The table shows the assignment of the relay numbers and of the analog in/outputs to the EP module addresses.

Symbol Description Default Function

Module

Address

Analog

Input

Relay

No.

Analog

Output Module

EP- Mod. 0 Relay + SP

EP- Mod. 1 Inactive

EP- Mod. 2 Inactive

EP- Mod. 3 Inactive

EP- Mod. 4 Inactive

EP- Mod. 5 Inactive

Relay + SP active =

Alarm relay + analog inputs active

Inactive = Module not active

Relay active =

Only alarm relay active

Relay + SP active =

Alarm relay + analog inputs active

1

2

3

4

5

01-04

05-08

09-12

21-24

01-05

06-10

11-15

13-16 16-20

17-20 21-25

26 -30

01-02

03-04

05-06

GC-05

EP-05

EP-05

07-08 EP-05

09-10 EP-05

11-12 EP-05

4.8.14 Error Indicator System Bus

All data packets received by the GC-05 are checked for completeness and compatibility. Faulty data packets are recorded by the error counter. Max. 1-2 faulty data packets are admissible a day.

A higher error rate mostly comes from incorrect wiring of the field bus line.

4.8.15 Analog Output

The Gas Controller Module as well as the EP-05 Modules 1 to 5 have two analog outputs (AO) with 4 to 20 mA signal each. The signal of one or more sensor points can be assigned to each of the analog outputs. The assignment is effected in the menu “SP Parameter” for each SP. The sensor point sends the signal, which is defined in the menu 

“C/A Mode”.

Out of the signals of all assigned sensor points the Gas Controller determines the minimum, the maximum or the average value and displays it at the analog output. The definition, which value is transmitted, is effected in the  menu “Analog Output X”.

The analog output can be calibrated at 4 and at 20 mA. Therefore an ampere meter (measuring range 25 mA) can be attached to the AO and the respective factor has to be changed until the analog output corresponds to 4 and/or 20 mA.

During calibration evaluation of the sensor point signals is not possible. This calibration is effected by the factory. The factors should not be changed.

Symbol

Max.

4.0

20.0

Description

Select

Output mode

Calibration

Default Status Function

Max.

Min. = Displays the minimum value of all assigned SP

Max. = Displays the maximum value of all assigned SP

Average = Displays the average value of all assigned SP

4.0

20.0

4.0 = Calibration factor at 4 mA

20.0 = Calibration factor at 20 mA