GoodWe ES Uniq Series User Manual
Below you will find brief information for ES Uniq GW3000-ES-C10, ES Uniq GW3000-ES-C11, ES Uniq GW3600-ES-C10, ES Uniq GW5000-ES-C10, ES Uniq GW6000-ES-C10, LX A5.0-10, LX A5.0-30, LX U5.0-30, GMK110, GM330, WiFi/LAN Kit-20, 4G Kit-CN-G20, 4G Kit-CN-G21, Ezlink3000. This manual describes the product information, installation, electrical connection, commissioning, troubleshooting and maintenance of the energy storage system, including inverters, batteries, smart meters and dongles. The system converts solar energy for household use and allows for smart energy consumption management.
Advertisement
Advertisement
V1.6 2025-08-18 Copyright Statement Copyright©GoodWe Technologies Co., Ltd. 2025. All rights reserved. No part of this manual can be reproduced or transmitted to the public platform in any form or by any means without the prior written authorization of GoodWe Technologies Co., Ltd. Trademarks GOODWE and other GOODWE trademarks are trademarks of GoodWe Technologies Co.,Ltd. All other trademarks or registered trademarks mentioned in this brochure are the property of their respective owners. NOTICE The information in this user manual is subject to change due to product updates or other reasons. This manual cannot replace the product safety labels unless otherwise specified. All descriptions in the manual are for guidance only. 1 Table of Contents 1 About This Manual 14 1.1 Overview 14 1.2 Applicable Model 14 1.3 Symbol Definition 15 2 Safety Precautions 17 2.1 General Safety 17 2.2 Personal Requirements 17 2.3 System Safety 18 2.3.1 PV String Safety 19 2.3.2 Inverter Safety 19 2.3.3 Battery Safety 20 2.3.4 Smart Meter Safety 22 2.4 Safety Symbols and Certification Marks 22 2.5 EU Declaration of Conformity 24 2.5.1 Equipment with Wireless Communication Modules 24 2.5.2 Equipment without Wireless Communication Modules (Except Battery) 24 2.5.3 Battery 25 3 System Introduction 26 3.1 System Overview 26 3.2 Product Overview 36 3.2.1 Inverter 36 2 3.2.2 Battery 37 3.2.2.1 LX A5.0-10 37 3.2.2.2 LX A5.0-30 37 3.2.2.3 LX U5.0-30 38 3.2.3 Smart Meter 38 3.2.4 Smart Dongle 39 3.3 Supported Grid Types 39 3.4 System Working Mode 40 3.5 Features 50 4 Check and Storage 53 4.1 Check Before Receiving 53 4.2 Deliverables 53 4.2.1 Inverter Deliverables 53 4.2.2 Battery Deliverables 55 4.2.2.1 Battery Deliverables (LX A5.0-10) 55 4.2.2.2 Battery Deliverables (LX A5.0-30) 56 4.2.2.3 Battery Deliverables (LX U5.0-30) 57 4.2.3 Busbar Deliverables 58 4.2.3.1 BCB-11-WW-0 59 4.2.3.2 BCB-22-WW-0 59 4.2.3.3 BCB-32-WW-0 59 4.2.4 Smart Meter Deliverables 60 3 4.2.4.1 Smart Meter Deliverables (GMK110) 60 4.2.4.2 Smart Meter Deliverables (GM330) 60 4.2.5 Smart Dongle 61 4.2.5.1 Smart Dongle (WiFi/LAN Kit-20) 61 4.2.5.2 Smart Dongle (4G Kit-CN-G20 & 4G Kit-CN-G21) 61 4.2.5.3 Smart Dongle (Ezlink3000) 61 4.3 Storage 62 5 Installation 65 5.1 System Installation and Commissioning Procedure 65 5.2 Installation Requirements 65 5.2.1 Installation Environment Requirements 65 5.2.2 Installation Space Requirements 67 5.2.3 Tool Requirements 68 5.3 Equipment Handling 70 5.4 Installing the Inverter 71 5.5 Installing the Battery System 72 5.5.1 LX A5.0-30 78 5.5.2 LX A5.0-10 81 5.5.3 LX U5.0-30 83 5.6 Installing the Smart Meter 84 6 System Wirings 86 6.1 System Wiring Electrical Block Diagram 4 86 6.2 Detailed System Wiring Diagram 88 6.2.1 Detailed System Wiring Diagram for Single Inverter 88 6.2.2 Detailed System Wiring Diagram for Parallel System 90 6.3 Preparing Materials 92 6.3.1 Preparing Breakers 93 6.3.2 Preparing Cables 94 6.4 Connecting the PE Cable 97 6.5 Connecting the PV Cable 98 6.6 Connecting the Battery Cable 100 6.6.1 Connecting the Power Cable between the Inverter and Battery 115 6.6.2 Connecting the Communication Cable between the Inverter and Battery 118 6.7 Connecting the AC Cable 120 6.8 Connecting the Meter Cable 122 6.9 Connecting the Inverter Communication Cable 125 6.10 Installing the Battery Cover 129 6.10.1 LX A5.0-10 129 6.10.2 LX A5.0-30 130 6.10.3 LX U5.0-30 130 7 System Commissioning 132 7.1 Check Before Power ON 132 7.2 Power ON 132 5 7.3 Indicators 135 7.3.1 Inverter Indicators 135 7.3.2 Battery Indicators 136 7.3.2.1 LX A5.0-10 136 7.3.2.2 LX A5.0-30, LX U5.0-30 138 7.3.3 Smart Meter Indicator 138 7.3.3.1 GMK110 139 7.3.3.2 GM330 139 7.3.4 Smart Dongle Indicator 139 7.3.4.1 WiFi/LAN Kit-20 139 7.3.4.2 4G Kit-CN-G20 & 4G Kit-CN-G21 141 7.3.4.3 Ezlink3000 141 8 Rapid System Configuration 143 8.1 Downloading the App 143 8.1.1 Downloading SolarGo App 143 8.1.2 Downloading SEMS+ APP 143 8.2 Connecting the inverter via SolarGo 144 8.3 Setting Communication Parameters 145 8.3.1 Setting Privacy and Security Parameters 146 8.3.2 Setting WLAN/LAN Parameters 149 8.3.3 Setting APN Parameters 151 8.3.4 Setting RS485 Communication Parameters 151 6 8.4 Quick System Setup 152 8.4.1 Quick System Setup (Type III) 153 8.5 Power Plant Creation 159 9 System Commissioning 161 9.1 Commissioning Method Overview 161 9.2 Configuration via LCD 161 9.2.1 LCD Overview 161 9.2.2 Quick Settings 163 9.2.3 Setting Advanced Parameters 169 9.2.4 Setting Immediate Charging 170 9.2.5 Setting the Basic Information 171 9.2.6 Viewing Device Information 171 9.2.7 Setting Port Connection 172 9.3 Configuration via SolarGo APP 176 9.3.1 App Introduction 176 9.3.1.1 Downloading and Installing the App 176 9.3.1.2 Connection Method 177 9.3.1.3 Introduction of Interface 178 9.3.2 Connecting the Energy Storage Inverter 9.3.2.1 Connecting the Energy Storage Inverter (Bluetooth) 179 181 9.3.3 Introduction of the Energy Storage Inverter Interface 182 9.3.4 Setting Communication Parameters 184 7 9.3.4.1 Setting Privacy and Security Parameters 184 9.3.4.2 Setting WLAN/LAN Parameters 187 9.3.4.3 Setting APN Parameters 189 9.3.4.4 Setting RS485 Communication Parameters 189 9.3.5 Quick System Setup 190 9.3.5.1 Quick System Setup (Type III) 9.3.6 Setting the Basic Information 191 197 9.3.6.1 Setting up Lightning Protection Alarm Function 197 9.3.6.2 Setting up Shadow Scanning Function 198 9.3.6.3 Setting Backup Power Parameters 199 9.3.7 Setting Advanced Parameters 201 9.3.7.1 Setting DRED/Remote Shutdown/RCR/EnWG 14a Function 201 9.3.7.2 Setting BACK-UP N and PE Relay Switches 202 9.3.7.3 Setting the On-Grid Power Limit 203 9.3.7.3.1 Setting the On-Grid Power Limit (General) 203 9.3.7.3.2 Setting the On-Grid Power Limit (Australia) 204 9.3.7.4 Setting the Arc Detection Function 206 9.3.7.5 Set Battery Function 206 9.3.7.5.1 Set Parameters for Lithium Battery 206 9.3.7.5.2 Setting Lead-acid Battery Parameter 210 9.3.7.6 Setting PV Connect Mode 214 9.3.8 Setting Customized Safety Parameters 8 215 9.3.8.1 Setting Reactive Curve 216 9.3.8.2 Setting Active Curve 220 9.3.8.3 Setting Grid Protection Parameters 226 9.3.8.4 Setting Grid Connection Parameters 227 9.3.8.5 Setting Voltage Fault Ride through Parameters 229 9.3.8.6 Setting Frequency Fault Ride through Parameters 230 9.3.9 Setting Generator/Load Control Parameters 231 9.3.9.1 Setting Load Control Parameters 231 9.3.9.2 Setting Generator Parameters 234 9.3.9.3 Setting Microgrid Parameters 237 9.3.10 Setting Smart Meter Parameters 239 9.3.10.1 Meter/CT Assisted Test 239 9.3.11 Equipment Maintenance 240 9.3.11.1 View Firmware Information/Firmware Upgrade 240 9.3.11.1.1 Regular Firmware Upgrades 240 9.3.11.1.2 One-click Firmware Upgrade 241 9.3.11.1.3 Automatic Firmware Upgrade 242 9.3.11.2 Changing Login Password 10 Power Plant Monitoring 243 245 10.1 SEMS+ 245 10.1.1 App Introduction 245 10.1.1.1 Complementary Products 9 245 10.1.1.2 Downloading and Installing the App 245 10.1.1.3 Connection Method 246 10.1.1.4 Setting Language and Server 246 10.1.1.5 Setting Communication Parameters 246 10.1.2 Account Management 247 10.1.2.1 Registering 247 10.1.2.2 Account Login 247 10.1.2.3 Switch 247 10.1.2.4 Canceling 247 10.1.2.5 Account Permissions 248 10.1.3 Viewing Power Plant Information 252 10.1.3.1 View All Power Plant Overview Information 252 10.1.3.2 Viewing Monopower Plant Details 253 10.1.3.2.1 Viewing Power Plant Details (Traditional Mode) 10.1.4 Viewing Alarm Information 254 254 10.1.4.1 Viewing Alarm Information for All Power Plants 254 10.1.4.2 Viewing the current power plant's alarm information 255 10.1.4.2.1 Viewing Alarm Information for the Current Power Plant (Traditional Mode) 10.1.4.3 Viewing the Current Device’s Alarm Information 255 256 10.1.5 Viewing Power Plant Report Information 257 10.1.6 Power Plant Management 259 10.1.6.1 Power Plant Creation 259 10 10.1.6.2 Configuring Power Plant Information 260 10.1.6.3 Power Plant Visitors Management 260 10.1.6.4 Power Plant Photos Management 261 10.1.6.5 Setting PV Component Layout 261 10.1.6.6 Adjusting the Information Displayed on the Power Station Details Page 261 10.1.6.7 Deleting Power Plant 262 10.1.6.8 Collecting Power Plant 262 10.1.7 Managing the Equipment in the Power Plant 262 10.1.7.1 Additional Equipment 262 10.1.7.2 Editing Device Information 264 10.1.7.3 Deleting Device 264 10.1.7.4 Upgrading Device Firmware Version 264 10.1.8 Remote Management Device 10.1.8.1 Setting Energy Storage Inverter Parameters 11 Maintenance 265 265 271 11.1 Power Off the System 271 11.2 Removing the Equipment 272 11.3 Disposing of the Equipment 272 11.4 Routine Maintenance 272 11.5 Fault 274 11.5.1 Viewing Fault/Alarms Information 11 274 11.5.2 Fault Information and Troubleshooting 274 11.5.2.1 System Failure 277 11.5.2.2 Inverter Troubleshooting 279 11.5.2.3 Battery Fault (LX A5.0-10) 322 11.5.2.4 Battery Fault (LX A5.0-30, LX U5.0-30) 324 11.5.3 Operation After Fault Clearance 11.5.3.1 Clear AFCI Alarm 327 328 12 Technical Parameters 329 12.1 Inverter Parameters 329 12.2 Battery Technical Data 339 12.2.1 LX A5.0-10 339 12.2.2 LX A5.0-30 340 12.2.3 LX U5.0-30 342 12.3 Smart Meter Technical Data 343 12.3.1 GMK110 343 12.3.2 GM330 344 12.4 Smart Dongle Technical Data 345 12.4.1 WiFi/LAN Kit-20 345 12.4.2 4G Kit-CN-G20, 4G Kit-CN-G21 346 12.4.3 Ezlink3000 346 13 Appendix 348 13.1 FAQ 348 12 13.1.1 How to Conduct Auxiliary Detection for Smart Meters/CT? 348 13.1.2 How to Upgrade the Device Version 348 13.2 Abbreviations 349 13.3 Explanation of Terms 352 13.4 Meaning of Battery SN Code 353 14 Contact Details 355 13 1 About This Manual 1.1 Overview The energy storage system consists of inverter, battery system, and smart meter. This manual describes the product information, installation, electrical connection, commissioning, troubleshooting and maintenance of the system. Read through this manual before installing and operating the products to understand product safety information and familiarize yourself with functions and features of the product. This manual is subject to update without notice. For more product details and latest documents, visit https://en.goodwe.com/. 1.2 Applicable Model The energy storage system consists the following products: Product type Product information Inverter GW3000-ES-C10 GW3000-ES-C11 GW3600-ES-C10 GW5000-ES-C10 GW6000-ES-C10 Battery system Smart Meter Description Nominal output power: 3.0kW Nominal output power: 3.6kW Nominal output power: 5.0kW Nominal output power: 6.0kW LX A5.0-10 Usable energy of 5.0kWh, supports a maximum of 15 batteries connected in parallel. LX A5.0-30 Usable energy of 5.12kWh, supports a maximum of 30 batteries connected in parallel. LX U5.0-30 Usable energy of 5.12kWh, supports a maximum of 30 batteries connected in parallel. GMK110 14 Product type Product information Description GM330 It is a monitoring module in the energy storage system which can detect information such as operating voltage, current, and other data in the system. WiFi/LAN Kit-20 In the single inverter scenario, the system operation information can be uploaded to a monitoring platform through WiFi or LAN signals. In the single inverter scenario, the system operation information can be uploaded to a monitoring platform through 4G signal. 4G Kit-CN-G20 Smart dongle 4G Kit-CN-G21 In parallel system with multi inverters, it is installed on the master inverter to upload the system running information to monitoring platform through WiFi or LAN signals. Ezlink3000 1.3 Symbol Definition DANGER Indicates a high-level hazard that, if not avoided, will result in death or serious injury. WARNING Indicates a medium-level hazard that, if not avoided, could result in death or serious injury. CAUTION Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury. 15 NOTICE Highlights key information and supplements the texts. Or some skills and methods to solve product-related problems to save time. 16 2 Safety Precautions Please strictly follow these safety instructions in the user manual during the operation. WARNING The products are designed and tested strictly to comply with related safety rules. Follow all the safety instructions and cautions before any operations. Improper operation might cause personal injury or property damage as the products are electrical equipment. 2.1 General Safety NOTICE • The information in this user manual is subject to change due to product updates or other reasons. This manual cannot replace the product safety labels unless otherwise specified. All descriptions in the manual are for guidance only. • Before installations, read through the user manual to learn about the product and the precautions. • All operations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations. • Use insulating tools and wear personal protective equipment(PPE) when operating the equipment to ensure personal safety. Wear anti-static gloves, wrist strips, and cloths when touching electronic devices to protect the equipment from damage. • Unauthorized dismantling or modification may damage the equipment, and the damage is not covered under the warranty. • Strictly follow the installation, operation, and configuration instructions in this manual or the user manual. The manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For more warranty details, please visit https://www.goodwe.com/warrantyrelated.html. 2.2 Personal Requirements 17 NOTICE • Personnel who install or maintain the equipment must be strictly trained, learn about safety precautions and correct operations. • Only qualified professionals or trained personnel are allowed to install, operate, maintain, and replace the equipment or parts. 2.3 System Safety DANGER • Disconnect the upstream switches to power off the equipment before any electrical connections. Do not work with power on. Otherwise, an electric shock may occur. • Install a breaker at the voltage input side of the equipment to prevent personal injury or equipment damage caused by energized electrical work. • All operations such as transportation, storage, installation, use and maintenance shall comply with applicable laws, regulations, standards and specifications. • Perform electrical connections in compliance with local laws, regulations, standards and specifications, including cables and component specifications. • Use the connectors included in the package to connect cables. The manufacturer shall not be liable for the equipment damage if connectors of other models are used. • Ensure all cables are connected correctly, tightly, and securely. Inappropriate wiring may cause poor connection and damage the equipment. • The PE cables must be connected and secured properly. • To protect the equipment and components from damage during transportation, ensure that the transportation personnel are professionally trained. All operations during the transportation have to be recorded. The equipment shall be kept in balance to avoid falling down. • The equipment is heavy. Please equip the corresponding personnel according to its weight, so that the equipment does not exceed the maximum weight that the personnel can carry to avoid personnel injuries. • Keep the equipment stable to avoid dumping, which can result in equipment damage and personal injuries. 18 WARNING • Do not apply mechanical load to terminals, otherwise the terminals may be damaged. • If the cable bears too much tension, the connection may be poor. Reserve a certain length of the cable before connecting it to corresponding ports. • Tie the cables of the same type together, and place cables of different types at least 30mm apart. Do not place the cables entangled or crossed. • Place the cables at least 30mm away from the heating components or heat sources, otherwise the insulation layer of the cables may be aging or broken due to high temperature. 2.3.1 PV String Safety WARNING • Ensure the PV module frames and the bracket system are securely grounded. • Ensure the DC cables are connected tightly, securely and correctly. Inappropriate wiring may cause poor contacts or high impedances, and damage the inverter. • Measure the positive and negative terminals of the DC cable using a multimeter to avoid reverse polarity connection. Also, the voltage should be within the permissible range. • Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and extremely high voltage. • The PV strings cannot be grounded. Ensure the minimum insulation resistance of PV string to the ground meets the minimum insulation resistance requirements before connecting the PV string to the inverter (R=maximum input voltage (V)/ 30mA). • Do not connect the same PV string to multiple inverters at the same time. Otherwise, the inverters may be damaged. • PV modules used with inverters must comply with IEC 61730 Class A standard. 2.3.2 Inverter Safety 19 WARNING • The voltage and frequency at the connecting point should meet the on-grid requirements. • Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the protective device should be at least 1.25 times the maximum AC output current. • The arc fault alarms will be cleared automatically if the alarms are triggered less than 5 times in 24 hours. The inverter will shutdown for protection after the 5th electric arc fault. The inverter can operate normally after the fault is solved. • BACK-UP is not recommended if the PV system is not configured with batteries. Otherwise, there may be a risk of system power outage. 2.3.3 Battery Safety DANGER • Keep Power Off before any operations to avoid danger of electric shock. Strictly follow all safety precautions outlined in this manual and safety labels on the equipment during the operation. • Do not disassemble, modify, or replace any part of the battery or the power control unit without official authorization from the manufacturer. Otherwise, it will cause electrical shock or damages to the equipment, which shall not be borne by the manufacturer. • Do not hit, pull, drag, squeeze or step on the equipment or put the battery into fire. Otherwise, the battery may explode. • Do not place the battery in a high temperature environment. Make sure that there is no direct sunlight and no heat source near the battery. When the ambient temperature exceeds 60 ℃, it will cause fire. • Do not use the battery or the power control unit if it is defective, broken, or damaged. Damaged battery may leak electrolyte. • Do not move the battery system while it is working. Contact after-sales service if the battery shall be replaced or added. • A short circuit in the battery may cause personal injury. The instantaneous high current caused by a short circuit can release a large amount of energy and may cause a fire. 20 WARNING • Factors such as temperature, humidity, weather conditions, etc. may limit the battery's current and affect its load. • Contact after-sale service immediately if the battery is not able to be started. Otherwise, the battery might be damaged permanently. • Inspect and maintain the battery regularly according to the maintenance requirements of the battery. Emergency Measures • Battery Electrolyte Leakage If the battery module leaks electrolyte, avoid contact with the leaking liquid or gas. The electrolyte is corrosive. It will cause skin irritation or chemical burn to the operator. Anyone contact the leaked substance accidentally has to act/respond as following: Breath in the leaked substance: Evacuate from the polluted area, and seek immediate medical assistance. Eye contact: Rinse your eyes for at least 15 minutes with clean water and seek immediate medical assistance. Skin contact: Thoroughly wash the touch area with soap and clean water, and seek immediate medical assistance. Ingestion: Induce vomiting, and seek immediate medical assistance. ○ ○ ○ ○ • Fire The battery may burn when the ambient temperature exceeds 150℃. Poisonous and hazardous gas may be released if the battery is on fire. In the event of a fire, please make sure that the carbon dioxide extinguisher or Novec1230 or FM-200 is nearby. The fire cannot be put out by ABC dry powder extinguisher. Firefighters are required to wear full protective clothing and self-contained breathing apparatus. • Battery triggers fire protection For batteries with fire protection functions, perform the following operations after the fire protection function is triggered: Immediately cut off the main power switch to ensure that no current passes through the battery system. Conduct a preliminary inspection of the appearance of the battery to determine if there is any damage, deformation, leakage, or odor. Check the battery casing, ○ ○ ○ ○ ○ 21 ○ ○ connectors, and cables. Use temperature sensors to detect the temperature of the battery and its environment, ensuring there is no risk of overheating. Isolate and label damaged batteries, and handle them properly in accordance with local regulations. 2.3.4 Smart Meter Safety WARNING If the voltage of the power grid fluctuates, resulting in the voltage over 265V. In this case, long-term overvoltage operation may cause damage to the meter. It is recommended to add a fuse with a rated current of 0.5A on the voltage input side of the meter to protect it. 2.4 Safety Symbols and Certification Marks DANGER • All labels and warning marks should be visible after the installation. Do not cover, scrawl, or damage any label on the equipment. • The following descriptions are for reference only. Please refer to the actual labeling of the equipment. No. Symbol Descriptions 1 Potential risks exist. Wear proper PPE before any operations. 2 HIGH VOLTAGE HAZARD. High voltage exists. Disconnect all incoming power and turn off the product before working on it. 3 High-temperature hazard. Do not touch the product under operation to avoid being burnt. 22 No. Symbol Descriptions 4 Operate the equipment properly to avoid explosion. 5 Batteries contain flammable materials, beware of fire. 6 The equipment contains corrosive electrolytes. In case of a leak in the equipment, avoid contacting the leaked liquid or gas. 7 Delayed discharge. Wait 5 minutes after power off until the components are completely discharged. 8 Install the equipment away from fire sources. 9 Keep away from children. 10 Do not pour with water. 11 Read through the user manual before any operations. 12 Wear PPE during installation, operation and maintaining. 13 Do not dispose of the System as household waste. Deal with it in compliance with local laws and regulations, or send it back to the manufacturer. 14 Grounding point. 23 No. Symbol Descriptions 15 Recycle regeneration mark. 16 CE Mark. 17 TUV mark. 18 RCM mark. 2.5 EU Declaration of Conformity 2.5.1 Equipment with Wireless Communication Modules The equipment with wireless communication modules sold in the European market meets the requirements of the following directives: • Radio Equipment Directive 2014/53/EU (RED) • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS) • Waste Electrical and Electronic Equipment 2012/19/EU • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) 2.5.2 Equipment without Wireless Communication Modules (Except Battery) The equipment without wireless communication modules sold in the European market meets the requirements of the following directives: • Electromagnetic compatibility Directive 2014/30/EU (EMC) • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD) • Restrictions of Hazardous Substances Directive 2011/65/EU and (EU) 2015/863 (RoHS) 24 • Waste Electrical and Electronic Equipment 2012/19/EU • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) 2.5.3 Battery The batteries sold in the European market meets the requirements of the following directives: • Electromagnetic compatibility Directive 2014/30/EU (EMC) • Electrical Apparatus Low Voltage Directive 2014/35/EU (LVD) • Battery Directive 2006/66/EC and Amending Directive 2013/56/EU • Waste Electrical and Electronic Equipment 2012/19/EU • Registration, Evaluation, Authorization and Restriction of Chemicals (EC) No 1907/2006 (REACH) You can download the EU Declaration of Conformity from our official website. 25 3 System Introduction 3.1 System Overview The residential smart inverter solution consists of inverter, battery system, smart meter, smart dongle, etc.. In the PV system, solar energy can be converted to electric energy for household needs. The IoT devices in the system manage the electrical equipment and energy consumption in a smart way by recognizing the overall power consumption and deciding whether the power is to be used by the loads, stored in batteries, or exported to the grid. WARNING • Select the battery model according to the inverter model and the approved battery list. For battery requirements used in the same system, such as whether the models can be mixed and matched, and whether the capacities are consistent, please refer to the corresponding model's battery user manual or contact the battery manufacturer for relevant requirements. Compatibility Overview: https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_Battery%20Co mpatibility%20Overview-EN.pdf • Due to product upgrades or other reasons, the document content may be updated irregularly. The matching relationship between inverters and IoT products can refer to: https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_Compatibilitylist-of-GoodWe-inverters-and-IoT-products-EN.pdf Scenario 26 Produc t Type Inverter Model Description GW3000-ES-C10 GW3000-ES-C11 GW3600-ES-C10 GW5000-ES-C10 GW6000-ES-C10 • When only one inverter is used in the system, it is supported to be connected to a generator or large loads. • When multiple inverters are used in the system, it is not supported to connect a generator or large loads; a maximum of 6 inverters are supported to form a parallel system, and the Ezlink3000 is required in the parallel system. • Requirements for parallel: The software version of all inverters in the system is the same. The ARM software version of the inverter is 12 (451) and above. The DSP software version of the inverter is 13 (13) and above. ○ ○ ○ LX A5.0-10 27 Produc t Type Battery System Model Battery of different models cannot be mixed. LX A5.0-30 Busbar Description • LX A5.0-10: The nominal charging and discharging current of a single battery is 60A; a maximum of 15 batteries can be connected in parallel in one system. • LX A5.0-30: The nominal charging current of a single battery is 60A, and the nominal discharging current is 100A; the maximum charging current is 90A; the maximum discharging current is 150A. A maximum of 30 batteries can be connected in parallel in one system. LX U5.0-30 The nominal charging current of a single battery is 60A; and the nominal discharging current is 100A; the maximum charging current is 90A; the maximum discharging current is 100A. A maximum of 30 batteries can be connected in parallel in one system. Lead Acid Battery • Supports connection to lead-acid batteries of AGM, GEL, and Flooded types. • The number of batteries that can be connected in series is calculated based on the voltage of leadacid batteries, and the total voltage of batteries connected in series is not allowed to exceed 60V. BCB-11-WW-0 BCB-22-WW-0 BCB-32-WW-0 BCB-33-WW-0 (Purchase from GoodWe) Please select the busbar according to the charging/discharging capacity of the inverter, the load size, and the charging/discharging capacity of the battery in the system. • BCB-11-WW-0: used with LX A5.0-10, the battery system supports a maximum working current of 360A, working power of 18kW, and can be connected to a maximum of 3 inverters, and 6 batteries. • BCB-22-WW-0: ○ 28 Produc t Type Model Description used with LX A5.0-10, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 12 batteries. used with LX A5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 6 batteries. used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 6 batteries. • BCB-32-WW-0: used with LX A5.0-10, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. used with LX A5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 8 batteries. • BCB-33-WW-0: used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. When the number of batteries exceeds 8, two 600A fuses need to be connected in parallel. • Others: Please prepare busbar based on actual system power and current. ○ ○ ○ ○ ○ ○ ○ 29 Produc t Type Model Description Smart Meter • Built-in Smart Meter (Standard) • GMK110 (purchase from GoodWe) • GM330 (purchase from GoodWe) • Built-in Smart Meter: When the number of parallel inverters is ≤2 and the length of CT cable is ≤10 meters, the built-in meter can be used. Built-in smart meter: 10-meter wire CT, default CT ratio: 120A/40mA. • GMK110: When the length of the built-in CT cable of the inverter is not enough for connection to the switchboard, please connect an external GMK110 smart meter. CT is not supported for changing to other type, CT ratio: 120A/40mA. • GM330: Supports purchasing from GOODWE or third-party, CT ratio requirement: nA/5A • nA: CT primary input current, n ranges from 200 to 5000. • 5A: CT secondary output current. Smart Dongle • WiFi/LAN Kit20 (Standard) • 4G Kit-CNG20(Only for China) • 4G Kit-CNG21(Only for China) • Ezlink3000 (purchase from GoodWe) • Please use the WiFi/LAN Kit-20, 4G Kit-CN-G20, 4G Kit-CN-G21 modules in single inverter system. • In parallel scenarios, the EzLink3000 must be connected to the master inverter. Do not connect any smart dongle to slave inverter. Ezlink3000 requires a firmware version of 05 or above. Supports SG Ready, large load specification requirements: Heavy Load - 1. Large load total power < GEN port maximum output power 2. Large load power + BACK-UP power < AC maximum input power (grid) 30 Produc t Type Generat or Model Description - Generator rated voltage meets inverter GEN port rated voltage. Microgrid Scenario WARNING • In microgrid scenarios, the PV open-circuit voltage of the hybrid inverter is not recommended to be ≥500V, so as to avoid triggering the over-voltage protection when the system voltage is too high under severe working conditions. • In microgrid systems, inverters are not supported in parallel and only one inverter is supported to be used in the system. • If the system is in a high temperature or BMS current limiting situation, it may cause the battery charging power to be limited, which may lead to high system voltage triggering over-voltage protection. • In microgrid scenarios, make sure that the overfrequency derating point of the on-grid inverter is the same as that of the hybrid inverter. • Make sure that the overfrequency derating curve of the on-grid inverter is set according to the following via SolarGo: End power set to 0% Pn ○ ○ Silent time set to 0 ○ Power response mode set to off 31 Produc t Type Hybrid Inverter Model Description GW3000-ES-C10 GW3000-ES-C11 GW3600-ES-C10 GW5000-ES-C10 GW6000-ES-C10 • In the microgrid system, parallelization is not supported by the inverter, and only a single inverter can be supported to use in the system. • Requirements: The ARM software version of the inverter is 12 (451) and above. The DSP software version of the inverter is 13 (13) and above. ○ ○ LX A5.0-10 32 Produc t Type Battery System Model Battery of different models cannot be mixed. LX A5.0-30 Busbar Description • LX A5.0-10: The nominal charging and discharging current of a single battery is 60A; a maximum of 15 batteries can be connected in parallel in one system. • LX A5.0-30: The nominal charging current of a single battery is 60A, and the nominal discharging current is 100A; the maximum charging current is 90A; the maximum discharging current is 150A. A maximum of 30 batteries can be connected in parallel in one system. LX U5.0-30 The nominal charging current of a single battery is 60A; and the nominal discharging current is 100A; the maximum charging current is 90A; the maximum discharging current is 100A. A maximum of 30 batteries can be connected in parallel in one system. Lead Acid Battery • Supports connection to lead-acid batteries of AGM, GEL, and Flooded types. • The number of batteries that can be connected in series is calculated based on the voltage of leadacid batteries, and the total voltage of batteries connected in series is not allowed to exceed 60V. BCB-11-WW-0 BCB-22-WW-0 BCB-32-WW-0 BCB-33-WW-0 (Purchase from GoodWe) Please select the busbar according to the charging/discharging capacity of the inverter, the load size, and the charging/discharging capacity of the battery in the system. • BCB-11-WW-0: used with LX A5.0-10, the battery system supports a maximum working current of 360A, working power of 18kW, and can be connected to a maximum of 3 inverters, and 6 batteries. • BCB-22-WW-0: ○ 33 Produc t Type Model Description used with LX A5.0-10, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 12 batteries. used with LX A5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 6 batteries. used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 6 batteries. • BCB-32-WW-0: used with LX A5.0-10, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. used with LX A5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 8 batteries. • BCB-33-WW-0: used with LX U5.0-30, the battery system supports a maximum working current of 720A, working power of 36kW, and can be connected to a maximum of 6 inverters, and 15 batteries. When the number of batteries exceeds 8, two 600A fuses need to be connected in parallel. • Others: Please prepare busbar based on actual system power and current. ○ ○ ○ ○ ○ ○ ○ 34 Produc t Type Model Description Smart Meter • Built-in Smart Meter (Standard) • GMK110 (purchase from GoodWe) • GM330 (purchase from GoodWe) • Built-in Smart Meter: When the number of parallel inverters is ≤2 and the length of CT cable is ≤10 meters, the built-in meter can be used. Built-in smart meter: 10-meter wire CT, default CT ratio: 120A/40mA. • GMK110: When the length of the built-in CT cable of the inverter is not enough for connection to the switchboard, please connect an external GMK110 smart meter. CT is not supported for changing to other type, CT ratio: 120A/40mA. • GM330: Supports purchasing from GOODWE or third-party, CT ratio requirement: nA/5A • nA: CT primary input current, n ranges from 200 to 5000. • 5A: CT secondary output current. Smart Dongle • WiFi/LAN Kit20 (Standard) • 4G Kit-CNG20(Only for China) • 4G Kit-CNG21(Only for China) Please use the WiFi/LAN Kit-20, 4G Kit-CN-G20, 4G KitCN-G21 modules in single inverter system. 35 Produc t Type Model Description • It’s recommended to use on-grid inverter sold in GOODWE, and is supported to use the third-party on-grid inverter. • In microgrid systems, make sure that the rated output power of the on-grid inverter ≤ the rated output power of the hybrid inverter. • When the microgrid system is in parallel, if power limitation is required, make sure: the hybrid inverter should be set in the on-grid power limit interface of the SolarGo APP, and the on-grid inverter should be set according to the actual instruments used. In order to ensure that the on-grid inverters can continue to generate power, the output power of the hybrid inverters must be adjusted in the microgrid mode interface of the SolarGo APP. ○ On-Grid Inverter - ○ Note: The output power control precision of different on-grid inverters varies. Please set the on-grid power limit control parameter value according to the actual situation. 3.2 Product Overview 3.2.1 Inverter Inverter controls and optimizes power through an integrated energy management system in the photovoltaic system. The electricity generated by the photovoltaic system can be supplied to the load, stored in Battery, or exported to Utility grid, among other functions. 36 No. Model 1 2 3 4 5 GW3000-ES-C10 GW3000-ES-C11 GW3600-ES-C10 GW5000-ES-C10 GW6000-ES-C10 Nominal Output Power 3000W 3000W 3600W 5000W 6000W Nominal Output Voltage 220/230/240 220/230/240 220/230/240 220/230/240 220/230/240 3.2.2 Battery The battery system stores and releases electricity based on the requirements of a PV energy storage system. The input and output ports of the energy storage system are both high-voltage direct current. The ES Uniq inverter supports connecting lead-acid batteries, and the product material of the battery can be obtained from the battery manufacturer. 3.2.2.1 LX A5.0-10 3.2.2.2 LX A5.0-30 37 3.2.2.3 LX U5.0-30 3.2.3 Smart Meter The smart meter can measure and monitor the data in the photovoltaic energy storage system, such as voltage, current, frequency, power factor, and power, etc.. 38 No. Model 1 GMK110 2 GM330 Applicable scenarios CT is not supported for changing to other type, CT ratio: 120A: 40mA Order the CT for GM330 from GoodWe or other suppliers. CT ratio: nA: 5A • nA: For the primary input current of CT, n ranges from 200 to 5000. • 5A: CT secondary output current. 3.2.4 Smart Dongle The smart dongle can transmit various power generation data to SEMS Portal, the remote monitoring platform, in real time, and can communicate with the SolarGo App to complete the near-end equipment commissioning. No. Model 1 WiFi/LAN Kit-20 2 4G Kit-CN-G20 3 4G Kit-CN-G21 4 Ezlink3000 Signal Bluetooth, WiFi, LAN Bluetooth, 4G 4G, bluetooth, GNSS Bluetooth, WiFi, LAN Applicable scenarios Single inverter scenario Master inverter of a parallel system 39 3.3 Supported Grid Types 3.4 System Working Mode NOTICE After the GW14.3-BAT-LV-G10 battery system is installed for the first time, it will automatically perform a full charge of the battery. Once completed, it will switch to the set operating mode. Self-use Mode • Self-use mode is the basic working mode of the system. • The power generated by the PV system supply the loads in priority; the excess power will charge the batteries, and then the remaining power will be sold to the utility grid. When the power generated in the PV system is insufficient, the battery will supply the loads in priority. If the battery power is insufficient, the load will be powered by the utility grid. 40 BACK-UP Mode • The BACK-UP mode is mainly applied to the scenario where the grid is unstable. • When the grid is disconnected, the inverter turns to off-grid mode and the battery will supply power to the BACK-UP loads; when the grid is restored, the inverter switches to on-grid mode. • To ensure that the battery SOC is sufficient to maintain normal operation of the system when it is off grid, the battery will be charged to the backup power SOC using PV or grid power during on-grid operation. If you need to purchase electricity from the power grid to charge the battery, please confirm compliance with local power grid laws and regulations. 41 42 TOU Mode It is recommended to use TOU mode in scenarios when the peak-valley electricity price varies a lot. Select TOU mode only when it meets the local laws and regulations. For example, set the battery to charge mode during Valley period to charge battery with grid power. And set the battery to discharge mode during Peak period to power the load with the battery. 43 44 Delayed Charging Mode • Suitable for areas with on-grid power output restrictions. • Setting a peak power limit allows the PV power that exceeds the on-grid limit to be used to charge the battery; or setting a PV charging time period, during which the PV power is utilized to charge the battery. 45 46 47 Demand Management Model • It is mainly applicable to industrial and commercial scenarios. • When the total power consumption of the load exceeds the power quota within a short period of time, battery discharge can be used to reduce the amount of power consumption exceeding the quota. • When the SOC of both battery strings in the inverter falls below the reserved SOC for demand management, the system purchases electricity from the grid based on the time period, load electricity consumption, and peak purchase limit. When the SOC of only one battery string in the inverter falls below the reserved SOC for demand management, the system purchases electricity from the grid based on load electricity consumption and the peak purchase limit. 48 Off-grid Mode NOTICE Please do not operate the energy storage system in pure off-grid mode for long periods of time, otherwise there is a risk of over-discharge when the battery cannot be charged in low temperature or low light conditions. When the power grid fails, the inverter switches to off-grid mode. • During the day, PV power generation is prioritized for supplying power to loads, and excess power is used to charge batteries. • Nighttime battery discharge powers the load to ensure uninterrupted power supply to the backup load. • Off-grid SOC recovery: After the system goes offline, the battery gradually recovers to the minimum SOC through photovoltaic power generation or other power 49 generation methods. 3.5 Features AFCI The inverter is equipped with an integrated AFCI circuit protection device for detecting arc faults (arc fauIt) and quickly cutting off the circuit when detected, thus preventing electrical fires. Reasons for the occurrence of electric arcs: • Damaged connectors in the PV system. • Wrong connected or broken cables. • Aging connectors and cables. 50 Troubleshooting: 1. When the inverter detects an arc, the type of barricade can be viewed through the inverter display or the App. 2. If the inverter triggers a fault less than 5 times in 24 hours, wait 5 minutes and the machine will automatically resume grid-tied machine protection. After the 5th electric arc fault, the inverter can operate normally after the fault is solved. For more details, refer to the SolarGo APP User Manual. Load control Inverter dry contact control port to support connection of additional contactors for controlling loads on or off. Supports domestic loads, heat pumps, etc.. The load control methods are as follows: • Time Control: Set the time to control the load to turn on or off, and the load will be automatically turned on or off in the set time period. • Switch Control: When the control mode is selected as ON, the load will be turned on; when the control mode is set to OFF, the load will be turned off. • BACK-UP LOAD CONTROL: The inverter has a built-in relay dry contact control port to control whether the load is turned off or not via a relay. In off-grid mode, the load connected to the relay port can be turned off if the overloaded battery SOC value at the BACK-UP end is detected to be lower than the battery off-grid protection setting. Rapid Shutdown (RSD) In the rapid shutdown system, the transmitter is used in conjunction with a receiver to achieve the rapid shutdown of the system. The receiver maintains the component output by receiving signals from the transmitter. The transmitter can be external or built into the inverter. In the event of an emergency, the component can be shut down by enabling an external trigger to stop the transmitter. • External Transmitter Transmitter Model: GTP-F2L-20, GTP-F2M-20 https://www.goodwe.com/Ftp/Installation-instructions/RSD2.0-transmitter.pdf Receiver Model: GR-B1F-20, GR-B2F-20 https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_QuickInstallation-Guide-POLY.pdf • Built-in Transmitter External trigger device: AC side circuit breaker ○ ○ ○ 51 ○ Receiver Model: GR-B1F-20, GR-B2F-20 https://en.goodwe.com/Ftp/EN/Downloads/User%20Manual/GW_RSD-20_QuickInstallation-Guide-POLY.pdf 52 4 Check and Storage 4.1 Check Before Receiving Check the following items before accept. 1. Check the outer packing box for damage, such as holes, cracks, deformation, and other signs of equipment damage. Do not unpack the package and contact the supplier as soon as possible if any damage is found. 2. Check the product model. If the product model is not what you requested, do not unpack the product and contact the supplier. 4.2 Deliverables WARNING Check the deliverables for correct model, complete contents, and intact appearance. Contact the supplier as soon as possible if any damage is found. 4.2.1 Inverter Deliverables Component Description Component Description Inverter x 1 Mounting plate x 1 Expansion screws x 4 Grounding screw x 1 Protective grounding terminal x 1 Battery power connection terminal x 2 53 Component Description Component Description PV DC terminal • GW3000-ES-C10、 GW3000-ES-C11 x 1 • Others x 2 Smart dongle x 1 2PIN terminal x1 6PIN terminal x 2 AC terminal x 1 Provided on an actual basis. Battery Connector x 1 PIN communication terminal x 20 AC PIN terminal x 10 CT x 1 Documents x 1 Lead-acid battery temperature sensor cable fixing sticker x 2 One-piece screwdriver x 1 Lead-acid battery temperature sensor cable x 1 BMS communication cable x 1 54 Component Description Component Description AC unlocking tool x1 4.2.2 Batteries Deliverables 4.2.2.1 LX A5.0-10 Component Description Component Description Battery module x1 (25--8) OT terminal x4 (5.5--5) OT terminal x 2 M5 grounding screw x2 Warning label x 1 Terminal resistor x 1 Electrical Label x 1 M4*8 screw x 8 (optional) Provided when selecting bracket installation method. Battery bracket x 2 (optional) Provided when selecting bracket installation method. Documents x 1 Negative power line (optional) x 1 55 Component Description Component Description Positive power line (optional) x 1 Grounding cable (optional) x 1 Communication cable (optional) x 1 Decorative cover (optional) x 1 Mounting plate bracket expansion screws (optional) x 4 Mounting plate (optional) x 1 Bracket (optional) x 1 Bracket screws (optional) x 4 4.2.2.2 LX A5.0-30 Componen t Description Component Description Battery module x1 Terminal resistor x 1 When connecting to a third-party busbar, this terminal resistor needs to be installed. • M5 OT terminal x 2: Recommended for 10mm2 cable • M8 OT terminal x 4: Recommended for 50mm2 cable • M10 OT terminal x 2: Recommended for 70mm2 cable M5*12 grounding screw x 2 56 Componen t Description Component Description Bracket x 2 For wall-mounted installation M6* 70 Expansion bolts x 4 For wall-mounted installation M5*12 grounding screw x2 For wall-mounted installation Line drawing template x 1 For wall-mounted installation Battery bracket x 2 (optional) For floor-mounted installation M4*8 screw x 8 For floor-mounted installation Documents x 1 Negative power line (optional) x 1 Positive power line (optional) x 1 Grounding cable (optional) x1 Communication cable (optional) x 1 Decorative cover (optional) x1 4.2.2.3 LX U5.0-30 Component Description Component Battery module x1 Description Cover x 1 57 Component Description Component Mounting plate x 1 Description Expansion bolt x 2 • 35-8 OT terminal x 4: Recommended for connecting 25mm2 or 35mm2 cables • 50-8 OT terminal x 4: Recommended for 50mm2 Locking bracket x 2 cable • 70-10 OT terminal x 2: Recommended for 70mm2 cable 14--5 Grounding terminal x 2 M5 Screw x 7 M10 Expansion bolt x 6 Cable harness fixing plate x 1 Power connector protect cover x 2 Documents x 1 Terminal resistor x 1 - - 58 4.2.3 Busbar Deliverables 4.2.3.1 BCB-11-WW-0 (Optional) Component Description Component 360A Manifold box x 1 (25--8) OT terminal x 18 (70--10) OT terminal x 2 Description M6 Expansion bolts x 4 - - Component Description 4.2.3.2 BCB-22-WW-0 Component Description 360A Manifold box x 1 (25--8) OT terminal x 36 (70--10) OT terminal x 6 M6 Expansion bolts x 4 - - 4.2.3.3 BCB-32-WW-0, BCB-33-WW-0 (Optional) Component Description Component 360A Manifold box x 1 Description M6 Expansion bolt x 4 59 Component Description Component Description (50--8) OT terminal x 30 (70--10) OT terminal x 6 - - 4.2.4 Smart Meter Deliverables 4.2.4.1 GMK110 Compone nt Compone nt Description Description Smart Meter and CT x 1 RS485 communication terminals x 1 Voltage input side terminal x 1 PIN terminal x 4 Screw driver x 1 Documents x 1 4.2.4.2 GM330 Component Description Component Description Smart Meter x1 2 PIN terminal x1 PIN terminal x 6 7 PIN terminal x1 60 Component Description Component Screw driver x 1 Description Documents x 1 4.2.5 Smart dongle 4.2.5.1 WiFi/LAN Kit-20 Component Description Component Smart dongle x 1 Description Documents x 1 4.2.5.2 4G Kit-CN-G20, 4G Kit-CN-G21 Component Description Component Smart dongle x 1 Description Documents x 1 4.2.5.3 Ezlink3000 Component Description Compone nt Smart dongle x1 Description LAN cable connector x 1 61 Component Description Compone nt Description Unlock tool x1 Some modules need to be removed with the tool. If the tool is not provided, remove the module by pressing the unlock button on the module Documents x1 4.3 Storage If the equipment is not put into use immediately, please store it according to the following requirements. After long-term storage, the equipment must be inspected and confirmed by professionals before it can be used again. 1. If the storage time of Inverter exceeds two years or the idle time after Installation exceeds six months, it is recommended to undergo inspection and testing by professionals before being put into operation. 2. To ensure the optimal electrical performance of the internal electronic components in the Inverter, it is recommended to power it on every 6 months during storage. If it has not been powered on for more than 6 months, a professional inspection and testing are advised before putting it into operation. 3. To ensure the performance and service life of the Battery, it is recommended to avoid prolonged idle storage. Extended storage may lead to deep Discharge of the Battery, causing irreversible chemical degradation, capacity decay, or even complete failure. Timely usage is advised. If long-term storage of the Battery is necessary, please follow the maintenance requirements below: Battery Model Initial SOC Range for Battery Storage Recommen ded Storage Temperatur e 30%~40% 0~35℃ LX A5.0-10 n*LX A5.010 62 Charging Discharge Maintenance Cycle[1] -20~0℃, ≤1 month 0~35℃, ≤6 months Battery Maintenance Method[2] LX A5.0-30 30%~40% 0~35℃ -20~35℃, ≤12 months 35~45℃, ≤6 months -20~0℃, ≤1 month LX U5.0-30 30%~40% 0~35℃ 0~35℃, ≤6 months 35~40℃, ≤1 month For maintenanc e methods, please consult the dealer or after-sales service center. NOTICE [1] The storage time is calculated from the SN date on the Battery outer packaging. After exceeding the storage cycle, charging Discharge maintenance is required. (Battery maintenance time = SN date + charging Discharge maintenance cycle). For the method to view the SN date, refer to: SN code meaning. [2] After the battery maintenance is qualified, if there is a Maintaining Label on the outer box, please update the maintenance information on the Maintaining Label. If there is no Maintaining Label, please record the maintenance time and battery SOC yourself and keep the data properly for easy maintenance record storage. Packaging requirements: Ensure the outer packaging box is not dismantle, and the desiccant inside the box is not missing. Environmental requirements: 1. Ensure the Storage is placed in a shaded area to avoid direct sunlight. 2. Ensure the storage environment is clean, with an appropriate temperature range and no condensation. If condensation is observed on the equipment, do not operate the device. 3. Ensure that Storage is kept away from flammable, explosive, and corrosive materials. Stack requirements: 1. Ensure the Inverter stack height and orientation are positioned according to the instructions on the packaging label. 63 2. Ensure there is no risk of tipping after Inverterstack. 64 5 Installation DANGER Install and connect the equipment with the deliverables included in the package. Otherwise, the manufacturer shall not be liable for the damage. 5.1 System Installation and Commissioning Procedure 5.2 Installation Requirements 5.2.1 Installation Environment Requirements 1. Do not install the equipment in a place near flammable, explosive, or corrosive materials. 2. The temperature and humidity at the installation site should be kept within the appropriate range. 3. Do not install the equipment in a place that is easy to touch, especially within children’s reach. 65 4. When the equipment is working, its temperature may exceed 60 ℃. Do not touch the surface to avoid burn. 5. Install the equipment in a sheltered place to avoid direct sunlight, rain, and snow. Build a sunshade if it is needed. 6. The place to install the equipment shall be well-ventilated for heat radiation and large enough for operations. 7. Check the protection rating of the equipment and ensure that the installation environment meets the requirements. The inverter, battery system, and smart dongle can be installed both indoors and outdoors, but the smart meter can only be installed indoors. 8. Install the equipment at a height that is convenient for operation and maintenance, electrical connections, and checking indicators and labels. 9. The altitude to install the inverter shall be lower than the maximum working altitude of the system. 10. Consult the manufacturer before installing the equipment outdoors in salt affected areas. A salt-affected area refers to the region within 500 meters offshore, and will be related to the sea wind, precipitation and topography. 11. Install the equipment away from electromagnetic interference. If there is any radio or wireless communication equipment below 30MHz near the equipment, you have to: • Inverter: add a multi-turn winding ferrite core at the AC output cable of the inverter, or add a low-pass EMI filter. Or the distance between the inverter and the wireless EMI equipment should be more than 30m. • Other equipment: the distance between the equipment and the wireless EMI equipment should be more than 30m. 12. The length of the DC cable and communication cable between the battery and the inverter must be less than 3m. Please ensure that the installation distance between the inverter and the battery meets the cable length requirements. NOTICE If installed in an environment below 0℃, the battery will not be able to continue charging to restore energy after being discharged, resulting in undervoltage protection. • LX A5.0-30, LX U5.0 -30: Charging temperature range: 0 < T ≤ 55°C; Discharging temperature range: -20 < T ≤ 55°C • LX A5.0-10: Charging temperature range: 0 < T ≤ 55°C; Discharging temperature range: 10 < T ≤ 55°C 66 5.2.2 Installation Space Requirements Reserve enough space for operations and heat dissipation when installing the system. When using CAT7 communication cables among inverters, the maximum 67 distance can reach 10 meters, while using CAT5 communication cables, the maximum distance can reach 5 meters. 5.2.3 Tool Requirements 68 NOTICE The following tools are recommended when installing the equipment. Use other auxiliary tools on site if necessary. Installation Tools Tool Description Tool Types Description Diagonal pliers RJ45 crimping tool Wire stripper YQK-70 hydraulic pliers Adjustable wrench PV connector tool A-2546B Impact drill (drill bits Φ8mm) Torque wrench M4, M5, M8 Rubber hammer Socket wrench set Marker Multimeter Range≤600V 69 Tool Description Tool Types Description Heat shrink tube Heat gun Cable tie Vacuum cleaner Personal Protective Equipment Tool Description Tool Types Description Insulating gloves and safety gloves Dust mask Goggles Safety shoes 5.3 Equipment Handling CAUTION 70 • Operations such as transportation, turnover, installation and so on must meet the requirements of the laws and regulations of the country or region where inverters are installed. • Move the equipment to the site before installation. Follow the instructions below to avoid personal injury or equipment damage. 1. Please equip the corresponding personnel according to its weight, so that the equipment does not exceed the maximum weight that the personnel can carry to avoid personnel injuries. 2. Wear safety gloves to avoid personal injury. 3. Keep balance to avoid falling down when moving the equipment. 5.4 Installing the Inverter CAUTION • When drilling, ensure the hole position avoids water pipes, cables, etc. inside the wall to prevent danger. • When punching holes, wear goggle and a dust mask to prevent dust from inhalation entering the respiratory tract or falling into the eyes. • Ensure the inverter is securely mounted to prevent falling and causing injury. 1. Place the mounting plate horizontally on the wall and use a marker to mark the drilling positions. 2. Use hammer drill for punching. 3. Use expansion bolt to secure the Inverter mounting plate bracket to the wall. 4. Mount the Inverter onto the backplate. After mounting, secure the backplate and Inverter using screw to ensure the Inverter Installation is stable. 71 5. 5.5 Installing the Battery System WARNING • Ensure that the battery system is installed vertically and securely. When using the locking bracket, the bracket should be vertically attached to the wall and the surface of the battery system. • Cover the equipment with a cardboard to prevent foreign matters when drilling holes. Otherwise, the system may be damaged. • After marking the drilling position with a marker pen, the battery system needs to be moved away to avoid equipment damage caused by the impact drill when drilling. LX A5.0-30: Stacking installation NOTICE Up to 6 batteries can be stacked. 72 1. Place the battery vertically, and remove the battery handles. 2. Install brackets on the battery, and secure them with screws. 3. Place the battery flat and stack multiple batteries. Ensure that the locating pin is inserted into the locating hole. LX A5.0-30: Cabinet Installation NOTICE • It is recommended to install it in a 19-inch standard cabinet with a length * width of 600*800mm and above, and the height should be determined based on the thickness of the battery (133mm) and above. • For cabinet installation, electrical labels and warning labels need to be attached to any position of the front panel of the battery (these labels are shipped as additional accessories). 1. Place the battery on the guide rail of the rack and secure the battery to the rack with screws from the handle. 、 73 LX A5.0-30: Wall-mounted Installation 1. Determine the drilling position with installation positioning cardboard and marker pen. 2. Use an impact drill to drill holes. 3. Install the battery brackets. 4. Install the battery on the brackets and use screws to secure the battery. 74 LX A5.0-10: Stacking installation NOTICE Up to 6 batteries can be stacked for floor-mounted installation. 1. Place the battery vertically. 2. Install the bracket on the bottom of the battery, and then remove the handles from the battery. 3. Install another bracket on the battery. 4. Use screws to tight the brackets, then place the battery flatly. 5. Stack multiple batteries. • Insert locating pin on the bracket into locating hole. Align the positioning pins on the lower battery bracket with the positioning holes on the upper battery bracket. 75 LX A5.0-10: Cabinet Installation NOTICE • It is recommended to use a 19-inch standard cabinet with physical length and width of 600*800mm and above. The height can be chosen according to the number of batteries in parallel. • For cabinet installation, electrical labels and warning labels need to be attached to any position of the front panel of the battery (these labels are shipped as additional accessories). 1. Stick the electrical label and warning label to the position of the front panel of any battery. 2. Place the battery on the guide rail of the rack and secure the battery to the rack with screws from the handle. 76 LXU 5.0--30: Floor-mounted Installation LXU 5.0--30: Wall-mounted Installation 77 5.5.1 LX A5.0-30 LX A5.0-30: Stacking installation NOTICE Up to 6 batteries can be stacked. 1. Place the battery vertically, and remove the battery handles. 2. Install brackets on the battery, and secure them with screws. 3. Place the battery flat and stack multiple batteries. Ensure that the locating pin is inserted into the locating hole. 78 LX A5.0-30: Cabinet Installation NOTICE • It is recommended to install it in a 19-inch standard cabinet with a length * width of 600*800mm and above, and the height should be determined based on the thickness of the battery (133mm) and above. • For cabinet installation, electrical labels and warning labels need to be attached to any position of the front panel of the battery (these labels are shipped as additional accessories). 1. Place the battery on the guide rail of the rack and secure the battery to the rack with screws from the handle. 79 LX A5.0-30: Wall-mounted Installation 1. Determine the drilling position with installation positioning cardboard and marker pen. 2. Use an impact drill to drill holes. 3. Install the battery brackets. 4. Install the battery on the brackets and use screws to secure the battery. 80 5.5.2 LX A5.0-10 LX A5.0-10: Stacking installation NOTICE Up to 6 batteries can be stacked for floor-mounted installation. 1. Place the battery vertically. 2. Install the bracket on the bottom of the battery, and then remove the handles from the battery. 3. Install another bracket on the battery. 4. Use screws to tight the brackets, then place the battery flatly. 5. Stack multiple batteries. • Insert locating pin on the bracket into locating hole. Align the positioning pins on the lower battery bracket with the positioning holes on the upper battery bracket. 81 LX A5.0-10: Cabinet Installation NOTICE • It is recommended to use a 19-inch standard cabinet with physical length and width of 600*800mm and above. The height can be chosen according to the number of batteries in parallel. • For cabinet installation, electrical labels and warning labels need to be attached to any position of the front panel of the battery (these labels are shipped as additional accessories). 1. Stick the electrical label and warning label to the position of the front panel of any battery. 2. Place the battery on the guide rail of the rack and secure the battery to the rack with screws from the handle. 82 LX A5.0-10: Wall-mounted Installation 5.5.3 LX U5.0-30 LX U5.0-30: Floor-mounted Installation 83 LX U5.0-30: Wall-mounted Installation 5.6 Installing the Smart Meter 84 WARNING In areas at risk of lightning, if the meter cable exceeds 10m and the cables are not wired with grounded metal conduits, you are recommended to use an external lightning protection device. GMK110 GM330 85 6 System Wirings DANGER • The erection, routing, and connection of cables must be in compliance with local laws and regulations. • Perform electrical connections in compliance with local laws and regulations, including operations, cables, and component specifications. • Disconnect the DC switches and the AC output switches to power off the equipment before any electrical connections. Do not work with power on. Otherwise, an electric shock may occur. • Tie the same type cables together, and place them separately from cables of different types. Do not place the cables entangled or crossed. • If the cable bears too much tension, the connection may be poor. Reserve a certain length of the cable before connecting it to the inverter cable port. • Make sure that the cable conductor is in full contact with the terminal and the cable insulation part is not crimped with the terminal when crimping the terminal. Otherwise, the device may not be able to work properly, or the connection may be unreliable during working, which may cause terminal block damage, etc.. NOTICE • Wear personal protective equipment like safety shoes, safety gloves, and insulating gloves during electrical connections. • All electrical connections should be performed by qualified professionals. • Cable colors in this document are for reference only. The cable specifications shall meet local laws and regulations. • For parallel systems, follow the safety precautions in the user manuals of related products in the system. 6.1 System Wiring Electrical Block Diagram NOTICE 86 • N and PE wiring of ON-GRID and BACK-UP ports of the inverter are different according to the regulation requirements of different regions. Refer to the specific requirements of local regulations. • The inverter features built-in relays for the ON_GRID and BACK_UP AC ports. When the inverter is in off-grid mode, the built-in ON_GRID state relay is disconnected; when the inverter is in on-grid operation mode, the built-in ONGRID relay is connected. • When the inverter is powered on, the BACK-UP AC port is energized. Power off the inverter first if maintenance is required on the BACK-UP loads. Otherwise, it may cause electric shock. N and PE cables are separately wired in the Main Panel NOTICE • Ensure that the grounding of BACK-UP is correctly tightened. Otherwise, the BACK-UP function may be abnormal in case of grid failure. • The following diagram is applicable to areas except Australia or New Zealand. 87 6.2 Detailed System Wiring Diagram 6.2.1 Detailed System Wiring Diagram for Single Inverter GM330 and other meters that meet the requirements can also be used in single inverter scenarios. Only the recommended types are shown here: With built-in smart meter 88 Use GM110 in the system 89 6.2.2 Detailed System Wiring Diagram for Parallel System • In parallel scenarios, the inverter connected to the Ezlink and smart meter is considered as the master inverter, while all the others are slave inverters. Do not connect any smart dongle to the slave inverters. • Generator, large loads and grid-tied PV inverter are not supported in parallel system. • The following diagram mainly introduces parallel connections. For other port connections, refer to the single system. Use GM330 in the system 90 Use GM110 in the system 91 6.3 Preparing Materials WARNING 92 • Do not connect loads between the inverter and the AC switch that is directly connected to the inverter. • Install one AC output circuit breaker for each inverter. Multiple inverters cannot share one AC circuit breaker. • An AC circuit breaker shall be installed on the AC side to make sure that the inverter can be safely disconnected with the grid when an exception happens. Select the appropriate AC circuit breaker in compliance with local laws and regulations. • When the inverter is powered on, the BACK-UP AC port is energized. Power off the inverter first if maintenance is required on the BACK-UP loads. Otherwise, it may cause electric shock. • For cables used in the same system, it is recommended that the conductor material, cross sectional area, length, etc. of the cables should be consistent. The AC cable for BACK-UP port of each inverter ○ ○ The AC cable for ON-GRID port of each inverter ○ The power cable between inverter and battery ○ The power cable between batteries ○ The power cable between inverter and busbar ○ The power cable between battery and busbar 6.3.1 Preparing Breakers No. Circuit breaker Recommended specifications Comment 1 • ON-GRID circuit breaker • BACK-UP load breaker • GEN breaker • GW3000-ES-C10, GW3000-ES-C11, GW3600-ES-C10: nominal current ≥40A, nominal voltage ≥230V • GW5000-ES-C10, GW6000-ES-C10: nominal current ≥50A, nominal voltage ≥230V Prepared by customers. 93 No. Circuit breaker Recommended specifications Comment Optional in compliance with local laws and regulations 2 Battery breaker • GW3000-ES-C10: nominal current ≥90A, nominal voltage ≥60V • GW3000-ES-C11: nominal current ≥175A, nominal voltage ≥60V • GW3600-ES-C10: nominal current ≥115A, nominal voltage ≥60V • GW5000-ES-C10: nominal current ≥150A, nominal voltage ≥60V • GW6000-ES-C10: nominal current ≥175A, nominal voltage ≥60V Prepared by customers. Optional in compliance with local laws and regulations 3 RCD • Type A • ON-GRID RCD: 300mA Prepared by customers. • BACK-UP RCD: 30mA 6.3.2 Preparing Cables No. Cable 1 Inverter PE cable Recommended specifications • Single-core outdoor copper cable • Conductor cross-sectional area: 6mm2 94 Acquisition method Prepared by customers No. Cable Recommended specifications • Single-core outdoor copper cable 2 Battery PE cable • Conductor cross-sectional area: • LX A5.0-10: 4mm²--6mm² • LX A5.0-30: 10mm² • LX U5.0-30: 10mm² 3 PV DC cable • Commonly used outdoor photovoltaic cable • Conductor cross-sectional area: 4 6mm² • Outer diameter: 4.8mm--6.3mm Acquisition method • Prepared by customers • LX A5.0-30, LX A5.0-10: Accessory acquisition (optional) Prepared by customers • Single-core outdoor copper cable • Wiring requirements for inverter battery ports: Conductor cross-sectional area: 25 -35mm² • Prepared by Outer diameter: 8--13mm customers • Requirements for cables between • LX U5.0-30: battery and busbar: Supports LX A5.0-30, cross sectional area of purchase from conductor: 50mm2 GoodWe LX A5.0-10, LX U5.0-30, cross • LX A5.0-30, LX sectional area of conductor: A5.0-10: 25mm2 Accessory • Requirements for cables between acquisition batteries: (optional) LX A5.0-30, cross sectional area of conductor: 50mm2 LX A5.0-10, LX U5.0-30, cross sectional area of conductor: 25mm2 ○ ○ ○ 4 Battery DC cable ○ ○ ○ 95 No. Cable Recommended specifications Acquisition method AC cable • AC input and output cables of inverter (BACKUP/GRID): Conductor cross-sectional area: 10mm²/ 8AWG Outer diameter of multi-core outdoor copper cable: 15mm-18mm Outer diameter of single-core outdoor copper cable: 5.5mm-7mm • Generator power cable (GEN): Conductor cross-sectional area: 10mm²/ 8AWG Multi-core outdoor copper cable outer diameter: 14mm--17mm Outer diameter of single-core outdoor copper cable: 5.5mm-7mm Prepared by customers ○ ○ ○ 5 ○ ○ ○ 6 Smart meter power cable 7 Battery communication cable 8 Smart meter RS485 communication cable • Outdoor copper cable • Conductor cross-sectional area: 1mm² Communication between the combiner box and the battery, as well as between batteries, requires the use of CAT 5E or higher specification standard shielded Ethernet cables and RJ45 shielded connectors. • Shielded twisted pair cable • Conductor cross-sectional area: 0.2mm²--0.4mm² 96 Prepared by customers • Prepared by customers • LX A5.0-10, LX A5.0-30: Accessory acquisition (optional) Prepared by customers No. Cable Recommended specifications Acquisition method 9 Communicatio n cable for parallel connected inverters WiFi/LAN Kit-20 Communicatio ns CAT 5E and above standard shielded network cable and RJ45 shielded connector Prepared by customers 10 Remote shutdown communication line Rapid shutdown communication line NS Protection communication line • Copper core twisted pair cable • Conductor cross-sectional area: 0.2mm²--0.4mm² Prepared by customers 6.4 Connecting the PE cable WARNING • The PE cable connected to the enclosure of the inverter cannot replace the PE cable connected to the AC output port. Make sure that both of the two PE cables are securely connected. • Make sure that all the grounding points on the enclosures are equipotentially connected when there are multiple inverters. • To improve the corrosion resistance of the terminal, you are recommended to apply silica gel or paint on the ground terminal after installing the PE cable. • Connect the PE cable first before installing the equipment. Disconnect the PE cable before dismantling the equipment. 97 Inverter Battery 6.5 Connecting the PV Cable DANGER 98 • Do not connect the same PV string to multiple inverters at the same time. Otherwise, the inverters may be damaged. • Confirm the following information before connecting the PV string to the inverter. Otherwise, the inverter may be damaged permanently or even cause fire and cause personal and property losses. 1. Make sure that the max short circuit current and the maximum input voltage per MPPT are within the permissible range. 2. Make sure that the positive pole of the PV string connects to the PV+ of the inverter. And the negative pole of the PV string connects to the PV- of the inverter. WARNING • The PV strings cannot be grounded. Ensure the minimum insulation resistance of PV string to the ground meets the minimum insulation resistance requirements before connecting the PV string to the inverter (R=maximum input voltage/ 30mA). • Ensure the DC cables are connected tightly, securely and correctly. • Measure the positive and negative terminals of the DC cable using a multimeter to avoid reverse polarity connection. Also, the voltage should be within the permissible range. NOTICE The two input strings per MPPT should contain the same number of identical PV modules with the same tilt and angle to ensure the best efficiency. 99 6.6 Connecting the Battery Cable DANGER • In a single inverter system, do not connect the same battery pack to multiple inverters, which may cause inverter damage. • It is forbidden to connect loads between the inverter and the battery. • When connecting battery cables, use insulated tools to prevent accidental electric shock or short circuit to the batteries. • Ensure that the open circuit voltage of the battery is within the permissible range of the inverter. • Install a DC breaker between the inverter and the battery in compliance with local laws and regulations. Battery system wiring diagram 100 101 LXA5.0-30: Hand-to-hand connection • The battery system supports a maximum working current of 160A, working power of 8kW, and it consists of a maximum of 1 inverter, and 30 batteries. 102 LXA5.0-30: Using with busbar BCB-22-WW-0 • The battery system supports a maximum working current of 160A, working power of 8kW, and it consists of a maximum of 6 inverter, and 6 batteries. 103 LXA5.0-30: Using with busbar BCB-32-WW-0 • The battery system supports a maximum working current of 160A, working power of 8kW, and it consists of a maximum of 6 inverter, and 15 batteries. 104 LXA5.0-30: Using with third-party busbar • The nominal charging current of a single battery is 60A; and the nominal discharging current is 100A; the maximum charging current is 90A; the maximum discharging current is 150A. A maximum of 30 batteries can be connected in parallel in one system. 105 LX A5.0-10: Hand-to-Hand Connection • The nominal charging and discharging current of a single battery is 60A. • The battery system supports a maximum working current of 160A, working power of 8kW, and it consists of a maximum of 1 inverter, and 2 batteries. 106 LX A5.0-10: Using with busbar BCB-22-WW-0 • The nominal charging and discharging current of a single battery is 60A. • The battery system supports a maximum working current of 360A, working power 107 of 18kW, and it consists of a maximum of 3 inverters, and 6 batteries. LX A5.0-10: Using with busbar BCB-22-WW-0 • The nominal charging and discharging current of a single battery is 60A. • The battery system supports a maximum working current of 160A, working power of 8kW, and it consists of a maximum of 6 inverter, and 12 batteries. 108 LX A5.0-10: Using with third-party busbar • The nominal charging and discharging current of a single battery is 60A. • The battery system supports a maximum working current of 900A, working power of 45kW, and 15 batteries. 109 LX U5.0-30: Hand-to-Hand Connection 110 LX U5.0-30: When the battery quantity is less than or equal to 6, and the busbar BCB22-WW-0 is used, the wiring diagram is as follows: LX U5.0-30: When the battery quantity is less than or equal to 8, and the busbar BCB32-WW-0 is used, the wiring diagram is as follows: 111 LX U5.0-30: When the battery quantity is less than or equal to 15, and the busbar BCB-33-WW-0 is used, the wiring diagram is as follows: 112 LX U5.0-30: When the battery quantity is less than or equal to 8, and a third-party busbar is used, the wiring diagram is as follows: LX U5.0-30: When the battery quantity is larger than 8, and a third-party busbar is used, the wiring diagram is as follows: LX A5.0-30 Communication Port Definition 113 PIN COM1 COM2 Description 1 - - 2 - - 3 Parallel OUT+ Parallel OUT+ Parallel operation communication port 4 CAN_1H CAN_1H 5 CAN_1L CAN_1L Connect the inverter communication port or battery parallel communication port 6 Parallel OUT2+ Parallel OUT2+ 7 - - 8 Parallel OUT- Parallel OUT- Reserved Parallel interlock communication port Reserved Parallel operation communication port LX A5.0-10 Communication Port Definition PIN COM1 COM2 1 - - 2 - - 3 Parallel OUT+ Parallel OUT+ 4 CAN_1H CAN_1H 5 CAN_1L CAN_1L 6 - - 7 - 8 Parallel OUT- Description Reserved Parallel operation communication port Connect the inverter communication port or battery parallel communication port Reserved Parallel OUT- Parallel operation communication port LX U5.0-30 Communication Port Definition PIN COM1 COM2 1 RS485A RS485A 2 RS485B- RS485B- 3 Parallel OUT+ Parallel OUT+ Parallel operation communication port 4 CAN_H CAN_H 5 CAN_L CAN_L Connect the inverter communication port or battery parallel communication port 6 Parallel OUT2+ Parallel OUT2+ Parallel operation communication port 7 - - Description Reserved Reserved 114 8 Parallel OUT- Parallel OUT- Parallel operation communication port 6.6.1 Connecting the Power Cable between the Inverter and Battery WARNING • Measure the positive and negative terminals of the DC cable using a multimeter to avoid reverse polarity connection. Also, the voltage should be within the permissible range. • Connect the battery cables to the corresponding terminals such BAT+, BAT- and grounding ports correctly. Otherwise it will cause damage to the equipment. • Ensure that the whole cable cores are inserted into the terminal holes, and no part of the cable core can be exposed. • Ensure that the cables are connected securely. Otherwise it will cause damage to the inverter due to overheat during its operation. • Do not connect one battery pack to more than one inverter at the same time. Otherwise, it may cause damage to the inverter. Overview of inverter and battery power cable 115 Making the inverter power cable 116 Inverter battery cover disassembly (optional) Battery power cable manufacturing (LX A5.0-10 and LX A5.0-30) Battery power cable manufacturing (LX U5.0-30) 117 6.6.2 Connecting the Communication Cable between the Inverter and Battery NOTICE It is recommended to use the included BMS communication cable in the package of the inverter. If the included communication cables do not meet the requirement, prepare shielded network cables and RJ connectors by yourself to make the cable. Only crimp PIN4 and PIN5 of the connector when making the cable, otherwise the communication may fail. Instructions for BMS communication connection between inverter and battery Inverter port Connected to the battery port Port definition 118 Description BMS(CAN) COM1 • The inverter communicates with the battery through CAN. • Connect the BMS port of the inverter to the COM1 port of the battery. 4: CAN_H 5: CAN_L NOTICE 119 • When connecting the lead-acid battery temperature sensor cable, it is recommended to connect the temperature sensor cable at a location with poor heat dissipation. For example, when lead-acid batteries are placed side by side, the sensor should be fixed on the lead-acid battery located in the middle. • To better protect the battery cell, a temperature sampling cable must be installed, and it is recommended to place the battery in a well-ventilated environment. 6.7 Connecting the AC Cable WARNING 120 • The residual current monitoring unit (RCMU) is integrated into the inverter to avoid that the residual current exceeds the limit. The inverter will disconnect with the utility grid quickly once it found the residual current exceeds the limit. • When wiring, ensure that the AC cable is completely matched with the "BACKUP", "ON-GRID", "GEN", and grounding ports of the AC terminal. Incorrect cable connection will lead to equipment damage. • Ensure that the whole cable cores are inserted into the terminal holes, and no part of the cable core can be exposed. • Ensure that the insulation board is inserted into the AC terminal tightly. • Ensure that the cables are connected securely. Otherwise it will cause damage to the inverter due to overheat during its operation. Inverter AC cover disassembly (optional) 121 6.8 Connecting the Meter Cable NOTICE • Contact the manufacturer for additional smart meters if multiple inverters are connected. • Ensure that the CT is connected in the correct direction and phase sequences, otherwise the monitoring data will be incorrect. • Ensure all cables are connected correctly, tightly, and securely. Inappropriate wiring may cause poor contacts and damage the equipment. • In areas at risk of lightning, if the meter cable exceeds 10m and the cables are not wired with grounded metal conduits, you are recommended to use an external lightning protection device. Wiring of GMK110 NOTICE 122 • Outer diameter of the AC cable should be smaller than the holes diameter of the CT, so that the AC cable can be threaded through the CT. • To ensure accurate current detection, the CT cable is recommended to be shorter than 30m. • Do not use network cable as the CT cable, otherwise the smart meter may be damaged due to high current. • The CTs vary slightly in dimensions and appearance among different models, but they are installed and connected in the same way. Connection steps Wiring of GMK110 123 Connection steps Installing the CT (Type I) Installing the CT (Type II) 124 6.9 Connecting the Inverter Communication Cable NOTICE • The communication functions are optional. Connect the cables based on actual needs. • The inverter supports parameter setting via Bluetooth nearby. It also supports connecting to mobile phones or WEB interfaces through communication modules such as WiFi, LAN and 4G to set device-related parameters, view device operation information and error messages, and keep abreast of the system status in a timely manner. • Please use the WiFi/LAN Kit-20 module in single inverter system. When the system contains multiple inverters in parallel to the network, the master inverter needs to be installed with Ezlink3000 module for networking. • If you need to use the remote shutdown function, please turn it on in the SolarGo App after wiring is completed. • Do not turn on the remote shutdown function in the SolarGo App if the inverter is not connected to a remote shutdown device, otherwise the inverter will be unable to operate on-grid. • In a parallel system, please connect the communication cable to the master inverter to achieve the remote shutdown function, otherwise, the function will not work. Communication Description 125 Numbe Function r CT connection 1-2 port Description Connecting the CT communication cable. 126 Numbe Function r 3-4 Remote Shutdown Rapid Shutdown NS Protection Description Provides signal control port to control equipment remote shutdown or realize NS protection function. Rapid shutdown: In the rapid shutdown system, the transmitter is used in conjunction with a receiver to achieve the rapid shutdown of the system. The receiver maintains the component output by receiving signals from the transmitter. The transmitter can be external or built into the inverter. In the event of an emergency, the component can be shut down by enabling an external trigger to stop the transmitter. Remote shutdown: • In the event of an accident, the equipment can be shut down. • Remote shutdown devices need to be normally closed switches. 5-6 Load control • It supports connection with dry contact signals to achieve functions such as load control. The capacity of the DO contact is 12V DC@1A. NO/COM is a Normally Open contact. • It supports the connection of SG Ready heat pumps and controls the heat pumps through dry contact. • Supported operating modes: Operating mode 2 (signal: 0:0 ): energy saving mode. In this mode, the heat pump operates in energy saving mode. Operating Mode 3 (Signal: 0:1 ): It’s recommended to turn on. In this mode, the heat pump increases the hot water reserve while maintaining the existing operation to store heat. ○ ○ 127 Numbe Function r Generator 7-8 start/stop control control port 9-10 11-12 13-14 EMS communication port Smart meter communication Lead-acid temperature measurement port Description Access to generator control signals is supported. It’s used to connect third-party EMS devices that support RS485 communication. The third-party EMS devices are not supported to be connected in the parallel scenario. Note: It’s the same line as EMS in PAR-1 & EMS port. Connecting to external smart meters through RS485 communication is supported. Temperature sensing wire to connect lead-acid temperature measurement PAR1&EMS Parallel communication port 1 EMS communication port (PAR-1&EMS) • CAN and BUS: parallel communication ports, using CAN communication to connect other inverters in the on-grid network; using BUS to control the parallel inverters in the on-grid and off-grid status. • RS485: used to connect third-party EMS devices that support RS485 communication. The thirdparty EMS devices are not supported to be connected in the parallel scenario. PAR-2 Parallel operation communication port 2 (PAR-2) For parallel communication, using CAN communication to connect to other inverters is supported; BUS is used to control the inverters in the on-grid and off-grid status. BMSCAN Battery BMS Communications When connected to a lithium-ion battery, it is used to connect the battery system BMS communication line and supports the use of CAN signal communication. Connecting the communication cable. 128 6.10 Installing the Battery Cover 6.10.1 LX A5.0-10 129 6.10.2 LX A5.0-30 6.10.3 LX U5.0-30 130 131 7 System Commissioning 7.1 Check Before Power ON No. Check Item 1 The inverter is firmly installed in a clean place where is well-ventilated and easy to operate. 2 Ensure that the ground wire, DC wire, AC wire, communication wire, and terminal resistor are connected correctly and securely. 3 Cable ties are intact, routed properly and evenly. 4 Unused wire holes and ports should be sealed up. 5 The used cable holes are sealed. 6 The voltage and frequency at the connection point meet the inverter grid connection requirements. 7.2 Power ON WARNING • When there are multiple inverters in the system, please ensure that all slave inverter AC sides are powered on within one minute after the master inverter AC side is powered on. • Battery black start scenarios: The inverter needs to be activated by battery. ○ When there is no inverter and you need to charge and discharge the battery, etc.. • After the battery system is started, please ensure that the communication between the inverter and the battery system is normal within 15 minutes. If the inverter cannot communicate with the battery system, the battery system breaker will be disconnected automatically, and the battery system will be powered off. • When there are multiple batteries in the system, starting any one of them can start all the batteries. ○ 132 Power on process 1. Turn on the BACK-UP circuit breaker. 2. Turn on the ON-GRID circuit breaker. 3. (Optional) Turn on the GEN circuit breaker. 4. (Selected in accordance with local laws and regulations) Turn on the circuit breaker between the PV module and the inverter. 5. Turn on the DC switch of the inverter. 6. (Selected in accordance with local laws and regulations) Turn on the switch between the inverter and the battery. 7. Turn on the battery switch. 8. Turn on the battery system switch (LX A5.0-10, LX A5.0-30). Turn on the battery system integration circuit breaker (LX U5.0-30). 9. (LX U5.0-30 only) Press the battery system button. Single Inverter System 133 Parallel System 134 7.3 Indicators 7.3.1 Inverter Indicators Indicat or Status Description The inverter is starting up and in the self-check mode. The inverter is powered on and in the standby mode. BACK-UP output overload. 135 Indicat or Status Description System failure. LCD ON: The inverter is powered on and in the standby mode. LCD OFF: The inverter is powered off. The grid is abnormal, and the power supply to the BACK-UP port of the inverter is normal. The grid is normal, and the power supply to the BACK-UP port of the inverter is normal. The BACK-UP port has no power supply. The monitoring module of the inverter is resetting. The inverter fails to connect with the communication Termination. Communication fault between the communication termination and server. The monitoring of the inverter operates well. The monitoring module of the inverter has not been started yet. 7.3.2 Battery Indicators 7.3.2.1 LX A5.0-10 Normal status SOC Indicator RUN light Battery system status Green light flashes 1 time/s. 136 The battery system is in the standby mode. SOC Indicator RUN light Battery system status The SOC indicator represents the battery system's usable energy. Green light flashes 2 time/s. The battery system is in an idle state. Green light is on. The battery system is in the charging state. Green light is on. The battery system is in discharging status. The last SOC indicator flashes 1 time/s. • When 25% ≤ SOC < 50%, SOC2 flashes. • When 25% ≤ SOC < 50%, SOC2 flashes. • When 25% ≤ SOC < 50%, SOC2 flashes. • When 25% ≤ SOC < 50%, SOC2 flashes. • When 95% ≤ SOC < 100%, SOC5 flashes. Abnormal status ALM Light Red light blinks 1 time/s. Battery system status Description Battery system alarms. Once an alarm occurs, the battery system will perform a self-check. After the self-checking is complete, the battery system enters into an operation or fault mode. 137 ALM Light Red light is on. Battery system status The battery system has malfunctione d. Description Check the SOC indicator status to identify the fault type and handle the problem as recommended in the Troubleshooting section. 7.3.2.2 LX A5.0-30, LX U5.0-30 RUN light Indicator No SOC indicator shows green. The first SOC indicator shows green. The first two SOC indicators are green. The first three SOC indicators are green. All SOC indicators are green. Green light is on. Green light flashes 1 time/s. Green light flashes 3 time/s. Green flashes slowly. ALM Light Red light is on. System Status SOC=0% 0%<SOC≤25% 0%<SOC≤25% 0%<SOC≤25% 0%<SOC≤25% The battery system is working normally. The battery system is in the standby mode. The PCS communication is lost. The battery system gives an alarm, and conducts a self-check. After the selfchecking is over, it will change to normal working status or fault status. Check the SOC indicator status to identify the fault type and handle the problem as recommended in the Troubleshooting section. 138 7.3.3 Smart Meter Indicator 7.3.3.1 GMK110 Type Power light Status Steady on Description The smart meter is power on. Off The smart meter has been powered off. Communication Blinks. indicator Off Meter communication is normal. Meter communication is abnormal or has no communication. 7.3.3.2 GM330 Type Power light Communication indicator Importing or exporting indicator Status On Blinks. Off Off Description Power on, no RS485 communication. Power on, RS485 communication works properly. The smart meter has been powered off. Reserved. Blinks. Press the Reset button for more than 5 seconds, power light, buying or selling electricity indicator light flash: Reset the meter. On Blinks. Importing from the grid. Exporting to the grid. Off Exporting to the grid. Reserved. 7.3.4 Smart Dongle Indicator 7.3.4.1 WiFi/LAN Kit-20 139 Indicator Status Description On: The smart dongle has been powered on. Power light Power Off: The smart dongle is not powered on. On: Communication in WiFi mode or LAN mode is normal. Blinks 1 time: The smart dongle Bluetooth has been turned on, and is waiting for connecting to the SolarGo App. Blinks 2 times: The smart dongle is not connected to the router. Blinks 4 times: The smart dongle is communicating normally with the router, but has not been connected to the server. Blinks 6 times: The smart dongle is recognizing the connected device. Off: The software of the smart dongle is resetting or is not powered on. Communi cation indicator Indicator Color Status On Description The 100Mbps wired network is normally connected. • The Ethernet cable is not connected. Communic ation indicator in LAN Port Green Off On Yellow Blinks. Off • Fail to connect the 100Mbps wired network. • The 10Mbps wired network is normally connected. The 10/100Mbps wired network is normally connected, but no communication data is received or transmitted. The communication data is being transmitted or received. The Ethernet cable is not connected. 140 Button Reload Description Press and hold for 0.5 to 3 seconds to reset the Smart Dongle. Press and hold for 6 to 20 seconds to restore the Smart Dongle to factory settings. 7.3.4.2 4G Kit-CN-G20 & 4G Kit-CN-G21 Indicator Status Power light Communica tion indicator Button Reload Description On: The smart dongle has been powered on. Power Off: The smart dongle is not powered on. On: The smart dongle is communicating normally with the server. Blinks 2 times: Smart dongle is not connected to the base station. Blinks 4 times: The smart dongle is connected to the base station, but has not been connected to the server. Blinks 6 times: The smart dongle is disconnected from the inverter. Off: The software of the smart dongle is resetting or is not powered on. Description Short press for 0.5 to 3 seconds to restart the smart dongle. Press and hold for 6 to 20 seconds to restore the Smart Dongle to factory settings. 7.3.4.3 Ezlink3000 Indicator / Silkscree n Power light Color Status Description Blink = The smart dongle is working properly. Blue OFF = The smart dongle is powered off. 141 Indicator / Silkscree n Communi cation indicator RELOAD Color Status Green - Description ON = The smart dongle is connected to the server. Blink 2 = The smart dongle is not connected to the router. Blink 4 = The smart dongle is connected to the router, but not connected to the server. - • Short press for 3 seconds to restart the smart dongle. • Long press for 3 to -10 seconds to restore factory settings. 142 8 Rapid System Configuration 8.1 Downloading the App 8.1.1 Downloading SolarGo App Make sure that the mobile phone meets the following requirements: • Mobile phone operating system: Android 5.0 or later, iOS 13.0 or later. • The mobile phone can access the Internet. • The mobile phone supports WLAN or Bluetooth. NOTICE Once the SolarGo App has been installed, you will receive automatic notifications when updates are available. Method 1: Search SolarGo in Google Play (Android) or App Store (iOS) to download and install the app. Method 2: Scan the QR code below to download and install the App. 8.1.2 Downloading SEMS+ APP Make sure that the mobile phone meets the following requirements: • Mobile phone operating system: Android 6.0 or later, iOS 13.0 or later. • The mobile phone can access the Internet. • The mobile phone supports WLAN or Bluetooth. 143 Download Method: Method 1: Search SEMS+ in Google Play (Android) or App Store (iOS) to download and install the App. Method 2: Scan the QR code below to download and install the App. 8.2 Connecting the inverter via SolarGo NOTICE The device name varies depending on the inverter model or smart dongle type: • Wi-Fi Kit: Solar-WiFi*** • Bluetooth Module: Solar-BLE*** • WiFi/LAN Kit-20: WLA-*** • Ezlink3000: CCM-BLE***; CCM-***; *** Connect to the inverter via Bluetooth 144 Connect to the inverter via WiFi 8.3 Setting communication parameters 145 NOTICE The communication configuration interface may be different if the inverter uses different communication modes or connects different communication modules. Please refer to the actual interface. 8.3.1 Setting Privacy and Security Type I Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set the parameters. Step 2 : Set the new password for the WiFi hotspot of the communication module, and tap Save. Step 3 Open the WiFi settings of your phone and connect to the inverter’s WiFi signal (Solar WiFi***) with the new password. 146 Type II Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set the parameters. Step 2 Enable Bluetooth Stays On or WLAN Control based on actual needs. 147 No. Parameters Description Bluetooth Stays On Disabled by default. Enable the function, the bluetooth of the device will be contentious on to keep connected to SolarGo. Otherwise, the bluetooth will be off in 5 minutes, and the device will be disconnected from SolarGo. WLAN Control Disabled by default. Enable the function, the device and the SolarGo can be connected through the WLAN when they are on the same LAN. Otherwise, they cannot be connected even if they are on the same LAN. 3 Modbus-TCP Enable the function, the third party monitoring platform can access inverter through Modbus-TCP communication protocol. 4 SSH control Ezlink After enabling this function, third-party platforms can connect to and control EzLink's Linux system. 1 2 Type III Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set 148 the parameters. Step 2 : Enable Bluetooth Stays On or Login Password based on actual needs. No. 1 2 Parameters Description Bluetooth Stays On Disabled by default. Enable the function, the bluetooth of the device will be contentious on to keep connected to SolarGo. Otherwise, the bluetooth will be off in 5 minutes, and the device will be disconnected from SolarGo. Login Password Disabled by default. Enable the function, you will be prompted to enter the login password when connecting the device to SolarGo. Use the initial password and change it at the first login prompt. 8.3.2 Setting WLAN/LAN parameters 149 NOTICE When the inverter is connected to different communication modules, the communication configuration interface may be different. Please refer to the actual interface. Step 1 : Tap Home > Settings > Communication Setting > WLAN/LAN to set the parameters. Step 2 : Configure the WLAN or LAN parameters based on actual needs. No. Parameters Description 1 Network Name Only for WLAN. Select WiFi based on the actual connecting. 2 Password Only for WLAN. WiFi password for the actual connected network. 3 DHCP Enable DHCP when the router is in dynamic IP mode. Disable DHCP when a switch is used or the router is in static IP mode. 150 No. Parameters 4 IP Address 5 Subnet Mask 6 Gateway Address 7 DNS Server Description Do not configure the parameters when DHCP is enabled. Configure the parameters according to the router or switch information when DHCP is disabled. 8.3.3 Configuring APN Parameters NOTICE • Configure the SIM card information of 4G communication device. • Configure the APN parameters through the Bluetooth module or WiFi module first before using a 4G module to achieve 4G communication. Step 1: Tap Home > Settings > Communication Settings > 4G to set the parameters. Step 2: Set the region and operator based on actual needs. 151 8.3.4 Setting RS485 Parameters NOTICE Set the communication address of the inverter. For a single inverter, the address is set based on actual needs. For multi connected inverters, the address of each inverter should be different while cannot be 247. Step 1: Tap Home > Settings > Communication Settings > RS485 to set the parameters. Step 2 : Set the Modbus Address and Baud Rate base on actual situation. 8.4 Quick Setting the Basic Information 152 NOTICE • The setting page varies depending on inverter model. • The parameters will be configured automatically after selecting the safety country/region, including overvoltage protection, undervoltage protection, overfrequency protection, underfrequency protection, voltage/frequency connection protection, cosφ curve, Q(U) curve, P(U) curve, FP curve, HVRT, LVRT, etc. Tap Home > Settings > Advanced Settings > Safety Parameters to check the parameters after selecting the safety country. • The power generation efficiency is different in different working modes. Set the working mode according to the local requirements and situation. Self-use mode: The basic working mode of the system. PV power generation is used to supply power to the load first, the excess power is used to charge the battery, and the remaining power is sold to the grid. When PV power generation cannot meet the load's power demand, the battery will supply power to the load; when the battery power also cannot meet the load's power demand, the grid will supply power to the load. Back-up mode: The back-up mode is mainly applied to the scenario where the grid is unstable. When the grid is disconnected, the inverter turns to off-grid mode and the battery will supply power to the load; when the grid is restored, the inverter switches to grid-tied mode. Economic mode: It is recommended to use economic mode in scenarios when the peak-valley electricity price varies a lot. Select Economic mode only when it meets the local laws and regulations. Set the battery to charge mode during Vally period to charge battery with grid power. And set the battery to discharge mode during Peak period to power the load with the battery. Off-grid mode: suitable for areas without power grid. PV and batteries form a pure off-grid system. PV generates electricity to power the load and excess electricity charges the battery. When PV power generation cannot meet the power demand of the load, the battery will supply power to the load. Smart charging: In some countries/regions, the PV power feed into the utility grid is limited. Select Smart Charging to charge the battery using the surplus power to minimize PV power waste. Peak shaving mode: Peak shaving mode is mainly applicable to peak power limited scenarios. When the total power consumption of the load exceeds the power consumption quota in a short period of time, battery discharge can be used to reduce the power exceeding the quota. ○ ○ ○ ○ ○ ○ 153 8.4.1 Quick Setting the Basic Information( Type III) Step 1: Tap Home > Settings > Quick Settings to set the parameters. Step 2 : Enter the password for quick settings. Password: goodwe2010 or 1111. Step 3: Select safety country accordingly. Tap Next to set the Battery Connect Mode. Step 4 : Select the actual mode in which the battery is connected to the inverter. The basic settings are completed if there is no battery connected in the system. Tap Next to set the Battery Model if there is any battery connected in the system. Step 5: Select the actual battery model. Tap Next to set the Working Mode. 154 Step 6:Set the working mode based on actual needs. Tap Next to conduct System 155 Self-Test. • If Peakshaving mode is selected, tap Settings to set the parameters. • No. Parameters Description Peakshaving 1 Start Time 2 End Time The utility grid will charge the battery between Start Time and End Time if the load power consumption do not exceed the power quota. Otherwise, only PV power can be used to charge the battery. 3 Peak Power Purchase Limit Set the maximum power limit allowed to purchase from the grid. When the loads consume power exceed the sum of the power generated in the PV system and Peak Power Purchase Limit, the excess power will be made up by the battery. 4 Reserved SOC For Peakshaving In Peak Shaving mode, the battery SOC should be lower than Reserved SOC For Peakshaving. Once the battery SOC is higher than Reserved SOC For Peakshaving, the peak shaving mode fails. 156 • When Self-Use Mode is selected, tap Settings to set the Depth Of Discharge(OnGrid)and Depth Of Discharge(Off-Grid). And tap Advanced Settings to set Back-Up Mode, Economic Mode or Smart Charging based on actual needs. If Economic Mode is selected, tap Add to set the working time and working mode of the battery group. No. Parameters Description Self-use mode 1 Depth Of Discharge (OnGrid) The maximum depth of discharge of the battery when the system is working on-grid. 2 Depth Of Discharge (Offgrid) The maximum depth of discharge of the battery when the system is working off-grid. 157 No. Parameters Description Back-up mode 3 Charging Power Enable Charging Power From Grid to allow power From Grid purchasing from the utility grid. 4 Rated Power The percentage of the purchasing power to the rated power of the inverter. TOU mode 5 Start Time Within the Start Time and End Time, the battery is charged or discharged according to the set Battery Mode as well as the Rated Power. 6 End Time 7 Charge Discharge Mode Charge or discharge according to actual needs. 8 Rated Power The percentage of the charging/discharging power to the rated power of the inverter. 9 Charge Cut-off SOC The battery stop charging/discharging once the battery SOC reaches Charge Cut-off SOC. Smart charging 10 11 12 13 Monthly-Repeat Set the smart charging months. More than one month can be set. Peak Power Sales Limit Set the Peak Power Sales Limit in compliance with local laws and regulations. The Peak Limiting Power shall be lower then the output power limit specified by local requirements. PV Prioritizes Charing Battery During charging time, the PV power will first charge the Start Charging battery. Time Step 7: Execute device self-check or skip it based on actual needs. Step 8 : Tap Recheck or Next to complete the test based on your actual needs. Tap Export to export the test reports if needed. Step 9 : Tap Complete to complete the quick settings. 158 8.5 Power Plant Creation Step 1: Click on the home page or power station list page, or click Create Station on the account page. Step 2: Based on the actual situation, fill in the relevant information about the power station in the Create Station interface. Step 3: Click Save & Exit to complete the power plant creation. At this point, no equipment has been added to the power plant. Alternatively, click Save & Continue to enter the equipment addition interface and enter the relevant equipment information based on the actual situation. Multiple pieces of equipment can be 159 added. 160 9 System Commissioning 9.1 Commissioning Method Overview The inverter without LCD screen only supports setting the inverter through the SolarGo APP. The inverter with LCD screen supports setting the inverter through LCD screen and the SolarGo APP. 9.2 Configuration via LCD 9.2.1 LCD Overview With the LCD screen, the user can: 1. Check the operating data, software version, alarms, etc. 2. Set parameters, safety regions, power limit, etc. Introduction of LCD interface LCD supports both touch and keys. Name/Icon Description Up button. Down button. Enter button. 161 Name/Icon Description • Short press: Exit button. • Long press 5 seconds: Restart the device Used to view information such as PV current, voltage, and power generation. Used to view information such as battery model and status. Used to view the alarm and fault information of the inverter. Used to enter the settings interface of the inverter. Used to view the status of the power grid and information. Used to check the status of the generator. Used to view the load information of the inverter. Return to the main screen. Cancel Return to previous menu. Next Go to the next setting page. Back Return to the previous setting page. LCD setting interface structure 162 9.2.2 Quick Settings Setting safety code 1. Tap Home >Quick Settings > Safe Code to set the parameters. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. Parameter Safety Code Description Safety Code select South Africa Select the corresponding safety code based on the country or region where the equipment is located. Pakistan Argentina Philippines 163 60Hz Default 60Hz Default 50Hz Default Set parameters for lithium battery 1. Tap Home > Quick Settings > BAT Setting to enter parameter setting interface. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. NOTICE Please make sure that you click Confirm on each page to ensure that the parameters take effect, otherwise the system will run with default parameters. Setting Basic Parameter BAT Connection Mode Battery Type GOODW E Description If the system is connected to a GOODWE brand lithium battery, please select GOODWE and choose the correct model. 164 Default If the third-party lithium battery model connected in the system is not in this list, please select it according to the actual situation: • Lithium 50Ah • Lithium 100Ah If the third-party lithium battery model connected to the system is in this list, please Others select the correct model according to the actual situation. If a lead-acid battery is connected to the Lead system, select Lead acid and choose the acid correct type of lead-acid. Only supports: GEL, AGM, Flooded. There is no battery connected in the system. Set according to the actual connected battery in the system. NO Battery BAT Setting Set parameters for lithium battery Parameter SOC Protection Depth Of Discharge (On-Grid) Depth Of Discharge (Off-Grid) Backup SOC Holding Description Enable or disable SOC protection. The maximum depth of discharge of the battery when the system is working on-grid. The maximum depth of discharge of the battery when the system is working off-grid. The battery will be charged to preset SOC protection value by utility grid or PV when the system is running on-grid, so that the battery SOC is sufficient to maintain normal working when the system is off-grid. Set parameters for lead-acid battery Parameter Maximum Current Description Charging 165 The battery charging mode is set to constant voltage charging by default. Charging The maximum charging voltage and current in the constant charge state. Please set them according to the battery technical parameters. Constant Voltage Float Voltage The Time Float Charging Maximum Current For Switch To Float Charge Battery Capacity Internal Resistance Temperature Compensation Lower Limit Of Discharge Voltage Maximum Discharging Current The battery charging current is less than Maximum Current For Switch To Float Charge and the duration reaches The Time Float Charging, the battery charging status changes from Constant Charge mode to Float Charge mode. When the battery is approaching full charge, it will switch to float charging mode. This value is the upper limit of charging voltage in this mode. Please set it according to the battery technical parameters. Please set it according to the battery technical parameter. The internal resistance of the battery. Please set it according to the battery technical parameters. By default, when the temperature is higher than 25℃, the upper limit of charging voltage will decrease by 3mV for every 1℃ increase. The actual settings should be based on the technical parameter of the battery. Please set it according to the battery technical parameters. Please set it according to the battery technical parameters. The greater the discharge current is, the shorter the working time of the battery is. Setting Working Mode 1. Tap Home >Quick Settings > Working Mode to set the parameters. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. NOTICE 166 Please make sure that you click Confirm on each page to ensure that the parameters take effect, otherwise the system will run with default parameters. Parameter Description Based on Self-use Mode, Back-up Mode and TOU Mode can be enabled at the same time, and the Self-use Mode inverter will automatically select the working mode. Operation priority: Back-up Mode>TOU Mode >Self-use Mode. Charging From Enabling this function allows the system to Grid purchase electricity from power grid. Back-up Mode The percentage of power purchased compare to Rated Power the rated power of the inverter. TOU Mode Within the start and end time, the battery will Time charge or discharge based on the set chargedischarge mode and rated power. Charge/Dischar Set to charge or discharge based on actual ge needs. The percentage of power during charging or Power (%) discharging compared to the rated power of the inverter. 167 The battery stop charging once the battery SOC reaches Charge Cut-off SOC. To set the SOC for stopping the battery discharge, please refer to section 9.2.2.2 on setting battery parameters and set the Depth of Discharge (On Grid) and Depth of Discharge (Off Grid) through the LCD screen. Bat (%) Setting PV Connect Mode 1. Tap Home >Quick Settings > PV Connect Mode to set the parameters. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. Parameter Stand-alone Connect Partial Parallel Connect Parallel Connect Description The PV strings are connected to the MPPT terminals one by one. The PV strings are connected to the inverter in both stand-alone and parallel connection. For example, one PV string connect to MPPT1 and MPPT2, another PV string connect to MPPT3. When the external PV string is connected to the inverter side PV input port, the same PV string is connected to multiple PV input ports. Setting the on-grid power limit 1. Tap Home >Quick Settings > Power Limit the parameters. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts 168 Confirm OK, the parameters are set successfully. Parameter Power Limit Export Power External CT Ratio Description Enable Power Limit when power limiting is required by local grid standards and requirements. Set the value based on the actual maximum power feed into the utility grid. Set the ratio of the primary current to the secondary current of the external CT. • Built in electric meter or GMK110: No need to set CT ratio. The default CT ratio is 120A/40mA. • GM330: Supports purchasing from GOODWE or third-party, CT ratio requirement: nA/5A • nA: For the primary input current of CT, n ranges from 200 to -5000. • 5A: CT secondary input current of CT. Meter/CT Assisted Test 1. Through the main interface, click > Quick Settings > Meter/ CT Assisted Test to enter the parameter setting interface. 2. Click Start Test to begin the test. After the test is completed, judge the test result according to the interface prompts. 169 9.2.3 Setting Advanced Parameters 1. Tap Home > Advanced Settings to set the parameters. Enter the initial password: 1111. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. Parameter One-click restart Battery Wake-up Off-grid Switch Shadow Scan Description By using this function, the inverter can be quickly restarted. After being turned on, the battery can be awakened when it shuts down due to undervoltage protection. Only applicable to lithium batteries without circuit breakers. After being turned on, the output voltage of the battery port is about 60V. In off-grid mode, the switch controls the on/off of the inverter's off-grid function. In on-grid mode, this function does not take effect. The switch is initially in the ON state, and the off-grid function is enabled. After the inverter is powered on, the off-grid output function of the inverter is enabled. In the off-grid state, turning off and then turning on the off-grid switch, the off-grid overload time can be known and the off-grid output can be restarted. Enable Shadow Scan when the PV panels are severely shadowed to optimize the power generation efficiency. 9.2.4 Setting Immediate Charging 1. Tap Home > Immediate Charging to set the parameters. 170 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. Parameter Immediate Charging SOC For Stopping Charging Immediate Charging Power Description Enable to charge the battery by the grid immediately. This takes effect once. Enable or Disable based on actual needs. Stop charging the battery once the battery SOC reaches SOC For Stopping Charging. Indicates the percentage of the charging power to the inverter rated power when enabling Immediate Charging. For example, setting the Immediate Charging Power of a 10kW inverter to 60, which means the charging power of the inverter is 10kW*60%=6kW. 9.2.5 Setting the Basic Information 1. Tap Home > Basic Settings to set the parameters. 2. Set the parameters based on actual needs. 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. 171 9.2.6 Viewing Device Information 1. Tap Home > Device Information to search the parameters. NOTICE Inverter serial number, DSP, BMS, LCD and ARM can be queried. 9.2.7 Setting Port Connection Setting Port Connection Generators 1. After connecting to the SolarGo APP, go to Home parameter setting interface. 2. Set the parameters based on actual needs. > Port Connection, entering the 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. NOTICE Please make sure that you click Confirm on each page to ensure that the parameters take effect, otherwise the system will run with default parameters. 172 No. Parameter 1 Generator ON/OFF 2 Rated Power 3 Run Time 4 Max Charging Power 5 SOC for Starting Charging 6 SOC For Stopping Charging 7 8 9 Maximum Operation Voltage Minimum Operation Voltage Upper Limit Of Operating Frequency Description Controls the start and stop of the generator. Only applicable to generators that support dry contact. Rated power of the generator. The duration of continuous operation of a generator. When the working time exceeds the set value, the generator will automatically shut down. This feature only applies to generators that support dry contact connection. Set the maximum charge power for the generator battery. Set the starting SOC for the generator to charge the battery. When the SOC of the battery is lower than the set value, the generator will charge the battery. Set the stopping SOC for the generator stopping charging the battery. When the SOC of the battery reaches the set value, the generator will stop charging the battery. Set the upper limit of operating voltage for the generator. Set the lower limit of operating voltage for the generator. Set the upper limit of operating frequency for the generator. 173 10 Lower Limit Of Operating Frequency 11 Delay Before Load 12 Prohibited Working Hours Set the lower limit of operating frequency for the generator. The no-load preheating time before the generator is loaded. Please set the generator prohibition time according to the actual situation. Setting Port Connection Load Control Dry Contact Mode 1. After connecting to the SolarGo APP, go to Home parameter setting interface. 2. Set the parameters based on actual needs. > Port Connection, entering the 3. After the setting is completed, please click Confirm. After the interface prompts Confirm OK, the parameters are set successfully. NOTICE Please make sure that you click Confirm on each page to ensure that the parameters take effect, otherwise the system will run with default parameters. 174 No. Parameter 1 Load Control ON/OFF 2 Dry Contact Mode 3 Time Mode 4 Load Control 1 5 Mode: Standard/Intelligent 6 Load Consumption Time 7 Load Rated Power 8 SOC Mode Description Set the load control function on/off. ON: When the switch is ON, the loads will be powered. OFF: When the switch is OFF, the power will be cut off. Set the time to enable the load, and the load will be powered automatically within the setting time period. Standard mode or intelligent mode can be selected. Set the 1st group of load control time, and a total of 4 groups can be set. Standard: The loads will be powered within the setting time period. Intelligent: When the residual energy generated by the PV exceeds the preset load power rating within a set time period, it starts to supply power to the load. Minimum time of operation after the load is turned on to avoid frequent switching of the load due to energy fluctuations. Only applicable to intelligent mode. When the residual energy generated by the PV exceeds the rated power of this load, it begins to power the load. Only applicable to intelligent mode. The inverter has an integrated relay controlling port, which can control whether to power the loads or not. 175 9 Off-Grid Battery Protection Value In off-grid mode, the load connected to the port will not be powered if the BACKUP overload is detected or the battery SOC value is lower than the Off-grid battery protection value. Please set off-grid battery protection values based on actual needs. 9.3 Configuration via SolarGo APP 9.3.1 Product Introduction NOTICE • All the user interface (UI) screenshots or words in this document are based on SolarGo App V6.4.0.The UI may be different due to the version upgrade. The screenshots, words or data are for reference only. • The method to set parameters is the same for all inverters. But the parameters displayed varies based on the equipment model and safety code. Refer to the actual interface display for specific parameters. • Before setting any parameters, read through user manual of the app and the inverter or charger to learn the product functions and features. When the inverter parameters are set improperly, the inverter may fail to connect to the utility grid or fail to connect to the utility grid in compliance with related requirements and damage the battery, which will affect the inverter’s power generation. SolarGo app is a mobile application that communicates with the inverter or the charger via Bluetooth, WIFi, 4G, or GPRS. Commonly used functions are as follows: • Check the operating data, software version, alarms, etc. • Set safety country, grid parameters, power limit, communication parameters, etc. • Set charging mode of the charger. • Equipment maintenance. 9.3.1.1 Downloading and Installing the App Make sure that the mobile phone meets the following requirements: 176 • Mobile phone operating system: Android 5.0 or later, iOS 13.0 or later. • The mobile phone can access the Internet. • The mobile phone supports WLAN or Bluetooth. NOTICE After installing the app, it can automatically prompt users to update the app version. Method 1: Search SolarGo in Google Play (Android) or App Store (iOS) to download and install the app. Method 2: Scan the QR code below to download and install the app. 9.3.1.2 App Connection Connect as the following shows after powering on the equipment. NOTICE The connection distance varies depending on smart dongles. Refer to the actual used smart dongles. 177 9.3.1.3 GUI Introductions to Login Page No. 1 Name/Icon Description Tap the icon to open the page downloading the SEMS Portal app. 178 No. Name/Icon 2 Description Tap to read the connection guide. Not found 3 • Check information such as app version, local contacts, etc. • Other settings, such as update date, switch language, set temperature unit, etc. 4 Select based on actual communication method. If you have Bluetooth/Wi any problems, tap or NOT Found to read the connection Fi/4G guides. • The list of all devices. The last digits of the device name are normally the serial number of the device. • Select the device by checking the serial number of the master inverter when multi inverters are parallel connected. • The device name varies depending on the inverter model or smart dongle model: Wi-Fi/LAN Kit, Wi-Fi Kit, Wi-Fi Box: Solar-WiFi*** ○ 5 6 Device List Search Device ○ External or integrated bluetooth mudule:Solar-BLE*** ○ WiFi/LAN Kit-20: WLA-*** ○ WiFi Kit-20: WFA-*** ○ Ezlink3000:CCM-BLE***;CCM-***;*** ○ 4G Kit-CN-G20/4G Kit-CN-G21: GSA-***; GSB-*** ○ 4G Kit-G20:GSC-*** ○ Micro inverter: WNN*** ○ AC Charger: *** Tap Search Device if the device is not found. 179 9.3.2 Setting Microgrid Parameters NOTICE When the inverter supports microgrid function, you can set microgrid parameters through SolarGo App. Step 1 : Tap Home > Settings > Port Connection to set the parameters. Step 2 : According to the actual interface prompts, enter the microgrid control interface and set the microgrid parameters according to actual needs. No. Parameters Description 1 Max.charging SOC Set the upper limit of charging SOC, and stop charging when the upper limit is reached. 180 No. Parameters Description Manual wake-up • When the grid fails, if the battery power is low, the energy storage inverter cannot be supported to work off the grid. Click this button to force the energy storage inverter to output voltage to the grid-connected inverter, thereby starting the gridconnected inverter. • Single effect. 3 Automatic wakeup • When the grid fails, if the battery power is low, the energy storage inverter cannot be supported to work off the grid. After enabling this function, the system will force the energy storage inverter to output voltage to the grid-connected inverter at a fixed time, thereby starting the grid-connected inverter. • Multiple effect. 4 Grid Import Power Limit Offset Set the adjustable range of the maximum power that the device can actually buy from the grid. 2 9.3.2.1 Connecting the Energy Storage Inverter (Bluetooth) Step 1: Confirm that the inverter is powered on and that both the communication module and the inverter are operating normally. Step 2: Depending on the type of communication module, select the Bluetooth tab on the SolarGo App home page. Step 3: Drag down or click Search Device to refresh the device list, confirm the inverter signal name based on the inverter serial number, and click the inverter signal name to enter the login interface. Select the device by checking the serial number of the master inverter when multi inverters are parallel connected. Step 4: When connecting the device via Bluetooth for the first time, a Bluetooth 181 pairing prompt will appear on the interface. Please click Pair to continue connecting and enter the login interface. Step 5: Log in to the app using your actual role and change your login password according to the prompts on the interface. Initial Login Password: 1234. 182 9.3.3 Introductions to Hybrid Inverters No. Name/Icon Description 1 Serial Number Serial number of the connected inverter. 2 Device Status Indicates the status of the inverter, such as Working,Fault, etc. 3 Energy Flow Chart Indicates the energy flow chart of the PV system. The actual page prevails. 4 Indicates the system status, such as Safety Code, Working System Status Mode, Battery Model, Battery Status, Power Limit, ThreePhase Unbalanced Output, etc.. 5 Home. Tap Home to check Serial Number, Device Status, Energy Flow Chart, System Status, etc. 6 Parameters. Tap Parameters to check the inverter Data. 183 No. 7 Name/Icon Description • Settings. Tap to perform quick settings, basic settings, advanced settings, etc. on the inverter. • Login required to access Quick Setup and Advanced Setup interfaces Initial password: goodwe2010 or 1111. 9.3.4 Setting communication parameters NOTICE The communication configuration interface may be different if the inverter uses different communication modes or connects different communication modules. Please refer to the actual interface. 9.3.4.1 Setting Privacy and Security Type I Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set the parameters. Step 2 : Set the new password for the WiFi hotspot of the communication module, and tap Save. Step 3 Open the WiFi settings of your phone and connect to the inverter’s WiFi signal (Solar WiFi***) with the new password. 184 Type II Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set the parameters. Step 2 Enable Bluetooth Stays On or WLAN Control based on actual needs. 185 No. Parameters Description Bluetooth Stays On Disabled by default. Enable the function, the bluetooth of the device will be contentious on to keep connected to SolarGo. Otherwise, the bluetooth will be off in 5 minutes, and the device will be disconnected from SolarGo. WLAN Control Disabled by default. Enable the function, the device and the SolarGo can be connected through the WLAN when they are on the same LAN. Otherwise, they cannot be connected even if they are on the same LAN. 3 Modbus-TCP Enable the function, the third party monitoring platform can access inverter through Modbus-TCP communication protocol. 4 SSH control Ezlink After enabling this function, third-party platforms can connect to and control EzLink's Linux system. 1 2 Type III Step 1 : Tap Home > Settings > Communication Setting > Privacy & Security to set 186 the parameters. Step 2 : Enable Bluetooth Stays On or Login Password based on actual needs. No. 1 2 Parameters Description Bluetooth Stays On Disabled by default. Enable the function, the bluetooth of the device will be contentious on to keep connected to SolarGo. Otherwise, the bluetooth will be off in 5 minutes, and the device will be disconnected from SolarGo. Login Password Disabled by default. Enable the function, you will be prompted to enter the login password when connecting the device to SolarGo. Use the initial password and change it at the first login prompt. 9.3.4.2 Setting WLAN/LAN parameters 187 NOTICE When the inverter is connected to different communication modules, the communication configuration interface may be different. Please refer to the actual interface. Step 1 : Tap Home > Settings > Communication Setting > WLAN/LAN to set the parameters. Step 2 : Configure the WLAN or LAN parameters based on actual needs. No. Parameters Description 1 Network Name Only for WLAN. Select WiFi based on the actual connecting. 2 Password Only for WLAN. WiFi password for the actual connected network. 3 DHCP Enable DHCP when the router is in dynamic IP mode. Disable DHCP when a switch is used or the router is in static IP mode. 188 No. Parameters 4 IP Address 5 Subnet Mask 6 Gateway Address 7 DNS Server Description Do not configure the parameters when DHCP is enabled. Configure the parameters according to the router or switch information when DHCP is disabled. 9.3.4.3 Configuring APN Parameters NOTICE • Configure the SIM card information of 4G communication device. • Configure the APN parameters through the Bluetooth module or WiFi module first before using a 4G module to achieve 4G communication. Step 1: Tap Home > Settings > Communication Settings > 4G to set the parameters. Step 2: Set the region and operator based on actual needs. 189 9.3.4.4 Setting RS485 Parameters NOTICE Set the communication address of the inverter. For a single inverter, the address is set based on actual needs. For multi connected inverters, the address of each inverter should be different while cannot be 247. Step 1: Tap Home > Settings > Communication Settings > RS485 to set the parameters. Step 2 : Set the Modbus Address and Baud Rate base on actual situation. 9.3.5 Quick Setting the Basic Information 190 NOTICE • The setting page varies depending on inverter model. • The parameters will be configured automatically after selecting the safety country/region, including overvoltage protection, undervoltage protection, overfrequency protection, underfrequency protection, voltage/frequency connection protection, cosφ curve, Q(U) curve, P(U) curve, FP curve, HVRT, LVRT, etc. Tap Home > Settings > Advanced Settings > Safety Parameters to check the parameters after selecting the safety country. • The power generation efficiency is different in different working modes. Set the working mode according to the local requirements and situation. Self-use mode: The basic working mode of the system. PV power generation is used to supply power to the load first, the excess power is used to charge the battery, and the remaining power is sold to the grid. When PV power generation cannot meet the load's power demand, the battery will supply power to the load; when the battery power also cannot meet the load's power demand, the grid will supply power to the load. Back-up mode: The back-up mode is mainly applied to the scenario where the grid is unstable. When the grid is disconnected, the inverter turns to off-grid mode and the battery will supply power to the load; when the grid is restored, the inverter switches to grid-tied mode. Economic mode: It is recommended to use economic mode in scenarios when the peak-valley electricity price varies a lot. Select Economic mode only when it meets the local laws and regulations. Set the battery to charge mode during Vally period to charge battery with grid power. And set the battery to discharge mode during Peak period to power the load with the battery. Off-grid mode: suitable for areas without power grid. PV and batteries form a pure off-grid system. PV generates electricity to power the load and excess electricity charges the battery. When PV power generation cannot meet the power demand of the load, the battery will supply power to the load. Smart charging: In some countries/regions, the PV power feed into the utility grid is limited. Select Smart Charging to charge the battery using the surplus power to minimize PV power waste. Peak shaving mode: Peak shaving mode is mainly applicable to peak power limited scenarios. When the total power consumption of the load exceeds the power consumption quota in a short period of time, battery discharge can be used to reduce the power exceeding the quota. ○ ○ ○ ○ ○ ○ 191 9.3.5.1 Quick Setting the Basic Information( Type III) Step 1: Tap Home > Settings > Quick Settings to set the parameters. Step 2 : Enter the password for quick settings. Password: goodwe2010 or 1111. Step 3: Select safety country accordingly. Tap Next to set the Battery Connect Mode. Step 4 : Select the actual mode in which the battery is connected to the inverter. The basic settings are completed if there is no battery connected in the system. Tap Next to set the Battery Model if there is any battery connected in the system. Step 5: Select the actual battery model. Tap Next to set the Working Mode. 192 Step 6:Set the working mode based on actual needs. Tap Next to conduct System 193 Self-Test. • If Peakshaving mode is selected, tap Settings to set the parameters. • No. Parameters Description Peakshaving 1 Start Time 2 End Time The utility grid will charge the battery between Start Time and End Time if the load power consumption do not exceed the power quota. Otherwise, only PV power can be used to charge the battery. 3 Peak Power Purchase Limit Set the maximum power limit allowed to purchase from the grid. When the loads consume power exceed the sum of the power generated in the PV system and Peak Power Purchase Limit, the excess power will be made up by the battery. 4 Reserved SOC For Peakshaving In Peak Shaving mode, the battery SOC should be lower than Reserved SOC For Peakshaving. Once the battery SOC is higher than Reserved SOC For Peakshaving, the peak shaving mode fails. 194 • When Self-Use Mode is selected, tap Settings to set the Depth Of Discharge(OnGrid)and Depth Of Discharge(Off-Grid). And tap Advanced Settings to set Back-Up Mode, Economic Mode or Smart Charging based on actual needs. If Economic Mode is selected, tap Add to set the working time and working mode of the battery group. No. Parameters Description Self-use mode 1 Depth Of Discharge (OnGrid) The maximum depth of discharge of the battery when the system is working on-grid. 2 Depth Of Discharge (Offgrid) The maximum depth of discharge of the battery when the system is working off-grid. 195 No. Parameters Description Back-up mode 3 Charging Power Enable Charging Power From Grid to allow power From Grid purchasing from the utility grid. 4 Rated Power The percentage of the purchasing power to the rated power of the inverter. TOU mode 5 Start Time Within the Start Time and End Time, the battery is charged or discharged according to the set Battery Mode as well as the Rated Power. 6 End Time 7 Charge Discharge Mode Charge or discharge according to actual needs. 8 Rated Power The percentage of the charging/discharging power to the rated power of the inverter. 9 Charge Cut-off SOC The battery stop charging/discharging once the battery SOC reaches Charge Cut-off SOC. Smart charging 10 11 12 13 Monthly-Repeat Set the smart charging months. More than one month can be set. Peak Power Sales Limit Set the Peak Power Sales Limit in compliance with local laws and regulations. The Peak Limiting Power shall be lower then the output power limit specified by local requirements. PV Prioritizes Charing Battery During charging time, the PV power will first charge the Start Charging battery. Time Step 7: Execute device self-check or skip it based on actual needs. Step 8 : Tap Recheck or Next to complete the test based on your actual needs. Tap Export to export the test reports if needed. Step 9 : Tap Complete to complete the quick settings. 196 9.3.6 Setting the Basic Information 9.3.6.1 Setting the SPD After enabling SPD, when the SPD module is abnormal, there will be SPD module abnormal alarm prompt. Step 1 : Tap Home > Settings > Basic Settings > SPD, to set the parameters. Step 2 : enable or disable the function based on actual needs. 197 9.3.6.2 Setting the Shadow Scan Enable Shadow Scan when the PV panels are severely shadowed to optimize the power generation efficiency. Step 1 : Tap Home > Settings > Basic Settings> Shadow Scan, to set the parameters. Step 2: Enable or disable the function based on actual needs. Set the Shadow Scan interval and MPPT shadow scan if the inverter supports. 198 9.3.6.3 Setting the Back-up After enabling Backup, the battery will power the load connected to the backup port of the inverter to ensure Uninterrupted Power Supply when the power grid fails. Step 1 : Tap Home > Settings > Basic Settings > Backup, to set the parameters. Step 2 : Set the backup supply function based on actual needs. 199 No. Parameters Description 1 UPS Mode- Full Wave Detection Check whether the utility grid voltage is too high or too low. 2 UPS Mode- Half Wave Detection Check whether the utility grid voltage is too low. 3 EPSmode-with LVRT support. Stop detecting utility grid voltage. 4 First Cold Start (Off-grid) It will only take effect once. In off-grid mode, enable First Cold Start (Off-grid) to output backup supply with battery or PV. 5 Take effect multiple times. In off-grid mode, enable First Cold Start Holding Cold Start (Off-grid) to output backup supply with (Off-grid) battery or PV. 200 No. 6 Parameters Description Clear Overload History Once the power of loads connected to the inverter BACK-UP ports exceeds the rated load power, the inverter will restart and detect the power again. The inverter will perform restart and detection several times until the overloading problem is solved. Tap Clear Overload History to reset the restart time interval after the power of the loads connected to the BACK-UP ports meets the requirements. The inverter will restart immediately. 9.3.7 Setting Advanced Parameters NOTICE Password for Advanced Settings: goodwe2010 or 1111. 9.3.7.1 Setting DRED/Remote Shutdown/RCR/EnWG 14a Enable DRED/Remote Shutdown/RCR before connecting the third party DRED, remote shutdown, or RCR device to comply with local laws and regulations. Step 1 : Tap Home > Settings > Advanced Settings > DRED/Remote Shutdown/RCR to set the parameters. Step 2 : Enable or disable the function based on actual needs. Step 3 :For areas where the EnWG 14a regulation applies, when enabling the RCR function, you need to select the RCR mode according to the actual device type and set the DI port power. 201 9.3.7.2 Setting the Backup N and PE Relay Switch To comply with local laws and regulations, ensure that the relay inside the back-up 202 port remains closed and the N and PE wires are connected when the inverter is working off-grid. Step 1 : Tap Home > Settings > Advanced Settings > Backup N and PE Relay Switch to set the parameters. Step 2 : Enable or disable the function based on actual needs. 9.3.7.3 Set the Grid-Connected Power Limit Parameters Step 1: TapHome > Settings > Advanced Settings > Power Limit to set the parameters. Step 2 : Turn on or off the anti-backflow function according to actual needs. Step 3 : After turning on the anti-backflow function, enter the parameter value according to actual needs and click "√" to successfully set the parameter. 9.3.7.3.1 Set the Grid-Connected Power Limit Parameters (General) 203 No. Parameters Description 1 Power Limit Turn on this function when output power needs to be limited according to the grid standards of some countries or regions. 2 Select Mode Set according to the maximum power that can be input to the grid. 3 External CT ratio Set the ratio of the primary current to the secondary current of the external CT. 9.3.7.3.2 Set Grid-Connected Power Limit Parameters (Australia) 204 No. Paramet ers Description 1 Soft Limit When output power needs to be limited according to grid standards in some countries or regions, turn on this function. Select Mode • Set according to the maximum power that can be actually input to the grid. • Supports setting of fixed power value or percentage. The set percentage is the percentage of the limit power to the rated power of the inverter. • After setting the fixed value, the percentage changes automatically; after setting the percentage, the fixed value changes automatically. 2 205 No. Paramet ers Description 3 Hard Limit After enabling this function, when the amount of electricity fed into the grid exceeds the limit value, the inverter will automatically disconnect from the grid. 4 External CT Ratio Set the ratio of the primary current to the secondary current of the external CT. 9.3.7.4 Set the AFCI Detection Step 1 : Tap Home > Settings > Advanced Settings > AFCI Test to set the parameters. Step 2 : Enable AFCI Test, Clear AFCI Alarm and Self-Check based on actual needs. No. Parameters Description 1 AFCI Test Enable or disable AFCI accordingly. 2 AFCI Test Status The detection status like Not Self-checking. 3 Clear AFCI Alarm Clear ARC Faulty alarm records. 4 Self-check Tap to check whether the AFCI function works normally. 9.3.7.5 Setting the Battery 9.3.7.5.1 Setting the Lithium Battery 206 Step 1: Tap Home > Settings> Advanced Settings > Battery Function Settings to set the parameters. Step 2: Set the parameters based on actual needs. No. Parameter Description Parameter Settings 1 Max. Charging Current Only applicable to certain models. Set the maximum charging current based on actual needs. 2 Max. Discharging Current Only applicable to certain models. Set the maximum discharging current based on actual needs. 207 No. Parameter Description Optional. This option is displayed on the interface when a battery that supports heating is connected. After the battery heating function is turned on, when the temperature is below the value that starts up the battery, PV power or electricity from the grid will be used to heat the battery. Heating Mode: • GW5.1-BAT-D-G20/GW8.3-BAT-D-G20 Low Power Mode: Maintains minimum battery power input capacity, turns on when the temperature is below -9℃, and turns off when the temperature is above or equal to -7℃. Medium Power Mode: to maintain the moderate power input capacity of the battery. It will be turned on when the temperature is less than 6℃, and turned off when it is greater than or equal to 8℃. High Power Mode: to maintain the higher power input capacity of the battery. It will be turned on when the temperature is less than 11℃, and turned off when it is greater than or equal to 13℃. • GW14.3-BAT-LV-G10 Low Power Mode: Maintains minimum battery power input capacity, turns on when the temperature is below 5℃, and turns off when the temperature is above or equal to 7℃. Medium Power Mode: to maintain the moderate power input capacity of the battery. It will be turned on when the temperature is less than 10℃, and turned off when it is greater than or equal to 12℃. High Power Mode: to maintain the higher power input capacity of the battery. It will be turned on when the temperature is less than 20℃, and turned off when it is greater than or equal to 22℃. ○ ○ 3 Battery Heating ○ ○ ○ ○ 208 No. Parameter Description 4 • After being turned on, the battery can be awakened when it shuts down due to undervoltage protection. Battery Wake-up • Only applicable to lithium batteries without circuit breakers. After being turned on, the output voltage of the battery port is about 60V. Limit Protection 5 SOC Protection Start battery protection when the battery capacity is lower than the Depth of Discharge. 6 SOC Upper Limit The upper limit value for battery charging. Charging stops when the battery SOC reaches the SOC upper limit. 7 Depth of Discharge The maximum discharge value allowed for the battery when the inverter is in the on-grid scenario. 8 Backup SOC Holding To ensure that the battery SOC is sufficient to maintain normal operation when the system is off-grid, the battery will purchase electricity from the grid and charge to the set SOC protection value when the system is connected to the grid. 9 Depth of Discharge The maximum discharge value allowed for the battery when the inverter is in the off-grid scenario. Off-grid SOC Recovery When the inverter is operating off-grid, if the battery SOC drops below the lower limit, the inverter stops outputting power and only charges the battery until the battery SOC returns to the off-grid recovery SOC value. If the SOC lower limit value is higher than the off-grid recovery SOC value, charge to SOC lower limit +10%. 10 Immediate Charging 11 Immediate Charging Enable to charge the battery by the grid immediately. This takes effect once. Enable or Disable based on actual needs. 209 No. Parameter Description 12 SOC for Stopping Charging Stop charging the battery once the battery SOC reaches SOC For Stopping Charging. 13 Immediate Charging Power Indicates the percentage of the charging power to the inverter rated power when enabling Immediate Charging. For example, for an inverter with a rated power of 10kW, when set to 60, the charging power is 6kW. 14 Start Start charging immediately. 15 Stop Immediately stop the current charging task. 9.3.7.5.2 Setting Lead-acid Battery Parameter Step 1: Tap Home > Settings> Advanced Settings > Battery Function Settings to set the parameters. Step 2: Set the parameters based on actual needs. 210 211 No. Parameter Description 1 Nominal Capacity Set the battery capacity according to the actual parameters. 2 Battery Internal Set the battery internal resistance according to the actual Resistance parameters. 3 Temperature Compensation When the battery temperature changes, the battery charging voltage will be affected. Based on 25°C, the charging voltage upper limit is adjusted according to the set value for every degree change in battery temperature. For example, if the charging temperature influence coefficient is set to 10, when the battery temperature rises to 26 degrees, the charging voltage upper limit decreases by 10 mV. 4 Lower Discharge Voltage Set the minimum voltage during battery discharge according to actual requirements. 5 Max. Discharging Current Set the maximum discharging current based on actual needs. 6 Max. Charging Current Set the maximum charging current based on actual needs. 7 Constant Charging Voltage Set the voltage value for constant charging of the battery according to actual requirements. 8 Floating Voltage Set the voltage value for battery float charging according to actual requirements. 9 Maximum The maximum charging current after switching the battery Current When charging mode from constant charging/equal charging to Switching to float charging. Floating Charge 212 No. Parameter Description 10 Time to Switch to Float Charging Mode The time required to switch the battery charging mode from constant charging/equal charging to float charging. 11 Equalization Charging Cycle Set the interval days for battery equalization charging. Restriction protection. 12 SOC Protection Start battery protection when the battery capacity is lower than the Depth of Discharge. 13 SOC Lower Limit (Grid Connection) The minimum battery charge that must be maintained when the inverter is connected to the grid. 14 Backup Power SOC Maintenance To ensure that the battery SOC is sufficient to maintain normal operation when the system is off-grid, the battery will purchase electricity from the grid and charge to the set SOC protection value when the system is connected to the grid. 15 SOC Lower Limit (Off-Grid) The minimum battery charge that must be maintained when the inverter is operating off-grid. Off-grid SOC Recovery When the inverter is operating off-grid, if the battery SOC drops below the lower limit, the inverter stops outputting power and only charges the battery until the battery SOC returns to the off-grid recovery SOC value. If the SOC lower limit value is higher than the off-grid recovery SOC value, charge to SOC lower limit +10%. 16 Immediate Charging 17 SOC for Stopping Charging Stop charging the battery once the battery SOC reaches SOC For Stopping Charging. 213 No. Parameter Description 18 Indicates the percentage of the charging power to the inverter rated power when enabling Immediate Charging. Immediate Charging Power For example, for an inverter with a rated power of 10kW, when set to 60, the charging power is 6kW. 19 Start Start charging immediately. 20 Stop Immediately stop the current charging task. 9.3.7.6 Setting PV Connect Mode Select the PV access mode based on the actual connections between the PV strings and MPPT ports of the inverter. Step 1 : Tap Home > Settings > Advanced Settings > PV Connect Mode to set the parameters. Step 2 : Set the access mode to Independent Access, Partial Parallel Connect or Parallel Connection based on actual connections. 214 No. Parameters Description 1 Stand-alone Connect The external PV string is connected to multi MPPT terminals of the inverter. Partial Parallel Connect The PV strings are connected to the inverter in both stand-alone and parallel connection. For example, one PV string connect to MPPT1 ad MPPT2, another PV string connect to MPPT3. Parallel Connect When an external PV string is connected to the PV input port on the inverter side, one PV string is connected to multiple PV input ports. 2 3 9.3.8 Setting Safety Parameters 215 NOTICE Set the custom safety parameters in compliance with local requirements. Do not change the parameters without the prior consent of the grid company. 9.3.8.1 Setting the Reactive Curve Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameter Settings > Reactive Power Mode to set the parameters. Step 2 :Set the parameters based on actual needs. Q(U) Curve 216 Cosφ Curve No. Parameters Description 1 Fix PF Enable Fix PF when it is required by local grid standards and requirements. After the parameters are set successfully, the power factor remains unchanged during the operation of the inverter. 2 Under-excited 3 Over-excited 4 Power Factor Fix PF Set the power factor as lagging or leading based on actual needs and local grid standards and requirements. Set the power factor based on actual needs. Range: 0-~0.8, or +0.8~+1. Fix Q 217 No. Parameters Description 1 Fix Q Enable Fix Q when it is required by local grid standards and requirements. 2 Overexcited/Underexcited Set the reactive power as inductive or capacitive reactive power based on actual needs and local grid standards and requirements. 3 Reactive Power Set the ratio of reactive power to apparent power. Q(U) Curve 1 Q(U) Curve Enable Q(U) Curve when it is required by local grid standards and requirements. 2 Mode Selection Set Q(U) curve mode, supporting basic mode and slope mode. Vn Voltage The percentage of actual voltage to the rated voltage at Vn point, n=1, 2, 3, 4. When set to 90, it means: V/Vrated% = 90%. 4 Vn Reactive Power The percentage of the reactive output power to the apparent power at Vn point, n=1, 2, 3, 4. For example, setting Vn Reactive Power to 48.5 means Q/Srated%=48.5%。 5 Voltage Deadband Width When Q(U) curve mode is set to slope mode, this parameter defines the voltage deadband range where no reactive power output is required. 6 Over-excitation Slope 7 Underexcitation Slope 3 8 Vn Reactive Power (In Q(U) slope mode) Sets the positive or negative slope for reactive power variation during over-voltage conditions. The percentage of the reactive output power to the apparent power at Vn point, n=1, 2, 3, 4. For example, setting Vn Reactive Power to 48.5 means Q/Srated%=48.5%。 218 No. Parameters Description 9 Q(U) Curve Response Time Constant The reactive power must reach 95% of the target value within 3 time constants, following a first-order low-pass filter curve. 10 Extended Function Enable the extended function and configure the corresponding parameters. 11 Lock-In Power 12 Lock-out Power When the inverter output reactive power to the rated power ratio is between the Lock-in power and Lock-out power, the ratio meets Q(U) curve requirements. Cosφ(P) Curve 1 Cosφ(P) Curve Enable Cosφ Curve when it is required by local grid standards and requirements. 2 Mode Selection Set cosφ(P) Curve Mode and support basic mode and slope mode configurations. 3 N-point Power The percentage of inverter output active power relative to rated power at the N-point. N=A, B, C, D, E。 4 N-point cosφ Value N-point Power Factor N=A, B, C, D, E。 5 Over-excitation Slope 6 Underexcitation Slope 7 N-point Power The percentage of inverter output active power relative to rated power at the N-point. N=A, B, C。 8 N-point cosφ Value N-point Power Factor N=A, B, C。 9 cosφ(P) Curve Response Time Constant The reactive power must reach 95% of the target value within 3 time constants, following a first-order low-pass filter curve. 10 Extended Function Enable the extended function and configure the corresponding parameters. When cosφ(P) curve mode is set to slope mode, configures the power variation slope as either positive or negative. 219 No. Parameters Description 11 Lock-in Voltage 12 Lock-out Voltage When the grid voltage is between Lock-in Voltage and Lock-out Voltage, the voltage meets Cosφ curve requirements. Q(P) Curve 1 Q(P) Curve Function Enable Q(P) Curve when it is required by local grid standards and requirements. 2 Mode Selection Set Q(P) curve mode, supporting basic mode and slope mode. 3 Pn-point Power The percentage of the output reactive power to the rated power at Pn point, n=1, 2, 3, 4, 5, 6. For example, setting to 90 means Q/Prated%=90%. 4 Pn-point Reactive Power The percentage of the output active power to the rated power at Pn point, n=1, 2, 3, 4, 5, 6. For example, When set to 90, it means: P/Prated% = 90%. 5 Over-excitation Slope 6 Underexcitation Slope When the Q(P) curve mode is set to slope mode, configure the power variation slope as either a positive or negative value. 7 Pn-point Power Ratio of reactive power to rated power at Pn points (n=1, 2, 3). For example, setting to 90 means Q/Prated%=90%. 8 Pn-point Reactive Power Ratio of active power to rated power at Pn points (n=1, 2, 3). For example, When set to 90, it means: P/Prated% = 90%. Time Constant The reactive power must reach 95% of the target value within 3 time constants, following a first-order low-pass filter curve. 9 220 9.3.8.2 Setting the Active Curve Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameter Settings> Active Power Mode to set the parameters. Step 2 : Set the parameters based on actual needs. P(F) Curve P(U) Curve 221 No. Parameter s Description 1 Output Active Power Set the inverter output power limit. 2 Power Gradient Set the change slope when the active output power increases or decreases. Over frequency Unloading 1 P(F) Curve According to the grid standards of some countries or regions, this function is enabled when the P(F) curve needs to be set. Set the Over frequency Unloading mode based on actual needs. 2 Over frequency Unloading mode 3 The inverter output active power will decrease when the utility Overfreque grid frequency is too high. The inverter output power will ncy decrease when the utility grid frequency is higher than Over Threshold frequency Threshold. 4 Buy and sell power conversion frequency 5 The inverter output active power will decrease when the utility Overfreque grid frequency is too high. The inverter output power will stop ncy decreasing when the utility grid frequency is higher thanOver Endpoint frequency Endpoint. • Slope mode: adjusts power based on the over frequency point and load reduction slope. • Stop mode: adjusts the power based on the over-frequency start point and over-frequency end point. When the set frequency value is reached, the system switches from selling electricity to buying electricity. 222 No. Parameter s Description 6 Overfrequency power slope reference power Adjust the inverter output power based on Apparent Active Power, Rated Active Power, Momentary Active Power, Or Max. Active Power. 7 Over frequency power slope The inverter output active power will increase when the utility grid frequency is too high. Indicates the slope when the inverter output power decreases. 8 Tentional Delay Ta Indicates the delayed response time when the inverter output power is higher than the Over frequency Threshold. 9 Hysteretic Power Recovery Slope Indicates the variation slope when the power recovers. 10 Frequency hysteresis point During over-frequency load reduction, if the frequency decreases, the power output is based on the lowest point of the load reduction power until the frequency is less than the hysteresis point and the power is restored. 11 Hysteresis waiting time For over-frequency load reduction and frequency decrease, when the frequency is less than the hysteresis point, the power recovery waiting time, that is, it takes a certain amount of time to recover the power. 12 Hysteresis power recovery slope reference power For over-frequency load reduction and frequency decrease, when the frequency is less than the hysteresis point, the power recovery benchmark, that is, the power recovery is based on the recovery slope * the rate of change of the reference power. Support: Pn rated power, Ps apparent power, Pm current power, Pmax maximum power, power difference (△P). 223 No. 13 Parameter s Hysteretic Power Recovery Slope Description For over-frequency load reduction and frequency reduction, when the frequency is less than the hysteresis point, the power change slope when the power is restored Underfrequency Loading 1 P(F) Curve According to the grid standards of some countries or regions, this function is enabled when the P(F) curve needs to be set. Set the Underfrequency Loading mode according to actual needs. 2 Underfrequ ency • Slope mode: adjust the power based on the under-frequency Loading point and the loading slope. mode • Stop mode: adjust the power based on the under-frequency start point and the under-frequency end point. 3 The inverter output active power will increase when the utility Underfrequ grid frequency is too low. The inverter output power will ency increase when the utility grid frequency is lower than Threshold Underfrequency Threshold. 4 Buy and sell power conversion frequency 5 The inverter output active power will increase when the utility Underfrequ grid frequency is too low. The inverter output power will stop ency increasing when the utility grid frequency is lower than Endpoint Underfrequency Endpoint. 6 Overfrequency power slope reference power When the set frequency value is reached, the system switches from selling electricity to buying electricity. Adjust the inverter output power based on Apparent Active Power, Rated Active Power, Momentary Active Power, Or Max. Active Power. 224 No. Parameter s Description 7 Underfrequ The inverter output active power will increase when the utility ency power grid frequency is too low. The slope of the inverter output slope power when it rises. 8 Tentional Delay Ta Indicates the delayed response time when the inverter output power is lower than the Underfrequency Threshold. 9 Hysteretic Power Recovery Slope Indicates the variation slope when the power recovers. 10 Frequency hysteresis point During underfrequency loading, if the frequency increases, the power is output according to the lowest point of the loaded power until the frequency is higher than the hysteresis point and the power is restored 11 Hysteresis waiting time For underfrequency loading, the frequency increases, when the frequency is higher than the hysteresis point, the waiting time for power recovery, that is, it takes a certain amount of time to recover the power 12 Hysteresis power recovery slope reference power For underfrequency loading, the frequency increases, when the frequency is higher than the hysteresis point, the benchmark for power recovery, that is, the power recovery is carried out according to the recovery slope * the rate of change of the benchmark power. Support: Pn rated power, Ps apparent power, Pm current power, Pmax maximum power, power difference (△P). 13 Hysteretic Power Recovery Slope For under-frequency loading, frequency increase, when the frequency is higher than the hysteresis point, the power change slope when power is restored 14 P(U) Curve Function According to the grid standards of some countries or regions, this function needs to be set when the P(U) curve is required. 225 No. Parameter s Description Vn Voltage The ratio of the actual value of the voltage at point Vn to the rated voltage, n=1,2,3,4. For example: when set to 90, it means: V/Vrated%=90%. Vn Active Power The ratio of the active power output of the inverter at point Vn to the apparent power, n=1,2,3,4. For example, setting Vn Reactive Power to 48.5 means P/Prated%=48.5%. 17 Output Response Mode Set the active power output response mode. Supports: First-order low-pass filtering, within the response time constant, output regulation is achieved according to the firstorder low-pass curve. Slope scheduling, output regulation is achieved according to the set power change slope. 18 Power Gradient When the output response mode is set to slope scheduling, active power scheduling is achieved according to the power change gradient. 19 PT-1 Behavior Tau Set the time constant within which the active power changes based on the first order LPF curve when the Output Response Mode is set to be PT-1 Behavior. 15 16 9.3.8.3 Setting grid protection parameters Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameters > Protection Parameters to set the parameters. Step 2: Set the parameters based on actual needs. No. Parameters Description 1 OV Stage n Trip Value Set the grid overvoltage protection threshold value, n=1,2,3,4. 2 OV Stage n Trip Time Set the grid overvoltage protection tripping time, n=1,2,3,4. 226 No. Parameters Description 3 UV Stage n Trip Value Set the grid undervoltage protection threshold value, n=1,2,3,4. 4 UV Stage n Trip Time Set the grid undervoltage protection tripping time. 5 10min Overvoltage Trip Set the 10min overvoltage protection threshold Threshold value. 6 10min Overvoltage Trip Set the 10min overvoltage protection tripping Time time. 7 OF Stage n Trip Value Set the grid overfrequency triggering n-th order protection point, n=1,2,3,4. 8 OF Stage n Trip Time Set the grid overfrequency trigger n-th order trip time, n=1,2,3,4. 9 UF Stage n Trip Value Set the grid underfrequency triggering n-th order protection point, n=1,2,3,4. 10 UF Stage n Trip Time Set the grid underfrequency trigger n-th order trip time, n=1,2,3,4. 9.3.8.4 Setting Connection Parameters Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameters > Protection Parameters to set the parameters. Step 2: Set the parameters based on actual needs. 227 No. Parameters Description Ramp Up 1 Upper Voltage The inverter cannot connect to the grid if it is powered on for the first connection and the grid voltage is higher than the Upper Voltage. 2 Lower Voltage The inverter cannot connect to the grid if it is powered on for the first connection and the grid voltage is lower than the Lower Voltage. 3 Upper Frequency The inverter cannot connect to the grid if it is powered on for the first connection and the grid frequency is higher than the Upper Frequency. 4 Lower Frequency The inverter cannot connect to the grid if it is powered on for the first connection and the grid frequency is lower than the Lower Frequency. 5 Observation Time The waiting time for connecting the inverter to the grid when meeting the following requirements. 1. The inverter is powered on for the first connection. 2. The utility grid voltage and frequency meet certain requirements. 6 Soft Ramp Up Enable the start up power slope. Gradient 7 Indicates the percentage of incremental output power per Soft Ramp Up minute based on the local requirements when the inverter is Gradient powered on for the first time. Reconnection 8 Upper Voltage The inverter cannot connect to the grid if it is reconnecting due to a fault and the grid voltage is higher than the Upper Voltage. 9 Lower Voltage The inverter cannot connect to the grid if it is reconnecting due to a fault and the grid voltage is lower than the Lower Voltage. 228 No. Parameters Description 10 Upper Frequency The inverter cannot connect to the grid if it is reconnecting due to a fault and the grid frequency is higher than the Upper Frequency. 11 Lower Frequency The inverter cannot connect to the grid if it is reconnecting due to a fault and the grid frequency is lower than the Lower Frequency. 12 Observation Time The waiting time for connecting the inverter to the grid when meeting the following requirements. 1. The inverter is reconnecting to the grid due to a fault. 2. The utility grid voltage and frequency meet certain requirements. 13 Reconnection Enable the start up power slope. Gradient 14 Indicates the percentage of incremental output power per minute based on the local requirements when the inverter is Reconnection powered on for the first time. For example, setting Gradient Reconnection Gradient to 10 means the reconnect slope is 10%P/Srated/min. 9.3.8.5 Setting Voltage Ride Through Parameters Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameters > Voltage Ride Through to set the parameters. Step 2 : Set the parameters based on actual needs. No. Parameters Description LVRT 1 UVn Voltage The ratio of the ride through voltage to the rated voltage at UVn point during LVRT. n=1,2,3,4,5,6,7。 2 UVn Time The ride through time at UVn point during LVRT. n=1,2,3,4,5,6,7 229 No. Parameters Description 3 Enter Into LVRT Threshold 4 Exit LVRT Endpoint 5 Slope K2 K-factor for reactive power during LVRT. 6 Zero Current Mode The system outputs zero current during LVRT. 7 Entry Threshold Set the entry threshold of zero current mode. 1 OVn Voltage The ratio of the ride through voltage to the rated voltage at OVn point during HVRT. n=1,2,3,4,5,6,7。 2 OVn Time The ride through time at OVn point during HVRT. n=1,2,3,4,5,6,7。 3 Enter High Crossing Threshold 4 Exit High Crossing Threshold 5 Slope K2 K-factor for reactive power during HVRT. 6 Zero Current Mode The system outputs zero current during HVRT. 7 Entry Threshold Set the entry threshold of zero current mode. The inverter will not be disconnected from the utility grid immediately when the grid voltage is between Enter Into LVRT Threshold and Exit LVRT Endpoint. HVRT The inverter will not be disconnected from the utility grid immediately when the grid voltage is between Enter High Crossing Threshold and Exit High Crossing Threshold. 230 9.3.8.6 Setting Frequency Ride Through Parameters Step 1 : Tap Home > Settings > Advanced Settings > Safety Parameters > Frequency Ride Through to set the parameters. Step 2 : Set the parameters based on actual needs. No. Parameters Description 1 UFn Frequency The frequency at the UFn point during frequency ride through. 2 UFn Frequency The frequency at the UFn point during frequency ride through. n=1,2,3。 3 UFn Time The ride through duration at the UFn point during frequency ride through. n=1,2,3。 4 OFn Frequency The frequency at the OFn point during frequency ride through. n=1,2,3。 5 OFn Time The ride through duration at the OFn point during frequency ride through. n=1,2,3。 9.3.9 Setting Generator/Load Control 9.3.9.1 Setting Generator/Load Control NOTICE • Loads and generators can be controlled by SolarGo app when the inverter supports load control function. • For ET40-50kW series inverters, the load control function is supported only when the inverter is used with STS. The inverter supports load control of the GENERATOR port or the BACKUP LOAD port. Step 1: Tap Home > Settings > Port Connection to set the parameters. Step 2: Select Generator Control or Load Control based on actual needs. 231 • Dry Contact Mode: when the switch is ON, the loads will be powered; when the switch is OFF, the power will be cut off. Turn on or off the switch based on actual needs. • Time Mode: set the time to enable the load, and the load will be powered automatically within the setting time period. Select standard mode or intelligent mode. No. Parameters Description 1 Standard The loads will be powered within the setting time period. 232 No. Parameters Description 2 Intelligent Once the excess energy of the photovoltaic exceeds the load nominal power within the time period, the loads will be powered. 3 Start Time 4 End Time The time mode will be on between the Start Time and End Time. 5 Repeat The repeat days. 6 The shortest load working time after the loads been Load Consumption powered. The time is set to prevent the loads be turned Time on and off frequently when the PV power fluctuates greatly. Only for Intelligent mode. 7 The loads will be powered when the excess energy of the Load Rated Power photovoltaic exceeds the nominal power of load. Only for Intelligent mode. • SOC Mode: the inverter has integrated dry contact controlling port, which can control whether the load is powered or not by contactor. In off-grid mode, the load connected to the port will not be powered if the BACKUP overload is detected or the battery SOC value is lower than the Off-grid battery protection value. Set Offgrid Battery Protection Value based on actual needs. 233 9.3.9.2 Setting the Generator Control NOTICE • When the inverter supports the generator control function, the generator can be controlled through the SolarGo App. • For ET40-50kW series inverters, the generator can be connected and controlled only when the inverter is used with STS. Step 1 : Tap Home > Settings > Port Connection to set the parameters. Step 2: Select Generator Connection or Load Connection based on actual needs. Step 3 : When setting the generator control function, select the generator type according to the actual access situation. Currently supported:Not Installed, Manual Control Of Generator or Automatic Control Generator. And set the parameters 234 according to the selected generator type. • Not Installed: If no generator is connected in the system, select Not Installed. • Manual Control Of Generator(Doesn’t Support Dry Node Connection): Start or stop the generator manually. The inverter cannot control the generator when Manual Control Of Generator(Doesn’t Support Dry Node Connection) is selected. • Automatic control generator (Supports dry node connection): If the generator has dry contact port and is connected to the inverter, set the generator control mode to Switch Control Mode or Automatic Control Mode based on actual needs. Switch Control Mode: The generator will start working when the Generator Dry Node Switch is on, and stop automaticallly after reaching Run Time. Automatic Control Mode: The generator will work during Run Time, but stop working during Prohibited Working Hours. ○ ○ 235 No. Parameters Description 1 Startup Mode Switch Control Mode/Automatic Control Mode Switch Control Mode 2 Generator Dry Node Switch Only for Switch Control Mode. 3 Run Time Set the generator’s continuous runtime, after which the generator will be turned off. Automatic Control Mode Prohibited Working Hours Set the time period during which the generator cannot work. 5 Run Time Set the generator’s continuous runtime, after which the generator will be turned off. If the generator start-up operation time includes prohibited working time, the generator will stop running during this time period; after the prohibited working time, the generator will restart running and timing. No. Parameters Description 4 Generator Information Settings 1 Rated Power Set the rated power of the generator. 2 Run Time Set the continuous running time of the generator. The generator will be shut down after the continuous running time ends. 3 Upper Voltage 4 Lower Voltage 5 Frequency Cap 6 Lower Frequency 7 Preheating time Set the operation voltage range of the generator. Set the operation frequency range of the generator. Set the generator no-load preheating time. Parameter settings for generator charging batteries 236 No. Parameters Description 8 Switch Select whether to use the generator to generate electricity to charge the battery. 9 Max.charging power (‰) The charging power when the generator generates electricity to charge the battery. 10 Start charging SOC When the battery SOC is lower than this value, the generator generates electricity to charge the battery. 11 Stop charging SOC When the battery SOC is higher than this value, stop charging the battery. 9.3.9.3 Set microgrid parameters NOTICE When the inverter supports microgrid function, you can set microgrid parameters through SolarGo App. Step 1 : Tap Home > Settings > Port Connection to set the parameters. Step 2 : According to the actual interface prompts, enter the microgrid control interface and set the microgrid parameters according to actual needs. 237 No. Parameters Description 1 Max.charging SOC Set the upper limit of charging SOC, and stop charging when the upper limit is reached. Manual wake-up • When the grid fails, if the battery power is low, the energy storage inverter cannot be supported to work off the grid. Click this button to force the energy storage inverter to output voltage to the grid-connected inverter, thereby starting the gridconnected inverter. • Single effect. 2 238 No. Parameters Description 3 Automatic wakeup • When the grid fails, if the battery power is low, the energy storage inverter cannot be supported to work off the grid. After enabling this function, the system will force the energy storage inverter to output voltage to the grid-connected inverter at a fixed time, thereby starting the grid-connected inverter. • Multiple effect. 4 Grid Import Power Limit Offset Set the adjustable range of the maximum power that the device can actually buy from the grid. 9.3.10 Setting the meter parameters 9.3.10.1 Meter/CT-Assisted Test Meter/CT-Assisted Test is used to auto-check if the Smart Meter and CT are connected in the right way and their working status. Step 1 : Tap Home > Settings > Meter/CT Assisted Test to set the function. Step 2 : Tap Start Test to start test. Check Test Result after test. 239 9.3.11 Equipment Maintenance 9.3.11.1 Checking Firmware Information/Upgrading Firmware Version Upgrade the DSP version, ARM version, BMS version, AFCI version, or STS version of the inverter, or firmware version of the communication module. Some devices do not support upgrading the firmware version through SolarGo app. NOTICE If the Firmware Upgrade dialog box pops up once logging into the app, click Firmware Upgrade to directly go to the firmware information page. 9.3.11.1.1 Upgrade the Firmware 240 NOTICE • When there is a red dot on the right side of the firmware information, please click to view the firmware update information. • During the upgrade process, please ensure that the network is stable and the device is connected to SolarGo, otherwise the upgrade may fail. Step 1 : Tap Home > Settings > Firmware Information to check the firmware version. Tap Firmware Upgrade after the inverter is logged in, if the firmware upgrade dialog box pops up, Step 2 : (Optional) tap Check For Update to confirm whether the latest firmware version is available for updating. Step 3: Tap Firmware Upgrade to enter the firmware upgrade interface. Step 4 : (Optional) Tap Learn More to view firmware-related information, such as the current version, the latest version, firmware update records, etc. Step 5 : Tap Upgrade and complete the upgrade according to the prompts on the interface. 241 9.3.11.1.2 Upgrade the Firmware NOTICE • When there is a red dot on the right side of the firmware information, please click to view the firmware update information. • During the upgrade process, please ensure that the network is stable and the device is connected to SolarGo, otherwise the upgrade may fail. Step 1 : Tap Home > Settings > Firmware Information. Tap Firmware Information as prompted to enter the firmware upgrade page. Step 2 : Tap Upgrade and follow the prompts to complete the upgrading. If you only need to upgrade a specific firmware version, tap Learn More to check the firmware related information and tap Firmware Upgrade below the firmware version you want to upgrade, and follow the on-screen prompts to complete the operation. Step 3 : Tap Learn More to view all current firmware version information. Step 4: (Optional)Tap ,to view the version upgrade record. 9.3.11.1.3 Automatic Upgrade 242 NOTICE • When using WiFi/LAN Kit-20 or WiFi Kit-20 module communication and the module firmware version is V2.0.1 or above, the device automatic upgrade function can be enabled. • After the device automatic upgrade function is enabled, if the module version is updated and the device has been connected to the network, the corresponding firmware version can be automatically upgraded. Step 1 : Tap Home > Settings > Firmware Information. Step 2 : Enable or disable the automatic device upgrade function according to actual needs. 9.3.11.2 Change the Login Password NOTICE The login password can be changed. Keep the changed password in mind after changing it. Contact the after-sales service if you forget the password. Step 1 : Tap Home > Settings > Change Login Password to change the password. Step 2 :Change the password based on actual needs. 243 244 10 Power Plant Monitoring 10.1 SEMS+ 10.1.1 APP Introduction SEMS+ App is a software for power plant monitoring and control, which allows you to remotely manage the power plant and equipment, view the operating data of the power plant, alarm messages and so on. 10.1.1.1 Complementary Products Support monitoring and management of related equipment from the GoodWe brand, such as inverters, smart meters, data loggers, charging stations, batteries, etc. 10.1.1.2 Downloading and Installing the App Make sure that the mobile phone meets the following requirements: • Mobile phone operating system: Android 6.0 or later, iOS 13.0 or later. • The mobile phone can access the Internet. • The mobile phone supports WLAN or Bluetooth. Download Method: Method 1: Search SEMS+ in Google Play (Android) or App Store (iOS) to download and install the App. Method 2: Scan the QR code below to download and install the App. 245 10.1.1.3 Connection Method 10.1.1.4 Setting Language and Server NOTICE Supports automatic server adaptation based on login account information. If you need to set it up yourself, when selecting the server, please confirm that the selected region matches the region associated with your account, otherwise you will not be able to log in. Please select the app display language according to your actual needs, and select the corresponding server according to your actual location. 10.1.1.5 Setting Communication Parameters The SEMS+ app supports connecting devices via Bluetooth or WiFi and configuring device network parameters to enable remote monitoring or device management. 246 NOTICE When the device model or smart communication stick type is different, the device name displayed will be different. *** is the device serial number: • Wi-Fi/LAN Kit; Wi-Fi Kit; Wi-Fi Box: Solar-WiFi*** • WiFi/LAN Kit-20: WLA-*** • WiFi Kit-20: WFA-*** • Ezlink3000: CCM-BLE***; CCM-***; *** • 4G Kit-CN-G20/4G Kit-CN-G21: GSA-***; GSB-*** • Charging pile: *** 10.1.2 Account Management 10.1.2.1 Registering Step 1: Click Register on the app's home page to enter the account registration interface. Step 2: Select the account type based on your actual needs, then click Next. Step 3: Enter your account information according to the actual situation, and click Register to complete the registration. 10.1.2.2 Login NOTICE • Before logging into the App, please register or get your account and password through your dealer. • After logging in your account, you can view or manage power station information, please refer to the actual interface. Step 1: Enter your account number and password, read and check the login agreement, and click Log In. 10.1.2.3 Switch Step 1: On the My interface, click Log Out > Log in with Another Account. Step 2: Select an existing account or add a new account based on your actual needs. 247 10.1.2.4 Canceling Step 1: On the My interface, click Account & Security. Step 2: Click Close Account, enter your account password, and click Submit. 10.1.2.5 Account Permissions The SEMS+ app supports different account types with different permissions. The operating permissions for different account types vary. Please refer to the table below for details. Top-level Secondary Third-level Four-level Five-level menu menu menu menu menu Permissions Administrators, Login & Register - - - - installers, marketing personnel, owners, visitors Administrators, Monitoring Information - - - installers, marketing personnel, owners, visitors Overview Administrators, Create Station - - - installers, owners, visitors Administrators, Station List - - - installers, marketing personnel, owners, visitors Administrators, Monitoring Station - - installers, marketing personnel, owners, visitors Station Details Add Device Device Device List 248 - Administrators, installers, and owners Search Administrators, Device installers, marketing personnel, owners, visitors Replace Administrators, Device installers, and owners Edit Device installers, and owners Delete Administrators, Device installers, and owners Device Monitoring Info Device Details Administrators, Device Remote Control Device Remote Upgrade Administrators, installers, marketing personnel, owners, visitors Administrators, installers, and owners Administrators and installers Administrators, Alarms - - installers, marketing personnel, owners, visitors Edit Station Delete Station Station Configuratio n Replacement History User Information - - n installers, and owners Administrators, installers, and owners Administrators, - installers, marketing personnel, owners - Administrators, installers, and owners Administrators, Home Configuratio Administrators, - installers, marketing personnel, owners, visitors 249 Administrators, Create Station - - - installers, owners, visitors Administrators, Alarm - - - - installers, marketing personnel Administrators, Warranty - - installers, marketing personnel, owners, visitors Report Center Administrators, - - installers, marketing personnel, owners Administrators, GoodWe Services News - - installers, marketing personnel, owners, visitors Administrators, Announceme nts Services - - installers, marketing personnel, owners, visitors Administrators, Community - - installers, marketing personnel, owners, visitors Create Station Administrators, - - installers, owners, visitors Administrators, Tools Network Link - - installers, marketing personnel, owners, visitors DNSP - - 250 Administrators, installers, marketing personnel, owners, visitors Administrators, Help - - - installers, marketing personnel, owners, visitors Administrators, User Profile - - - installers, marketing personnel, owners, visitors Administrators, User Information - - - installers, marketing personnel, owners, visitors Administrators, Setting - - - installers, marketing personnel, owners, visitors Administrators, Email My - - installers, marketing personnel, owners, visitors Administrators, Password - - Account installers, marketing personnel, owners, visitors Security Secondary Account Administrators, - - installers, marketing personnel Administrators, Close Account - - installers, marketing personnel, owners, visitors Auth Remote - - 251 Administrators, Management Control Auth installers, marketing personnel, owners, visitors Monitoring Auth - - Owners Administrators, Apps - - - installers, marketing personnel, owners, visitors Administrators, About - - - installers, marketing personnel, owners, visitors Administrators, Logout - - installers, marketing personnel, owners, visitors Logout Administrators, Login anther Account - - installers, marketing personnel, owners, visitors 10.1.3 Viewing Power Plant Information 10.1.3.1 View All Power Plant Overview Information After logging into the SEMS+ App with your account password, you can view an overview of the power generation status of all power plants in your current account on the monitoring page. Or, on the power plant page, arrange all power plant lists by different sorting and filtering conditions to view detailed information about the power plants. 252 No. Description Display the total power generation of all power plants, including: today's power 1 generation, this month's power generation, this year's power generation, and total power generation. When the number of power plants is greater than or equal to 10, the power generation volume for that year is not displayed. Display total installed capacity and power plant operating status. The operating 2 status of a power station is classified as: Running, Waiting, Offline, or Faulted. The power station status is only Running when all equipment in the power station is operating normally. Display statistical charts showing the power plant's electricity generation for the 3 current month, the current year, or total electricity generation, or statistical charts comparing electricity generation with the previous year. Click to enlarge the statistical chart. 4 Display environmental contribution data such as CO₂ Reduction, Trees Planted Equivalent, and Standard Coal Saved. 5 Power Plant Creation. 6 Search for power stations. Enter the SN, power station name, or email address to quickly search for the corresponding power station. 7 Power plant operation status. Display the current power plant operating status and the number of power plants operating in each status. Click on the operating status to filter power plants with the corresponding operating status. 8 • Set up a list of power plants to display KPI indicators: Current Power, Rev. Today, Rev. Total, Gen. Today, Gen. Total • Set the sorting method for the power station list: By Default, By Capacity • Set the display mode for the power station list: Station Card, Station List • Set the selection method for the power station list: Scope, Category, Capacity 9 Power station. Click on the name of the power station to view detailed information about it. Different types of power stations display different information. Please refer to the actual situation. 253 10.1.3.2 Viewing Monopower Plant Details Step 1: If there are multiple power stations, you can quickly search for them on the power station page by entering the equipment SN, power station name, or email address. Step 2: Click on the power plant name to enter the power plant details interface and view detailed information. 10.1.3.2.1 Viewing Power Plant Details (Traditional Mode) No. Description 1 Current power plant name. 2 Collect Power Plant. 3 Configure power plant information. Support: Configure basic power plant information, modify user information, add power plant photos, set PV component layout, etc. 4 The chart displays current power plant operation information, such as energy flow diagrams, power generation, load power consumption, AC output, and other information. 5 • Device List. Display equipment currently used in power stations, such as inverters, batteries, data collectors, charging stations, etc. • Click on the device card to view detailed information about the device. 6 Power plant alarm information. 10.1.4 Viewing Alarm Information 254 10.1.4.1 Viewing Alarm Information for All Power Plants Step 1: Click the Fault tab on the power plant detailed page to enter the alarm query page. Step 2: (Optional) Enter the power station name or equipment SN number in the search box to quickly locate the power station or equipment you want to view. Step 3: Click on the alarm name to view detailed alarm information. 10.1.4.2 Viewing the current power plant's alarm information 10.1.4.2.1 Viewing Alarm Information for the Current Power Plant (Traditional Mode) Step 1: If there are multiple power plants, click on the power plant name on the power plant list page to enter the power plant details page. Step 2: Click Alarms to go to the alarm page and check out the alarm details. Click to filter alert information according to actual needs. 255 10.1.4.3 Viewing the Current Device’s Alarm Information Step 1: If there are multiple power plants, click on the power plant name on the power plant list page to enter the power plant details page. Step 2: Select a device from the device list to enter the device details page. If there are any alerts, you can view the 10 most recent alerts directly on the device details page. 256 10.1.5 Viewing Power Plant Report Information Viewing Power Plant Report Step 1: Click Service > Report Center to enter the report center interface. Step 2: Select the time period you want to query, search for the power plant you want to query, and click on the power plant name to enter the report interface. To download the report, click > Export. 257 Viewing Power Plant Bills Step 1: Click Service > Report Center to enter the report center interface. Step 2: Select the time period you want to query, search for the power station you want to query, swipe left and click to enter the Bill interface to view the bill. 258 10.1.6 Power Plant Management 10.1.6.1 Power Plant Creation Step 1: Click on the home page or power station list page, or click Create Station on the account page. Step 2: Based on the actual situation, fill in the relevant information about the power station in the Create Station interface. Step 3: Click Save & Exit to complete the power plant creation. At this point, no equipment has been added to the power plant. Alternatively, click Save & Continue to enter the equipment addition interface and enter the relevant equipment information based on the actual situation. Multiple pieces of equipment can be added. 259 10.1.6.2 Configuring Power Plant Information NOTICE After the power station has been successfully created, you can update the power station configuration information according to actual needs. When the configuration information entered conflicts with the actual conditions of the power station, the actual conditions of the power station shall prevail. The basic information provided here is for reference only. Step 1: (Optional) If there are multiple power plants, select the power plant you want to set up in the power plant list interface. Step 2: On the power plant details page, click >Basic Information to access the information viewing interface. Step 3: Click to enter the information modification interface, modify the information according to your actual needs, and click Confirm to save the changes. 10.1.6.3 Power Plant Visitors Management Supports adding power plant visitors to view basic power plant information. Visitors to the power station cannot view all interfaces. Please refer to the actual interface. Step 1: (Optional) If there are multiple power plants, select the power plant you want 260 to set up in the power plant list interface. Step 2: In the power station details interface, go to >User Information>Add to enter the visitor addition interface. Step 3: After entering the visitor information, click Confirm to complete the addition. To delete an added visitor, select the visitor you want to delete in the User Information interface, swipe right, and click Delete. 10.1.6.4 Power Plant Photos Management Add photos of power plants to quickly identify different power plants. Step 1: (Optional) If there are multiple power plants, select the power plant you want to set up in the power plant list interface. Step 2: On the power station details page, click >Station Photos>Add to enter the power station photo addition interface. Step 3: Follow the prompts on the screen to add photos by selecting Take a Photo or Choose from Album. If you need to delete power plant photos, please refer to the following steps. 10.1.6.5 Setting PV Component Layout Set the PV Layout Design parameters based on the actual PV module conditions. The information here is for recording PV layout only and will not change the actual PV layout. Step 1: (Optional) If there are multiple power plants, select the power plant you want to set up in the power plant list interface. Step 2: Enter the adjustment interface via > PV Layout Design. Step 3: Click Row/Column and arrange the components in each row and column according to the actual PV component installation situation. Step 4: Click Array Name to enter the Array Settings interface, and set the PV array name, angle, and orientation information according to the actual situation. 10.1.6.6 Adjusting the Information Displayed on the Power Station Details Page The content displayed on the power plant details page can be adjusted according to actual needs, such as displaying or hiding the Energy Flow Chart, or placing the Energy Flow Chart at the top or bottom of the interface. Step 1: (Optional) If there are multiple power plants, select the power plant you want 261 to set up in the power plant list interface. Step 2: Go to the power plant details page and click > Home Configuration. Step 3: Based on actual needs, refer to the interface prompts to select the information to be displayed, or adjust the display order of each piece of information. 10.1.6.7 Deleting Power Plant NOTICE For power plant visitors, deleting a power plant only means unlinking this power plant from the visitor's account. Step 1: (Optional) If there are multiple power plants, click on the power plant name to enter the power plant details page. Step 2: Click on the power plant details interface. Step 3: Click Delete, then click Confirm to delete the current power station. 10.1.6.8 Collect Power Plant If there is a power plant you want to follow, click on the power plant on the right side to bookmark it. Click again to cancel the bookmark. Click and select Favorited in the filter Scope to display all your favorite power plants. 10.1.7 Managing the Equipment in the Power Plant 10.1.7.1 Additional Equipment 262 NOTICE • When the type of power station varies, the type of equipment supported to be added is different, please refer to the actual interface. • When Environmental Monitor is connected to a data collector, it can be added to the station to view the data collected by Environmental Monitor. Step 1: Click the name of the plant on the plant list page to enter the plant details page. Step 2: Click Device > to enter the Add Device interface. Step 3: Select the type of device to be added according to actual needs. Step 4: Scan for devices or manually add devices according to the interface prompts. When scanning to add, select the desired device from the scanned devices to add that device. When adding manually, add the device by scanning the device QR code or manually entering the device information. The interface for adding devices varies for different device types, so please refer to the actual situation. Step 5: When adding devices manually, if there is a need to add more than one device, return to the Power Station Details screen and repeat steps 3 and 4. 263 10.1.7.2 Editing Device Information Modification of equipment names in power stations is supported. Step 1: (Optional) If there are multiple power plants, click on the power plant name to enter the power plant details page. Step 2: On the power station details interface, click Device to enter the device information page. Select the device you want to edit, swipe left, and tap . Step 3: Enter the new device name and click Submit. 10.1.7.3 Deleting Device Step 1: (Optional) If there are multiple power plants, click on the power plant name to enter the power plant details page. Step 2: On the power station details interface, click Device to enter the device information page. Select the device you want to alternate, swipe left, and tap . Step 3: Read the pop-up prompt and click OK to delete the current device. 10.1.7.4 Upgrading Device Firmware Version Step 1: (Optional) If there are multiple power plants, select the power plant you want to set up in the power plant list interface. Step 2: Click Device to enter the device information page, and select the device for which you want to upgrade the firmware version. Step 3: Click on the device serial number in the middle of the page to enter the 264 Firmware Version page. If there is an upgrade available, click Upgrade and follow the instructions on the screen to upgrade your device. Click to view the firmware upgrade history. 10.1.8 Remote Management Device NOTICE • After completing the creation of the power station and adding equipment to it, you can remotely set device parameters via the SEMS+ app. • Before setting parameters, please carefully read this manual and the user manual for the corresponding model of equipment to familiarize yourself with the product's functions and features. Incorrect grid parameter settings may cause devices to fail to connect to the grid or fail to connect to the grid in accordance with grid requirements when operations such as starting grid connection and stopping grid connection are issued to the devices, thereby affecting power generation. • Only for use by professionals who are familiar with local regulations and standards, electrical systems, and who have received professional training and are knowledgeable about this product. • Different account permissions have different parameters that can be set remotely. The interface is displayed based on the actual account used. Please refer to the actual interface. • Different device models have different parameter setting interfaces. Please refer to the actual device for details. 10.1.8.1 Setting Energy Storage Inverter Parameters Step 1: (Optional) If there are multiple power plants, select the power plant you want to set up in the power plant list interface. Step 2: Click Device to enter the device information page, and select the device for which you want to upgrade the firmware version. Step 3: Click , read the interface prompts, and set the inverter parameters according to actual needs. 265 No. Parameter Description Safety Based on the grid standards of the country/region where the inverter is located, as well as the application scenario settings of the inverter. 2 Battery Model Set the battery type. 3 Depth of Discharge (OnGrid) The maximum depth of discharge of the battery when the system is working on-grid. 4 Depth of Discharge (OffGrid) The maximum depth of discharge of the battery when the system is working off-grid. 1 Battery 5 Backup SOC Holding 6 SOC Protection The battery will be charged to preset SOC protection value by utility grid or PV when the system is running on-grid, so that the battery SOC is sufficient to maintain normal working when the system is off-grid. Start battery protection when the battery capacity is lower than the Depth of Discharge. 266 No. Parameter Description This option is displayed on the interface when a battery that supports heating is connected. After the battery heating function is turned on, when the temperature is below the value that starts up the battery, PV power or electricity from the grid will be used to heat the battery. Heating Mode: • GW5.1-BAT-D-G20/GW8.3-BAT-D-G20 Low Power Mode: Maintains minimum battery power input capacity, turns on when the temperature is below -9℃, and turns off when the temperature is above or equal to -7℃. Medium Power Mode: to maintain the moderate power input capacity of the battery. It will be turned on when the temperature is less than 6℃, and turned off when it is greater than or equal to 8℃. High Power Mode: to maintain the higher power input capacity of the battery. It will be turned on when the temperature is less than 11℃, and turned off when it is greater than or equal to 13℃. • GW14.3-BAT-LV-G10 Low Power Mode: Maintains minimum battery power input capacity, turns on when the temperature is below 5℃, and turns off when the temperature is above or equal to 7℃. Medium Power Mode: to maintain the moderate power input capacity of the battery. It will be turned on when the temperature is less than 10℃, and turned off when it is greater than or equal to 12℃. High Power Mode: to maintain the higher power input capacity of the battery. It will be turned on when the temperature is less than 20℃, and turned off when it is greater than or equal to 22℃. ○ ○ 7 Battery Heating ○ ○ ○ ○ 8 Daily Heating Period Set the battery heating time period according to actual needs. 267 No. Parameter 9 Battery Wake-up After being turned on, the battery can be awakened when it shuts down due to undervoltage protection. Battery Breathing Light • Only applicable to inverters of ESA 3-10kW series. Set the duration of the device's breathing light flashes. Support: Normally open, normally closed, 3 minutes. • The default mode is to turn on for three minutes after powering up and then automatically turn off. 10 Description Mode 268 No. Parameter Description Set the working mode of the inverter according to actual needs. • Self-use Mode BACK-UP Mode: Recommended for use in areas with unstable power grids. When the grid is disconnected, the inverter turns to off-grid mode and the battery will supply power to the BACKUP loads; when the grid is restored, the inverter switches to grid-tied mode. Economic Mode: It is recommended to use TOU mode in scenarios when the peak-valley electricity price varies a lot. Select TOU mode only when it meets the local laws and regulations. Based on actual needs, during off-peak hours, the battery can be set to charging mode to purchase electricity from the grid for charging; during peak hours, the battery can be set to discharge mode to supply power to the load through the battery. • Delayed charging: Suitable for areas with grid connection power output restrictions. By setting peak power limits and charging time periods, photovoltaic power generation that exceeds grid connection limits can be used to charge batteries, reducing photovoltaic waste. • Demand-based electricity fee management: Mainly applicable to scenarios where peak power consumption is limited. When the total power consumption of the load exceeds the power quota within a short period of time, battery discharge can be used to reduce the amount of power consumption exceeding the quota. ○ ○ 11 Working Mode 12 On-Grid Power Limitation Enable Power Limit when power limiting is required by local grid standards and requirements. 13 Maximum OnGrid Output Power Set the value based on the actual maximum power feed into the utility grid. 269 No. Parameter 14 Power Factor 15 Q(U) 16 COS(φ) 17 P(F) Description Set the power factor according to actual needs. When Q(U) curves need to be set according to the power grid standards of certain countries or regions, enable this function. When Cosφ curves need to be set according to the power grid standards of certain countries or regions, enable this function. When P(F) curves need to be set according to the power grid standards of certain countries or regions, enable this function. Others 18 Backup Supply 19 Shadow Scan After enabling Backup, the battery will power the load connected to the BACK-UP port of the inverter to ensure Uninterrupted Power Supply when the power grid fails. When photovoltaic panels are severely shaded, enabling the shadow scanning function can optimize the power generation efficiency of the inverter. 270 11 Maintenance 11.1 Power Off the System DANGER • Power off the equipment before operations and maintenance. Otherwise, the equipment may be damaged or electric shocks may occur. • Delayed discharge. Wait until the components are discharged after power off. • Push the air switch to restart the battery. • Strictly follow the power off requirements to avoid damaging the system. • When there are multiple batteries in the system, powering off any one of the batteries can power off all the batteries. NOTICE • Install the circuit breaker between the inverter and the battery or between the two batteries in compliance with local laws and regulations. • To ensure effective protection, the cover of the battery system switch should remain closed. The cover can be closed automatically after being opened. Fasten the cover with screws if the switch is not to be used for a long-term period. Power down process 1. Turn off the BACK-UP circuit breaker. 2. Turn off the ON-GRID circuit breaker. 3. (Optional) Turn off the GEN circuit breaker. 4. (Selected in accordance with local laws and regulations) Turn off the circuit breaker between the PV module and the inverter. 5. Turn off the DC switch of the inverter. 6. (Selected in accordance with local laws and regulations) Turn off the switch between the inverter and the battery. 7. Turn off the battery system switch. 8. Turn off the battery system switch (LX A5.0-10, LX A5.0-30). Turn off the battery 271 system integrated circuit breaker or press and hold the battery system button for ≥5 seconds, and the battery system integrated circuit breaker will automatically turn off(only applicable to LX U5.0-30). 11.2 Removing the Equipment DANGER • Make sure that the equipment is powered off. • Wear proper PPE during operations. • Please use standard disassembly tools when removing wiring terminals to avoid damaging the terminals or equipment. • Unless otherwise specified, the dismantling process of the equipment is in reverse order to the installation process, and it will not be further elaborated in this document. 1. Power off the System. 2. Label the cables connected in the system with tags indicating the cable type. 3. Disconnect the connecting cables of the inverter, battery, and smart meter in the system, such as DC cables, AC cables, communication cables, and PE cables. 4. Remove equipment such as the smart dongle, inverter, battery, and smart meter. 5. Properly store the equipment and ensure that the storage conditions meet the requirements if it needs to be put into use later. 11.3 Disposing of the Equipment If the equipment cannot work anymore, dispose of it according to the local disposal requirements for electrical equipment waste. The equipment cannot be disposed of together with household waste. 11.4 Routine Maintenance WARNING 272 • Contact after-sales service for help if you find any problems that may influence the battery or the hybrid inverter. Disassemble without permission is strictly forbidden. • Contact after-sales service for help if the copper conductor is exposed. Do not touch or disassemble privately because high voltage danger exists. • In case of other emergencies, contact the after-sales service as soon as possible. Operate following the instructions or wait for the after-sales service personnel. Maintainin g Item Maintaining Method Maintainin g Period Maintaining Purpose System clean Check the heat sink, air intake, and air outlet for foreign matter or dust. Check whether the installation space meets requirements and whether there is any debris around the device. Once half a year Prevent heat dissipation failures. Once 6-12 months Ensure that the equipment is installed securely. Once 6-12 months Confirm the reliability of electrical connections. Once a year Confirm that the machine seal and waterproof performance are intact. System installation Electrical connection Sealing Check whether the equipment are installed securely and whether the screws are installed tightly. Check whether the equipment is damaged or deformed. Check whether the cables are securely connected. Check whether the cables are broken or whether there is any exposed copper core. Check whether all the terminals and ports are properly sealed. Reseal the cable hole if it is not sealed or too big. 273 Maintainin g Item Maintaining Method Maintainin g Period Maintaining Purpose Battery maintenanc e If the battery is not used for a long time or is not fully charged, it is recommended to charge the battery regularly. Once/15 days Protect the battery's lifespan. 11.5 Fault 11.5.1 Viewing Fault/Alarms Information All detailed information about faults/alarms in the energy storage system is displayed on the SolarGo App, SEMS Portal App, and LCD display screen. If your product has any abnormalities and no relevant fault information is seen on the SolarGo App, SEMS Portal App, or LCD display screen, please contact the after-sales service center. • Viewing method one: LCD screen Click or select the fault information icon system alarms or fault information. on the screen to view energy storage • Viewing Method 2: SolarGo App View energy storage system alarm information through Home>Parameters>Alarms. • Viewing Method 3: SEMS Portal App 1. Open the SEMS Portal App and log in with any account. 2. All power station fault information can be viewed through the Power Plant >Alarm. 3. Click on the specific fault name to view detailed information about the fault: [time of occurrence], [possible cause], and [solution]. 11.5.2 Fault Information and Troubleshooting Please follow the below methods to troubleshoot fault. If the troubleshooting methods do not resolve the issue, please contact the after-sales service center. When contacting the after-sales service center, please collect the following 274 information to facilitate a quick resolution. 1. Product information, such as: serial number, software version, device Installation time, fault occurrence time, fault occurrence Frequency, etc. 2. Equipment Installation environment, such as weather conditions, whether the modules are obstructed, shaded, etc. It is recommended to provide photos, videos, and other files to assist in problem analysis. 3. Utility grid status. If the system encounters an issue not listed, or if following the instructions does not resolve the problem or abnormality, immediately cease system operation and contact your distributor without delay. No. 1 Fault Unable to detect smart dongle wireless signal Solution Measures 1. Please ensure that no other devices are connected to the smart dongle wireless signal. 2. Please ensure the SolarGo app is updated to the latest version. 3. Ensure the power supply of the smart dongle is normal, with the blue signal light flashing or steadily lit. 4. Ensure the smart device is within the communication range of the smart dongle. 5. Refresh the App device list. 6. Restart inverter. 2 Unable to connect to smart dongle wireless signal 1. Please ensure that no other devices are connected to the smart dongle wireless signal. 2. Restart the inverter or smart dongle and try to reconnect to the smart dongle wireless signal. 3. Ensure that bluetooth is successfully encrypted and paired. 275 No. Fault Solution Measures 1. Please ensure that the router is turned on. 3 4 5 6 7 Ezlink indicator flashes twice Ezlink indicator flashes four times Ezlink indicator extinguishing Ezlink indicator extinguishing Unable to find router SSID 2. When using LAN communication, ensure that the LAN cable is properly connected and the communication configuration is correct. Enable or disable the DHCP function based on actual conditions. 3. When using WiFi communication, ensure that the wireless network connection is normal and the wireless signal strength meets the requirements. Enable or disable the DHCP function based on actual conditions. 1. Please ensure that the smart dongle is properly connected to the router via WiFi or LAN, and that the router has normal Internet access. 2. If the issue is not resolved, please contact the aftersales service center. Please ensure that the inverter has been power on. If the issue persists, please contact the after-sales service center. Please ensure that inverter is powered on. 1. Place the router close to the smart dongle, or add a WiFi repeater to enhance the WiFi signal. 2. Reduce the number of devices connected to the router. 276 No. Fault Solution Measures 1. Restart inverter. 8 After all configurations are completed, the smart dongle fails to connect with the router. 9 After all configurations are completed, smart dongle fails to connect with server. 2. Check if the network name, encryption method, and password in the WiFi configuration are the same as those in router. 3. Restart router. 4. Place the router closer to the smart dongle, or add a WiFi repeater to enhance the WiFi signal. Restart router and inverter. 11.5.2.1 System failure. If unlisted problems occur in the system, or if following the instructions does not stop the problem or abnormality, stop operating the system immediately and contact your dealer immediately. No. 1 Fault Unable to search for the wireless signal of the smart dongle. Solutions/measures to address the issue 1. Please ensure that no other devices are connected to the smart dongle's wireless signal. 2. Please ensure that the SolarGo app has been updated to the latest version. 3. Please ensure that the smart dongle is powered on properly, and the blue indicator light is blinking or steady on. 4. Ensure that the smart device is within the communication range of the smart dongle. 5. Refresh the device list in the app. 6. Restart the inverter. 277 No. Fault Solutions/measures to address the issue 2 Unable to connect to the wireless signal of the smart dongle. 1. Please ensure that no other devices are connected to the smart dongle's wireless signal. 2. Restart the inverter or smart dongle, and try to reconnect to the wireless signal of the smart dongle again. 3. Ensure successful pairing of Bluetooth. 1. Make sure that the router is powered on. 3 2. When communicating via LAN, make sure that both LAN cable connection and LAN configuration are proper. Enable or disable DHCP based on actual needs. The Ezlink indicator flashes 3. When communicating via WiFi, make sure that the wireless network connection is OK and the wireless twice. signal strength meets the requirements. Enable or disable DHCP based on actual needs. 4 1. Make sure that the smart dongle is connected to the router via WiFi or LAN properly, and the router can The Ezlink access the Internet. indicator flashes 2. If the problem persists, contact the after sales service. four times. 5 Make sure that the inverter is powered on. If the problem persists, contact the after sales service. If the problem persists, contact the after sales service. 6 7 The Ezlink indicator is off. The Ezlink indicator is off. Cannot find router SSID. Make sure that the inverter is powered on. If the problem persists, contact the after sales service. 1. Put the router nearer to the Smart Dongle. Or add a WiFi relay device to enhance the WiFi signal. 2. Reduce the number of devices connected to router. 278 No. Fault Solutions/measures to address the issue 1. Restart the inverter. 8 After completing all configurations, the Smart Dongle fails connecting to the router. 9 After completing all configurations, the Smart Dongle fails connecting to the router. 2. Check if the SSID, encryption method and password on WiFi configuration page are the same with that of Router. 3. Restart the router. 4. Put the router nearer to the Smart Dongle. Or add a WiFi relay device to enhance the WiFi signal. Restart the router and the inverter. 11.5.2.2 Inverter Troubleshooting No. 1 Fault Cause Troubleshooting Suggestions Grid Power Outage 1.Utility grid power fails. 2. The AC circuit or the AC breaker is disconnected. 1. The alarm is automatically cleared after the grid power supply is restored. 2. Check whether the AC cable is connected and the AC breaker is on. 279 No. Fault Cause Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If it occurs frequently, please check if the grid voltage is within the allowable range. 2 Grid Overvoltage The grid voltage is higher than the permissible range or the high voltage duration exceeds the high voltage ridethrough setting. • Contact the local power company if the grid voltage exceeds the permissible range. • Modify the overvoltage protection threshold, HVRT or disable the overvoltage protection function after obtaining the consent of the local power company if the grid frequency is within the permissible range. 3. Check whether the AC breaker and the output cables are connected securely and correctly if the problem persists. 280 No. Fault Cause Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If it occurs frequently, please check if the grid voltage is within the allowable range. 3 Grid Undervoltage The grid voltage is lower than the permissible range, or the duration of low voltage exceeds the requirement of LVRT. • Contact the local power company if the grid voltage exceeds the permissible range. • Modify the undervoltage protection threshold, LVRT or disable the undervoltage protection function after obtaining the consent of the local power company if the grid frequency is within the permissible range. 3. Check whether the AC breaker and the output cables are connected securely and correctly if the problem persists. 281 No. Fault Cause Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If it occurs frequently, please check if the grid voltage is within the allowable range. 4 Grid Rapid Overvoltage The grid voltage is detected to be abnormal or ultrahigh. • Contact the local power company if the grid voltage exceeds the permissible range. • Modify the undervoltage protection threshold, LVRT or disable the undervoltage protection function after obtaining the consent of the local power company if the grid frequency is within the permissible range. 3. Check whether the AC breaker and the output cables are connected securely and correctly if the problem persists. 282 No. 5 Fault Grid 10min Overvoltage Cause The moving average of grid voltage in 10min exceeds the range of safety requirements. 283 Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. Check if the grid voltage is running at a high voltage for a long time. If it occurs frequently, please check if the grid voltage is within the allowable range. • Contact the local power company if the grid voltage exceeds the permissible range. • If the grid voltage is within the allowable range, please modify the Grid 10min Overvoltage protection value with the consent of the local power operator. No. 6 Fault Grid Overfrequency Cause Utility grid exception. The actual grid frequency exceeds the requirement of the local grid standard. 284 Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid frequency is within the permissible range. • Contact the local power company if the grid frequency exceeds the permissible range. • Modify the grid overfrequency protection threshold after obtaining the consent of the local power company if the grid frequency is within the permissible range. No. 7 Fault Grid Underfrequency Cause Utility grid exception. The actual grid frequency is lower than the requirement of the local grid standard. Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid frequency is within the permissible range. • Contact the local power company if the grid frequency exceeds the permissible range. Modify the grid overfrequency protection threshold after obtaining the consent of the local power company if the grid frequency is within the permissible range. 285 No. 8 Fault Grid Frequency Unstable Cause Utility grid exception. The actual grid frequency change rate does not meet the requirement of the local grid standard 286 Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid frequency is within the permissible range. • Contact the local power company if the grid frequency exceeds the permissible range. • Contact the dealer or the after-sales service if the grid frequency is within the permissible range. No. 9 Fault Grid Phase Unstable Cause Utility grid exception. Grid voltage phase change rates do not meet local grid standards. 287 Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid frequency is within the permissible range. • Contact the local power company if the grid frequency exceeds the permissible range. • Contact the dealer or the after-sales service if the grid frequency is within the permissible range. No. 10 11 Fault Anti-islanding Protection LVRT Undervoltage Cause The utility grid is disconnected. The utility grid is disconnected according to the safety regulations, but the grid voltage is maintained due to the loads. Utility grid exception. The duration of the grid voltage abnormality exceeds the time specified for high and low penetration. 288 Troubleshooting Suggestions 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the grid frequency is within the permissible range. • Contact the local power company if the grid frequency exceeds the permissible range. • Contact the dealer or the after-sales service if the grid frequency is within the permissible range. No. 12 Fault HVRT Overvoltage 13 Grid Waveform Abnormal 14 Grid Phase Loss Grid Phase Loss 15 Grid Voltage Imbalance Cause Troubleshooting Suggestions Utility grid exception. The duration of the grid voltage abnormality exceeds the time specified for high and low penetration. 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If the problem occurs frequently, check whether the voltage and frequency of the power grid are within the permissible range and stable. If no, contact the local power operator; If yes, please contact the local service center. Utility grid exception. Abnormal grid voltage detection triggers a fault. Utility grid exception. There is a single phase drop in the grid voltage. Excessive differences in grid phase voltages. 289 1. If the problem occurs occasionally, the utility grid may be abnormal temporarily. The inverter will recover automatically after detecting that the utility grid is normal. 2. If it occurs frequently, please check whether the voltage and frequency of the power grid are within the permissible range and stable, if not, please contact your local power operator; if yes, please contact your dealer or after-sales service center. No. 16 17 18 19 Cause Troubleshooting Suggestions Grid Phase Sequence Abnormal Abnormal wiring of inverter and grid: wiring out of sequence. 1. Check whether the wiring of Inverter and Utility grid is in positive sequence. After the wiring is corrected (e.g., by swapping any two phase wires), the fault will automatically disappear. 2. If the wiring is correct and fault persists, please contact the dealer or customer service center. Grid Rapid Shutdown Protection Quickly shut down the output upon detecting the grid disconnected operating condition. 1. The fault automatically disappears after the grid power supply is restored. Neutral Line Loss (Split Grid) Phase separation Utility grid neutral line loss. 1. The alarm is automatically cleared after the grid power supply is restored. 2. Check whether the AC cable is connected and the AC breaker is on. EMS/Forced Off-Grid EMS Issue a forced off-grid command, but the off-grid function is not enabled. Enable off-grid function Fault 290 No. 20 21 22 Fault GFCI Protection (30mA) GFCI Protection (60mA) GFCI Protection (150mA) Cause Troubleshooting Suggestions The input insulation impedance becomes low when the inverter is working. 1. If the problem occurs occasionally, it may be caused by a cable exception. The inverter will recover automatically after the problem is solved. 2. Check whether the impedance between the PV string and PE is too low if the problem occurs frequently or persists. The input insulation impedance becomes low when the inverter is working. 1. If the problem occurs occasionally, it may be caused by a cable exception. The inverter will recover automatically after the problem is solved. 2. Check whether the impedance between the PV string and PE is too low if the problem occurs frequently or persists. The input insulation impedance becomes low when the inverter is working. 1. If the problem occurs occasionally, it may be caused by a cable exception. The inverter will recover automatically after the problem is solved. 2. Check whether the impedance between the PV string and PE is too low if the problem occurs frequently or persists. 291 No. 23 24 25 Fault GFCI Protection (300mA) DCI Protection Level 1 DCI Protection Level 2 Cause Troubleshooting Suggestions The input insulation impedance becomes low when the inverter is working. 1. If the problem occurs occasionally, it may be caused by a cable exception. The inverter will recover automatically after the problem is solved. 2. Check whether the impedance between the PV string and PE is too low if the problem occurs frequently or persists. The DC component of the output current exceeds the safety range or default range. 1. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. 2. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. The DC component of the output current exceeds the safety range or default range. 1. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. 2. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. 292 No. 26 27 28 Cause Troubleshooting Suggestions Low Insulation Resistance 1. The PV string is short-circuited to PE. 2. The installation environment of PV strings is relatively humid for a long time and the insulation of PE cable is poor. 1. Check the impedance of the PV string to the ground. If there is a short circuit phenomenon, please check the short circuit point and rectify it. 2. Check whether the PE cable is connected correctly. 3. If it is confirmed that the impedance is indeed lower than the default value in cloudy and rainy days, please reset the "insulation impedance protection value". Grounding Abnormal 1. The PE cable of the inverter is not connected. 2. When the output of PV String is grounded, the output side of Inverter is not connected to an isolation transformer. 1. Please confirm if the PE cable of the inverter is properly connected. 2. In the scenario where the output of PV String is grounded, please confirm whether an isolation transformer is connected on the output side of Inverter. L-PE Short Circuit Output phase line to PE low impedance or short circuit. Detect output phase line to PE impedance, identify locations with low impedance and repair them. Fault 293 No. 29 30 31 Fault DCV Protection Level 1 DCV Protection Level 2 Hard Export Limit Protection Cause Troubleshooting Suggestions Abnormal fluctuation of load 1. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. 2. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. Abnormal fluctuation of load 1. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. 2. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. Abnormal fluctuation of load 1. If the exception is caused by an external fault, the inverter will recover automatically after solving the problem. 2. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. 294 Cause Troubleshooting Suggestions Internal Comm Loss Refer to the specific subcode reasons. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. 33 Multiple GFCI Failures North American safety regulations require multiple failures can not be automatically recovered, you need to manually or wait for 24h recovery 1. Check if the PV String to ground impedance is too low. 34 North American safety regulations require multiple failures can not be Multiple AFCI Failures automatically recovered, you need to manually or wait for 24h recovery 35 Inverter external device communication loss, may be peripheral power supply problems, communication protocol mismatch, not configure the appropriate peripheral, etc.. No. 32 Fault External Comm Loss 295 1. After the machine is re-ongrid, check whether the voltage current of each circuit is abnormally reduced to zero; 2. Check whether the DC side terminal is securely connected. Judgement is based on the actual model and the detection enable bit, some models do not support the peripheral will not be detected. No. 36 37 38 39 Cause Troubleshooting Suggestions 1. Prevent the Inverter from continuous overload output. 1. Disconnect some off-grid loads to reduce the off-grid output Power of the inverter. 2. Prevent damage to the load caused by Inverter output overvoltage. 1. If it occurs occasionally, it may be caused by load switching and does not require manual intervention. 2. If the problem occurs frequently, contact the dealer or the after-sales service. On-grid PWM Sync Fault On-grid PWM Sync Fault Abnormal occurrence in carrier synchronization ongrid. 1. Check if the synchronization line connection is normal. 2. Check whether the master-slave settings are normal. 3. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. External Box Failure Excessive waiting time for Box cut relay when switching on-grid to off-grid 1. Check whether the Box is working properly; 2. Check whether the Box communication wiring is correct; Fault Back-up Output Overload Back-up Output Overvoltage 296 Cause Troubleshooting Suggestions 1. This fault will always be displayed when the generator is not connected. 2. During generator operation, failure to meet generator safety regulations will trigger this fault. 1. Ignore the fault when the generator is not connected. 2. The occurrence of fault in the generator under fault conditions is normal. After the generator recovers, wait for a period of time, and the fault will automatically clear. 3. The fault will not affect the normal operation of the off-grid mode. 4. The generator and Utility grid are connected simultaneously and meet the safety requirements, with utility grid taking priority for on-grid, operating in the Utility grid on-grid state. External STS Failure Inverter and STS connection cable abnormality Check that the harness connection wire sequence between the inverter and STS corresponds in one-toone sequence. CT Loss CT connecting wire disconnection (required by Japanese safety regulations) 1. Check whether the CT wiring is correct; No. 40 41 42 Fault Generator Failure 297 No. Fault 43 Export Limit Protection 44 Bypass Over Load 45 Black Start Failure Cause Troubleshooting Suggestions 1. Inverter fault reporting and grid disconnection. 2. Meter communication instability. 3. Reverse flow conditions occur. 1. Check if there are any other error messages in Inverter. If so, perform targeted troubleshooting. 2. Check if meter connection is normal. 3. If the problem occurs frequently and the PV station cannot work properly, contact the dealer or the after-sales service. Parallel communication cable is not securely connected or parallel operation IO Chip damage Parallel communication cable is not securely connected or some units are offline. Check whether the parallel communication cable is firmly connected, and then check whether the IO chip is damaged, if so, replace the IO chip. Check whether all machines are power on and whether the parallel communication cables are securely connected. 46 Paralell I/O Check Abnormal 47 Paralell CAN Comm Abnormal 48 Parallel Grid Line Reversed /Paralell Grid Line Reversed Some machines have grid wires reversed Rewire the grid. from others. 49 Parallel Back-up Line Reversed Some machines have backup cables Reconnect the backup cable. reversed. 298 No. Fault 50 Inverter Soft Start Failure 51 Off grid AC Ins Volt High Cause Inverter soft start failure during offgrid cold start. 52 AC HCT Check Abnormal The sampling of the AC HCT is abnormal. 53 AC HCT Failure The sampling of HCT is abnormal. 54 GFCI HCT Check Abnormal The sampling of the GFCI HCT is abnormal. 55 GFCI HCT Failure GFCI HCT is abnormal. 299 Troubleshooting Suggestions Check machine inverter module for damage. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. 56 57 58 Cause Troubleshooting Suggestions Relay Check Abnormal Relay abnormal, reasons are as follows: 1. Relay abnormality (relay short circuit). 2. The relay sampling circuit is abnormal. 3. The AC cable is connected improperly, like a virtual connection or short circuit. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Relay Failure 1. Relay abnormality (relay short circuit). 2. The relay sampling circuit is abnormal. 3. The AC cable is connected improperly, like a virtual connection or short circuit. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. AFCI Failure (String 17~32) 1. The DC side connection terminal is loose. 2. The DC side connection terminals are falsely connected. 3. The DC cable core breakage and false connection. 1. After the machine is re-ongrid, check whether the voltage current of each circuit is abnormally reduced to zero. 2. Check whether the DC side terminal is securely connected. Fault 300 No. 59 60 61 62 Fault Cause Troubleshooting Suggestions AFCI Failure (String 33~48) 1. The DC side connection terminal is loose. 2. The DC side connection terminals are falsely connected. 3. The DC cable core breakage and false connection. 1. After the machine is re-ongrid, check whether the voltage current of each circuit is abnormally reduced to zero. 2. Check whether the DC side terminal is securely connected. Flash R/W Abnormal Causes are possibly as follows: Flash content has changed; flash life is exhausted. 1. Upgrade to the latest version of the program. 2. Contact the dealer or the after-sales service. AFCI Failure (String 1~16) 1. The DC side connection terminal is loose. 2. The DC side connection terminals are falsely connected. 3. The DC cable core breakage and false connection. 1. After the machine is re-ongrid, check whether the voltage current of each circuit is abnormally reduced to zero. 2. Check whether the DC side terminal is securely connected. The arc-pulling module does not detect an arc-pulling fault during the arcpulling self-test. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. AFCI Check Failure 301 No. 63 64 Fault Cause AC Terminal Overtemperature AC terminal temperature is too high, causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. Cabinet Overtemperature Cavity temperature is too high, causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. 302 Troubleshooting Suggestions 1. Check whether the ventilation of the inverter installation location is good and whether the ambient temperature exceeds the maximum allowable ambient temperature range. 2. If the ventilation is poor or the ambient temperature is too high, please improve the ventilation and heat dissipation conditions. 3. Contact the dealer or after-sales service if both the ventilation and the ambient temperature are normal. No. 65 66 Fault Cause Inv Module Overtemperature Inverter module temperature is too high, causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. Boost Module Overtemperature Boost module temperature is too high, causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. 303 Troubleshooting Suggestions No. 67 68 Fault Cause AC Capacitor Overtemperature Output filter capacitor temperature is too high, causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. Relay Failure 2 Relay abnormal, reasons are as follows: 1. Relay abnormality (relay short circuit). 2. The relay sampling circuit is abnormal. 3. The AC cable is connected improperly, like a virtual connection or short circuit. 304 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. Fault Cause PV IGBT Short Circuit Causes are possibly as follows: 1. IGBT short circuit. 2. The inverter sampling circuit is abnormal. 70 PV IGBT Open Circuit 1. A software problem caused the wave not to be sent. 2. The drive circuit is abnormal. 3. IGBT open circuit 71 NTC Abnormal Abnormal NTC temperature sensor 72 PWM Abnormal Abnormal waveform appears in PWM 69 305 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. Fault Cause 73 CPU Interrupt Abnormal CPU Interruption anomaly occurs. 74 Microelectronic Failure Functional safety detects an anomaly. 75 PV HCT Failure Abnormal boost current sensor. 76 1.5V Ref Abnormal The reference circuit is abnormal. 77 0.3V Ref Abnormal The reference circuit is abnormal. 306 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. Fault Cause CPLD Version Error CPLD version identification error. CPLD Comm Failure CPLD and DSP communication content error or timeout. 80 Model Type Error Troubleshooting about model recognition error. 81 SVG Precharge Failure 82 SVG Mode PID Prevention Failure 83 DSP Version Error 78 79 SVG Precharge hardware failure. PID prevent hardware anomaly. DSP version identification error. 307 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Contact the dealer or the after-sales service. Contact the dealer or the after-sales service. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. Fault 84 BUS Overvoltage 85 P-BUS Overvoltage 86 N-BUS Overvoltage 87 BUS Overvoltage (Slave CPU 1) BUS/Overvoltage(Slav e CPU 1) 88 89 90 91 92 93 94 P-BUS Overvoltage (Slave CPU 1) N-BUS Overvoltage (Slave CPU 1) BUS Overvoltage (Slave CPU 2) P-BUS Overvoltage (Slave CPU 2) N-BUS Overvoltage (Slave CPU 2) P-BUS Overvoltage (CPLD) N-BUS Overvoltage (CPLD) Cause BUS overvoltage. Causes are possibly as follows: 1. The PV voltage is too high. 2. The sampling of the inverter BUS voltage is abnormal. 3. The isolation of the transformer of the inverter is poor, so two inverters influence each other when connected to the grid. One of the inverters reports DC overvoltage. 308 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. 95 96 97 98 Fault MOS Continuous Overvoltage Cause Troubleshooting Suggestions 1. Software issue causes the inverter drive to shut down earlier than the flyback drive. 2. Inverter drive circuit abnormality causes failure to turn on. 3. The PV voltage is too high. 4. Mos sampling anomaly. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Bus Short Circuit 1. The hardware is damaged. Bus Sample Abnormal 1. Bus voltage sampling hardware failure. DC Sample Abnormal 1. Bus voltage sampling hardware failure. 2. Battery voltage sampling hardware failure. 3. Dcrly relay failure. 309 If the inverter continues to be off-grid after a BUS shortcircuit fault occurs, please contact your dealer or aftersales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. 99 100 101 102 Fault Cause Troubleshooting Suggestions PV Input Overvoltage PV input voltage is too high. Causes are possibly as follows: Incorrect photovoltaic array configuration, with too many PV Battery panels connected in series in the string, causing the string's open-circuit voltage to exceed the maximum operating voltage of the Inverter. Check the serial connection of the PV array. Make sure that the open circuit voltage of the PV string is not higher than the maximum operating voltage of the inverter. The inverter alarm disappears automatically when the PV array is configured correctly. PV Continuous Hardware Overcurrent 1. The PV configuration is not proper. 2. The hardware is damaged. PV Continuous Software Overcurrent 1. The module configuration is not proper. 2. The hardware is damaged. FlyCap Software Overvoltage FlyCap overvoltage. Causes are possibly as follows: 1. The PV voltage is too high. 2. The sampling of the inverter FlyCap voltage is abnormal. 310 Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. No. 103 104 105 106 Fault Cause FlyCap Hardware Overvoltage FlyCap overvoltage. Causes are possibly as follows: 1. The PV voltage is too high. 2. The sampling of the inverter FlyCap voltage is abnormal. FlyCap Undervoltage FlyCap undervoltage. Causes are possibly as follows: 1. PV Energy deficit; 2. The sampling of the inverter FlyCap voltage is abnormal. FlyCap Precharge Failure FlyCap precharge failure. Causes are possibly as follows: 1. PV Energy deficit; 2. The sampling of the inverter FlyCap voltage is abnormal. FlyCap Precharge Abnormal 1. Unreasonable control loop parameters 2. The hardware is damaged. 311 Troubleshooting Suggestions No. Troubleshooting Suggestions Fault Cause 107 PV String Overcurrent (String 1~16) Causes are possibly as follows: 1. String overcurrent. 2. String current sensor abnormality. 108 PV String Overcurrent (String 17~32) As above. 109 PV String Reversed (String 1~16) The PV strings are connected reversely. Check whether PV strings are connected reversely. 110 PV String Reversed (String 17~32) The PV strings are connected reversely. Check whether PV strings are connected reversely. 111 PV String Loss (String 1~16) String fuse disconnected (if applicable). Check if the fuse is blown. 112 PV String Loss (String 17~32) String fuse disconnected (if applicable). Check if the fuse is blown. 312 No. 113 Fault Cause Troubleshooting Suggestions PV Input Mode Error There are three modes of PV access modes, taking the four-way MPPT as an example: 1. Parallel mode: i.e. AAAA mode (homogenous mode), PV1-PV4 homogenous, fourway PV connected to the same PV panel. 2. Partial parallel mode: i.e. AACC mode, PV1 and PV2 are connected in the same source, PV3 and PV4 are connected in the same source. 3. Independent mode: i.e. ABCD mode (nonhomologous), PV1, PV2, PV3, PV4 are connected independently, and each of the four-way PV is connected to a photovoltaic panel. This fault is reported if the actual access mode of the PV does not match the PV Check that the PV access mode is set correctly (ABCD, AACC, AAAA) and reset the PV access mode in the correct way. 1. Confirm that the actual access to each PV is properly connected. 2. If the PV has been connected correctly, check whether the currently set “PV Access Mode” corresponds to the actual access mode through APP or screen. 3. If the currently set “PV access mode” does not match the actual access mode, you need to set the “PV access mode” to a mode that matches the actual situation through APP or screen, and then disconnect the PV and AC power supply and restart after the setup is completed. 4. After the setting is completed, if the current "PV access mode" is consistent with the actual access mode, but this fault is still reported, please contact the dealer or after-sales service center. 313 No. Fault Cause Troubleshooting Suggestions access mode set by the device. 114 PV String Reversed (String 33~48) The PV strings are connected reversely. 115 PV String Loss (String 33~48) String fuse disconnected (if applicable). PV String Overcurrent (String 33~48) Causes are possibly as follows: 1. String overcurrent. 2. String current sensor abnormality. 116 117 BAT 1 Precharge Failure Battery 1 precharge circuit failure (burnt precharge resistor, etc.) 314 Check whether PV strings are connected reversely. Check if the fuse is blown. As above. Check whether the precharging circuit is good, whether the battery voltage and bus voltage are consistent after powering up the battery only, if not, please contact the dealer or after-sales service center. No. 118 119 120 121 122 123 Cause Troubleshooting Suggestions BAT 1 Relay Failure Battery 1 relay does not operate properly. After the battery is powered up, check if the battery relay works and if you hear a closing sound, if it does not work, please contact your dealer or after-sales service center. BAT 1 Overvoltage Battery 1 access voltage exceeds the rated range of the machine. Verify that the battery voltage is within the rated range of the machine. Fault BAT 2 Precharge Failure Battery 2 precharge circuit failure (burnt precharge resistor, etc.) BAT 2 Relay Failure Battery 2 relay does not operate properly. BAT 2 Overvoltage BAT 1 Reversed Battery 2 access voltage exceeds the rated range of the machine. Positive and negative poles of Battery 1 are connected reversely. 315 Check whether the precharging circuit is good, whether the battery voltage and bus voltage are consistent after powering up the battery only, if not, please contact the dealer or after-sales service center. After the battery is powered up, check if the battery relay works and if you hear a closing sound, if it does not work, please contact your dealer or after-sales service center. Verify that the battery voltage is within the rated range of the machine. Check the battery and machine terminals for positive and negative consistency. No. Fault Cause 124 BAT 2 Reversed Battery 2 positive and negative are connected reversely. 125 BAT Connection Abnormal Battery abnormal connection. Bat Overtemperature Battery temperature is too high. Causes are possibly as follows: 1. The inverter is installed in a place with poor ventilation. 2. The ambient temperature exceeds 60℃. 3. A fault occurs in the internal fan of the inverter. 125 127 Ref Voltage Abnormal 128 AC SPD Fault 129 DC SPD Fault The reference circuit is abnormal. AC side lightning protection device failure. DC side lightning protection device failure. 316 Troubleshooting Suggestions Check the battery and machine terminals for positive and negative consistency. Check whether the battery is working properly. Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. Replace AC side lightning protection devices. Replace DC side lightning protection devices. No. 130 131 132 Fault Cause Internal Fan Abnormal Internal fan abnormality. Causes are possibly as follows: 1. Abnormal fan power supply. 2. Mechanical exception (blocking). 3. Fan aging damage. External Fan Abnormal External fan abnormality. Causes are possibly as follows: 1. Abnormal fan power supply. 2. Mechanical exception (blocking). 3. Fan aging damage. PID Abnormal PID hardware failure or high PV voltage PID pause. 317 Troubleshooting Suggestions Disconnect the AC output side switch and the DC input side switch. After 5 minutes, close the AC output side switch and the DC input side switch. If fault persists, please contact the dealer or after-sales service center. PID pause warning caused by high PV voltage does not need to be dealt with, PID hardware failure can be cleared by turning the PID switch off and on again to clear the PID fault, replace the PID unit. No. 133 134 Fault Cause Trip-Switch Trip Warning Causes are possibly as follows: 1. An overcurrent or PV reversal has occurred causing the disconnect switch to trip; PV IGBT Short Circuit Warning Causes are possibly as follows: 1. An overcurrent occurs causing the disconnect switch to trip. 318 Troubleshooting Suggestions Contact the dealer or the after-sales service. The reason for disconnection, for the occurrence of PV short circuit or reverse connection, it is necessary to check whether there is a historical PV short circuit warning or historical PV reverse connection warning, and if there is, it is necessary for the maintenance personnel to check the corresponding PV situation. After checking that there are no faults you can manually close the disconnect switch and clear this warning via the APP interface clear history faults operation. Contact the dealer or the after-sales service. Maintenance personnel need to follow the historical PV short circuit warning subcode to check whether there is any fault in the shortcircuited Boost hardware and external strings; after checking there is no fault, the warning can be cleared by clearing the historical fault operation through the APP interface. No. 135 136 Fault Cause PV String Reversed Warning(String 1~16) Causes are possibly as follows: 1. The PV reverse connection has occurred causing the disconnecting switch to trip; PV String Reversed Warning(String 17~32) Causes are possibly as follows: 1. The PV reverse connection has occurred causing the disconnecting switch to trip; 319 Troubleshooting Suggestions Contact the dealer or the after-sales service. Maintenance personnel need to follow the historical PV reverse connection warning subcode to check whether the corresponding string is reverse connected and whether there is pressure difference in the PV panel configuration; after the check is complete and there is no fault, the warning can be cleared by clearing the historical fault operation through the APP interface. Contact the dealer or the after-sales service. Maintenance personnel need to follow the historical PV reverse connection warning subcode to check whether the corresponding string is reverse connected and whether there is pressure difference in the PV panel configuration; after the check is complete and there is no fault, the warning can be cleared by clearing the historical fault operation through the APP interface. Cause Troubleshooting Suggestions Flash R/W Error Flash R/W Error Causes are possibly as follows: Flash content has changed; flash life is exhausted. 1. Upgrade the latest version of the program. 2. Contact the dealer or the after-sales service. 138 Meter Comm Loss This warning may be reported only after enabling the antireverse flow function. Causes are possibly as follows: 1. Meter not connected. 2. The communication wire connecting the meter to the inverter is wired incorrectly. Check the wiring of the meter and connect the meter correctly, if the fault still exists after checking, contact the dealer or the after-sales service. 139 PV Type Identification Failure PV panel recognizes hardware anomaly. 140 PV String Mismatch PV string mismatches. Two sets of string opencircuit voltages under the same MPPT have different configurations. 141 CT Loss CT Loss 142 CT Reversed CT Reversed 143 PE Loss Ground wire not connected. No. 137 Fault 320 Contact the dealer or the after-sales service. Check the open-circuit voltage of the two strings, and configure the strings with the same open-circuit voltage under the same MPPT, as long time string mismatch is a potential safety hazard. Check whether the CT wiring is correct. Check whether the CT wiring is correct. Check the ground wire. No. Fault 144 PV String Terminal Overtemperature (String 1~8) 145 PV String Terminal Overtemperature (String 9~16) 146 PV String Terminal Overtemperature (String 17~20) 147 PV String Reversed Warning (String 33~48) 148 Battery 1 Low Voltage 149 Battery 2 Low Voltage Cause Troubleshooting Suggestions 37176 Register PV Terminal Temperature Alarm Subcode 1 has a set position. 37177 Register PV Terminal Temperature Alarm Subcode 2 has a set position. 37178 Register PV Terminal Temperature Alarm Subcode 3 has a set position. Causes are possibly as follows: 1. The PV reverse connection has occurred causing the disconnecting switch to trip. Battery voltage below set value. Battery voltage below set value. 321 Contact the distributor or after-sales service center; Maintenance personnel need to follow the historical PV reverse connection warning subcode to check whether the corresponding string is reverse connected and whether there is pressure difference in the PV panel configuration; after the check is complete and there is no fault, the warning can be cleared by clearing the historical fault operation through the APP interface. No. 150 Fault Cause Low Battery Supply Voltage When the battery is in non-charging mode, the voltage is lower than the shutdown voltage. Troubleshooting Suggestions 11.5.2.3 Battery Fault (LX A5.0-10) When the battery ALM indicator turns red, troubleshoot the issue by referring to the SOC indicator's display status. No. SOC Indicator Fault Solutions/measures to address the issue 1 Battery Overvoltage Power off and wait for 2 hours. If the problem persists, please contact the aftersales service. 2 Battery Undervoltage Contact the after-sales service. 3 High Cell Temperature 4 Low Charging Temperature 5 Low Discharging Temperature 6 Overcurrent Charging 7 Overcurrent Discharging 8 Low Insulation Resistance Power off and wait for 2 hours. If the problem persists, please contact the aftersales service. Turn off the device to wait for the temperature to return to normal. If the problem persists after restarting, please contact the after-sales service center. Turn off the device to wait for the temperature to return to normal. If the problem persists after restarting, please contact the after-sales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Contact the after-sales service. 322 No. 9 10 11 SOC Indicator Fault Solutions/measures to address the issue Excessive Temperature Difference Voltage Difference Exception Inconsistency of Battery Cells Power off and wait for 2 hours. If the problem persists, please contact the aftersales service. Leave the battery alone for 12h after restarting. If the problem persists, please contact the after-sales service center. 12 Wire Harness Exception 13 MOS OpenCircuit Fault 14 MOS OpenCircuit Fault 15 Cluster Fault 16 Interlock Failure 17 18 19 20 BMU Communication Fault MCU Communication Fault Open Contact Sticking Fault Precharge Failure Contact the after-sales service. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Please check if the battery model matches. If not, please contact the after-sales service center. Check whether the termination resistor is installed properly and restart the battery. Contact the after-sale service if the problem persists. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. Contact the after-sales service. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. 323 No. SOC Indicator 21 22 23 24 Fault Solutions/measures to address the issue MOS Overtemperature Fault Current Diverter Overtemperature Reverse Connection Fault Microelectronic Fault Power off and wait for 2 hours. If the problem persists, please contact the aftersales service. Power off and wait for 2 hours. If the problem persists, please contact the aftersales service. Contact the after-sales service. Contact the after sales service. 11.5.2.4 Battery Fault (LX A5.0-30, LX U5.0-30) Alarm state When the battery ALM indicator turns red, troubleshoot the issue by referring to the SOC indicator's display status. No. 1 SOC Indicator Fault Solutions/measures to address the issue Battery overvoltage protection Battery undervoltage protection 1. Check whether the Charging Current Limit of the inverter is 0 through SolarGo. If yes, please confirm whether the communication cable connection between the battery and the inverter is reliable and the communication is normal. 2. Power off and wait for 5 minutes, then restart to confirm if the fault persists. 3. If the fault is not restored, please contact the after-sales service center. 324 No. 2 3 4 SOC Indicator Fault Solutions/measures to address the issue Overcurrent Protection 1. Check if the battery model is correct through SolarGo and confirm if the realtime current of the battery is greater than the Charging/Discharging Current Limit. Please contact the after-sales service center. 2. When it is less than the Charging/Discharging Current Limit., turn off the battery or upgrade the program, restart to confirm whether the fault persists. 3. If the fault is not restored, please contact the after-sales service center. Over temperature protection Low temperature protection Pole over temperature protection Balancing Fault Low SOH Fault 5 Precharge Failure 6 Wire Harness Exception Power off and wait for 60 minutes, wait for the temperature to recover. If the problem persists after restarting, please contact the after-sales service center. Power off and wait for 30 minutes. If the problem persists after restarting, please contact the after-sales service center. 1. Confirm if the battery output terminal is connected in reverse to the inverter. 2. Power off and wait for 30 minutes. If the problem persists after restarting, please contact the after-sales service center. Confirm if the battery switch is closed. If the battery switch is closed and the problem still exists. Please contact the after-sales service center. 325 No. 7 SOC Indicator Fault Solutions/measures to address the issue Relay or MOS over Temperature Diverter over Temperature Power off and wait for 30 minutes. If the problem persists after restarting, please contact the after-sales service center. Other BMS Faults: Output Port over Temperature Fault 1. Check if the battery power cable is connected tightly. Power off and wait for 5 minutes. If the problem persists after restarting, please contact the after-sales service center. Other Protections: MOS cannot be Closed Other Protections: MOS Adhesion Power off and wait for 5 minutes. If the problem persists after restarting, please contact the after-sales service center. 10 Other Protections: Cluster Fault 1. Confirm whether the type and installation position of the terminal resistor used are correct. 2. Confirm whether the communication cable between batteries, the cable between batteries and inverters are reliable and the communication is normal. 3. If the fault is not restored, please contact the after-sales service center. 11 1. Confirm whether the communication Other cable between batteries, the cable Protections: between batteries and inverters are Communication reliable and the communication is normal. Loss with 2. If the fault is not restored, please contact Inverter the after-sales service center. 8 9 326 No. 12 13 14 15 SOC Indicator Fault Solutions/measures to address the issue 1. Confirm whether the type and installation position of the terminal resistor used are correct. Other 2. Confirm whether the communication Protections: cable between batteries, the cable BMU between batteries and inverters are Communication reliable and the communication is normal. Failure 3. Power off and wait for 5 minutes. If the problem persists after restarting, please contact the after-sales service center. Other Protections: Air Switch Adhesion Fault Other Protections: Software Fault Other Protections: Hardware Overcurrent Fault Other Protections: Microelectronic s Fault 16 Power off and wait for 5 minutes. If the problem persists after restarting, please contact the after-sales service center. Restart the battery. If the problem persists after restarting, please contact the aftersales service center. 1. Upgrade software Heating Film Abnormal 2. Power off and wait for 5 minutes. If the problem persists after restarting, please contact the after-sales service center. 11.5.3 Operation After Fault Clearance 327 In the energy conservation system, after some fault clearances complete, further operations are needed for the system to restore normal work. 11.5.3.1 Clear AFCI Alarm [Software]: SolarGo App [Clearance method] 1. Home > Settings > Advanced Settings > DC AFCI 2. Tap [Clear AFCI Alarm]. 328 12 Technical Parameters 12.1 Inverter Parameters Technical Data GW3000-ESC10 GW3600-ESC10 GW5000-ES-C10 GW6000-ESC10 Li-Ion/Leadacid Li-Ion/Lead-acid Li-Ion/Leadacid 48 48 48 40~60 40~60 40~60 44.2 44.2 44.2 1 1 1 90 120 140 90 120 140 3.6*2 5.0*2 6.0*2 3.96*2 5.5*2 6.6*2 7.2 10.0 12.0 600 600 600 Battery Input Data Battery Type*1 Li-Ion/Leadacid Nominal Battery 48 Voltage (V) Battery Voltage Range 40~60 (V) Start-up 44.2 Voltage (V) Number of 1 Battery Input Max. Continuous 70 Charging Current (A) Max. Continuous 70 Discharging Current (A) Max. Charge 3.0*2 Power (kW) Max. 3.3*2 Discharge Power (kW) PV String Input Data Max. Input 6.0 Power (kW) Max. Input 600 Voltage (V)*4 329 MPPT Operating 60~550 Voltage Range (V)*5 MPPT Voltage Range at 180~500 Nominal Power (V) Start-up 58 Voltage (V) Nominal Input 360 Voltage (V) Max. Input Current per 20 MPPT (A) Max. Short Circuit Current 26 per MPPT (A) Max. Backfeed Current to The 0 Array (A) Number of MPPT 1 Trackers Number of Strings per 1 MPPT AC Output Data (On-grid) Nominal Output Power 3.0 (kW) Nominal Apparent Power Output 3.0 to Utility Grid (VA) Max. AC Active 3.3 Power (W)*7*8 60~550 60~550 60~550 120~500 150~500 180~500 58 58 58 360 360 360 20 20 20 26 26 26 0 0 0 2 2 2 1 1 1 3.6 5.0 6.0 3.6 5.0 6.0 3.96*10 5.5 6.6 330 Max. Apparent Power Output to Utility Grid (VA)*7*8 Nominal Power at 40℃ (W) Max. Power at 40℃ (Including AC Overload) (W)*8 Nominal Apparent Power from Utility Grid (VA) Max. Apparent Power from Utility Grid (kVA) Nominal Power at 40℃ (kW) Max. Power at 40℃ (Including AC Overload) (kW) Nominal Output Voltage (V) Output Voltage Range (V) 3.3 3.96*10 5.5 6.6 3.0 3.6 5.0 6.0 3.0 3.6 5.0 6.0 3.0 3.6 5.0 6.0 7.04 7.04 8.8 8.8 3.0 3.6 5.0 6.0 3.0 3.6 5.0 6.0 220/230/240 220/230/240 220/230/240 220/230/240 170~280 170~280 170~280 170~280 331 Nominal AC Grid Frequency (Hz) AC Grid Frequency Range (Hz) Max. AC Current Output to Utility Grid (A) Max. AC Current From Utility Grid (A) 50/60 50/60 50/60 50/60 45~55/55~65 45~55/55~65 45~55/55~65 45~55/55~65 15.0 18.0*9 25.0 30.0 32.0 32.0 40.0 40.0 13.7 at 220V 13.1 at 230V 12.5 at 240V 16.4 at 220V 15.7 at 230V 15.0 at 240V 22.8 at 220V 21.8 at 230V 20.9 at 240V 27.3 at 220V 26.1 at 230V 25.0 at 240V 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs Nominal Output Current (A) 13.7 at 220V 13.1 at 230V 12.5 at 240V 16.4 at 220V 15.7 at 230V 15.0 at 240V 22.8 at 220V 21.8 at 230V 20.9 at 240V 27.3 at 220V 26.1 at 230V 25.0 at 240V Power Factor ~1 (Adjustable from 0.8 leading to 0.8 lagging) ~1 (Adjustable from 0.8 leading to 0.8 lagging) ~1 (Adjustable from 0.8 leading to 0.8 lagging) ~1 (Adjustable from 0.8 leading to 0.8 lagging) Max. Total Harmonic Distortion <3% <3% <3% <3% Nominal AC Current From Utility Grid (A) Max. Output Fault Current (Peak and Duration) (A) Inrush Current (Peak and Duration) (A) 332 Maximum Output 53 Overcurrent Protection (A) Type of Voltage (a.c. a.c. or d.c.) AC Output Data (Back-up) Back-up Nominal 3.0 Apparent Power (kVA) Max. Output Apparent 3.3(6.0, 10s) Power without Grid(kVA) Max. Output Apparent 7.04 Power with Grid (kVA) Nominal Output Current (A) Max. Output Current without Grid(A) Max. Output Current with Grid(A) Max. Output Fault Current (Peak and Duration) (A) Inrush Current (Peak and Duration) (A) 53 88 88 a.c. a.c. a.c. 3.6 5.0 6.0 3.96(7.2, 10s) 5.5(10.0, 10s) 6.6(12.0, 10s) 7.04 8.8 8.8 13.7 at 220V 13.1 at 230V 12.5 at 240V 16.4 at 220V 15.7 at 230V 15.0 at 240V 22.8 at 220V 21.8 at 230V 20.9 at 240V 27.3 at 220V 26.1 at 230V 25.0 at 240V 15 18 25 30 32 32 40 40 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 96A, 3μs 333 Maximum Output Overcurrent Protection (A) Nominal Output Voltage (V) Nominal Output Frequency (Hz) Output THDv (@Linear Load) Switching from Grid Connected Mode to Standalone Mode Switching from standalone mode to Grid connected mode 53 53 88 88 220/230/240 220/230/240 220/230/240 220/230/240 50/60 50/60 50/60 50/60 <3% <3% <3% <3% <10ms <10ms <10ms <10ms <10ms <10ms <10ms <10ms 3.0 3.6 5.0 6.0 3.3 3.96 5.5 6.6 AC Data (Generator) Nominal Apparent Power from AC generator (kVA) Max. Apparent Power from AC generator (VA) 334 Nominal Intput Voltage (V) Input Voltage Range (V) Nominal AC generator Frequency (Hz) AC generator Frequency Range (Hz) Max. AC Current From AC generator (A) Nominal AC Current From AC generator (A) Efficiency Max. Efficiency European Efficiency CEC Efficiency Max. Battery to AC Efficiency MPPT Efficiency Protection PV String Current Monitoring PV Insulation Resistance Detection 220/230/240 220/230/240 220/230/240 220/230/240 170~280 170~280 170~280 170~280 50/60 50/60 50/60 50/60 45~55 / 55~65 45~55 / 55~65 45~55 / 55~65 45~55 / 55~65 32.0 32.0 40.0 40.0 13.7 at 220V 13.1 at 230V 12.5 at 240V 16.4 at 220V 15.7 at 230V 15.0 at 240V 22.8 at 220V 21.8 at 230V 20.9 at 240V 27.3 at 220V 26.1 at 230V 25.0 at 240V 97.6% 97.6% 97.6% 97.6% 96.2% 96.2% 96.2% 96.2% 96.2% 96.2% 96.2% 96.2% 95.5% 95.5% 95.5% 95.5% 99.9% 99.9% 99.9% 99.9% Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated 335 Residual Current Monitoring PV Reverse Polarity Protection Anti-islanding Protection AC Overcurrent Protection AC Short Circuit Protection AC Overvoltage Protection DC Switch DC Surge Protection AC Surge Protection AFCI Rapid Shutdown Remote Shutdown General Data Operating Temperature Range (℃) Operating Environment Storage Temperature (℃) Relative Humidity Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Integrated Type III Type III Type III Type III Type III Type III Type III Type III Optional Optional Optional Optional Optional Optional Optional Optional Integrated Integrated Integrated Integrated -35~+60 -35~+60 -35~+60 -35~+60 Outdoor Outdoor Outdoor Outdoor -40~+85 -40~+85 -40~+85 -40~+85 0~95% 0~95% 0~95% 0~95% 336 Max. Operating Altitude (m) 3000 3000 3000 3000 Cooling Method Natural Convection Natural Convection Natural Convection Natural Convection User Interface LCD, WLAN+APP LCD, WLAN+APP LCD, WLAN+APP LCD, WLAN+APP Communicatio n with BMS CAN CAN CAN CAN Communicatio n RS485, WiFI+LAN+Bl uetooth RS485, WiFI+LAN+Bl uetooth RS485, WiFI+LAN+Blueto oth RS485, WiFI+LAN+Blu etooth ModbusRTU、 ModbusRTU、 Modbus-RTU、 ModbusRTU、 Modbus-TCP Modbus-TCP Weight (kg) 14.5 15.5 15.5 15.5 Dimension (W×H×D mm) 560*415*204 560*415*20 4 560*415*204 560*415*204 Noise Emission (dB) <30 <30 <30 <30 Non-isolated Non-isolated Non-isolated Non-isolated <10 <10 <10 <10 IP66 IP66 IP66 IP66 DC Connector PV: jinko ((4~6 mm²) BAT: OT (Max.35mm²) PV: jinko ((4~6 mm²) BAT: OT (Max.35mm² ) PV: jinko ((4~6 mm²) BAT: OT (Max.35mm²) PV: jinko ((4~6 mm²) BAT: OT (Max.35mm²) AC Connector Tubulose (Max.10mm²) Tubulose (Max.10mm² ) Tubulose (Max.10mm²) Tubulose (Max.10mm²) Communicatio n Protocols Topology Selfconsumption at Night (W) Ingress Protection Rating 337 Modbus-TCP Modbus-TCP Environmental Category Pollution Degree Overvoltage Category Protective Class 4K4H 4K4H 4K4H 4K4H III III III III DC II / AC III DC II / AC III DC II / AC III DC II / AC III I I I I The Decisive Voltage Class (DVC) Battery: A PV: C AC: C Com: A Battery: A PV: C AC: C Com: A Battery: A PV: C AC: C Com: A Battery: A PV: C AC: C Com: A Mounting Method Wall Mounted Wall Mounted Wall Mounted Wall Mounted Active Antiislanding Method SMS(Slipmode frequency) +AFD SMS(Slipmode frequency) +AFD SMS(Slip-mode frequency) +AFD SMS(Slipmode frequency) +AFD single phase single phase single phase single phase China China China China Type of Electrical Supply System Country of Manufacture Certification Grid Standards Safety Regulation EMC NRS 097-2-1, IEC 62116, IEC 61727 IEC 62109-1, IEC 62109-2 IEC 62920, IEC 61000-6-2, IEC 61000-6-4, IEC 61000-2-2, EN 300328, EN 301489, EN IEC 62311, EN 62479 *1:The Li-lon battery usually contain two mainstream type: LFP and Ternary Lithium battery. *2: When the PV input voltage is higher than 500V, the battery charging and discharging power will be gradually limited, and the power limitation will be lifted after the input voltage is lowered. *4:When the input voltage is 580V-600V, the inverter will enter standby mode, and the voltage returns to 580V to enter the normal operation state. *5:Please refer to the user manual for the MPPT Voltage Range at Nominal Power. 338 *6: The maximum input current per string is 16A. Or For the MPPT with two strings, the current of each string is 16A. *7: For Sri Lanka, Max. Output Power (kW) is 3.0kW for GW3000-ES-C10, 3.6kW for GW3600-ES-C10, 5.0kW for GW5000-ES-C10, 6.0kW for GW6000-ES-C10. *9: For Jordan, Max. AC Current Output to Utility Grid is 15.7A for GW3600-ES-C10. *10: For Jordan, Max. AC Active Power and Max. Apparent Power Output to Utility Grid are both 3.6kW/kVA for GW3600-ES-C10. 12.2 Battery Technical Data 12.2.1 LX A5.0-10 Technical Parameters Usable Energy (kWh) *1 Battery Module Number of Modules Cell Type Nominal Voltage (V) Operating Voltage Range (V) Nominal Charge/Discharge Current (A) *2 Nominal Charge/Discharge Power (kW) *2 Operating Temperature Range (℃) Relative Humidity Max. Operating Altitude (m) Communication Weight(kg) Dimension(W×H×D mm) LX A5.0-10 2* LX A5.0-10 n*LX A5.0-10 5 10 n×5 LX A5.0-10:51.2V 5.0kWh 1 2 LFP(LiFePO4) 51.2 n 47.5~57.6 60 120 n×60*3 3 6 n×3*3 Range (℃) Charge: 0 ~ +50; Discharge: -10 ~ +50 0~95% 3000 CAN 40 80 n×40 LX A5.0-10 Module: 442×133×420 (Excluding hanger); 483×133×452 ( Including hanger) 339 Technical LX A5.0-10 2* LX A5.0-10 n*LX A5.0-10 Parameters Ingress Protection IP21 Rating Storage 0 ~ +40 (≤ One year); -20 ~ 0 (≤ One month); -40 ~ 45 (≤ One month) Temperature(℃) Mounting Method Cabinet/Floor stacked Round-trip Efficiency 96.7% *4 Cycle Life *5 ≥5000 Safety IEC62619, IEC 63056, IEC62040-1, INmetro Standard EN IEC61000-6-1, EN IEC61000-6-2, EN IEC61000-6-3, EN and EMC IEC61000-6-4 Certificat Transporta ion UN38.3, ADR tion *1: Test conditions, 100% DOD, 0.2C charge & discharge at +25±2°C for battery system at beginning life. System Usable Energy may vary with different Inverter. *2: Nominal Dis-/Charge Current and power derating will occur related to Temperature and SOC. *3: Based on Using Battery Combiner Box to parallelize battery modules. *4: Based on 2.5~3.65V voltage rang @25±2°C of Cell under C.2C/0.2C Cell test condition. Round-trip Efficiency is approximately 94%~95. *5: Based on 2.87~3.59V voltage rang @25±2°C of Cell under 0.6C/0.6C test condition and 70% EOL. n: Max. 15. 12.2.2 LX A5.0-30 Technical Parameters Nominal Capacity (kWh) Usable Energy (kWh) *1 LX A5.0-30 Cell Type Operating Voltage Range (V) Nominal Charge Current (A)*2 LFP (LiFePO4) 5.12 5 43.2~ 58.24 60 340 Technical Parameters Max. Charge Current (A) *2*3 Nominal Discharge Current (A)*3 Max. Discharge Current (A) *2*3 Max. Pulse Discharge Current (A) Max. Discharge Power (W) *2 *3 Communication Operating Temperature (℃) LX A5.0-30 90 100 150 <200 (30s) 7200 CAN Charge: 0<T≤55℃ Discharge: -20<T≤55℃ Max. Storage Time Max. Operating Altitude (m) Weight (kg) 12 Months (maintenance-free) Dimension (W×H×D mm) 442/133* 520 (core part) 483/133* 559 (max. dimensions) Ingress Protection Rating IP20 Scalability Mounting Method 4000 44 Supports up to 30 in parallel connection (150kWh) (Handin-hand/Busbar) Standard rack/floor mounted, wall-mounted Round-trip Efficiency *1 Cycle Life ≥96% >6000 @25±2℃0.5C 70% SOH 90% DOD Safety IEC62619, IEC63056, N140 EMC EN IEC 61000--6--1, EN IEC 61000--6--2, EN IEC 61000--6-3, EN IEC 61000--6--4 Transportation UN38.3, ADR Environment ROHS Life (Year) ≥25 341 Technical Parameters LX A5.0-30 *1: Test conditions: 100% DOD, 0.2C charge & discharge at 25°C±2 ℃, at the beginning of life. *2: Max. charge / discharge current may be variant with vary among different inverter models. *3: Recommend/Max. Charging/Discharging Current/ Nominal/Max. Power* derating will occur related to temperature and SOC. 12.2.3 LX U5.0-30 Technical Parameters Nominal Battery Energy (kWh) Usable Energy (kWh) *1 Cell Type Nominal Voltage (V) Operating Voltage Range (V) Nominal Charge Current (A) Max. Continuous Charge Current (A)*2*3 Nominal Discharge Current (A) Max. Continuous Discharging Current (A)*2*3 Pulse Discharge Current (A)*2*3 Max. Continuous Charge/Discharge Power (kW) Communication Charging Temperature Range (℃) Discharging Temperature Range (℃) LX U5.0-30 5.12 5 LiFePO4 51.2 43.2~58.24 60 90 100 100 < 200A (30S) 4.95 CAN 0<T≤55 -20<T≤55 342 Technical Parameters LX U5.0-30 Ambient Temperature (℃) 0<T≤40 (Recommended 10<T≤30) Relative Humidity Max. Storage Time Max. Operating Altitude (m) Heating Fire Suppression Unit Weight (kg) Unit Dimension (W×H×D mm) Enclosure Protection Rating Application Scalability Mounting Method Round-trip Efficiency Cycle Life Safety 5~95% 12 Months (maintenance-free) Optional heating:-20<T≤40 (Recommend 10<T≤30) 4000 Optional Optional, Aerosol 50 460*580*160 IP65 On Grid / On Grid + Backup / Off Grid 30P Wall-/ Grounded- Mounted / Grounded ≥96% >6000 @25±2℃ 0.5C 70%SOH 90%DOD VDE2510-50, IEC62619, IEC62040, N140, IEC63056 EN IEC61000-6-1, EN IEC61000-6-2, EN IEC61000-6-3, EN EMC IEC61000-6-4 Transportation UN38.3, ADR Environment ROHS Life (Year) ≥25 *1 Test conditions: 100% DOD, 0.2C charge & discharge at 25°C±2℃,at the beginning of life. *2 The system's working current and power values will be related to temperature and State of Charge (SOC). *3 Max charge / discharge current values may be variant with different inverter models. 12.3 Smart Meter Technical Data 12.3.1 GMK110 343 Technical Parameters Application Nominal Voltage (V) Voltage Voltage Range (V) Input Data Nominal Voltage Frequency (Hz) CT Ratio Current CT Quantity Communication Communication Distance (m) User Interface Voltage/Current Accuracy Active Energy Reactive Energy Power Consumption (w) Mechanica Dimension (W×H×D mm) l Weight (g) Parameter Mounting Method s Ingress Protection Rating Environme Operating Temperature Range (℃) ntal Storage Temperature Range (℃) Parameter Relative Humidity (Nons Condensing) Max. Operating Altitude (m) GMK110 Single phase 220 85~288 50/60 120A/40mA 1 RS485 1000 2LED Class I Class I Class II <5 19*85*67 50 Rail Installation IP20 -30~ 60 -30~ 60 0~95% 3000 12.3.2 GM330 Technical Parameters Voltage Range L-N (Vac) Voltage Range L-L (Vac) Nominal Frequency (Hz) CT Ratio GM330 Three-phase, split-phase, single-phase 172~817 100~472 50/60 nA:5A Communication Method RS485 Support Grid Type Measuring Range 344 Technical Parameters Communication Parameters Precision Accuracy General Data Environmental Parameters Certification Parameters GM330 Communication Distance (m/ft) 1000/3280 Voltage/Current Active Energy Reactive Energy Dimension (WxHxDmm/in) Class 0.5 Class 0.5 Class 1 72x85x72/2.83x3.35×2.83 Housing 4 modules Weight (g/Ib) Mounting Method 240/0.53 DIN rail User Interface 4 LEDs, Reset Button Power Consumption (w) <5 Ingress Protection Rating Operating Temperature Range (℃/°F) Storage Temperature Range (℃/°F) Relative Humidity (No Condensing) Max. Operating Altitude (m/ft) IP20 Certificate UL1741/ANSI -30~+70/-22~+158 -30~70/-22~+158 0~95% 3000/9842 12.4 Smart Dongle Technical Data 12.4.1 WiFi/LAN Kit-20 Technical Parameters Output Voltage (V) Power Consumption (W) Communication Interface Ethernet WiFi/LAN Kit-20 5 <2 USB 10M/100Mbps Self-adaption 345 Technical Parameters Communication Wireless Parameters Bluetooth WiFi/LAN Kit-20 IEEE 802.11 b/g/n @2.4 GHz Bluetooth V4.2 BR/EDR and Bluetooth LE standard Dimension (W×H×D mm) Weight (g) Mechanical Parameters Ingress Protection Rating Mounting Method Operating Temperature Range (℃) Storage Temperature Range (℃) Relative Humidity Max. Working Altitude (m) 48.3*159.5*32.1 82 IP65 USB port insertion and removal -30~+60 -40~+70 0-95% 4000 12.4.2 4G Kit-CN-G20, 4G Kit-CN-G21 Technical Parameters Output Voltage (V) Power Consumption (W) Communication Interface Ethernet Communication Wireless Parameters Bluetooth WiFi/LAN Kit-20 5 <2 USB 10M/100Mbps Self-adaption IEEE 802.11 b/g/n @2.4 GHz Bluetooth V4.2 BR/EDR and Bluetooth LE standard Dimension (W×H×D mm) Weight (g) Mechanical Parameters Ingress Protection Rating Mounting Method Operating Temperature Range (℃) Storage Temperature Range (℃) Relative Humidity Max. Working Altitude (m) 48.3*159.5*32.1 82 IP65 USB port insertion and removal -30~+60 -40~+70 0-95% 4000 12.4.3 Ezlink3000 346 Technical Parameters Ezlink3000 General Data Connection Interface USB Ethernet Interface 10/100Mbps self-adaption, communication distance (optional) ≤100m Mounting Method Plug-and-play Indicator LED indicator Dimension (W×H×D 49*153*32 mm) Weight (g) 130 Ingress Protection IP65 Rating Power Consumption (W) ≤2W (typical value) Working Mode STA Wireless Parameters Bluetooth Bluetooth 5.1 Communication WiFi Communication 802.11 b/g/n (2.412GHz-2.484GHz) Environmental Parameters Operating Temperature -30~ +60 Range (℃) Storage Temperature -30~ +70 Range (℃) Relative Humidity 0-100% (no condensing) Max. Working Altitude 4000 (m) 347 13 Appendix 13.1 FAQ 13.1.1 How to conduct auxiliary detection for smart meters/CT? Meter detection function, which can detect whether the CT of the meter is connected correctly and the current operation status of the meter and CT. • Approach 1: 1. Access the detection page through Home > Settings > Electricity Meter/ CT Auxiliary Detection. 2. Click "Start Detection" and wait for the detection to complete. Then, view the detection results. • Approach 2: 1. Access the detection page through > [System Setup] > [Quick Setting] > [Meter/CT Assisted Test]. 2. Click "Start Detection" and wait for the detection to complete. Then, view the detection results. 13.1.2 How to Upgrade the Device Version Through the firmware information, you can view or upgrade the DSP version, ARM version, BMS version, and smart dongle software version of the inverter. Some smart dongles do not support software version upgrade via SolarGo App, and the actual situation shall prevail. • Upgrade prompt: When the user opens the APP, an upgrade prompt will pop up on the homepage, and the user can choose whether to upgrade or not. If you choose to upgrade, you can complete the upgrade by following the prompts on the interface. • Regular upgrade: Access the firmware information viewing interface through "Home" > "Settings" > "Firmware Information" 348 Click "Check for Updates". If there is a new version, complete the upgrade according to the prompts on the interface. • Forced Upgrade: The APP will push upgrade information, and users need to upgrade according to the prompts to continue using the app. You can complete the upgrade by following the prompts on the interface. 13.2 Abbreviations Abbreviation Ubatt Ubatt,r Ibatt,max (C/D) EC,R UDCmax UMPP IDC,max ISC PV PAC,r Sr (to grid) Smax (to grid) Sr (from grid) Smax (from grid) UAC,r fAC,r IAC,max(to grid) IAC,max(from grid) P.F. English Description Battery Voltage Range Nominal Battery Voltage Max. Charging Current Max. Discharging Current Rated Energy Max.Input Voltage MPPT Operating Voltage Range Max. Input Current per MPPT Max. Short Circuit Current per MPPT Nominal Output Power Nominal Apparent Power Output to Utility Grid Max. Apparent Power Output to Utility Grid Nominal Apparent Power from Utility Grid Max. Apparent Power from Utility Grid Nominal Output Voltage Nominal AC Grid Frequency Max. AC Current Output to Utility Grid Max. AC Current From Utility Grid Power Factor 349 Chinese Description 电池电压范围 额定电池电压 最⼤充/放电电流 额定能量 最⼤输⼊电压 MPPT 电压范围 每路 MPPT 最⼤输⼊电流 每路 MPPT 最⼤短路电流 Nominal Output Power 额定并⽹输出视在功率 最⼤并⽹输出视在功率 从电⽹买电额定输出视在功率 从电⽹买电最⼤输出视在功率 Nominal Output Voltage 输出电压频率 最⼤并⽹输出电流 最⼤输⼊电流 功率因数 Abbreviation Sr Smax IAC,max UAC,r fAC,r Toperating IDC,max UDC UDC,r UAC UAC,r Toperating Pmax PRF PD PAC,r F (Hz) ISC PV Udcmin-Udcmax UAC,rang(L-N) Usys,max Haltitude,max PF THDi THDv English Description Back-up Nominal apparent power Max. Output Apparent Power (VA) Max. Output Apparent Power without Grid Max. Output Current Nominal Output Voltage Nominal Output Freqency Operating Temperature Range Max. Input Current Input Voltage DC Power Supply Power Supply/AC Power Supply Power Supply/Input Voltage Range Operating Temperature Range Max Output Power TX Power Power Consumption Power Consumption Frequency Max. Input Short Circuit Current Range of input Operating Voltage Power Supply Input Voltage Max System Voltage Max. Operating Altitude Power Factor Total Harmonic Distortion of Current Total Harmonic Distortion of Voltage 350 Chinese Description 离⽹额定视在功率 最⼤输出视在功率 最⼤输出电流 最⼤输出电压 额定输出电压频率 ⼯作温度范围 最⼤输⼊电流 输⼊电压 直流输⼊ 输⼊电压范围/交流输⼊ 输⼊电压范围/交流输⼊ ⼯作温度范围 最⼤功率 发射功率 功耗 功耗 频率 最⼤输⼊短路电流 ⼯作电压范围 适配器输⼊电压范围 最⼤系统电压 最⾼⼯作海拔⾼度 功率因数 电流谐波 电压谐波 Abbreviation C&I SEMS MPPT PID Voc Anti PID PID Recovery PLC Modbus TCP/IP Modbus RTU SCR UPS ECO mode TOU ESS PCS RSD EPO SPD ARC DRED RCR AFCI GFCI RCMU FRT HVRT English Description Commercial & Industrial Smart Energy Management System Maximum Power Point Tracking Potential-Induced Degradation Open-Circuit Voltage Anti-PID PID Recovery Power-line Commucation Modbus Transmission Control / Internet Protocol Modbus Remote Terminal Unit Short-Circuit Ratio Uninterruptable Power Supply Economical Mode Time of Use Energy Stroage System Power Conversion System Rapid shutdown Emergency Power Off Surge Protection Device zero injection/zero export Power Limit / Export Power Limit Demand Response Enabling Device Ripple Control Receiver AFCI Ground Fault Circuit Interrupter Residual Current Monitioring Unit Fault Ride Through High Voltage Ride Through 351 Chinese Description ⼯商业 智慧能源管理系统 最⼤功率点跟踪 电位诱发衰减 开路电压 防PID PID修复 电⼒线载波通信 基于TCP/IP层的modbus 基于串⾏链路的modbus 短路⽐ 不间断电源 经济模式 使⽤时间 储能系统 电能转换系统 Rapid Shutdown 紧急关断 防雷保护 防逆流 命令响应设备 AFCI直流拉弧保护 接地故障分断器 残余电流监控装置 故障穿越 ⾼电压穿越 Abbreviation LVRT EMS BMS BMU BCU SOC SOH SOE SOP SOF SOS DOD English Description Low Voltage Ride Through Energy Management System Battery Management System Battery Measure Unit Battery Control Unit State of Charge State of Health State Of Energy State Of Power State Of Function State Of Safety Depth of discharge Chinese Description 低电压穿越 能量管理系统 电池管理系统 电池采集单元 电池控制单元 电池的荷电状态 电池健康度 电池剩余能量 电池充放电能⼒ 电池的功能状态 安全状态 放电深度 13.3 Explanation of Terms • Overvoltage Category Definition Category I: applies to equipment connected to a circuit where measures have been taken to reduce transient overvoltage to a low level. Category II: applies to fixed downstream equipment. For example, appliances, portable tools and other plug-connected equipment; Voltage category III is used if there are special requirements for the reliability and suitability of such equipment. Category III: applies to fixed downstream equipment, including the main distribution board. For example, switchgear and other equipment in an industrial installation Category IV: applies to the upstream equipment in the power supply of the distribution device, including measuring instruments and upstream over-current protection devices. • Definition of Types of Damp Places ○ ○ ○ ○ Environmental Parameters Temperature Range Humidity Range Level 3K3 4K2 4K4H 0~+40℃ -33~+40℃ -33~+40℃ 5% to 85% 5% to 85% 5% to 85% • Definition of Environmental Category: 352 Outdoor Inverter: The ambient air temperature range is -25 to +60℃, and it is suitable for environments with pollution degree 3. Indoor Type II Inverter: The ambient air temperature range is -25 to +40℃, and it is suitable for environments with pollution degree 3. Indoor Type I Inverter: The ambient air temperature range is 0 to +40℃, and it is suitable for environments with pollution degree 2. • Definition of Pollution Degree Categories: Pollution Degree 1: No pollution or only dry non-conductive pollution. ○ ○ ○ ○ ○ ○ ○ Pollution Degree 2: In general, there is only non-conductive pollution, but the transient conductive pollution caused by occasional condensation must be taken into account. Pollution Degree 3: There is conductive pollution, or the non-conductive pollution becomes conductive pollution due to condensation. Pollution Degree 4: Persistent conductive pollution, such as pollution caused by conductive dust or rain and snow. 13.4 Battery SN Code Meaning Bits 11-14 of the product SN code are the production time code. The above picture has a production date of 2023-08-08 • The 11th and 12th digits are the last two digits of the year of production, e.g., 2023 is represented by 23; • The 13th digit is the month of production, e.g., August is represented by 8; as follows: Month 1~ 9 10 11 12 Month 1~ 9 A B C • The 14th digit is the date of production, e.g., the 8th day is indicated by 8; 353 • priority is given to the use of numerical representation, e.g., 1~9 indicates the 1st~9th day, A indicates the 10th day, and so on. The letters I and O are not used to avoid confusion. The details are as follows: Production Date 1 2 3 4 5 6 7 8 9 Code 1 2 3 4 5 6 7 8 9 Production Date 10 11 12 13 14 15 16 17 18 19 20 Code A B C D E F G H J K L Production Date 21 22 23 24 25 26 27 28 29 30 31 Code M N P Q R S T U V W 354 X 14 Contact Details GoodWe Technologies Co., Ltd. No. 90 Zijin Rd., New District, Suzhou, China 400-998-1212 www.goodwe.com [email protected] 355 ">
Download
Advertisement
Key features
Integrated energy management system
Multiple system working modes
Remote monitoring via SEMS Portal
Support for parallel systems (up to 6 inverters)
Compatibility with lithium and lead-acid batteries
Smart control and optimization of power flow
Frequently asked questions
Self-use mode is the basic working mode of the system.
The smart meter can measure and monitor voltage, current, frequency, power factor, and power in the photovoltaic energy storage system.
When the number of batteries exceeds 8, two 600A fuses need to be connected in parallel.