Wire assignment, connection cable

5 Connecting to power supply

5.8 Wiring plan - version IP 66/IP 68, 1 bar

1

2

Fig. 36: Wire assignment in permanently connected connection cable

1 brown (+) and blue (-) to power supply or to the processing system

2 Shielding

5.9 Switch-on phase

After connecting the instrument to power supply or after a voltage recurrence, the instrument carries out a self-check for approx. 30 s:

• Internal check of the electronics

Indication of the instrument type, hardware and software version, measurement loop name on the display or PC

• Indication of the status message "F 105 Determine measured

value" on the display or PC

• The output signal jumps to the set fault current

As soon as a plausible measured value is found, the corresponding current is outputted to the signal cable. The value corresponds to the actual level as well as the settings already carried out, e.g. factory setting.

VEGAPULS 69 • 4 … 20 mA/HART two-wire 35