
Ensure that new device is working in the same manner as the previous device
Restore the I/O device application parameters in order to restart the device with the same configuration as before the failure
Faulty Device Replacement enables you to avoid configuring a new device when a faulty device is replaced: You enter the device name in the new device, and the task is completed. You have a new configuration scheme for I/O and smart devices, which allows: l l
Creating an automatic network configuration
Managing automatic application parameters
Faulty Device Replacement is implemented using the combination of DHCP and
FTP/TFTP standard protocols. The device implements a DHCP client and an FTP or TFTP client. Choosing between FTP and TFTP has no direct impact on your l l l system. The choice depends only on device memory footprint: TFTP is much smaller than FTP.
Faulty Device Replacement offers the following functionality l l
FDR Manager
FDR Agent
Faulty Device Replacement management is based on three entities:
Agent device embedding the DHCP client and FTP/TFTP client
DHCP server
FTP/TFTP server
The logical Role Name should be written on devices. The technician can get the new device from stores, enter the corresponding Role Name into the device, and place the device in the system. The device automatically gets its configuration and starts running with no further input from the technician. This process is designed to get your machine up and running quickly. All the technician has to do for any FDR compliant device is to enter the Role Name into the new device.
65
Software Settings
Address Server
Limits
This table displays the parameters and limits of the Address Server.
Parameter
Maximum number of Address Server entries
Maximum size of the configuration file per device
Total size of Faulty Device Replacement storage
Maximum Role Name size
Limit
128
4K bytes
512K bytes
16 Characters l l
Note: For the DHCP Server to work correctly the following must be observed:
Address class and subnet class configured for the devices has to match
Address class of the NOE and of the devices has to be the same
Operating on a
Corporate
Network
Available FDR
Agents
BOOTP and
DHCP
Compatible
Devices
Note: Operating on a corporate network l l
Before placing the NOE on a corporate network, Schneider Automation recommends that you discuss the installation with your MIS department. It is likely that your company's corporate network has at least one DHCP Server running already. If the NOE's DHCP server is running on the same network, it may disturb the network.
To avoid any possible problem related to the NOE's DHCP server on the corporate network, you have to ensure that the DHCP server is not running in the
NOE by not having address entries in the configuration. If there are no configured devices in the Address Server Configuration page, then the NOE will not start the
DHCP server.
Three FDR agents are available l l l
Momentum ENT
Micro ETZ
ATV58*
*Available 2002
The role-name.prm
configuration files are stored in the NOE in non-volatile memory. Therefore, after a power failure all configurations will be available.
Use either the MAC Address or the Role Name to assign IP addresses. Therefore, you may use the DHCP server with devices that support BOOTP only, such as
Momentum ENT v1.
66
Software Settings
Quantum NOE Address Server Configuration
Introduction
The Quantum NOE 771 module address server function enables the user to enter
Ethernet node addresses using BOOTP or DHCP. With BOOTP or DHCP, the IP address is assigned instead of the MAC address or the computer name.
Only Ethernet nodes provided in the list may refer to an IP address.
The screen shot shows the Server Address Configuration screen.
IP Configuration Access Control
HTTP modification
Locked in operation
I/O Scanning Global Data SNMP Address Server
BISCUIT
Password
Bandwidth
7
8
9
5
6
1
2
3
4
Client/Server address table
MAC address
00.00.54.00.1D.B7
00.00.54.A1.1D.B7
00.00.47.00.35.B7
Name
device_IO_1 device_IO_4
IP address
139.124.10.50
139.124.10.51
139.124.10.52
139.124.10.53
139.124.10.60
Netmask
255.255.0.0
255.255.0.0
255.255.0.0
255.255.0.0
255.255.0.0
Gateway
139.124.10.1
139.124.10.1
139.124.10.5
139.124.10.1
139.124.10.5
Parameter description
Parameter
Disabled during operation
Password
MAC address
Name
IP address
Subnet mask
Gateway
Description
Activates password protection for page security when accessing via the Webserver.
Password for security.
MAC address of the IP address destination
Computer name of the IP address destination
IP address
Assigned Subnet mask
Assigned Gateway address
67
Software Settings
3.8
Bandwidth Monitor Configuration
At a Glance
Introduction
What's in this
Section?
This chapter contains a description about how to configure the Bandwidth Monitor.
This section contains the following topics:
Topic
Bandwidth Monitoring
Quantum NOE Bandwidth Monitor Configuration
Page
68
Software Settings
Bandwidth Monitoring
Overview
Available
Services
Bandwidth Monitoring allows the user to monitor the NOE’s CPU allocation for each of the following services: Global Data, I/O Scanning, and Messaging. The
Bandwidth Monitoring service retrieves workload data and returns one of two pieces of information: whether the module has free resources or whether the module is working at capacity. Knowing the resource allocation helps you: l l
Decide about allocating your resources
Determine the number of NOEs needed in a system
The services accessed and monitored are: l l l
Global Data
I/O Scanner
Modbus Messaging
If the user want to use Bandwidth Monitoring, he do not need to develop a new set of access functions. The actual NOE CPU load is computed each second.
69
Software Settings
Bandwidth
Monitoring Load
Rates
The Bandwidth Monitoring service checks once a second and computes four (4) values in private data: l l l
Percentage of NOE’s CPU allocated to Global Data
Percentage of NOE’s CPU allocated to the I/O Scanner
Percentage of NOE’s CPU allocated to Messaging l Percentage of NOE’s CPU allocated to other services and idle
Results are returned as percentages. CPU time spent in other services is shown as
"Other" or "Free." Bandwidth Monitoring uses the same functions as used by SNMP.
The three service rates, Global Data, I/O Scanner, and Messaging, are computed using the following formula:
(Current load * 100) / Maximum Load
Table of Maximum Load Rates
Diagnostic Service Workload Data Returned
Global Data
I/O Scanner
Messaging
Number of published variables per second
Number of transactions per second
Number of messages treated per second
The current load is computed dynamically.
Maximum load for NOE 771 x1
800
4200
410
Note: The loads are dependent on controller scan time. Each application has an expected scan time. Therefore, when evaluating the loads, the user should ensure that the controller scan time is set to the expected scan time for the application being modelled.
70
Software Settings
Quantum NOE Bandwidth Monitor Configuration
Introduction
Using the program window of the Bandwidth monitor, the user can display the distribution of the network load.
The illustration shows the Bandwidth Monitor dialog box.
ETHERNET_1
Model Family
TCP/IP 10/100 regular connection
Module IP Address
IP Address
0
. 0 . 0 . 0
Subnetwork Mask
0
. 0 . 0 . 0
Modul Address
Rack Module
Gateway Address
0
. 0 . 0 . 0
Module Utilities
YES
Access Control
YES
I/O Scanning
YES
YES
YES
Global Data
SNMP
Address Server
IP Configuration Access Control I/O Scanning Global Data SNMP Address Server
Global Data
Information
Estimated publishers period
1 ms
Messaging Information
0
Bandwidth
Estimated transactions per second
Configuration checking
Distribution estimate
Update distribution estimate
0
% I/O Scanning
0
% Global Data
0
% Messaging
0
% Others (idle)
Parameter description
Parameter
Time span
Transactions per second in the message service
% I/O retrieve
% Global data
% Messaging
% Other (idle)
Description
Scan time of the network load in milliseconds.
Node scan time for the messaging procedure.
Percentage of the network load used for I/O scanner data
Percentage of the network load used for retrieving/sending global data
Percentage of the network load used for nodes from the messaging list.
Percentage of the network load used for all nodes / network traffic, which would otherwise not be shown.
71
Software Settings
72
Index
Numerics
A
B
C
D
E
F
G
Gateway
H
Health Bits
A C
73
Index
I
I/O Scanner
M
Management Information Base (MIB), 45
Modbus I/O Scanner
N
NOE 771 x0
P
Peer Cop I/O Scanner
R
S
Simple Network Management Protocol
T
Transparent Factory
Transparent Factory Ethernet (TFE), 45
Transparent Factory Ethernet Private MIB,
74
Download
Advertisement
Key features
Comprehensive TCP/IP Ethernet Configuration
I/O Scanner for Periodic Data Exchange
Global Data (Publish/Subscribe) for Real-time Variable Synchronization
SNMP Support for Network Management
Address Server for Faulty Device Replacement
Bandwidth Monitoring for Network Performance
Configurable via Unity Pro Software
Frequently asked questions
In Unity Pro, navigate to the Communication folder, right-click on "Networks," and select the Ethernet network type to add a new network.
Global Data is a real-time Publisher/Subscriber mechanism that provides efficient data exchange and synchronization for PLC application variables across a distribution group without requiring MSTR instructions.
The IP address parameters can be configured via the "IP Configuration" tab within Unity Pro, where you can set a static IP, or enable the module to receive its IP from a BOOTP server, or configure it through the module's embedded Web page.