advertisement
![Municipal Tie (Optional Municipal Tie Board FS-MT). Siemens FS-250 | Manualzz Municipal Tie (Optional Municipal Tie Board FS-MT). Siemens FS-250 | Manualzz](http://s1.manualzz.com/store/data/001168350_1-84101b0edd38e65805d7b0420797f60c-360x466.png)
FS-250 WITH RELEASING OPERATING INSTRUCTIONS
Pre-Alarm Operation
In case of an alarm on one of the devices on a releasing zone, the Pre-Alarm LED flashes, the LCD displays prealarm condition, the buzzer activates on-steady and any NACs configured to sound Pre-alarm will sound.
Alarm Operation
When another alarm occurs and the set threshold is satisfied on a releasing zone, the agent release timer is activated. The LCD display will display the timer as it counts down. The screen will display “agent release in XX seconds” and the “Pre-Discharge” LED will be on. Proceed according to the established emergency plan. Assure that all personnel are accounted for and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Authorized Personnel Only
To Abort the suppression release
Press the Abort switch, depending on the configuration of the panel the pre discharge timer will be halted or reset. Proceed to clearing and acknowledging the alarm.
To acknowledge the alarm:
To acknowledge the alarm, press the Acknowledge button. The local buzzer will be silenced and the Alarm
LED will change from on-flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, press the Alarm Silence switch. The notification appliances will be silenced. The Alarm Silenced LED will be on-steady.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined
time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing the System
Reset switch.
To initiate manual release:
Press the Manual Release switch. This will immediately activate the releasing zone and put the panel to discharge condition regardless of the previous condition of the panel.
NOTE: Manual release and abort switch are installed external to the panel and normally monitored by contact devices.
Trouble is indicated by:
Trouble LED flashes
LCD will display trouble conditions
Buzzer activates on-pulsing
Trouble Operation
To silence the trouble buzzer:
Operate the Button Enable key switch to the ON position and press the Acknowledge button. The Trouble
LED changes to on-steady. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence
Normal Standby Condition
The green Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Telephone Number: _____________________________________________
Frame these instructions and mount them near the annunciator for operator reference.
22
MAINTENANCE
GENERAL
The FS-250 provides a maintenance mode to allow for the setting and controlling of various features in the system.
The maintenance functions are protected by a four digit password. To access the maintenance features press the “MENU” button four times and select “Maint. Level” from the display, enter the four digit code when prompted and then press “Enter”. The functions listed below are now accessible to the user by using the function buttons on either side of the display.
Disable/Enable Devices
Disable/ Enable Groups
Disable Zones
Disable NACs
Disable City Tie
Disable DACT
Disable Status Relays
Disable/Enable Detector Applications
Quick Test
Print History
Print Sensor Levels
Edit Device Labels
Edit System Labels
Program a Device
Set the Time
Set the Date
Change the Password
Clear the History
Refer to the programming manual for more information about accessing and using the maintenance level functions.
45
QUICK TEST
If the control unit has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify the remote monitoring station before performing test operations, since an off-normal condition will be indicated.
The Quick Test mode makes it fast and easy to test a system by eliminating the need to reset the panel after each device is activated. Quick test is done on a loop basis so that the remainder of the system will continue to operate normally. Once the loop is placed into quick test, the NACs will sound for a short configurable period as each device on the loop is activated. In this way a single person is able to quickly check that each device is working and activating the system.
The printer may also be enabled or disabled during “Quick Test” as desired.
Refer to the programming manual for the details of accessing the Quick test functions.
For any required service, contact a factory-authorized representative.
46
APPENDIX-C: TROUBLESHOOTING
DEFINITIONS FOR EVENT HISTORY ENTRIES
A. General
ENTRY INDICATES
ALRM Alarm
AVCntr Alarm Verify counter
CrossZone cross zone point
LCDxx
MANL PULL
Mntc
PAS
PAS INHBT
LCD Annunciator xx
Manual pull station
Detector maintenance alert
Positive alarm sequence
PAS inhibit switch
PRE SIGNL pre-signal
PreA Pre-alarm
SUPERVSRY Supervisory
SUPR Supervisory
TRBL Trouble
TROUBLE Trouble
WATERFLOW Waterflow
63
B. System Troubles
ENTRY INDICATES
AC Trouble
AddrLp 1 DBLSHT
AddrLp 1 OPEN
AddrLp 1 SHORT
BATT Trouble
CITY Trouble
DACT Acct Trb
DACT Com Trouble
DACT PL x Trouble
FLASH FATAL Trb
GRND FAULT Trbl
LCDxx NoRespons
LCDxx Not Pgmd
LCDxx Trouble
MNLP Bad Msg
MNLP Fifo Xmit
MNLP NoRespons
NACxx Trouble
PC Pgmr Trb
QuickTest Abort
Trb Reminder
AC input low or off
Double short trouble on addressable loop 1
Open circuit trouble on addressable loop 1
Short circuit trouble on addressable loop 1
Battery input low or off
Local Energy circuit open
DACT account reporting trouble
DACT communication trouble with main processor
Open or short on DACT phone line x
Configuration Flash memory trouble
Ground Fault trouble
LCD Annunciator xx programmed but is not responding
LCD Annunciator xx is not programmed but is responding
LCD Annunciator xx reports trouble
Main processor to loop processor communication trouble
Main processor to loop processor communication trouble
Main processor to loop processor communication trouble
NAC xx wiring is open or shorted
Control panel is not receiving communication from PC
Quick Test Timer expired causing abnormal exit of Quick Test
Trouble Reminder timer expired
64
C. System Events
ENTRY INDICATES/NOTES
Alarm Silenced
All AV Ctrs Clr
AutoProgram Run
Backup Cnfg Check
Backup Cnfg Edit
ConfigsCompared
ConfigsSwapped
EventHist Clear
Mnt Levl Enter
Mnt Levl Exit
MAIN, LCDxx shown on bottom line
All AV counters cleared
Auto programming function run
Backup configuration validated, result on bottom line
Backup configuration edited
Backup and primary configurations compared, result on bottom line
Backup and Primary configurations swapped
Event History cleared
Entered Maintenance level
Exited Maintenance level
Mnt Levl PW Changed Changed Maintenance level password
NACxx Active Confirm NAC activation confirmed
Panel Reset MAIN, LCDxx shown on bottom line
Power Up
PriConfigCopied
QuickTest Exit
Primary configuration copied to backup
Exited Quick Test, MAIN or LCDxx shown on bottom line
QuickTest Start Started Quick Test, MAIN or LCDxx shown on bottom line
System Date Changed Changed system date, old and new dates shown on lines 3 and 4
System Time Changed Changed system time, old and new times shown on lines 3 and 4
Tech Levl Enter Entered Tech level
Tech Levl Exit Exited Tech level
Tech Levl PW Changed Changed Tech level password
User Levl Enter Entered User level
User Levl Exit Exited User level
65
APPENDIX-E: ALARM VERIFICATION
Alarm verification provides FS-250 with a way to verify an alarm from area type addressable smoke detectors connected to intelligent loops (FS-DLC). This feature reduces the incidence of false alarms. Only detectors that do not contain an integral alarm verification feature can be used.
Addressable detectors connected to FS-DLCs indicate that an alarm condition has been detected. If the device is subject to alarm verification, the FS-DLC alerts the control panel that the device has entered verification but is not yet considered to be in alarm. The FS-DLC starts a timer using the FS-250 system Retard-Reset Period. When the timer expires, the FS-DLC begins the fixed 60-second confirmation period. If the device is no longer in alarm during the confirmation period, the verification cycle is considered complete and detection of a subsequent alarm from that device results in the verification cycle restarting. If the device still reports in the alarm state during this confirmation period, the alarm condition is reported to the control panel and the system annunciates the alarm condition.
See the figure below for a graphic illustration of Alarm Verification.
NOTE: For devices connected to the FS-DLC, the Detector Restart period is 0 seconds.
ALARM VERIFICATION TIMING DIAGRAM
ALARM VERIFICATION PERIOD
RETARD-RESET-RESTART PERIOD -- MAXIMUM 60 SECONDS
NO ALARM AT CONTROL UNIT
CONTROL UNIT
RETARD-RESET PERIOD
DETECTOR RESTART
(POWER-UP) PERIOD
CONFIRMATION PERIOD -- 60 SECONDS
ALARM REQUIRED AT CONTROL UNIT
OPTIONAL
REGION
A t=0 Seconds
B C D E t=n Seconds
A - Smoke detector goes into alarm.
AB - RETARD-RESET PERIOD (Control Unit) - Control unit senses detector in alarm and retards (delays) alarm signal, usually by de-energizing power to the detector. Length of time vaires with design. (11 to 55 seconds)
BC - RESTART PERIOD (Detector Power-up Time) - Power to the detector is reapplied and time is allowed for detector to become operational for alarm. Time varies with detector design.
AC - RETARD-RESET-RESTART PERIOD - No alarm obtained from control unit. Maximum permissible time is 60 seconds.
CD - CONFIRMATION PERIOD - Detector is operational for alarm at point C. If detector is still in alarm at point C, control unit will alarm. If detector is not in alarm, system returns to standby. If the detector re-alarms at any time during the confirmation period the control unit will alarm.
DE - OPTIONAL REGION - Either an alarm can occur at control unit or restart of the alarm verification cycle can occur.
AD - ALARM VERIFICATION PERIOD - Consists of the retard-reset-restart and confirmation periods.
67
APPENDIX-F: APPLICATION SPECIFIC
DETECTION
Application Specific Detection (ASD) allows the system designer to program an HFP-11 detector’s sensitivity, pre-alarm threshold, and other alarm-related parameters using English descriptions of the detector's environment (application). This eliminates the need for detailed knowledge of smoke detector terminology and operation. The designer can set all of the critical detector parameters by simply selecting an application description that closely fits the one where the detector is to be installed.
For example, to use ASD to select the optimal parameters for a detector in a hotel lobby, select the LOBBY application in the FS-CT2 tool for that device. The system will automatically transmit the factory determined sensitivity, pre-alarm threshold, and detection algorithm (Ralgorithm) to the corresponding device. This eliminates the guesswork of selecting these parameters for different environments.
ASD Application
Disable
Office (Retail)
Warehouse (Light Manufacturing)
Lobby
Computer Room
Dormitory
Healthcare
Parking Garage
Utility (Transformer) Room
Precious Storage (Sensitive
Environment)
Hostile Environment
Duct (Open air or duct housing)
ASD APPLICATIONS
ASD Description
No Applications (Standard Photo/thermal Detector)
Reasonably clean, climate controlled atmosphere
Airborne dust, equipment, fork truck and light to medium dock area exhaust fumes
Relatively clean area, temperature changes, cellular phones, smoking
Very controlled environment, clean, temperature closely regulated, high cost clean machinery operating, no smoking, high air velocity
Airborne dust and temperature changes, living quarters, cooking fumes, smoking
Higher level risk, relatively clean, electronic equipment
Airborne dust, car and diesel fumes, temperature swings
Normal to somewhat dirty environment, heat from running equipment
Sensitive materials or equipment storage, clean dust-free environment, earliest warning desired
Dirty, dusty, humid, operating equipment, RF present, wide temperature swings
Dirty, dusty, humid, wide temperature swings, high air velocity
68
APPENDIX-G: TESTING/MAINTENANCE
If the system is connected to the fire department, etc., or actuates an internal system, disarm the appropriate outputs before servicing to prevent actuation. Notify the fire department and personnel at your facility that a System test is being performed so that any alarm sounding can be ignored during the test. Notify the fire department before resetting the system.
Inspection, Testing, and Maintenance of the fire alarm system should be performed in accordance with NFPA 72, The National Fire Alarm Code and all applicable local codes.
69
APPENDIX-H: LCD, CONTROLS AND
INDICATORS
The FS-250 has a sounder, 6 LEDs, 4 navigational push buttons adjacent to the LCD display
(M1-M4), 3 dedicated push buttons, alphanumeric keypad and communication port connector.
Communication Port Connector
The communication port is connected to the serial output terminal of the computer that has the
FS-CT2 programming tool. This is used to upload and/or download panel configuration if this method of programming is used.
The computer must be disconnected from the panel if not in use.
LEDS, Sounder and Dedicated Push Buttons
The LEDs operate as follows:
POWER (Green)
ALARM (Red)
ALARM SIL (Yellow)
Normally ON (steady) – indicates that power is applied to the panel.
OFF indicates that the panel is not powered up.
Normally OFF – indicates that there is no alarm event in the system.
ON (flashing) – indicates that at least ONE alarm event is unacknowledged.
ON (pulsing) – indicates that ALL alarm events have been acknowledged.
Normally OFF – indicates that NACs are in the OFF state if the system is in normal supervisory mode.
If any event is present, it indicates that the silenceable NACs are in the OFF state.
ON (steady) – indicates that at least one silenceable NAC has been activated.
PRE-ALARM (Yellow)
SUPERVISORY (Yellow)
TROUBLE (Yellow)
DISCHARGE LED (Yellow)
Normally OFF – indicates that there is no pre-alarm event in the system.
ON (flashing) – indicates that at least ONE pre-alarm event is unacknowledged.
ON (steady) – indicates that ALL pre-alarm events have been acknowledged.
Normally OFF – indicates that there is no supervisory event in the system.
ON (flashing) – indicates that at least ONE supervisory event is unacknowledged.
ON (steady) – indicates that ALL supervisory events have been acknowledged.
Normally OFF – indicates that there is no trouble event in the system.
ON (flashing) – indicates that at least ONE trouble event is unacknowledged.
ON (steady) – indicates that ALL trouble events have been acknowledged.
Indicates that one of the releasing circuits is active
PRE-DISCHARGE LED (yellow) Indicates that the panel is counting down the release delay timer before discharge
ABORT Led (Yellow) Indicates that one of the devices which have been assigned to abort the discharge is active
70
The sounder operates as follows:
SOUNDER Normally OFF – indicates that the system is in supervisory mode or all events in the system have been acknowledged.
ON (steady) – indicates that at least ONE unacknowledged alarm is present in the system.
ON (pulsing) – indicates that at least ONE unacknowledged non-alarm (trouble, supervisory or pre-alarm) event is present in the system.
Dedicated Push Buttons:
ALARM SILENCED When pressed when ALARM SILENCED LED is OFF, silences all the activated silenceable NACs.
When pressed when the ALARM SILENCED LED is ON, reactivates all previously silenced NACs.
ACKNOWLEDGE
RESET
M1 – M4
When pressed, acknowledges all events that are unacknowledged.
When pressed, initiates a system reset.
These push buttons are used for navigation while in the USER screen.
If events are present in the system, M1 (UP button) is used to scroll up to the next event and M2 (DOWN button) is used to scroll to the previous event, M3 (TOP button) is used to place the list at the top of the queue and M4 (NEXT QUE) is used to go to the next queue (if present) of lower priority.
Alphanumeric Keypad:
The alphanumeric keypads are used to enter the password to access the maintenance and technician modes of the panel. It allows the user to program the panel using these keypads without using the FS-CT2 programming tool.
Refer to the FS-250 Programming Manual (P/N 315-049403).
LCD Display:
The LCD operates as follows:
Supervisory Mode:
Line 1 – First Custom Message and System ID
Line 2 – Second Custom Message and System ID
Line 3 – Current Time
Line 4 – Day and Date
20 supervisory msg01
20 supervisory msg02
10:16:30 am
Monday 07/26/04
Active Event Mode:
Line 1 – Event type, Event location in the list and time the event occurred.
Line 2 – First 20 character custom message.
Line 3 – Second 20 character custom message.
R-SUP 100/100 10:14
20 char custom msg01
20 char custom msg02
1003 Dual in/rel
Line 4 – acknowledged or unacknowledged event, address of the device where the event occurred and a generic description of the device or trouble type.
71
The events are displayed one at a time and cycle through a circular list once the first event or last event message is reached.
72
APPENDIX-I: GLOSSARY
Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, or an automatic smoke detector.
Alarm Silence Inhibit. An option that prevents a human operator from silencing the notification appliances for a preset period of time.
Alarm System. A combination of compatible initiating devices, control panels, and notification appliances designed and installed to produce an alarm signal in the event of a fire.
Alarm Verification. A preset option that causes the control panel to verify alarms originated by smoke detectors before indicating an alarm.
Annunciator. A remotely located, electrically powered display, separate from the control panel, containing LEDs or lamps to indicate the states of the fire alarm system.
Audible Signal. An audible signal is a sound made by one or more audible notification appliances, such as bells or horns, in response to the operation of an initiating device.
Authority Having Jurisdiction (AHJ). The organization, office, or individual responsible for approving equipment, installation or procedure.
Auto-Silence. The capability of a control to automatically silence the notification appliances after a preset period of time.
Auxiliary Relays. Control relays that energize only during alarm conditions that are used to either apply power to or remove power from other equipment during an alarm condition.
Class A Circuit. An initiating device or notification appliance circuit within which all components remain fully functional, even though a single open or ground exists in the circuit.
Class B Circuit. An initiating device or notification appliance circuit within which some or all components may be disabled with a single open or ground exists in the circuit.
Detector - FirePrint™. An intelligent fire detector that blends photoelectric, thermal and neural network technologies for superior protection without false alarms.
Detector - Smoke, Photoelectric Type. A detector employing the photoelectric principle of reflection or obstruction of light by smoke.
Detector - Thermal Type. An addressable thermal sensor that is programmable as either a fixed temperature (135° F) or as a rate of rise detector.
End Of Line (EOL). A device used to terminate a supervised circuit.
General Alarm. A term usually applied to the simultaneous operation of all the notification appliances on a system.
73
Ground Fault. A trouble condition in which a low resistance has been detected between the system wiring and conduit ground.
Initiating Device. A manually or automatically operated device such as a manual pull station, smoke detector, heat detector, waterflow switch or tamper switch.
Initiating Device Circuit (IDC). A circuit to which initiating devices are connected.
Labeled. Equipment or materials to which have been attached a label, symbol, or other identifying mark of an organization acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of the production of such labeled equipment or materials. And by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Listed. Equipment or materials included in a list published by an organization acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of listed equipment or materials. And whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.
NEC. National Electrical Code also published as NFPA standard 70.
Notification Appliance. An electrically operated appliance used to indicate the system status such as a bell, horn, strobe light or speaker.
Notification Appliance Circuit (NAC). A circuit to which notification appliances are connected.
Power Supply. That portion of the fire alarm control panel, which provides the power needed to operate all control panel modules, as well as that, needed to operate all electrically powered initiating devices and all notification appliances.
Quick Test. A term pertaining to the test mode of the system, that automatically resets after a service technician tests initiating devices.
Supervisory Alarm. A signal indicating the operation of a supervisory device.
Supervisory Device. A device that monitors the condition of a sprinkler system such as a gate-valve switch, water-level switch, low pressure switch, low temperature switch or fire pump monitor.
Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or ground, occurring in the device or wiring associated with a fire alarm signal.
Waterflow Switch. An assembly approved for service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition.
Zone. A designated area of a building. Commonly, zone, is interchanged with initiating device circuit.
74
75
Siemens Building Technologies, Inc. P/N 315-049353-6 (10.12.05)
8 Fernwood Road
Florham Park, New Jersey 07932
advertisement
Related manuals
advertisement
Table of contents
- 7 INTRODUCTION
- 7 CONTROL PANEL LIMITATIONS
- 8 PREFACE
- 9 DESCRIPTIONS
- 9 FS-250 SYSTEM DESCRIPTION
- 9 Power Supply
- 9 P2 Addressable Device Circuit
- 10 Notification Appliance Circuits
- 10 Serial Interface Circuit
- 10 Status Relays
- 10 Programming Port
- 11 OPTIONAL MODULES
- 11 FS-MT Municipal Tie Board
- 11 FS-DACT Board
- 11 FS-NPE Transformer Assembly
- 11 FS-DLC Loop Driver Board
- 11 Battery Sets
- 11 FS-REL Releasing Module
- 12 AUXILIARY MODULES
- 12 Serial LCD Annunciator
- 12 Serial Relay Unit and Serial Relay Extender
- 12 Serial Annunciator Unit and Serial Annunciator Extender
- 12 PAD-3 Remote Signal Expander
- 13 P2 ADDRESSABLE DEVICES
- 13 FirePrintâ„¢ Smoke Detector
- 13 Heat Detectors
- 13 Addressable Modules (Monitor and Control)
- 13 Manual Stations
- 13 Programming P2 Devices
- 15 EVENT HISTORY
- 15 GENERAL DESIGN FEATURES
- 15 Environmental
- 15 Power Limiting
- 15 Ground Fault Detection
- 15 NAC Operation
- 15 Transient Protection
- 15 Security Features
- 16 REGULATORY STANDARDS
- 16 Federal Communications Commission
- 16 Underwriters Laboratories
- 17 GENERAL SPECIFICATIONS
- 17 Environmental
- 17 Primary Supply
- 17 Secondary and Trouble Power Supply
- 17 Auxiliary Power Outputs
- 17 Status Relays
- 18 Notification Appliance Circuits
- 18 Serial Interface Circuit
- 18 P2 Addressable Device Circuits
- 19 Municipal Tie (Optional Municipal Tie Board FS-MT)
- 19 DACT Circuit (Optional DACT Board FS-DACT)
- 19 Additional Transformer (Optional Transformer Sub-Assembly FS-NPE)
- 19 FS-REL (Optional Releasing Module)