MGC2 – UserManual
Specifications subject to change without notice. | USA 160811 | Page 12 of 34
4.5 Menu Relay Parameter
Reading and changes of the parameter for each single alarm relay.
Relay Parameter
(Main menu)
R 01
(Selection relay No. – only registered modules possible)
Relay Mode
De-energized
Static / Flash
0 s
Latching Mode
No
Time Recurr. DI
0 s 0 0
Relay mode
See 4.5.1
Relay function
See 4.5.2
Activation of latching mode
See 4.5.3
Definition horn function
See 4.5.4
External Mode
DI: ON = 0: OFF = 0
Definition external operation
See 4.5.5
ON-Delay Time
0 s
Delay time for relay ON
See 4.5.6
OFF-Delay Time
0 s
Delay time for relay OFF
See 4.5.6
4.5.1 Relay Mode
Definition of the relay mode – in activation status it is only overridden by the flashing function:
Symbol
R 01
De-energized
Description Setting Status Function
Relay No.
Relay Mode De-energized
Selection relay
De-energized = Alarm OFF = Relay OFF Energized
= Alarm ON = Relay OFF
4.5.2 Relay Function Static / Flash
Definition of the relay function – acts directly on the relay output:
Symbol
R 01
0
Description Setting Status Function
Relay No.
Selection relay
0 = Relay function static
Function 0 > 0 = Relay function flashing (= time interval in sec.)
Impulse / Break = 1:1
PolyGard ® is a registered trademark of MSR-Electronic GmbH
12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.IN
TEC | relevantsolutions.com/inteccontrols
advertisement
advertisement
Table of contents
- 4 1 Application
- 4 2 Description
- 4 2.1 Normal Mode
- 4 2.2 Alarm Mode
- 4 2.3 Fault Mode
- 5 3 Operating Instruction
- 5 3.1 Description Keypad User Interface
- 5 3.2 Setting / Change Parameters or Setpoints
- 6 3.3 Code Levels
- 7 4 Menu Overview
- 8 4.1 Fault Management
- 8 4.1.1 Acknowledge a Fault
- 8 4.1.2 Error Memory
- 9 4.1.3 System Errors
- 10 4.2 Status Alarm
- 10 4.3 Status Relay
- 10 4.3.1 Manual Operation of the Relays
- 11 4.4 Menu Sensor Readings
- 12 4.5 Menu Relay Parameter
- 12 4.5.1 Relay Mode
- 12 4.5.2 Relay Function Static / Flash
- 13 4.5.3 Latching Mode
- 13 4.5.4 Horn Function
- 14 4.5.5 External Operation of Alarm Relay
- 14 4.5.6 Delay Mode of Alarm Relay
- 15 4.6 Menu SP Parameter
- 16 4.6.1 Activate – Deactivate SP
- 16 4.6.2 Lock or Unlock SP
- 17 4.6.3 Selection Gas Type
- 18 4.6.6 Threshold/Hysteresis
- 18 4.6.7 Delay for Alarm ON and/or OFF
- 19 4.6.8 Control Mode Current or Average Value
- 19 4.6.9 SP Fault Assigned to Alarm
- 19 4.6.10 Alarm Assigned to Alarm Relay
- 19 4.6.11 SP Signal Assigned to Analog Output
- 20 4.7 Menu Data Logger
- 20 4.7.1 Data Logger Switch On/Off
- 21 4.7.2 Current Value
- 22 4.7.3 CV Log Rate
- 22 4.7.4 Alarm Status
- 23 4.7.5 Error Status
- 24 4.8 Menu System Parameter
- 26 4.8.1 Service Mode
- 26 4.8.2 Software Version
- 26 4.8.3 SP Address Mode
- 26 4.8.4 Language
- 26 4.8.5 Maintenance Concept
- 27 4.8.6 Average Function
- 27 4.8.7 System Time, System Date
- 27 4.8.8 Service Password (Maintenance)
- 27 4.8.9 GC Address
- 28 4.8.11 Acknowledge a Relay in Latching Mode by a DI
- 28 4.8.12 Power On Time
- 28 4.8.13 Registration of Expansions Modules
- 29 4.8.14 Error Indicator System Bus
- 29 4.8.15 Analog Output
- 30 4.8.16 Relay Multiplication
- 31 5 Programming Operation
- 31 5.1.2 Analog Output Setup
- 32 5.1.3 Relay Setup
- 33 5.1.4 Sensor Setup
- 34 6 Notes & General Information
- 34 6.1 Intended Product Application
- 34 6.2 Installer’s Responsibilities
- 34 6.3 Maintenance
- 34 6.4 Limited Warranty