CP-Series
19.
E
NVIRONMENT
Operational temperature
Storage temperature
Output de-rating
Humidity
Atmospheric pressure
Altitude
Overvoltage category
Impulse withstand voltage
Degree of pollution
Vibration sinusoidal
Shock
CP20.248
24V, 20A, 480W, S INGLE P HASE
-25°C to +70°C (-13°F to 158°F) The operational temperature is the ambient or surrounding temperature and is defined as the air temperature 2cm below the device.
For storage and transportation -40°C to +85°C (-40°F to 185°F)
6.4W/°C
12W/°C
1.33A/1000m or 5°C/1000m
Between +45°C and +60°C (113°F to 140°F)
Between +60°C and +70°C (140°F to 158°F)
For altitudes >2000m (6560ft), see Fig. 19-2
The de-rating is not hardware controlled. The user has to take care by him-self to stay below the derated current limits in order not to overload the unit.
5 to 95% r.h.
110-54kPa
Up to 5000m (16 400ft)
II
According to IEC 60068-2-30
According to IEC 60664-1, for altitudes up to 5000m
4kV (according to overvoltage category III)
2
Input to PE
According to IEC 60664-1, for altitudes up to 2000m
2-17.8Hz: ±1.6mm
17.8-500Hz: 2g
2 hours / axis
30g 6ms, 20g 11ms
3 bumps / direction
18 bumps in total
According to IEC 60664-1, not conductive
According to IEC 60068-2-6
According to IEC 60068-2-27
Shock and vibration is tested in combination with DIN-Rails according to EN 60715 with a height of
15mm and a thickness of 1.3mm and standard orientation.
Fig. 19-1 Output current vs. ambient temp.
Allowed Output Current at 24V
24A
20A
15A
A...90 to 264Vac, continuous
B... short term
(max. 60s every 10 minutes)
B
A
Fig. 19-2 Output current vs. altitude
Allowed Output Current at 24V
24A
20A
16A
C
B
A
A... Tamb < 60°C
B... Tamb < 45°C
C... Short term
0
-25 0 45 60 70°C
Ambient Temperature
Altitude
AP *)
0m
110kPa
*) Atmospheric pressure
2000m
80kPa
5000m
54kPa
May 2020 / Rev 0.1 DS-CP20.248-EN All parameters are typical values specified 230Vac, 50Hz input voltage, 24V, 20A output load,
25°C ambient and after a 5 minutes run-in time unless otherwise noted. www.pulspower.com Phone +49 89 9278 0 Germany
20/33
advertisement
Related manuals
advertisement
Table of contents
- 3 Intended Use
- 4 Installation Instructions
- 5 AC-Input
- 6 DC-Input
- 6 Input Inrush Current
- 7 Output
- 9 Hold-up Time
- 9 DC OK Relay Contact
- 10 Power Supply Condition Display
- 12 Remote ON / OFF Function
- 13 Efficiency and Power Losses
- 14 Functional Diagram
- 15 Front Side and User Elements
- 16 Connection Terminals
- 17 Lifetime Expectancy
- 20 Environment
- 21 Safety and Protection Features
- 22 Dielectric Strength
- 23 Approvals
- 23 Regulatory Compliance
- 24 Physical Dimensions and Weight
- 25 Accessories
- 25 Wall/Panel Mount Bracket
- 26 UF20.241 Buffer Module
- 26 YR40.241 - Redundancy Module
- 26 YR40.242 - Redundancy Module
- 27 YR40.245 - Redundancy Modules
- 28 Application Notes
- 28 Peak Current Capability
- 29 Output Circuit Breakers
- 30 Charging of Batteries
- 30 Series Operation
- 30 Parallel Use to Increase Output Power
- 31 Parallel Use for Redundancy
- 32 Operation on Two Phases
- 32 Use in a Tightly Sealed Enclosure
- 33 Mounting Orientations