Modes
This section describes the Inverter's modes and switching between modes.
Inverter Modes
The Inverter's user constants and monitoring functions are organized in groups called modes that make it easier to read and set user constants.The Inverter is equipped with 5 modes.
The 5 modes and their primary functions are shown in the Table 3.2
.
Drive mode
Mode
Quick programming mode
Table 3.2 Modes
Primary function(s)
The Inverter can be run in this mode.
Use this mode when monitoring values such as frequency references or output current, displaying fault information, or displaying the fault history.
Use this mode to reference and set the minimum user constants to operate the
Inverter (e.g., the operating environment of the Inverter and Digital Operator).
Use this mode to reference and set all user constants.
Advanced programming mode
Verify mode
Autotuning mode*
Use this mode to read/set user constants that have been changed from their factoryset values.
Use this mode when running a motor with unknown motor constants in the vector control method. The motor constants are calculated and set automatically.
This mode can also be used to measure only the motor line-to-line resistance.
* Always perform autotuning with the motor before operating using vector control. Autotuning mode will not be displayed during operation or when an error has occurred. The factory setting of the Inverter is A1-02 = 0 for V/f control.
Modes
Switching Modes
The mode selection display will appear when the MENU Key is pressed from a monitor or setting display.
Press the MENU Key from the mode selection display to switch between the modes.
Press the DATA/ENTER Key from the mode selection key to monitor data and from a monitor display to access the setting display.
MENU Power ON
Drive Mode
DATA
ENTER
ESC
DRIVE QUICK ADV VERIFYA.TUNE
Quick
Programming Mode
MENU
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
(Operation possible)
DATA
ENTER
ESC
DRIVE QUICK ADV VERIFYA.TUNE
Advanced
Programming Mode
MENU
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
ESC
DRIVE QUICK ADV VERIFYA.TUNE
DATA
ENTER
DATA
ENTER
ESC ESC
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
MENU
Verify Mode DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
Autotuning
Mode
MENU
ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
If a user constant is changed the number will be dislayed.
DATA
ENTER
When returning from a setting display, the rightmost digit of the monitor display will flash.
DATA
ENTER
ESC ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
Mode Selection Displays
Lit
Monitor Displays
Flashing Not lit
Fig 3.3 Mode Transitions
Setting Displays
IMPORTANT
When running the Inverter after using Digital Operator, press the MENU Key to enter the drive mode (DRIVE indicator will flash) and then press the DATA/ENTER Key from the drive mode display to bring up the monitor display (DRIVE indicator will light). Run Commands can't be received from any other display. (Monitor display in the drive mode will appear when the power is turned ON.)
3-
5
3
-6
Drive Mode
Drive mode is the mode in which the Inverter can be operated. The following monitor displays are possible in drive mode: The frequency reference, output frequency, output current, and output voltage, as well as fault information and the fault history.
When b1-01 (Reference selection) is set to 0, the frequency can be changed from the frequency setting display.
Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be written and the monitor display will be returned to when the DATA/ENTER Key is pressed after changing the setting.
Example Operations
Key operations in drive mode are shown in the following figure.
Mode Selection Display
MENU
Monitor Constant Display
Power ON
Detailed Monitor Constant
Display
Monitor Display
Drive Mode
DRIVE QUICK ADV VERIFYA.TUNE
DATA
ENTER
Frequency reference
ESC
DATA
ENTER
Frequency reference setting/ display unit o1-03
ESC
ESC
Output frequency
Output current
ESC
ESC
Monitor setting for o1-01
ESC
Status Monitor
RESET
Frequency reference
DATA
ENTER
ESC
ESC
Fan operating time
DATA
ENTER
ESC
ESC
Error Trace
RESET
Current error
DATA
ENTER
ESC
ESC
Operating time at error DATA
ENTER
ESC
ESC
ESC
Fault History
RESET
1st previous error
ESC
Operating time at 4th previous error
ESC
DATA
ENTER
ESC
DATA
ENTER
ESC
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
Fig 3.4 Operations in Drive Mode
IMPORTANT
The display for the first monitor constant (frequency reference) will be displayed when power is turned ON.
The monitor item displayed at startup can be set in o1-02 (Monitor Selection after Power Up).
Operation cannot be started from the mode selection display.
Modes
Quick Programming Mode
In quick programming mode, the constants required for Inverter trial operation can be monitored and set.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
Refer to Chapter 5 User Constants for details on the constants displayed in quick programming mode.
Example Operations
Key operations in quick programming mode are shown in the following figure.
Monitor Display Setting Display Mode Selection Display
MENU
Quick Programming Mode
DRIVE QUICK ADV VERIFYA.TUNE
DATA
ENTER
Control method selection DATA
ENTER
ESC
ESC
ESC
Reference selection
DATA
ENTER
ESC
Operation method selection
DATA
ENTER
ESC ESC
Stopping method selection
DATA
ENTER
ESC
C1-01: Acceleration time 1
C1-02: Deceleration time 1
C6-01: CT/VT selection
C6-02: Carrier frequency
selection d1-01: Frequency reference 1 d1-02: Frequency reference 2 d1-03: Frequency reference 3 d1-04: Frequency reference 4 d1-17: Jog frequency reference
E1-01: Input voltage setting
E1-03: V/f pattern selection
E1-04: Max. output frequency
E1-05: Max. voltage
E1-06: Base frequency
E1-09: Min. output frequency
E1-13: Base voltage (VBASE)
E2-01: Motor rated current
AO CH1 output gain
DATA
ENTER
ESC
ESC
ESC
AO CH2 output gain
DATA
ENTER
ESC
Motor protection selection
DATA
ENTER
ESC
ESC
Deceleration stall selection
DATA
ENTER
ESC ESC
DRIVE QUICK ADV VERIFYA.TUNE
Fig 3.5 Operations in Quick Programming Mode
3-
7
3
-8
Advanced Programming Mode
In advanced programming mode, all Inverter constants can be monitored and set.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
Refer to Chapter 5 User Constants for details on the constants.
Example Operations
Key operations in advanced programming mode are shown in the following figure.
Mode Selection Display
MENU
DATA
ENTER
Advanced Programming Mode
Function Selection Display
Setup settings: A1-xx
RESET
Monitor Display Setting Display
DRIVE QUICK ADV VERIFYA.TUNE
ESC
Language DATA
ENTER
ESC
ESC
Access level DATA
ENTER
ESC
ESC
Control mode selection DATA
ENTER
ESC
ESC
ESC
PID control: b5-xx
RESET
PID control mode selection
DATA
ENTER
ESC
ESC
Proportional gain
DATA
ENTER
ESC
ESC
PID feedback command loss detection time DATA
ENTER
ESC
ESC
ESC
Torque limits: L7-xx
RESET
Forward torque limit
ESC
Reverse torque limit DATA
ENTER
ESC
ESC
Reverse regenerative torque limit DATA
ENTER
ESC
ESC
DATA
ENTER
ESC
ESC
Copy functions: o3-xx
RESET
DRIVE QUICK ADV VERIFYA.TUNE
Copy function selection
DATA
ENTER
ESC
ESC
Read permitted selection DATA
ENTER
ESC
ESC
DRIVE QUICK ADV VERIFYA.TUNE
DRIVE QUICK ADV VERIFYA.TUNE
Fig 3.6 Operations in Advanced Programming Mode
Modes
9
10
11
Setting User Constants
Here, the procedure is shown to change C1-01 (Acceleration Time 1) from 10 s to 20 s.
Step
No.
Table 3.3 Setting User Constants in Advanced Programming Mode
Digital Operator Display Description
1 Power supply turned ON.
2
3
4
5
6
7
8
MENU Key pressed to enter drive mode.
MENU Key pressed to enter quick programming mode.
MENU Key pressed to enter advanced programming mode.
DATA/ENTER pressed to access monitor display.
Increment or Decrement Key pressed to display C1-01 (Acceleration Time 1).
DATA/ENTER Key pressed to access setting display. The setting of C1-01 (10.00) is displayed.
Shift/RESET Key pressed to move the flashing digit to the right.
Increment Key pressed to change set value to
20.00 s.
DATA/ENTER Key pressed to enter the set data. “END” is displayed for 10 s and then the entered value is displayed for 0.5 s.
The monitor display for C1-01 returns.
3-
9
3
-10
Verify Mode
Verify mode is used to display any constants that have been changed from their default settings in a programming mode or by autotuning. “None” will be displayed if no settings have been changed.
Of the environment mode settings, only A1-02 will be displayed if it has been changed. Other environment modes settings will not be displayed even if they have been changed from their default settings.
Even in verify mode, the same procedures can be used to change settings as are used in the programming modes. Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be written and the monitor display will be returned to when the DATA/ENTER Key is pressed after changing the setting.
Example Operations
An example of key operations is given below for when the following settings have been changed from their default settings: b1-01 (Reference Selection), C1-01 (Acceleration Time 1), E1-01 (Input Voltage Setting), and
E2-01 (Motor Rated Current).
Mode Selection Display
MENU
Monitor Display Setting Display
Verify Mode
DRIVE QUICK ADV VERIFYA.TUNE
DATA
ENTER
Frequency reference selection
DATA
ENTER
ESC
Frequency reference selection
DATA
ENTER
ESC
Acceleration time 1 DATA
ENTER
ESC
Acceleration time 1
DATA
ENTER
ESC
Input voltage setting DATA
ENTER
ESC
Input voltage setting
DATA
ENTER
ESC
ESC
Motor rated current
DRIVE QUICK ADV VERIFYA.TUNE
Fig 3.7 Operations in Verify Mode
DATA
ENTER
ESC
Motor rated current
DRIVE QUICK ADV VERIFYA.TUNE
DATA
ENTER
Modes
Autotuning Mode
Autotuning automatically tunes and sets the required motor constants when operating in the vector control method. Always perform autotuning before starting operation.
When V/f control has been selected, stationary autotuning for only line-to-line resistance can be selected.
When the motor cannot be disconnected from the load, perform stationary autotuning. Contact your Yaskawa representatives to set motor constants by calculation.
The Inverter's autotuning function automatically determines the motor constants, while a servo system's autotuning function determines the size of a load, so these autotuning functions are fundamentally different.
The factory setting of the Inverter is A1-02 = 0 for V/f control.
Example of Operation
Set the motor output power (in kW), rated voltage, rated current, rated frequency, rated speed, and number of poles specified on the nameplate on the motor and then press the RUN Key. The motor is automatically run and the motor constants measured based on these settings and autotuning will be set.
Always set the above items. Autotuning cannot be started otherwise, e.g., it cannot be started from the motor rated voltage display.
Constants can be changed from the setting displays. Use the Increment, Decrement, and Shift/RESET Keys to change the frequency. The user constant will be written and the monitor display will be returned to when the
DATA/ENTER Key is pressed after changing the setting.
The following example shows autotuning for open-loop vector control while operating the motor without switching to motor 2.
3-
11
3
-12
Autotuning
MENU
DRIVE QUICK ADV VERIFYA.TUNE
Autotuning Monitor Display
Tuning mode
ESC
Motor output power
ESC
Motor rated voltage
ESC
Motor rated current
ESC
Motor base frequency
ESC
No. of motor poles
ESC
Motor base speed
Setting Display
Tuning mode: rotational tuning DATA
ENTER
DATA
ENTER
ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
Motor output power
DATA
ENTER
ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
Motor rated voltage
DATA
ENTER
ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
Motor rated current
DATA
ENTER
ESC
DATA
ENTER
ESC
DRIVE QUICK ADV VERIFYA.TUNE
Motor base frequency
DATA
ENTER
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
No. of motor poles
DATA
ENTER
ESC
DATA
ENTER
DRIVE QUICK ADV VERIFYA.TUNE
Motor base speed
DATA
ENTER
ESC
ESC
Autotuning start*
RUN
DRIVE QUICK ADV VERIFYA.TUNE
Autotuning Stop command input
ESC
DRIVE QUICK ADV VERIFYA.TUNE
Autotuning completed
DRIVE QUICK ADV VERIFYA.TUNE
* TUn10 will be displayed during rotational autotuning and TUn11 will be displayed during stationary autotuning. The DRIVE indicator will light when autotuning starts.
Fig 3.8 Operation in Autotuning Mode
IMPORTANT
If a fault occurs during autotuning, refer to Chapter 7 Troubleshooting.
Trial Operation
This chapter describes the procedures for trial operation of the Inverter and provides an example of trial operation.
Trial Operation Procedure............................................4-2
Trial Operation Procedures..........................................4-3
Adjustment Suggestions ............................................4-18