Component Names and Settings. YASKAWA Varispeed-606PC3, Varispeed V7 COMPACT GENERAL-PURPOSE INVERTER (VOLTAGE VECTOR CONTROL) FOR DeviceNet COMMUNICATIONS
Anúncio
Anúncio
56
Item
Explicit Message
Communications
Communications
Power Supply
Specifications
Up to 32 bytes of data can be transferred in conformance with the DeviceNet AC/DC drive profile.
11 to 25 VDC (20 mA max.)
Component Names and Settings
Rotary Switches
The rotary switches are used to set the DeviceNet baud rate and MAC
ID (node address). Always turn OFF the Inverter’s input power supply before changing the rotary switch settings. The settings will be enabled the next time the power is turned ON.
RATE
S1
0
1 2
9 8
3
7
4
5
6
Baud rate setting
S3 0
1 2
9 8
3
4
5
7
6
0
1 2
9 8
3
4
5
7
6
MSB LSB
ADDRESS
S4
MAC ID Setting
10 s digit (MSB)
MAC ID Setting
1 s digit (LSB)
Baud Rate Setting Switch (S1)
Setting 0 1 2 3 to 9
Baud Rate 125 kbps 250 kbps 500 kbps Use setting in constant n152.
MAC ID Setting Switches (S3 and S4)
The Inverter’s MAC ID is set on the MSB (S3) and LSB (S4) rotary switches.
MAC ID = (MSB setting × 10) + (LSB setting)
The MAC ID setting range is 0 to 63. If a value between 64 and 99 is set, the MAC ID setting in constant n150 will be used.