Residential Smart Inverter Solutions
ES Uniq 8.0-12kW
LX A5.0-10
LX A5.0-30
User Manual
1
Copyright Statement:
Copyright © GoodWe Technologies Co., Ltd. 2024. All rights reserved.
No part of this manual can be reproduced or transmitted to the public platform in any form or by
any means without the prior written authorization of GoodWe Technologies Co.,Ltd.
Trademarks
and other GOODWE trademarks are trademarks of GoodWe Technologies Co., Ltd. All
other trademarks or registered trademarks mentioned in this manual are owned by the company.
NOTICE
The information in this user manual is subject to change due to product updates or other reasons.
This manual cannot replace the product safety labels unless otherwise specified. All descriptions in
the manual are for guidance only.
2
1 About This Manual ....................................................................................................................................................... 8
1.1 Overview ............................................................................................................................................................... 8
1.2 Applicable Model ............................................................................................................................................. 8
1.3 Symbol Definition ............................................................................................................................................. 9
2 Safety Precautions ...................................................................................................................................................... 10
2.1 General Safety .................................................................................................................................................. 10
2.2 Personnel Requirements ............................................................................................................................. 10
2.3 System Installation ......................................................................................................................................... 11
2.3.1 PV String Safety .................................................................................................................................. 13
2.3.2 Inverter Safety ..................................................................................................................................... 13
2.3.3 Battery Safety ...................................................................................................................................... 14
2.3.4 Smart Meter Safety........................................................................................................................... 15
2.4 Safety Symbols and Certification Marks ............................................................................................ 15
2.5 EU Declaration of Conformity .................................................................................................................. 17
2.5.1 Equipment with Wireless Communication Modules ...................................................... 17
2.5.2 Equipment without Wireless Communication Modules (Except Battery) ........... 17
2.5.3 Battery ..................................................................................................................................................... 18
3 System Introduction................................................................................................................................................... 19
3.1 System Overview ............................................................................................................................................ 19
3.2 Product Overview ........................................................................................................................................... 21
3.2.1 Inverter .................................................................................................................................................... 21
3.2.3 Smart Meter ......................................................................................................................................... 22
3.2.4 Smart Dongle....................................................................................................................................... 23
3.3 Supported Grid Types .................................................................................................................................. 24
3.4 System Working Mode ................................................................................................................................ 24
4 Check and Storage ...................................................................................................................................................... 28
3
4.1 Check before Acceptance .......................................................................................................................... 28
4.2 Package Content ............................................................................................................................................. 28
4.2.1 Inverter deliverables (ES Uniq) ................................................................................................... 28
4.2.2 Battery deliverables (LX A5.0-10).............................................................................................. 29
4.2.3 Battery deliverables (LX A5.0-30).............................................................................................. 31
4.2.4 Smart Meter Deliverables (GMK110) ...................................................................................... 32
4.2.5 Smart Meter (GM3000) .................................................................................................................. 32
4.2.6 Smart Dongle (WiFi/LAN Kit-20) ............................................................................................... 33
4.2.7 Smart Dongle (Ezlink3000) ........................................................................................................... 33
4.3 Storage ................................................................................................................................................................. 33
5 Installation ....................................................................................................................................................................... 35
5.1 System Installation and Commissioning Procedure .................................................................... 35
5.2 Installation Requirements .......................................................................................................................... 35
5.2.1 Installation Environment Requirements ................................................................................ 35
5.2.2 Installation Space Requirements ............................................................................................... 37
5.2.3 Tool Requirements ............................................................................................................................ 37
5.3 Equipment Handling ..................................................................................................................................... 39
5.4 Installing the Inverter ................................................................................................................................... 39
5.5 Installing the Battery System ................................................................................................................... 40
5.6 Installing the Smart Meter......................................................................................................................... 44
6 System Wirings ............................................................................................................................................................. 46
6.1 System Wiring Diagram .............................................................................................................................. 46
6.2 Detailed System Wiring Diagram........................................................................................................... 47
6.2.1 Detailed System Wiring Diagram For Single Inverter .................................................... 47
6.2.2 Detailed System Wiring Diagram For Parallel System ................................................... 49
6.3 Preparing Materials ....................................................................................................................................... 49
4
6.3.1 Preparing Breakers ............................................................................................................................ 50
6.3.2 Preparing Cables ................................................................................................................................ 51
6.4 Connecting the PE cable............................................................................................................................. 53
6.5 Connecting the PV Cable ........................................................................................................................... 54
6.6 Connecting the Battery Cable ................................................................................................................. 55
6.6.1 Connecting the Power Cable between the Inverter and Battery ............................. 63
6.6.2 Connecting the Communication Cable between the Inverter and Battery ....... 66
6.7 Connecting the AC Cable ........................................................................................................................... 68
6.8 Connecting the Meter Cable .................................................................................................................... 69
6.9 Connecting the Inverter Communication Cable ............................................................................ 71
6.10 Connect the smart dongle ...................................................................................................................... 73
7 System Commissioning ............................................................................................................................................ 74
7.1 Check before Power ON ............................................................................................................................. 74
7.2 Power ON............................................................................................................................................................ 74
7.2.1 Power on a single inverter system ........................................................................................... 75
7.2.2 Power on a parallel system........................................................................................................... 76
7.3 Indicators ............................................................................................................................................................ 76
7.3.1 Inverter Indicators ............................................................................................................................. 76
7.3.2 Battery Indicators .............................................................................................................................. 77
7.3.3 Smart Meter Indicator..................................................................................................................... 79
7.3.4 Smart Dongle Indicator .................................................................................................................. 80
8 Quick System Commissioning .............................................................................................................................. 83
8.1 Downloading the App .................................................................................................................................. 83
8.2 Connecting the Inverter .............................................................................................................................. 83
8.3 Communication Settings ............................................................................................................................ 85
8.4 Quick Settings .................................................................................................................................................. 86
5
8.5 Creating Power Plants .................................................................................................................................. 89
9 System Commissioning ............................................................................................................................................ 90
9.1 SolarGo Overview ........................................................................................................................................... 90
9.1.1 App Interface Structure .................................................................................................................. 91
9.1.2 Introduction to the SolarGo App Login Interface ............................................................ 92
9.1.3 Introduction to the Main Interface of SolarGo App ....................................................... 93
9.2 Connecting the Inverter .............................................................................................................................. 94
9.3 Quick Settings .................................................................................................................................................. 96
9.4 Communication Settings ............................................................................................................................ 98
9.5 Setting the Basic Information .................................................................................................................. 99
9.5.1 Setting the Basic Information ..................................................................................................... 99
9.5.2 Setting Advanced Parameters ................................................................................................. 100
9.5.3 Setting Power Limit Parameters ............................................................................................. 101
9.5.4 Setting the Battery Parameters ............................................................................................... 102
9.5.5 Setting Generator Parameters ................................................................................................. 105
9.5.6 Setting Load Control..................................................................................................................... 106
9.6 Setting Safety Parameters....................................................................................................................... 107
9.6.1 Setting the Basic Safety Parameters ..................................................................................... 107
9.6.2 Setting Customized Safety Parameters .............................................................................. 108
10 Monitoring Power Plant ..................................................................................................................................... 114
10.1 SEMS Portal Overview ............................................................................................................................ 114
10.2 Manage power plant or equipment ............................................................................................... 116
10.2.1 Power plant creation .................................................................................................................. 116
10.2.2 Power plant management ....................................................................................................... 117
10.2.3 Managing the equipment in the power plant.............................................................. 118
10.3 Power plant monitoring ........................................................................................................................ 119
6
10.3.1 Viewing power plant information ....................................................................................... 119
10.3.2 Viewing Alarm Information .................................................................................................... 120
11 Maintenance ............................................................................................................................................................. 122
11.1 Power OFF the System ........................................................................................................................... 122
11.2 Removing the Equipment .................................................................................................................... 124
11.3 Disposing of the Equipment ............................................................................................................... 124
11.4 Routine Maintenance.............................................................................................................................. 124
11.5 Troubleshooting ........................................................................................................................................ 125
11.5.1 System Troubleshooting .......................................................................................................... 126
11.5.2 Inverter Troubleshooting ......................................................................................................... 127
11.5.3 Battery fault (LX A5.0-30) ........................................................................................................ 140
11.5.4 Battery fault (LX A5.0-10) ........................................................................................................ 141
12 Parameters................................................................................................................................................................. 145
12.1 Inverter Parameters ................................................................................................................................. 145
12.2 Battery Technical Data............................................................................................................................ 150
12.3 Smart Meter Technical Data ................................................................................................................ 152
12.4 Smart Dongle Technical Data ............................................................................................................. 154
13 Appendix .................................................................................................................................................................... 157
13.1 FAQ ................................................................................................................................................................... 157
13.1.1 How to conduct auxiliary detection for smart meters/CT?................................... 157
13.1.2 How to Upgrade the Device Version ................................................................................. 157
13.2 Abbreviations .............................................................................................................................................. 158
7
1 About This Manual
1.1 Overview
The energy storage system consists of inverter, battery system, and smart meter. This manual
describes the product information, installation, electrical connection, commissioning,
troubleshooting and maintenance of the system. Read through this manual before installing and
operating the products. This manual is subject to update without notice. For more product details
and latest documents, visit https://en.goodwe.com/.
1.2 Applicable Model
The energy storage system consists the following products:
Product type
Inverter
Product information
Description
ES Uniq Series
Rated output power: 8kW-12kW
Useable energy of 5.0kWh, supports a
LX A5.0-10
maximum of 6 batteries connected in
parallel.
Battery system
Useable energy of 5.12kWh, supports a
LX A5.0-30
maximum of 6 batteries connected in
parallel.
GMK110
Smart meter
The monitoring module in the energy
storage system can detect information such
GM330
as operating voltage, current, and other data
in the system.
In single inverter scenario, system operation
WiFi/LAN Kit-20
information can be uploaded to monitoring
platform through WiFi or LAN signals.
Smart dongle
In parallel system with multi inverters, it is
Ezlink3000
installed on the master inverter, uploads the
system running information to monitoring
platform through WiFi or LAN signals.
8
1.3 Symbol Definition
DANGER
Indicates a high-level hazard that, if not avoided, will result in death or serious injury.
WARNING
Indicates a medium-level hazard that, if not avoided, could result in death or serious injury.
CAUTION
Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury.
NOTICE
Highlights key information and supplements the texts. Or some skills and methods to solve
product-related problems to save time.
9
2 Safety Precautions
Please strictly follow these safety instructions in the user manual during the operation.
WARNING
The products are designed and tested strictly to comply with related safety rules. Read and
follow all the safety instructions and cautions before any operations. Improper operation
might cause personal injury or property damage as the products are electrical equipment.
2.1 General Safety
NOTICE
The information in this user manual is subject to change due to product updates or
other reasons. This manual cannot replace the product safety labels unless otherwise
specified. All descriptions in the manual are for guidance only.
Before installations, read through the user manual to learn about the product and the
precautions.
All operations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
Use insulating tools and wear personal protective equipment (PPE) when operating the
equipment to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips
when touching electronic devices to protect the equipment from damage.
Unauthorized dismantling or modification may damage the equipment, the damage is
not covered under the warranty.
Strictly follow the installation, operation, and configuration instructions in this manual.
The manufacturer shall not be liable for equipment damage or personal injury if you do
not follow the instructions. For more warranty details, please visit
https://en.goodwe.com/warranty.
2.2 Personnel Requirements
NOTICE
Personnel who install or maintain the equipment must be strictly trained, learn about
safety precautions and correct operations.
10
Only qualified professionals or trained personnel are allowed to install, operate,
maintain, and replace the equipment or parts.
2.3 System Installation
DANGER
Disconnect the upstream and downstream switches to power off the equipment before
any electrical connections. Do not work with power on. Otherwise, an electric shock may
occur.
Install a breaker at the voltage input side of the equipment to prevent personal injury or
equipment damage caused by energized electrical work.
All operations such as transportation, storage, installation, use and maintenance shall
comply with applicable laws, regulations, standards and specifications.
Perform electrical connections in compliance with local laws, regulations, standards and
specifications. Including operations, cables, and component specifications.
Connect cables using the connectors included in the package. The manufacturer shall
not be liable for equipment damage if other connectors are used.
Ensure all cables are connected tightly, securely, and correctly. Inappropriate wiring may
cause poor contacts and damage the equipment.
The PE cables must be connected and secured properly.
To protect the equipment and components from damage during transportation, ensure
that the transportation personnel are professionally trained. All operations during the
transportation have to be recorded. The equipment shall be kept in balance, thus
avoiding falling down.
The equipment is heavy. Please equip the corresponding personnel according to its
weight, so that the equipment does not exceed the weight range of the human body
can carry, and cause personnel injury.
Keep the equipment stable to avoid dumping, which can result in equipment damage
and personal injuries.
WARNING
Do not apply mechanical load to terminals, otherwise the terminals may be damaged.
If the cable bears too much tension, the connection may be poor. Reserve a certain
length of the cable before connecting it to corresponding ports.
Tie the cables of the same type together, and place cables of different types at least
11
30mm apart. Do not place the cables entangled or crossed.
Place the cables at least 30mm away from the heating components or heat sources,
otherwise the insulation layer of the cables may be aging or broken due to high
temperature.
12
2.3.1 PV String Safety
WARNING
Ensure the component frames and the bracket system are securely grounded.
Ensure the DC cables are connected tightly, securely and correctly. Inappropriate wiring
may cause poor contacts or high impedances, and damage the inverter.
Measure the DC cable using a multimeter to avoid reverse polarity connection. Also, the
voltage should be within the permissible range.
Measure the DC cable using a multimeter to avoid reverse polarity connection. Also, the
voltage should be under the max DC input voltage. The manufacturer shall not be liable
for the damage caused by reverse connection and overvoltage.
The PV strings cannot be grounded. Ensure the minimum insulation resistance of PV
string to the ground meets the minimum insulation resistance requirements before
connecting the PV string to the inverter (R=maximum input voltage (V)/ 30mA).
Do not connect one PV string to more than one inverter at the same time. Otherwise, it
may cause damage to the inverter.
Photovoltaic modules used with inverters must comply with IEC 61730 Class A standard.
2.3.2 Inverter Safety
WARNING
The voltage and frequency at the connecting point should meet the on-grid
requirements.
Additional protective devices like circuit breakers or fuses are recommended on the AC
side. Specification of the protective device should be at least 1.25 times the maximum
AC output current.
The arc fault alarms will be cleared automatically if the alarms are triggered less than 5
times in 24 hours. The inverter will shutdown for protection after the 5th electric arc
fault. The inverter can operate normally after the fault is solved.
BACK-UP is not recommended if the PV system is not configured with batteries.
Otherwise, there may be a risk of system power outage.
13
2.3.3 Battery Safety
DANGER
Keep Power Off before any operations to avoid danger. Strictly follow all safety
precautions outlined in this manual and safety labels on the equipment during the
operation.
Do not disassemble, modify, or replace any part of the battery or the power control unit
without official authorization from the manufacturer. Otherwise, it will cause electrical
shock or damages to the equipment, which shall not be borne by the manufacturer.
Do not hit, pull, drag, squeeze or step on the equipment or put the battery into fire.
Otherwise, the battery may explode.
Do not place the battery in a high temperature environment. Make sure that there is no
direct sunlight and no heat source near the battery. When the ambient temperature
exceeds 60 ℃, it will cause fire.
Do not use the battery or the power control unit if it is defective, broken, or damaged.
Damaged battery may leak electrolyte.
Do not move the battery system while it is working. Contact after-sales service if the
battery shall be replaced or added.
A short circuit in the battery may cause personal injury. The instantaneous high current
caused by a short circuit can release a large amount of energy and may cause a fire.
WARNING
Factors such as: temperature, humidity, weather conditions, etc. may limit the battery's
current and affect its load.
Contact after-sale service immediately if the battery is not able to be started. Otherwise,
the battery might be damaged permanently.
Inspect and maintain the battery regularly according to the maintenance requirements
of the battery.
Emergency Measures
Battery Electrolyte Leakage
If the battery module leaks electrolyte, avoid contact with the leaking liquid or gas. The
electrolyte is corrosive. It will cause skin irritation or chemical burn to the operator. Anyone
contact the leaked substance accidentally has to do as following:
Breath in the leaked substance: Evacuate from the polluted area, and seek immediate
medical assistance.
Eye contact: Rinse your eyes for at least 15 minutes with clean water and seek immediate
14
medical assistance.
Skin contact: Thoroughly wash the touch area with soap and clean water, and seek
immediate medical assistance.
Ingestion: Induce vomiting, and seek immediate medical assistance.
Fire
The battery may explode when the ambient temperature exceeds 150℃. Poisonous and
hazardous gas may be released if the battery is on fire.
In the event of a fire, please make sure that the carbon dioxide extinguisher or Novec1230
or FM-200 is nearby.
The fire cannot be put out by ABC dry powder extinguisher. Firefighters are required to wear
full protective clothing and self-contained breathing apparatus.
2.3.4 Smart Meter Safety
WARNING
If the voltage of the power grid fluctuates, resulting in the voltage to exceed 265V, in this
case, long-term overvoltage operation may cause damage to the meter. It is recommended
to add a fuse with a rated current of 0.5A on the voltage input side of the meter to protect
it.
2.4 Safety Symbols and Certification Marks
DANGER
All labels and warning marks should be visible after the installation. Do not cover, scrawl,
or damage any label on the equipment.
The following descriptions are for reference only.
Number
1
Symbol
Descriptions
Potential risks exist. Wear proper personnel
protective equipment before any operations.
HIGH VOLTAGE HAZARD. Disconnect all incoming
2
power and turn off the product before working on
it.
15
3
4
5
High-temperature hazard. Do not touch the product
under operation to avoid being burnt.
Operate the equipment properly to avoid explosion.
Batteries contain flammable materials, beware of
fire.
The equipment contains corrosive electrolytes. In
6
case of a leak in the equipment, avoid contact the
leaked liquid or gas.
7
Delayed discharge. Wait 5 minutes after power off
until the components are completely discharged.
8
Install the equipment away from fire sources.
9
Keep the equipment away from children.
10
Do not pour with water.
11
12
Read through the user manual before any
operations.
Wear personal protective equipment during
installation, operation and maintaining.
Do not dispose of the System as household waste.
13
Deal with it in compliance with local laws and
regulations, or send it back to the manufacturer.
14
Grounding point.
16
15
Recycle regeneration mark.
16
CE mark
17
TUV mark
18
RCM mark
2.5 EU Declaration of Conformity
2.5.1 Equipment with Wireless Communication Modules
GoodWe Technologies Co., Ltd. hereby declares that the equipment with wireless communication
modules sold in the European market meets the requirements of the following directives:
Radio Equipment Directive 2014/53/EU (RED)
Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
Waste Electrical and Electronic Equipment 2012/19/EU
Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH)
2.5.2 Equipment without Wireless Communication Modules (Except
Battery)
GoodWe Technologies Co., Ltd. hereby declares that the equipment without wireless communication
modules sold in the European market meets the requirements of the following directives:
Electromagnetic compatibility Directive 2014/30/EU (EMC)
Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS)
Waste Electrical and Electronic Equipment 2012/19/EU
Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH)
17
2.5.3 Battery
GoodWe Technologies Co., Ltd. hereby declares that batteries sold in the European market meets
the requirements of the following directives:
Electromagnetic compatibility Directive 2014/30/EU (EMC)
Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD)
Battery Directive 2006/66/EC and Amending Directive 2013/56/EU
Waste Electrical and Electronic Equipment 2012/19/EU
Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH)
You can download the EU Declaration of Conformity on the official website: https://en.goodwe.com.
18
3 System Introduction
3.1 System Overview
The residential smart inverter solution consists of inverter, battery system, smart meter, smart
dongle, etc.. In the PV system, solar energy can be convert to electric energy for household needs.
The IoT devices in the system controls the electrical equipment by recognizing the overall power
consumption situation. So that the power will be managed in a smart way, deciding whether the
power is to be used by the loads, stored in batteries, or exported to the grid, etc.
Product
Type
Model
Description
When only one inverter is used in the system, it is
supported to connect generator.
GW8000-ES-C10
Inverter
GW10K-ES-C10
GW12K-ES-C10
When multiple inverters are used in the system, it is not
supported to connect generator; a maximum of 16
inverters are supported to form a parallel system, and
the Ezlink3000 is required in the parallel system.
Requirements for parallel system:
The software version of all inverters in the system
19
is the same.
The ARM software version of the inverter is 08
(415) and above.
The DSP software version of the inverter is
00(2525) and above.
Battery of different models cannot be mix used.
LX A5.0-10: The nominal charging and discharging
LX A5.0-10
current of a single battery is 60A; a maximum of 15
batteries can be connected in parallel in one system.
LX A5.0-30: The nominal charging current of a single
battery is 60A, and the discharging current is 100A; the
maximum continuous charging current is 90A; the
Battery
LX A5.0-30
maximum continuous discharging current is 150A. A
maximum of 30 batteries can be connected in parallel
system
in one system.
Supports connection to lead-acid batteries of AGM,
GEL, and Flooded types.
Lead Acid Battery
The number of batteries that can be connected in series
is calculated based on the voltage of lead-acid
batteries, and the total voltage of batteries connected
in series is not allowed to exceed 60V.
When the charging and discharging current between
the battery and the inverter is less than 160A, it
supports direct connection between battery and
inverter without using a busbar. For example: It
supports connecting GW8000-ES-C10 to LX A5.0-30
without using a busbar. For detailed battery wiring
BCB-11-WW-0
Busbar
methods, please refer to 6.6 Connecting Battery Cables.
BCB-22-WW-0
When the charging and discharging current between
BCB-32-WW-0
battery and inverter is ≥160A, a busbar or busbar box
(Purchase from
GoodWe)
must be used to connect the inverter. (Current ≥ M x
IBat rated. (M: The quantity of batteries connected in
parallel in the system, IBat rated: The rated current of
the battery).
BCB-11-WW-0: Used with LX A5.0-10, the battery
system supports a maximum working current of
360A, working power of 18kW, and can connect to
a maximum of 3 inverters, and 6 batteries.
BCB-22-WW-0: Used with LX A5.0-10, the battery
20
system supports a maximum working current of
720A, working power of 36kW, and can connect to
a maximum of 6 inverters, and 12 batteries.
BCB-32-WW-0: Used with LX A5.0-30, the battery
system supports a maximum working current of
720A, working power of 36kW, and can connect to
a maximum of 6 inverters, and 15 batteries.
Others: Please prepare busbar based on actual
system power and current.
Built-in smart meter: 10-meter wire CT, default CT ratio:
120A/40mA
Built-in Smart
Smart meter
GMK110: When the length of the built-in CT cable of
Meter
the inverter is not enough for connection to the
(Standard)
switchboard, it can be extended through an external
GMK110 smart meter. CT is not supported for changing
GMK110
to other type, CT ratio: 120A/40mA
(Optional)
GM330
CM330: order the CT for GM330 from GoodWe or other
(purchase from
suppliers. CT ratio: nA/5A.
GoodWe)
nA: CT primary input current, n ranges from 200 to
5000.
5A: CT Secondary input current.
WiFi/LAN Kit-
Please use the WiFi/LAN Kit-20 module in single
inverter system.
20 (Standard)
Smart dongle
Ezlink3000
In parallel scenarios, the EzLink3000 must be connected
(purchase from
GoodWe)
to the master inverter. Do not connect any smart
dongle to slave inverter. Ezlink3000 requires a firmware
version of 04 or above.
3.2 Product Overview
3.2.1 Inverter
Inverters control and optimize the power in PV systems through an integrated energy
management system. The power generated in the PV system can be used, stored in the
battery, output to the utility grid, etc.
21
Nominal output
Number
Model
1
GW8000-ES-C10
8kW
220/230/240
2
GW10K-ES-C10
10kW
220/230/240
3
GW12K-ES-C10
12kW
220/230/240
power
Nominal output voltage
3.2.3 Smart Meter
The smart meter can measure and monitor the data in the photovoltaic energy storage system, such
as voltage, current, frequency, power factor, and power.
22
Number
Model
1
GMK110
Applicable scenarios
CT is not supported for changing to other type, CT ratio:
120A/40mA
Order the CT for GM330 from GoodWe or other suppliers. CT
2
GM330
ratio: nA/5A.
nA: CT primary input current, n ranges from 200 to 5000.
5A: CT secondary input current.
3.2.4 Smart Dongle
The smart dongle can transmit various power generation data to SEMS Portal, the remote
monitoring platform, in real time. And connect to the SolarGo App to complete local equipment
commissioning.
Number
Model
Signal
Applicable scenarios
1
WiFi/LAN Kit-20
Bluetooth, WiFi, LAN
Single inverter scenario
23
2
Ezlink3000
Bluetooth, WiFi, LAN
Master inverter of a parallel
system
3.3 Supported Grid Types
3.4 System Working Mode
Self-Use Mode
Self-use mode is the basic working mode of the system.
When the power generated in the PV system is sufficient, it will supply the loads in priority. The
excess power will charge the batteries first, then the remaining power will be sold to the utility
grid. When the power generated in the PV system is insufficient, the battery will supply the loads
in priority. If the battery power is insufficient, the load will be powered by the utility grid.
24
BACK-UP Mode
The BACK-UP mode is mainly applied to the scenario where the grid is unstable.
When the grid is disconnected, the inverter turns to off-grid mode and the battery will supply
power to the BACK-UP loads; when the grid is restored, the inverter switches to grid-tied mode.
The battery will be charged to preset SOC protection value by utility grid or PV when the system
is running on-grid. So that the battery SOC is sufficient to maintain normal working when the
system is off-grid. The purchase of electricity from the power grid to charge the battery must
comply with local laws and regulations.
25
Economic mode
It is recommended to use economic mode in scenarios when the peak-valley electricity price varies a
26
lot. Select economic mode only when it meets the local laws and regulations.
For example, set the battery to charge mode during Valley period to charge battery with grid power.
And set the battery to discharge mode during Peak period to power the load with the battery.
27
4 Check and Storage
4.1 Check before Acceptance
Check the following items before accept the product.
1. Check the outer packing box for damage, such as holes, cracks, deformation, and other signs of
equipment damage. Do not unpack the package and contact the supplier as soon as possible if
any damage is found.
2. Check the product model. If the product model is not what you requested, do not unpack the
product and contact the supplier.
4.2 Package Content
WARNING
Check the deliverables for correct model, complete contents, and intact appearance. Contact the
supplier as soon as possible if any damage is found.
4.2.1 Inverter deliverables (ES Uniq)
Component
Description
Component
Description
Inverter x1
Mounting plate x1
Expansion screws x4
Screw x1
Battery power
Nut x8
connection
terminal x 2
AC terminal x 6
PE terminal x 1
28
PV DC terminal
GW8000-ES-C10 x 3
Smart dongle x 1
GW10K-ES-C10、
GW12K-ES-C10 x 4
2PIN terminal x 2
2PIN terminal x 2
AC protection cover
2PIN terminal x 2
x1
BMS
Waterproof rubber seal x 1
communication
cable x 1
CT connection cable x 1
Documents x 1
PIN terminal x 14
Battery screw x 2
Lead-acid battery
temperature sensor cable x
Magnet x 1
1
4.2.2 Battery deliverables (LX A5.0-10)
Battery
Component
Description
Component
Description
M5 OT terminal x
Battery module x 1
2
M8 OT terminal
29
x4
M5 grounding
Warning label x
screw x 2
1
Terminal resistor x
Electrical Label x
1
1
Battery bracket x
Documents x 1
2 (optional)
Support column x
M4*8 screw x 8
2 (optional)
(optional)
When selecting stacking way to install the battery, the battery bracket, support
column, and M4*8 screw are included in the package.
Busbar box (BCB-11-WW-0) (optional)
Component
Description
Component
Description
360A busbar box x
M6 expansion bolt x
1
4
M8 OT terminal x
18
M10 OT terminal x
-
-
Component
Description
2
Busbar box (BCB-22-WW-0) (optional)
Component
Description
720A busbar box
M6 expansion bolt x
x1
4
30
M8 OT terminal x
36
M10 OT terminal
-
-
x6
4.2.3 Battery deliverables (LX A5.0-30)
Battery
Component
Description
Component
Description
Terminal resistor x 1
When connecting to a
third-party busbar, the
Battery module x 1
battery needs to be
equipped with this
terminal resistor.
M5 OT terminal x 2:
Recommended for
connecting 70mm2
cables
M8 OT terminal x 2:
Recommended for
M5*12 grounding screw x
connecting 70mm2
2
cables
M10 OT terminal x
2: Recommended
for connecting
70mm2 cables
Documents x 1
-
-
Wall mounting rack x 2
M6*70 expansion bolt x 4
For wall-mounted
For wall-mounted
installation
installation
M5*12 grounding
Installation positioning
screw x 2
cardboard x 1
For wall-mounted
For wall-mounted
31
installation
installation
Battery bracket x 2
M4*8 screw x 8
(optional)
For floor-mounted
For floor-mounted
installation
installation
Busbar box (BCB-32-WW-0) (optional)
Component
Description
Component
720A busbar box x 1
Description
M6 expansion bolt x 4
M8 OT terminal x
30
M10 OT terminal x
-
-
6
4.2.4 Smart Meter Deliverables (GMK110)
Component
Description
Component
Description
RS485
Smart meter and
communication
CT x 1
terminal x 1
Voltage input
PIN terminal x 4
side terminal x 1
Screw driver x 1
Documents x 1
4.2.5 Smart Meter (GM3000)
Component
Description
Component
Smart meter
Description
2PIN terminal x 1
and CT x 1
32
PIN
2PIN terminal x 1
terminal x 6
Screw driver
Documents x 1
x1
4.2.6 Smart Dongle (WiFi/LAN Kit-20)
Component
Description
Component
Description
Smart dongle x 1
Documents x 1
4.2.7 Smart Dongle (Ezlink3000)
Component
Description
Component
Description
LAN cable connector x
Smart dongle x 1
1
Unlock tool x 1
Remove the module using
the removing tool if it is
included. If the tool is not
Documents x 1
provided, remove the
module by pressing the
unlock button on the
module.
4.3 Storage
If the equipment is not to be installed or used immediately, please ensure that the storage
environment meets the following requirements: If the equipment has been long term stored, it
should be checked by professionals before being put into use.
Packing requirements:
Do not unpack the outer package or throw the desiccant away.
33
Installation environment requirements:
1. Place the equipment in a cool place where away from direct sunlight.
2. Store the equipment in a clean place. Make sure the temperature and humidity are appropriate
and no condensation. Do not install the equipment if the ports or terminals are condensed.
Battery storage temperature range (T):
LX A5.0-10/LX A5.0-30:
When -20℃≤T﹤0℃ or 35℃﹤T≤45℃, the storage period cannot exceed 1 month.
When 0℃≤T≤35℃, the storage period cannot exceed 1 year.
3. Keep the equipment away from flammable, explosive, and corrosive matters.
Stacking requirements:
1. The height and direction of the stacking inverter should follow the instructions on the packing
box.
2. The inverter must be stacked with caution to prevent them from falling.
Battery Dis-/Charge Requirements:
Storage SOC: 25%-50% SOC. Circle the charge-discharge every 6 months.
34
5 Installation
DANGER
Install and connect the equipment using the deliverables included in the package.
Otherwise, the manufacturer shall not be liable for the damage.
5.1 System Installation and Commissioning Procedure
5.2 Installation Requirements
5.2.1 Installation Environment Requirements
1. Do not install the equipment in a place near flammable, explosive, or corrosive materials.
2. The temperature and humidity at the installation site should be within the appropriate range.
3. Do not install the equipment in a place that is easy to touch, especially within children’s reach.
4. 60℃ high temperature exists when the equipment is working. Do not touch the surface to avoid
burning.
5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a
sunshade if it is needed.
35
6. The place to install the equipment shall be well-ventilated for heat radiation and large
enough for operations.
7. Check the protection rating of the equipment and ensure that the installation environment
meets the requirements. The inverter, battery system, and smart dongle can be installed both
indoors and outdoors. But the smart meter can only be installed indoors.
8. Install the equipment at a height that is convenient for operation and maintenance, electrical
connections, and checking indicators and labels.
9. The altitude to install the equipment shall be lower than the maximum working altitude of the
system.
10. Consult the manufacturer before installing the equipment outdoors in salt affected areas. A salt
affected area refers to the region within 500 meters offshore, and will be related to the sea wind,
precipitation and topography.
11. Install the equipment away from electromagnetic interference. If there is any radio or wireless
communication equipment below 30MHz near the equipment, you have to:
Inverter: add a multi-turn winding ferrite core at the AC output cable of the inverter, or add a
low-pass EMI filter.
Other equipment: the distance between the equipment and the wireless EMI equipment
should be more than 30m.
36
5.2.2 Installation Space Requirements
Reserve enough space for operations and heat dissipation when installing the system.
When using CAT7 communication cables among inverters, the maximum distance can
reach 10 meters, while using CAT5 communication cables, the maximum distance can reach
5 meters.
5.2.3 Tool Requirements
NOTICE
The following tools are recommended when installing the equipment. Use other auxiliary
tools on site if necessary.
Installation Tools
Tool
Description
Tool
Diagonal pliers
Description
RJ45 crimping tool
37
Wire stripper
YQK-70 hydraulic pliers
PV connector tool
Adjustable wrench
PV-CZM-61100
Impact drill (drill bits
Torque wrench
Φ8mm, 10mm)
M4、M5、M6、M8、M10
Rubber hammer
Socket wrench set
Multimeter
Marker
Range≤600V
Heat shrink tube
Heat gun
Cable tie
Vacuum cleaner
Level
-
-
Tool
Description
Personal Protective Equipment
Tool
Description
Insulation gloves and
Dust mask
safety gloves
38
Goggles
Safety shoes
5.3 Equipment Handling
CAUTION
Operations such as transportation, turnover, installing and so on must meet the requirements
of local laws and regulations.
Move the equipment to the site before installation. Follow the instructions below to avoid
personal injury or equipment damage.
1. Consider the weight of the equipment before moving it. Assign enough personnel to
move the equipment to avoid personal injury.
2. Wear safety gloves to avoid personal injury.
3. Keep balance to avoid falling down when moving the equipment.
5.4 Installing the Inverter
CAUTION
Avoid the water pipes and cables buried in the wall when drilling holes.
Wear goggles and a dust mask to prevent the dust from being inhaled or contacting eyes
when drilling holes.
Make sure the inverter is firmly installed in case of falling down.
Step 1: Put the mounting plate on the wall horizontally and mark positions for drilling holes.
Step 2: Drill holes with hammer drill.
Step 3: Use expansion bolts to fix the mounting plate on the wall.
Step 5: Install the inverter on the mounting plate. Tighten the nuts to secure the mounting plate
and the inverter.
39
5.5 Installing the Battery System
WARNING
Ensure that the battery system is installed vertically and securely. When using the locking
bracket, the bracket should be vertically attached to the wall and the surface of the battery
system.
Cover the equipment with a cardboard to prevent foreign matters when drilling holes.
Otherwise, the system may be damaged.
After marking the drilling position with a marker pen, the battery system needs to be moved
away to avoid equipment damage caused by the impact drill when drilling.
Cover the equipment with a cardboard to prevent foreign matters when drilling holes.
Otherwise, the system may be damaged.
LX A5.0-30: Floor-mounted installation
NOTICE
Up to 6 batteries can be stacked for floor-mounted installation.
Step 1: Place the battery vertically, and remove the battery handles.
Step 2: Install brackets on the battery, and secure them with screws.
40
Step 3: Place the battery flat and stack multiple batteries. Ensure that the locating pin is inserted
into the locating hole.
LX A5.0-30: Rack-mounted Installation
NOTICE
It is recommended to install it in a 19-inch standard rack with a length * width of 600*800mm
and above, and the height should be determined based on the thickness of the battery
(133mm) and above.
For rack-mounted installation, electrical labels and warning labels need to be attached to any
position of the front panel of the battery (these labels are shipped as additional accessories).
Step 2: Place the battery on the guide rail of the rack and secure the battery to the rack with screws
from the handle.
41
LX A5.0-30: Wall-mounted Installation
Step 1: Determine the drilling position with installation positioning cardboard and marker pen.
Step 2: Use an impact drill to drill holes.
Step 3: Install the battery brackets.
Step 4: Install the battery on the brackets and use screws to secure the battery.
LX A5.0-10: Floor-mounted Installation
NOTICE
Up to 6 batteries can be stacked for floor-mounted installation.
42
Step 1: Tighten the support column to make it fit against the surface of the bracket.
Step 2: Place the battery vertically.
Step 3: Install the brackets on the battery, and tighten them with screws.
Step 4: Place the battery flatly, and stack batteries.
Insert locating pin on the bracket into locating hole.
Unscrew the support columns of the second layer and above to the left, and screw them
down tightly to fit with the battery box of the next layer.
LX A5.0-10: Rack-mounted Installation
NOTICE
It is recommended to use a 19-inch standard rack with physical length and width of
600*800mm and above. The height can be chosen according to the number of batteries
in parallel.
For rack-mounted installation, electrical labels and warning labels need to be attached to
any position of the front panel of the battery (these labels are shipped as additional
accessories).
Step 1: Stick the electrical label and warning label to the position of the front panel of any battery.
Step 2: Place the battery on the guide rail of the rack and secure the battery to the rack with screws
from the handle.
43
5.6 Installing the Smart Meter
WARNING
In areas at risk of lightning, if the meter cable exceeds 10m and the cables are not wired with
grounded metal conduits, you are recommended to use an external lightning protection device.
GMK110
44
GM330
45
6 System Wirings
DANGER
Perform electrical connections in compliance with local laws and regulations. Including
operations, cables, and component specifications.
Disconnect the DC switches and the AC output switches to power off the equipment
before any electrical connections. Do not work with power on. Otherwise, an electric
shock may occur.
Tie the same type cables together, and place them separately from cables of different
types. Do not place the cables entangled or crossed.
If the cable bears too much tension, the connection may be poor. Reserve a certain
length of the cable before connecting it to the Inverter cable port.
Make sure that the cable conductor is in full contact with the terminal and the cable
insulation
 part is not crimped with the terminal when crimping the terminal.
Otherwise, the device may
 not be able to work properly, or the connection may be
unreliable during working, which
 may cause terminal block damage, etc.
NOTICE
Wear personal protective equipment like safety shoes, safety gloves, and insulating
gloves during electrical connections.
All electrical connections should be performed by qualified professionals.
Cable colors in this document are for reference only. The cable specifications shall meet
local laws and regulations.
For parallel systems, Follow the safety precautions in the user manuals of related
products in the system.
6.1 System Wiring Diagram
NOTICE
N and PE wiring ON-GRID and BACK-UP of the inverter are different based on the
regulation requirements of different regions. Refer to the specific requirements of local
regulations.
There are built-in relays inside of the inverter’s ON-GRID and BACK-UP AC ports. When
the inverter is in the off-grid mode, the built-in ON-GRID relay is open; while when the
inverter is in grid-tied mode, it is closed.
When the inverter is powered on, the BACK-UP AC port is energized. Power off the
46
inverter first if maintenance is required on the BACK-UP loads. Otherwise, it may cause
electric shock.
N and PE cables are separately wired in the Main Panel.
NOTICE
Ensure that the grounding of BACK-UP is correctly and tightened. Otherwise, the BACKUP function may be abnormal in case of grid failure.
The following diagram is applicable to areas except Australia or New Zealand.
6.2 Detailed System Wiring Diagram
6.2.1 Detailed System Wiring Diagram For Single Inverter
GM330 and other meters that meet the requirements can also be used in single inverter
scenarios. Here only the recommended types are shown.
With built-in smart meter
47
With GMK110 smart meter
48
6.2.2 Detailed System Wiring Diagram For Parallel System
In parallel scenarios, the inverter connecting to Ezlink and smart meter is considered as
the master inverter, while all the others are slave inverters. Do not connect any smart
dongle to the slave inverters.
Generator is not supported in parallel system.
The following diagram mainly introduces parallel connections. For other port
connections, refer to the single system.
Use GM3000 in the system
6.3 Preparing Materials
WARNING
Do not connect loads between the inverter and the AC switch directly connected to the
inverter.
Install one AC output circuit breaker for each inverter. Multiple inverters cannot share
one AC circuit breaker.
49
An AC circuit breaker shall be installed on the AC side to make sure that the inverter can
safely disconnect the grid when an exception happens. Select the appropriate AC circuit
breaker in compliance with local laws and regulations.
When the inverter is powered on, the BACK-UP AC port is energized. Power off the
inverter first if maintenance is required on the BACK-UP loads. Otherwise, it may cause
electric shock.
For cables used in the same system, it is recommended that the conductor
material, cross sectional area, length, etc. of the cables should be consistent.
The AC cable for BACK-UP port of each inverter
The AC cable for ON-GRID port of each inverter
The power cable between inverter and battery
The power cable between batteries
The power cable between inverter and busbar
The power cable between battery and busbar
6.3.1 Preparing Breakers
Number
Circuit breaker
Recommended specifications
1
ON-GRID circuit
Rated current ≥ 90A, rated voltage ≥
breaker
230V
Comment
Prepared by
customers.
Optional in compliance with local laws
and regulations
GW8000-ES-C10: Rated current
2
Battery breaker
≥63A, rated voltage ≥230V
Prepared by
GW12K-ES-C10: rated current ≥
customers.
300A, rated voltage ≥ 60V
GW12K-ES-C10: rated current ≥
300A, rated voltage ≥ 60V
GW8000-ES-C10: Rated current
≥63A, rated voltage ≥230V
3
GEN breaker
GW10K-ES-C10, GW12K-ES-C10:
Rated current ≥ 75A, rated voltage ≥
Prepared by
customers.
230V
Off-grid load
4
breaker
Rated current ≥ 90A, rated voltage ≥
230V
Prepared by
customers.
50
Optional in compliance with local laws
and regulations
5
RCD
Type A
ON-GRID RCD: 300mA
Prepared by
customers.
BACK-UP RCD: 30mA
6.3.2 Preparing Cables
Number
Cable
Recommended specifications
Single-core outdoor copper cable
1
Inverter PE cable
Conductor cross-sectional area:
S=6mm²
Single-core outdoor copper cable
2
Battery PE cable
cross sectional area of conductor
LX A5.0-10:4mm²-6mm²
LX A5.0-30:10mm²
Obtain method
Prepared by
customers.
Prepared by
customers.
LX A5.0-30:
Supports purchase
from GoodWe
Commonly used outdoor
photovoltaic cable
3
PV DC cable
Conductor cross-sectional area:
10mm²- 16mm²
Prepared by
customers.
Outer diameter: 6.5mm-8.5mm
Single-core outdoor copper cable
Wiring requirements for inverter
battery ports:
Conductor cross-sectional area:
6mm²
Outer diameter: 6.5mm-8.5mm
4
Battery DC cable
Requirements for cables between
battery and busbar:
LX A5.0-30, cross sectional area
of conductor: 50mm²
LX A5.0-10, cross sectional area
of conductor: 25mm²
Requirements for cables between
battery and battery:
51
Prepared by
customers.
LX A5.0-30:
Supports purchase
from GoodWe
LX A5.0-30, cross sectional area
of conductor: 50mm²
LX A5.0-10, cross sectional area
of conductor: 25mm²
AC input and output cables of
inverter (BACKUP/GRID):
Cross sectional area of
conductor: 10mm² or 6AWG
Outer diameter of multi-core
outdoor copper cable: 23.3mm24.8mm
Outer diameter of single-core
outdoor copper cable: 8.3mm5
AC cable
8.7mm
Generator power cable (GEN):
Prepared by
customers.
Cross sectional area of
conductor: 10mm² or 6AWG
Multi-core outdoor copper
cable outer diameter: 20mm21mm
Outer diameter of single-core
outdoor copper cable: 8.3mm8.7mm
6
7
Smart meter power
cable
battery
communication line
Outdoor copper cable
Conductor cross-sectional area:
6mm²
Prepared by
customers.
Communication between batteries and
Prepared by
inverters as well as between batteries
customers.
requires the use of CAT 5E or above
LX A5.0-30:
standard shielded network cables and
Supports purchase
RJ45 shielded connector.
from GoodWe
52
8
Smart meter RS485
Shielded twisted pair cable
communication
Conductor cross-sectional area:
cable
Communication
9
10
0.2mm²- 0.3mm²
Prepared by
customers.
CAT 5E and above standard shielded
cable for parallel
network cable and RJ45 shielded
connected inverters
connector
Remote shutdown
Copper core twisted pair cable
and NS Protection
Conductor cross-sectional area:
communication line
0.2mm²- 0.3mm²
Prepared by
customers.
Prepared by
customers.
6.4 Connecting the PE cable
WARNING
The PE cable connected to the enclosure of the inverter cannot replace the PE cable
connected to the AC output port. Make sure that both of the two PE cables are securely
connected.
Make sure that all the grounding points on the enclosures are equipotentially connected
when there are multiple inverters.
To improve the corrosion resistance of the terminal, you are recommended to apply silica gel
or paint on the ground terminal after installing the PE cable.
Connect the PE cable first before installing the equipment. Disconnect the PE cable before
dismantling the equipment.
Inverter
Battery
53
6.5 Connecting the PV Cable
DANGER
Do not connect one PV string to more than one inverter at the same time. Otherwise, it may
cause damage to the inverter.
Confirm the following information before connecting the PV string to the inverter. Otherwise,
the inverter may be damaged permanently or even cause fire and cause personal and
property losses.
1. Make sure that the max short circuit current and the max input voltage per MPPT are
within the permissible range.
2. Make sure that the positive pole of the PV string connects to the PV+ of the inverter. And
the negative pole of the PV string connects to the PV- of the inverter.
WARNING
The PV strings cannot be grounded. Ensure the minimum insulation resistance of the PV
string to the ground meets the minimum insulation resistance requirements before
connecting the PV string to the inverter (R=maximum input voltage/ 30mA).
Ensure the DC cables are connected tightly, securely and correctly.
Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the
voltage should be within the permissible range.
NOTICE
The two input strings per MPPT should be of the same type, the same number of modules, the
same tilt and angle to ensure the best efficiency.
54
6.6 Connecting the Battery Cable
DANGER
In a single inverter system, do not connect the same battery pack to multiple inverters, which
may cause inverter damage.
It is forbidden to connect loads between the inverter and batteries.
When connecting battery cables, use insulated tools to prevent accidental electric shock or
short circuit to the batteries.
Ensure that the open circuit voltage of the battery is within the permissible range of the
inverter.
Install a DC breaker between the inverter and the battery in compliance with local local laws
and regulations.
Battery system wiring diagram
55
LXA5.0-30: Hand-to-hand connection
The battery system supports a maximum working current of 160A, working power of 8kW, and
can connect to a maximum of 1 inverter, and 30 batteries
56
LXA5.0-30: Use with busbar BCB-32-WW-0
The battery system supports a maximum working current of 720A, working power of 36kW, and
can connect to a maximum of 6 inverters, and 15 batteries.
57
LXA5.0-30: Use with third-party busbar
The complexity of the parallel system increases with the increase in the number of inverters.
When the number of inverters in parallel system is ≥ 6, please contact the after-sales service to
confirm the installation and application environment of the inverter to ensure stable operation of
the system.
The nominal charging current of a single battery is 60A; The nominal discharging current is 100A;
The maximum continuous charging current is 90A; The maximum continuous discharging current
is 150A, and a maximum of 30 batteries can be paralleled in the same system.
LX A5.0-10: Hand-to-Hand Connection
The nominal charging and discharging current of a single battery is 60A.
The battery system supports a maximum working current of 120A, working power of 8kW, a
maximum of 1 inverter, and 2 batteries.
58
LX A5.0-10: Use with busbar BCB-11-WW-0
The nominal charging and discharging current of a single battery is 60A.
The battery system supports a maximum working current of 360A, working power of 18kW, a
maximum of 3 inverters, and 6 batteries.
59
LX A5.0-10: Use with busbar BCB-22-WW-0
The nominal charging and discharging current of a single battery is 60A.
The battery system can support a maximum working current of 720A, working power of 36kW, a
maximum of 6 inverters, and 12 batteries.
60
LX A5.0-10: Use with third-party busbar
The nominal charging and discharging current of a single battery is 60A.
The complexity of the parallel system increases with the increase in the number of inverters.
When the number of inverters in parallel system is ≥ 6, please contact the after-sales service to
confirm the installation and application environment of the inverter to ensure stable operation of
the system.
The battery system supports a maximum working current of 900A, working power of 45kW, and
15 batteries.
61
LX A5.0-30 communication port definition:
PIN
COM1
COM2
Description
1
-
-
2
-
-
3
Parallel OUT+
Parallel OUT+
4
CAN_1H
CAN_1H
5
CAN_1L
CAN_1L
or battery parallel communication port
6
Parallel OUT2+
Parallel OUT2+
Parallel interlock communication port
7
-
-
8
Parallel OUT-
Parallel OUT-
Reserved
Parallel communication port
Connect the inverter communication port
Reserved
Communication port for parallel system
LX A5.0-10 Communication Port Definition
62
PIN
COM1
COM2
Description
1
-
-
2
-
-
3
Parallel OUT+
Parallel OUT+
4
CAN_1H
CAN_1H
5
CAN_1L
CAN_1L
Reserved
Parallel communication port
Connect the inverter communication port
or battery parallel communication port
6
Reserved
7
8
Parallel OUT-
Parallel OUT-
Communication port for parallel system
6.6.1 Connecting the Power Cable between the Inverter and Battery
WARNING
Measure the DC cable using the multimeter to avoid reverse polarity connection. Also,
the voltage should be within the permissible range.
Connect the battery cables to the corresponding terminals such BAT+, BAT- and
grounding ports correctly. Otherwise it will cause damage to the inverter.
Ensure that the whole cable cores are inserted into the terminal holes. No part of the
cable core can be exposed.
Ensure that the cables are connected securely. Otherwise it will cause damage to the
inverter due to overheat during its operation.
Do not connect one battery pack to more than one inverter at the same time. Otherwise,
it may cause damage to the inverter.
Overview of inverter and battery power cable
63
Make the inverter power cable
64
Battery power cable manufacturing (LX A5.0-10 and LX A5.0-30)
65
6.6.2 Connecting the Communication Cable between the Inverter
and Battery
NOTICE
The BMS cable is included in the package of the inverter, the included BMS communication
cable is recommended. If more communication cables are needed, prepare shielded network
cables and RJ connectors by yourself to make the cable. Only crimp PIN4 and PIN5 of the
connector when making the cable, otherwise the communication may fail.
Instructions for BMS communication connection between inverter and battery
Inverter
Connected to the
port
battery port
Port
definition
Description
The inverter communicates with
BMS(CAN)
COM1
4:CAN_H
5:CAN_L
the battery through CAN.
Connect the BMS1 port of the
inverter to to the COM1 port of
the battery.
66
NOTICE
When connecting the lead-acid battery temperature sensor cable, it is
recommended to connect the temperature sensor cable at a location with poor heat
dissipation. For example, when lead-acid batteries are placed side by side, the
sensor should be fixed on the lead-acid battery located in the middle.
To better protect the battery cell, a temperature sampling cable must be installed,
and it is recommended to place the battery in a well-ventilated environment.
67
6.7 Connecting the AC Cable
WARNING
The residual current monitoring unit (RCMU) is integrated into the inverter to avoid the
residual current exceeds the limit. The inverter will disconnect the utility grid quickly once it
found the residual current exceeds the limit.
When wiring, ensure that the AC cable is completely matched with the "BACKUP", "ON-GRID",
"GEN", and grounding ports of the AC terminal. Incorrect cable connection will lead to
equipment damage.
Ensure that the whole cable cores are inserted into the terminal holes. No part of the cable
core can be exposed.
Ensure that the insulation board is inserted into the AC terminal tightly.
Ensure that the cables are connected securely. Otherwise it will cause damage to the inverter
due to overheat during its operation.
68
6.8 Connecting the Meter Cable
NOTICE
Contact the manufacturer for additional smart meters if multiple inverters are
connected.
Ensure that the CT is connected in the correct direction and phase sequences, otherwise
the monitoring data will be incorrect.
Ensure the cables are connected tightly, securely and correctly. Inappropriate wiring may
cause poor contacts and damage the equipment.
In areas at risk of lightning, if the meter cable exceeds 10m and the cables are not wired
with grounded metal conduits, you are recommended to use an external lightning
protection device.
Wiring of GMK110
NOTICE
69
Outer diameter of the AC cable should be smaller than the hole diameter of the CT, so
that the AC cable can be routed through the CT.
To ensure accurate current detection, the CT cable is recommended to be shorter than
30m.
Do not use network cable as the CT cable, otherwise the smart meter may be damaged
due to high current.
The CTs vary slightly in dimensions and appearance depending on the model, but they
are installed and connected in the same way.
Connection steps
Wiring of GM3000
Connection steps
70
Installing the CT (Type I)
Installing the CT (Type II)
6.9 Connecting the Inverter Communication Cable
NOTICE
The communication functions are optional. Connect the cables based on actual needs.
If you need to use the remote shutdown function, please turn it on in the SolarGo App
71
after wiring is completed.
Do not turn on the function in the SolarGo App if the inverter is not connected to a
remote shutdown device, otherwise the inverter will be unable to operate on-grid.
In a parallel system, please connect the communication cable to the master inverter to
achieve the remote shutdown function, otherwise, the function will not work.
Communication Descriptions
Number
Function
Description
1
CT
Connecting the CT communication cable.
2
PAR1/PAR2
3
BMS(CAN)
Lead-acid battery
4
temperature
measurement port.
5
5
The communication port for parallel operation of
inverters.
For communication between the inverter and the
battery.
For connecting lead-acid battery temperature
measurement cable.
Remote shutdown/NS
Provides signal control port to control equipment
Protection
remote shutdown or realize NS protection function.
GEN port
Used to control the generator. It can only be used in
a single inverter scenario.
Connecting the communication cable
72
6.10 Connect the smart dongle
NOTICE
The inverter supports connecting to mobile phones or WEB interfaces via Bluetooth,
WiFi, LAN, and 4G smart dongle (China version) to set device-related parameters, view
equipment operation information and error messages, and promptly understand the
system status.
In single inverter system, install the WiFi/LAN Kit-20 smart dongle. When using multiple
inverters to form a parallel system, the master inverter needs to be equipped with an
Ezlink module for networking.
73
7 System Commissioning
7.1 Check before Power ON
Number
Check Item
The inverter is firmly installed in a clean place where is well-ventilated and
1
2
easy to operate.
The PE, DC input, AC output, communication cables, and terminal
resistors are connected correctly and securely.
3
Cable ties are intact, routed properly and evenly.
4
Unused wire holes and ports should be sealed up.
5
The used cable holes are sealed.
The voltage and frequency at the connection point meet the inverter grid
6
connection requirements.
7.2 Power ON
WARNING
When there are multiple inverters in the system, please ensure that all slave inverter AC
sides are powered on within one minute after the master inverter AC side is powered on.
Battery black start scenarios:
The inverter needs to be activated by battery.
If there is no inverter, it is necessary to manage the charging and discharging of
battery, etc.
After the battery system is started, please ensure that the communication
between the inverter and the battery system is normal within 15 minutes. If the
inverter cannot communicate normally with the battery system, the battery
system switch will be automatically disconnected, and the battery system will be
powered off.
When there are multiple batteries in the system, starting any one of them can start all
74
the batteries.
7.2.1 Power on a single inverter system
75
7.2.2 Power on a parallel system
7.3 Indicators
7.3.1 Inverter Indicators
Indicator
Status
Description
The inverter is power on and in the standby mode.
The inverter is starting up and in the self-check
mode.
The inverter is in normal operation under grid-tied
or off-grid mode.
BACK-UP output overload.
System fault.
The inverter is powered off.
The grid is abnormal, and the power supply to the
76
BACK-UP port of the inverter is normal.
The grid is normal, and the power supply to the
BACK-UP port of the inverter is normal.
The BACK-UP port has no power supply.
The monitoring module of the inverter is resetting.
The inverter fails to connect with the
communication Termination.
Communication fault between the communication
Termination and Server.
The monitoring of the inverter operates well.
The monitoring module of the inverter has not
been started yet.
Indicator
Description
75%<SOC≤100%
50%<SOC≤75%
25%<SOC≤50%
0%<SOC≤25%
No battery connected.
Indicator light blinking during battery discharging: for example, when the battery SOC is
between 25% and 50%, the light at the 50% position blinks.
7.3.2 Battery Indicators
LX A5.0-30
77
Indicator
System Status
No green displayed on
SOC=0%
the SOC indicator
The first SOC indicator
0%<SOC≤25%
shows green
The first two SOC indicators
are green
The first three SOC
50%<SOC≤75%
indicators are green
The four SOC indicators are
green
75%<SOC≤100%
The battery system is working
Green light steady on
RUN light
25%<SOC≤50%
properly.
The battery system is in standby
Green flashes 1 time/s
mode.
Green light blinks 1 time/s
The PCS communication is lost
After the battery system gives an
alarm, it will conduct a self-check and
Red light blink 1 time/s
wait until the self-check is over, then it
will change to normal working status
or fault status.
Check both the button indicator and
ALM Light
the SOC indicator status to determine
the fault that has 
 occurred and
Red light steady on
handle the problem follow the
methods recommended in the
Troubleshooting section.
LX A5.0-10
Normal status
SOC indicator
RUN light
Battery system status
78
The SOC indicator represents the battery
Green flashes 1
The battery system is in
time/s
standby mode.
Green light
The battery system is in
blinks 1 time/s
an idle state.
Green light
The battery system is in
steady on
the charging state.
When 25% ≤ SOC < 50%, SOC2 flashes
Green light
The battery system is in
When 50% ≤ SOC < 75%, SOC3 flashes
steady on
discharging status.
system's useable energy.
The last SOC indicator blinks 1 time/s.
When 5%≤SOC<25%, SOC 1 blinks.
When 75% ≤ SOC < 95%, SOC4 flashes.
When 95% ≤ SOC ≤ 100%, SOC5 flashes
abnormal state
ALM Light
Battery system
Description
status
Once an alarm occurs, the battery system
Red light blink 1
time/s
will perform a self-check. After the battery
Battery system alarm
system &#xD; self-check is complete, the
battery system enters operation or fault
mode.
Check both the button indicator and the
Red light steady on
The battery system
has malfunctioned.
SOC indicator status to determine the fault
that has &#xD; occurred and handle the
problem follow the methods recommended
in the Troubleshooting section.
7.3.3 Smart Meter Indicator
GMK110
Type
Power indicator light
Description
Status
Steady on
The smart meter is power on.
Off
The smart meter has been powered off.
79
Communication
indicator
Blinks
Meter communication is normal
Meter communication is abnormal or has no
Off
communication
GM330
Type
Description
Status
Steady on
Power indicator light
Blinks
Communication
Power on, no RS485 communication.
Power on, RS485 communication works
properly.
Off
The smart meter has been powered off.
Off
Reserved
Press the Reset button for more than 5
indicator
Blinks
seconds, power light, buying or selling
electricity indicator light flash: Reset the
meter.
Importing or
exporting indicator
Steady on
Importing from the grid.
Blinks
Exporting to the grid.
Off
Exporting to the grid.
Reserved
7.3.4 Smart Dongle Indicator
WiFi/LAN Kit-20
Indicator
Power light
Description
Status
Constantly on: The smart dongle has been
powered on.
Power Off: The smart dongle is not powered
on.
Communicatio
n indicator
Steady on: Communication in WiFi mode or
LAN mode is normal.
Blinks 2 times: The smart dongle is not
connected to the router.
80
Blinks 4 times: The smart dongle is
communicating normally with the router, but
has not connected to the server.
Off: The software of the smart dongle is
reseting or is not powered on.
Indicator
Color
Description
Status
The connection of the wired network
Steady on
at 100Mbps is normal.
The Ethernet cable is not
connected.
Green
The connection of the wired
Off
Communication
network at 100Mbps is abnormal.
indicator in LAN
The connection of the wired
Port
network at 100Mbps is normal.
The connection of the wired network
at 10Mbps is normal, but no
Steady on
communication data is received or
transmitted.
Yellow
The communication data is being
Blinks
transmitted or received.
Off
The Ethernet cable is not connected.
Description
Button
Press and hold for 0.5 to 3 seconds to reset the Smart Dongle.
Reload
Press and hold for 6 to 20 seconds to restore the Smart Dongle to
factory settings.
Ezlink3000
Indicator/
silkscreen
Color
Status
Description
Blink = The Ezlink is working properly.
Power light
Blue
OFF = The Ezlink is powered off.
81
ON = The Ezlink is connected to the server.
Communica
Blink 2 = The Ezlink is not connected to the
tion
indicator
router.
Green
Blink 4 = The Ezlink is connected to the router,
but not connected to the server.
Short press for 3s to restart the Ezlink.
RELOAD
-
-
Long press for 3-10s to restore factory
settings.
82
8 Quick System Commissioning
8.1 Downloading the App
Make sure that the mobile phone meets the following requirements:
Mobile phone operating system: Android 4.3 or later, iOS 9.0 or later.
The mobile phone can access the Internet.
The mobile phone supports WLAN or Bluetooth.
Method 1: Search SolarGo in Google Play (Android) or App Store (iOS) to download and
install the app.
Method 2: Scan the QR code below to download and install the app.
8.2 Connecting the Inverter
NOTICE
The device name varies depending on the inverter model or smart dongle type:
Wi-Fi Kit:Solar-WiFi***
Bluetooth Module: Solar-BLE***
WiFi/LAN Kit-20:WLA-***
Ezlink3000:CCM-BLE***;CCM-***;***
83
Connect to the inverter via Bluetooth
Connecting the inverter via WiFi
84
8.3 Communication Settings
NOTICE
The communication configuration interface may vary depending on the type of
smart dongle connected to the inverter. Please refer to the actual interface for
accurate information.
Step 1: Enter the setting page through "Home" > "Settings" > "Communication
Configuration" > "Network Settings".
Step 2: Configure the WLAN or LAN network based on the actual situation.
Number
Name/Icon
Description
Applicable to WLAN. Please select the corresponding
1
Network Name
network based on your actual situation and communicate
the device with the router or switch.
2
Password
Applicable to WLAN. Enter the password for the network you
actually selected.
When the router is using the dynamic IP mode, turn on
3
DHCP
the DHCP function.
When using the router in static IP mode or using a switch,
turn off the DHCP function.
85
4
IP address
5
Subnet mask
6
Gateway address
7
DNS Server
When DHCP is enabled, there is no need to configure this
parameter.
When DHCP is turned off, please configure this parameter
according to the information of the router or switch.
8.4 Quick Settings
NOTICE
When selecting the safety regulation country/region, the system will
automatically configure the overvoltage and undervoltage protection,
overfrequency and underfrequency protection, inverter on-grid
voltage/frequency, connection slope, Cosφ curve, Q(U) curve, P(U) curve, FP
curve, high and low voltage ride-through, etc. according to the safety regulation
requirements of different regions.
The generation efficiency of inverter differs in different working modes. Please
set according to the local actual electricity consumption.
86
Description
Parameter Name
Safety regulations
Select the corresponding safety code based on the country or region
where the equipment is located.
Select the actual mode for connecting the battery to the inverter. If there is
BAT Access Mode
no battery connected in the system, it is unnecessary to configure the
battery model and working mode, and the equipment will operate in the
self-use mode by default.
Select Battery Model
Working Mode
Select the battery type and model based on actual situation.
Set the working mode of the device during operation. Supports: Self-use
mode and back-up mode.
When the self-use mode is selected, the interface will be displayed as follows. You need to enter
the advanced mode to choose the specific working mode and set the corresponding parameter
values.
87
Description
Parameter Name
Self-use mode: based on the self-use mode, Back-up mode, Economic mode, and Smart charging
can be enabled at the same time, and the inverter will automatically select the working mode.
Operation priority: BACK-UP mode > Economic mode > Smart Charging mode > Self-use mode.
Depth of discharge(ongrid)
Depth of discharge(offgrid)
The maximum depth of discharge of the battery when the system is
working on-grid.
The maximum depth of discharge of the battery when the system is
working off-grid.
BACK-UP Mode
Charging From Grid
Rated power
Enabling this function allows the system to purchase electricity from
power grid.
The percentage of power purchased compared to the rated power of
the inverter.
Economic mode
Start time
Within the start and end time, the battery will charge or discharge
End time
based on the set charge-discharge mode and rated power.
Charge and discharge
Set to charge or discharge based on actual needs.
88
mode
Rated power
Charge/Discharge Cut-off
SOC
The percentage of power during charging or discharging compared to
the rated power of the inverter.
The battery stop charging/discharging once the battery SOC reaches
Charge Cut-off SOC.
After setting the parameters, click Complete to restart.
8.5 Creating Power Plants
NOTICE
Login to the SEMS Portal app using the account and password before creating
power plants. If you have any questions, refer to the Plant Monitoring section.
Step 1: Enter the interface for creating a power plant.
Step 2: Carefully read the prompts on the interface and fill in the power plant information
based on actual conditions. (* refers to the mandatory items)
Step 3: Add devices according to the interface prompts to complete the creation of the
power plant.
89
9 System Commissioning
9.1 SolarGo Overview
SolarGo App is a mobile application that communicates with the inverter through
bluetooth or WiFi modules. Commonly used functions are as follows:
1. Check the operating data, software version, alarms, etc.
2. Set grid parameters, communication parameters, safety countries, power limitation,
etc.
3. Equipment maintenance.
4. Upgrade the firmware version of the equipment.
90
9.1.1 App Interface Structure
91
9.1.2 Introduction to the SolarGo App Login Interface
Num
Name/Ico
ber
n
Description
1
Tap the icon to open the page downloading the SEMS Portal app.
2
Tap to read the connection guide.
Not found
Check information such as app version, local contacts, etc.
Other settings, such as update date, switch language, set
3
temperature unit, etc.
Bluetooth/
4
5
WiFi
Device List
Select based on actual communication method. If you have any
problems, tap or NOT Found to read the connection guides.
The list of all devices. The last digits of the device name are
normally the serial number of the device.
92
Select the device by checking the serial number of the master
inverter when multi inverters are parallel connected.
The device name varies depending on the inverter model or
communication module.
Search
6
Device
Tap Search Device if the device is not found.
9.1.3 Introduction to the Main Interface of SolarGo App
Single inverter and multiple inverters
Numb
er
Name/Icon
Description
Serial number of the connected inverter or serial number of the
1
Serial Number
2
Device Status
Indicates the status of the inverter, such as Working, Fault, etc.
Energy Flow
Indicates the energy flow chart of the PV system. The actual
3
4
Chart
System Status
master inverter in the parallel system.
page prevails.
Indicates the system status, such as Safety Code, Working
Mode, Battery Model, Battery Status, Power Limit, Three-Phase
93
Unbalanced Output, etc.
Home. Tap Home to check Serial Number, Device Status, Energy
5
Home
Flow Chart, System Status, etc.
Parameters. Tap Parameters to check the running parameters of
6
the system.
Settings. Log in before entering Quick Settings and Advanced
7
Settings. Initial password: goodwe2010 or 1111.
Tap Total Number to check serial number of all inverters. Tap
8
Parallel
the serial number to enter the setting page of the single
inverter.
9.2 Connecting the Inverter
NOTICE
The device name varies depending on the inverter model or communication module:
Wi-Fi Kit:Solar-WiFi***
Bluetooth Module: Solar-BLE***
WiFi/LAN Kit-20:WLA-***
Ezlink3000:CCM-BLE***;CCM-***;***
Connect to the inverter via Bluetooth
94
Connecting the inverter via WiFi
95
9.3 Quick Settings
NOTICE
When selecting the safety regulation country/region, the system will automatically
configure the overvoltage and undervoltage protection, overfrequency and
underfrequency protection, inverter on-grid voltage/frequency, connection slope,
Cosφ curve, Q(U) curve, P(U) curve, FP curve, high and low voltage ride-through, etc.
according to the safety regulation requirements of different regions.
The generation efficiency of inverter differs in different working modes. Please set
according to the local actual electricity consumption.
96
Description
Parameter Name
Safety regulations
Select the corresponding safety code based on the country or region
where the equipment is located.
Select the actual mode for connecting the battery to the inverter. If
BAT Access Mode
there is no battery connected in the system, it is unnecessary to
configure the battery model and working mode, and the equipment
will operate in the self-use mode by default.
Select the actual battery model.
Select Battery Model
Battery Type only supports: AGM/GEL/Wet Battery (Flooded).
Please set the correct type in the APP according to the selected
battery.
Working Mode
Set the working mode of the device during operation. Supports: selfuse mode and back-up mode.
When the self-use mode is selected, the interface will be displayed as follows. You need to enter
the advanced mode to choose the specific working mode and set the corresponding parameter
values.
Description
Parameter Name
97
Self-use mode: based on the self-use mode, Back-up mode, Economic mode, and Smart
charging can be enabled at the same time, and the inverter will automatically select the working
mode. Operation priority: BACK-UP mode > Economic mode > Smart Charging mode > Self-use
mode.
Depth of discharge(ongrid)
Depth of discharge(offgrid)
The maximum depth of discharge of the battery when the system is
working on-grid.
The maximum depth of discharge of the battery when the system is
working off-grid.
BACK-UP Mode
Charging From Grid
Rated power
Enabling this function allows the system to purchase electricity from power
grid.
The percentage of power purchased compared to the rated power of the
inverter.
Economic mode
Start time
Within the start and end time, the battery will charge or discharge based
End time
on the set charge-discharge mode and rated power.
Charge and discharge
mode
Rated power
Charge/Discharge Cutoff SOC
Set to charge or discharge based on actual needs.
The percentage of power during charging or discharging compared to the
rated power of the inverter.
The battery stop charging/discharging once the battery SOC reaches
Charge Cut-off SOC.
9.4 Communication Settings
NOTICE
The communication configuration interface may vary depending on the type of
smart dongle connected to the inverter. Please refer to the actual interface for
accurate information.
98
Step 1: Enter the setting page through "Home" > "Settings" > "Communication
Configuration" > "Network Settings".
Step 2: Configure the WLAN or LAN network based on the actual situation.
Number
Name/Icon
Description
Applicable to WLAN. Please select the corresponding network
Network Name
1
based on your actual situation and communicate the device
with the router or switch.
Password
2
Applicable to WLAN. Enter the password for the network you
actually selected.
When the router is using the dynamic IP mode, turn on the
DHCP
3
DHCP function.
When using the router in static IP mode or using a switch,
turn off the DHCP function.
4
IP address
5
Subnet mask
6
Gateway address
7
DNS Server
When DHCP is enabled, there is no need to configure this
parameter.
When DHCP is turned off, please configure this parameter
according to the information of the router or switch.
9.5 Setting the Basic Information
9.5.1 Setting the Basic Information
Step 1: Tap Home> Settings > Basic Settings, to set the parameters.
Step 2: Set the functions based on actual needs.
Shadow Scan and SPD
Number
Parameter Name
Description
Enable Shadow Scan when the PV panels are
1
Shadow Scan
severely shadowed to optimize the power
generation efficiency.
99
After enabling SPD, when the SPD module is
2
SPD
abnormal, there will be SPD module abnormal
alarm prompt.
Setting the Backup Function
After enabling Backup, the battery will power the load connected to the backup port of the
inverter to ensure Uninterrupted Power Supply when the power grid fails.
Number
1
Parameter Name
Description
UPS Mode - Full Wave
Check whether the utility grid voltage is too high
Detection
or too low.
UPS Mode - Half Wave
2
Detection
EPS Mode - Supports
3
LVRT
Check whether the utility grid voltage is too low.
Stop detecting utility grid voltage.
Once the power of loads connected to the
inverter BACK-UP ports exceeds the rated load
power, the inverter will restart and detect the
power again. The inverter will perform restart and
4
Clear Overload History
detection several times until the overloading
problem is solved. Tap Clear Overload History to
reset the restart time interval after the power of
the loads connected to the BACK-UP ports meets
the requirements. The inverter will restart
immediately
9.5.2 Setting Advanced Parameters
Step 1: Tap Home > Settings > Advanced Settings to set the parameters.
Step 2: Set the parameters based on actual needs. Tap‘√’or Save to save the settings.
The parameters are set successfully.
100
Number
Parameter Name
Description
AFCI Test
Enable or disable AFCI accordingly.
The test status, like Not Self-checking, self-
AFCI Test Status
1
AFCI Test
check succeeded, etc.
Clear AFCI Alarm
Clear ARC Faulty alarm records.
Tap to check whether the AFCI function
Self-check
works normally.
Stand-alone Connect
The PV strings are connected to the MPPT
terminals one by one.
The PV strings are connected to the inverter
2
PV Access
Mode
in both stand&#x2;alone and parallel
Partial Parallel
connection. For example, one PV string
Connect
connect to MPPT1 ad MPPT2, another PV
string connect to MPPT3.
The external PV string is connected to multi
Parallel Connect
MPPT terminals of the inverter.
9.5.3 Setting Power Limit Parameters
Step 1 Tap Home > Settings> Advanced Settings > Power Limit to set the parameters.
Step 2: Enable or disable the power limit function based on actual needs.
Step 3: Enter the parameters and tap √. The parameters are set successfully.
Number
Parameter Name
1
Power Limit
2
Export Power
3
External CT Ratio
Description
Enable Power Limit when power limiting is required
by local grid standards and requirements.
Set the value based on the actual maximum power
feed into the utility grid.
Set the ratio of the primary current to the
101
secondary current of the external CT.
9.5.4 Setting the Battery Parameters
Lithium ion battery
Step 1: Enter the parameter setting interface through Home > Settings > Advanced
Settings > Battery Function Settings.
Step 2: Enter the parameters and tap √. The parameters are set successfully.
Number
Parameter Name
1
Max. Charging Current
2
3
Description
Set the maximum charging current based on actual
needs.
Max. Discharging
Set the maximum discharging current based on actual
Current
needs.
SOC Protection
Start battery protection when the battery capacity is
lower than the Depth of Discharge.
Depth of
4
5
discharge(on-grid)
Indicates the depth of discharge of the battery when
Depth of
the inverter is on-grid or off-grid.
discharge(off-grid)
The battery will be charged to preset SOC protection
6
Backup SOC Holding
value by utility grid or PV when the system is running
on-grid. So that the battery SOC is sufficient to
maintain normal working when the system is off-grid.
Enable to charge the battery by the grid immediately.
7
Immediate Charging
Take effect once. Enable or Disable based on actual
needs.
8
SOC For Stopping
Stop charging the battery once the battery SOC
Charging
reaches SOC For Stopping Charging.
Immediate Charging
9
Power
Indicates the percentage of the charging power to the
inverter rated power when enabling Immediate
102
Charging.
For example, setting the Immediate Charging Power of
a 10kW inverter to 60 means the charging power of
the inverter is 10kW*60%=6kW.
Lead Acid Battery
NOTICE
1. Before setting the parameters of lead-acid batteries, it is necessary to read the
user manual, technical parameters and other related materials of lead-acid
batteries. To ensure the safety of batteries, please strictly follow the relevant
materials of lead-acid battery manufacturers to set the battery parameters.
Otherwise, the risks caused thereby shall not be within the scope of the
responsibility of the inverter manufacturer.
2. The voltage range of lead-acid batteries needs to match the inverter, and the
recommended voltage of lead-acid batteries connected to the inverter is ≤60V,
otherwise the inverter may not operate properly.
3. The SOC of lead-acid batteries is calculated by the inverter BMS, not the actual
battery capacity, which may result in SOC value deviation or jump. SOC is only
used as a reference for battery capacity. Performing SOC value calibration after
the battery is fully charged can improve the accuracy of the SOC value.
Step 1: Enter the parameter settings interface through Home > Settings > Advanced
Settings > Battery Function.
Step 2: Enter the parameters and tap √. The parameters are set successfully.
Number
1
Parameter Name
Battery Capacity
Description
Please set it according to the battery technical
parameters.
When the battery is approaching full charge, it
will switch to float charging mode. This value is
2
Floating Voltage
the upper limit of charging voltage in this mode.
Please set it according to the battery
technical parameters.
3
Constant Charging
The battery charging mode is set to constant
103
Voltage
voltage charging by default; this value is the
upper limit of charging voltage in this mode.
Please set it according to the battery
technical parameters.
Please set it according to the battery technical
4
Minimum discharge
parameters. To protect the battery performance
voltage
and life, this parameter should not be set too
low.
5
6
Max. Charging
Current
Max. Discharging
Current
The maximum current during charging, used to
limit the charging current. Please set it
according to the battery technical parameters.
Please set it according to the battery technical
parameters. The greater the discharge current is,
the shorter the working time of the battery is.
The maximum charging current in the floating
charge state. Please set it according to the
7
Maximum floating
charge current
battery technical parameters.
When the battery is nearly fully charged, it will
enter the floating charge state. Please refer to
the technical parameters of the corresponding
battery model for specific definitions.
8
Battery Internal
The internal resistance of the battery. Please set
Resistance
it according to the battery technical parameters.
When the battery charging status changes from
9
Time to switch to
float charging mode
constant charging to float charging, and the
duration reaches the set value, the battery
charging mode will switch to float charging
mode. The default duration is 180s.
By default, when the temperature is higher than
10
Charge temperature
compensation
25℃, the upper limit of charging voltage will
decrease by 3mV for every 1℃ increase. The
actual settings should be based on the technical
parameter of the battery.
104
9.5.5 Setting Generator Parameters
Step 1: After connecting to the SolarGo APP, go to Home > Settings > Port Connection >
Generator Connection. After selecting the generator type, enter the parameter setting
interface.
Step 2: Enter the parameters and tap √. The parameters are set successfully.
Manual control generator (Does not support dry contact connection): This type of
generator only supports manual start and stop.
Automatic control generator (Supporting dry contact connection): This type of generator
supports automatic start and stop.
Number
Parameter Name
Description
Set the switch control mode and automatic control mode.
In the switch control mode, the start and stop of the
Dry contact control
1
mode
generator can be remotely controlled. In automatic
control mode, the generator automatically starts and
stops based on preset parameters. This feature only
applies to generators that support dry contact
connection.
Set a prohibited working time. During this period, the
2
No working time
generator will stop working. This feature only applies to
generators that support dry contact connection.
3
Rated power
Rated power of the generator.
The duration of continuous operation of a generator.
When the working time exceeds the set value, the
4
Running time
generator will automatically shut down. This feature only
applies to generators that support dry contact
connection.
5
Upper Voltage
Set the upper limit of operating frequency for the
generator.
105
The time mode will be on between the Start Time and
6
Lower Voltage
End Time. Set the upper limit of operating frequency for
the generator.
Upper frequency
Set the upper limit of operating frequency for the
limit
generator.
8
Lower Frequency
Set the lower limit of the generator's operating frequency.
9
Preheating time
10
Switch
7
The no-load preheating time before the generator is
loaded.
Turn on or off the function of the generator to charge the
battery.
Maximum charging
11
Set the maximum charge power for the generator battery.
power
Set the start voltage for generator to charge battery.
12
starting voltage
When the voltage of the battery is lower than the set
value, the generator will charge the battery.
Set the stop voltage for generator to charge battery.
13
stop voltage
When the voltage of the battery is higher than the set
value, the generator will stop charging the battery.
9.5.6 Setting Load Control
Step 1: After connecting to the SolarGo APP, enter the parameter setting interface through
Home > Settings > Port Connection > Load Control.
Step 2: Enter the parameters and tap √. The parameters are set successfully.
Number
Parameter Name
Description
The loads will be powered within the setting time period.
1
Dry Contact Mode
when the switch is ON, the loads will be powered; when the
switch is OFF, the power will be cut off. Turn the switch on
or off based on actual needs.
2
Time Mode
set the time to enable the load, and the load will be
106
powered automatically within the setting time period.
the inverter has an integrated relay controlling port, which
can control the loads off or on. In off-grid mode, the load
3
SOC mode
connected to the port will not be powered if the BACKUP
overload is detected or the battery SOC value is lower than
the Off-grid battery protection value.
9.6 Setting Safety Parameters
9.6.1 Setting the Basic Safety Parameters
NOTICE
The grid standards of some countries/regions require that inverters shall set
functions to meet local requirements.
Step 1: Tap Home > Settings > Advanced Settings, to set the parameters.
Number
Parameter Name
Description
Enable DRED/Remote Shutdown/RCR before
1
DRED/Remote
connecting the third party DRED, remote
Shutdown/RCR
shutdown, or RCR device to comply with local
laws and regulations.
Three-phase
2
Unbalanced Output
Enable Three-phase Unbalanced Output when
the utility grid company adopts phase separate
billing.
To comply with local laws and regulations, ensure
3
Backup N and PE Relay
that the relay inside the back-up port remains
Switch
closed and the N and PE wires are connected
when the inverter is working off-grid.
Enable AUTO TEST to set auto test for grid tying
4
AutoTest
in compliance with local grid standards and
requirements.
107
9.6.2 Setting Customized Safety Parameters
NOTICE
Set the custom safety parameters in compliance with local requirements. Do not
change the parameters without the prior consent of the grid company.
9.6.2.1 Setting the Active Power Mode
Setting the P(F) Curve
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameters > Active Power
Mode Settings to set the parameters.
Step 2: Set the parameters based on actual needs.
Setting the P(U) Curve
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameters > Active Power
Mode Settings to set the parameters.
Step 2: Enter the parameters. The inverter will adjust the active output power to the
apparent power ratio in real-time according to the actual grid voltage to the rated voltage
ratio.
108
9.6.2.2 Setting the Reactive Power Mode
Setting the Fix PF
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Set the parameter based on actual needs. The power factor remains fixed during
the inverter working process.
Number
Parameter Name
1
Fix PF
2
Under-excited
Description
Enable Fix PF when it is required by local grid
standards and requirements.
Set the power factor as lagging or leading based on
actual needs and local grid standards and
3
Over excitation
4
Power Factor
requirements.
Set the power factor based on actual needs. Range: 0~-0.8, or +0.8~+1.
Setting the Fix Q
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Set the parameter based on actual needs. The output reactive power remains fixed
during the inverter working process.
109
Number
Parameter Name
1
Fix Q
2
Under-excited
Description
Enable Fix Q when it is required by local grid standards
and requirements.
Set the reactive power as inductive or capacitive
reactive power based on actual needs and local grid
3
Over excitation
4
Power Factor
standards and requirements.
The percentage of reactive output power to apparent
power.
Setting the Q(U) Curve
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Enter the parameters. The inverter will adjust the reactive power to the apparent
power ratio in real-time according to the actual grid voltage to the rated voltage ratio.
Setting the Cosφ Curve
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameter Settings >
Reactive Power Mode to set the parameters.
Step 2: Enter the parameters. The inverter will adjust the active output power to the
apparent power ratio in real-time according to the actual grid voltage to the rated voltage
ratio.
110
Setting Protection Parameters
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameters > Protection
Parameters to set the parameters.
Step 2: Set the parameters based on actual needs.
Number
Parameter Name
Description
Voltage Protection Parameters
1
OV Stage n Trip Value
2
OV Stage n Trip Time
3
UV Stage n Trip Value
4
UV Stage n Trip Time
5
Grid 10min Overvoltage
Set the grid overvoltage protection threshold value,
n = 1, 2, 3.
Set the grid overvoltage protection tripping time, n
= 1, 2, 3.
Set the grid undervoltage protection threshold value,
n= 1, 2, 3.
Set the grid undervoltage protection tripping time, n
= 1, 2, 3.
Set the 10min overvoltage protection threshold
value.
Frequency Protection Parameters
111
6
OF Stage n Trip Value
7
OF Stage n Trip Time
8
UF Stage n Trip Value
9
UF Stage n Trip Time
Set the grid overfrequency protection threshold
value, n = 1, 2.
Set the grid overfrequency protection tripping time,
n = 1, 2.
Set the grid underfrequency protection threshold
value, n = 1, 2.
Set the grid underfrequency protection tripping
time, n = 1, 2.
Setting Connection Parameters
Step 1: Tap Home > Settings > Advanced Settings > Safety Parameters > Protection
Parameters to set the parameters.
Step 2: Set the parameters based on actual needs.
Setting Voltage Ride through Parameters
Step 1: Enter the parameter setting page through Home > Settings > Advanced
Settings > Safety Parameter Settings > Voltage Fault Ride-Through.
Step 2: Set the parameters based on actual needs.
112
Number
Parameter Name
Description
LVRT
1
2
Ride Through Voltage
The inverter will not be disconnected from the
Start Point
utility grid immediately when the grid voltage is
Ride Through Voltage
between Ride Through Voltage Start Point and Ride
End Point
Through Voltage End Point.
Ride Through Time Start
3
Point
Ride Through Time End
4
5
Point
Indicates the longest duration the inverter can
remain connected to the grid when the grid voltage
is at the Ride Through Voltage Start Point.
Indicates the longest duration the inverter can
remain connected to the grid when the grid voltage
is at the Ride Through Voltage End Point.
Ride Through Trip
LVRT is allowed when the grid voltage is lower than
Threshold
Ride Through Trip Threshold
Ride Through Voltage
The inverter will not be disconnected from the
Start Point
utility grid immediately when the grid voltage is
Ride Through Voltage
between Ride Through Voltage Start Point and Ride
End Point
Through Voltage End Point.
HVRT
6
7
Ride Through Time Start
8
Point
Ride Through Time End
9
10
Point
Indicates the longest duration the inverter can
remain connected to the grid when the grid voltage
is at the Ride Through Voltage Start Point.
Indicates the longest duration the inverter can
remain connected to the grid when the grid voltage
is at the Ride Through Voltage End Point.
Ride Through Trip
HVRT is allowed when the grid voltage is higher
Threshold
than Ride Through Trip Threshold
113
10 Monitoring Power Plant
10.1 SEMS Portal Overview
SEMS Portal App is a monitoring platform. Commonly used functions are as follows:
1. Manage the organization or User information;
2. Add and monitor the power plant information;
3. Equipment maintenance.
Login Page of SEMS Portal App
Number
Name
Description
1
Login Area
Enter the user name, password to login to the app.
2
Forget Password
Tap to reset the password by verifying the account.
Tap to register an end-user account. Contact the
3
Register
manufacturer or the company as prompted if you need
a company account.
114
4
APPs
Tap to download SolarGo app.
Configure WiFi parameters to establish communication
5
Configuration
between the inverter and the server and realize remote
monitoring and managing.
Power plant for
6
demonstration
Click to enter the power plant for demonstration
interface, where the content displayed is based on the
account permissions of the viewer. The page is for
reference only.
Introduction to the Home Page Interface of SEMS Portal App
Number
Name
Create power plant.
1
2
Description
Power plant
Display the current operating status of the power plant.
115
operation status
3
Search for
Search for power stations by selecting their name, equipment
power plant
SN number, email, or on the map.
Power
4
generation
statistics
Click to switch between today, this month, total generated
power and cumulative earnings.
Home of power plant monitoring.
5
Plants
Alarms Check all alarms, happening alarms, and recovered
6
Alarms
alarms.
When using Wi Fi Kit on the device, this button can be used
7
WiFi
8
to set up WiFi related settings.
Message Set and check system messages.
Message
Discovery To Edit the account, create My QR Code, set
9
Discovery
Income Settings, etc.
10.2 Manage power plant or equipment
10.2.1 Power plant creation
Step 1: Enter the interface for creating a power plant.
Step 2: Carefully read the prompts on the interface and fill in the power plant information
based on actual conditions. (* refers to the mandatory items)
116
Step 3: Add devices according to the interface prompts to complete the creation of the
power plant.
10.2.2 Power plant management
Step 1: Enter the power plant monitoring page and delete or modify the power plant
information based on actual needs.
117
10.2.3 Managing the equipment in the power plant
Step 1: Click on the power plant in the power plant monitoring interface to enter the
power plant details page.
Step 2: Click the serial number of the device to enter the device details page, and add,
delete, or replace the device based on actual needs.
118
10.3 Power plant monitoring
10.3.1 Viewing power plant information
After logging into SEMS Portal App with the account and password, you will enter the home page of
the power plant, where the overall operation status of all power plants under the account will be
displayed. Click Monitoring to enter the power plant monitoring interface to view all power plant
information.
The displayed content of different interfaces of power plant equipment varies, please refer to the
actual situation.
Step 1: (Optional) if there are multiple power plants, you can search for information such as the
power plant name, inverter SN number, or the owner's phone number to quickly locate the power
plant.
Or click the map sign to search for power plant information and quickly locate the power plant.
Step 2: Click on the power plant name in the power plant list or the power plant icon on the map to
view the detailed information of the power plant.
Step 3: On the power plant details interface, check the power plant information, power generation
details, equipment information, faults, and other conditions according to the prompts on the
interface.
119
10.3.2 Viewing Alarm Information
Step 1: Click the Fault tab on the power plant details page to enter the alarm query page.
Step 2: Click on the alarm name to view detailed alarm information.
120
121
11 Maintenance
11.1 Power OFF the System
DANGER
Power off the equipment before operations and maintenance. Otherwise, the equipment
may be damaged or electric shocks may occur.
Delayed discharge. Wait until the components are discharged after power off.
Push the air switch to restart the battery.
Strictly follow the power off requirements to avoid damaging the system
When there are multiple batteries in the system, powering off any one of the batteries
can power off all the batteries.
NOTICE
Install the circuit breaker between the inverter and the battery or between the two
batteries in compliance with local laws and regulations.
To ensure effective protection, the cover of the battery system switch should remain
closed. The cover can be closed automatically after being opened. Fasten the cover with
screws if the switch is not to be used for a long-term period.
Single inverter system power off
122
Parallel system power off
123
11.2 Removing the Equipment
DANGER
Make sure that the equipment is powered off.
Wear proper personal protective equipment during operations.
Please use standard disassembly tools when removing wiring terminals to avoid
damaging the terminals or equipment.
Unless otherwise specified, the dismantling process of the equipment is in reverse order
to the installation process, and it will not be further elaborated in this document.
Step 1: Power off the system.
Step 2: Label the cables connected in the system with tags indicating the cable type.
Step 3: Disconnect the connecting cables of the inverter, battery, and smart meter in the
system, such as DC cables, AC cables, communication cables, and PE cables.
Step 4: Remove equipment such as the smart dongle, inverter, battery, and smart meter.
Step 5: Properly store the equipment and ensure that the storage conditions meet the
requirements if it needs to be put into use later.
11.3 Disposing of the Equipment
If the equipment cannot work anymore, dispose of it according to the local disposal
requirements for electrical equipment waste. The equipment cannot be disposed of
together with household waste.
11.4 Routine Maintenance
WARNING
Contact after-sales service for help if you find any problems that may influence the
battery or the hybrid inverter. Disassemble without permission is strictly forbidden.
Contact after-sales service for help if the copper conductor is exposed. Do not touch or
disassemble privately because high voltage danger exists.
In case of other emergencies, contact the after-sales service as soon as possible. Operate
following the instructions or wait for the after-sales service personnel.
124
Maintaining Item
Maintaining method
Maintaining
Maintaining
Period
purpose
Check the heat sink, air intake,
and air outlet for foreign matter
or dust.
System clean
Check whether the installation
space meets requirements and
Once half a
year
Prevent heat
dissipation
failures.
whether there is any debris
around the device.
Check whether the equipment are
System
installation
installed securely and whether the
screws are installed tightly.
Check whether the equipment is
Ensure that
Once 6-12
months
Check whether the cables are
connection
equipment is
installed
securely.
damaged or deformed.
Electrical
the
securely connected. Check
whether the cables are broken or
whether there is any exposed
Confirm the
Once 6-12
reliability of
months
electrical
connections.
copper core.
Confirm that
Check whether all the terminals
Sealing
and ports are properly sealed.
Reseal the cable hole if it is not
the machine
Once a year
sealed or too big.
seal and
waterproof
performance
are intact.
If the battery is not used for a
Battery
long time or is not fully charged,
maintenance
it is recommended to charge the
battery regularly.
Protect the
Once/15 days
battery's
lifespan.
11.5 Troubleshooting
Perform troubleshooting according to the following methods. Contact the after-sales
125
service if these methods do not work.
Collect the information below before contacting the after-sales service, so that the
problems can be solved quickly.
1. Product information like serial number, software version, installation date, fault time,
fault &#xD; frequency, etc.
2. Installation environment, including weather conditions, whether the PV modules are
sheltered or shadowed, etc. It is recommended to provide some photos and videos to
assist in analyzing the problem.
3. Utility grid situation.
11.5.1 System Troubleshooting
Num
ber
Cause
Solutions/measures to address the issue
1. Please ensure that no other devices are connected
to the smart dongle's wireless signal.
2. Please ensure that the SolarGo app has been
updated to the latest version.
1
Unable to search for
3. Please ensure that the smart dongle is powered
the wireless signal of
on properly, and the blue indicator light is
the smart dongle.
blinking or steadly on.
4. Ensure that the smart device is within the
communication range of the smart dongle.
5. Refresh the device list in the app.
6. Restart the inverter
1. Please ensure that no other devices are connected
Unable to connect to
2
the wireless signal of
the smart dongle.
to the smart dongle's wireless signal.
2. Restart the inverter or smart dongle, and try to
reconnect to the wireless signal of the smart
dongle again.
3. Ensure successful pairing of Bluetooth.
1. Make sure that the router is powered on.
2. When communicating via LAN, make sure that
3
The Ezlink indicator
flashes twice.
both LAN cable connection and LAN
configuration are proper. Enable or disable DHCP
based on actual needs.
126
3. When communicating via WiFi, make sure that the
wireless network connection is OK and the
wireless signal strength meets the requirements.
Enable or disable DHCP based on actual needs.
1. Make sure that the smart dongle is connected to
the router via WiFi or LAN properly, and the router
4
The Ezlink indicator
flashes four times.
5
can access the Internet.
2. If the problem persists, contact the after sales
service.
Make sure that the inverter is powered on. If the
The Ezlink indicator is
problem persists, contact the after sales service.
off.
6
The Ezlink indicator is
Make sure that the inverter is powered on.
off.
1. Put the router nearer to the Smart Dongle. Or add
7
Cannot find router
SSID
a WiFi relay device to enhance the WiFi signal.
2. Reduce the number of devices connected to
router.
1. Restart the inverter
After completing all
8
2. Check if the SSID, encryption method and
configurations, the
password on WiFi configuration page are the
Smart Dongle fails
same with that of Router.
connecting to the
3. Restart the router.
router.
4. Put the router nearer to the Smart Dongle. Or add
a WiFi relay device to enhance the WiFi signal.
After completing all
configurations, the
9
Smart Dongle fails
Restart the router and the inverter.
connecting to the
router.
11.5.2 Inverter Troubleshooting
Number
Fault
Solutions/measures to address
Cause
the issue
127
1. Utility grid power
fails.
1
Utility Loss
2. The AC cable is
disconnected, or
the AC breaker is
off.
1. The alarm is automatically cleared
after the grid power supply is
restored.
2. Check whether the AC cable is
connected and the AC breaker is on.
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will
recover automatically after
detecting that the utility grid is
normal.
2. If it occurs frequently, please check
if the grid voltage is within the
allowable range.
The grid voltage
2
Contact the local power
exceeds the
company if the grid voltage
Grid
permissible range, or
exceeds the permissible range.
Overvoltage
the duration of high
voltage exceeds the
requirement of HVRT.
Modify the overvoltage
protection threshold, HVRT or
disable the overvoltage
protection function after
obtaining the consent of the
local power company if the grid
frequency is within the
permissible range.
3. Check whether the AC breaker and
the output cables are connected
securely and correctly if the
problem persists.
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will
3
Grid Rapid
Overvoltage
The grid voltage is
recover automatically after
abnormal or
detecting that the utility grid is
ultra&#x2;high.
normal.
2. Check if the grid voltage is running
at a high voltage for a long time. If
it occurs frequently, please check if
128
the grid voltage is within the
allowable range.
Contact the local power
company if the grid voltage
exceeds the permissible range.
Modify the grid overvoltage
rapid protection threshold after
obtaining the consent of the
local power company if the grid
voltage is within the permissible
range.
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will
recover automatically after
detecting that the utility grid is
normal.
2. If it occurs frequently, please check
if the grid voltage is within the
allowable range.
The grid voltage is
4
Contact the local power
lower than the
company if the grid voltage
Grid
permissible range, or
exceeds the permissible range.
Undervoltage
the duration of low
voltage exceeds the
requirement of LVRT.
Modify the undervoltage
protection threshold, LVRT or
disable the undervoltage
protection function after
obtaining the consent of the
local power company if the grid
frequency is within the
permissible range.
3. Check whether the AC breaker and
the output cables are connected
securely and correctly if the
problem persists.
The moving average
5
Grid 10min
Overvoltage
1. If the problem occurs occasionally,
of grid voltage in
the utility grid may be abnormal
10min exceeds the
temporarily. The inverter will
range of safety
recover automatically after
requirements.
detecting that the utility grid is
129
normal.
2. Check if the grid voltage is running
at a high voltage for a long time. If
it occurs frequently, please check if
the grid voltage is within the
allowable range.
Contact the local power
company if the grid voltage
exceeds the permissible range.
Modify the grid overvoltage
rapid protection threshold after
obtaining the consent of the
local power company if the grid
voltage is within the permissible
range.
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will
recover automatically after
detecting that the utility grid is
normal.
2. If the problem occurs frequently,
6
Grid
Overfrequency
Utility grid exception.
check whether the grid frequency is
The actual grid
within the permissible range.
frequency exceeds the
Contact the local power
requirement of the
company if the grid frequency
local grid standard.
exceeds the permissible range.
Modify the overfrequency
protection threshold or disable
the overfrequency protection
function after obtaining the
consent of the local power
company if the grid frequency is
within the permissible range.
Utility grid exception.
Grid
7
Underfrequenc
y
1. If the problem occurs occasionally,
The actual grid
the utility grid may be abnormal
frequency is lower
temporarily. The inverter will
than the requirement
recover automatically after
of the local grid
detecting that the utility grid is
standard.
normal.
130
2. If the problem occurs frequently,
check whether the grid frequency is
within the permissible range.
Contact the local power
company if the grid frequency
exceeds the permissible range.
Modify the underfrequency
protection threshold or disable
the underfrequency protection
function after obtaining the
consent of the local power
company if the grid frequency is
within the permissible range. Or
close Grid Underfrequency
function.Grid Underfrequency
1. If the problem occurs occasionally,
the utility grid may be abnormal
temporarily. The inverter will
recover automatically after
detecting that the utility grid is
Utility grid exception.
2. If the problem occurs frequently,
The actual grid
8
normal.
Grid Frequency
frequency change rate
check whether the grid frequency is
Instability
does not meet the
within the permissible range.
requirement of the
Contact the local power
local grid standard.
company if the grid frequency
exceeds the permissible range.
Contact the dealer or the aftersales service if the grid
frequency is within the
permissible range.
The utility grid is
disconnected. The
utility grid is
1. Check whether the utility grid is
disconnected
9
Anti-islanding
according to the
safety regulations, but
the grid voltage is
maintained due to the
loads.
131
disconnected.
2. Contact the dealer or the after-sales
service.
10
LVRT
Undervoltage
Utility grid exception.
1. If the problem occurs occasionally,
The duration of the
the utility grid may be abnormal
utility grid exception
temporarily. The inverter will
exceeds the set time
recover automatically after
of LVRT.
detecting that the utility grid is
normal.
Utility grid exception.
11
HVRT
Overvoltage
2. If the problem occurs frequently,
The duration of utility
check whether the grid frequency is
grid exception
within the permissible range. If not,
exceeds the set time
contact the local power company. If
of HVRT.
yes, contact the dealer or the aftersales service.
Abnormal
1. If the problem occurs occasionally,
GFCI 30mA
Abnormal
GFCI 60mA
12
Abnormal
GFCI
150mA
it may be caused by a cable
The input insulation
impedance becomes
low when the inverter
is working.
exception. The inverter will recover
automatically after the problem is
solved.
2. Check whether the impedance
between the PV string and PE is too
low if the problem occurs frequently
Abnormal
or persists.
GFCI
1. If the problem is caused by an
external fault like a utility grid
Large DC of
AC current
13
L1
Large DC of
AC current
L2
The DC component of
the output current
exceeds the safety
range or default
exception or frequency exception,
the inverter will recover
automatically after solving the
problem.
2. If the problem occurs frequently
range.
and the PV station cannot work
properly, contact the dealer or the
after-sales service.
The PV string is shortcircuited to PE.
The PV system is in a
14
Isolation Fail
moist environment
and the cable is not
well insulated to the
ground.
1. Check whether the resistance of the
PV string to PE exceeds 50kΩ. If no,
check the short circuit point.
2. Check whether the PE cable is
connected correctly.
3. If it is confirmed that the insulation
resistance is indeed lower than the
default value in rainy weather,
132
please reset the "Insulation
Resistance Protection Point".
Inverters for the Australian and New
Zealand markets can also be alerted in
the following ways in the event of
insulation impedance failure:
1. The inverter is equipped with the
buzzer: the buzzer sounds
continuously for 1 minute in case of
failure; If the fault is not resolved,
the buzzer sounds every 30
minutes.
2. Add the inverter to the monitoring
platform, and set the alarm
reminder, the alarm information can
be sent to the customer by emails.
1. The PE cable of the
inverter is not
15
connected.
1. Please confirm if the PE cable of the
2. When the output
inverter is properly connected.
Abnormal
of the photovoltaic
system
string is grounded,
string is grounded, please confirm
grounding
the AC output
whether the AC output cables L and
cables L and N of
N of the inverter are reversely
the inverter are
connected.
2. If the output of the photovoltaic
connected
reversely.
1. If the exception is caused by an
external fault, the inverter will
recover automatically after solving
16
Anti Reverse
Abnormal fluctuation
power Failure
of load
the problem.
2. If the problem occurs frequently
and the PV station cannot work
properly, contact the dealer or the
after-sales service.
1. Frame format error
17
Internal Comm
Loss
2. Parity checking
error
3. Can bus offline
133
Disconnect the AC output switch and
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
4. Hardware CRC
error
5. Send (receive)
control bit is
receive (send).
6. Transmit to the
unit that is not
allowed.
Disconnect the AC output switch and
18
AC HCT Check
The sampling of the
abnormal
AC HCT is abnormal.
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
Disconnect the AC output switch and
GFCI HCT
19
Check
abnormal
The sampling of the
GFCI HCT is abnormal.
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
1. Relay Dev Fail
2. The control circuit
is abnormal.
20
Relay Chk Fail
3. The AC cable is
connected
improperly, like a
virtual connection
Disconnect the AC output switch and
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
or short circuit.
Disconnect the AC output switch and
21
Flash Fault
The internal Flash
storage is abnormal
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
22
AFCI Fault
1. The connection of
Please check if the component
DC string terminals
connection cables are correctly
is not firm.
connected according to the wiring
2. The DC cable
requirements in the quick installation
wiring is damaged.
23
manual.
AFCI Self-test
AFCI detection
Disconnect the AC output switch and
Fault
equipment is
DC input switch, then connect them 5
134
abnormal.
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
1. Check whether the ventilation of
1. The installation
location of the
inverter is not
ventilated.
Cavity
24
the inverter installation location is
good and whether the ambient
temperature exceeds the maximum
allowable ambient temperature
range.
2. The ambient
Overtemperatu
temperature is too
re
high, exceeding
60℃.
2. If the ventilation is poor or the
ambient temperature is too high,
please improve the ventilation and
heat dissipation conditions.
3. Internal fan
3. Contact the dealer or after-sales
working
service if both the ventilation and
abnormally
the ambient temperature are
normal.
1. The PV voltage is
too high.
25
BUS
Overvoltage
2. The sampling of
the inverter BUS
voltage is
The PV array
configuration is not
PV Input
correct. Too many PV
Overvoltage
panels are connected
in series in the PV
string.
1. The PV
27
minutes later. Contact the dealer or the
after-sales service if the problem
Check the serial connection of the PV
array. Make sure that the open circuit
voltage of the PV string is not higher
than the maximum operating voltage
of the inverter.
Disconnect the AC output switch and
PV Continuous
configuration is
DC input switch, then connect them 5
Hardware
not proper.
minutes later. Contact the dealer or the
Overcurrent
2. The hardware is
PV Continuous
Software
Overcurrent
after-sales service if the problem
persists.
damaged.
28
DC input switch, then connect them 5
persists.
abnormal.
26
Disconnect the AC output switch and
Disconnect the AC output switch and
1. The PV
configuration is
not proper.
2. The hardware is
135
DC input switch, then connect them 5
minutes later. Contact the dealer or the
after-sales service if the problem
persists.
damaged.
String1 PV
String
29
Reversed
The PV strings are
Check whether the PV1 and PV2 strings
String1 PV
connected reversely.
are connected reversely.
String
Reversed
In case of no generator connection,
1. Generator is not
connected.
2. The generator is
Generator
30
waveform
detection fault
faulty.
3. The parameter
settings of the
generator exceed
the requirements
of the
specification.
ignore this fault. If a generator is
connected, immediately stop the
generator operation. Check if the
generator has any fault and whether
the parameter settings meet the
requirements. If there is no fault with
the generator and the parameter
settings do not exceed the
requirements, and the fault still exists
after restarting the generator, please
contact your dealer or after-sales
service center.
In case of no generator connection,
1. Generator is not
connected.
2. The generator is
Abnormal
31
connection of
generator
faulty.
3. The parameter
settings of the
generator exceed
the requirements
of the
specification.
ignore this fault. If a generator is
connected, immediately stop the
generator operation. Check if the
generator has any fault and whether
the parameter settings meet the
requirements. If there is no fault with
the generator and the parameter
settings do not exceed the
requirements, and the fault still exists
after restarting the generator, please
contact your dealer or after-sales
service center.
1. Generator is not
Generator
32
voltage is
abnormal
In case the generator is not connected,
connected.
ignore this fault. If a generator is
2. The generator is
connected, immediately stop the
faulty.
generator operation. Check if the
3. The voltage setting
generator has any fault and if the
of the generator
voltage setting meets the
exceeds the
requirements. If the generator is in
136
requirements of
good condition and the voltage setting
the specification.
does not exceed the requirements, but
the fault still exists after restarting the
generator, please contact your dealer
or after-sales service center.
In case the generator is not connected,
1. Generator is not
connected.
2. The generator is
Abnormal
33
generator
frequency
faulty.
3. The generator
frequency setting
exceeds the
requirements of
the specification.
ignore this fault. If a generator is
connected, immediately stop the
generator operation. Check if the
generator has any fault and if the
frequency setting meets the
requirements. If the generator is in
good condition, the frequency setting
is within the requirements, but the
malfunction still persists after restarting
the generator, please contact your
dealer or after-sales service center.
1. The load
1. When a generator is connected to
connected to the
the port, immediately stop the
generator is too
operation of the generator, check
large, and the
whether the line is properly
current or power
connected, and confirm whether the
of the GEN port
parameters such as output voltage,
exceeds the
current, and power on the back-up
requirements
side exceed the parameter
specified in the
requirements of the specification. If
specification.
the cable is not properly connected,
2. The short circuit on
34
check and reconnect it. If the
GEN port
the back-up side
parameters exceed the
overload
leads to the
requirements of the specifications,
current of the
reset the parameters according to
generator port
the requirements. If the circuit is
exceeding the
intact and the parameter settings
requirements
are within the specified range, but
specified in the
the problem persists, please contact
specifications.
your dealer or after-sales service
3. When used as a
high-load port, the
center.
2. When the port is connected to a
high load exceeds
heavy load, turn off the heavy load,
the requirements
check if the line is properly
specified in the
connected, and confirm if the load
137
specifications.
exceeds the requirements of the
specification. If the cable is not
properly connected, check and
reconnect it. If the load exceeds the
requirements in the specification,
reduce the load. If the cables are
well connected and the load does
not exceed the specifications, and
the fault still exists, please contact
your dealer or after-sales service
center.
1. Check whether the WiFi signal is
normal. If it is not, check whether
the router works well.
2. Check whether Ezlink obtains IP
successfully via APP. Execute the
Communicatio
following actions if IP is not
n indicator of
35
the inverter
Ezlink connection
and Ezlink
failed
obtained:
3. Reset the communication
parameters via APP.
indicator in
4. Check whether the server
error
connection is correct.
5. Log in to the website mqtt.goodwepower.com via a computer to view
the resolved IP address and obtain
the server connection information.
1. Incorrect communication cable
connection or unreliable cable
connection cause communication
failure.
2. Connect the smart meter and Ezlink
Unable to log
in to the
36
parallel system
interface in
module to the same master inverter
Parallel networking
to ensure the success rate of
failed
networking.
3. Check whether the inverter
APP
communication indicator is normal.
If it is not, please check the
individual inverter according to its
own troubleshooting method.
4. If the above methods cannot solve
138
the problem, please try to restart
the inverter and get networking
again.
1. Check whether the parallel
communication cable is connected
37
Parallel IO
check fail
Communication of
parallel inverters in
error
correctly and firmly.
2. If the communication cable
connection is normal, it may be an
internal communication failure.
Please contact the dealer or After
Sale Service.
38
Parallel Grid
AC L and N cables are
line reversed
connected reversely.
1. Check the grid wiring. Reconnect
the ON-GRID AC cable to make sure
the grid is wired correctly.
1. Check the BMS communication
cable connection, and make sure it
is reliable.
Battery
39
indicator
Check whether the battery type is
Battery failure
matched via APP. If you can't solve
abnormal
it, please refer to the user manual of
the corresponding battery for
troubleshooting.
1. Check whether the quantity of
parallel machines in the system is
the same with the actual connected
ones.
2. If it is, get the SN of the
Device offline
40
displayed on
APP
corresponding offline inverter from
Communication failure
the equipment list, and
or equipment failure
troubleshoot the corresponding
inverter according to its user
manual.
3. Check whether the communication
connection of the equipment is
normal, with no loose, aging or
wrong connection, etc.
139
11.5.3 Battery fault (LX A5.0-30)
Alarm state
When the battery ALM indicator turns red, troubleshoot the issue by referring to the
SOC indicator's display status.
Number
1
SOC indicator
Fault Name
Solutions
Power off and wait for 2 hours. If
Battery
abnormality
the problem persists, please
contact the after-sales service.
Turn off the device to wait for the
2
Abnormal
temperature
temperature to return to normal. If
the problem persists after
restarting, please contact the
after-sales service center.
3
4
5
6
7
Abnormal
current
Restart the battery. If the problem
persists, please contact the aftersales service.
Balancing
fault
Power off and wait for 2 hours. If
the problem persists, please
contact the after-sales service.
Wire harness
exception
Relay opencircuit fault
Restart the battery. If the problem
persists, please contact the aftersales service.
Restart the battery. If the problem
persists, please contact the aftersales service.
Relay
Restart the battery. If the problem
adhesion
persists, please contact the after-
fault
sales service.
Please check if the battery model
8
Cluster Fault
matches. If not, please contact the
after-sales service center.
140
Communicati
9
on failure
Open contact
10
sticking fault
Precharge
11
Failure
12
Restart the battery. If the problem
persists, please contact the aftersales service.
Contact the after-sales service.
Restart the battery. If the problem
persists, please contact the aftersales service.
Component
Power off and wait for 2 hours. If
temperature
the problem persists, please
fault
contact the after-sales service.
Restart the battery. If the problem
Software fault
13
persists, please contact the aftersales service.
14
Hardware
Restart the battery. If the problem
overcurrent
persists, please contact the after-
fault
sales service.
Microelectron
15
ic Fault
persists, please contact the aftersales service.
Inconsistency
of software
16
Restart the battery. If the problem
and hardware
versions
Please check if the battery model,
SN number, and software version
number match. If they do not
match, contact the after-sale
service.
11.5.4 Battery fault (LX A5.0-10)
When the battery ALM indicator turns red, troubleshoot the issue by referring to the
SOC indicator's display status.
Number
1
SOC indicator
Fault Name
Solutions
Battery
Power off and wait for 2 hours. If the
141
Overvoltage
problem persists, please contact the
after-sales service.
2
3
Battery
Undervoltage
Contact the after-sales service.
Power off and wait for 2 hours. If the
High Cell
Temperature
problem persists, please contact the
after-sales service.
Turn off the device to wait for the
4
Low Charging
Temperature
temperature to return to normal. If
the problem persists after restarting,
please contact the after-sales service
center.
Turn off the device to wait for the
5
Low
temperature to return to normal. If
Discharging
the problem persists after restarting,
Temperature
please contact the after-sales service
center.
6
7
Overcurrent
Charging
Restart the battery. If the problem
persists, please contact the after-sales
service.
Overcurrent
Discharging
Restart the battery. If the problem
persists, please contact the after-sales
service.
Low
8
Insulation
Contact the after-sales service.
Resistance
9
Excessive
Power off and wait for 2 hours. If the
temperature
problem persists, please contact the
difference
after-sales service.
Leave the battery alone for 12h after
Voltage
10
Difference
Exception
11
Inconsistency
142
restarting. If the problem persists,
please contact the after-sales service
center.
Contact the after-sales service.
of battery
cells
12
13
14
Wire harness
exception
MOS OpenCircuit Fault
MOS OpenCircuit Fault
Restart the battery. If the problem
persists, please contact the after-sales
service.
Restart the battery. If the problem
persists, please contact the after-sales
service.
Restart the battery. If the problem
persists, please contact the after-sales
service.
Please check if the battery model
15
Cluster Fault
matches. If not, please contact the
after-sales service center.
Check whether the termination
16
Interlock
resistor is installed properly and
failure
restart the battery. Contact the aftersale service if the problem persists.
17
18
19
20
21
22
BMU
Restart the battery. If the problem
communicati
persists, please contact the after-sales
on fault
service.
MCU
Restart the battery. If the problem
Communicati
persists, please contact the after-sales
on Fault
service.
Open contact
sticking fault
Precharge
Failure
Contact the after-sales service.
Restart the battery. If the problem
persists, please contact the after-sales
service.
MOS over-
Power off and wait for 2 hours. If the
temperature
problem persists, please contact the
fault
after-sales service.
Current
Power off and wait for 2 hours. If the
Diverter
problem persists, please contact the
143
Overtemperat
after-sales service.
ure
Reverse
23
Connection
Contact the after-sales service.
Fault
24
Microelectron
ic Fault
144
Contact the after-sales service.
12 Parameters
12.1 Inverter Parameters
Technical Parameters
GW8000-ES-C10
GW10K-ES-C10
GW12K-ES-C10
Battery Input Data
Type
Li-Ion/Lead-acid
Li-Ion/Leadacid
Li-Ion/Lead-acid
Rated Voltage (V)
48
48
48
Voltage Range (V)
40~60
40~60
40~60
160
200
240
160(176 at
200(220 at
10min)
10min)
8,000
10,000
12,000
8,800
11,000
13,200
16,000
20,000
24,000
600
600
600
60~550
60~550
60~550
180~500
170~500
200~500
Start-up Voltage (V)
58
58
58
Nominal Input Voltage (V)
360
360
360
32/16
32/32
32/32
Max. Continuous
Charging Current (A)
Max. Continuous
Discharging Current (A)*1
Maximum Charge power
(W)
Maximum Discharge
Power (W)
240(264 at 10min)
PV Input Data
Maximum Input power
(W) *2
Max. Input Voltage (V)
MPPT Operating Voltage
Range (V)
MPPT Voltage Range at
Nominal Power (V)
Max. Input Current per
MPPT (A) *4
145
Max. Short Circuit Current
per MPPT (A)
Max. Backfeed Current to
The Array (A)
Number of MPPT
Number of Strings per
MPPT
48/24
48/48
48/48
0
0
0
2
2
3
2/2
2/2
2/2
8,000
10,000
12,000
8,800
11,000
13,200
8,000
10,000
12,000
16,500
16,500
16,500
220/230/240
220/230/240
220/230/240
170~280
170~280
170~280
50/60
50/60
50/60
40.0
50.0
60.0
75.0
75.0
75.0
36.4/34.8/33.3
45.5/43.5/41.7
54.5/52.2/50.0
AC Output Data (On-grid)
Nominal Apparent
Power Output to Utility
Grid (VA)
Max. Apparent Power
Output to Utility Grid (VA)
Nominal Apparent Power
from Utility Grid (VA)
Max. Apparent Power
from Utility Grid (VA)
Nominal Output Voltage
(V)
Output Voltage Range (V)
Nominal AC Grid
Frequency (Hz)
Maximum on-grid output
current (A)
Maximum input current
(A)
Nominal Output Current
(A)
Power Factor
Total Harmonic Current
~1 (Adjustable from
0.8 lead...0.8 lag)
<3%
~1 (Adjustable
from 0.8
lead...0.8 lag) }
<3%
146
~1 (Adjustable from
0.8 lead...0.8 lag)
<3%
Distortion
Voltage Type (a.c. or d.c.)
a.c
a.c
a.c
8,000
10,000
12,000
AC Output Data (Back-up)
Back-up Nominal
Apparent Power (VA)
Max. Output Apparent
Power (VA) *4
Nominal Output Current
(A)
Maximum output current
(A)
Nominal Output Voltage
(V)
Nominal Output
Frequency (Hz)
Total Harmonic Voltage
Distortion(@ linear load)
8,800 (16,000 @10s)
11,000 (20,000
@10s)
13,200 (24,000 @10s)
36.4/34.8/33.3
45.5/43.5/41.7
54.5/52.2/50.0
40.0
50.0
60.0
220/230/240
220/230/240
220/230/240
50/60
50/60
50/60
<3%
<3%
<3%
8,000
10,000
12,000
11,000
12,000
12,000
220/230/240
220/230/240
220/230/240
170~280
170~280
170~280
50/60
50/60
50/60
45~55 / 55~65
45~55 / 55~65
45~55 / 55~65
50
54.5
54.5
36.4/34.8/33.3
45.5/43.5/41.7
54.5/52.2/50.0
Generator Port Parameters
Nominal Input Apparent
Power (VA)
Max. Input Apparent
Power (VA)
Nominal Input Voltage (V)
Input voltage range (V)
Input Voltage Frequency
(Hz)
Voltage Frequency Range
(Hz)
Max. Input Current (A)
Nominal Input Current (A)
Efficiency
147
Max. Efficiency
97.6%
European Efficiency
96.2%
CEC Efficiency
96.2%
Max. Battery to AC
95.5%
Efficiency
MPPT Efficiency
99.9%
Protection
PV String Current
Monitoring
Insulation Resistance
Detection
Residual Current
Monitoring
PV Reverse Polarity
Protection
Battery Reverse Polarity
Protection*2
Anti-islanding Protection
AC Overcurrent
Protection
AC Short Circuit
Protection
AC Overvoltage
Protection
DC switch
DC Surge Protection*3
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Integrated
Type III (optional for
Type II)
Type III
(optional for
Type II)
Type III (optional for
Type II)
AC Surge Protection
Type III
Type III
Type III
AFCI
Optional
Optional
Optional
Remote Shutdown
Integrated
Integrated
Integrated
148
General Data
Operating Temperature
Range (℃)
Relative Humidity
Maximum Operating
Altitude (m)
-35~+60
-35~+60
-35~+60
0~95%
0~95%
0~95%
3000
3000
3000
Cooling Method
Smart Fan Cooling
User Interface
LED, WLAN+APP
BMS Communication
Smart Fan
Cooling
LED,
WLAN+APP
Smart Fan Cooling
LED, WLAN+APP
CAN
CAN
CAN
RS485
RS485
RS485
Monitoring
LAN+WiFi
LAN+WiFi
LAN+WiFi
Weight (Kg)
27
29
29
560*445*226
560*445*226
560*445*226
<50
<55
<55
Non-isolated
Non-isolated
Non-isolated
<10
<10
<10
IP65
IP65
IP65
MC4,VACONN
MC4,VACONN
MC4,VACONN
Terminal
Terminal
Terminal
Communication with
Meter
Dimension (W x H x D
mm)
Noise Emission (dB)
Topology
Self-consumption at
Night (W)
Ingress Protection Rating
DC connector
AC Connector
Environmental Category
Pollution Degree
Overvoltage Category
Ingress Protection Rating
VACONN Terminal
VACONN
Terminal
VACONN Terminal
4K4H
4K4H
4K4H
III
III
III
DC II / AC III
DC II / AC III
DC II / AC III
I
I
I
149
Storage Temperature (℃)
-40~+85
-40~+85
-40~+85
Battery: A
Battery: A
Battery: A
The Decisive Voltage
PV:C
PV:C
PV:C
Class (DVC)
AC: C
AC: C
AC: C
COM:A
COM:A
COM:A
Wall Mounted
Wall Mounted
Wall Mounted
Mounting Method
Certification
Safety Regulation
EMC
IEC62109-1&2
EN61000-6-1,EN61000-6-2,EN61000-6-3,EN61000-6-4,
12.2 Battery Technical Data
LX A5.0-10
Technical Parameters
usable energy (kWh) * 1
LX A5.0-10
2*LX A5.0-10
n*LX A5.0-10
5
10
n×5
Battery Module
Number of Modules
LX A5.0-10:51.2V 5.0kWh
1
2
Cell Type
LFP(LiFePO4)
Nominal Voltage (V)
51.2
Operating Voltage Range (V)
Nominal Charge/Discharge Current
(A) *2
Nominal Charge/Discharge Power
(kW) *2
Operating Temperature Range (℃)
n
47.5~57.6
60
120
n×60*3
3
6
n×3*3
Charge: 0 ~ +50; Discharge: -10 ~ +50
Relative Humidity
0~95%
Max. Operating Altitude (m)
3000
Communication
CAN
Weight (Kg)
Dimensions (W x H x D mm)
40
80
n×40
Single LX A5.0-10 module: 442×133×420 (without
handle); 483×133×452 (with handle)
150
Ingress Protection Rating
Storage Temperature (℃)
IP21
0 ~ +35 (≤ 1 year); -20 ~ 0 (≤ 1 month); -40 ~ 45 (≤
1 month)
Mounting Method
Rack mounted/Ground mounted
Round-trip Efficiency
95%
Safety
Standard and
Certification
EMC
IEC62619,IEC 63056,IEC62040-1,INmetro
EN IEC61000-6-1,EN IEC61000-6-2,EN IEC610006-3,EN IEC61000-6-4
Transportation
UN38.3,ADR
*1: Test conditions, 100% DOD, 0.2℃ charge & discharge at +25±2 °C for battery system at
beginning life. System Usable Energy may vary with different Inverter.
*2: The nominal charge and discharge current and power are affected by temperature and
SOC status.
*3: Under the condition of using busbar box to achieve parallel connection of batteries.
*4: New battery, within the range of 2.5~3.65V, at the temperature range of 25+2℃, under
the condition of 0.2C/0.2C charge and discharge. The efficiency is 94%~95% under the
charging and discharging condition of 0.6C/0.6C.
n:n≤15。
LX A5.0-30
Technical Parameters
LX A5.0-30
Nominal Capacity (kWh)
5.12
usable energy (kWh) * 1
5
Cell Type
LFP (LiFePO4)
Operating Voltage Range (V)
43.2~58.24
Nominal Charge Current (A) *3
60
Max. Continuous Charge Current (A) *2*3
90
Nominal Discharge Current (A) *3
100
Max. Continuous Discharge Current (A)
150
*2*3
Max. Pulse Discharge Current (A)
200A(30s)
Max. Continuous Discharge Power (W)
7200
151
Communication
CAN
Ambient Temperature
0<T≤40℃ (Recommended 10<T≤30℃)
Operating Temperature Range (℃)
Charge: 0<T≤55℃; Discharge: -20<T≤55℃
Max. Storage Time
12 Months (maintenance-free)
Maximum Operating Altitude (m)
4000
Weight (Kg)
44
442*133*520 (core part), 483*133*559 (max.
Dimensions (W x H x D mm)
dimensions)
Ingress Protection Rating
IP20
Application Method
On-grid/On-grid + Back-up/Back-up
Supports up to 30 in parallel connection(150kWh)
Scalability
(Hand-in-hand/Busbar connection)
Mounting Method
19-inch standard rack/floor mounted, wall-mounted
Cycle Efficiency*1
≥96%
Cycle Life
6000(25℃±2℃,0.2C,70%EOL)
Warranty*4
10 years
Safety
Standard
and
Certification
IEC62619、IEC63056、N140
EN IEC61000-6-1、EN IEC61000-6-2、EN IEC61000-
EMC
6-3、EN IEC61000-6-4
Transportation
UN38.3、ADR
Environment
ROHS、REACH
*1: Test conditions: 100% DOD, 0.2C charge & discharge at 25°C± 2 ℃,at the beginning of life.
*2: Max. charge / discharge current may be variant with different inverter models
*3: Recommend/Max. Charging/Discharging Current/ Nominal/Max. Power* derating will occur
related to temperature and SOC.
*4: The warranty is due whichever reached first of warranty period or energy throughput.
12.3 Smart Meter Technical Data
Technical Parameters
GMK110
Application
Input Data
Voltage
Single phase
Nominal Voltage (V)
152
220
Voltage Range (V)
Nominal Voltage
Frequency (Hz)
CT Ratio
Current
85~288
50/60
120A/40mA
CT Quantity
1
Communication
RS485
Communication distance (m)
1000
User Interface
2LED
Accuracy
Voltage/Current
Class I
Active Energy
Class I
Reactive Energy
Class II
Power Consumption (w)
<5
Dimensions (W x H x D mm)
Mechanical
Parameters
19*85*67
Weight (g)
50
Mounting Method
Rail Installation
Ingress Protection Rating
Environmental
Parameters
IP20
Operating Temperature Range (℃)
-30 ~ 60
Storage Temperature Range (℃)
-30 ~ 60
Relative Humidity (Non-Condensing)
0~95%
Max. Operating Altitude (m)
3000
GM330
Technical Parameters
Type of Electrical Supply System
Nominal Voltage L-N
(V)
Input Data
Nominal Voltage L-L
Voltage
(V)
Voltage Range
Three-phase
220/230
380/400
0.88Un-1.1Un
Nominal Voltage
Frequency (Hz)
153
50/60
Current
CT Ratio
nA:5A
Communication
RS485
Communication distance (m)
1000
User Interface
Accuracy
4 LEDs, Reset Button
Voltage/Current
Class 0.5
Active Energy
Class 0.5
Reactive Energy
Class 1
Power Consumption (w)
<5
Dimensions (W * H * D)
Mechanical
Parameters
72*85*72
Weight (g)
240
Mounting Method
Rail Installation
Ingress Protection Rating
Environmental
Parameters
IP20
Operating Temperature Range (℃)
-30~70
Storage Temperature Range (℃)
-30~70
Relative Humidity (No
0~95%
Condensing)
Max. Operating Altitude (m)
3000
12.4 Smart Dongle Technical Data
Technical Parameters
WiFi/LAN Kit-20
Output Voltage (V)
5
Power Consumption (W)
≤2
Communication Interface
USB
Communication
Ethernet
10M/100Mbps Self-adaption
Wireless
IEEE 802.11 b/g/n @2.4 GHz
Parameters
Bluetooth
Mechanical
Dimensions (W x H x
Parameters
D mm)
Bluetooth V4.2 BR/EDR and Bluetooth LE
standard
48.3*159.5*32.1
154
Weight (g)
82
Ingress Protection
Rating
Mounting Method
IP65
USB port insertion and removal
Operating Temperature Range (℃)
-30~+60
Storage Temperature Range (℃)
-40~+70
Relative Humidity
0-95%
Max. Operating Altitude (m)
4000
Technical Parameters
Ezlink3000
General Data
Connection Interface
Ethernet interface (optional)
USB
10/100Mbps self-adaption, communication distance
≤100m
Mounting Method
Plug-and-play
Indicator
LED indicator status
Dimensions (W * H * D mm)
49*153*32
Weight (gram)
130
Ingress Protection Rating
IP65
Power Consumption (W)
≤2W (typical value)
Working Mode
STA
Wireless Parameters
Bluetooth Communication
Bluetooth 5.1
WiFi Communication
802.11 b/g/n(2.412GHz-2.484GHz)
Environmental Parameters
Operating Temperature Range
(℃)
-30 ~ +60
Storage Temperature Range (℃)
-30 ~ +70
Relative Humidity
0-100% (no condensing)
155
Max. Working Altitude (m)
4000
156
13 Appendix
13.1 FAQ
13.1.1 How to conduct auxiliary detection for smart meters/CT?
Meter detection function, which can detect whether the CT of the meter is connected
correctly and the current operation status of the meter and CT.
Step 1: Access the detection page through Home > Settings > Electricity Meter/CT
Auxiliary Detection.
Step 2: Click "Start Detection" and wait for the detection to complete. Then, view the
detection results.
13.1.2 How to Upgrade the Device Version
Through the firmware information, you can view or upgrade the DSP version, ARM version,
BMS version, and communication module software version of the inverter. Some smart
dongles do not support software version upgrade via SolarGo App, and the actual situation
shall prevail.
Upgrade prompt:
When the user opens the APP, an upgrade prompt will pop up on the homepage, and the
user can choose whether to upgrade or not. If you choose to upgrade, you can complete
the upgrade by following the prompts on the interface.
Regular upgrade:
Step 1: Access the firmware information viewing interface through "Home" > "Settings" >
"Firmware Information".
Step 2: Click "Check for Updates". If there is a new version, complete the upgrade
according to the prompts on the interface.
Forced Upgrade:
The APP will push upgrade information, and users need to upgrade according to the
157
prompts; otherwise, they will not be able to use the APP. You can complete the upgrade by
following the prompts on the interface.
13.2 Abbreviations
Abbreviation
English Description
Ubatt
Battery Voltage Range
Ubatt,r
Nominal Battery Voltage
Ibatt,max (C/D)
Max. Continuous Charging Current
Max. Continuous Discharging Current
EC,R
Rated Energy
UDCmax
Max. Input Voltage
UMPP
MPPT Operating Voltage Range
IDC,max
Max. Input Current per MPPT
ISC PV
Max. Short Circuit Current per MPPT
PAC,r
Nominal Output Power
Sr (to grid)
Nominal Apparent Power Output to Utility Grid
Smax (to grid)
Max. Apparent Power Output to Utility Grid
Sr (from grid)
Nominal Apparent Power from Utility Grid
Smax (from grid)
Max. Apparent Power from Utility Grid
UAC,r
Nominal Output Voltage
fAC,r
Nominal AC Grid Frequency
IAC,max(to grid)
Max. AC Current Output to Utility Grid
IAC,max(from grid)
Max. AC Current From Utility Grid
P.F.
Power Factor
Sr
Back-up Nominal apparent power
Smax
Max. Output Apparent Power (VA)
Max. Output Apparent Power without Grid
IAC,max
Max. Output Current
UAC,r
Nominal Output Voltage
fAC,r
Nominal Output Frequency
158
Toperating
Operating Temperature Range
IDC,max
Max. Input Current
UDC
Input Voltage
UDC,r
DC Power Supply
UAC
Power Supply/AC Power Supply
UAC,r
Power Supply/Input Voltage Range
Toperating
Operating Temperature Range
Pmax
Max Output Power
PRF
TX Power
PD
Power Consumption
PAC,r
Power Consumption
F (Hz)
Frequency
ISC PV
Max. Input Short Circuit Current
Udcmin-Udcmax
Range of input Operating Voltage
UAC,rang(L-N)
Power Supply Input Voltage
Usys,max
Max System Voltage
Haltitude,max
Max. Operating Altitude
PF
Power Factor
THDi
Total Harmonic Distortion of Current
THDv
Total Harmonic Distortion of Voltage
C&I
Commercial & Industrial
SEMS
Smart Energy Management System
MPPT
Maximum Power Point Tracking
PID
Potential-Induced Degradation
Voc
Open-Circuit Voltage
Anti PID
Anti-PID
PID Recovery
PID Recovery
PLC
Power-line Communication
Modbus TCP/IP
Modbus Transmission Control / Internet Protocol
Modbus RTU
Modbus Remote Terminal Unit
SCR
Short-Circuit Ratio
UPS
Uninterruptable Power Supply
159
ECO mode
Economical Mode
TOU
Time of Use
ESS
Energy Storage System
PCS
Power Conversion System
RSD
Remote shutdown
EPO
Emergency Power Off
SPD
Surge Protection Device
ARC
zero injection/zero export
Power Limit / Export Power Limit
DRED
Demand Response Enabling Device
RCR
Ripple Control Receiver
AFCI
AFCI
GFCI
Ground Fault Circuit Interrupter
RCMU
Residual Current Monitoring Unit
FRT
Fault Ride Through
HVRT
High Voltage Ride Through
LVRT
Low Voltage Ride Through
EMS
Energy Management System
BMS
Battery Management System
BMU
Battery Measure Unit
BCU
Battery Control Unit
SOC
State of Charge
SOH
State of Health
SOE
State Of Energy
SOP
State Of Power
SOF
State Of Function
SOS
State Of Safety
DOD
Depth of discharge
160
">