Mitsubishi Electric Breaker tester Y-2005 Instruction Manual
Add to My manuals38 Pages
Mitsubishi Electric Breaker tester Y-2005 is a portable tester for Mitsubishi Low-Voltage Air Circuit Breakers series AE-SW, AE-SS and AE-SH. It allows you to check the characteristics of electronic trip relays in the field without applying current to the breaker. The tester includes various features for testing different parameters, such as overcurrent tripping, ground fault tripping, and pick-up currents, as well as measuring operating times.
advertisement
▼
Scroll to page 2
of
38
![Mitsubishi Electric Breaker Tester Y-2005 Instruction Manual | Manualzz Mitsubishi Electric Breaker Tester Y-2005 Instruction Manual | Manualzz](http://s1.manualzz.com/store/data/078281632_1-b7d8f805368e043b77e5dd9c9f77dc9f-360x466.png)
Low-Voltage Air Circuit Breakers type AE Field test device Y-2005 INSTRUCTION MANUAL <Contents> 1. Specification ..................................................................................................... 2 2. Part names and functions (for AE-SW) ............................................... 3 3. Connection (for AE-SW) ............................................................................. 5 4. Initial setting and operation (for AE-SW) ............................................ 6 5. Tests (for AE-SW) ......................................................................................... 8 6. Settings and accuracy (for AE-SW) ................................................... 15 7. Inspection form (for AE-SW) ................................................................. 20 8. Part names and functions (for AE-SS/SH) .................................... 23 9. Connection (for AE-SS/SH) .................................................................. 25 10. Initial setting and operation (for AE-SS/SH) ............................... 26 11. Tests (for AE-SS/SH) ........................................................................... 28 12. Settings and accuracy (for AE-SS/SH) ......................................... 33 13. Inspection form (for AE-SS/SH) ....................................................... 36 <Models> AE630-SW AE1000-SW AE1250-SW AE1600-SW AE2000-SWA AE2000-SW AE2500-SW AE3200-SW AE4000-SWA AE4000-SW AE5000-SW AE6300-SW AE630-SH AE1000-SH AE1250-SH AE1600-SH AE2000-SH AE2500-SH AE3200-SH AE630-SS AE1000-SS AE1250-SS AE1600-SS AE2000-SS AE2500-SS AE3200-SS AE4000-SSC AE4000-SSA AE4000-SS AE5000-SS AE6300-SS IMPORTANT NOTE: Before using this device, please read this instruction manual carefully, and make sure that final user receives this manual. OBSERVE THE FOLLOWING FOR SAFETY: ● Before using this device, make sure to read this Instruction manual thoroughly. The cautionary items noted herein are of the utmost importance for the safe use of this device, and should always be strictly followed. ● Store this instruction manual together with the device so that it can be read anytime during use. ● Also read the instruction manual for AE-SW to be tested, and take care not to damage the air circuit breaker. ● These safety precautions and Instruction manual is prepared for an electrical expert. The following symbols have been used: Failure to follow these instructions may result in dangerous conditions, DANGER which in turn could lead to severe personal injury or even death. Failure to follow these instructions may result in dangerous conditions, CAUTION which could result in moderate to slight personal injury or damage to equipment and facilities Warning for possible electrification under certain conditions. Warning for possible outbreak of a fire under certain conditions. This means prohibition. Never ignore this indication. Be sure to follow these instructions without fail. DANGER ● Do not use this device on the conditions over ratings. Otherwise ground-fault, short circuit fault or fire may occur due to dielectric breakdown. ● Do not touch the terminals of Breaker and Y-2005. There is a risk of electrical shock. CAUTION ● Test should be performed by an electrical expert. ● Test should be performed only after shutting off the electric power and verifying that there is no voltage present. Failure to do so may result in an electrical shock. ● Connect for tests in accordance with the description given in this instruction manual. Otherwise, electric shocks or malfunction may occur. ● Do not install in areas subject to high temperatures, high humidity, dust, corrosive gas, vibrations, shocks, etc. To do so may result in malfunction or fire. ● This tester is for 100-240VAC 50/60Hz. Using it at other specifications may cause fires or malfunction. ● After testing, remove the wiring used for testing and restore the circuit breaker to its original condition. Any other conditions may cause fires or malfunction. ● When discard products, dispose of as industrial waste. E-1 1. Specification The Y-2005 breaker tester is a light-weight portable tester for MITSUBISHI Low-Voltage Air Circuit Breakers series AE-SW, AE-SS and AE-SH. The characteristics of electronic trip relay can be checked in the field without applying a current to circuit breaker. Input voltage Power consumption VA Range of signal output Test power output and trip check power output Terminal for checking the signal output Stop signal input Test items Signal level Time counter Working temperature range Storage temperature range Dimensions Weight Attachments 100-240V AC 50/60Hz (available voltage range: AC85-264V) 100VA or less Voltage signal equivalent to 1%~2500% of Rated current In (CT rating) (continuously adjustable). *The output at 100% of CT rating is 141mV at 50Hz or 170mV at 60Hz. DC30V 5W The same signal as the signal output is output to the terminal on the back side (load impedance: 100kΩ or more). "a" contact, "b" contact or test terminal (ETR) LTD, STD, INST/MCR, GFR, PAL, PAL2 and Trip check *ER check is not available. Max. 2500% of Rated current setting (Ir) (accuracy: ±2.5% at CT rating) 0.000s±2ms~999.999s±1% 0~40℃ (humidity: 85%Rh or less) -10℃~50℃(humidity: 85%Rh or less) 220mm (width) X 150mm (height) X 340mm (depth) 4.8kg AC power cord, test cable, carry case Earth leakage protection (ER) check is not available with this tester. Please make a reference separately about the ER operating check method. When carrying out ETR check of Type WD,Please make inquiries. Power plug of AC power cord is equipped with grounding pin. Please use the outlet with grounding for the electric shock prevention. E-2 2. Part names and functions (for AE-SW) The ratio to CT rating “RATIO” indicated on the front face of Y-2005 is a ratio of Current setting Ir at AE-SW Electronic trip relay (ETR) to Rated current In(CT rating). Be careful in testing or operating. ●Front view Stop signal indicating LED a: The trip signal is made by the "a" (make) contact. b: The trip signal is made by the "b" (break) contact. ETR: The trip signal is input from ETR through the test connector. Output frequency indicating LED OUTPUT pin indicating LED S1: Overcurrent tripping (L/C/R-pole) S2: Ground fault tripping S3: N-pole overcurrent tripping Signal level indicator The indication varies depending on the decimal point position as follows: H 0.000: Ratio to CT rating [RATIO] 00000.0: Test signal level [TEST SIGNAL(%)] Trip check mode indicating LED TESTING mode indicating LED Lights with START and goes out with STOP or TRIP. Time counter LED TRIP indicating (Indicates operating time) LED Signal level mode switch Test power indicating LED Output pin switch Output frequency switch Stop signal input switch TRIP CHECK mode switch Test power manual connecting switch (auxiliary function) STOP switch Use this switch to stop testing Signal adjusting switches The signal level can be changed continuously with three digits even during testing. START switch The test signal is output, and the time counter starts. Signal setting keypad The signal level can be set to the desired value. RESET switch The time counter and trip indicating LED are reset. C E-3 2 0 ‥‥ SET ●Back view For calibration, inquire at any of our branch offices or service centers. The test signal output can be checked by connecting an AC voltmeter. Signal output checking terminal (usually not in use) Power switch (With overcurrent protective function) AC Power input connector Available in the range from 100VAC to 240VAC. DANGER Test signal output connector (With reverse insertion prevention.) Stop signal input terminals To be connected with the "a" contact or "b" contact of a trip indicator, main contact, auxiliary switch or the like. When using the “Stop signal input terminals”, check that no power is supplied and that there is no interference with other wiring in the panelboad. Otherwise, electric shocks or short circuits may occur. E-4 3. Connection (for AE-SW) DANGER Do not touch the terminals. Otherwise, electric shocks may occur. Electronic trip relay (ETR) Note) This figure includes Display (*option) and MCR switch (*option). When checking a dielectric voltage test or insulation resistance measurement of the circuit breaker and panelboad, remove all wiring for Y-2005. Otherwise, trouble may occur. Breaker tester Y-2005 Test cable Test connector (With reverse insertion prevention) AC plug (with earth pin) These are used when the stop signal is input from other than the test cable (test connector of ETR). ①When using the main contact of breaker. … Set the “Stop signal input switch” on the front face to [b]. ②When using the "a" contact of auxiliary switch (AX). … Set the “Stop signal input switch” to [b]. ③When using the "b" contact of auxiliary switch (AX). … Set the “Stop signal input switch” to [a]. ④When using the OCR alarm switch (AL). … Set the “Stop signal input switch” to [a]. *Connect to the circuit breaker's control circuit terminal block ( 97 and 98 ). ⑤When using the alarm contacts. … Set the “Stop signal input switch” to [a]. *Connect to the circuit breaker's control circuit terminal block ( 524 ~ 564 and 513 ). *For using these alarm contacts, the Power supply module with alarm contact (type: P3, P4 OR P5) is required. E-5 4. Initial setting and operation (for AE-SW) Start the setting and operation after carefully reading an instruction manual for AE-SW (IB63366) and 6. Settings and accuracy in this instruction manual to understand the characteristics of ETR. 4.1 Setting of rated current (1)Open the front cover of ETR. (2)Connect a test cable to ETR as described in Chapter 3. (3)Turn on the “Power switch” on the back panel. (4)Set a mode with the corresponding switches described below. The settings are changed in turn by pushing the switches. As for function of each setting, see chapter 2. ・Output frequency ・Stop signal ・Output pin ・Test mode 50Hz / 60Hz a / b / ETR S1 / S2 / S3 usual test / TRIP CHECK *When power is turned on, each item is set to the marked position. (5)Setting of Rated current This tester outputs a signal at the ratio of Current setting Ir at ETR to Rated current In(CT rating). Therefore, at the beginning, the ratio to CT rating should be set in % of Rated current In(CT rating). ①Set a mode to H ○.○○○ with “Signal level mode switch TEST SIGNAL(%) / RATIO “. (When power is turned on, the rated current is set to H 1.000 ). ②Input a value of the rated current to H ○.○○○ with “Signal adjusting switches” or “Signal setting keypad”. ●When testing the Overcurrent tripping or pre-alarm characteristics. (i)In case of WS or WB type relay; Input a value of Ir setting dial of ETR. Example) In case that Ir is set to 0.8: Input H 0.800 . (ii)In case of WM type relay; Input a value calculated by (Ir [A]÷In [A]). Example) In case that In=1600A and Ir=1283A: 1283A÷1600A=0.802, therefore input ●When testing the ground fault characteristics. Set to H 1.000 even if Ir setting dial of ETR is not set to 1.0. E-6 H 0.802 . 4.2 How to operate DANGER Test should be performed only after shutting off the electric power and verifying that there is no voltage present. Failure to do so may result in an electrical shock. When current is flowing in the main circuit of breaker, it is combined with the test signal of Y-2005, consequently does not become correct characteristic. The operating test should be performed in the state that load current does not flow in the main circuit. (1)Set the “Signal level indicator” to ○○○○○.○ by pushing the “Signal level mode switch TEST SIGNAL(%) / RATIO “. (2)Set a signal level in % of Ir by using the “Signal adjusting switches” or “Signal setting keypad”. ●When using the “Signal adjusting switches”: 10% Continuing to push the switches increases or decreases the signal level continuously. ●When using the “Signal setting keypad”: ① Push a clear key C . ② Since figures are shifted to left every time you push numerical keys, enter the desired values. ③ Push a set key SET . 1% 0.1% To set to 200%Ir, push and 00200.0 C 2 0 0 0 SET , is set. (3)Push START switch, and the test signal is output. Then the time counter starts from mode indicating LED” lights. 000.000 , and also the “TESTING (4)Push STOP switch, and the test signal is stopped. Then the time counter stops, and the “TESTING mode indicating LED” goes off. In case of tripping, the “TRIP indicating LED” lights and the time counter stops automatically. (5)Push RESET switch to reset the “TRIP indicating LED” and the time counter. This switch is used for retesting. E-7 5. Test (for AE-SW) It is possible to display a trip current value on LCD by supplying control power to ETR, if Display (DP1 or DP2) (*option) is equipped. However, this value may become somewhat larger than the value displayed by Y-2005, especially in case of STD and INST trip. Furthermore, since the test signal from Y-2005 is not input into the Extension module (EX1), even if it supplies the test current to ETR, the measuring current value displayed on LCD will be as “0”. 5.1 LTD Pick-up current test (1)Set the signal level to approximately 90% of LTD pick-up current. (2)Push START switch. (3)Increase the signal level with “Signal adjusting switch”, and take a reading of pick-up value. (i)In case of WS type relay The pick-up value is calculated by; (Pick-up level at a point where ETR turns a [OVER] LED on)÷Iu. Example) When the [OVER] LED lights at 94% with Iu=0.8, the pick-up value is 94%÷0.8=117.5%. (ii)In case of WM type relay The LTD pick-up level can be taken at a point where ETR turns a [100%] LED on. (4)Push STOP switch. (5)Push RESET switch and start at (1), if testing again. Increase the signal level with this 1% step key. Signal adjusting switches 5.2 LTD operating time test (1)Set a desired signal level. (i)In case of WS type relay The operating time is to be taken at 200%Iu, therefore, if Iu is set to 1.0, set the signal level to 00200.0 . In case that Iu is not set to 1.0, for example, if Iu is 0.9, since 0.9×200%=180%, set the signal level to 00180.0 (ii)In case of WM type relay The operating time is to be taken at 120%IL, therefore, if IL is set to 1.05, since 1.05×120%=126%, set the signal level to 00126.0 . . (2)The Isd (short-time-delay pick-up current) and Ii (instantaneous pick-up current) setting dial of ETR should be set to 1.2 times or more the above-mentioned signal level. (3)Push START switch. (4)After tripping, the operating time is indicated. (5)Push RESET switch and start at (3), if testing again. Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on the way, the operating time at the next test becomes short. This memory effect can be reset by tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping ETR one-time. To trip, perform the trip check in accordance with 5.12. <Hint> In section 5.1 and 5.2, if Iu of WS type relay is not set to 1.0, the reading value of the signal level can be regarded as the LTD pick-up current (%) by setting the value of H ○.○○○ to Ir×Iu. Also, when measuring the LTD operating time, test can be performed with the signal level 00200.0 . However, when checking the STD or INST characteristics, return the setting of H ○.○○○ to a former value. E-8 5.3 STD Pick-up current test (1)Set Ii (instantaneous pick-up current) setting dial of ETR to the maximum, and set Tsd (short-time-delay operating time) to the minimum (0.06s). * If the setting value of Tg is large, exact measurement cannot be performed in the following (5). Increase the signal level with this 10% step key. (2)Set the signal level to approximately 80% of Isd. Signal adjusting switches (3)Push START switch, and immediately increase the signal level with a 10% signal adjusting switch until ETR trips and Time counter LED stops. Increase the signal level by using 10% step key. Since it takes a long time to test in case of 1% or 0.1% step, the LTD pick-up may operate before STD. If LTD pick-up operates even the 10% step, start again at approximately 95% of Isd. (4)Read the signal level indicated at the time. (5)Furthermore, measure the operating time near the pick-up current measured in (3) by using 1% step key. The point where the operating time becomes short suddenly serves as accurate measured value of Isd. (6)Push RESET switch and start at (2), if testing again. 5.4 STD operating time test (1)Set Ii setting dial of ETR to the maximum. (3)Push START switch. Time→ (2)Set a desired signal level. For example, if Isd setting dial is set to 4, since 400%×1.5=600%, set the signal level to 00600.0 . *Where, 1.5 is a value that the operating time becomes flat. Tsd Isd (4)After tripping, the operating time is indicated. Isd×1.5 When the stop signal is made by the main Take the reading of the counter as it contact, auxiliary switch (AX) or OCR alarm is. switch (AL). When the stop signal is made through the test Add 20ms (mechanical operating time) connector of ETR or alarm contacts of Power to the reading of the counter. supply module (type: P3, P4 or P5). (5)Push RESET switch and start at (3), if testing again. If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD, or change the test current. Moreover, ETR may operate as INST when checking STD operating time at Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd to “I2t OFF” temporarily. E-9 → Current 5.5 INST Pick-up current test (1)When the MCR switch (*option) is equipped, set Ii setting dial to "INST” side (See right figure). (2)Set the signal level to approximately 90% of Ii. ●INST (standard) (3)Push START switch while continuing to push a [L/S LOCK] button of ETR, then increase the signal level by using the “Signal adjusting switch” until ETR trips and Time counter LED stops. Increase the signal level with this 10% step key. (4)Read the signal level indicated at the time. (5)Push RESET ●MCR (*option) (INST/MCR selectable) switch and start at (2), if testing again. Signal adjusting switches (6) For models with MCR, if you change the dial to the INST side and test, return the dial to its original position. 5.6 INST operating time test Time → (1)Set a desired signal level. For example, if Ii setting dial is set to 10, since 1000%×1.5=1500%, set the signal level to 01500.0 . *Where, 1.5 is a value that the operating time becomes flat. Ti (2)Push START → Current switch while continuing to push the [L/S LOCK] button of ETR. Ii I i ×1.5 (3)After tripping, the operating time is indicated. When the stop signal is made by the main Take the reading of the counter as it contact, auxiliary switch (AX) or OCR alarm is. switch (AL). When the stop signal is made through the test Add 20ms (mechanical operating time) connector of ETR or alarm contacts of Power to the reading of the counter. supply module (type: P3, P4 or P5). (4)Push RESET switch and start at (2), if testing again. 5.7 MCR function check (*Only when MCR switch is equipped) (1)Set Ii setting dial of ETR to "MCR" side. (2)When the state of circuit breaker is off, ETR operates as INST. Check the INST operation in accordance with section 5.5 and 5.6. * This test is checking that instantaneous characteristics is effective during breaker closing operation ( from open to close ) . ●INST (standard) ●MCR (*option) (INST/MCR selectable) (3)Confirms that the breaker does not operate as INST even when the same test as section 5.5 and 5.6 is carried out. In this case, it operates as STD in case of WS or WM type relay. In case of WB type relay, it does not trip. E-10 5.8 GFR Pick-up current test (TRIP mode) (*Only when G1 module is equipped) (1)Set Tg (ground fault operating time) setting dial of ETR to the minimum (0.10s) of “TRIP” side. * If the setting value of Tg is large, exact measurement cannot be performed in the following (4). (2)Set the “Signal output pin” to [S2] and the rated current to H 1.000 in accordance with section 4.1(5). Increase the signal level with this 1% step key. (3)Set the signal level to approximately 80% of Ig (ground fault pick-up current). (4)Push START switch, and immediately increase the signal level with the “Signal adjusting switch” until ETR trips and Time counter LED stops. (5)Read the signal level indicated at the time. (6)Push RESET switch and start at (3), if testing again. Signal adjusting switches 5.9 GFR operating time test (TRIP mode) (*Only when G1 module is equipped) (1)Set Tg setting dial of ETR to “TRIP” side. (2)Set the “Signal output pin” to [S2] and the rated current to (3)Set the “Signal level indicator” to ○○○○○.○ H 1.000 in accordance with section 4.1(5). by pushing the “Signal level mode switch (5)Push START Tg switch. Ig (6)After tripping, the operating time is indicated. Ig×1.5 When the stop signal is made by the main Take the reading of the counter as it contact, auxiliary switch (AX) or OCR alarm is. switch (AL). When the stop signal is made through the test Add 20ms (mechanical operating time) connector of ETR or alarm contacts of Power to the reading of the counter. supply module (type: P3, P4 or P5). (8)Push RESET “. Time (4)Set a desired signal level. For example, if Ig setting dial is set to 0.3, since 30%×1.5=45%, set the signal level to 00045.0 . * Where, 1.5 is a value that the operating time becomes flat. TEST SIGNAL(%) / RATIO switch and start at (5), if testing again. When checking the short time operation such as GFR operating time test, in order to measure the operating time with accuracy, push the “Test power manual connecting switch VT “, and push the START switch after the “Test power indicating LED” lighting. If do not pushing the “Test power manual connecting switch VT “, exact measurement cannot be performed. E-11 Current 5.10 GFR Pick-up current test (ALARM mode) (*Only when G1 module is equipped) (1)Set Tg (ground fault operating time) setting dial of ETR to the minimum (0.10s) of “ALARM” side. * If the setting value of Tg is large, exact measurement cannot be performed in the following (5). (2)Set the “Signal output pin” to [S2] and the rated current to H 1.000 in accordance with section 4.1(5). (3)Set the signal level to approximately 80% of Ig (ground fault pick-up current). (4)Push START switch. Increase the signal level with this 1% step key. (5)Increase the signal level using the "Signal adjusting switch", and take a reading of the counter at a point where ETR turns a [GFR] LED on. (6)Push RESET switch and start at (3), if testing again. Signal adjusting switches 5.11 GFR operating time test (ALARM mode) (*Only when type P3, P4 or P5 module and G1 module are equipped) (1)Set Tg setting dial of ETR to “ALARM” side. (2)Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block). (3)Connect the "Stop signal input" on the back of tester and the contact terminal for GFR (between 544 and 513 of the circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a]. *The terminal allocation for GFR ( 544 and 513 ) described in above is the assignment at the factory shipments. If this allocation is changed by using the display (DP1 or DP2), it differs from the above allocation. (4)Set a desired signal level (See section 5.9). (5)Push START switch. (6)After operation, the operating time is indicated. (7)Push RESET switch and start at (4), if testing again. E-12 5.12 Trip check This function enables the circuit breaker to operate instantaneously. It is effective when checking panel sequence, resetting the memory effect for overcurrent and the like. (1)Set a test mode to [TC] (trip check). (2)In case of WM type relay, if MCR switch (*option) is equipped, set Ii setting dial to "INST" side. *In case of WB type relay, unless Ii setting dial is set to "INST" side, ETR does not trip. (3)Push START switch. (4)Confirms that the circuit breaker trips instantaneously. (5)Push RESET switch and start at (3), if testing again. When checking the circuit breaker operating time, push the “Test power manual connecting switch VT “, and push START switch after the “Test power indicating LED” lighting. If do not pushing the “Test power manual connecting switch VT “, exact measurement cannot be performed. 5.13 PAL pick-up current test (1)Set the signal level to approximately 80% of Ip. (2)Push START Increase the signal level with this 1% step key. switch. (3)Increase the signal level using the "Signal adjusting switch", and take a reading of the counter at a point where [PAL] LED of ETR blinks. (4)Push STOP switch. (5)Push RESET switch and start at (1), if testing again. Signal adjusting switches 5.14 PAL operating time test (*Only when type P3, P4 or P5 of Power supply module is equipped) (1)Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block). (2)Connect the "Stop signal input" on the back of tester and the contact terminal for PAL OUT (between 554 and 513 of the circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a]. *The terminal allocation for PAL OUT ( 554 and 513 ) described in above is the assignment at the factory shipments. If this allocation is changed by using the display (DP1 or DP2), it differs from the above allocation. (3)Set a desired signal level (See section 5.2). (4)Push START switch. (5)After operation, the operating time is indicated. (6)Push RESET switch and start at (3), if testing again. Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on the way, the operating time at the next test becomes short. This memory effect can be reset by tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping ETR one-time. To trip, perform the trip check in accordance with 5.12. E-13 5.15 PAL2 pick-up current test (*Only when AP module is equipped) Increase the signal level with this 1% step key. (1)Set the signal level to approximately 80% of Ip2. (2)Push START switch. (3)Increase the signal level using the "Signal adjusting switch", and take a reading of the counter at a point where [PAL2] LED of ETR blinks. (4)Push STOP switch. (5)Push RESET switch and start at (1), if testing again. Signal adjusting switches 5.16 PAL2 operating time test (*Only when P3, P4 or P5 module and AP module are equipped) (1)Supply power to ETR (between P1 and P2 of the circuit breaker's control circuit terminal block). (2)Connect the "Stop signal input" on the back of tester and the contact terminal for PAL2 OUT (between 544 and 513 of the circuit breaker's control circuit terminal block). Then set the "Stop signal input switch" to [a]. *The terminal allocation for PAL2 OUT ( 544 and 513 ) described in above is the assignment at the factory shipments. If this allocation is changed by using the display (DP1 or DP2), it differs from the above allocation. (3)Set a desired signal level (See section 5.2). (4)Push START switch. (5)After operation, the operating time is indicated. (6)Push RESET switch and start at (3), if testing again. Since ETR has a memory effect for overcurrent state, when the operating time test is interrupted on the way, the operating time at the next test becomes short. This memory effect can be reset by tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping ETR one-time. To trip, perform the trip check in accordance with 5.12. 5.17 OCR alarm switch (AL) check The OCR alarm switch (AL) is a contact (“a” contact) of short time operation (30-50ms) Note). This time can be measured with the oscilloscope, the millisecond counter or the like. Note): In case of the manual reset type (MRE) (*option), AL is output continuously. This contact output is not reset until pushing the manual reset button of breaker. Y-2005 enables a check of operation even if breaker is in the state of OFF. However, as for AL checking, since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually). E-14 6. Settings and accuracy (for AE-SW) 6.1 Settings and accuracy of type WS relay ① ⑥ ② ③ *Note): In case of AE4000-SW~AE6300-SW, the max. breaking time is 0.05s. ⑤ ④ 3 ⑦ 3 *Note) ■The figure includes optional G1 setting module, Display and MCR. Adjustable setting range AE630-SW~AE1600-SW AE2000-SWA AE2000-SW~AE3200-SW AE4000-SWA AE4000-SW AE5000-SW 0.5~1.0(0.05step) ×In (CT rating) No. Setting item Mark ① Rated current setting Ir ② Uninterrupted current Iu 0.8~1.0×Ir(0.02step), Pick-up current: 1.15xIu ③ ④ LTD time TL 12-25-50-100-150s STD Pick-up current Isd ⑤ STD time Tsd ⑥ INST. Pick-up current Ii ⑦ ⑧ Pre-alarm current Ip Iu×0.68~1.0(0.04step)-OVER ±10% Pre-alarm time Tp 1/2 TL (after 1/2TL, PAL output contact turns on) ±20% AE6300-SW at Iu×2 1.5-2-2.5-3-4-5-6-7-8-9-10 ×Ir 0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s (I2t ON) (I2t OFF) 16~2 - 2~16 ×Ir 12~2 - 2~12 ×Ir 10~2 - 2~10 ×Ir (INST) (MCR) WS1 (INST) (MCR) WS2 (INST) (MCR) WS3 Accuracy ― 1.05×Iu…Non pick-up 1.25×Iu…Pick-up ±20% ±15% ±20% (0.06…±0.02s) ±15% *Note): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided. Relation of setting dial In (CT rating) Ir Iu Ip Isd Ip2 (see page19) Ii Load current LED(60, 80, 100, OVER) Ig (see page18) E-15 6.2 Settings and accuracy of type WM relay *Note): In case of AE4000-SW~AE6300-SW, the max. breaking time is 0.05s. ① ⑥ ② ③ ⑤ ④ 3 ⑦ 3 *Note) ■The figure includes optional G1 setting module, Display and MCR. No. Setting item Mark ① ② ③ ④ Rated current setting STD pick-up current Ir IL TL Isd ⑤ STD time Tsd ⑥ INST. pick-up current Ii ⑦ ⑧ Pre-alarm current Ip Pre-alarm time Tp LTD pick-up current LTD time Adjustable setting range AE630-SW~AE1600-SW AE2000-SWA AE2000-SW~AE3200-SW AE4000-SWA AE6300-SW AE4000-SW AE5000-SW 0.63 ~ 1.0×In (*Set to specified current value before shipment (fixed)) Accuracy ― 1.0-1.05-1.1-1.15-1.2 ×Ir ± 5% 15-20-25-30-40-60s at IL×1.2 ±20% 1.5-2-2.5-3-3.5-4-4.5-5 ×Ir 0.5-0.4-0.3-0.2-0.1-0.06- 0.06-0.1-0.2-0.3-0.4-0.5s (I2t ON) (I2t OFF) 16~2 – 2~16 ×Ir 12~2 – 2~12 ×Ir 10~2 – 2~10 ×Ir (INST) (MCR) WM1 (INST) (MCR) WM2 (INST) (MCR) WM3 IL×0.68~1.0(0.04step)-OVER ±15% ±20% 3) (0.06…±0.02s) 1/2 TL (after 1/2TL, PAL output contact turns on) ±15% 3) ±5% ±20% *Note1): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided. *Note2): When the WM type relay is used, the pre-alarm current at the setting, OVER , is the same as that at 1.0. *Note3): When used without voltage applied to the control power supply(ETR power supply module), Tsd, Ii operation on time may increase max. 20ms. Relation of setting dial In (CT rating) Ir (Fixed) IL Ip Isd Ip2 (see page19) Ii Load current LED(40, 60, 80, 100) Ig (see page18) E-16 6.3 Settings and accuracy of type WB relay *Note): In case of AE4000-SW~AE6300-SW, the max. breaking time is 0.05s. ① ⑥ ⑦ *Note) ■The figure includes MCR function. No. Setting item Mark ① Rated current setting Ir ⑥ INST. pick-up current Ii ⑦ ⑧ Pre-alarm current Ip Pre-alarm time Tp Adjustable setting range AE630-SW~AE1600-SW AE2000-SWA AE2000-SW~AE3200-SW AE4000-SWA AE4000-SW AE5000-SW 0.5 ~ 1.0(0.05step) ×In (CT rating) 16~2 - 2~16 ×Ir 12~2 - 2~12 ×Ir (INST) (MCR) WB1 (INST) (MCR) WB2 Ir×0.68~1.0(0.04step)-OVER AE6300-SW Accuracy ― 10~2 - 2~10 ×Ir (INST) (MCR) WB3 75s at Ir×2 (after 1/2TL, PAL output contact turns on) ±15% ±5% ±20% *Note): The table shows data obtained on the breakers provided with MCR (*option). For breakers without MCR, the setting position for MCR is not provided. Relation of setting dial In (CT rating) Ir Ii Ip Load current LED(60, 80, 100, OVER) Ig (see page18) E-17 6.4 Settings and accuracy of G1 module ① Ground fault protection characteristics ① Pick-up current:Ig 0.1 ② 1.0 Operation time (s) 3.0±20% ② Ground fault time:Tg 0.15±20% <0.1 (0.04~0.1s) % of rated current In (CT rating) No. Setting item ① Ground fault Pick-up ② Ground fault time Mark Adjustable setting range Accuracy Ig 0.1~1.0×In (0.1step) ±20% Tg 3.0-1.5-0.8-0.5-0.3-0.15-<0.1 - <0.1-0.15-0.3-0.5-0.8-1.5-3.0 s (Trip) (Alarm) ±20% E-18 6.5 Settings and accuracy of AP module ① ② ●For type WS relay ●For type WM relay ① 2nd pre-alarm current:Ip2 ① 2nd pre-alarm current:Ip2 LTD operating time:TL 12-25-50-100-150s (at Iu×2) ② 2nd pre-alarm operating time:Tp2 (FLAT) Operation time (s) Operation time (s) LTD operating time:TL 15-20-25-30-40-60s (at IL×1.2) ② 2nd pre-alarm operating time:Tp2 (FLAT) ② 2nd pre-alarm operating time:Tp2 (×TL) ② 2nd pre-alarm operating time:Tp2 (×TL) Current (% of Iu) No. Setting items Mark ① 2nd pre-alarm current Ip2 ② 2nd pre-alarm operating time Tp2 Current (% of IL) Adjustable setting range Accuracy 0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 ×Iu 0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 ×IL ±10% WS WM 0.9-0.8-0.7-0.6-0.5-0.4-0.3×TL – 5-10-15-20-30-40-60s (×TL) (FLAT) E-19 ± 5% ±20% WS WM 7. Inspection form (for AE-SW) Inspection report form for WS type relay Date: Checked person: Name of Panel/Distribution system: ACB Type CT rating (In) Serial number ETR type ETR serial number There must be no breakage of ETR. External There must be no loosening of terminal appearance screws of Control circuit terminal block. Rated current setting (Ir) Uninterrupted current (Iu) LTD Operating time (TL) Pickup current (Isd) STD Operating time (Tsd) I2t ON/OFF settings Pickup current (Ii) INST INST/MCR settings Pickup current (Ip) Confirmation PAL of settings Operating time (Tp) Pickup current (Ig) GFR 3) Operating time (Tg) TRIP/ALARM settings Pickup current (IΔn) ER 3) Operating time (Te) TRIP/ALARM settings Pickup current (Ip2) PAL2 3) Operating time (Tp2) Pickup current (%) LTD Operating time (s) Pickup current (%) STD 2) Operating time (s) Pickup current (%) INST 1) Operating time (s) Pickup current (%) Pickup/ Operating time PAL Operating time (s) Pickup current (%) GFR 3) Operating time (s) Pickup current (%) 3), 4) ER Operating time (s) Pickup current (%) 3) PAL2 Operating time (s) Trip indicator LED (L, S, I, PAL, GFR 3), ER 3), 4), PAL2 3)) Trip indicator contact output Outputs (L, S/I, PAL, GFR 3)/ER 3), 4)/PAL2 3)) There must be no breakage. There must be connected securely. Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check. 105% - 125%Iu TL±20% at 200%Iu Isd±15% Tsd±20% at 150%Isd Ii±15% ≤ Max. breaking time at 150%Ii Ip±10% TL/2±20% at 200%Iu Ig±20% Tg±20% at 150%Ig IΔn+0%-30% Te±20% at 150%IΔn Ip2±10% Tp2±20% at 200%Iu Only if Power supply with alarm contact (type: P3/P4/P5) is equipped. AL (*standard): 30ms (1pulse) MRE (*option): continuously OCR alarm switch (AL) output 5) Result Other items to be checked. Note1): If ETR operates as LTD or STD in checking INST pick-up current, use the L/S LOCK (LTD/STD LOCK) button of ETR. Note2): If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD, or change the test current. Moreover, ETR may operate as INST when checking STD operating time at Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd to “I2t OFF” temporarily. Note3): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note4): Please make a reference separately about the ER operating check method. Note5): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually). E-20 Inspection report form for WM type relay Date: Checked person: Name of Panel/Distribution system: ACB Type CT rating (In) Serial number ETR type ETR serial number There must be no breakage of ETR. External There must be no loosening of terminal appearance screws of Control circuit terminal block. Rated current setting (Ir) Pickup current (IL) LTD Operating time (TL) Pickup current (Isd) STD Operating time (Tsd) I2t ON/OFF settings Pickup current (Ii) INST INST/MCR settings Pickup current (Ip) Confirmation PAL of settings Operating time (Tp) Pickup current (Ig) GFR 3) Operating time (Tg) TRIP/ALARM settings Pickup current (IΔn) ER 3) Operating time (Te) TRIP/ALARM settings Pickup current (Ip2) PAL2 3) Operating time (Tp2) Pickup current (%) LTD Operating time (s) Pickup current (%) STD 2), 6) Operating time (s) (%) 1), 6) Pickup current INST Operating time (s) Pickup current (%) Pickup/ Operating time PAL Operating time (s) Pickup current (%) GFR 3) Operating time (s) Pickup current (%) 3), 4) ER Operating time (s) Pickup current (%) 3) PAL2 Operating time (s) Trip indicator LED (L, S, I, PAL, GFR 3), ER 3), 4), PAL2 3)) Trip indicator contact output Outputs (L, S/I, PAL, GFR 3)/ER 3), 4)/PAL2 3)) There must be no breakage. There must be connected securely. Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check. IL±5% TL±20% at 120%IL Isd±15% Tsd±20% at 150%Isd Ii±15% ≤ Max. breaking time at 150%Ii Ip±5% TL/2±20% at 120%IL Ig±20% Tg±20% at 150%Ig IΔn+0%-30% Te±20% at 150%IΔn Ip2±5% Tp2±20% at 120%IL Only if Power supply with alarm contact (type: P3/P4/P5) is equipped. AL (*standard): 30ms (1pulse) MRE (*option): continuously OCR alarm switch (AL) output 5) Result Other items to be checked. Note1): If ETR operates as LTD or STD in checking INST pick-up current, use the L/S LOCK (LTD/STD LOCK) button of ETR. Note2): If ETR operates as LTD or INST in checking STD pick-up current, change the set value of INST/LTD, or change the test current. Moreover, ETR may operate as INST when checking STD operating time at Isd=10. In this case, lower the test current to near 140%Isd, or lower the test current after setting Tsd to “I2t OFF” temporarily. Note3): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note4): Please make a reference separately about the ER operating check method. Note5): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually). Note6): When used without voltage applied to the control power supply(ETR power supply module), Tsd, Ii operation on time may increase max. 20ms. E-21 Inspection report form for WB type relay Date: Checked person: Name of Panel/Distribution system: ACB Type CT rating (In) Serial number ETR type ETR serial number There must be no breakage of ETR. External There must be no loosening of terminal appearance screws of Control circuit terminal block. Rated current setting (Ir) Pickup current (Ii) INST INST/MCR settings Pickup current (Ip) PAL Operating time (Tp) Pickup current (Ig) Confirmation GFR 1) Operating time (Tg) of settings TRIP/ALARM settings Pickup current (IΔn) ER 1) Operating time (Te) TRIP/ALARM settings Pickup current (Ip2) PAL2 1) Operating time (Tp2) Pickup current (%) INST Operating time (s) Pickup current (%) PAL Operating time (s) Pickup current (%) Pickup/ Operating time GFR 1) Operating time (s) Pickup current (%) 1), 2) ER Operating time (s) Pickup current (%) 1) PAL2 Operating time (s) Trip indicator LED (I, PAL, GFR 1), ER 1), 2), PAL2 1)) Trip indicator contact output Outputs (I, PAL, GFR 1)/ER 1), 2)/PAL2 1)) There must be no breakage. There must be connected securely. Fill in the setting values. If setting was changed during check, reset the value to the previous settings at the completion of check. Ii±15% ≤ Max. breaking time at 150%Ii Ip±10% 75s±20% at 200%Ir Ig±20% Tg±20% at 150%Ig IΔn+0%-30% Te±20% at 150%IΔn Ip2±10% Tp2±20% at 200%Ir Only if Power supply with alarm contact (type: P3/P4/P5) is equipped. AL (*standard): 30ms (1pulse) MRE (*option): continuously OCR alarm switch (AL) output 3) Result Other items to be checked. Note1): Check and fill in the blanks only if any Optional setting module (G1/E1/AP) is equipped. Note2): Please make a reference separately about the ER operating check method. Note3): Since AL is included in the trip mechanism, AL is output only when tripping from ON state. (AL cannot be output unless tripping actually). E-22 8. Part names and functions (for AE-SS/SH) The ratio to CT rating “RATIO” indicated on the front face of Y-2005 is a ratio of RATED CURRENT In at AE-SS Electronic trip relay to RATED CURRENT MAX In max(CT rating). Be careful in testing or operating. ●Front view Signal level indicator The indication varies depending on the decimal point position as follows: H 0.000: Ratio to CT rating [RATIO] 00000.0: Test signal level [TEST SIGNAL(%)] Stop signal indicating LED a: The trip signal is made by the "a" (make) contact. b: The trip signal is made by the "b" (break) contact. ETR: The trip signal is input from ETR through the test connector. Output frequency indicating LED OUTPUT pin indicating LED ●C/S/SL type relay ●M type relay S1: Overcurrent tripping S1: L-pole test (L/C/R-pole) S2: C-pole test/ S2: Ground fault tripping Ground fault tripping S3: N-pole overcurrent tripping S3: R-pole test Trip check mode indicating LED TESTING mode indicating LED Lights with START and goes out with STOP or TRIP. TRIP indicating Time counter LED (Indicates operating time) LED Signal level mode switch Test power indicating LED Output pin switch Output frequency switch Stop signal input switch TRIP CHECK mode switch Test power manual connecting switch (auxiliary function) STOP switch Use this switch to stop testing Signal adjusting switches The signal level can be changed continuously with three digits even during testing. START switch The test signal is output, and the time counter starts. Signal setting keypad The signal level can be set to the desired value. RESET switch The time counter and trip indicating LED are reset. C E-23 2 0 ‥‥ SET ●Back view For calibration, inquire at any of our branch offices or service centers. The test signal output can be checked by connecting an AC voltmeter. Signal output checking terminal (usually not in use) Power switch (With overcurrent protective function) AC Power input connector Available in the range from 100VAC to 240VAC. DANGER Test signal output connector (With reverse insertion prevention.) Stop signal input terminals To be connected with the "a" contact or "b" contact of a trip indicator, main contact, auxiliary switch or the like. When using the “Stop signal input terminals”, check that no power is supplied and that there is no interference with other wiring in the panelboad. Otherwise, electric shocks or short circuits may occur. E-24 9. Connection (for AE-SS/SH) Do not touch the terminals. DANGER Otherwise, electric shocks may occur. When conducting a withstand voltage test or insulation resistance measurement of the circuit breaker, remove the wiring of Y-2005. Otherwise, trouble may occur. Breaker tester Y-2005 Test cable AC plug (with earth) Test connector (Prevents inserting in the reverse direction.) ・When measuring the operating time including that of the circuit breaker, connect with the "a" contact or "b" contact of the auxiliary switch (AX). ・"a" contact of the auxiliary switch (AX) ... Set the stop signal to [b]. ・"b" contact of the auxiliary switch (AX) ... Set the stop signal to [a]. ・When measuring the pre-alarm operating time, connect with the PAL OUT contact. "a" contact between PAL OUT T0+ and T4 ... Set the stop signal to [a]. ※ To operate the PAL OUT contact, control power is required for the trip relay. E-25 10. Initial setting and operation (for AE-SS/SH) Start the setting and operation after carefully reading an instruction manual for AE-SS/SH and 12. Settings and accuracy in this instruction manual to understand the characteristics of Electronic trip relay. 10.1 Setting of rated current (1) Open the front cover of Electronic trip relay. (2) Connect as described in paragraph 9. (3) Turn on the power switch on the back panel, and the time counter and other indicator lights at the front. (4) Set the following with the corresponding switches. The settings are changed in turn by pushing the switches. (The function of each setting, see paragraph 8). ・ Output frequency 50Hz ・ Stop signal a , b, ETR , 60Hz ・ Output pin S1 , S2, S3 ・ Test mode usual test , TRIP CHECK When the power is turned on, each item is set to the marked position. (5) Setting of the rated current First, set the ratio to CT rating because this tester is designed so that signals are output in percentages (%) of RATED CURRENT In at Electronic trip relay to RATED CURRENT MAX In max(CT rating). When the power is turned on, the rated current is set to H1.000 (IN=1.000×INMAX). ① In the case of a C type or S type relay, set the mode to H ○○○○ with the TEST SIGNAL(%) / RATIO signal level mode switch. Set to the value of the rated current setting dial of the trip relay with the signal adjusting switches or signal setting switches. Example: In the case where the rated current (IN) is set to 0.8, set to H0.800 . ② In the case of an M type relay, set as follows: Example: In the case where INMAX=1600A and IN=1283A, 1283A÷1600A=0.802, therefore set to H0.802. ③ In the case of measuring the ground fault tripping characteristics, set to H1.000 (even if the rated current is not set to 1.0). E-26 10.2 How to operate Test should be performed only after shutting off the electric power and verifying that there is no voltage present. Failure to do so may result in an electrical shock. DANGER When current is flowing in the main circuit of breaker, it is combined with the test signal of Y-2005, consequently does not become correct characteristic. The operating test should be performed in the state that load current does not flow in the main circuit. (1) Set the signal level indicator to ○○○○○.○ by pushing the TEST SIGNAL(%) / RATIO signal level mode switch. (2) Set the signal level with the signal adjusting switches or signal setting switches in % of IN set in 10.1 (5). When using the signal adjusting switches Continuing to push the switches 10% increases or decreases the signal 1% 0.1% level continuously. When using the signal setting switches ① Push the C (clear) key. To set 200%, push ② Since figures are shifted to the left every C 2 0 0 0 SET, and 0200.0 is set. time you push the numeral keys, indicate the desired value. ③ Push the SET key. (3) START Push the [START] switch, and the test signal is output, the time counter starts from 000.000, and also the [TESTING] mode indicating LED lights. (4) STOP To stop testing, push the [STOP] switch, and the test signal is stopped, the time counter stops, and also the [TESTING] mode indicating LED goes out. (5) With tripping, the TRIP indicating LED lights, and the time counter stops. Read the operating time at the time counter. (6) RESET Push the [RESET] switch to reset the TRIP indicating LED and the time counter, so that testing can be restarted. E-27 11. Test (for AE-SS/SH) 11.1 LTD Pick-up current test (1) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM". (2) Set the signal level to approximately 90% of the pick-up current. (3) Push the START switch. (4) Increase the signal with the signal adjusting switch, and measure the pick-up value. ① In the case of a C type or S type relay, the long-time-delay pick-up current is to be taken when the [OVER] LED of the trip relay lights. In the case where IU of the S relay is not set to 1.0, for example, if IU is 0.8 and the [OVER] LED lights are at 94%, the pick-up value is 94%÷0.8=117.5%. ② In the case of an M type relay, the long-time-delay pick-up current is to be taken when the [100%] LED lights. (5) Push the STOP switch. (6) Return the trip relay setting changed in (1) to the initial condition. 11.2 LTD operating time test (1) Set the signal level to be tested. ① In the case of a C type or S type relay, the operating time is to be taken at 200%, therefore set the signal level to 00200.0. In the case where IU of the S relay is not set to "1.0", for example, if IU is 0.9, 0.9×200%=180%, therefore set the signal level to 00180.0. ② In the case of an M relay, for example, if the long-time-delay pick-up current (IL) is set to "1.05", 1.05×120%=126%, therefore set the signal level to 00126.0. (2) Set the short-time-delay pick-up current (IS) setting dial and the instantaneous pick-up current (II) setting dial of the trip relay to 1.2 times the above-mentioned signal level or more. If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (3) Push the START switch. (4) After tripping, the operating time is indicated. (5) Push the RESET switch. (6) Return the trip relay settings changed in (2) to the initial conditions. Since Electronic trip relay has a memory effect for overcurrent state, when the operating time test is interrupted on the way, the operating time at the next test becomes short. This memory effect can be reset by tripping. Therefore, if operating time test is interrupted on the way, perform the next test after tripping Electronic trip relay one-time. To trip, perform the trip check in accordance with 11.10. <Hint> In 11.1 and 11.2, if IU of the S relay is not set to "1.0", the reading of the signal level is regarded as the long-time-delay pick-up current (%) by setting the value of H○.○○○ to IN×IU. When measuring the long-time-delay operating time, measurement can be performed with the signal level 00200.0. When performing the short-time-delay or instantaneous tests, return the setting of H○.○○○ to the initial value. E-28 11.3 STD Pick-up current test (1) Set the instantaneous pick-up current (II) setting dial of the trip relay to the maximum. Set the short-time-delay operating time (TS) to 0s. (minimum). If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (2) Set the signal level to approximately 80% of the short-time-delay pick-up current. (3) Push the START switch, immediately increase the signal with the signal adjusting switch until Electronic trip relay trips and Time counter LED stops. Increase the signal with this key Signal adjusting switches (4) Read the signal level indicated at the time. (5) In addition, measure the operating times before and after the short-time-delay pick-up current measured above, and take the point where the operating time shortens suddenly as the measured value of the short-time-delay pick-up current (IS). (6) Return the trip relay settings changed in (1) to the initial conditions. * If there is a long delay in increasing the signal, long-time-delay operation may be performed before reaching the short-time-delay pick-up current. In this case, start again from approximately 95% of the short-time-delay pickup current. 11.4 STD operating time test (1) Set the instantaneous pick-up current (II) of the trip relay to the maximum. If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (2) Set the signal level to be tested. For example, if the short-time-delay pick-up current (IS) setting dial is set to 4.5, 450%×1.5=675%, therefore set the signal level to 00675.0. Here, 1.5 is the value with which the operating time becomes flat. Time→ * Ts Is (3) Push the START switch. Is×1.5 → Current (4) After tripping, the operating time is indicated. When the stop signal is made by the main contact or auxiliary switch (AX) When the stop signal is made through the test connector of Electronic trip relay Take the reading of the counter as it is. Add 20ms. (mechanical operating time) to the reading of the counter. (5) Push the RESET switch. (6) Return the trip relay settings changed in (1) to the initial conditions. (7) Be aware that instantaneous operation may be performed near the instantaneous pick-up current (II) due to the influence of the signal making phase. E-29 11.5 INST Pick-up current test (1) Set the long-time-delay operating time (TL) setting dial of the trip relay to the maximum. If the INST/MCR switch is provided, set the switch to "INST." If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (2) Set the signal level to approximately 80% of the instantaneous pick-up current (I). (3) Push the START switch with the [STD LOCK] switch of the trip relay pushed, immediately increase the signal with the signal adjusting switch until Electronic trip relay trips and Time counter LED stops. Increase the signal level with this 10% step key. (4) Read the signal level. (5) Push the RESET switch. (6) Return the trip relay settings changed in (1) to the initial Signal adjusting switches conditions. * If there is a long delay in increasing the signal, long-time-delay operation may be performed before reaching the instantaneous pick-up current. In this case, start again from approximately 95% of the instantaneous pick-up current. * If the MCR/INST switch of the trip relay is set to MCR when the circuit breaker is on, instantaneous operation is not performed but short-time-delay or long-time-delay operation is performed. 11.6 INST operating time test Time → (1) Set the signal level to be tested. For example, if the instantaneous pick-up current (II) setting dial is set to "10", 1000%×1.5=1500%, therefore set the signal level to TI 01500.0. * → Current Here, 1.5 is the value with which the operating time becomes flat. II I I×1.5 (2) Push the START switch with the [STD LOCK] switch of the trip relay pushed. (3) After tripping, the operating time is indicated. When the stop signal is made by the main contact or auxiliary switch (AX) When the stop signal is made through the test connector of Electronic trip relay Take the reading of the counter as it is. Add 20ms. (mechanical operating time) to the reading of the counter. (4) Push the [RESET] switch. When checking the short time operation such as INST operating time test, in order to measure the operating time with accuracy, push the “Test power manual connecting switch VT “, and push START switch after the “Test power indicating LED” lighting. If do not pushing the “Test power manual connecting switch VT “, exact measurement cannot be performed. 11.7 MCR function check (1) Set the INST/MCR switch of the trip relay to MCR. Set the stop signal of Y-2005 to ETR. (2) Instantaneous operation is performed with the circuit breaker off. Check the instantaneous operation in accordance with 11.5 and 11.6. * This test is checking that instantaneous characteristics is effective during breaker closing operation (from open to close). (3) Instantaneous tripping characteristics disappear with the circuit breaker on. Set the signal level exceeding the instantaneous pick-up current (II), and check that instantaneous operation is not performed. E-30 11.8 GFR Pick-up current test (1) Set the ground fault alarm switch of the trip relay to "TRIP," and set the ground fault operating time (TG) to "0.3"s. (minimum). (2) Set the signal output pin to [S2], and set the rated current to H1.000 in accordance with paragraph 10. (3) Set the rated current of the tester to IN=1×INMAX. (See 10.1 (5) ③). (4) Set the signal level to approximately 80% of the ground fault pick-up current (IG). (5) Push the START switch, immediately increase the signal with the signal adjusting switch until Electronic trip relay trips and Time counter LED stops. (6) Read the signal level indicated at the time. (7) In addition, push the START switch at several points before and after the ground fault pick-up current measured in (6), and take the minimum value with which the trip relay trips as the measured value of the ground fault pick-up current (IG). (8) Return the trip relay settings changed in (1) to the initial conditions. 11.9 GFR operating time test (1) Set the signal level to be tested. (2) Set the ground fault alarm switch of the trip relay to "TRIP." (3) Set the signal output pin to [S2], and set the rated current to H1.000 in accordance with paragraph 10. For example, if the ground fault pick-up current (IG) is set to "0.3", 30%×1.5=45%, therefore set the signal level to 00045.0. Here, 1.5 is the value with which the operating time becomes flat. Time * TG (4) Push the START switch. IG IG×1.5 (5) After tripping, the operating time is indicated. When the stop signal is made by the main contact or auxiliary switch (AX) When the stop signal is made through the test connector of Electronic trip relay Take the reading of the counter as it is. Add 20ms. (mechanical operating time) to the reading of the counter. (6) Push the RESET switch. (7) Return the trip relay setting changed in (2) to the initial condition. When checking the short time operation such as GFR operating time test, in order to measure the operating time with accuracy, push the “Test power manual connecting switch VT “, and push the START switch after the “Test power indicating LED” lighting. If do not pushing the “Test power manual connecting switch VT “, exact measurement cannot be performed. E-31 Current 11.10 Trip check The circuit breaker can be tripped instantaneously with this trip check, which is effective when checking the panel sequence and resetting the memory effect in 11.2 (7). (1) Set the test mode to "TC" (trip check). (2) If the INST/MCR switch is provided for the trip relay, set the switch to "INST." (3) Push the START switch. (4) Check that the circuit breaker is tripped instantaneously. (5) Push the RESET switch. (6) Return the trip relay setting changed in (2) to the initial condition. When checking the circuit breaker operating time, push the “Test power manual connecting switch VT “, and push START switch after the “Test power indicating LED” lighting. If do not pushing the “Test power manual connecting switch VT “, exact measurement cannot be performed. 11.11 PAL pick-up current test (1) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (2) Set the signal level to approximately 80% of the pre-alarm pick-up current (IP). (3) Push the START switch. (4) Increase the signal with the signal adjusting switch, and take the value with which the [PAL] LED of the trip relay lights as the measured value of the pre-alarm pick-up current. (5) Push the STOP switch. (6) Return the trip relay setting to the initial condition. 11.12 PAL operating time test (1) Input control power to the trip relay (between R+ and R1- or between R+ and R2- of the circuit breaker's control circuit terminal block). (2) If the trip relay has the ground fault function (GFR), set the ground fault alarm switch to "ALARM." (3) Set the stop signal input of the tester to [a], and connect the PAL OUT contacts (T0+ and T4-) of the circuit breaker with the input terminals on the back of the tester. (4) Set the signal level to be tested. (See 11.2 LTD operating time test). (5) Push the START switch. (6) After operation, the operating time is indicated. (7) Push the RESET switch. (8) Return the trip relay setting to the initial condition. 11.13 OCR alarm switch (AL) check Measure the AL operating time with an oscilloscope, millisecond counter or the like. The minimum AL operating time is 30 ms., however, when measured with Y-2005, the operating time is approximately 5 ms. shorter than that taken when tripping at the actual current. E-32 12. Settings and accuracy (for AE-SS/SH) 12.1 Settings and accuracy of type C relay Maximum rated current INMAX (CT rating) ① ⑤ ③ STD LOCK switch ④ No. Item Mark Setting range AE630~4000-SS /AE-SH [tolerance] AE5000-SS AE6300-SS 0.5-0.6-0.7-0.8-0.9-1.0×INMAX ① Rated current IN [The LTD pick-up current ranges from 105% to 125% of the rated current.] ② LTD time TL 150 s. at 2×IN (fixed) [±20%] ③ STD Pick-up current IS 2-3-4-6-8-10×IN [±15%] ④ STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5×IS [±20%] ⑤ INST pick-up current II ⑥ Pre-alarm pick-up current IP 4-6-8-10-12-16×IN 4-6-8-10-12×IN 4-6-8-10×IN [±15%] [±15%] [±15%] 0.7-0.8-0.9-1.0-OVER×IN E-33 [±10%] 12.2 Settings and accuracy of type S/SL relay Maximum rated current INMAX (CT rating) ② ① ⑧ ⑥ ⑨ ④ ⑦ STD LOCK switch ⑩ ③ ⑤ ⑪ No. ① Item Rated current Mark Setting range AE630~4000-SS /AE-SH [tolerance] IN 0.5-0.6-0.7-0.8-0.9-1.0×INMAX AE5000-SS AE6300-SS 0.8~1.0×IN ② Uninterrupted current IU ③ LTD time TL ④ STD Pick-up current ⑤ [The LTD pick-up current ranges from 105% to 125% of the uninterrupted current.] S series: 50-100-150s. at 2×IU [±20%] SL series: 10-15-20-25-30s. at 5×IU [±20%] IS 2-3-4-6-8-10×IN [±15%] STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5×IS [±20%] ⑥ INST pick-up current II 4-6-8-10-12-16×IN [±15%] ⑦ (INST/MCR) switch - Switch to select instantaneous tripping characteristics or MCR. ⑧ Pre-alarm pick-up current IP 0.7-0.8-0.9-1.0-OVER×IU [±10%] ⑨ Ground fault pick-up current (Note 1) IG 0.1-0.2-0.3-0.5×INMAX [±20%] [±20%] ⑩ Ground fault operating time TG 0.3-0.8-1.5-3 s. at 1.5×IG ⑪ Ground fault alarm switch - Switch to select tripping or only alarm with a ground fault. (Note 1) (Note 2) (Note 2) 4-6-8-10-12×IN [±15%] 0.2-0.3-0.5×INMAX 4-6-8-10×IN [±15%] [±20%] The setting for AE4000-SS is the same as that for AE5000-SS and AE6000-SS. "MCR" is an abbreviation for "making current release", which has INST characteristics only when the circuit breaker is turned on (make). After the circuit breaker is turned on (make), the INST characteristics disappear. E-34 12.3 Settings and accuracy of type M relay Maximum rated current INMAX (CT rating) ② ① ⑧ ⑦ ⑨ ⑤ STD LOCK switch ③ ⑩ ⑥ ⑪ ④ No. Item Symbol Setting range AE630~4000-SS /AE-SH [tolerance] AE5000-SS AE6300-SS ① Rated current IN Set at the factory within the range of 0.5~1.0×INMAX ② LTD Pick-up current IL 1.0-1.05-1.1-1.15-1.2×IN [±5%] ③ LTD time YL 15-20-25-30-40-60s. at 1.2×IL [±20%] ④ LTD Pick-up time fine adjustment - 0.8~1.0~1.2×TL ⑤ STD Pick-up current IS 2-2.5-3-3.5-4-4.5×IN [±15%] ⑥ STD time TS 0-0.1-0.2-0.3-0.4-0.5s. at 1.5×IS [±20%] ⑦ INST pick-up current II 4-6-8-10-12-16×IN [±15%] ⑧ Pre-alarm pick-up current IP 0.84-0.88-0.92-0.96-1.0×IL ⑨ Ground (Note) ⑩ ⑪ pick-up current 4-6-8-10×IN [±15%] [±5%] IG 0.1-0.2-0.3-0.5 ×INMAX [±20%] Ground fault operating time TG 0.3-0.8-1.5-3s. at 1.5×IG Ground fault alarm switch - Switch to select tripping or only alarm with a ground fault. (Note) fault 4-6-8-10-12×IN [±15%] 0.2-0.3-0.5×INMAX The setting for AE4000-SS is the same as that for AE5000-SS and AE6300-SS. E-35 [±20%] [±20%] 13. Inspection form (for AE-SS/SH) Inspection report form for S type relay Date: E-36 Checked person: 三菱低圧気中遮断器 AE形 Low-Voltage Air Circuit Breakers type AE フィールドテスト装置Y-2005 Field test device Y-2005 当社管理用コードです。 This is our administrative code. LN338A475H04 IB63C07-E2403
advertisement
Key Features
- Portable design
- Field testing without current
- Various test modes
- Time counter
- Signal level adjustment
- Trip check function
- Ground fault testing
- Pre-alarm testing
- Compatible with AE-SW, AE-SS, and AE-SH series
Related manuals
Frequently Answers and Questions
What circuit breaker series is the Y-2005 compatible with?
The Y-2005 is compatible with Mitsubishi Low-Voltage Air Circuit Breakers series AE-SW, AE-SS and AE-SH.
How does the Y-2005 test the trip relay without applying current?
The Y-2005 utilizes a voltage signal to simulate the current conditions of the trip relay without needing actual current flow. This allows for safe and convenient testing in the field.
What type of tests can be performed with the Y-2005?
The Y-2005 can perform various tests, including overcurrent tripping, ground fault tripping, pick-up currents, and operating times. Specific tests vary depending on the circuit breaker type and available modules.