Lifetime Expectancy. Puls Dimension CP Series, DIMENSION CP20.248, CP20.248
Add to My manuals33 Pages
advertisement
CP-Series
CP20.248
24V, 20A, 480W, S INGLE P HASE
16.
L
IFETIME
E
XPECTANCY
The Lifetime expectancy shown in the table indicates the minimum operating hours (service life) and is determined by the lifetime expectancy of the built-in electrolytic capacitors. Lifetime expectancy is specified in operational hours and is calculated according to the capacitor’s manufacturer spec ification. The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years
(131 400h). Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices.
Lifetime expectancy
AC 100V
40 000h
111 000h
23 000h
113 000h
313 000h
66 000h
AC 120V
51 000h
130 000h
33 000h
145 000h
368 000h
93 000h
AC 230V
88 000h
157 000h
63 000h
248 000h
443 000h
178 000h
At 24V, 20A and 40°C
At 24V, 10A and 40°C
At 24V, 24A and 40°C
At 24V, 20A and 25°C
At 24V, 10A and 25°C
At 24V, 24A and 25°C
17.
MTBF
MTBF stands for M ean T ime B etween F ailure, which is calculated according to statistical device failures, and indicates reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily represent the life of a product.
The MTBF figure is a statistical representation of the likelihood of a device to fail. A MTBF figure of e.g. 1 000 000h means that statistically one unit will fail every 100 hours if 10 000 units are installed in the field. However, it cannot be determined if the failed unit has been running for 50 000h or only for 100h.
For these types of units the MTTF ( M ean T ime T o F ailure) value is the same value as the MTBF value.
MTBF SN 29500, IEC 61709
MTBF MIL HDBK 217F
AC 100V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
AC 120V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
AC 230V
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
T.B.D.
At 24V, 20A and 40°C
At 24V, 20A and 25°C
At 24V, 20A and 40°C;
Ground Benign GB40
At 24V, 20A and 25°C;
Ground Benign GB25
At 24V, 20A and 40°C;
Ground Fixed GF40
At 24V, 20A and 25°C;
Ground Fixed GF25
May 2020 / Rev 0.1 DS-CP20.248-EN All parameters are typical values specified 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
17/33
CP20.248
24V, 20A, 480W, S INGLE P HASE CP-Series
18.
EMC
The EMC behavior of the device is designed for applications in industrial environment as well as in residential, commercial and light industry environments.
The device complies with EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 and EN 61000-3-3.
The device complies with FCC Part 15 rules. Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not suited to supply a local DC power network in residential, commercial and light-industrial environments. No restrictions apply for local DC power networks in industrial environments.
EMC Immunity
Electrostatic discharge
Electromagnetic RF field
Fast transients (Burst)
Surge voltage on input
Surge voltage on output
Conducted disturbance
Mains voltage dips
Voltage interruptions
Powerful transients
Power lines and housing
EN 61000-4-2 Contact discharge
Air discharge
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
80MHz-2.7GHz
2.7-6GHz
Input lines
Output lines
L → N
N → PE
L → PE
+ → -
+ → PE
- → PE
0.15-80MHz
0% of 100Vac
40% of 100Vac
70% of 100Vac
0% of 120Vac
40% of 120Vac
70% of 120Vac
0% of 200Vac
40% of 200Vac
70% of 200Vac
EN 61000-4-11
VDE 0160
0V
Over entire load range
8kV
15kV
20V/m
10V/m
4kV
2kV
2kV
4kV
4kV
1kV
2kV
2kV
10V
0Vac, 20ms
40Vac, 200ms
70Vac, 500ms
0Vac, 20ms
48Vac, 200ms
84Vac, 500ms
0Vac, 20ms
80Vac, 200ms
140Vac, 500ms
5000ms
750V, 0.3ms
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion C
Criterion A
Criterion A
Criterion A
Criterion A
Criterion C
Criterion A
EMC Immunity Signal and communication lines
Fast transients (Burst)
Surge voltage
EN 61000-4-4
EN 61000-4-5
Signals with coupling clamp
DC OK, Alarm contact → PE
2kV
1kV
Criterion A
Criterion A
Performance criterions:
A: Device shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. The device may shut-down and restarts by itself. No damage or hazards for the device will occur.
May 2020 / Rev 0.1 DS-CP20.248-EN All parameters are typical values specified 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
18/33
CP-Series
EMC Emission
Conducted emission input lines
Conducted emission output lines
Radiated emission
Harmonic input current
Voltage fluctuations, flicker
EN 55011, EN 55032, FCC Part 15, CISPR 11, CISPR
32
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
EN 55011, EN 55032, CISPR 11, CISPR 32
EN 61000-3-2 - Class A equipment
EN 61000-3-2 - Class C equipment
EN 61000-3-3
Switching Frequencies
PFC converter
Main converter
Auxiliary converter
Microcontroller
100kHz
80kHz to 140kHz
60kHz
8MHz, 8MHz, 32MHz
CP20.248
24V, 20A, 480W, S INGLE P HASE
Class B
Limits for local DC power networks not fulfilled.
Class B
Fulfilled
Fulfilled in the load range from 8 to 24A
Fulfilled, tested with non-pulsing constant current loads.
Fixed frequency
Output load dependent
Fixed frequency
The device utilize in total 3 microcontrollers
May 2020 / Rev 0.1 DS-CP20.248-EN All parameters are typical values specified 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
19/33
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 4 Installation Instructions
- 5 AC-Input
- 6 DC-Input
- 6 Input Inrush Current
- 7 Output
- 9 Hold-up Time
- 9 DC OK Relay Contact
- 10 Power Supply Condition Display
- 12 Remote ON / OFF Function
- 13 Efficiency and Power Losses
- 14 Functional Diagram
- 15 Front Side and User Elements
- 16 Connection Terminals
- 17 Lifetime Expectancy
- 20 Environment
- 21 Safety and Protection Features
- 22 Dielectric Strength
- 23 Approvals
- 23 Regulatory Compliance
- 24 Physical Dimensions and Weight
- 25 Accessories
- 25 Wall/Panel Mount Bracket
- 26 UF20.241 Buffer Module
- 26 YR40.241 - Redundancy Module
- 26 YR40.242 - Redundancy Module
- 27 YR40.245 - Redundancy Modules
- 28 Application Notes
- 28 Peak Current Capability
- 29 Output Circuit Breakers
- 30 Charging of Batteries
- 30 Series Operation
- 30 Parallel Use to Increase Output Power
- 31 Parallel Use for Redundancy
- 32 Operation on Two Phases
- 32 Use in a Tightly Sealed Enclosure
- 33 Mounting Orientations