10. Specifications
Recommended Peripheral Devices
It is recommended that the following peripheral devices be mounted between the AC main circuit power supply and Varispeed V7 input terminals R/L1, S/L2, and T/L3.
• MCCB (Molded-case Circuit Breaker)/Fuse:
Always connect for wiring protection.
• Magnetic Contactor:
Mount a surge suppressor on the coil. (Refer to the table shown below.) When using a magnetic contactor to start and stop the
Inverter, do not exceed one start per hour.
Recommended MCCB Magnetic Contactors and Fuses
• 200 V 3-phase
Varispeed V7
Model
V7**
20P
1
0.3
V7**
20P
2
0.6
Capacity
(kVA)
Rated Output
Current (A)
MCCB type
NF30 (MIT-
SUBISHI)
Magnetic contactor
(Fuji Electric
FA Components &
Systems)
Fuse (UL
Class RK5)
0.8
5 A
HI-
7E
5 A
1.6
5 A
HI-
7E
5 A
• 200 V Single-phase
Varispeed V7
Model
Capacity (kVA)
Rated Output
Current (A)
V7**
B0P1
0.3
0.8
V7**
20P
4
1.1
3
5 A
HI-
7E
5 A
V7**
B0P2
0.6
1.5
V7**
20P
7
1.9
5
V7**
21P
5
3.0
V7**
22P
2
4.2
V7**
23P
7
6.7
V7**
25P
5
9.5
10 A 20 A 20 A 30 A 50 A 60 A
HI-
7E
10 A 20 A 20 A 30 A 50 A 60 A
V7**
B0P4
1.1
3
8
HI-
10-
2E
V7**
B0P7
1.9
5
11
HI-
10-
2E
17.5
25.0
33.0
V7**
B1P5
3.0
8
HI-
20E
HI-
30E
V7**
B2P2
4.2
11
V7**
27P
5
13.0
HI-
50E
V7**
B3P7
6.7
17.5
239
240
Varispeed V7
Model
MCCB type
NF30, NF50
(MITSUBISHI)
Magnetic contactor
(Fuji Electric FA
Components &
Systems)
Fuse (UL Class
RK5)
• 400 A 3-phase
V7**
B0P1
5 A
V7**
B0P2
5 A
V7**
B0P4
10 A
HI-7E HI-7E HI-7E
5 A 5 A 10 A
V7**
B0P7
20 A
HI-
10-2E
20 A
V7**
B1P5
V7**
B2P2
20 A 40 A
HI-
15E
HI-
20E
20 A 40 A
V7**
B3P7
50 A
HI-
30E
50 A
Varispeed V7
Model
Capacity
(kVA)
Rated Output
Current (A)
MCCB type
NF30, NF50
(MITSUB-
ISHI)
Magnetic contactor
(Fuji Electric
FA Components &
Systems)
Fuse (UL
Class RK5)
V7**
40P2
0.9
1.2
5 A
HI-
7E
5 A
V7**
40P4
1.4
V7**
40P7
2.6
1.8
5 A
HI-
7E
5 A
3.4
5 A
HI-
7E
5 A
V7**
41P5
3.7
V7**
42P2
4.2
V7**
43P0
5.5
V7**
43P7
6.6
4.8
10 A
HI-
10-
2E
10 A
5.5
10 A
HI-
10-
2E
10 A
7.2
20 A
HI-
10-
2E
20 A
8.6
20 A
HI-
10-
2E
20 A
V7**
45P5
11.0
V7**
47P5
14.0
14.8
30 A
HI-
20E
30 A
18.0
30 A
HI-
20E
30 A
Surge Suppressors
Surge Suppressors
Coils and Relays
200 V to
230 V
Large size magnetic contactors
Control relays
MY-2, -3 (OMRON)
HH-22, -23 (FUJI)
MM-2, -4 (OMRON)
Model
DCR2-
Specifications
50A22E
10A25C
250 VAC
0.5
µF
200 Ω
250 VAC
0.1
µF
100 Ω
Code No.
C002417
C002482
10. Specifications
• Ground Fault Interrupter:
Select a ground fault interrupter not affected by high frequencies. To prevent malfunctions, the current should be 200 mA or higher and the operating time 0.1 s or longer.
Example:
• NV series by Mitsubishi Electric Co., Ltd. (manufactured in 1988 and after)
• EGSG series by Fuji Electric Co., Ltd. (manufactured in 1984 and after)
• AC and DC Reactor:
Install an AC reactor to connect to a power supply transformer of large capacity (600 kVA or more) or to improve power factor on the power supply side.
• Noise Filter:
Use a noise filter exclusively for Inverter if radio noise generated from the Inverter causes other control devices to malfunction.
NOTE
1. Never connect a general LC/RC noise filter to the Inverter output circuit.
2. Do not connect a phase-advancing capacitor to the I/O sides and/or a surge suppressor to the output side.
3. When a magnetic contactor is installed between the
Inverter and the motor, do not turn it ON/OFF during operation.
For the details of the peripheral devices, refer to the catalog.