MPC-6000 / MPC-7000 / RND-2
Fire Alarm System Control Unit
Installation, Operation and Maintenance Manual
Siemens Building Technologies, Inc.
8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600 • Fax: (973) 593-6670
Web: www.faradayfirealarms.com
P/N 315-447309-5
TABLE OF CONTENTS
INTRODUCTION ....................................................................................................................................................... 1
CONTROL UNIT LIMITATIONS.........................................................................................................................................1
INSTALLATION AND WARRANTY INFORMATION .....................................................................................................2
Installer Information: ..........................................................................................................................................................2
Original Purchaser Information:.........................................................................................................................................2
PREFACE...............................................................................................................................................................................3
DESCRIPTIONS........................................................................................................................................................ 4
MPC-6000 SYSTEM DESCRIPTION ...................................................................................................................................4
Power Supply .......................................................................................................................................................................4
X1 Addressable Device Circuit ............................................................................................................................................4
Notification Appliance Circuits ...........................................................................................................................................5
Serial Interface Circuit ........................................................................................................................................................5
Status Relays........................................................................................................................................................................5
Programming Port...............................................................................................................................................................5
MPC-7000 SYSTEM DESCRIPTION ...................................................................................................................................6
Power Supply .......................................................................................................................................................................6
X1 Addressable Device Circuits ..........................................................................................................................................6
Notification Appliance Circuits ...........................................................................................................................................7
Serial Interface Circuit ........................................................................................................................................................7
Status Relays........................................................................................................................................................................7
Programming Port...............................................................................................................................................................7
RND-2 SYSTEM DESCRIPTION .........................................................................................................................................8
Power Supply .......................................................................................................................................................................8
Serial Interface Circuit ........................................................................................................................................................9
Status Relays........................................................................................................................................................................9
Programming Port...............................................................................................................................................................9
OPTIONAL MODULES ......................................................................................................................................................10
CT-1K City Tie Board (MPC-6000 / MPC-7000 / RND-2) ...............................................................................................10
MPC-DACT DACT Board (MPC-6000 / MPC-7000 / RND-2) .........................................................................................10
NPE-1 Transformer Assembly (MPC-6000 / MPC-7000) .................................................................................................10
NEM-1 NAC Expansion Board (MPC-7000).....................................................................................................................10
LEM-1 Loop Expander Board (MPC-7000) ......................................................................................................................10
FDLC Loop Driver Board (MPC-7000) ............................................................................................................................10
HBC-1 Battery Charger (MPC-7000)................................................................................................................................10
Battery Sets ........................................................................................................................................................................10
AUXILIARY MODULES ....................................................................................................................................................11
Serial LCD Annunciator ....................................................................................................................................................11
Serial Relay Unit and Serial Relay Extender.....................................................................................................................11
Serial Annunciator Unit and Serial Annunciator Extender ...............................................................................................11
RSE-300 Remote Signal Expander.....................................................................................................................................11
X1 ADDRESSABLE DEVICES ..........................................................................................................................................12
Fire Smart™ Smoke Detector............................................................................................................................................12
Heat Detectors ...................................................................................................................................................................12
Addressable Modules (Monitor and Control) ....................................................................................................................12
Manual Stations .................................................................................................................................................................12
Programming X1 Devices ..................................................................................................................................................12
EVENT HISTORY ...............................................................................................................................................................13
GENERAL DESIGN FEATURES .......................................................................................................................................14
Environmental....................................................................................................................................................................14
Power Limiting ..................................................................................................................................................................14
Ground Fault Detection.....................................................................................................................................................14
i
NAC Operation ..................................................................................................................................................................14
Transient Protection ..........................................................................................................................................................14
Security Features ...............................................................................................................................................................14
REGULATORY STANDARDS...........................................................................................................................................15
Federal Communications Commission ..............................................................................................................................15
Underwriters Laboratories ................................................................................................................................................15
GENERAL SPECIFICATIONS ...........................................................................................................................................16
Environmental....................................................................................................................................................................16
Primary Supply ..................................................................................................................................................................16
Secondary and Trouble Power Supply...............................................................................................................................16
Auxiliary Power Outputs ...................................................................................................................................................16
Status Relays......................................................................................................................................................................16
Notification Appliance Circuits .........................................................................................................................................17
Serial Interface Circuit ......................................................................................................................................................17
X1 Addressable Device Circuits ........................................................................................................................................17
City Tie (Optional City Tie Board P/N CT-1K) .................................................................................................................18
DACT Circuit (Optional DACT Board MPC-DACT) ........................................................................................................18
Additional Transformer (Optional Transformer Assembly NPE-1)...................................................................................18
CONTROL UNIT OPERATION ............................................................................................................................... 19
OPERATION INSTRUCTIONS ..........................................................................................................................................19
Standby Condition..............................................................................................................................................................19
Alarm Conditions...............................................................................................................................................................19
Trouble Conditions ............................................................................................................................................................20
Supervisory Conditions......................................................................................................................................................21
Pre-Alarm Conditions........................................................................................................................................................21
Maintenance ......................................................................................................................................................................21
ADDITIONAL OPERATING PROCEDURES ...................................................................................................................22
Lamp Test...........................................................................................................................................................................22
Drill ...................................................................................................................................................................................22
Recall .................................................................................................................................................................................22
Alert ...................................................................................................................................................................................22
History ...............................................................................................................................................................................23
MPC-6000 / MPC-7000 / RND-2 OPERATING INSTRUCTIONS ....................................................................................24
Alarm Operation ................................................................................................................................................................24
Authorized Personnel Only ................................................................................................................................................24
Trouble Operation .............................................................................................................................................................24
Normal Standby Condition ................................................................................................................................................24
RDC-2 OPERATING INSTRUCTIONS..............................................................................................................................25
Alarm Operation ................................................................................................................................................................25
Authorized Personnel Only ................................................................................................................................................25
Trouble Operation .............................................................................................................................................................25
Normal Standby Condition ................................................................................................................................................25
CONTROL UNIT INSTALLATION .......................................................................................................................... 26
PARTS SUPPLIED – MPC-6000 / MPC-7000 / RND-2 .....................................................................................................26
Enclosure Packages (Black or Red)...................................................................................................................................26
Electronics Package MPC-6000 / MPC-7000 ...................................................................................................................26
Electronics Package RND-2 ..............................................................................................................................................26
With NPE-1 Transformer Package ....................................................................................................................................26
CAUTION ............................................................................................................................................................................26
CONTROL UNIT LOCATION............................................................................................................................................27
INSTALLATION .................................................................................................................................................................27
ENCLOSURE MOUNTING ................................................................................................................................................27
MPC-6000 and RND-2 Enclosure Mounting Pictures.......................................................................................................28
MPC-7000 Enclosure Mounting Pictures..........................................................................................................................29
Remove Knock-Outs...........................................................................................................................................................29
Main Board Installation – P/N MPC6-MB / MPC7-MB....................................................................................................30
Bridge Rectifier Installation – P/N 130-PM3223 ..............................................................................................................31
ii
Transformer Mounting – P/N NPE-1.................................................................................................................................32
Loop Driver Board(s) Mounting – P/N FDLC...................................................................................................................33
Display Board Installation – P/N MPC-DB or RND2-DB ................................................................................................34
Ground Wire Installation – P/N 600-149373....................................................................................................................34
SYSTEM WIRING.................................................................................................................................................... 35
AC Supply Connection .......................................................................................................................................................35
Battery Installation ............................................................................................................................................................36
Powering the Control Unit ................................................................................................................................................36
Optional Modules ..............................................................................................................................................................36
Check System Operation ....................................................................................................................................................36
WIRING................................................................................................................................................................................36
Control Unit Wiring Overview...........................................................................................................................................37
Wiring Entering Enclosure ................................................................................................................................................37
Install Wiring .....................................................................................................................................................................37
Wiring Separation..............................................................................................................................................................38
Primary And Secondary Power Wiring .............................................................................................................................39
Status Relays And Auxiliary Power Outputs Wiring..........................................................................................................39
MPC-6000 System Power Requirements (Does not include NAC power) .........................................................................40
RND-2 System Power Requirements..................................................................................................................................40
MPC-7000 System Power Requirement (Does not include NAC power)...........................................................................40
Auxiliary Power Supply .....................................................................................................................................................41
Battery Size Calculations...................................................................................................................................................41
NAC Wiring .......................................................................................................................................................................42
Serial Interface Circuit ......................................................................................................................................................43
Serial Remote Device Wiring Overview.............................................................................................................................44
X1 Addresable Device Circuit(s) .......................................................................................................................................45
X1 Addressable Device Wiring Diagrams .........................................................................................................................46
PROGRAMMING THE CONTROL UNIT ................................................................................................................ 48
KEYPAD PROGRAMMING ...............................................................................................................................................48
PC PROGRAMMING ..........................................................................................................................................................48
PROGRAMMING SECURITY............................................................................................................................................48
MAINTENANCE ...................................................................................................................................................... 49
GENERAL............................................................................................................................................................................49
QUICK TEST .......................................................................................................................................................................50
APPENDIX-A: REFERENCE DATA ....................................................................................................................... 51
WIRE SELECTION GUIDES ..............................................................................................................................................51
Resistance of Solid Copper Wire .......................................................................................................................................51
Notification Appliance Circuit Wire Selection Guide ........................................................................................................51
Maximum Wire Loop Distance (Feet)................................................................................................................................51
Addressable Device Circuit Wire Selection Guide ............................................................................................................52
Line Resistance Graph.......................................................................................................................................................52
BATTERY SIZE CALCULATIONS ...................................................................................................................................53
MPC-6000 Current Calculations.......................................................................................................................................53
RND-2 Current Calculations .............................................................................................................................................53
MPC-7000 Current Calculation ........................................................................................................................................53
Auxiliary Module Battery Calculations .............................................................................................................................55
Device Current Calculations .............................................................................................................................................55
Total System Currents........................................................................................................................................................56
Battery Size ........................................................................................................................................................................56
APPENDIX-B: COMPATIBLE DEVICES................................................................................................................ 57
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS.....................................................................................................57
Faraday X1 Manual Pull Stations .....................................................................................................................................57
Faraday X1 Modules .........................................................................................................................................................57
Faraday X1 Photo Electric Detectors................................................................................................................................57
Faraday X1 Bases..............................................................................................................................................................57
Faraday X1 Accessories ....................................................................................................................................................57
iii
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS ..............................................................................................58
Notification Appliances......................................................................................................................................................58
Accessory Devices..............................................................................................................................................................61
DEVICES FOR AUXILIARY POWER OUTPUTS ............................................................................................................61
Door Holders .....................................................................................................................................................................61
Relays.................................................................................................................................................................................61
APPENDIX-C: TROUBLESHOOTING.................................................................................................................... 62
DEFINITIONS FOR EVENT HISTORY ENTRIES ...........................................................................................................62
A. General..........................................................................................................................................................................62
B. System Troubles.............................................................................................................................................................63
C. System Events ................................................................................................................................................................64
APPENDIX-D: MODULE INSTALLATION INSTRUCTIONS LIST ........................................................................ 65
APPENDIX-E: GLOSSARY .................................................................................................................................... 66
iv
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
INTRODUCTION
CONTROL UNIT LIMITATIONS
This control unit may not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and notification devices (horn, lights, etc.) connected to it. Electrical ratings of the initiation and notification appliances must be compatible with the electrical ratings of the control unit and must be properly interconnected. The wiring used for interconnection must be large enough to carry the total current for all appliances without excessive voltage drop. The
RND-2 will not indicate alarm conditions without being connected to and configured correctly on an MPC-NET2 network.
The control unit must be connected to a dedicated primary electrical source that has a high degree of reliability and adequate capacity for this control unit. The only means of disconnecting this power source shall be available only to authorized personnel and clearly marked "Fire Alarm Circuit Control".
The control unit must also have connected to it a battery set (24V) that has enough capacity to properly operate the system for 24 or 60 (depending on system type) hours standby and 5 minutes alarm per NFPA 72 (chapter 1). These batteries do lose capacity with age. Batteries must be replaced when they fail to provide the control unit with the required standby and alarm power or after 4 years, whichever happens first. These batteries must be checked for performance at least two (2) times a year or more often if local requirements dictate.
Fire alarm control units cannot last forever. Even though this control unit was made to last for the expected life of the fire alarm system, any part could fail at any time. Therefore a regular test program should be followed and documented to make sure that each part of the system is tested as in Chapter 7 of NFPA 72 or more often if dictated by local code requirements.
Malfunctioning units must be replaced or repaired immediately by factory authorized service personnel.
This control unit is designed to show an alarm condition when the initiating devices connected to it detect specific conditions. These conditions may or may not represent a lifethreatening condition. Also, evacuation of a building or area unnecessarily may subject individuals to an unnecessary hazard. Therefore, it is most important that the building owner, manager, or representative promulgate, distribute, and/or post instructions describing steps to be taken when the fire alarm control unit signals an alarm condition. These instructions should be developed in cooperation and conformance with representatives of the local authority having jurisdiction.
As a backup or precautionary measure, it is strongly suggested that one of these steps should be to notify the local fire department of an abnormal condition even where the DACT option (or similar device) is included in the system.
1
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
INSTALLATION AND WARRANTY INFORMATION
Warranty Information: Faraday (the Manufacturer) provides a limited warranty to the original purchaser of this product. The original purchaser is the party to whom the manufacturer issued its sales order, generally the manufacturer's distribution. In order to preserve this warranty, it is important that only persons who have been properly trained and authorized by the manufacturer service the product.
Other parties involved in the installation of this product may have also provided a warranty, which may be different from that of the manufacturer. The manufacturer will only be responsible to the original purchaser and only for the manufacturer's own warranty. For further information regarding the manufacturers warranty, contact the original purchaser.
OWNER'S MANUAL: The owner's manual does not purport to cover all the details or variations in the equipment described, nor does it provide for every possible contingency to be met in connection with installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are not covered sufficiently, the matter should be referred to the installer or original purchaser listed below.
Installer Information:
Installer:
Company:
Address:
City:
Phone:
Date installed:
Installer's signature:
Original Purchaser Information:
Company:
Address:
City:
Phone:
Date purchased:
Purchaser's purchase order number:
Faraday sales order acknowledgment number:
Original purchaser's signature:
State: Zip:
State: Zip:
2
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PREFACE
Along with the use of this instruction manual, the appropriate following standards and the manufacturer's instructions for initiating and notification devices should be used to install and maintain a functioning fire alarm signaling system.
NFPA 70 National Electrical Code
NFPA 72 National Fire Alarm Code
NFPA 101 Life Safety Code
For other standards that may apply contact the authority having jurisdiction.
For NFPA publications, contact:
National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
3
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
DESCRIPTIONS
MPC-6000 SYSTEM DESCRIPTION
The MPC-6000 is a modular fire alarm control unit. It features advanced addressable detection, programming, and memory capability. Its base configuration includes a power supply, an X1 addressable device circuit, four/two notification circuits (NAC), serial interface circuit, four status relays and a programming port.
The MPC-6000 control unit mounts in a 22" x 18" backbox with overall cover size of 22-9/32" x
18-3/8". Operating controls and indicators are mounted on the inside hinged plate. An 80
(4x20) – alphanumeric character LCD provides specific indications for addressable devices while LEDs indicate general panel status.
Semi-flush mounting kits are available for the enclosure.
The main board mounts in the rear of the enclosure. The power supply is physically contiguous with the main board. The MPC-6000 main board (MPC6-MB) provides the connections for external field wiring. Optional boards mount on the main board or on the rear of the enclosure.
The display board mounts on the inner-hinged plate.
All normal operation is controlled via a membrane keypad. Displays are provided by an 80character, alphanumeric, backlit LCD display and by discrete LED indicators for major control unit functions.
The 80-character LCD is used to display event data, including alarms and troubles, identification of zone or device, and presentation of history. The display is controlled by a set of four push-button switches commanding the control processor. A back light is included in the display to assure visibility in low light, but to conserve power, it is only activated during a reported event or on operation of a display control switch.
Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM,
SUPERVISORY, ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct pushbutton controls are provided for ALARM SILENCE, ACKNOWLEDGE, MENU and SYSTEM
RESET.
Power Supply
A regulated fullwave rectified 24V nominal power supply provides all operating power to the control unit for both standby and alarm conditions. Sufficient battery charging capability is available to charge 38.5 AH sealed lead-acid batteries within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only up to 12 AH. The back-up battery is 24V, maintained by floating on the power supply. The battery will be automatically disconnected at low battery voltage to prevent deep discharge.
X1 Addressable Device Circuit
The MPC-6000 control unit has one addressable device circuit utilizing the X1 Detection
Technology. The circuit has the capacity for 252 addresses.
4
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Notification Appliance Circuits
The MPC-6000 control unit has four independent Class B (Style Y) notification appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation. This reduces the number of NACs to two. Each circuit can be selected to give continuous output or one of eight sounding patterns available in the control unit including the Faraday SYNC Protocol.
There is also a system coder capable of zone-coded operation. All of the NACs are power limited.
Serial Interface Circuit
The MPC-6000 control unit has a Serial Interface Circuit that will drive up to 16 remote LCD annunciators and 8 Serial Relay Units and Serial Annunciator Units.
Status Relays
Four relays with dry contacts are provided. These relays are programmable to power fail, alarm, trouble and supervisory functions. The relay contacts are Form C and are rated 1A @
28VDC resistive.
Programming Port
An RJ-11 jack is provided for a non-isolated RS-232 connection for temporary connection to a computer for panel programming.
5
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MPC-7000 SYSTEM DESCRIPTION
The MPC-7000 is an expandable modular fire alarm control unit. It features advanced addressable detection, programming, and memory capability. Its base configuration includes a power supply, two X1 addressable device circuits, four/two notification circuits (NAC), serial interface circuit, four status relays and a programming port.
The basic MPC-7000 control unit mounts in a 38" x 18" backbox with overall cover size of 38-
9/32" x 18-3/8". Operating controls and indicators are mounted on the plate with a polycarbonate decal for identification. An 80-character LCD provides specific indications for addressable devices while LEDs indicate general panel status.
Semi-flush mounting kits are available for the enclosure.
The main board mounts in the rear of the enclosure. The power supply is physically contiguous with the main board. The MPC-7000 main board (MPC7-MB) provides the connections for external field wiring and connection points for optional modules. Optional boards mount on the main board or mount on the rear of the enclosure.
The display board and controls mount on the inner-hinged plate.
All normal operation is controlled from the front of the control unit via push-button switches.
Displays are provided by an 80-character, alphanumeric, backlit LCD display and by discrete
LED indicators for major control unit functions.
The 80-character LCD is used to display event data, including alarms and troubles, identification of zone or device, and presentation of history. The display is controlled by a set of four push-button switches commanding the control processor. A backlight is included in the display to assure visibility in low light, but to conserve power, it is only activated during a reported event or on operation of a display control switch.
Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM,
SUPERVISORY, ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct pushbutton controls are provided for ALARM SILENCE, ACKNOWLEDGE, MENU and SYSTEM
RESET.
Power Supply
A 24V nominal power supply provides all operating power to the control unit for both standby and alarm conditions. Sufficient battery charging capability is available to charge 38.5 AH sealed lead-acid batteries within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only up to 18 AH. The back-up battery is 24V, maintained by floating on the power supply. The battery will be automatically disconnected at low battery voltage to prevent deep discharge.
X1 Addressable Device Circuits
The MPC-7000 control unit has two addressable device circuits (expandable to three or four), utilizing the X1 Detection Technology. Each circuit has the capacity for 252 addresses.
6
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Notification Appliance Circuits
The MPC-7000 control unit has four (expandable to twelve) independent Class B (Style Y) notification appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation. This reduces the number of NACs to two (six). Each circuit can be selected to give continuous output or one of eight sounding patterns available in the control unit including the
Faraday SYNC Protocol. There is also a system coder capable of zone-coded operation. All of the NACs are power limited.
Serial Interface Circuit
The MPC-7000 control unit has a Serial Interface Circuit that will drive up to 16 remote LCD annunciators and 8 Serial Relay Units and Serial Annunciator Units.
Status Relays
Four relays with dry contacts are provided. These relays are programmable to power fail, alarm, trouble and supervisory functions. The relay contacts are Form C and are rated 1A @
28VDC resistive
Programming Port
An RJ-11 jack is provided for a non-isolated RS-232 connection for temporary connection to a computer for panel programming.
7
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
RND-2 SYSTEM DESCRIPTION
The RND-2 is a Remote Network Display designed to connect to a Faraday MPC-NET2
Network. It features advanced programming, and memory capability. Its base configuration includes a power supply, serial interface circuit, four status relays and a programming port.
In a system with multiple panels connected via the MPC-NET2, the RND is used to
Acknowledge, Silence and Reset the total system.
The RND-2 Network annunciator mounts in a 22" x 18" backbox with overall cover size of 22-
9/32" x 18-3/8". Operating controls and indicators are mounted on the inside hinged plate. An
80 (4x20) – alphanumeric character LCD provides specific indications for addressable devices while LEDs indicate general panel status.
Semi-flush mounting kits are available for the enclosure.
The main board mounts in the rear of the enclosure. The power supply is physically contiguous with the main board. The RND-2 main board (MPC6-MB) provides the connections for external field wiring. Optional boards mount on the main board or on the rear of the enclosure.
The display board mounts on the inner-hinged plate.
All normal operation is controlled via a membrane keypad. Displays are provided by an 80character, alphanumeric, backlit LCD and by discrete LED indicators for major control unit functions.
The 80-character LCD is used to display event data, including alarms and troubles, identification of zone or device, and presentation of history. The display is controlled by a set of four push-button switches commanding the control processor. A back light is included in the display to assure visibility in low light, but to conserve power, it is only activated during a reported event or on operation of a display control switch.
Individual LEDs on the panel are provided to indicate SYSTEM ALARM, PREALARM,
SUPERVISORY, ALARM SILENCED, SYSTEM TROUBLE and AC POWER ON. Direct pushbutton controls are provided for ALARM SILENCE, ACKNOWLEDGE, MENU and SYSTEM
RESET.
Power Supply
A regulated fullwave rectified 24V nominal power supply provides all operating power to the control unit for both standby and alarm conditions. Sufficient battery charging capability is available to charge 38.5 AH sealed lead-acid batteries within code requirements for 60 hour quiescent plus 5 minutes alarm. The cabinet will hold batteries only up to 12 AH. The back-up battery is 24V, maintained by floating on the power supply. The battery will be automatically disconnected at low battery voltage to prevent deep discharge.
8
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Serial Interface Circuit
The RND-2 control unit has a Serial Interface Circuit that will drive up to 16 remote LCD annunciators and 8 Serial Relay Units and Serial Annunciator Units.
Status Relays
Four relays with dry contacts are provided. These relays are programmable to power fail, alarm, trouble and supervisory functions. The relay contacts are Form C and are rated 1A @
28VDC resistive.
Programming Port
An RJ-11 jack is provided for a non-isolated RS-232 connection for temporary connection to a computer for panel programming.
9
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
OPTIONAL MODULES
CT-1K City Tie Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday CT-1K city tie board provides local energy and polarity reversal connections. The polarity reversal connections provide a trouble circuit and an alarm circuit with optional trouble output. The CT-1K mounts onto the main termination board. (Cannot be used in conjunction with a DACT Board).
MPC-DACT DACT Board (MPC-6000 / MPC-7000 / RND-2)
The Faraday MPC-DACT Digital Alarm Communication Transmitter board will send control unit status data to a remote receiving station. The MPC-DACT mounts onto the main termination board (Cannot be used in conjunction with the City Tie Board).
NPE-1 Transformer Assembly (MPC-6000 / MPC-7000)
The Faraday NPE-1 optional transformer assembly provides an additional 3 amps of NAC power. The transformer mounts in the cabinet above the two transformers that come standard with the MPC-6000 / MPC-7000. A maximum of one optional NPE-1 is allowed per system.
NEM-1 NAC Expansion Board (MPC-7000)
The NEM-1 NAC Expansion Board has eight independent Class B (Style Y) notification appliance circuits (NACs). Pairs of NACs can be combined for Class A (Style Z) operation.
This reduces the number of NACs to four. Each circuit can be selected to give continuous output or one of eight sounding patterns available in the control unit including the Faraday
SYNC Protocol. There is also a system coder capable of zone-coded operation. All of the
NACs are power limited. Maximum of one NAC Expander board per MPC-7000 system.
LEM-1 Loop Expander Board (MPC-7000)
The LEM-1 has circuitry for the addition of an additional two FDLC Loop Driver boards to a
MPC-7000 panel. (FDLC Loop Driver Boards are not included). A maximum of one Loop
Expander Board is allowed per MPC-7000 system.
FDLC Loop Driver Board (MPC-7000)
The FDLC has one addressable device circuit that is programmed for connection to Faraday addressable devices using the X1. The circuit has the capacity for 252 addresses. A maximum of four FDLC boards per MPC-7000 panel is allowed. (Loops 3 and 4 require a LEM-1 Loop
Expander Board.)
HBC-1 Battery Charger (MPC-7000)
The HBC-1 is an optional battery charger to increase the charging capacity of the MPC-7000 to 100AH lead acid batteries.
Battery Sets
The MPC-6000 / MPC-7000 / RND-2 control units are designed to use only sealed lead-acid or equivalent batteries for back-up power. Attaching a close-coupled battery box, if required, may allow use of battery sets beyond the physical capacity of the enclosure (12AH for the MPC-
6000 and 18AH for the MPC-7000). Maximum battery charging capacity for the MPC-6000 is
38.5AH. Maximum battery charging capacity for the MPC-7000 is 38.5AH. (100AH with the optional battery charger HBC-1.)
10
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
AUXILIARY MODULES
Serial LCD Annunciator
The RDC-2 Serial LCD Annunciator consists of a backlit 80 character LCD alphanumeric display, 4 menu buttons, 4 dedicated buttons for operator interaction, 6 LED indicators, and a security key-switch. The display and controls on the annunciator are the same as those on the front of the control unit, including a key-switch for security. The backlight operates only when the data are being accessed, to conserve power. Up to sixteen annunciators may be addressed by the communications circuit, but some may require additional RSE-300 auxiliary power supplies, depending on the total accessory power loading.
Serial Relay Unit and Serial Relay Extender
The SRU-2 Serial Relay Unit includes a processor board and a relay board. The processor board receives commands from the control unit for activating the relays and transmits supervision and control functions to the control unit. The processor board can control up to 3 relay boards. Each relay board provides 8 relays with Form C contacts. The control unit can address up to 8 Serial Relay Units and/or Serial Annunciator Units. RSE-300 auxiliary power supplies will be required to power units beyond the control unit capability.
Serial Annunciator Unit and Serial Annunciator Extender
The SLU-2 Serial Annunciator Unit includes a processor board and an annunciator driver board. The processor board receives commands from the control unit for activating the outputs and transmits supervision and control functions to the control unit. The processor board can control up to 4 annunciator driver boards. Each driver board provides 16 supervised outputs for
LEDs or incandescent lamps. The control unit can address up to 8 Serial Relay Units and/or
Serial Annunciator Units. RSE-300 auxiliary power supplies will be required to power units beyond the control unit capability.
RSE-300 Remote Signal Expander
The RSE-300 is a notification appliance circuit expander with a built-in auxiliary power output.
This power source is designed to provide power for notification appliances, door holders and 4wire smoke detectors. The RSE-300 provides 6 amps of 24 VDC power for multiple uses. All 6 amps can be directed to 4 Notification Appliance Circuits (NACs). Each is rated at 3 amps and is power limited. Either 1 or 2 inputs can control the four outputs. These outputs are compatible with Faraday notification appliances.
The RSE-300 can be configured so that the inputs can be programmed to provide steady outputs, ANSI temporal outputs, or Faraday SYNC protocol for synchronized horn/strobe outputs. It can also be programmed to silence Faraday sync horns while the sync strobes remain on, using two wires. This requires a silenceable and non-silenceable input.
The RSE-300 also offers a 3 amp auxiliary output for driving other portions of your fire alarm system.
11
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
X1 ADDRESSABLE DEVICES
Fire Smart™ Smoke Detector
The control unit processor sends the sensitivity and pre-alarm settings to the detectors and polls the detectors as to their status. The detector determines normal, trouble, pre-alarm or alarm conditions and communicates the status to the control unit.
• Variable Thesholds - The detectors can be set to operate in various pre-programmed optimizations, depending on installation locations.
• Operator Alerts - The control unit can trigger an alarm or trouble automatically on the occurrence of a number of conditions of the detector. These include:
Maintenance alert
Pre-alarm alert
No response
Incorrect response
Heat Detectors
Addressable heat sensing detectors may be intermixed on the circuit for locations where heat sensing may be the most effective detection mode. The heat detectors may be programmed, through the control unit, for rate of rise operation.
Addressable Modules (Monitor and Control)
In addition to detectors, the circuit can communicate with addressable modules, allowing initiating devices or notification appliances with local power sources, and supervising the power sources.
Manual Stations
Addressable manual stations may be intermixed on the circuit with proper response programmed into the control unit.
Programming X1 Devices
X1 devices can be programmed in the following manner:
• 8720 Device Programmer/ Loop Tester - Refer to the 8720 User’s Manual, P/N 315-
033260FA, for further information.
• MPC-6000 / MPC-7000 / RND-2 Panel Keypad – Refer to the MPC-6000 / MPC-7000 /
RND-2 Programmer’s Manual, P/N 315-049403FA, for detailed information of system programming. Used only for field removal and reinstallation of individual devices.
12
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
EVENT HISTORY
The control unit includes a non-volatile memory recording up to 2000 system events. Identified alarm, trouble, supervisory trouble and other significant events will be recorded along with the date and time of occurrence and can be inspected by operating front panel push buttons.
Events recorded in the history are:
• Alarm, Trouble or Supervisory conditions.
• Drill, Recall and General Evacuation.
• Activation of NACs or modules used for sounders or strobes.
• Unit used for command functions. (Silence, acknowledge, reset, etc.)
• PAS_INHIBIT switch activation.
• Alarm silence (manual and automatic).
• Entry to Programmer Mode.
• Validity check on backup configuration. (Errors detected or no errors detected)
• Running of comparison function. (Same or different)
• Replacement of primary configuration.
• Exit from Programmer Mode.
• System time or date change.
• Input point disable/enable.
• Start and stop of walk test.
• Expiration of Walk Test Timer.
• Expiration of re-ring timer.
• Alarm verification counter rollover.
• Alarm of zone with no outputs.
• Activation of points defined for logging.
• Detector maintenance alerts.
13
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
GENERAL DESIGN FEATURES
Environmental
All hardware is suitable for use in a dry, interior or protected location.
Power Limiting
The AC power and battery wiring are not power limited. All other circuits leaving the control unit are power limited, provided the proper installation rules are maintained.
Ground Fault Detection
The control unit provides system ground fault detection and is annunciated as a trouble condition on the system. In addition, each addressable loop circuit has its own ground detection circuitry and indicator.
System (+) Ground Fault Threshold = 40K
Ω
System (-) Ground Fault Threshold = 300k
Ω
Loop Circuit Ground Fault Threshold = 20k
Ω
NAC Operation
The notification appliance circuits are commanded and controlled by a microprocessor to provide more versatility than in a total hardware system
• Output Sounding Patterns - The notification appliance circuits are operable in different sounding patterns. Any circuit is selectable to any of eight software-generated patterns or continuous sounding. For convenience, three of the patterns are preprogrammed for March
Time, Temporal, and Faraday SYNC Protocol.
• Audible Silence Inhibit - In addition to designation of water flow zones, the entire control unit may be programmed to inhibit audible silence for 0, 1, 3, or 6 minutes from the last alarm. System reset may also be inhibited.
Transient Protection
Transient protection devices are provided to meet UL864 requirements.
Security Features
Processor control and addressing allow inclusion of several functions to assure security and proper programming of the system.
Multi-level password protection of programming functions prevents unauthorized configuration changes.
Device type supervision: If the type reported by an addressable detector or module does not agree with the configuration, the system reports a trouble.
Device address supervision: The system checks that all configured devices on the addressable device circuit and the Serial Interface Circuit responds to an address poll. If a configured device is missing, the system reports a trouble. The system also polls unused addresses periodically. If a device responds to such a poll of a non-configured device, the system reports a trouble. Two devices addressed the same also cause a trouble to be reported.
14
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
REGULATORY STANDARDS
The MPC-6000 / MPC-7000 control units and the RND-2 network annunciator meet the requirements of industry and government regulatory agencies as noted.
Federal Communications Commission
The MPC-DACT meets the Class A requirements of the Code of Federal Regulations (CFR
47), Part 15, for electromagnetic field emissions. The MPC-DACT also meets the requirements of the Code of Federal Regulations (CFR 47), Part 68, for connection of equipment to the public switched telephone network.
Underwriters Laboratories
The MPC-6000 / MPC-7000 Fire Alarm control units and the RND-2 network annunciator are listed under UL Standard 864 for compliance to NFPA Standard 72 for fire service.
15
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
GENERAL SPECIFICATIONS
Operating specifications for the MPC-6000 / MPC-7000 / RND-2 are as follows:
Environmental
• Operating temperature - 32 - 120°F (0 - 49°C)
• Relative humidity - Up to 85% @ 86°F (30°C)
Primary Supply
• Primary Input Voltage: 120 VAC (60 Hz) nominal
• MPC-6000 / RND-2 Maximum primary input current: 2.4A at 120 VAC
• MPC-7000 Maximum primary input current: 3.2A at 120 VAC
Secondary and Trouble Power Supply
• 24 volt lead-acid battery set
• Maximum Charge Voltage: 27.8 VDC
• Automatic Low Battery Disconnect - Disconnect Voltage: 18VDC
• MPC-6000 / RND-2 Maximum Charge Current: 1.7A
• MPC-7000 Maximum Charge Current: 3.8A
• MPC-6000 / RND-2 Battery capacity: 7-38.5 AH (over 12 AH requires separate enclosure for the batteries)
• MPC-7000 Battery capacity: 7-38.5 AH / 100 AH with optional Battery Charger, HBC-1
(over 18 AH requires separate enclosure for the batteries)
Auxiliary Power Outputs
• 0.4 amp maximum per power output circuit
MPC-6000 / RND-2 0.5 amp total / MPC-7000 1.0 amp maximum available for auxiliary power output circuits, Serial Interface Circuits and option boards
• Non-Resettable Power Outputs
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Power limited
Voltage: 24 VDC nominal
Ripple: 1.5 VAC maximum
Status Relays
Four relays programmable for alarm, supervisory, trouble, loss of AC.
1 A, 28 VDC maximum, resistive
• Form C Contact
16
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Notification Appliance Circuits
• Supervised
• Maximum Standby Current: 3.4mA
• Maximum Line resistance @ 24VRMS:
Current Draw Line
Ω
2.0
Ω
8.0
• Alarm Voltage: 24 V FW nominal
• Maximum Ripple: 16 VAC
• MPC-6000 Four Style Z/Class B or two Style Y/Class A circuits
• MPC-7000 Four Style Z/Class B or two Style Y/Class A circuits
Expandable to twelve Style Z/Class B or six Style Y/Class A circuits
• Maximum NAC Current: 1.5 A / NAC circuit
MPC-6000 maximum total NAC current 3.0A (6.0A with optional NPE-1 transformer installed)
MPC-7000 Maximum total NAC current 5.0A (8.0A with optional NPE-1 transformer installed)
Serial Interface Circuit limited
• Supervised
• (+, -) Voltage: 24 VDC nominal
• (X+, X-) Voltage RS485 levels
• Maximum wire loop resistance: 11 ohms/line
• Communications Protocol: RS485
X1 Addressable Device Circuits
• Supervised
• Voltage: 24 VDC nominal
• Maximum Current (shorted): 0.375A
• Maximum wire loop resistance: 50 ohms (see graph on page 48)
• Style 4 or 6 circuit
• 252 Addresses: detectors and modules max.
• MPC-6000: One circuit
• RND-2: No loop circuits
• MPC-7000: Two circuits expandable to four
17
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
City Tie (Optional City Tie Board P/N CT-1K)
CA Reverse Polarity: Selectable for Alarm with Trouble or Alarm only operation
• Supervised by receiver for short or open circuit
• Supervised by control unit for grounded circuit
• Voltage: 24 VDC nominal
• Current: 0.020A maximum (normal or trouble)
• Current: 0.025A maximum (shorted)
• Ripple: 1.5 VAC maximum
CT Reverse Polarity: Programmable for Trouble or Supervisory or both
• Supervised by receiver for short or open circuit
• Supervised by control unit for grounded circuit
• Voltage: 24 VDC nominal
• Current: 0.020A maximum (normal or alarm)
• Current: 0.025A maximum (shorted)
• Ripple: 1.5 VAC maximum
LE Local Energy
• Not power limited
• Supervised for open or grounded circuit by control unit
• Voltage: 24 VDC nominal
• Standby Current: 0.007A maximum
• Alarm Current: 0.400A maximum
• Ripple: 1.5 VAC maximum
• Maximum wire loop resistance: 30 ohms
• Trip coil impedance: 14.5 ohms
DACT Circuit (Optional DACT Board MPC-DACT) limited
• Supervised for short or open circuit
• Maximum Voltage: 60 VDC
• Maximum Current (shorted): 0.100A
Additional Transformer (Optional Transformer Assembly NPE-1)
• Provides an additional 3.0A of NAC power (max 1 per panel)
18
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
CONTROL UNIT OPERATION
OPERATION INSTRUCTIONS
Standby Condition
In normal standby operation, the green AC POWER ON LED should be illuminated and no other indicator operating. The display will show the system name, “System Normal” announcement and the current date, day, and time.
Alarm Conditions
When a general alarm occurs, all NACs with output type set to “ALARM” activate.
To activate a general alarm, proceed as follows:
• On the MENU display, select "GENERAL ALARM".
• At the next screen, select "Yes".
Silence and reset the system as with any alarm.
In case of alarm, the system alarm LED activates (ON - flashing) and the buzzer activates (ON
- steady). Local audible and visual signals and remote alarm signals operate and the LCD panel display indicates the zone or point initiating the alarm.
On receipt of an alarm, proceed in accordance with the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department.
To silence the audible after evacuation, where permitted by the codes and control unit programming, press ALARM SILENCE. The alarm audible will be silenced, the alarm silence
LED will be illuminated and a system trouble indicated.
Operating the ACKNOWLEDGE button will silence the local buzzer and change the LED alarm indicator from flashing to steady.
Alarms detected on devices with usage designated as “waterflow” indicate sprinkler operation and the audible alarms cannot be silenced in this condition. Operation of alarm silence will produce no effect.
• POSITIVE Alarm Sequence (PAS)
Activation of a zone programmed for PAS, activates the Alarm LED, display and buzzer
(pulsing), and starts the PAS timer, but delays all other outputs (system and user) for 15 seconds.
19
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Operation of the ACKNOWLEDGE button within 15 seconds will add a number of seconds (60-
180) to the PAS timer. If the ACKNOWLEDGE button is not operated within 15 seconds, the system and user outputs activate.
If the initiating device and the panel are reset before the PAS timer times out, the alarm sequence is aborted.
An alarm condition on a detector programmed for direct alarm response (such as the key switch on a manual station) will override the PAS timer and activate the outputs.
A point activated by a PRE-SIGNAL alarm device activates the alarm relay, alarm DACT, alarm LEDs and buzzers, and all user-programmed outputs normally, except NACs. Only presignal type NACs operate at this time. Pre-signal type NACs are for constantly attended central locations manned by trained building personnel.
Operation of the SYSTEM RESET button within the pre-programmed time (60-180 seconds) after initiation of the pre-signal prevents operation of the general alarm.
Failure to act within the pre-programmed time (60-180 seconds) will result in activation of the general alarm.
Receipt of a general alarm during the delay period immediately sounds the general alarm building NACs.
Do not reset the system until the alarm condition has been cleared. The LCD will indicate the area in which the alarm was detected. The detector or module associated with the device initiating the alarm will display a light indicating activation (if applicable).
When the alarm condition has been corrected, return the system to standby operation by pressing the SYSTEM RESET button.
Trouble Conditions
In case of a trouble condition, the system trouble LED and any programmed trouble LEDs activate (ON – pulsing), the LCD identifies the problem and the buzzer sounds (pulsing). Refer to the applicable section of the system manual to determine the probable cause of the trouble and the action to be taken.
When a trouble has been noted, the buzzer may be silenced by pressing the ACKNOWLEDGE button. The trouble LEDs will change to ON - steady. If the trouble has not been corrected when the trouble resound reminder timer expires, the trouble display reverts to its original condition and the buzzer resounds (pulsing).
If the control unit is programmed for “trouble acknowledge required”, when the indicated trouble condition has been cleared, the system reverts to standby condition only after the
ACKNOWLEDGE button is pressed.
Some trouble conditions require a system reset to restore the control unit.
20
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Supervisory Conditions
In case of a supervisory condition, the system supervisory LED activates (ON – flashing) and the sounder activates (ON – pulsing). When the supervisory has been listed, the buzzer is silenced by pressing the “ACKNOWLEDGE” button. The supervisory trouble LED changes to steady – ON. When the supervisory is cleared, the supervisory condition is still indicated until it is acknowledged.
Pre-Alarm Conditions
• A pre-alarm condition is annunciated by Pre-alarm LEDs and buzzers on the control unit and LCD Annunciators and Remote Processors. The LEDs flash and buzzers are on steady until acknowledgment.
• Acknowledging the Pre-alarm condition puts LEDs on steady and buzzers off.
• If pre-alarm has been acknowledged and the system restores to normal, the condition clears. If the system proceeds into an alarm condition, the pre-alarm condition clears whether or not it has been acknowledged and is replaced by alarm.
Maintenance
In order to insure continued safe and reliable operation of the fire alarm system, periodic inspection and testing should be performed in accordance with applicable NFPA 72 standards.
If the system has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and/or notify the remote monitoring station before performing test operations.
For any required service, refer to the system manual or contact a factory authorized representative.
21
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
ADDITIONAL OPERATING PROCEDURES
In addition to the basic fire alarm instructions above, several features are included to facilitate maintenance and increase the versatility of the system. Following are procedures to call up these functions.
Lamp Test
Lamp Test activates the buzzer and turns on all the LEDs on the user interface for 2 seconds, then reverts to its previous state.
To operate the lamp test, press the MENU button. The LCD will change to a MENU screen.
Press the button next to the “More” indication twice. Then press the button by the “Lamp Test” indication. All lamps on the unit being operated will then light. Operating the button next to “Esc” will then return the control unit to normal display. Note that the lamp test operates the indicators only on the unit being operated, and no record is reported to system history.
Drill
When selected, activates all NACs assigned to the Output Zone selected for “Drill”.
To activate a fire alarm drill, proceed as follows:
• On the MENU display, select "More".
• At the next screen, select "DRILL".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate drill signal.
Recall
When selected, activates all NACs assigned to Output Zones selected for “Recall”.
To signal recall after a drill, proceed as follows:
• At the next screen, select "More".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate recall signal.
Alert
When selected, activates all NACs assigned to the Output Zone selected for “Alert”.
To activate an alert alarm, proceed as follows:
• On the MENU display, select "ALERT".
• At the next screen, select "Yes".
• Operate ALARM SILENCE to terminate alert signal.
22
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
History
The last 2000 system events are time-tagged and recorded for review in the user level event history. This history is available to anyone with the door key, but may be erased only at the maintenance security level.
• Operation of history:
New events overwrite old when filled.
Printer (if used) records all events.
For more information see the Event History section.
• Access to history:
To recall past events, proceed as follows:
Press “MENU” button.
Operate button identified as "More".
Operate button identified as "More".
Operate button identified as "View History".
Operate upper left button (M1) for previous event display.
Operate lower left button for (M2) next event display.
Operate upper right button (M3) to exit to MENU DISPLAY.
The display reverts to its previous state if there is no action performed within 30 seconds.
23
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MPC-6000 / MPC-7000 / RND-2 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the panel buzzer sounds steady. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Authorized Personnel Only
To acknowledge the alarm:
To acknowledge the alarm, press the Acknowledge button. The local buzzer will be silenced and the Alarm LED will change from on-flashing to on-steady.
Note: The alarm may only be acknowledged at the node which initiates the alarm or the
RND-2.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, press the Alarm Silenced button. The silenceable notification appliances will be silenced. The Alarm Silenced LED will be on-steady.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing the System Reset switch.
Trouble Operation
Trouble is indicated by:
Trouble LED flashes
LCD will display trouble conditions
Panel buzzer sounds on-pulsing
To acknowledge the trouble:
Press the Acknowledge button. The Trouble LED turns on-steady and the buzzer turns off. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to initiate a fire alarm sequence.
Normal Standby Condition
The green AC Power On LED will be lit and no other indicators on
.
For service, contact: ___________________________________________
Telephone Number: ___________________________________________
Frame these instructions and mount them near the control unit for operator reference.
24
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
RDC-2 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm condition and the buzzer activates onsteady. Local audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been received at the Fire Department.
Authorized Personnel Only
To acknowledge the alarm:
To acknowledge the alarm, press the Acknowledge button. The local buzzer will be silenced and the Alarm LED will change from on-flashing to on-steady.
Note: The alarm may only be acknowledged at the node which initiates the alarm or the
RND-2.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, operate the Button
Enable key switch and press the Alarm Silence switch. The silenceable notification appliances will be silenced. The Alarm Silence LED will be on-steady.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by placing the Button Enable key switch to the OK position and then pressing the System Reset switch.
Trouble Operation
Trouble is indicated by:
Trouble LED flashes
LCD will display trouble conditions
Buzzer activates on-pulsing
To acknowledge the trouble:
Operate the Button Enable key switch to the ON position and press the Acknowledge button.
The Trouble LED changes to on-steady. When the trouble condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may cause a fire alarm condition not to
initiate a fire alarm sequence
Normal Standby Condition
The green Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Telephone Number: ___________________________________________
Frame these instructions and mount them near the annunciator for operator reference.
25
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
CONTROL UNIT INSTALLATION
PARTS SUPPLIED – MPC-6000 / MPC-7000 / RND-2
Enclosure Packages (Black or Red)
Assembly
• Front Door Assembly with Window
Electronics Package MPC-6000 / MPC-7000
MPC(6/7)-MB Main Board 575-447328 Nameplate (MPC-7000)
MPC(6/7)-DB Display Board
FDLC Loop Driver Board (2 with MPC-7000)
215-649113 Keyboard
330-944373 Thermal pad
465-633943 Battery cable assembly
315-447309 Installation and Operation Manual
315-447311 Operating Instructions
575-447310 Riser Diagram (MPC-6000)
906-220604 #6-32 x 1/4” Screws (17)
375-F943165 Spacers (8)
140-820405 24K Ohm 1/2W Resistor (4)
140-820350 120 Ohm 1/2W Resistor (2)
555-446055 Cable Assembly, 26 Pin
130-PM3223 Bridge Rectifier
555-449116 Rectifier Cable Assembly
899-G67197 #6-32 Keps Nuts (1)
950-220604 #6-32 Nut (1)
600-149373 Ground Wire Assembly
575-447388 Riser Diagram (MPC-7000)
575-447312 Nameplate (MPC-6000)
Electronics Package RND-2
MPC6-MB Main Board
RND2-DB Display board for RND-2
575-447328 Nameplate (RND-2)
215-649113 Keyboard
330-944373 Thermal pad
465-633943 Battery cable assembly
315-447309 Installation and Operation Manual
950-220604 #6-32 Nut (1)
906-220604 #6-32 x 1/4” Screws (17)
375-F943165 Spacers (8)
140-820405 24K Ohm 1/2W Resistor (4)
140-820350 120 Ohm 1/2W Resistor (2)
555-446055 Cable Assembly, 26 Pin
130-PM3223 Bridge Rectifier
555-449116 Rectifier Cable Assembly
899-G67197 #6-32 Keps Nuts (1)
315-447311 Operating Instructions
575-447310 Riser Diagram (RND-2)
600-149373 Ground Wire Assembly
With NPE-1 Transformer Package
Transformer Assembly (120VAC) (2 required) (899-G67197) #6-32 Keps Nuts (2)
CAUTION
1. Remove the printed circuit boards for any procedure that may cause dust, metal shavings, grease (or such matter that may affect the operation of the boards) to get in contact with the units.
26
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2. Disconnect all sources of power prior to installing or removing modules, connecting or disconnecting wiring and programming jumpers.
CONTROL UNIT LOCATION
The control unit should be located near an exit at ground level, where the normal ambient temperature is maintained within the control unit specification (See General Specifications).
The unit should be in an area that is free of dust, vibration, moisture and condensation. Any auxiliary battery box or other accessory not connected through a protective device or a circuit designed for remote connection must be within 20 ft. and in the same room, connected through electrical conduit.
INSTALLATION
The enclosures must be fastened securely to a clean, dry, shock-free, and vibration-free surface. Consider the following when mounting the box.
• Mounting height for visual and manual access to the display and keypad
• Weight and size of backbox
• Local mounting codes
When mounting the backbox, position the backbox clear of obstructions so that the door can open freely and so that indicators and controls are easily accessible.
The fire alarm control unit must be mounted in a properly accessible location as required by applicable codes. Any auxiliary battery box or other accessory not connected through a protective device or a circuit designed for remote connection must be within 20 ft. and in the same room, connected through electrical conduit.
Installation is to be done only by qualified personnel who have thoroughly read and understood these instructions. The fire alarm control unit must be mounted in a properly accessible location as required by applicable codes.
ENCLOSURE MOUNTING
Install the backbox:
• Select a clean, dry, shock and vibration free surface.
• Position the backbox clear of obstructions so that the front door opens freely and the controls and indicators are easily accessible.
• Mark the locations of the two upper mounting bolts of the backbox on the wall.
There are two key-shaped cutouts on the top of the backbox. Make sure the end with the two key-shaped cutouts is on top when installing the backbox.
• Drill the two holes located in the previous step and screw in the top bolts, leaving a small gap between the wall and each top bolt.
27
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
The screw type and length must be able to support the control panel, options and battery set.
You may need a different screw type, depending on the wall material.
Place the backbox over the two top bolts and allow it to slide down over the bolts.
• Mark, drill, and install the two bottom bolts in the backbox.
• Tighten all four bolts securely against the back wall of the backbox.
• The RSE-300 Auxiliary Power Supply or battery enclosure may be mounted immediately below the main enclosure, close nipple, allowing a minimum of 1 inch in between the enclosures for clearance between the doors. Keeping the wire run to the control unit short will keep the voltage drop to a minimum.
• If a semi-flush mount installation is desired, use the SFTK-6(R/B) Semi-flush Trim for the
MPC-6000 / RND-2 and the SFTK-7(R/B) Semi-flush Trim for the MPC-7000. The backbox can be mounted up to 3 1/2 inches into the wall. Place the semi-flush trim around the backbox and affix to the wall with four #10 x 3/4 inch wood screws (provided with trim).
You may need a different screw type, depending on the wall material.
For semi-flush installations, if the RSE-300 Auxiliary Power Supply or a battery enclosure is required, it may be mounted immediately above or below the main enclosure, close nipple, allowing a minimum of 3 inches in between the enclosures for clearance between the semiflush trims. Keeping the wire run to the control unit short will keep the voltage drop to a minimum.
MPC-6000 and RND-2 Enclosure Mounting Pictures
28
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MPC-7000 Enclosure Mounting Pictures
Remove Knock-Outs
Prepare the enclosure for electrical wiring by breaking out the appropriate conduit entry points.
Segregation is required between power limited and non-power limited conductors. In order to maintain the minimum separation, follow the wire routing illustrated on page 38. Separation of at least a 1/4 inch is required between the non-power limited and power limited conductors.
Power limited and non-power limited wiring must be run in separate conduit.
Attach conduit (if required) and run wires as required. Label each field cable for future reference.
Basic system wiring and detector siting must be in accordance with NFPA 72 or other instructions from the appropriate local authority having jurisdiction. Unit connections and limitations are as indicated on the wiring diagrams included in System Wiring part of this manual.
Wire reference data are included in Appendix A.
29
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Main Board Installation – P/N MPC6-MB / MPC7-MB
Secure the board to the back of enclosure using the provided #6-32 x 1/4 screws (P/N 906-
220604). (Eight for the MPC6-MB and ten for the MPC7-MB.)
MPC-6000 / RND-2 MPC-7000
30
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Bridge Rectifier Installation – P/N 130-PM3223
• Secure the bridge rectifier (P/N 130-PM3223) to the backbox, placing the thermal pad (P/N
330-944373) between the Bridge Rectifier and the backbox using a provided #6 keps nut
(P/N 899-G67197). See drawing below for details.
• Wire Bridge Rectifier to Rectifier Cable Assembly (555-449116). Red wire goes to the plus
(+) connection of Bridge Rectifier and Black wire goes to the minus (-) connection of the
Bridge Rectifier. Gray wires connect to the AC connections of the Bridge Rectifier. Plug
Rectifier Cable Assembly into J4 on the Main Board (P/N MPC(6/7)-MB).
31
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Transformer Mounting – P/N NPE-1
• Place the NPE-1 transformer assemblies (one for RND-2, two for MPC-6000 or MPC-7000) over the bottom one or two sets of studs on the left side of the enclosure, if desired.
Mounting the transformer can be accomplished before mounting the enclosure.
• Tighten provided transformer-mounting nuts (P/N 899-G67197) (2 per NPE-1).
• Plug the transformer assemblies into connectors J1 and J2 on the Main Board (P/N
MPC(6/7)-MB). Bottom transformer plugs into J1.
• If optional additional transformer (P/N NPE-1) is required, install it also at this time.
• Optional transformer plugs into connector J3 on the Main Board (P/N MPC(6/7)-MB).
NPE-1
Transformer
RND-2
MPC-6000
MPC-7000
32
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Loop Driver Board(s) Mounting – P/N FDLC
• Place the provided standoffs (P/N 375-F943165) in locations shown on the Main Board
(four for the MPC-6000 and eight for the MPC-7000).
• Carefully align connector J1 on the Loop Driver Board with connector J9 on the MPC-6000
Main Board (P/N MPC6-MB) or with connectors J9 and J14 on the MPC-7000 Main Board
(P/N MPC7-MB).
375-F943165
Standoffs
FDLC
Loop Driver Boards
MPC-6000
MPC-7000
33
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Display Board Installation – P/N MPC-DB or RND2-DB
• With the Inner Front Plate closed, carefully pass connector and cable from keypad through vertical slot in front plate.
• Remove backing from keypad and carefully attach keypad to front plate. Center window in keypad on large opening in front plate.
• Attach the cable connection from the keypad on the Inner Front Plate to connector J3 on the Display Board (P/N MPC(6/7)-DB or RND2-DB).
• Secure Display Board (P/N MPC(6/7)-DB or RND2-DB) to Inner Front Plate Assembly using four of the provided #6-32x1/4” screws (P/N 906-220604).
• Plug the Cable Assembly (P/N 555-446055) into connector J1 of the Display Board (P/N
MPC(6/7)-DB or RND2-DB) and to connector J11 of the Main Board (P/N MPC6-MB or
MPC7-MB).
Display
Board
J3 - Keypad
Connection
906-220604 (4)
#6-32 x 1/4 SCREW
MPC-6000 showing Display
Board and Keyboard being attached to Front Plate Ass'y
J1 - Connection to Main
Termination
Board
PLATE
ASS'Y
MPC-7000 showing Display
Board attached to Front Plate Ass'y
34
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Ground Wire Installation – P/N 600-149373
Attach Ground Wire (P/N 600-149373) to inside of outer door using provided #6 nut (P/N 950-
220604).
Attach Ground Wire (P/N 600-149373) to outside of inner door using provided #6 screw (P/N
906-220604).
SYSTEM WIRING
Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray voltages.
WARNING
Damage may result if a high voltage insulation tester is used on wiring while connected to the control unit.
Terminate the field wiring to the main board in accordance with the diagrams in System Wiring
Section and the system design documents.
All wiring must be in accordance with local codes and the National Electrical Code. Use only wire as described in Article 760 of the National Electric Code.
AC Supply Connection
Wire the AC supply to terminal block TB1 on the main board. The supply should originate from a separate, fused circuit. It should be provided with a breaker or other means of isolation.
(Refer to Primary and Secondary Wiring Section for connection diagram.)
Observe the wiring order — the bottom terminal is ground and must be wired back to the electrical panel ground (earth) bonding point or another good ground acceptable to the authority having jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical panel neutral distribution bar and must not be grounded.
Dangerous voltages will be present on this terminal block and on other components surrounding it and the transformer when the AC supply is turned on. Do not touch.
35
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Battery Installation
WARNING
Improper battery connections or shorting battery terminals may damage the system and/or batteries and may cause personal injuries.
Use the battery calculation chart to determine the battery size. Place the batteries in the space provided in the bottom of the backbox. If a battery set larger than12 AH (MPC-6000, RND-2) or
18 AH (MPC-7000) is required, a separate enclosure must be used. The Faraday 14050 may be used for battery sets 18 AH and smaller. The Faraday BE-1 may be used for battery sets
38.5 AH up to 100 AH.
The control unit uses a 24V battery set. Connect the two 12V batteries (or four 6V batteries) in series with wire that is rated for the maximum worst-case battery current draw. Route the battery leads to the left of the enclosure and up to the battery connector, J4. The battery leads are not power-limited. DO NOT CONNECT THE BATTERIES YET.
Powering the Control Unit
After all modules and wiring are installed and properly checked, apply AC power to the control unit. AC POWER ON LED, SYSTEM TROUBLE LED, and the trouble buzzer should be on.
Observe polarity. Connect the B- (black) lead from the main board into the black or - terminal of the battery set and the B+ (red) lead from the main board into the red or + terminal of the battery set. (Refer to Primary and Secondary Wiring for diagram.)
Optional Modules
See Appendix D for the installation instructions for each optional module. Installation
Instructions are also provided with each module. Follow these instructions for proper installation.
When using the MPC-DACT, select the proper System Type in the “System Parameter” tabs of
CIS-4. This automatically sets the “DACT Pwr Fail Tmr.”
Remote Station 15 Hours
Central Station 6 Hours
Check System Operation
Check for proper operation of all the system functions. See Operation Instructions section on page 19.
WIRING
Basic system wiring and detector locations must be in accordance with NFPA 72 or other instructions from the appropriate local authority having jurisdiction.
Devices that may be satisfactorily used with the control unit are shown in the compatible device listing in Appendix B.
Wire reference data are included in Appendix A.
36
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Control Unit Wiring Overview
In compliance with NEC Article 760 and UL 864, all power limited fire protective signaling conductors must be separated a minimum of 1/4 inch from all of the following wiring located within a control panel:
• Power
• Class 1 or non-power limited fire protective signaling conductors
To meet these requirements, the following guidelines must be observed when installing modules and wiring to this control panel.
When installing power limited field wiring, the installer must comply with NEC article 760, which states:
The fire alarm power-limited circuits are installed using Types FPL, FPLR, FPLP or permitted substitute cable, provided these power-limited cable conductors extending beyond the jacket are separated by a minimum of 0.25 in. (6.35 mm) or by a nonconductive sleeve or nonconductive barrier from all other conductors.
If energy limited cable or equivalent is not used within the MPC-6000 / MPC-7000 / RND-2 enclosure, then the following guidelines do not apply. In that case, be sure to follow standard wiring practices.
Wiring Entering Enclosure
• Non-Power Limited Wiring - Wiring entering the enclosure from the bottom left side of the backbox is considered non-power limited wiring. Wiring must be in the shortest route and must not overlap any other wiring.
• Power Limited Wiring - Wiring entering the enclosure from the top and the left side of the backbox is considered power limited. Wiring must be in the shortest route and must not overlap any other wiring.
Install Wiring
The primary mains input must have a separate or dedicated circuit breaker. Wire in accordance with local codes and NEC 760.
• Remove the knockouts in the backbox for the entry of field wiring. (Refer to Enclosure
Mounting Pictures on pages 28 and 29 and Wiring Separation Diagram on next page for the location of knockouts.)
• Pull all field wiring into the backbox. Do not dress the wiring until the location of all the equipment is known.
Install the wiring from the external power source to the approximate location of the power supply.
The overall arrangement of boards in the control unit is shown in the following diagram.
37
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Wiring Separation
All high voltage and non-power limited wiring must be kept separate from power limited wiring.
A separation of at least a 1/4 inch must be maintained, with high voltage and non-power limited wiring running in separate conduit openings from power limited wiring.
KNOCKOUTS FOR MPC-6000/MPC7000/RND-2
A Non-power limited - High Voltage
(AC power) or B
B Non-power limited - High Voltage
(AC power) or A
C Power limited
D Non-power limited
(Battery If external enclosure required)
E Power limited
F Non-power limited if Local Energy Box used
F Power limited or G or H
G Power limited or F or H
H Power limited or F or G
A C E G
A C E G
A C
7 or 8 (w/4)
5
7 or 8 (w/4)
LOOP #1
4
LOOP #2
4
E G
6
2
AC
POWER
TX-3
TO DISPLAY
BOARD
BRDG
TX-2
TX-1
AC
N
GND
BB+
BAT.
1 3
1+
1-
2+
2-
3+
3-
4+
4-
6
OPTIONAL
2
2
AC
POWER
TX-3
TO DISPLAY
BOARD
BRDG
TX-2
TX-1
AC
N
GND
BB+
BAT.
1
5
4
10
3
3+
3-
4+
4-
1+
1-
2+
2-
OPTIONAL
2
AC
POWER
2
TX-3
TO DISPLAY
BOARD
BRDG
TX-2
TX-1
1
AC
N
GND
BB+
BAT.
9
10
3
BATTERIES
1+
1-
2+
2-
3+
3-
4+
4-
BATTERIES BATTERIES
B D
RND-2
F H B D
MPC-6000
F H
B D
MPC-7000
F H
SYSTEM MODULES FOR MPC-6000/MPC-7000/RND-2
3. MPC-DACT DACT Board or CT-1K City Tie
4. FDLC Loop Driver Board – requires Main Board
or LEM-1 Loop Expansion Board
5. 12523 or 12523A Network Interface Board
(Cannot be used with an expansion module in
the uppermost position)
6. NPE-1 Expansion Transformer
7. NEM-1 NAC Expansion Module
8. LEM-1 Loop Expansion Module
9. HBC-1 Optional Battery Charger
10. Future Expansion
38
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Primary And Secondary Power Wiring
The AC main connections (TB1) and the battery connections (J4) must be made along the lefthand side of the main termination board (P/N MPC6-MB or MCP7-MB). Route all high voltage and non-power limited wiring together and away from power limited wiring. Use the battery calculation chart to determine battery size.
Supervised
120 VAC 60Hz
2.4A Max MPC-6000 / RND-2
3.2A Max MPC-7000
Non-Power Limited
AC
N
GND
Keep All Non-Power Limited Wiring
Separate from Power Limited Wiring
TX-1
AC
N
GND
BB+
BAT.
Battery Connections
Supervised
Non-Power Limited
For MPC-6000
24V Battery Set (7 to 38.5AH)
For MPC-7000
24V Battery Set (7 to 38.5AH)
(up to 100 AH if HBC-1 Battery
Charger is used)
For RND-2
24V Battery Set (7 to 38.5AH)
Status Relays And Auxiliary Power Outputs Wiring
The right side of the main board provides for connection of status relay contacts and auxiliary power connections (TB5-8). Four relays with dry contacts are provided. These contacts are programmable to alarm, pre-alarm, trouble and supervisory indications. The relay contacts are
Form C and are rated 1A @ 28VDC resistive.
The right-hand edge of the main termination board (TB9) provides for resettable and nonresettable auxiliary power connections.
Auxiliary Power Outputs
0.4A max. @24VDC nominal
Supervised, Power Limited
Maximum current of all auxiliary outputs circuits, Serial Interface
Circuit and option boards is:
0.5A for the MPC-6000/RND-2
1.0A for the MPC-7000
Programmable
Relay Circuit 1
NAC
Circuit
Programmable
Relay Circuit 2
Programmable
Relay Circuit 3
Programmable
Relay Circuit 4
Status Relay Contacts
(Shown in normal standby condition)
1A 28VDC max Resistive
For connection to a
Power Limited Source,
Supervised
C – Common
NO – Normally Open
NC – Normally Closed
39
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MPC-6000 System Power Requirements (Does not include NAC power)
6000
Amps
MPC-6000 Control Unit (Includes 1 FDLC) 0.190
Addressable Device Circuit Power # of Devices X 0.0018 Amps
Auxiliary Power Outputs *
CT-1K City Tie Board
MPC-DACT DACT Board
Depends on devices installed
0.055
0.054
RDC-2 Remote LCD Annunciator *
SRU-2/SRE-8 Serial Relay Unit *
SLU-2/SLE-16 Serial Annunciator Unit *
Total current requirements
Must be less than or equal to
RND-2 System Power Requirements
0.085
0.032+0.020 A for each relay
0.070+ load of each LED or lamp
0.190
0.75
RND-2 Control Unit (No FDLC)
Auxiliary Power Outputs *
CT-1K City Tie Board
MPC-DACT DACT Board
RDC-2 Remote LCD Annunciator *
Total current requirements
Must be less than or equal to
Amps
0.090
Depends on devices installed
0.055
0. 090
0.054
0.085
0.75
MPC-7000 System Power Requirement (Does not include NAC power)
7000
Amps
MPC-7000 Control Unit (Includes 2 FDLCs) 0.500
FDLC Loop Driver Board 0.100 x # of FDLCs on LEM-1
NEM-1 Signal Expansion Board 0.250
LEM-1 Loop Expansion Board
HBC-1 Battery Charger
1
0
0
Addressable Device Circuit Power
Auxiliary Power Outputs *
CT-1K City Tie Board
MPC-DACT DACT Board
RDC-2 Remote LCD Annunciator *
# of Devices X 0.0018 Amps
Depends on devices installed
0.055
0.054
0.085
SRU-2/ SRE-8 Serial Relay Unit *
SLU-2/ SLE-16 Serial Annunciator Unit *
Total current requirements
Must be less than or equal to
0.500
0.250
0
0
0.032+0.020 A for each relay
0.070+ load of each LED or lamp
3.22
1
Does not include charging current of 1.9A for a fully discharged battery.
40
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Auxiliary Power Supply
*Connect an RSE-300 auxiliary supply when power requirement calculation indicates that an additional source is required. For further information, refer to Appendix D.
Battery Size Calculations
For calculation of battery size requirements see Appendix A.
41
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
NAC Wiring
At the lower right corner of the main board the terminal blocks TB12 and TB13 are used for the connection of notification appliances. Four individual NACs marked 1 through 4 are provided and the polarity shown is when the NAC is activated.
NAC Rating:
Alarm Voltage: 24V FW regulated (nominal)
Max. Alarm Current: 1.5A/NAC circuit
Max. Ripple: 16VAC
Max. Wire Voltage Drop: 1.0VDC
Max. Standby Current: 1.0mA
NOTE:
The maximum total current for the MPC-6000
NACs is 3.0A and 6.0A with the optional additional Transformer P/N NPE-1.
The maximum total current for the MPC-7000
NACs is 5.0A and 8.0A with the optional additional Transformer P/N NPE-1.
Typical
Notification Appliance Circuit
Style Z, Class A
Supervised, Power Limited
See Appendix B for
Compatible Devices
No EOL Device
Typical
Notification Appliance Circuit
Style Y, Class B
Supervised, Power Limited
See Appendix B for
Compatible Devices
24K 1/2W
NAC 3
Polarity Shown
In Activated Condition
See table for NAC Jumper
Configurations
NAC 1,2
See Typical
Wiring
Use the following table to configure the NACs for either Class A or Class B operation.
NAC #s Class “B”
Operation
Paired Class
“A” Operation
1,2 JP1 JP2
3,4 JP3 JP4
42
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Serial Interface Circuit
The serial interface circuit can address up to 16 standard annunciators and/or 8 remote processors to drive graphic annunciation or relay modules. Devices on the circuit may be connected up to 4000 feet from the control unit. At the top of the main board the terminal blocks are used for the connection of remote serial devices.
Addressable
Device Circuit
IN
OUT
Do Not Use
Serial Interface Circuit,
(+, -) 24VDC nominal, 0.4 max
(X+, X-) RS-485 levels
Wire Type-Twisted Pair For Data
Wire Resistance-11 ohms/line (4000’ max)
Supervised, Power Limited.
See the following Installation Instructions for Compatible Devices:
RDC-2, P/N 315-049103FA
SLU-2, P/N 315-447345
SRU-2, P/N 315-447344
Auxiliary Power
Circuit
• Remote Device Power - When connecting devices on the serial interface circuit, a limited amount of current is available from the control unit. If more current supply is required for the connected devices, auxiliary power must be provided. Each address on the circuit must be fully powered from either control unit or auxiliary power (no combined source can be
configured).
43
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Serial Remote Device Wiring Overview
When connecting devices on the Serial Interface Circuit, the data wires must be daisy chained and with no T-taps to preserve the integrity of the data. Each end (two places) must be terminated with a 120 ohm termination resistor. The following diagrams show the proper wiring.
44
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
X1 Addresable Device Circuit(s)
These devices are polled by the control unit every few seconds and input or output functions communicated to determine device status or function. The control unit monitors all device addresses for alarm and trouble conditions.
MPC-6000 - X1 ADDRESSABLE DEVICE CIRCUIT
Addressable
Loop Circuit 1
Addressable Device Circuit
Style 4 or 6 Operation
24VDC nominal
0.375 Amp. Max.
Wire Resistance-50 ohms max
(See Appendix A, Line
Resistance Graph)
Supervised, Power Limited
See Appendix B for
Compatible Devices
Addressable
Loop Circuit 1
Addressable
Loop Circuit 2
Addressable Device Circuits
Style 4 or 6 Operation
24VDC nominal
0.375 Amp. Max.
Wire Resistance-50 ohms max.
(See Appendix A, Line Resistance
Graph)
Supervised, Power Limited
MPC-7000 - X1 ADDRESSABLE DEVICE CIRCUIT
IN
Serial Interface
Circuit (IN & OUT)
OUT
45
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
X1 Addressable Device Wiring Diagrams
Refer to the instruction sheets packed with each device.
Detectors and modules may be wired together according to several NFPA defined wiring styles. The wiring style that is appropriate for your installation should be determined from the relevant building codes and the local authority having jurisdiction.
Style 4 wiring permits branching of circuit connections. The control equipment supervises modules because they are active and must respond periodically to the control unit’s poll.
X1 ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 4
SUPERVISED
POWER LIMITED
TO OPTIONAL
BRANCH(ES) OF
LOOP CIRCUIT
NOTE: Faraday X1 Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 252 devices per addressable device circuit.
A Maximum of 20 devices recommended per Isolator Module. A Maximum of 12 Isolator Modules per addressable device circuit.
46
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
X1 ADDRESSABLE DEVICE CIRCUIT WIRING / OPERATION COMPARABLE TO NFPA STYLE 6
Style 6 provides redundant communication paths.
SUPERVISED
POWER LIMITED
.
NOTE: Faraday X1 Devices: Detectors, Monitor Modules, or Control Modules up to a maximum of 252 devices per addressable device circuit.
A Maximum of 20 devices recommended between Isolator Modules. A Maximum of 12 Isolator Modules per addressable device circuit.
47
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
PROGRAMMING THE CONTROL UNIT
KEYPAD PROGRAMMING
Customized programming of the control unit may be accomplished through the keypad in the control unit. See the Faraday MPC-6000 / MPC-7000 / RND-2 Programmer’s Manual, P/N
315-049403FA, for detailed information of system programming.
PC PROGRAMMING
Programming the panel may also be done by a temporary connection to the programming port with a computer. This is the recommended method to program the panel.
The Faraday CIS-4 software is available to allow programming the control unit by connection to a Personal Computer (PC) with an EIA-232 serial port. This allows ease of operation by preparing the program in advance and downloading to the control unit in a simple, rapid operation.
Uploading or downloading of a configuration requires technician level. The control unit automatically verifies a downloaded configuration for regulatory and system restriction compliance. After verifying the new configuration, a comparison of the new and old configurations may be printed. Switchover to the new configuration requires confirmation at the control unit. See the Faraday online help for detailed information of system programming.
PROGRAMMING SECURITY
The following levels of security protect the system from unauthorized use:
• User – Locked Door
• Maintenance – Locked Door and 4-digit Maint. Password
• Technician – Locked Door and 6-digit Tech Password
The User and Maintenance Levels are also accessible from the Remote LCD Annunciators.
48
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
MAINTENANCE
GENERAL
The MPC-6000 / MPC-7000 / RND-2 provides a maintenance mode to allow for the setting and controlling of various features in the system. Since the RND-2 does not have devices connected to it, some of these functions are not available on the RND-2.
The maintenance functions are protected by a four digit password. To access the maintenance features press the “MENU” button four times and select “Maint. Level” from the display, enter the four digit code when prompted and then press “Enter”. The functions listed below are now accessible to the user by using the function buttons on either side of the display.
Disable/Enable Devices
Disable/ Enable Groups
Disable Zones
Disable NACs
Disable City Tie
Disable DACT
Disable Status relays
Disable/Enable Detector Applications
Quick Test
Print History
Print Sensor levels
Edit Device labels
Edit System Labels
Program a Device
Set the time
Set the date
Change the password
Clear the history
Refer to the programming manual for more information about accessing and using the maintenance level functions.
49
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
QUICK TEST
If the control unit has remote connections to the Fire Department or other monitor, be sure to disable the remote signals and notify the remote monitoring station before performing test operations, since an off-normal condition will be indicated.
The Quick Test mode makes it fast and easy to test a system by eliminating the need to reset the panel after each device is activated. Quick test may be done on a loop basis (if there are multiple loops), so that the remainder of the system may continue to operate normally. Once the loop is placed into quick test, the NACs will sound for a short configurable period as each device on the loop is activated. In this way a single person is able to quickly check that each device is working and activating the system.
The printer may also be enabled or disabled during “Quick Test” as desired.
Refer to the programming manual for the details of accessing the Quick test functions.
For any required service, contact a factory-authorized representative.
50
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
APPENDIX-A: REFERENCE DATA
This appendix provides reference for the following topics:
• Wire selection guides
• Battery size calculations
WIRE SELECTION GUIDES
Resistance of Solid Copper Wire
AWG Ohms per Thousand Feet*
18 8.08
16 5.08
14 3.19
12 2.01
*NEC Chapter 9, Table 8.
Notification Appliance Circuit Wire Selection Guide
The following chart is based on the following premises:
• V=IR
• The entire load is at the end of the wire run (worst case).
• Resistance is of solid copper wire.
Contact your local distributor or the factory if further information is needed in your circumstances.
Maximum Wire Loop Distance (Feet)
Signal Load (A) 18 AWG 16 AWG 14 AWG 12 AWG
1237 1968 3134 4975
0.10
0.25
0.50
0.75
1.00
1.25
1.50
51
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Addressable Device Circuit Wire Selection Guide
Each addressable device circuit must meet the following requirements:
• Total loop resistance - 50 ohm maximum with 252 devices. (Refer to following graph.)
• Total loop capacitance - 0.5uF max line to line and 1.0uF max line to shield
Line Resistance Graph
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
50 60 70 80 90 100 110 120 130 140 150 190
Max Number of Devices Per Loop
FDLC LINE RESISTANCE vs MAX NUMBER OF DEVICES
Note: The total number of devices can not exceed 252.
160 170 180 200 210 220 230 240 250 260
* The terminal blocks of Faraday X1 devices are rated for a maximum of 14AWG wire.
52
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
BATTERY SIZE CALCULATIONS
MPC-6000 Current Calculations
Panel and Module Current
MPC-6000 Control Unit (includes one loop driver board)
CT-1K City Tie Standby
Alarm (Table 1)
MPC-DACT DACT
Board
Standby
Alarm
Total Panel currents
Place these totals in the Total System Current Table
Go to Auxiliary Module Current calculations
RND-2 Current Calculations
Panel and Module Current
RND-2 Control Unit (no loop driver board)
CT-1K City Tie Standby
MPC-DACT DACT
Board
Alarm (Table 1)
Standby
Total Panel currents
Alarm
Place these totals in the Total System Current Table
Go to Auxiliary Module Current calculations
MPC-7000 Current Calculation
Panel and Module Current
Standby Current (A) Alarm Current (A)
0.190 0.190
0.005
+
NA
0.038
+
+
+
NA
0.054
NA +
Standby Current (A) Alarm Current (A)
0.090 0.090
0.005
+
NA
0.038
+
0.054
NA
+
+
NA
+
MPC-7000 Control Unit (includes two loop driver boards)
CT-1K City Tie Standby
Alarm (Table 1)
FDLC Loop Standby 0.100 X
Driver (on LEM-1) Alarm 0.100 X
HBC-1 Standby
1
0
Loop Expander Bd. Alarm 0
NEM-1 Standby 0.015
NAC Expander Bd. Alarm 0.250
MPC-DACT DACT Standby 0.038
0.005
Standby Current (A) Alarm Current (A)
+
NA
N/A
N/A
N/A
+
Board Alarm 0.054 NA
Total Panel currents
1
Does not include charging current of 1.9A for a fully discharged battery.
0.450
+
+
N/A
0 N/A
0.015 N/A
NA
+
0.500
0
0.250
Place totals in the Total System Current table
Go to Auxiliary Module Current calculations
53
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
TABLE 1
When using the CT-1K City Tie Board add the following currents for standby and alarm for features being used:
Type of City Tie Connection
1. Local Energy
Standby
+ 0.007
Reverse Polarity Alarm Output (CA)
2. Alarm
3. Alarm w/Trouble
+ 0
0
4. Reverse Polarity Trouble Output (CT) + 0
Alarm
+ 0.020
+ 0.020
+ 0.020
+ 0.020
54
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Auxiliary Module Battery Calculations
Panel and Module Current
RDC-2 Remote
Annunciator
Standby 0.020 X =
Alarm 0.085 X =
SRU-2 Serial
Relay Unit
SRE-8 Serial
Relay Extender
SLU-2 Serial
Annunciator Unit
SLE-16 Serial
Annunciator
Extender
Total Auxiliary
Module Current
Standby 0.032 X =
Alarm 0.192 X =
Standby 0.000 X =
Alarm 0.160 X =
Standby 0.018 X =
Alarm (Note 5) 0.040 X =
Standby 0.005 X =
Alarm (Note 5) 0.000 X =
Place these totals in the Total System Current table
Go to Device Current Calculations
Device Current Calculations
Device Current
Catalog # Quantity
Standby
Alarm
Standby
Alarm
Standby
Alarm
Standby
Alarm
4-wire Smoke Detectors
Catalog # Quantity
Standby
End of Line Relay
Catalog #
Alarm
Standby
Alarm
Quantity
Notification Appliances
Catalog # Quantity
Other =
TOTAL DEVICE Current
X Current (A)
X =
X =
X =
X =
X =
X =
X =
X =
X Current (A)
X =
X =
X =
X =
X Current (A)
X =
X Current (A)
X =
X =
X =
X =
Place these totals in the Total System Current table
Go to Total System Current Calculations
Standby Current (A) Alarm Current (A)
+
NA
+
NA
+
NA
+
NA
+
NA
NA
+
+
+
NA
+
NA
+
+
NA
+
NA
+
NA
NA
NA
NA
+
Standby Current (A) Alarm Current (A)
+ NA
NA
+
+
NA
NA
+
NA
+
NA
+
NA
+
NA
+
NA
+
NA
+
+
+
+
+
+
+
55
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Total System Currents
Total Panel & Modules current
STANDBY (A)
Total Auxiliary current
Total Device current
TOTAL PANEL+ Modules + DEVICES (Note 2)
+
+
Use the Total Panel+ Modules + Devices for the Battery Size Calculations
Battery Size
ALARM (A)
+
+
Total Standby
Current
(from above)
Hours of Standby Required per NFPA 72 Standard
(4, 24 or 60)
A. x ____ Hours
AH for Standby
=
(Note 3, 4)
Total Alarm Current
(from above)
5 Minutes of Alarm
Operation per NFPA 72 Standard*
A. x 0.33 Hours =
AH for Alarm
(Note 3, 4)
A.H. for
Standby
A.H. for
Alarm
Calculated
A.H.
De-rating
Factor
A.H. Required
Battery
Capacity
+ 1.25
Notes:
1. An additional multiplier is included to compensate for the higher discharge rate in alarm. Battery capacity decreases with age.
2. The Standby current + Alarm current for an MPC-6000 must never exceed 3.0 Amps when using the two supplied transformers and 6.0 Amps when using the supplied transformers and the NPE-1 optional transformer assembly.
The Standby current + Alarm current for an MPC-7000 must never exceed 5.0 Amps when using two supplied transformers and 8.0 Amps when using the supplied transformers and the NPE-1 optional transformer assembly.
The Standby current + Alarm current for an RND-2 must never exceed 0.9 Amps when using the supplied transformer assembly.
3. The following states the maximum standby current allowed for a MPC-6000 / RND-2 panel using a 38.5
AH battery set:
60 hours of standby time is 0.457 Amps
24 hours of standby time is 1.144 Amps
4. The following states the maximum standby current allowed for a MPC-7000 panel using a 100 AH battery set:
60 hours of standby time is 1.29 Amps
24 hours of standby time is 3.22 Amps
5. Does not include lamp or LED current, add separately. Refer to installation instructions P/N 315-447345 for maximum activated current rating of individual drive circuits.
56
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
APPENDIX-B: COMPATIBLE DEVICES
DEVICES FOR ADDRESSABLE DEVICE CIRCUITS
Faraday X1 Manual Pull Stations
Faraday
Cat. No.
8700-S Manual Station, Single Action
8700-D Manual Station, Double Action
8700-M Manual Station, Single Action, Metal
Faraday X1 Modules
Faraday
Cat. No.
8701
8702
8703
8704
8705
Mini- Module for Contact Devices
Module for Contact Devices
Dual Module for Contact Devices
Module for Contact Devices with Relay
Conventional Detector Zone Module
Description
Description
Faraday X1 Photo Electric Detectors
Faraday
Cat. No.
8710
8712
Photo Detector
Thermal Detector, Fixed or Fixed/Rate of Rise
8713 Fire Smart™ Photo/Thermal Detector
Faraday X1 Bases
Faraday
Cat. No.
8853, 8715, 8716, 8840, 8717
8853, 8715, 8716
8853, 8715, 8716
8853
8715
8716
Base
Audible Base
Relay Base
8840 Duct Housing
8717 Duct Housing with Relay
Faraday X1 Accessories
8710, 8712, 8713
8710, 8712, 8713
8710, 8712, 8713
8710, 8813
8710, 8713
Faraday
Cat. No.
8726C
8726W
8727C
8727W
Description
Intelligent Remote Lamp, Ceiling mount
Intelligent Remote Lamp, Wall mount
Remote Lamp, Ceiling mount
Remote Lamp, Wall mount
Notes:
1. Faraday X1 devices, detectors and modules, up to a maximum of 252 addresses may be used per addressable X1 FDLC Loop Driver Circuit.
2. For specific wiring and installation information, read the instructions provided with each device.
57
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS
The following lists compatible devices for the auxiliary power outputs.
• Notification
Devices
Notification Appliances
Description Catalog
Number
446 (*1)
477 (*1)
2700 (*5)
2700 (*5)
2700 (*5)
2700 (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*5)
2701 (*5)
2701 (*5)
2701 (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2701 (*1) (*5)
2705-L
2705-Z (*2)
2830 (*3)
2831 (*3)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2834 (*3) (*5)
2880
2880
2880
2880
2881
2881
2881
2881
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
Bell-Vibrating
Bell-Single Stroke
Adapter Strobe
Adapter Strobe
Adapter Strobe
Adapter Strobe
Adapter Strobe – 446x Bell only
Adapter Strobe – 477x Bell only
Adapter Strobe – Strobe only
Adapter Strobe – Strobe only
Adapter Strobe – Strobe only
Adapter Strobe – Strobe only
Adapter Strobe – 446x Bell/Strobe
Adapter Strobe – 446x Bell/Strobe
Adapter Strobe – 446x Bell/Strobe
Adapter Strobe – 446x Bell/Strobe
Adapter Strobe – 477x Bell/Strobe
Adapter Strobe – 477x Bell/Strobe
Adapter Strobe – 477x Bell/Strobe
Adapter Strobe – 477x Bell/Strobe
WP Strobe Light
WP Sync Strobe Light
Sync/Non Sync Electronic Horn
Sync/Non Sync Electronic Horn
Sync/Non Sync Electronic Horn w/Adapter
Horn only
Strobe only
Strobe only
Strobe only
Strobe only
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal
Electronic Signal-8T w/Adapter
Audible only
Audible only
Audible only
Audible only
Audible only
Audible only
Strobe only
Strobe only
Strobe only
Strobe only
Setting
N/A
N/A
15cd
30cd
75cd
110cd
N/A
N/A
15cd
30cd
75cd
110cd
15cd
30cd
75cd
110cd
15cd
30cd
75cd
110cd
Steady or Temporal
Steady or Temporal
Steady or Temporal
15cd
30cd
75cd
110cd
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
Horn
Chime or Bell
Slow Whoop
Temporal or HI-Lo
Siren
SS Bell
Horn
Chime or Bell
Slow Whoop
Temporal or HI-Lo
Siren
SS Bell
Horn
Chime or Bell
Slow Whoop
Temporal or Hi-Lo
Siren
SS Bell
15cd
30cd
75cd
110cd
Max # per NAC with max current
5
4
5
5
4
4
X
32
25
13
9
6
6
8
7
32
25
13
9
8
7
32
25
13
9
19
16
10
X
49
49
49
7
47
51
40
65
38
53
47
51
40
65
38
53
47
51
40
65
38
53
32
25
13
9
X = Not Compatible
58
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
2884 (*5)
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
Audible/Strobe
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
5394 (*5)
Electronic Chime w/Adapter
Chime only
Strobe only
Strobe only
Strobe only
Strobe only
Chime/Strobe
Chime/Strobe
Chime/Strobe
Chime/Strobe
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
5398 (*5)
Electronic Chime w/Adapter
Chime only
Strobe only
Strobe only
Strobe only
Strobe only
Chime/Strobe
Chime/Strobe
Chime/Strobe
Chime/Strobe
5406 Sync Control Unit
6230 Horn
6234 (*5)
6234 (*5)
6234 (*5)
Horn w/Adapter
Horn only
Strobe only
6234 (*5)
6234 (*5)
6234 (*5)
6234 (*5)
6234 (*5)
6234 (*5)
6234 (*5)
Strobe only
Strobe only
Strobe only
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
6235-L Horn/Strobe
6235-Z (*2) Horn w/Sync Strobe
6235-Z (*2)
6235-Z (*2)
6235-Z (*2)
6238 (*5)
6238 (*5)
Horn only
Strobe only
WP Horn/Strobe
Horn w/Adapter
Horn only
6238 (*5)
6238 (*5)
Strobe only
Strobe only
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
Chime/Bell, 15cd
Chime/Bell, 30cd
Chime/Bell, 75cd
Chime/Bell, 110cd
Slow Whoop, 15cd
Slow Whoop, 30cd
Slow Whoop, 75cd
Slow Whoop, 110cd
Temporal or Hi-Lo, 15cd
Temporal or Hi-Lo, 30cd
Temporal or Hi-Lo, 75cd
Temporal or Hi-Lo, 110cd
Siren, 15cd
Siren, 30cd
Siren, 75cd
Siren, 110cd
SS Bell, 15cd
SS Bell, 30cd
SS Bell, 75cd
SS Bell, 110cd
N/A
N/A
15cd
30cd
75cd
110cd
Chime, 15cd
Chime, 30cd
Chime, 75cd
Chime, 110cd
N/A
15cd
30cd
75cd
110cd
Chime, 15cd
Chime, 30cd
Chime, 75cd
Chime, 110cd
N/A
N/A
N/A
15cd
30cd
75cd
110cd
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15cd
30cd
27
21
12
8
See P/N 315-545222
55
55
32
25
13
9
20
17
11
8
55
X
X
26
X
X
55
32
25
X = Not Compatible
19
16
10
7
20
16
10
8
18
15
10
7
21
18
11
8
17
15
10
7
20
17
10
8
157
157
32
25
13
9
27
21
12
8
157
157
32
25
13
9
59
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
6238 (*5)
6238 (*5)
6238 (*5)
6238 (*5)
6238 (*5)
6238 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6254 (*5)
6255-L
Strobe only
Strobe only
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn w/Adapter
Horn only
Strobe only
Strobe only
Strobe only
Strobe only
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
WP Horn only
6255-L Horn/Strobe
6255-Z (*2) WP Horn w/Sync Strobe
6255-Z (*2)
6255-Z (*2)
WP Horn only
Strobe only
6255-Z (*2)
6258 (*5)
6258 (*5)
6258 (*5)
6258 (*5)
WP Horn/Strobe
Horn w/Adapter
Horn only
Strobe only
Strobe only
6258 (*5)
6258 (*5)
6258 (*5)
6258 (*5)
6258 (*5)
6258 (*5)
6300
6301
6304 (*5)
6304 (*5)
Strobe only
Strobe only
Horn/Strobe
Horn/Strobe
Horn/Strobe
Horn/Strobe
Mini-Horn
Mini-Horn
Mini-Horn w/Adapter
Mini-Horn only
75cd
110cd
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
N/A
15cd
30cd
75cd
110cd
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
15cd
30cd
75cd
110cd
Horn, 15cd
Horn, 30cd
Horn, 75cd
Horn, 110cd
Steady or Temporal
Steady or Temporal
N/A
6304 (*5)
6304 (*5)
6304 (*5)
6304 (*5)
6304 (*5)
Strobe only
Strobe only
Strobe only
Strobe only
Mini-Horn/Strobe
6304 (*5)
6304 (*5)
6304 (*5)
Mini-Horn/Strobe
Mini-Horn/Strobe
Mini-Horn/Strobe
6310 Mini-Horn-S/T
6311 Mini-Horn-S/T
15cd
30cd
75cd
110cd
Mini-Horn, 15cd
Mini-Horn, 30cd
Mini-Horn, 75cd
Mini-Horn, 110cd
N/A
N/A
6314 (*5)
6314 (*5)
6314 (*5)
6314 (*5)
6314 (*5)
Mini-Horn-S/T w/Adapter
Mini-Horn only
Strobe only
Strobe only
Strobe only
N/A
15cd
30cd
75cd
115
32
25
13
6314 (*5)
6314 (*5)
6314 (*5)
6314 (*5)
6314 (*5)
Strobe only
Mini-Horn/Strobe
Mini-Horn/Strobe
Mini-Horn/Strobe
Mini-Horn/Strobe
110cd
Mini-Horn, 15cd
Mini-Horn, 30cd
Mini-Horn, 75cd
Mini-Horn, 110cd
9
25
20
12
8
X = Not Compatible
Key:
(*1) 1=10” gong, 4=4” gong, 5=chime, 6=6” gong, 8=8” gong
(*2) Sync Strobe Light requires 5406 Sync Control Module or panel NACs programmed for synchronized operation.
(*3) Sync Electronic Horn and Sync Strobe Light require 5406 Sync Control Module or panel NACs programmed for
synchronized operation.
(*4) See Installation Instructions for the current of the desired tone.
(*5) See Installation Instructions for the current of the adapter strobe.
Cat. No. xxxx-L = Strobe Light (UL1971 110cd) Cat. No. xxxx-Z = Sync Strobe Light (UL1971 110cd)
32
25
13
9
25
20
12
8
115
115
13
9
20
17
11
8
26
32
25
13
9
14
12
9
7
26
7
115
115
115
13
9
14
12
9
X
26
32
25
X
X
26
X
60
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Accessory Devices
Faraday Cat.
No.
Mfg. Part Number Description
Faraday
R711-1 711-1
RSE-100 15070
RSE 300
15222A
RSE-300
15222A
Remote Signal Expander
Remote Signal Expander
Signal Expander Panel
1. The accessory devices listed above may be wired to activate from the notification appliance circuits.
2. For specific wiring and installation information, read the instructions provided with each device.
DEVICES FOR AUXILIARY POWER OUTPUTS
The following lists compatible devices for the auxiliary power outputs.
• Relays
Four Wire (Separately Powered) Heat & Smoke Detectors. See Devices for Initiating Device
Circuits.
Door Holders
Not applicable at this time.
Relays
Faraday Cat.
No.
Mfg. Part Number Description
Faraday
R711-1 711-1
Controls
R712-1 MR-101/C
R712-2 MR-201/C
R712-4 MR-104/C
R712-8 MR-204/C
9273 PAM-4
System
PM6849 A77-716B
Notes:
1. The accessory devices listed above may be wired to the auxiliary power outputs.
2. For specific wiring and installation information, read the instructions provided with each device.
61
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
APPENDIX-C: TROUBLESHOOTING
DEFINITIONS FOR EVENT HISTORY ENTRIES
A. General
ENTRY INDICATES
ALRM Alarm
AVCntr Alarm Verify counter
CrossZone cross zone point
LCDxx LCD Annunciator xx
MANL PULL
Mntc
PAS
PAS INHBT
Manual pull station
Detector maintenance alert
Positive alarm sequence
PAS inhibit switch
PRE SIGNL pre-signal
PreA Pre-alarm
SUPERVSRY Supervisory
SUPR Supervisory
TRBL Trouble
TROUBLE Trouble
WATERFLOW Waterflow
62
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
B. System Troubles
ENTRY INDICATES
AC Trouble
AddrLp 1 DBLSHT
AddrLp 1 OPEN
AddrLp 1 SHORT
BATT Trouble
CITY Trouble
DACT Acct Trb
DACT Com Trouble
DACT PL x Trouble
FLASH FATAL Trb
GRND FAULT Trbl
LCDxx NoRespons
LCDxx Not Pgmd
LCDxx Trouble
MNLP Bad Msg
MNLP Fifo Xmit
MNLP NoRespons
NACxx Trouble
PC Pgmr Trb
QuickTest Abort
Trb Reminder
AC input low or off
Double short trouble on addressable loop 1
Open circuit trouble on addressable loop 1
Short circuit trouble on addressable loop 1
Battery input low or off
Local Energy circuit open
DACT account reporting trouble
DACT communication trouble with main processor
Open or short on DACT phone line x
Configuration Flash memory trouble
Ground Fault trouble
LCD Annunciator xx programmed but is not responding
LCD Annunciator xx is not programmed but is responding
LCD Annunciator xx reports trouble
Main processor to loop processor communication trouble
Main processor to loop processor communication trouble
Main processor to loop processor communication trouble
NAC xx wiring is open or shorted
Control unit is not receiving communication from PC
Quick Test Timer expired causing abnormal exit of Quick Test
Trouble Reminder timer expired
63
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
C. System Events
ENTRY INDICATES/NOTES
Alarm Silenced
All AV Ctrs Clr
AutoProgram Run
Backup Cnfg Check
Backup Cnfg Edit
ConfigsCompared
MAIN, LCDxx shown on bottom line
All AV counters cleared
Auto programming function run
Backup configuration validated, result on bottom line
Backup configuration edited
Backup and primary configurations compared, result on bottom line
ConfigsSwapped
EventHist Clear
Mnt Levl Enter
Backup and Primary configurations swapped
Event History cleared
Entered Maintenance level
Mnt Levl Exit Exited Maintenance level
Mnt Levl PW Changed Changed Maintenance level password
NACxx Active Confirm NAC activation confirmed
Panel Reset
Power Up
MAIN, LCDxx shown on bottom line
PriConfigCopied
QuickTest Exit
QuickTest Start
Primary configuration copied to backup
Exited Quick Test, MAIN or LCDxx shown on bottom line
Started Quick Test, MAIN or LCDxx shown on bottom line
System Date Changed Changed system date, old and new dates shown on lines 3 and 4
System Time Changed Changed system time, old and new times shown on lines 3 and 4
Tech Levl Enter
Tech Levl Exit
Entered Tech level
Exited Tech level
Tech Levl PW Changed Changed Tech level password
User Levl Enter
User Levl Exit
Entered User level
Exited User level
64
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
APPENDIX-D: MODULE INSTALLATION
INSTRUCTIONS LIST
This Appendix provides a list of installation instructions for the following option modules and accessories:
• RDC-2 Remote LCD Annunciator Operating Instructions 315-049104FA
65
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
APPENDIX-E: GLOSSARY
Alarm Signal. A signal indicating an emergency requiring immediate action, such as an alarm for fire from a manual station, a waterflow alarm, or an automatic smoke detector.
Alarm Silence Inhibit. An option that prevents a human operator from silencing the notification appliances for a preset period of time.
Alarm System. A combination of compatible initiating devices, control units, and notification appliances designed and installed to produce an alarm signal in the event of a fire.
Alarm Verification. A preset option that causes the control unit to verify alarms originated by smoke detectors before indicating an alarm.
Annunciator. A remotely located, electrically powered display, separate from the control unit, containing LEDs or lamps to indicate the states of the fire alarm system.
Audible Signal. An audible signal is a sound made by one or more audible notification appliances, such as bells or horns, in response to the operation of an initiating device.
Authority Having Jurisdiction (AHJ). The organization, office, or individual responsible for approving equipment, installation or procedure.
Auto-Silence. The capability of a control to automatically silence the notification appliances after a preset period of time.
Auxiliary Relays. Control relays that energize only during alarm conditions that are used to either apply power to or remove power from other equipment during an alarm condition.
Class A Circuit. An initiating device or notification appliance circuit within which all components remain fully functional, even though a single open or ground exists in the circuit.
Class B Circuit. An initiating device or notification appliance circuit within which some or all components may be disabled with a single open or ground exists in the circuit.
Detector - FireSmart™. An intelligent fire detector that blends photoelectric, thermal and neural network technologies for superior protection without false alarms.
Detector - Smoke, Photoelectric Type. A detector employing the photoelectric principle of reflection or obstruction of light by smoke.
Detector - Thermal Type. An addressable thermal sensor that is programmable as either a fixed temperature (135° F) or as a rate of rise detector.
End Of Line (EOL). A device used to terminate a supervised circuit.
66
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
General Alarm. A term usually applied to the simultaneous operation of all the notification appliances on a system.
Ground Fault. A trouble condition in which a low resistance has been detected between the system wiring and conduit ground.
Initiating Device. A manually or automatically operated device such as a manual pull station, smoke detector, heat detector, waterflow switch or tamper switch.
Initiating Device Circuit (IDC). A circuit to which initiating devices are connected.
Labeled. Equipment or materials to which have been attached a label, symbol, or other identifying mark of an organization acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of the production of such labeled equipment or materials. And by whose labeling the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Listed. Equipment or materials included in a list published by an organization acceptable to the authority having jurisdiction and concerned with product evaluation, that maintains periodic inspection of production of listed equipment or materials. And whose listing states either that the equipment or material meets appropriate standards or has been tested and found suitable for use in a specified manner.
NEC. National Electrical Code also published as NFPA standard 70.
Notification Appliance. An electrically operated appliance used to indicate the system status such as a bell, horn, strobe light or speaker.
Notification Appliance Circuit (NAC). A circuit to which notification appliances are connected.
Power Supply. That portion of the fire alarm control unit, which provides the power needed to operate all control unit modules, as well as that, needed to operate all electrically powered initiating devices and all notification appliances.
Quick Test. A term pertaining to the test mode of the system, that automatically resets after a service technician tests initiating devices.
Supervisory Alarm. A signal indicating the operation of a supervisory device.
Supervisory Device. A device that monitors the condition of a sprinkler system such as a gate-valve switch, water-level switch, low pressure switch, low temperature switch or fire pump monitor.
Trouble Signal. An audible signal indicating trouble of any nature, such as a circuit break or ground, occurring in the device or wiring associated with a fire alarm signal.
67
MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
Waterflow Switch. An assembly approved for service and so constructed and installed that any flow of water from a sprinkler system equal to or greater than that from a single automatic sprinkler head will result in activation of this switch and subsequent indication of an alarm condition.
Zone. A designated area of a building. Commonly, zone, is interchanged with initiating device circuit.
68
Siemens Building Technologies, Inc.
8 Fernwood Road • Florham Park, NJ 07932
Tel: (973) 593-2600 • Fax: (973) 593-6670
Web: www.faradayfirealarms.com
P/N 315-447309-5
advertisement
Related manuals
advertisement
Table of contents
- 7 INTRODUCTION
- 7 CONTROL UNIT LIMITATIONS
- 8 INSTALLATION AND WARRANTY INFORMATION
- 8 Installer Information
- 8 Original Purchaser Information
- 9 PREFACE
- 10 DESCRIPTIONS
- 10 MPC-6000 SYSTEM DESCRIPTION
- 10 Power Supply
- 10 X1 Addressable Device Circuit
- 11 Notification Appliance Circuits
- 11 Serial Interface Circuit
- 11 Status Relays
- 11 Programming Port
- 12 MPC-7000 SYSTEM DESCRIPTION
- 12 Power Supply
- 12 X1 Addressable Device Circuits
- 13 Notification Appliance Circuits
- 13 Serial Interface Circuit
- 13 Status Relays
- 13 Programming Port
- 14 RND-2 SYSTEM DESCRIPTION
- 14 Power Supply
- 15 Serial Interface Circuit
- 15 Status Relays
- 15 Programming Port
- 16 OPTIONAL MODULES
- 16 CT-1K City Tie Board (MPC-6000 / MPC-7000 / RND-2)
- 16 MPC-DACT DACT Board (MPC-6000 / MPC-7000 / RND-2)
- 16 NPE-1 Transformer Assembly (MPC-6000 / MPC-7000)
- 16 NEM-1 NAC Expansion Board (MPC-7000)
- 16 LEM-1 Loop Expander Board (MPC-7000)
- 16 FDLC Loop Driver Board (MPC-7000)
- 16 HBC-1 Battery Charger (MPC-7000)
- 16 Battery Sets
- 17 AUXILIARY MODULES
- 17 Serial LCD Annunciator
- 17 Serial Relay Unit and Serial Relay Extender
- 17 Serial Annunciator Unit and Serial Annunciator Extender
- 17 RSE-300 Remote Signal Expander
- 18 X1 ADDRESSABLE DEVICES
- 18 Fire Smart™ Smoke Detector
- 18 Heat Detectors
- 18 Addressable Modules (Monitor and Control)
- 18 Manual Stations
- 18 Programming X1 Devices
- 19 EVENT HISTORY
- 20 GENERAL DESIGN FEATURES
- 20 Environmental
- 20 Power Limiting
- 20 Ground Fault Detection
- 20 NAC Operation
- 20 Transient Protection
- 20 Security Features
- 21 REGULATORY STANDARDS
- 21 Federal Communications Commission
- 21 Underwriters Laboratories
- 22 GENERAL SPECIFICATIONS
- 22 Environmental
- 22 Primary Supply
- 22 Secondary and Trouble Power Supply
- 22 Auxiliary Power Outputs
- 22 Status Relays
- 23 Notification Appliance Circuits
- 23 Serial Interface Circuit
- 23 X1 Addressable Device Circuits
- 24 City Tie (Optional City Tie Board P/N CT-1K)
- 24 DACT Circuit (Optional DACT Board MPC-DACT)
- 24 Additional Transformer (Optional Transformer Assembly NPE-1)
- 25 CONTROL UNIT OPERATION
- 25 OPERATION INSTRUCTIONS
- 25 Standby Condition
- 25 Alarm Conditions
- 26 Trouble Conditions
- 27 Supervisory Conditions
- 27 Pre-Alarm Conditions
- 27 Maintenance
- 28 ADDITIONAL OPERATING PROCEDURES
- 28 Lamp Test
- 28 Drill
- 28 Recall
- 28 Alert
- 29 History
- 30 MPC-6000 / MPC-7000 / RND-2 OPERATING INSTRUCTIONS
- 30 Alarm Operation
- 30 Authorized Personnel Only
- 30 Trouble Operation
- 30 Normal Standby Condition
- 31 RDC-2 OPERATING INSTRUCTIONS
- 31 Alarm Operation
- 31 Authorized Personnel Only
- 31 Trouble Operation
- 31 Normal Standby Condition
- 32 CONTROL UNIT INSTALLATION
- 32 PARTS SUPPLIED – MPC-6000 / MPC-7000 / RND
- 32 Enclosure Packages (Black or Red)
- 32 Electronics Package MPC-6000 / MPC
- 32 Electronics Package RND
- 32 With NPE-1 Transformer Package
- 32 CAUTION
- 33 CONTROL UNIT LOCATION
- 33 INSTALLATION
- 33 ENCLOSURE MOUNTING
- 34 MPC-6000 and RND-2 Enclosure Mounting Pictures
- 35 MPC-7000 Enclosure Mounting Pictures
- 35 Remove Knock-Outs
- 36 Main Board Installation – P/N MPC6-MB / MPC7-MB
- 37 Bridge Rectifier Installation – P/N 130-PM
- 38 Transformer Mounting – P/N NPE
- 39 Loop Driver Board(s) Mounting – P/N FDLC
- 40 Display Board Installation – P/N MPC-DB or RND2-DB
- 40 Ground Wire Installation – P/N
- 41 SYSTEM WIRING
- 41 AC Supply Connection
- 42 Battery Installation
- 42 Powering the Control Unit
- 42 Optional Modules
- 42 Check System Operation
- 42 WIRING
- 43 Control Unit Wiring Overview
- 43 Wiring Entering Enclosure
- 43 Install Wiring
- 44 Wiring Separation
- 45 Primary And Secondary Power Wiring
- 45 Status Relays And Auxiliary Power Outputs Wiring
- 46 MPC-6000 System Power Requirements (Does not include NAC power)
- 46 RND-2 System Power Requirements
- 46 MPC-7000 System Power Requirement (Does not include NAC power)
- 47 Auxiliary Power Supply
- 47 Battery Size Calculations
- 48 NAC Wiring
- 49 Serial Interface Circuit
- 50 Serial Remote Device Wiring Overview
- 51 X1 Addresable Device Circuit(s)
- 52 X1 Addressable Device Wiring Diagrams
- 54 PROGRAMMING THE CONTROL UNIT
- 54 KEYPAD PROGRAMMING
- 54 PC PROGRAMMING
- 54 PROGRAMMING SECURITY
- 55 MAINTENANCE
- 55 GENERAL
- 56 QUICK TEST
- 57 APPENDIX-A: REFERENCE DATA
- 57 WIRE SELECTION GUIDES
- 57 Resistance of Solid Copper Wire
- 57 Notification Appliance Circuit Wire Selection Guide
- 57 Maximum Wire Loop Distance (Feet)
- 58 Addressable Device Circuit Wire Selection Guide
- 58 Line Resistance Graph
- 59 BATTERY SIZE CALCULATIONS
- 59 MPC-6000 Current Calculations
- 59 RND-2 Current Calculations
- 59 MPC-7000 Current Calculation
- 61 Auxiliary Module Battery Calculations
- 61 Device Current Calculations
- 62 Total System Currents
- 62 Battery Size
- 63 APPENDIX-B: COMPATIBLE DEVICES
- 63 DEVICES FOR ADDRESSABLE DEVICE CIRCUITS
- 63 Faraday X1 Manual Pull Stations
- 63 Faraday X1 Modules
- 63 Faraday X1 Photo Electric Detectors
- 63 Faraday X1 Bases
- 63 Faraday X1 Accessories
- 64 DEVICES FOR NOTIFICATION APPLIANCE CIRCUITS
- 64 Notification Appliances
- 67 Accessory Devices
- 67 DEVICES FOR AUXILIARY POWER OUTPUTS
- 67 Door Holders
- 67 Relays
- 68 APPENDIX-C: TROUBLESHOOTING
- 68 DEFINITIONS FOR EVENT HISTORY ENTRIES
- 68 A. General
- 69 B. System Troubles
- 70 C. System Events
- 71 APPENDIX-D: MODULE INSTALLATION INSTRUCTIONS LIST
- 72 APPENDIX-E: GLOSSARY