Operating Instructions VEGAPULS 69

Add to My manuals
88 Pages

advertisement

Operating Instructions VEGAPULS 69 | Manualzz

6 Set up with the display and adjustment module

6.4 Parameter adjustment - Quick setup

To quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module.

Carry out the following steps in the below sequence.

You can find "Extended adjustment" in the next sub-chapter.

1. Measurement loop name

In the first menu item you assign a suitable measurement loop name.

Permitted are names with max. 19 characters.

2. Medium

In this menu item you select the type of bulk solid. The selection comprises different granulate sizes.

3. Application/Vessel bottom

In this menu item you specify the application and the form of the vessel bottom.

4. Vessel height/Measuring range

In this menu item you enter the height of the vessel and hence the active measuring range.

5. Max. adjustment

In this menu item you carry out the max. adjustment.

Enter the measuring distance for 100 % filling.

VEGAPULS 69 • 4 … 20 mA/HART two-wire 39