User Constant Tables. YASKAWA Varispeed f7
Oglas
Oglas
5
-8
User Constant Tables
A: Setup Settings
The following settings are made with the environment constants (A constants): Language displayed on the
Digital Operator, access level, control method, initialization of constants.
Initialize Mode: A1
User constants for the environment modes are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
A1-00
A1-01
Language selection for
Digital
Operator display
Used to select the language displayed on the Digital
Operator (LED).
0: English
1: Japanese
2: German
3: French
4: Italian
5: Spanish
6: Portuguese
This constant is not initialized by the initialize operation.
Constant access level
Used to set the constant access level (set/read.)
0: Monitoring only
(Monitoring drive mode and setting A1-01 and
A1-04.)
1: Used to select user constant
(Only constants set in
A2-01 to A2-32 can be read and set.)
2: Advanced
(Constants can be read and set in both quick programming mode and advanced programming
(A) mode.)
0 to 6
0 to 2
1
2
Yes A
Yes A
A
A
A
A
A 100H -
A 101H
4-17
6-154
A1-02
Control method selection
Used to select the control method for the Inverter
0: V/f control
1: V/f with PG
2: Open loop vector
3: Flux vector
This constant is not initialized by the initialize operation.
0 to 2
0 to 3
0 No Q Q Q Q 102H
4-5
4-7
4-18
User Constant Tables
Constant
Number
Name
A1-03 Initialize
A1-04 Password
A1-05
Password setting
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Used to initialize the constants using the specified method.
0: No initializing
1110: Initializes using the
User constants
2220: Initializes using a two-wire sequence.
(Initializes to the factory setting.)
3330: Initializes using a three-wire sequence.
Password input when a password has been set in A1-05.
This function write-protects some constants of the initialize mode.
If the password is changed,
A1-01 to A1-03 and A2-01 to A2-32 constants can no longer be changed. (Programming mode constants can be changed.)
Used to set a four digit number as the password.
This constant is not usually displayed. When the Password (A1-04) is displayed, hold down the RESET Key and press the Menu Key and the password will be displayed.
0 to
3330
0 to
9999
0 to
9999
0
0
0
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
103H
104H
105H
-
4-17
6-155
4-17
6-155
User-set Constants: A2
The constants set by the user are listed in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
A2-01 to
A2-32
User setting constants
Used to set the constant numbers that can be set/read.
Maximum 32.
Effective when the Constant
Access Level (A1-01) is set to User Program (1). Constants set in constants A2-01 to A2-32 can be set/read in programming mode.
b1-01 to o3-02
No A A A A
MEMO
BUS
Register
Page
106H to
125H
6-155
5-
9
5
-10
Application Constants: b
The following settings are made with the application constants (B constants): Operation method selection, DC injection braking, speed searching, timer functions, dwell functions, DROOP functions, energy saving functions, and zero-servo.
Operation Mode Selections: b1
User constants for operation mode selection are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page b1-01
Reference selection b1-02
Operation method selection b1-03
Stopping method selection
Set the frequency reference input method.
0: Digital Operator
1: Control circuit terminal
(analog input)
2: MEMOBUS communications
3: Option board
4: Pulse train input
Set the Run Command input method.
0: Digital Operator
1: Control circuit terminal
(sequence input)
2: MEMOBUS communications
3: Option board
0 to 4
0 to 3
Used to set the stopping method used when a Stop
Command is input.
0: Deceleration to stop
1: Coast to stop
2: DC injection braking stop
(Stops faster than coast to stop, no regenerative operation.)
3: Coast to stop with timer
(Run Commands are disregarded during deceleration.)
0 to 3 *
1
1
0
No
No
No
Q
Q
Q
Q
Q
Q
Q
Q
Q
Q 180H
Q 181H
Q 182H
4-5
6-6
6-78
6-97
4-5
6-15
6-78
6-97
4-6
6-17 b1-04
Prohibition of reverse operation
0: Reverse enabled
1: Reverse disabled
0 or 1 0 No A A A A 183H 6-65
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page b1-05 b1-06 b1-07 b1-08
Operation selection for setting E1-
09 or less
Used to set the method of operation when the frequency reference input is less than the minimum output frequency (E1-09).
0: Run at frequency reference (E1-09 not effective).
1: STOP (Frequencies below E1-09 in the coast to stop state.)
2: Run at min. frequency.
(E1-09)
3: Run at zero-speed (Frequencies below E1-09 are zero)
Read sequence input twice
Used to set the responsiveness of the control inputs
(forward/reverse and multifunction inputs.)
0: Two scans every 2 ms
(Use for fast responses.)
1: Two scans every 5 ms
(Use for possible malfunction due to noise.)
Operation selection after switching to remote mode
Used to set the operation mode by switching to the
Remote mode using the
Local/Remote Key.
0: Run signals that are input during mode switching are disregarded. (Input
Run signals after switching the mode.)
1: Run signals become effective immediately after switching to the
Remote mode.
Run Command selection in programming modes
Used to set an operation interlock in programming modes.
0: Cannot operate.
1: Can operate (Disabled when Digital Operator is set to select Run Command (when b1-02 = 0)).
2: Cannot operate. (Cannot be in programming mode during operation.)
* 0 or 1 for flux vector control.
0 to 3
0 or 1
0 or 1
0 to 1
0 to 2
0
1
0
0
No
No
No
No
No
A
A
A
No
A
A
A
No
A
A
A
A
A
A
A
184H 6-17
185H
186H
187H -
-
-
5-
11
5
-12
DC Injection Braking: b2
User constants for injection braking are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b2-01
Zero-speed level (DC injection braking starting frequency) b2-02
DC injection braking current b2-03
DC injection braking time at start b2-04
DC injection braking time at stop
Used to set the frequency which starts DC injection braking in units of Hz when deceleration to stop is selected.
When b2-01 is less than E1-
09, E1-09 is used to set the starting frequency for the
DC injection braking.
In flux vector control, b2-01 is used to set the starting frequency for the zero-speed control.
Sets the DC injection braking current as a percentage of the Inverter rated current.
The DC injection braking current in flux control is affected by any change to the setting of E2-03.
Used to set the time to perform DC injection braking at start in units of 1 second.
Used to stop coasting motor and restart it. When the set value is 0, DC injection braking at start is not performed.
Used to set the time to perform DC injection braking at stop (zero-speed control in flux vector control) in units of 1 second.
Used to prevent coasting after the Stop Command is input. When the set value is
0.00, DC injection braking at stop is not performed.
0.0 to
10.0
0 to
100
0.00
to
10.00
0.00
to
10.00
0.5 Hz No
50% No
0.00 s No
0.50 s No
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
A 189H
6-17
6-144
A No 18AH
A
A
A 18BH
6-18
6-22
6-18
6-22
A 18CH 6-18 b2-08
Magnetic flux compensation volume
Sets the magnetic flux compensation as a percentage of the no-load current.
0 to
1000
0% No No No A A 190H -
User Constant Tables
Speed Search: b3
User constants for the speed search are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b3-01
Speed search selection
(current detection or speed calculation)
Enables/disables the speed search function for the Run
Command and sets the speed search method.
0:Disabled, speed calculation
1: Enabled, speed calculation
2: Disabled, current detection
3: Enabled, current detection
Speed Calculation:
When the search is started, the motor speed is calculated and acceleration/ deceleration is performed from the calculated speed to the specified frequency
(motor direction is also searched).
0 to 3 2
*1 No A A
MEMO
BUS
Register
Page
A No 191H 6-68 b3-02 b3-03
Speed search deceleration time
(current detection)
Current Detection:
The speed search is started from the frequency when power was momentarily lost and the maximum frequency, and the speed is detected at the search current level.
Speed search operating current (current detection)
Sets the speed search operation current as a percentage, taking the Inverter rated current as 100%.
Not usually necessary to set.
When restarting is not possible with the factory settings, reduce the value.
Sets the output frequency deceleration time during speed search in 1-second units.
Set the time for deceleration from the maximum output frequency to the minimum output frequency.
0 to
200
0.1 to
10.0
120%
*1
2.0 s
No
No
A No A No 192H 6-68
A No A No 193H 6-68
5-
13
5
-14
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page b3-05 b3-10 b3-14 b3-17 b3-18 b3-19
Speed search wait time (current detection or speed calculation)
Sets the magnetic contactor operating delay time when there is a magnetic contactor on the output side of the
Inverter. When a speed search is performed after recovering from a momentary power loss, the search operation is delayed by the time set here.
Sets the magnetic flux compensation as a percentage of the noload current.
Operation restarts at a speed obtained by multiplying the speed from the speed search by the compensation gain
(excitation search only.)
Increase this setting if overvoltages occur when a speed search is performed after a long baseblock, for example, in searches at startup.
Rotation direction search selection
Speed search retrial current level
Speed search retrial detection time
0: Disabled (operates with specified rotation direction)
1: Enabled (operates with rotation direction found by search)
Sets the current level to retry a speed search as a percentage, taking the Inverter rated current as 100%.
Sets the time for detection in a speed search retrial in units of seconds.
Number of speed search retrials
Sets the number of times that a speed search can be retried.
0.0 to
20.0
1.00 to
1.20
0 or 1
0 to
200
0.00 to
1.00
0 to 10
0.2 s
1.10
1
150%
*2
No
No
No
No
0.01 s No
0 No
A
A
A
A
A
A
A
No
A
No
No
No
* 1. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 2. When C6-01 = 1, the upper limit is 120 %.
A
A
A
A
A
A
A 195H 6-68
No 19AH 6-68
No
No
No
No
19EH 6-69
1F0H 6-69
1F1H 6-69
1F2H 6-69
User Constant Tables
Timer Function: b4
User constants for timer functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b4-01 b4-02
Timer function ONdelay time
Timer function OFFdelay time
Sets the timer function output ON-delay time (dead band) for the timer function input, in 1-second units.
Enabled when a timer function is set in H1 or H2-
.
Sets the timer function output OFF-delay time (dead band) for the timer function input, in 1-second units.
Enabled when a timer function is set in H1 or H2-
.
0.0 to
300.0
0.0 to
300.0
0.0 s
0.0 s
No
No
A
A
A
A
A
A
MEMO
BUS
Register
Page
A 1A3H 6-107
A 1A4H 6-107
PID Control: b5
User constants for PID control are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b5-01 b5-02 b5-03 b5-04 b5-05
PID control method selection
Proportional gain
(P)
Integral (I) time
Integral (I) limit
Derivative
(D) time
0: Disabled
1: Enabled (Deviation is Dcontrolled.)
2: Enabled (Feedback value is D-controlled.)
3: PID control enabled
(frequency reference +
PID output, D control of deviation)
4: PID control enabled
(frequency reference +
PID output, D control of feedback value).
Sets P-control proportional gain as a percentage.
P-control is not performed when the setting is 0.00.
Sets I-control integral time in 1-second units.
I-control is not performed when the setting is 0.0.
Sets the I-control limit as a percentage of the maximum output frequency.
Sets D-control derivative time in 1-second units.
D-control is not performed when the setting is 0.00.
0 to 4
0.00
to
25.00
0.0 to
360.0
0.0 to
100.0
0.00 to
10.00
0
1.00
1.0 s
100.0% Yes A
0.00 s
No
Yes
Yes
Yes
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
1A5H 6-109
1A6H 6-109
1A7H 6-109
1A8H 6-109
1A9H 6-109
5-
15
5
-16
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation b5-06 PID limit b5-07 b5-08 b5-09
PID output characteristics selection
Sets the limit after PID-control as a percentage of the maximum output frequency.
PID offset adjustment
Sets the offset after PID-control as a percentage of the maximum output frequency.
PID primary delay time constant
Sets the time constant for low pass filter for PID-control outputs in 1-second units.
Not usually necessary to set.
Select forward/reverse for
PID output.
0: PID output is forward.
1: PID output is reverse
(highlights the output code)
0.0 to
100.0
-100.0
to
+100.0
0.00 to
10.00
0 or 1
100.0% Yes A
0.0%
0.00 s
0
Yes
Yes
No
A
A
A
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
A
A
A
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
1AAH 6-109
1ABH 6-109
1ACH 6-109
1ADH 6-109 b5-10 b5-11 b5-12 b5-13 b5-14
PID output gain
Selection of
PID feedback command loss detection
Sets output gain.
PID reverse output selection
0: 0 limit when PID output is negative.
1: Reverses when PID output is negative.
0 limit when reverse prohibit is selected using b1-04.
0: No detection of loss of
PID feedback.
1: Detection of loss of PID feedback.
Operation continues during detection, with the malfunctioning contact not operating.
2: Detection of loss of PID feedback.
Coasts to stop during detection, and fault contact operates.
PID feedback command loss detection level
PID feedback command loss detection time
Sets the PID feedback loss detection level as a percent units, with the maximum output frequency at 100%.
Sets the PID feedback loss detection level in s units.
0.0 to
25.0
0 or 1
0 to 2
0 to
100
0.0 to
25.5
1.0
0
0
0%
1.0 s
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
1AEH 6-109
1AFH 6-109
1B0H 6-110
1B1H 6-110
1B2H 6-110 b5-15
PID sleep function operation level
Set the PID sleep function start level as a frequency.
0.0 to
400.0
*1
0.0 to
300.0
*2
0.0 Hz No A A A A 1B3H 6-110
User Constant Tables
Constant
Number
Name Description b5-16
PID sleep operation delay time
Set the delay time until the
PID sleep function starts in seconds.
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
0.0 to
25.5
b5-17
Accel/decel time for PID reference
Set the accel/decel time for
PID reference in seconds.
0.0 to
25.5
0.0 to
6000.0
0.0 s
0.0 s
No
No
A
A
A
A
A
A
A
A
1B4H 6-110
1B5H 6-110
Dwell Functions: b6
User constants for dwell functions are shown in the following table.
Constant
Number b6-01 b6-02 b6-03
Name
Dwell frequency at start
Description
Dwell time at start
Run Command
Output frequency
ON
OFF b6-01 b6-03 Time
Dwell frequency at stop b6-02 b6-04
The dwell function is used to output frequency temporarily when driving a motor with a heavy load.
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
0.0 to
400.0
*1
0.0 Hz No A A A A 1B6H
0.0 to
300.0
*2
Page
4-20
6-29
0.0 to
10.0
0.0 to
400.0
*1
0.0 to
300.0
*2
0.0 s
0.0 Hz
No
No
A
A
A
A
A
A
A
A
1B7H
1B8H
4-20
6-29
4-20
6-29 b6-04
Dwell time at stop
0.0 to
10.0
0.0 s No A A A A 1B9H
4-20
6-29
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
5-
17
5
-18
Droop Control: b7
User constants for droop functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b7-01
Droop control gain b7-02
Droop control delay time
Sets the slip as a percentage of maximum frequency when the maximum output frequency is specified and the rated torque occurs.
Droop-control is not performed when the setting is
0.0.
Droop control responsiveness constant
When hunting or oscillation occurs, increase the value.
0.0 to
100.0
0.03 to
2.00
0.0
MEMO
BUS
Register
Page
Yes No No No A 1CAH
4-20
6-143
0.05 s Yes No No No A 1CBH
4-20
6-143
Energy Saving: b8
User constants for energy-saving control functions are shown in the following table.
Constant
Number b8-01 b8-02 b8-03 b8-04 b8-05
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Energy-saving mode selection
Select whether to enable or disable energy-saving control.
0: Disable
1: Enable
Energy-saving gain
Set the energy-saving gain with the vector control method.
Energy-saving filter time constant
Set the energy-saving filter time constant with the vector control method.
Energy-saving coefficient
Set the maximum motor efficiency value.
Set the motor rated capacity in E2-11, and adjust the value by 5% at a time until output power reaches a minimum value.
Power detection filter time constant
Set the time constant for output power detection.
0 or 1
0.0 to
10.0
0.00 to
10.00
0.0 to
655.00
0 to
2000
0
0.7
*1
0.50 s
*2
288.20
*3
*4
20 ms
No
Yes
Yes
No
No
A
No
No
A
A
A
No
No
A
A
A
A
A
No
No
A
A
A
1CCH 6-117
1CDH 6-117
1CEH 6-117
No 1CFH 6-117
No 1D0H 6-117
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page b8-06
Search operation voltage limiter
Set the limit value of the voltage control range during search operation.
Perform search operation to optimize operations using minute variations in voltage using energy-saving control.
Set to 0 to disable the search operation. 100% is the motor base voltage.
0 to
100
0% No A A
* 1. The factory setting is 1.0 when using flux vector control.
* 2. The factory setting is 2.00 s when Inverter capacity is 55 kW min.
The factory setting will change when the control method is changed. The open-loop vector factory setting is given.
* 3. By setting E2-11 (Motor rated output) the appropriate value will be set.
* 4. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
No No 1D1H 6-117
Zero-Servo: b9
User constants for zero-servo functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector b9-01
Zero-servo gain b9-02
Zero-servo completion width
Adjust the strength of the zero-servo lock.
Enabled when the “zeroservo command” is set for the multi-function input.
When the zero-servo command has been input and the frequency reference drop below excitation level (b2-
01), a position control loop is created and the motor stops. Increasing the zeroservo gain in turn increases the strength of the lock.
Increasing it by too much will cause oscillation.
Sets the output width of the zero-servo completion signal.
Enabled when the “zeroservo completion (end)” is set for a multi-function input. The zero-servo completion signal is ON when the current position is within the range (the zero-servo start position ± zero-servo completion width.)
Set the allowable position displacement from the zeroservo start position to 4 times the pulse rate of the
PG (pulse generator, encoder) in use.
0 to
100
0 to
16383
5
10
MEMO
BUS
Register
Page
No No No No A 1DAH 6-144
No No No No A 1DBH 6-144
5-
19
5
-20
Autotuning Constants: C
The following settings are made with the autotuning constants (C constants): Acceleration/deceleration times, s-curve characteristics, slip compensation, torque compensation, speed control, and carrier frequency functions.
Acceleration/Deceleration: C1
User constants for acceleration and deceleration times are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
C1-01
C1-02
C1-03
C1-04
C1-05
C1-06
C1-07
C1-08
Acceleration time 1
Deceleration time 1
Acceleration time 2
Deceleration time 2
Acceleration time 3
Deceleration time 3
Acceleration time 4
Deceleration time 4
C1-09
Emergency stop time
Sets the acceleration time to accelerate from 0 to the maximum output frequency, in 1second units.
Sets the deceleration time to decelerate from the maximum output frequency to 0, in 1-second units.
The acceleration time when the multi-function input
“accel/decel time 1” is set to
ON.
The deceleration time when the multi-function input
“accel/decel time 1” is set to
ON.
The acceleration time when the multi-function input
“accel/decel time 2” is set to
ON.
The deceleration time when the multi-function input
“accel/decel time 2” is set to
ON.
0.0 to
6000.0
*1
The acceleration time when the multi-function input
“accel/decel time 1” and
“accel/decel time 2” are set to ON.
The deceleration time when the multi-function input
“accel/decel time 1” and
“accel/decel time 2” are set to ON.
The deceleration time when the multi-function input
“Emergency (fast) stop” is set to ON.
This function can be used as a stopping method when a fault has been detected.
10.0 s
Yes Q
Yes Q
Yes A
Yes A
No
No
No
No
No
A
A
A
A
A
Q
Q
A
A
A
A
A
A
A
Q
Q
A
A
A
A
A
A
A
Q 200H
Q 201H
A 202H
A 203H
A 204H
A 205H
A 206H
A 207H
A 208H
4-5
4-20
6-25
4-5
4-20
6-25
4-20
6-25
4-20
6-25
4-20
6-25
4-20
6-25
4-20
6-25
4-20
6-25
4-20
6-24
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
C1-10
Accel/decel time setting unit
0: 0.01-second units
1: 0.1-second units
0 or 1 1 No A A A A 209H
4-20
6-25
6-26
C1-11
Accel/decel time switching frequency
Sets the frequency for automatic acceleration/deceleration switching.
Below set frequency: Accel/ decel time 4
Above set frequency: Accel/ decel time 1
The multi-function input
“accel/decel time 1” or
“accel/decel time 2” take priority.
0.0 to
400.0
*2
0.0 to
300.0
*3
0.0 Hz No A A A A 20AH
4-20
6-25
* 1. The setting range for acceleration/deceleration times will depends on the setting for C1-10. When C1-10 is set to 0, the setting range for acceleration/ deceleration times becomes 0.00 to 600.00 seconds.
* 2. When C6-01=0, the upper limit is 150.0.
* 3. When C6-01=1, the upper limit is 400.0.
S-curve Acceleration/Deceleration: C2
User constants for S-curve characteristics are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
C2-01
C2-02
C2-03
S-curve characteristic time at acceleration start
S-curve characteristic time at acceleration end
All sections of the S-curve characteristic time are set in seconds units.
When the S-curve characteristic time is set, the accel/decel times will increase by only half of the S-curve characteristic times at start and end.
S-curve characteristic time at deceleration start
Run Command
Output frequency
ON
C2-02
C2-01
OFF
C2-03
C2-04
Time
C2-04
S-curve characteristic time at deceleration end
0.00 to
2.50
0.20 s No
0.00 to
2.50
0.20 s No
0.00 to
2.50
0.20 s No
A A A A 20BH
A A A A 20CH
0.00 to
2.50
0.00 s No A A A A 20EH
4-20
6-26
4-20
6-26
A A A A 20DH
4-20
6-26
4-20
6-26
5-
21
5
-22
Motor Slip Compensation: C3
User constants for slip compensation are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
C3-01
C3-02
Slip compensation gain
Slip compensation primary delay time
C3-03
Slip compensation limit
Used to improve speed accuracy when operating with a load.
Usually setting is not necessary.
Adjust this constant at the following times.
• When actual speed is low, increase the set value.
• When actual speed is high, decrease the set value.
Used as the applicable control gain when using flux vector control.
Slip compensation primary delay time is set in ms units.
Usually setting is not necessary.
Adjust this constant at the following times.
• Reduce the setting when slip compensation responsive is slow.
• When speed is not stabilized, increase the setting.
Sets the slip compensation limit as a percentage of motor rated slip.
0.0 to
2.5
0 to
10000
0 to
250
0.0*
2000 ms
*
200%
Yes
No
No
A
A
A
No
No
No
A
A
A
A
No
No
20FH
210H
4-18
6-43
4-18
6-43
211H 6-43
C3-04
C3-05
Slip compensation selection during regeneration
0: Disabled.
1: Enabled.
When the slip compensation during regeneration function has been activated, as regeneration capacity increases momentarily, it may be necessary to use a braking option (braking resistor,
Braking Resistor Unit or
Braking Unit.)
Output voltage limit operation selection
0: Disabled.
1: Enabled. (The motor flux will be lowered automatically when the output voltage become saturated.)
0 or 1
0 or 1
0
0
No
No
A
No
* The factory setting will change when the control method is changed. The V/f control factory settings are given.
No
No
A
A
No
A
212H 6-43
213H 6-43
User Constant Tables
Torque Compensation: C4
User constants for are torque compensation shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
C4-01
Torque compensation gain
C4-02
Torque compensation primary delay time constant
Sets torque compensation gain as a ratio.
Usually setting is not necessary.
Adjust in the following circumstances:
• When the cable is long; increase the set value.
• When the motor capacity is smaller than the Inverter capacity (Max. applicable motor capacity), increase the set values.
• When the motor is oscillating, decrease the set values.
Adjust the output current range at minimum speed rotation so that it does not exceed the Inverter rated output current.
Do not alter the torque compensation gain from its default (1.00) when using the open loop vector control method.
The torque compensation delay time is set in ms units.
Usually setting is not necessary.
Adjust in the following circumstances:
• When the motor is oscillating, increase the set values.
• When the responsiveness of the motor is low, decrease the set values.
0.00 to
2.50
0 to
10000
1.00
200 ms
*
Yes
No
A
A
A
A
MEMO
BUS
Register
Page
A No 215H
A No 216H
4-18
6-46
4-18
6-46
C4-03
C4-04
Forward starting torque
Reverse starting torque
Sets the forward starting torque as a percentage of the motor rated torque.
Sets the reverse starting torque as a percentage of the motor rated torque.
-
0.0 to
200.0
200.0 to 0.0
0.0%
0.0%
No
No
No
No
No
No
A
A
No
No
217H
218H
C4-05
Starting torque time constant
Sets the delay time in ms for starting torque. The filter is disabled if the time is set to 0 to 4 ms.
0 to
200
10 ms No No
* The factory setting will change when the control method is changed. The V/f control factory setting is given.
No A No 219H -
-
-
5-
23
5
-24
Speed Control (ASR): C5
User constants for speed control are shown in the following table.
Constant
Number
Name
C5-01
ASR proportional
(P) gain 1
C5-02
ASR integral (I) time 1
Description
Sets the proportional gain of the speed loop (ASR.)
Sets the integral time of the speed loop (ASR) in 1-second units.
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
1.00 to
300.00
*1
20.00
*2
Yes No A No A 21BH
4-19
6-135
0.000 to
10.000
0.500
s
*2
Yes No A No A 21CH
4-19
6-135
C5-03
C5-04
C5-05 ASR limit
C5-06
C5-07
C5-08
ASR proportional
(P) gain 2
ASR integral (I) time 2
ASR primary delay time
ASR switching frequency
ASR integral (I) limit
Usually setting is not necessary.
Set to change the rotational speed gain.
1.00 to
300.00
*1
P I
0
P=C5-01
I=C5-02
P=C5-03
I=C5-04
E1-04 Motor speed (Hz)
0.000 to
10.000
Sets the upper limit for the compensation frequency for the speed control loop (ASR) to a percentage of the maximum output frequency.
0.0 to
20.0
Sets the filter time constant for outputting torque references from the speed control loop (ASR). It is set in 1-second units.
Usually setting is not necessary.
Sets the frequency for switching between Proportion Gain 1, 2 and
Integral Time 1, 2 in Hz units.
The multi-function input “ASR switching proportional gain” has the priority.
Sets the upper limit for the integral
(I) amount for the speed control loop (ASR) to a percentage of the rated load.
0.000 to
0.500
0.0 to
300.0
*3
0 to
400
20.00
*2
0.500
s
*2
5.0%
0.004 s
Yes
Yes
No
No
No
No
A
A
No
No
No
No
A
A
A
21DH
21EH
220H
4-19
6-136
4-19
6-136
4-19
6-136
0.0 Hz No No No No A 221H
4-19
6-136
400%
No
No
No
No
A
No
No
No
No 21FH 6-136
A 222H 6-136
* 1. When using V/f with PG control, 0.00 to 300.00. The flux vector setting ranges are given.
* 2. When the control method changes, the factory setting is changed. The flux vector control factory settings are given. Refer to Factory Settings that
Change with the Control Method (A1-02) .
* 3. When C6-01 = 1, the upper limit is 400.0.
User Constant Tables
Carrier Frequency: C6
User constants for the carrier frequency are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
C6-01
CT/VT selection
C6-02
Carrier frequency selection
0: CT (low carrier, constant torque,
150% per minute)
1: VT (high carrier, variable torque, 120% per minute)
Select carrier wave fixed pattern.
0: Low-noise PWM
1: 2.0 kHz
2: 5.0 kHz
3: 8.0 kHz
4: 10.0 kHz
5: 12.5 kHz
6: 15.0 kHz
F: Enables detailed settings using constants C6-03 to C6-05
0 or 1
0,1
(C6-
01=0)
0 to F
(C6-
01=1)
C6-03
*4
Carrier frequency upper limit
Set the carrier frequency upper limit and lower limit in kHz units.
The carrier frequency gain is set as follows:
With the vector control method, the upper limit of the carrier frequency is fixed in C6-03.
C6-04
*4
Carrier frequency lower limit
Carrier frequency
2.0 to
15.0
*3
2.0 to
2.5
0.4 to
15.0
*3
2.0 to
2.5
1
*1
0
6
1
*1
(C6-
01=0)
*2
(C6-
01=1)
15.0 kHz
*2
2.0 kHz
15.0 kHz
*2
2.0
kHz
No
No
No
No
Q
Q
A
A
Q
Q
A
A
Q
Q
A
No
Q
Q
A
A
223H
224H
225H
226H
4-5
4-20
6-2
4-6
4-18
4-19
6-2
6-2
6-2
C6-05
*4
Carrier frequency proportional gain
Output frequency x (C6-05) x K
Output frequency
(Max. output frequency)
K is a coefficient that depends on the setting of C6-03.
C6-03 ≥ 10.0 kHz: K = 3
10.0 kHz > C6-03 ≥ 5.0 kHz: K = 2
5.0 kHz > C6-03: K = 1
00 to
99
00 No A A
* 1. Only 1(VT) can be set for 200 V Class 110 kW as well as 400 V Class 220 kW and 300 kW Inverters.
* 2. The factory settings depend on the capacity of the Inverter. The values for a 200 V Class Inverter of 0.4 kW are given.
* 3. The setting ranges depend on the capacity of the Inverter. The values for a 200 V Class Inverter of 0.4 kW are given.
* 4. This constant can be monitored or set only when F is set for C6-02.
No A 227H 6-2
5-
25
5
-26
Reference Constants: d
The following settings are made with the reference constants (d constants): Frequency references.
Preset Reference: d1
User constants for frequency references are shown in the following table.
Constant
Number
Name d1-01
Frequency reference 1
Description
Sets the frequency reference in the units used in o1-03.
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
0.00
Hz
Yes Q Q Q Q
MEMO
BUS
Register
280H
Page
4-6
6-10 d1-02 d1-03 d1-04 d1-05 d1-06 d1-07 d1-08 d1-09 d1-10 d1-11
Frequency reference 2
Frequency reference 3
Frequency reference 4
Frequency reference 5
Frequency reference 6
The frequency reference when multi-step speed reference 1 is ON for a multifunction input.
The frequency reference when multi-step speed reference 2 is ON for a multifunction input.
The frequency reference when multi-step speed references 1 and 2 are ON for multi-function inputs.
The frequency when multistep speed reference 3 is ON for a multi-function input.
The frequency reference when multi-step speed references 1 and 3 are ON for multi-function inputs.
0.00 to
400.00
*1 *3
Frequency reference 7
Frequency reference 8
Frequency reference 9
The frequency reference when multi-step speed references 2 and 3 are ON for multi-function inputs.
The frequency reference when multi-step speed references 1, 2, and 3 are ON for multi-function inputs.
The frequency reference when multi-step speed reference 4 is ON for a multifunction input.
Frequency reference 10
The frequency reference when multi-step speed references 1 and 4 are ON for multi-function inputs.
Frequency reference 11
The frequency reference when multi-step speed references 2 and 4 are ON for a multi-function inputs.
0.00 to
300.00
*1 *2
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
Yes Q
Yes Q
Yes Q
Yes A
Yes A
Yes A
Yes A
Yes A
Yes A
Yes A
Q
Q
Q
A
A
A
A
A
A
A
Q
Q
Q
A
A
A
A
A
A
A
Q 281H
Q 282H
Q 283H
4-6
6-10
4-6
6-10
4-6
6-10
A 284H 6-10
A 285H 6-10
A 286H 6-10
A 287H 6-10
A 288H -
A 28BH -
A 28CH -
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector d1-12 d1-13 d1-14 d1-15 d1-16 d1-17
Frequency reference 12
The frequency reference when multi-step speed references 1, 2, and 4 are ON for multi-function inputs.
Frequency reference 13
The frequency reference when multi-step speed references 3 and 4 are ON for multi-function inputs.
Frequency reference 14
The frequency reference when multi-step speed references 1, 3, and 4 are ON for multi-function inputs.
Frequency reference 15
The frequency reference when multi-step speed references 2, 3, and 4 are ON for multi-function inputs.
Frequency reference 16
The frequency reference when multi-step speed references 1, 2, 3, and 4 are ON for multi-function inputs.
Jog frequency reference
The frequency reference when the jog frequency reference selection, FJOG command, or RJOG command is
ON.
0.00 to
400.00
*1 *3
0.00 to
300.00
*1 *2
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
0.00
Hz
6.00
Hz
Yes
Yes
Yes
Yes
Yes
Yes
Note The unit is set in o1-03 (frequency units of reference setting and monitor), default: 0.01 Hz.
* 1. The upper limit of the setting range depends on the upper limit set in E1-04.
* 2. When C6-01 = 1, the upper limit is 400.00.
* 3. When C6-01 = 0, the upper limit is 150.00.
A
A
A
A
A
Q
A
A
A
A
A
Q
A
A
A
A
A
Q
A
A
A
A
A
Q
MEMO
BUS
Register
28DH
28EH
28FH
290H
291H
292H
Page
-
-
-
-
-
4-6
6-10
6-86
Reference Limits: d2
User constants for frequency reference limits are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector d2-01 d2-02
Frequency reference upper limit
Frequency reference lower limit d2-03
Master speed reference lower limit
Set the output frequency upper limit as a percent, taking the max. output frequency to be 100%.
Sets the output frequency lower limit as a percentage of the maximum output frequency.
Set the master speed reference lower limit as a percent, taking the max. output frequency to be 100%.
0.0 to
110.0
100.0% No
0.0 to
110.0
0.0 to
110.0
0.0%
0.0%
No
No
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
A 289H
A 28AH
A 293H
6-41
6-81
6-41
6-81
6-41
6-81
5-
27
5
-28
Jump Frequencies: d3
User constants for jump frequencies are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page d3-01
Jump frequency 1 d3-02
Jump frequency 2 d3-03
Jump frequency 3
Set the center values of the jump frequencies in Hz.
This function is disabled by setting the jump frequency to
0 Hz. Always ensure that the following applies: d3-01 ≥ d3-02 ≥ d3-03
Operation in the jump frequency range is prohibited but during acceleration and deceleration, speed changes smoothly without jump.
0.0 to
400.0
*1
0.0 Hz No
0.0 to
300.0
*2
0.0 Hz
0.0 Hz
No
No
A
A
A
A
A
A
A
A
A
A 294H
4-20
6-38
A 295H
4-20
6-38
A 296H
4-20
6-38 d3-04
Jump frequency width
Sets the jump frequency bandwidth in Hz.
The jump frequency will be the jump frequency ± d3-04.
* 1. When C6-01 = 1, the upper limit is 150.0.
* 2. When C6-01 = 0, the upper limit is 400.0.
0.0 to
20.0
1.0 Hz No A A A A 297H
4-20
6-38
Reference Frequency Hold: d4
User constants for the reference frequency hold function are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector d4-01
Frequency reference hold function selection
Sets whether or not frequencies on hold will be recorded.
0: Disabled (when operation is stopped or the power is turned on again starts at
0.)
1: Enabled (when operation is stopped or the power is turned on again starts at the previous hold frequency.)
This function is available when the multi-function inputs “accel/decel Ramp
Hold” or “up/down” commands are set.
0 or 1 0 No A A A
MEMO
BUS
Register
Page
A 298H 6-80
User Constant Tables
Constant
Number
Name d4-02
+ - Speed limits
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Set the frequency to be add to or subtracted from the analog frequency reference as a percent, taking the maximum output frequency to be
100%.
Enabled when the increase
(+) speed command or decrease (-) speed command is set for a multi-function input.
0 to
100
10% No A A A A 299H 6-84
Torque Control: d5
User constants for the torque control are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector d5-01 d5-02 d5-03
Torque control selection
0: Speed control (C5-01 to
C5-07)
1: Torque control
This function is only available in flux vector control method. To use the function for switching between speed and torque control, set to 0 and set the multi-function input to “speed/torque control change.”
Torque reference delay time
Set the torque reference delay time in ms units.
This function can be used to adjust the noise of the torque control signal or the responsiveness with the host controller. When oscillation occurs during torque control, increase the set value.
Speed limit selection
Set the speed limit command method for the torque control method.
1: The analog input limit from a frequency reference (see b1-01)
2: Limited by d5-04 constant setting values.
0 or 1
0 to
1000
1 or 2
0
0 ms
1
MEMO
BUS
Register
Page
No No No No A 29AH 6-128
No No No No A 29BH 6-128
No No No No A 29CH 6-128
5-
29
5
-30
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page d5-04 Speed limit d5-05 d5-06
Speed limit bias
Speed/ torque control switching timer
Set the speed limit during torque control as a percentage of the maximum output frequency.
This function is enabled when d5-03 is set to 2.
Directions are as follows.
+: Run Command direction
-: Run Command opposite
direction
Set the speed limit bias as a percentage of the maximum output frequency.
Bias is given to the specified speed limit. It can be used to adjust the margin for the speed limit.
Set the delay time from inputting the multi-function input “speed/torque control change” (from On to OFF or
OFF to ON) until the control is actually changed, in ms units.
This function is enabled when the multi-function input “speed/torque control change” is set. In the speed/ torque control switching timer, the analog inputs hold the values of when the
“speed/torque control change” changes. Always be sure to allow time for this process to finish completely.
-120 to
+120
0 to
120
0 to
1000
0%
10%
0 ms
No
No
No
No
No
No
No
No
No
No
No
No
A
A
A
29DH 6-128
29EH 6-128
29FH 6-129
User Constant Tables
Field Weakening: d6
User constants for the field weakening command are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector d6-01 d6-02 d6-03 d6-06
Field weakening level
Field frequency
Field forcing function selection
Field forcing limit
Set the Inverter output voltage when the field weakening command is input.
It is enabled when the field weakening command is set for a multi-function input.
Set the level as a percentage taking the voltage set in the
V/f pattern as 100%.
Set the lower limit in hertz of the frequency range where field control is valid.
The field weakening command is valid only at frequencies above this setting and only when the speed is in agreement with the current speed reference.
Set the field forcing function.
0: Disabled
1: Enabled
Set the excitation current reference’s upper limit for field forcing. Set the limit as a percentage, taking the motor’s no-load current as
100%. Enabled for operation other than DC excitation.
Usually, there is no need to change this setting
0 to
100
0.0 to
400.0
*1
0.0 to
300.0
*2
0 or 1
100 to
400
80% No
0.0 Hz No
0
A
A
MEMO
BUS
Register
Page
A No No 2A0H -
A No No 2A1H -
No No No A
400% No No No A
A 2A2H -
A 2A5H -
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
5-
31
5
-32
Motor Constant Constants: E
The following settings are made with the motor constant constants (E constants): V/f characteristics and motor constants.
V/f Pattern: E1
User constants for V/f characteristics are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
E1-01
Input voltage setting
E1-03
V/f pattern selection
E1-04
E1-05
E1-06
E1-07
E1-08
E1-09
Max. output frequency
Max. voltage
Base frequency
Mid. output frequency
Mid. output frequency voltage
Min. output frequency
Set the Inverter input voltage in
1 volt.
This setting is used as a reference value in protection functions.
0 to E: Select from the 15 preset patterns.
F: Custom user-set patterns
(Applicable for settings
E1-04 to E1-10.)
155 to
255
*1
0 to F
Output voltage (V)
Frequency (Hz)
To set V/f characteristics in a straight line, set the same values for E1-07 and E1-09. In this case, the setting for E1-08 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E1-04 (FMAX) ≥ E1-06 (FA) >
E1-07 (FB) ≥ E1-09 (FMIN)
40.0 to
400.0
*6
40.0 to
300.0
*5
0.0 to
255.0
*1
0.0 to
400.0
*6
0.0 to
300.0
*5
0.0 to
400.0
*6
0.0 to
300.0
*5
0.0 to
255
*1
0.0 to
400.0
*6
0.0 to
300.0
*5
200 V
*1
F
60.0
Hz
*2
200.0
V
*1*2
60.0
Hz
*2
3.0 Hz
*2
15.0 V
*1 *2
1.5 Hz
*2
E1-10
Min. output frequency voltage
0.0 to
255.0
*1
9.0 V
*1 *2
No
No
No
No
No
No
No
No
No
Q
Q
Q
Q
Q
A
A
Q
A
Q
Q
Q
Q
Q
A
A
Q
A
Q
No
Q
Q
Q
A
A
Q
A
Q
No
Q
Q
Q
No
No
A
No
MEMO
BUS
Register
300H
Page
4-5
6-121
302H 6-121
303H 6-122
304H 6-122
305H 6-122
306H 6-122
307H
308H 6-122
309H
4-18
4-19
6-122
4-18
4-19
6-122
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
E1-11
Mid. output frequency
2
0.0 to
400.0
*6
0.0 to
300.0
*5
0.0 Hz
*3
No A A
E1-12
Mid. output frequency voltage 2
Set only to fine-adjust V/f for the output range. Normally, this setting is not required.
0.0 to
255.0
*1
0.0 V
*3
No A A
E1-13
Base voltage
0.0 to
255.0
*1
0.0 V
*4
No A A
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 3. E1-11 and E1-12 are disregarded when set to 0.0.
* 4. E1-13 is set to the same value as E1-05 by autotuning.
* 5. When C6-01 = 1, the upper limit is 400.0.
* 6. When C6-01 = 0, the upper limit is 150.0.
A
A
Q
A
A
Q
MEMO
BUS
Register
Page
30AH 6-122
30BH 6-122
30CH 6-122
5-
33
5
-34
Motor Setup: E2
User constants for motor 1 are shown in the following table.
Constant
Number
E2-01
E2-02
E2-03
E2-04
E2-05
E2-06
E2-07
E2-08
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Motor rated current
Motor rated slip
Motor noload current
Number of motor poles
Motor lineto-line resistance
Motor leak inductance
Motor iron saturation coefficient 1
Motor iron saturation coefficient 2
Sets the motor rated current in 1 A units.
These set values will become the reference values for motor protection, torque limits and torque control.
This constant is automatically set during autotuning.
Sets the motor rated slip in
Hz units.
These set values will become the reference values for slip compensation.
This constant is automatically set during autotuning.
Sets the motor no-load current in 1 A units.
This constant is automatically set during autotuning.
Sets the number of motor poles.
This constant is automatically set during autotuning.
Sets the motor phase-tophase resistance in Ω units.
This constant is automatically set during autotuning.
Sets the voltage drop due to motor leakage inductance as a percentage of the motor rated voltage.
This constant is automatically set during autotuning.
Sets the motor iron saturation coefficient at 50% of magnetic flux.
This constant is automatically set during autotuning.
Sets the motor iron saturation coefficient at 75% of magnetic flux.
This constant is automatically set during autotuning.
0.32 to
6.40
*2
0.00 to
20.00
0.00 to
1.89
*3
0.000
to
65.000
0.0 to
40.0
0.00 to
0.50
0.50 to
0.75
*4
1.90 A
*1
2.90
Hz
*1
1.20 A
*1
9.842
Ω
*1
18.2%
*1
0.50
0.75
No
No
No
No
No
No
No
Q
A
A
A
No
No
No
Q
A
A
A
No
No
No
Q
A
A
Q
A
A
30EH
30FH
4-5
6-60
6-119
6-117
6-119
310H 6-119
2 to 48 4 poles No No Q No Q 311H 6-119
A
A
A
A
A
A
A
A
312H 6-119
313H 6-119
314H 6-119
315H 6-119
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
E2-09
E2-10
E2-11
Motor mechanical loss
Sets motor mechanical loss as a percentage of motor rated output (W).
Usually setting is not necessary.
Adjust in the following circumstances:
• When torque loss is large due to motor bearing.
• When the torque loss in the pump or fan is large.
The set mechanical loss will compensate for torque.
Motor iron loss for torque compensation
Sets motor iron loss in W units.
Motor rated output
Set the rated output of the motor in units of 0.01 kW.
This constant is automatically set during autotuning.
0.0 to
10.0
0 to
65535
0.00 to
650.00
0.0
14 W
*1
0.40 kW
*1
No
No
No
No
A
Q
No
A
Q
No
No
Q
A
No
Q
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V Class Inverter of 0.4 kW is given.
* 3. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 4. The lower limit of E2-08 is the setting value of E2-07.
316H -
317H 6-120
318H 6-117
5-
35
5
-36
Motor 2 V/f Pattern: E3
User constants for motor 2 V/f characteristics are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
E3-01
Motor 2 control method selection
0: V/f control
1: V/f control with PG
2: Open-loop vector control
3: Flux vector control
0 to 2
0 to 3
0 No A A A
MEMO
BUS
Register
Page
A 319H -
E3-02
Motor 2 max. output frequency
(FMAX)
40.0 to
400.0
*4
40.0 to
300.0
*3
60.0
Hz
No A A
E3-03
Motor 2 max. voltage
(VMAX)
0.0 to
255.0
*1
200.0
V
*2
No A A
E3-04
Motor 2 max. voltage frequency
(FA)
E3-05
Motor 2 mid. output frequency 1
(FB)
E3-06
Motor 2 mid. output frequency voltage 1
(VC)
E3-07
Motor 2 min. output frequency
(FMIN)
Output voltage (V)
Frequency (Hz)
To set V/f characteristics in a straight line, set the same values for E3-05 and E3-07.
In this case, the setting for E3-06 will be disregarded.
Always ensure that the four frequencies are set in the following manner:
E3-02 (FMAX) ≥ E3-04 (FA) >
E3-05 (FB) > E3-07 (FMIN)
0.0 to
400.0
*4
0.0 to
300.0
*3
0.0 to
400.0
*4
0.0 to
300.0
*3
0.0 to
255.0
*1
60.0
Hz
3.0 Hz
*2
15.0 V
*1
No
No
No
A
A
A
A
A
A
0.0 to
400.0
*4
0.0 to
300.0
*3
1.5 Hz
*2
No A A
E3-08
Motor 2 min. output frequency voltage
(VMIN)
0.0 to
255.0
*1
9.0 V
*1
No A A
* 1. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 2. The factory setting will change when the control method is changed. The V/f control factory settings are given.
* 3. When C6-01 = 1, the upper limit is 400.0.
* 4. When C6-01 = 0, the upper limit is 150.0.
A
A
A
A 31AH -
A 31BH -
A 31CH -
A No 31DH -
A No 31EH -
A A 31FH -
A No 320H -
User Constant Tables
Motor 2 Setup: E4
User constants for motor 2 are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
E4-01
E4-02
E4-03
E4-04
E4-05
E4-06
E4-07
Motor 2 rated current
Sets the motor rated current in 1 A units.
These set values will become the reference values for motor protection, torque limits and torque control.
This constant is automatically set during autotuning.
0.32
to 6.40
*2
Motor 2 rated slip
Motor 2 noload current
Sets the motor rated slip in
Hz units.
These set values will become the reference values for slip compensation.
This constant is automatically set during autotuning.
Sets the motor no-load current in 1 A units.
This constant is automatically set during autotuning.
Motor 2 number of poles (number of poles)
Sets the number of motor poles.
This constant is automatically set during autotuning.
Motor 2 line-to-line resistance
Motor 2 leak inductance
Sets the motor phase-tophase resistance in Ω units.
This constant is automatically set during autotuning.
Sets the voltage drop due to motor leakage inductance as a percentage of the motor rated voltage.
This constant is automatically set during autotuning.
Motor 2 rated capacity
Set the rated output of the motor in units of 0.01 kW.
This constant is automatically set during autotuning.
0.00 to
20.00
0.00 to
1.89
*3
1.90 A
*1
2.90
Hz
*1
1.20 A
*1
2 to 48 4 poles
0.000 to
65.000
0.0 to
40.0
0.00 to
650.00
9.842
Ω
*1
18.2%
*1
0.40 kW
*1
No
No
No
No
No
No
No
A
A
A
No
A
No
A
A
A
A
A
A
No
A
A
A
A
No
A
A
A
A
A
A
A
A
A
A
321H 6-60
322H
323H
324H
325H
326H
327H -
-
-
-
-
-
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The values for a 200 V Class Inverter of 0.4 kW is given.
* 3. If a multi-function input is set for motor 2 (H1 = 16), the setting range will depend upon the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
5-
37
5
-38
Option Constants: F
The following settings are made with the option constants (F constants): Settings for option boards
PG Option Setup: F1
User constants for the PG Speed Control Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
F1-01 PG constant
Sets the number of PG (pulse generator or encoder) pulses.
Sets the number of pulses per motor revolution.
F1-02
F1-03
Operation selection at
PG open circuit
(PGO)
Operation selection at overspeed
(OS)
Sets the PG disconnection stopping method.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-
09.)
3: Continue operation (To protect the motor or machinery, do not normally make this setting.)
Sets the stopping method when an overspeed (OS) fault occurs.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-
09.)
3: Continue operation (To protect the motor or machinery, do not normally make this setting.)
0 to
60000
0 to 3
0 to 3
600
1
1
No No Q No Q 380H 6-156
No No A No A 381H 6-156
No No A No A 382H 6-156
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
F1-04
Operation selection at deviation
F1-05 PG rotation
F1-06
F1-07
F1-08
F1-09
Sets the stopping method when a speed deviation
(DEV) fault occurs.
0: Ramp to stop
(Deceleration stop using
Deceleration Time 1, C1-
02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-
09.)
3: Continue operation (DEV is displayed and operation continued.)
0: Phase A leads with Forward Run Command.
(Phase B leads with
Reverse Run Command.)
1: Phase B leads with Forward Run Command.
(Phase A leads with
Reverse Run Command.)
PG division rate (PG pulse monitor)
Sets the division ratio for the
PG speed control board pulse output.
Division ratio = (1+ n) /m
(n=0 or 1 m=1 to 32)
F1-06 n m
This constant is only effective when a PG-B2 is used.
The possible division ratio settings are: 1/32 ≤ F1-06 ≤
1.
Integral value during accel/decel enable/disable
Sets integral control during acceleration/deceleration to either enabled or disabled.
0: Disabled (The integral function isn't used while accelerating or decelerating; it is used at constant speeds.)
1: Enabled (The integral function is used at all times.)
Overspeed detection level
Overspeed detection delay time
Sets the overspeed detection method.
Frequencies above that set for F1-08 (set as a percentage of the maximum output frequency) that continue to exceed this frequency for the time set in F1-09 are detected as overspeed faults.
0 to 3
0 or 1
1 to
132
0 or 1
0 to
120
0.0 to
2.0
3
0
1
0
115%
0.0 s
*
No
No
No
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
No
No
No
No
No
No
A
A
A
No
A
A
383H 6-156
384H 6-157
385H 6-157
386H 6-157
387H 6-157
388H 6-157
5-
39
5
-40
Constant
Number
F1-10
F1-11
F1-12
F1-13
F1-14
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Excessive speed deviation detection level
Excessive speed deviation detection delay time
Sets the speed deviation detection method.
Any speed deviation above the F1-10 set level (set as a percentage of the maximum output frequency) that continues for the time set in F1-
11 is detected as a speed deviation.
Speed deviation is the difference between actual motor speed and the reference command speed.
Number of
PG gear teeth 1
Sets the number of teeth on the gears if there are gears between the PG and the motor.
0 to 50 10%
0.0 to
10.0
0 to
1000
0.5 s
0
Number of
PG gear teeth 2
Input pulses from PG 60
F1-01
F1-13
F1-12
A gear ratio of 1 will be used if either of these constants is set to 0.
0
PG opencircuit detection time
Used to set the PG disconnection detection time. PGO will be detected if the detection time continues beyond the set time.
0.0 to
10.0
2.0 s
No
No
No
No
No
No
No
No
No
No
A
A
A
A
A
No
No
No
No
No
A
A
MEMO
BUS
Register
Page
No 38BH 6-157
No 38CH 6-157
A
389H 6-157
38AH 6-157
38DH 6-157
* The factory setting will change when the control method is changed. The flux vector control factory setting is given.
Analog Reference Board: F2
User constants for the Analog Reference Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
F2-01
Bi-polar or uni-polar input selection
Sets the functions for channel 1 to 3 which are effective when the AI-14B Analog
Reference Board is used.
0: 3-channel individual
(Channel 1: terminal A1,
Channel 2: terminal A2,
Channel 3: terminal A3)
1: 3-channel addition (Addition values are the frequency reference)
When set to 0, select 1 for b1-01. In this case the multifunction input “Option/
Inverter selection” cannot be used.
0 or 1 0 No A A A A 38FH 6-163
User Constant Tables
Digital Reference Board: F3
User constants for the Digital Reference Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
F3-01
Digital input option
Sets the Digital Reference
Board input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5digit input)
7: Binary input
6 is only effective when the
DI-16H2 is used.
When o1-03 is set to 2 or higher, the input will be
BCD, and the units will change to the o1-03 setting.
0 to 7 0 No A A A
MEMO
BUS
Register
Page
A 390H 6-163
5-
41
5
-42
Analog Monitor Boards: F4
User constants for the Analog Monitor Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
F4-01
F4-02
F4-03
F4-04
F4-05
Channel 1 monitor selection
Channel 1 gain
Channel 2 monitor selection
Channel 2 gain
Effective when the Analog
Monitor Board is used.
Monitor selection:
Set the number of the monitor item to be output. (U1-
)
The monitor items that can be set depends on the control method.
Gain:
Set the multiple of 10 V for outputting monitor items.
4, 10 to 14, 25, 28, 31, 34,
35, 39, 40, 42 cannot be set.
29 to 31 are not used. When the AO-12 Analog Monitor
Board is used, outputs of ±
10 V are possible. To output
± 10 V, set F4-07 or F4-08 to
1. When the AO-08 Analog
Monitor Board is used, only outputs of 0 to +10 V are possible.
A meter calibration function is available.*
1 to 99
0.00 to
2.50
1 to 99
0.00 to
2.50
Channel 1 output monitor bias
Sets the channel 1 item bias to 100%/10 V when the Analog Monitor Board is used.
-10.0 to
10.0
2
1.00
3
0.50
0.0%
No
Yes
No
Yes
Yes
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
391H 6-91
392H 6-91
393H 6-91
394H 6-91
395H 6-91
F4-06
F4-07
F4-08
Channel 2 output monitor bias
Analog output signal level for channel 1
Analog output signal level for channel 2
Sets the channel 2 item bias to 100%/10 V when the Analog Monitor Board is used.
-10.0 to
10.0
0: 0 to 10 V
1: -10 to +10 V
0: 0 to 10 V
1: -10 to +10 V
0 or 1
0 or 1
0.0%
0
0
Yes
No
No
A
A
A
A
A
A
A
A
A
A
A
A
396H 6-91
397H 6-91
398H 6-91
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
User Constant Tables
Digital Output Boards (DO-02C and DO-08): F5
User constants for the Digital Output Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
F5-01
F5-02
F5-03
F5-04
F5-05
F5-06
F5-07
F5-08
F5-09
Channel 1 output selection
Channel 2 output selection
Channel 3 output selection
Channel 4 output selection
Channel 5 output selection
Channel 6 output selection
Channel 7 output selection
Channel 8 output selection
DO-08 output mode selection
Effective when a Digital
Output Board (DO-02C or
DO-08) is used.
Set the number of the multifunction output to be output.
Effective when a Digital
Output Board (DO-02C or
DO-08) is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08
Digital Output Board is used.
Set the output mode.
0: 8-channel individual outputs
1: Binary code output
2: Output according to
F5-01 to F5-08 settings.
0 to 37
0 to 37
0 to 37
0 to 37
0 to 37
0 to 37
0 to 37 0F
0 to 37 0F
0 to 2
0
1
2
4
6
37
0
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
A 399H 6-160
A 39AH 6-160
A 39BH 6-160
A 39CH 6-160
A 39DH 6-160
A 39EH 6-160
A 39FH 6-161
A 3A0H 6-161
A 3A1H 6-161
5-
43
5
-44
Communications Option Boards: F6
User constants for a Communications Option Board are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
F6-01
F6-02
F6-03
F6-04
F6-06
F6-08
F6-09
Operation selection after communications error
Set the stopping method for communications errors.
0: Deceleration stop using deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using deceleration time in C1-
09
3: Continue operation
Input level of external fault from
Communications
Option
Board
Stopping method for external fault from
Communications
Option
Board
Number of
SI-T BUS error detection
0: Always detect
1: Detect during operation
0: Deceleration stop using deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using deceleration time in C1-
09
3: Continue operation
Trace sampling from
Communications
Option
Board
Torque reference/ torque limit selection from optical option
Operation selection after SI-T
WDT error
-
0: Torque reference/torque limit from transmission disabled.
1: Torque reference/torque limit from transmission enabled.
Set the stopping method for
SI-T WDT errors (E5).
0: Deceleration stop using deceleration time in C1-
02
1: Coast to stop
2: Emergency stop using deceleration time in C1-
09
3: Continue operation
Set the number which SI-T detects BUS errors.
0 to 3
0 or 1
0 to 3
0 to
60000
0 or 1
0 to 3
2 to 10
1
0
1
0
0
1
2
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
MEMO
BUS
Register
Page
A 3A2H -
A 3A3H -
A 3A4H -
A 3A5H -
No No No No A 3A7H -
A
A
A 3B6H -
A 3B7H -
User Constant Tables
Terminal Function Constants: H
The following settings are made with the terminal function constants (H constants): Settings for external terminal functions.
Multi-function Contact Inputs: H1
User constants for multi-function contact inputs are shown in the following tables.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H1-01
H1-02
H1-03
H1-04
H1-05
H1-06
Terminal S3 function selection
Multi-function contact input
1
Terminal S4 function selection
Multi-function contact input
2
Terminal S5 function selection
Multi-function contact input
3
Terminal S6 function selection
Multi-function contact input
4
Terminal S7 function selection
Multi-function contact input
5
Terminal S8 function selection
Multi-function contact input
6
0 to 78 24
0 to768 14
0 to78
0 to 78
0 to 78
3 (0)
4 (3)
6 (4)
0 to 78 8 (6)
* The values in parentheses indicate factory settings when initialized in 3-wire sequence.
*
*
*
*
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
400H
401H
402H
403H
404H
4-5H -
-
-
-
-
-
Multi-function Contact Input Functions
6
7
4
5
8
9
Setting
Value
0
1
Function
3-wire sequence (Forward/Reverse Run Command)
Local/Remote selection (ON: Operator, OFF: Constant setting)
2
3
Option/Inverter selection (ON: Option board)
Multi-step speed reference 1
When H3-09 is set to 2, this function is combined with the master/auxiliary speed switch.
Multi-step speed reference 2
Multi-step speed reference 3
Jog frequency command (higher priority than multi-step speed reference)
Accel/decel time 1
External baseblock NO (NO contact: Baseblock at ON)
External baseblock NC (NC contact: Baseblock at OFF)
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
Yes Yes Yes Yes 6-16
Yes Yes Yes Yes 6-78
Yes Yes Yes Yes
6-85
6-163
Yes Yes Yes Yes 6-10
Yes Yes Yes Yes 6-10
Yes Yes Yes Yes 6-10
Yes Yes Yes Yes 6-10
Yes Yes Yes Yes 6-26
Yes Yes Yes Yes 6-79
Yes Yes Yes Yes 6-79
5-
45
5
-46
Setting
Value
Function
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
A
Acceleration/deceleration ramp hold (ON: Acceleration/deceleration stopped, frequency on hold)
OH2 alarm signal input (ON: OH2 will be displayed) B
C
D
Multi-function analog input selection (ON: Enable)
No V/f control with PG (ON: Speed feedback control disabled,) (normal V/f control)
Speed control integral reset (ON: Integral control disabled) E
F Not used (Set when a terminal is not used)
10 Up command (Always set with the down command)
11 Down command (Always set with the up command)
12 FJOG command (ON: Forward run at jog frequency d1-17)
13 RJOG command (ON: Reverse run at jog frequency d1-17)
14 Fault reset (Reset when turned ON)
15
Emergency stop. (Normally open condition: Deceleration to stop in deceleration time set in C1-09 when ON.)
16 Motor switch command (Motor 2 selection)
17
Emergency stop (Normally closed condition: Deceleration to stop in deceleration time set in C1-09 when OFF)
18
Timer function input (Functions are set in b4-01 and b4-02 and the timer function outputs are set in H1 and H2 .)
19 PID control disable (ON: PID control disabled)
1A Accel/Decel time 2
1B
Constants write enable (ON: All constants can be written-in. OFF: All constants other than frequency monitor are write protected.)
1C
1D
Trim control increase (ON: d4-02 frequency is added to analog frequency reference.)
Trim control decrease (ON: d4-02 frequency is subtracted from analog frequency reference.)
1E Analog frequency reference sample/hold
20 to
2F
External fault (Desired settings possible)
Input mode: NO contact/NC contact, Detection mode: Normal/during operation
30
PID control integral reset (reset when reset command is input or when stopped during PID control)
31 PID control integral hold (ON: Hold)
32 Multi-step speed reference 4
34 PID soft starter ON/OFF
35 PID input characteristics switch
60 DC injection braking command (ON: Performs DC injection braking)
61
External search command 1 (ON: Speed search from maximum output frequency)
62 External search command 2 (ON: Speed search from set frequency)
Yes Yes Yes Yes 6-80
Yes Yes Yes Yes
Yes Yes Yes Yes
No Yes No
-
-
No 6-136
No Yes No Yes 6-136
-
Yes Yes Yes Yes 6-81
Yes Yes Yes Yes 6-81
Yes Yes Yes Yes 6-86
Yes Yes Yes Yes 6-86
Yes Yes Yes Yes 7-2
Yes Yes Yes Yes 6-24
Yes Yes Yes Yes -
Yes Yes Yes Yes 6-24
Yes Yes Yes Yes
6-107
7-18
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-26
Yes Yes Yes Yes 6-154
Yes Yes Yes Yes 6-84
Yes Yes Yes Yes 6-84
Yes Yes Yes Yes 6-85
Yes Yes Yes Yes 6-87
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes -
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-23
Yes No Yes No 6-69
Yes No Yes No 6-69
User Constant Tables
Setting
Value
Function
63
Field weakening command (ON: Field weakening control set for d6-01 and d6-02)
64 External speed search command 3
65 KEB (deceleration at momentary power loss) command (NC contact)
66 KEB (deceleration at momentary power loss) command (NO contact)
67
Communications test mode (“Pass” is displayed when the communication test is passed.)
68 High-slip braking (HSB)
71 Speed/torque control change (ON: Torque control)
72 Zero-servo command (ON: Zero-servo)
77 Speed control (ASR) proportional gain switch (ON: C5-03)
78 Polarity reversing command for external torque reference
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
Yes Yes No No -
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes -
-
-
Yes Yes Yes Yes 6-106
Yes
No
Yes
No
No
No
No
Yes
-
6-130
6-134
No No No Yes 6-144
No No No Yes 6-136
No No No Yes 6-130
Multi-function Contact Outputs: H2
User constants for multi-function outputs are shown in the following tables.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H2-01
H2-02
Terminal
M1-M2 function selection
(contact)
Multi-function contact output
Terminal P1 function selection
(open collector)
Multi-function contact output 1
H2-03
Terminal P2 function selection
(open collector)
Multi-function contact output 2
0 to 37
0 to 37
0 to 37
0
1
2
No
No
No
A
A
A
A
A
A
A
A
A
A 40BH -
A 40CH -
A 40DH -
Multi-function Contact Output Functions
Setting
Value
0
1
2
3
Function
During run (ON: Run Command is ON or voltage is being output)
Zero-speed
Frequency agree 1 (L4-02 used.)
Desired frequency agree 1 (ON: Output frequency = ±L4-01, L4-02 used and during frequency agree)
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
Yes Yes Yes Yes 6-88
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6-88
6-54
Yes Yes Yes Yes 6-54
5-
47
5
-48
Setting
Value
Function
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
4
5
6
Frequency (FOUT) detection 1 (ON: +L4-01 ≥ output frequency ≥ -L4-01,
L4-02 used)
Frequency (FOUT) detection 2 (ON: Output frequency ≥ +L4-01 or output frequency ≤ -L4-01, L4-02 used)
Inverter operation ready
READY: After initialization, no faults
During DC bus undervoltage (UV) detection 7
8
9
A
During baseblock (ON: during baseblock)
Frequency reference selection (ON: Frequency reference from Operator)
B
Run Command selection status (ON: Run Command from Operator)
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection at ON)
Loss of frequency reference (Effective when 1 is set for L4-05) C
D
E
Braking resistor fault (ON: Resistor overheat or braking transistor fault)
Fault (ON: Digital Operator communications error or fault other than CPF00 and CPF01 has occurred.)
Not used. (Set when the terminals are not used.) F
10 Minor fault (ON: Alarm displayed)
11 Fault reset command active
12 Timer function output
13 Frequency agree 2 (L4-04 used)
14
Desired frequency agree 2 (ON: Output frequency = L4-03, L4-04 used, and during frequency agree)
15 Frequency detection 3 (ON: Output frequency ≤ L4-03, L4-04 used)
16 Frequency detection 4 (ON: Output frequency ≥ L4-03, L4-04 used)
17
Overtorque/undertorque detection 1 NC (NC Contact: Torque detection at
OFF)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
Yes Yes Yes Yes
Yes Yes Yes Yes
-
-
-
-
-
-
-
Yes Yes Yes Yes 6-107
Yes Yes Yes Yes 6-54
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6-54
6-54
-
6-57
6-74
6-76
-
6-54
6-54
6-54
6-57
18
19
1A
1B
1C
1D
Overtorque/undertorque detection 2 NO (NO Contact: Torque detection at
ON)
Overtorque/undertorque detection 2 NC (NC Contact: Torque detection at
OFF)
During reverse run (ON: During reverse run)
During baseblock 2 (OFF: During baseblock)
Motor selection (Motor 2 selected)
During regeneration (ON: During regeneration)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
No No No Yes
6-57
6-57
1E Restart enabled (ON: Restart enabled)
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6-74
6-61
6-89
20 Inverter overheat (OH) pre-alarm (ON: Temperature exceeds L8-02 setting) Yes Yes Yes Yes 6-89
30 During torque limit (current limit) (ON: During torque limit)
31 During speed limit (ON: During speed limit)
No No Yes Yes -
No No No Yes 6-89
-
-
-
-
User Constant Tables
Setting
Value
Function
32
Speed control circuit operating for torque control (except when stopped).
The external torque reference will be limited if torque control is selected
(internal torque reference < external torque reference).
Output when the motor is rotating at the speed limit.
33 Zero-servo end (ON: Zero-servo function completed)
37
During run 2 (ON: Frequency output, OFF: Base block, DC injection braking, initial excitation, operation stop)
V/f
No
Control Methods
V/f with
PG
No
Open
Loop
Vector
No
Flux
Vector
Page
Yes 6-130
No No No Yes
6-89
6-145
Yes Yes Yes Yes 6-89
Analog Inputs: H3
User constants for analog inputs are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H3-01
H3-02
H3-03
Signal level selection
(terminal
A1)
Bias (terminal A1)
0: 0 to ±10V
1: 0 to ±10V
Gain (terminal A1)
Sets the frequency when 10
V is input, as a percentage of the maximum output frequency.
Sets the frequency when 0 V is input, as a percentage of the maximum frequency.
0 or 1
0.0 to
1000.0
-100.0
to
+100.0
H3-04
Signal level selection
(terminal
A3)
H3-05
Multi-function analog input (terminal A3) function selection
0: 0 to ±10V
1: 0 to ±10V
Select from the functions listed in the following table.
Refer to the next page.
H3-06
H3-07
Gain (terminal A3)
Sets the input gain (level) when 10V is input.
Set according to the 100% value selected from H3-05.
Bias (terminal A3)
Sets the input gain (level) when 0V is input.
Set according to the 100% value selected from H3-05.
0 to 1F
-
0 or 1
0.0 to
1000.0
100.0 to
+100.0
0 No
100.0% Yes
0.0% Yes A
0
1F
No
No
100.0% Yes
0.0% Yes
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A 410H 6-35
A 411H 6-35
A 412H 6-35
A 413H
6-35
6-129
A 414H
6-35
6-129
A 415H
6-35
6-129
A 416H
6-35
6-129
5-
49
5
-50
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
H3-08
Signal level selection
(terminal
A2)
0: 0 to +10V, with lower limit
1: 0 to ±10V, without lower limit
2: 4 to 20 mA.
Switch current and voltage input using the switch on the control panel.
H3-09
Multi-function analog input
(terminal
A2) function selection
Select multi-function analog input function for terminal
A2. Refer to the next table.
0 to 2
0 to 1F
H3-10
H3-11
H3-12
H3-13
Gain
(terminal
A2)
Bias
(terminal
A2)
Analog input filter time constant
Terminal
A1/A2 switching
2
0
No
No
A
A
Sets the input gain (level) when 10 V (20 mA) is input.
Set according to the 100% value for the function set for
H3-09.
Sets the input gain (level) when 0 V (4 mA) is input.
Set according to the 100% value for the function set for
H3-09.
Sets primary delay filter time constant in seconds for the analog input terminal.
Effective for noise control etc.
0: Use terminal A1 analog input as main speed frequency reference.
1: Use terminal A2 analog input as main speed frequency reference.
Effective when H3-09 is set to 2 and H3-05 is not set to 0 or 2.
0.0 to
1000.0
-100.0
to
+100.0
0.00 to
2.00
0 or 1
100.0% Yes A
0.0%
0.00
s
0.03
s
0
Yes
No
No
A
A
A
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
417H
418H
419H
41AH
6-35
6-129
6-35
6-129
6-35
6-129
6-35
6-129
41BH 6-36
41CH -
User Constant Tables
H3-05 and H3-09 Settings
Setting
Value
0
Function
Add to terminal A1
Contents (100%)
Maximum output frequency
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Page
Yes Yes Yes Yes
6-37
6-130
1 Frequency gain
Frequency reference (voltage) command value
Yes Yes Yes Yes 6-36
2
3
4
5
6
7
Auxiliary frequency reference 1
(2nd step analog)
Auxiliary frequency reference 2
(3rd step analog)
Voltage bias
Accel/decel change (reduction coefficient)
DC injection braking current
Overtorque/undertorque detection level
Maximum output frequency
Maximum output frequency
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
6-11
6-11
200V (200V-class), 400V (400V-class) Yes Yes No No
Set acceleration and deceleration times
(C1-01 to C1-08)
Yes Yes Yes Yes
-
6-27
Yes Yes Yes No 6-23 Inverter rated output current
Motor rated torque for vector control
Inverter rated output current for V/f control
Inverter rated output current
Yes
Yes
Yes
Yes
Yes
No
Yes
No
6-59
6-53 8
9
Stall prevention level during run
Frequency reference lower limit level
Jump frequency A
B
C
D
E
PID feedback
PID target value
Frequency bias 2
Motor temperature input
10 Positive torque limit
11 Negative torque limit
12 Regenerative torque limit
13
Torque reference/torque limit at speed control
14 Torque compensation
15 Positive/negative torque limit
1F Analog input not used.
16 to 1E Not used
Maximum output frequency
Maximum output frequency
Maximum output frequency
Maximum output frequency
Maximum output frequency
10 V = 100%
Motor's rated torque
Motor's rated torque
Motor's rated torque
Motor’s rated torque
Motor’s rated torque
Motor's rated torque
-
-
Yes
Yes
No
No
Yes
Yes
No
No
Yes
Yes
No
Yes
Yes
Yes
6-42
6-39
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-111
Yes Yes Yes Yes 6-37
Yes Yes Yes Yes 6-64
No No Yes Yes 6-50
No No Yes Yes 6-50
No No Yes Yes 6-50
Yes 6-130
Yes 6-130
No No Yes Yes 6-50
Yes Yes Yes Yes 6-11
-
5-
51
5
-52
Multi-function Analog Outputs: H4
User constants for multi-function analog outputs are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H4-01
Monitor selection
(terminal
FM)
Sets the number of the monitor item to be output (U1-
) from terminal FM. The monitor items that can be set depends on the control method.
4, 10 to 14, 25, 28 to 31, 34,
35, 39 to 43 cannot be set.
1 to 99
H4-02
H4-03
H4-04
H4-05
Gain (terminal FM)
Sets the multi-function analog output 1 voltage level gain.
Sets whether the monitor item output will be output in multiples of 10 V.
The maximum output from the terminal is 10 V.
A meter calibration function is available.
*
Bias (terminal FM)
Monitor selection
(terminal
AM)
0.00 to
2.50
Sets the multi-function analog output 1 voltage level bias.
Sets output characteristic up/ down parallel movement as a percentage of 10 V.
The maximum output from the terminal is 10 V.
A meter calibration function is available.
-10.0 to
+10.0
Sets the number of the monitor item to be output (U1-
) from terminal AM.
The monitor items that can be set depends on the control method.
4, 10 to 14, 25, 28 to 31, 34,
35, 39 to 43 cannot be set.
1 to 99
Gain (terminal AM)
Set the voltage level gain for multi-function analog output 2.
Set the number of multiples of 10 V to be output as the
100% output for the monitor items. The maximum output from the terminal is 10 V.
A meter calibration function is available.
*
0.00 to
2.50
2
1.00
0.0% Yes A
3
0.50
No
Yes Q
No
A
A
Yes Q
A
Q
A
A
Q
A
Q
A
A
Q
A 41DH 6-90
Q 41EH
Q 421H
4-6
6-90
A 41FH 6-90
A 420H 6-90
4-6
6-90
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H4-06
H4-07
H4-08
Bias (terminal AM)
Sets the multi-function analog output 2 voltage level bias.
Sets output characteristic up/ down parallel movement as a percentage of 10 V.
The maximum output from the terminal is 10 V.
A meter calibration function is available.
*
-10.0 to
+10.0
Analog output 1 signal level selection
Sets the signal output level for multi-function output 1
(terminal FM)
0: 0 to +10 V output
1: 0 to ±10 V output
Analog output 2 signal level selection
Sets the signal output level for multi-function output 2
(terminal AM)
0: 0 to +10 V output
1: 0 to ±10 V output
0 or 1
0 or 1
0.0%
0
0
Yes
No
No
A
A
A
A
A
A
A
A
A
A
A
A
422H 6-91
423H 6-91
424H -
* The CH1 output can be adjusted when the H4-02 or H4-03 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
The CH2 output can be adjusted when the H4-05 or H4-06 setting is displayed in Quick, Advanced, or Verify mode while the motor is stopped.
For analog output, the value equivalent to 100% of output value of monitored item is multiplied by the gain setting and the set bias is added.
MEMOBUS Communications: H5
User constants for MEMOBUS communications are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H5-01
H5-02
Slave address
Set the Inverter's slave address.
Communication speed selection
Set the baud rate for 6CN
MEMOBUS communications.
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
H5-03
Communication parity selection
Set the parity for 6CN
MEMOBUS communications.
0: No parity
1: Even parity
2: Odd parity
0 to 20
*
0 to 4
0 to 2
1FH
3
0
No
No
No
A
A
A
A
A
A
A
A
A
A 425H 6-97
A 426H 6-97
A 427H 6-97
5-
53
5
-54
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H5-04
H5-05
H5-06
H5-07
Stopping method after communication error
RTS control ON/
OFF
Set the stopping method for communications errors.
0: Deceleration to stop using deceleration time in
C1-02
1: Coast to stop
2: Emergency stop using deceleration time in C1-
09
3: Continue operation
Communication error detection selection
Send wait time
Set whether or not a communications timeout is to be detected as a communications error.
0: Do not detect.
1: Detect
Set the time from the
Inverter receiving data to when the Inverter starts to send.
Select to enable or disable
RTS control.
0: Disabled (RTS is always
ON)
1: Enabled (RTS turns ON only when sending)
0 to 3
0 or 1
5 to 65 5 ms
0 or 1
* Set H5-01 to 0 to disable Inverter responses to MEMOBUS communications.
3
1
1
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
428H 6-97
429H 6-97
42AH 6-97
42BH 6-97
Pulse Train I/O: H6
User constants for pulse I/O are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
H6-01
H6-02
Pulse train input function selection
Pulse train input scaling
0: Frequency reference
1: PID feedback value
2: PID target value
0 to 2 0 No A A
A
A
A
A 42CH
6-6
6-40
6-110
A 42DH
6-6
6-40
H6-03
Pulse train input gain
H6-04
Pulse train input bias
H6-05
Pulse train input filter time
Set the number of pulses in hertz, taking the reference to be 100%.
1000 to
32000
Set the input gain level as a percent when the pulse train set in H6-02 is input.
0.0 to
1000.0
1440
Hz
Yes A
100.0% Yes A
Set the input bias when the pulse train is 0.
-100.0 to
100.0
0.0% Yes A
Set the pulse train input primary delay filter time constant in seconds.
0.00 to
2.00
0.10 s Yes A
A
A
A
A
A
A
A 42EH 6-40
A 42FH 6-40
A 430H 6-40
User Constant Tables
Constant
Number
Name
H6-06
Pulse train monitor selection
H6-07
Pulse train monitor scaling
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Select the pulse train monitor output items (value of the
part of U1 ).
There are two types of monitor items: Speed-related items and PID-related items.
Set the number of pulses output when speed is 100% in hertz.
Set H6-06 to 2, and H6-07 to
0, to make the pulse train monitor output synchronously to the output frequency.
1, 2, 5,
20, 24,
36
0 to
32000
2
1440
Hz
Yes
Yes
A
A
A
A
A
A
A
A
431H 6-93
432H 6-93
Protection Function Constants: L
The following settings are made with the protection function constants (L constants): Motor selection function, power loss ridethrough function, stall prevention function, frequency detection, torque limits, and hardware protection.
Motor Overload: L1
User constants for motor overloads are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
L1-01
Motor protection selection
Sets whether the motor overload function is enabled or disabled at electric thermal overload relay.
0: Disabled
1: General-purpose motor protection
2: Inverter motor protection
3: Vector motor protection
In some applications when the Inverter power supply is turned off, the thermal value is reset, so even if this constant is set to 1, protection may not be effective.
When several motors are connected to one Inverter, set to 0 and ensure that each motor is installed with a protection device.
0 to 3 1 No Q Q Q
MEMO
BUS
Register
Page
Q 480H
4-6
6-60
5-
55
5
-56
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L1-02
L1-03
L1-04
L1-05
Motor protection time constant
Sets the electric thermal detection time in seconds units.
Usually setting is not necessary.
The factory setting is 150% overload for one minute.
When the motor's overload resistance is known, also set the overload resistance protection time for when the motor is hot started.
Alarm operation selection during motor overheating
Set Multi-function input ter-
A3 (H3-05)
(H3-09) to E and select the operation when the input motor temperature (thermistor) input exceeds the
( alarm detection level [1.17 V
±
5%)].
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-
09.
3: Continue operation (H3 on the Operator flashes).
0.1 to
5.0
0 to 3
Motor overheating operation selection
Motor temperature input filter time constant
Set Multi-function input ter-
A3 (H3-05)
(H3-09) to E and select the operation when the motor temperature (thermistor) input exceeds the operation
( detection level [2.34V
±
5%)].
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-
09.
0 to 2
Set Multi-function input ter-
A3 (H3-05) or
(H3-09) to E and set the primary delay time constant for
0.00 to
10.00
motor temperature (thermistor) inputs in seconds.
1.0 min No
3
1
No
No
0.20 s No
A
A
A
A
A
A
A
A
A
A
A
A
A 481H 6-60
A 482H 6-63
A 483H 6-63
A 484H 6-63
User Constant Tables
Power Loss Ridethrough: L2
User constants for power loss ridethroughs are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L2-01
L2-02
L2-03
L2-04
L2-05
Momentary power loss detection
0: Disabled [main circuit undervoltage (UV1) detection]
1: Enabled [Restarted when the power returns within the time for L2-02. When
L2-02 is exceeded, main circuit undervoltage
(UV1) is detected.]
2: Enabled while CPU is operating. [Restarts when power returns during control operations. Does not detect main circuit undervoltage. (UV1)]
Momentary power loss ridethru time
Ridethrough time, when
Momentary Power Loss
Selection (L2-01) is set to 1, in units of seconds.
Min. baseblock time
Voltage recovery time
Sets the Inverter's minimum baseblock time in units of one second, when the
Inverter is restarted after power loss ridethrough.
Sets the time to approximately 0.7 times the motor secondary circuit time constant.
When an overcurrent or overvoltage occurs when starting a speed search or DC injection braking, increase the set values.
Sets the time required to return the Inverter output voltage to normal voltage at the completion of a speed search, in units of one second.
Sets the time required to recover from 0 V to the maximum voltage.
Undervoltage detection level
Sets the main circuit undervoltage (UV) detection level
(main circuit DC voltage) in
V units.
Usually setting is not necessary.
Insert an AC reactor in the
Inverter input side to lower the main circuit undervoltage detection level.
0 to 2
0 to
25.5
0.1 to
5.0
0.0 to
5.0
150 to
210
*2
0
0.1 s
*1
0.2 s
*1
0.3 s
*1
190 V
*2
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A 485H 6-66
A 486H 6-66
A 487H
A 488H
6-66
6-69
6-67
6-69
A 489H 6-67
5-
57
5
-58
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L2-06
L2-07
KEB deceleration time
Sets in seconds the time required to decelerate from the speed where the deceleration at momentary power loss command (KEB) is input to zero-speed.
Momentary recovery time
Set in seconds the time to accelerate to the set speed after recovery from a momentary power loss.
0.0 to
200.0
0.0 to
25.5
0.0 s
0.0 s
*3
No
No
A
A
A
A
A
A
L2-08
Frequency reduction gain at KEB start
Sets as a percent the about to reduce the output frequency at the beginning of deceleration at momentary power loss (KEB).
Reduction = slip frequency before KEB operation × L2-
08 × 2
0 to
300
100% No A A
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 3. If the setting is 0, the axis will accelerate to the specified speed over the specified acceleration time (C1-01 to C1-08).
A
A
A
A
48AH
48BH
48CH -
-
-
Stall Prevention: L3
User constants for the stall prevention function are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L3-01
Stall prevention selection during accel
0: Disabled (Acceleration as set. With a heavy load, the motor may stall.)
1: Enabled (Acceleration stopped when L3-02 level is exceeded. Acceleration starts again when the current is returned.)
2: Intelligent acceleration mode (Using the L3-02 level as a basis, acceleration is automatically adjusted.
Set acceleration time is disregarded.)
0 to 2 1 No A A A No 48FH
4-20
6-30
L3-02
Stall prevention level during accel
Effective when L3-01 is set to 1 or 2.
Set as a percentage of
Inverter rated current.
Usually setting is not necessary. The factory setting reduces the set values when the motor stalls.
0 to
200
120%
*1
150%
*1
No A A A No 490H
4-20
6-30
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L3-03
L3-04
L3-05
Stall prevention limit during accel
Sets the lower limit for stall prevention during acceleration, as a percentage of the
Inverter rated current, when operation is in the frequency range above E1-06.
Usually setting is not necessary.
Stall prevention selection during decel
0: Disabled (Deceleration as set. If deceleration time is too short, a main circuit overvoltage may result.)
1: Enabled (Deceleration is stopped when the main circuit voltage exceeds the overvoltage level.
Deceleration restarts when voltage is returned.)
2: Intelligent deceleration mode (Deceleration rate is automatically adjusted so that in Inverter can decelerate in the shortest possible time. Set deceleration time is disregarded.)
3: Enabled (with Braking
Resistor Unit)
When a braking option
(Braking Resistor, Braking
Resistor Unit, Braking Unit) is used, always set to 0 or 3.
Stall prevention selection during running
0: Disabled (Runs as set.
With a heavy load, the motor may stall.)
1: Deceleration time 1 (the deceleration time for the stall prevention function is C1-02.)
2: Deceleration time 2 (the deceleration time for the stall prevention function is C1-04.)
L3-06
Stall prevention level during running
Effective when L3-05 is 1 or
2.
Set as a percentage of the
Inverter rated output current.
Usually setting is not necessary.
The factory setting reduces the set values when the motor stalls.
0 to
100
0 to 3
*2
0 to 2
30 to
200
50%
1
1
120%
*1
150%
*1
No
No
No
No
A
Q
A
A
A
Q
A
A
A
Q
No
No
No
Q
No
No
491H
492H
493H
494H
4-20
6-30
4-6
4-20
6-32
4-20
6-52
4-20
6-52
5-
59
5
-60
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L3-11
L3-12
Overvoltage inhibit selection
Overvoltage inhibit voltage level
0: Disabled
1: Enabled
Used to enable or disable the function for inhibiting main circuit overvoltages by reducing the regenerative torque limit according to the main circuit overvoltage level.
If this function is enabled, when the main circuit voltage rises, operation will be performed with the regenerative torque less than the set value.
Sets the main circuit voltage level for which the regenerative torque limit is restricted to 0.
Usually, there is no need to change this setting.
If main circuit overvoltages occur even with the overvoltage inhibit function enabled, reduce this setting.
0 or 1
350 to
390
*3
0
380V
*3
* 1. C6-01 = 1:120 %, C6-01 = 0:150 %
* 2. When using flux vector control, 0 to 2.
* 3. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
No No No A
No No No A
A
A
4C7H
4C8H
4-20
6-34
7-2
4-20
6-34
Reference Detection: L4
User constants for the reference detection function are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L4-01
Speed agreement detection level
L4-02
Speed agreement detection width
Effective when “Desired frequency (ref/setting) agree
1,” “Frequency detection 1,” or “Frequency detection 2" is set for a multi-function output.
Frequencies to be detected are set in Hz units.
Effective when “Frequency
(speed) agree 1,” “Desired frequency (speed) agree 1,” or “Frequency (FOUT) detection 1,” Frequency
(FOUT) detection 2 is set for a multi-function output.
Sets the frequency detection width in Hz units.
0.0 to
400.0
*1
0.0 to
300.0
*2
0.0 to
20.0
0.0 Hz No
2.0 Hz No
A
A
A
A
A
A
A 499H 6-53
A 49AH 6-53
User Constant Tables
Constant
Number
L4-03
L4-04
Name
Speed agreement detection level (+/-)
Speed agreement detection width (+/-)
L4-05
Operation when frequency reference is missing
Description
Effective when “Desired frequency (speed) agree 2,”
“Frequency (FOUT) detection 3,” or “Frequency
(FOUT) detection 4" is set for a multi-function output.
Frequency that should be detected is set in Hz units.
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
-400.0 to
+400.0
*3
-300.0 to
+300.0
*4
0.0 Hz No A A A A 49BH 6-54
Effective when “Frequency
(speed) agree 2,” “Desired frequency (speed) agree 2,”
Frequency (FOUT) detection
3 or “Frequency detection 4" is set for a multi-function output.
Frequency detection width is set in Hz units.
0: Stop (Operation follows the frequency reference.)
1: Operation at 80% speed continues. (At 80% of speed before the frequency reference was lost)
Frequency reference is lost:
Frequency reference dropped over 90% in 400 ms.
0.0 to
20.0
0 or 1
2.0 Hz
0
No
No
A
A
A
A
A
A
A
A
49CH 6-54
49DH 6-74
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
* 3. When C6-01 = 0, -150.0 to +150.0.
* 4. When C6-01 = 1, -400.0 to +400.0.
Fault Restart: L5
User constants for restarting faults are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L5-01
L5-02
Number of auto restart attempts
Sets the number of auto restart attempts.
Automatically restarts after a fault and conducts a speed search from the run frequency.
Auto restart operation selection
Sets whether a fault contact output is activated during fault restart.
0: Not output (Fault contact is not activated.)
1: Output (Fault contact is activated.)
0 to 10
0 or 1
0
0
No
No
A
A
A
A
A
A
A 49EH 6-75
A 49FH 6-75
5-
61
5
-62
Torque Detection: L6
User constants for the torque detection function are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L6-01
L6-02
L6-03
Torque detection selection 1
Torque detection level 1
Torque detection time 1
0: Overtorque/undertorque detection disabled.
1: Overtorque detection only with speed agreement; operation continues after overtorque
(warning).
2: Overtorque detected continuously during operation; operation continues after overtorque (warning).
3: Overtorque detection only with speed agreement; output stopped upon detection (protected operation).
4: Overtorque detected continuously during operation; output stopped upon detection (protected operation).
5: Undertorque detection only with speed agreement; operation continues after overtorque
(warning).
6: Undertorque detected continuously during operation; operation continues after overtorque (warning).
7: Undertorque detection only with speed agreement; output stopped upon detection (protected operation).
8: Undertorque detected continuously during operation; output stopped upon detection (protected operation).
Open loop vector control:
Motor rated torque is set as
100%.
V/f control: Inverter rated current is set as 100%.
Sets the overtorque/undertorque detection time in 1second units.
0 to 8
0 to
300
0.0 to
10.0
0 No
150% No
0.1 s No
A
A
A
A
A
A
A
A
A
A 4A1H 6-56
A 4A2H 6-56
A 4A3H 6-57
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L6-04
L6-05
L6-06
Torque detection selection 2 Output of torque detection 1 is enabled by setting B or 17
Torque detection level 2 for H2 and output of torque detection 1 is enabled
Torque by setting 18 or 18 for H2-
.
detection time 2
0 to 8
0 to
300
0.0 to
10.0
0
150%
0.1 s
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
4A4H 6-57
4A5H 6-57
4A6H 6-57
Torque Limits: L7
User constants for torque limits are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L7-01
Forward drive torque limit
L7-02
L7-03
Reverse drive torque limit
Sets the torque limit value as a percentage of the motor rated torque.
Four individual regions can be set.
Output torque
Positive torque
Forward regenerative torque limit
Reverse
Regenerative state
Regenerative state
No. of motor rotations
Forward
Negative torque
L7-04
Reverse regenerative torque limit
L7-06
Integral time setting for torque limit
0 to
300
0 to
300
0 to
300
0 to
300
Set the integral time for the torque limit. When integral control is set for the torque limit, reduce this setting to increase the change in frequency for the torque limit.
5 to
10000
200%
200%
200%
200%
200 ms
No
No
No
No
No
No
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
A
A
4A7H
4A8H
4A9H
A 4AAH
No 4ACH
4-20
6-49
4-20
6-49
4-20
6-49
4-20
6-49
4-20
6-49
5-
63
5
-64
Constant
Number
Name
L7-07
Control method selection for torque limit during acceleration and deceleration
Description
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
Select the control method for the torque limit during acceleration and deceleration.
0: Proportional control (integral control during constant speed)
1: Integral control
Usually, this constant does not need to be set.
For applications in which the torque limit will be reached during acceleration and deceleration, torque control can be given priority by selecting integral control.
When the torque is limited, the acceleration and deceleration times may increase or the motor speed may not agree with the speed reference value.
0 or 1 0 No No No A No 4C9H
4-20
6-49
Hardware Protection: L8
User constants for hardware protection functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L8-01
Protect selection for internal DB resistor
(Type ERF)
0: Disabled (no overheating protection)
1: Enabled (overheating protection)
L8-02
L8-03
Overheat pre-alarm level
Operation selection after overheat prealarm
Sets the detection temperature for the Inverter overheat detection pre-alarm in ° C.
The pre-alarm detects when the cooling fin temperature reaches the set value.
Sets the operation for when the Inverter overheat prealarm goes ON.
0: Decelerate to stop in deceleration time C1-02.
1: Coast to stop
2: Fast stop in fast-stop time
C1-09.
3: Continue operation
(Monitor display only.)
A fault will be given in setting 0 to 2 and a minor fault will be given in setting 3.
0 or 1
50 to
130
0 to 3
0
95 ° C
*1
3
No
No
No
A
A
A
A
A
A
A
A
A
A 4ADH 6-76
A 4AEH 6-77
A 4AFH 6-77
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
L8-05
Input openphase protection selection
L8-07
Output open-phase protection selection
0: Disabled
1: Enabled (Detects if input current open-phase, power supply voltage imbalance or main circuit electrostatic capacitor deterioration occurs.)
0: Disabled
1: Enabled (Detects one output open-phase.)
2: Enabled (Detects more than one output openphases)
Output open-phase is detected at less than 5% of
Inverter rated current.
When applied motor capacity is small for Inverter capacity, output open-phase may be detected inadvertently or open-phase may not be detected. In this case, set to 0.
0 or 1
0 to 1
0 to 2
0
0
No
No
A
A
A
A
L8-09
L8-10
L8-11
L8-12
L8-15
L8-18
Ground protection selection
0: Disabled
1: Enabled
Cooling fan control selection
Set the ON/OFF control for the cooling fan.
0: ON only when Inverter is
ON
1: ON whenever power is
ON
Cooling fan control delay time
Set the time in seconds to delay turning OFF the cooling fan after the cooling fan
OFF command is received.
Ambient temperature
Set the ambient temperature.
If set to 60 ° C, the Inverter overload protection function
(OL2) will start 20 % earlier.
OL2 characteristics selection at low speeds
Soft CLA selection
0: OL2 characteristics at low speeds disabled.
1: OL2 characteristics at low speeds enabled.
0: Disable (gain = 0)
1: Enable
0 or 1
0 or 1
0 to
300
45 to
60
0 or 1
0 or 1
1
0
60 s
45
1
1
*2
° C
No
No
No
No
No
No
A
A
A
A
A
A
* 1. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
* 2. When the control method is changed, the factory setting will change. The V/f control factory setting is given.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
4B1H
4B3H
4B5H
4B6H
4B7H
4B8H
4BBH
4BEH -
-
-
-
-
-
-
-
5-
65
5
-66
N: Special Adjustments
The following settings are made with the special adjustments constants (N constants): Hunting prevention, speed feedback detection control, high-slip braking, and feed forward control.
Hunting Prevention Function: N1
User constants for hunting prevention are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
N1-01
Huntingprevention function selection
N1-02
Huntingprevention gain
0: Hunting-prevention function disabled
1: Hunting-prevention function enabled
The hunting-prevention function suppresses hunting when the motor is operating with a light load.
This function is enabled in V/f control method only.
If high response is to be given priority over vibration suppression, disable the hunting-prevention function.
Set the hunting-prevention gain multiplication factor.
Normally, there is no need to make this setting.
Make the adjustments as follows:
• If vibration occurs with light load, increase the setting.
• If the motor stalls, reduce the setting.
If the setting is too large, the voltage will be too suppressed and the motor may stall.
0 or 1
0.00 to
2.50
1
1.00
No
No
A
A
A No No 580H 6-47
A No No 581H
4-18
6-47
User Constant Tables
Speed Feedback Protection Control Functions: N2
User constants for speed feedback protection control functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
N2-01
N2-02
Speed feedback detection control
(AFR) gain
Set the internal speed feedback detection control gain using the multiplication function.
Normally, there is no need to make this setting.
Adjust this constant as follows:
• If hunting occurs, increase the set value.
• If response is low, decrease the set value.
Adjust the setting by 0.05 at a time, while checking the response.
Speed feedback detection control
(AFR) time constant
Set the time constant to decide the rate of change in the speed feedback detection control.
N2-03
Speed feedback detection control
(AFR) time constant 2
Set the time constant to decide the amount of change in the speed.
0.00 to
10.00
0 to
2000
0 to
2000
1.00
No No No A No 584H
4-18
6-48
50 ms No No No A No 585H 6-48
750 ms No No No A No 586H 6-48
High-slip Braking: N3
User constants for high-slip braking are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
N3-01
N3-02
High-slip braking deceleration frequency width
Sets the frequency width for deceleration during high-slip braking as a percent, taking the Maximum Frequency
(E1-04) as 100%.
High-slip braking current limit
Sets the current limit for deceleration during high-slip braking as a percent, taking the motor rated current as
100%. The resulting limit must be 150% of the Inverter rated current or less.
1 to 20 5%
100 to
200
150%
No
No
A
A
A
A
No
No
No
No
588H
589H -
-
5-
67
5
-68
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
N3-03
N3-04
High-slip braking stop dwell time
Set in seconds the dwell time for the output frequency for
FMIN (1.5 Hz) during V/f control.
Effective only during deceleration for high-slip braking.
High-slip braking OL time
Set the OL time when the output frequency does not change for some reason during deceleration for high-slip braking.
0.0 to
10.0
30 to
1200
1.0 s
40 s
No
No
A
A
A
A
No
No
No 58AH
No 58BH -
-
Feed Forward: N5
User constants for the feed forward control are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
N5-01
Feed forward control selection
N5-02
Motor acceleration time
Select the feed forward control.
0: Disabled
1: Enabled
Set the time required to accelerate the motor at the rated torque (T
100
) to the rated speed (Nr).
J: GD
2
/4, P: Motor rated output ta =
2 π x J [kgm2] x Nr [min-1]
60 x T100 [N x m]
[s]
However,
T100 =
60
2 x
P [kW]
Nr [min-1]
× 103 [N x m]
0 or 1
0.001 to
10.000
0
0.178 s
*
No No No No A 5B0H
4-20
6-141
No No No No A 5B1H
4-20
6-141
N5-03
Feed forward proportional gain
Set the proportional gain for feed forward control.
Speed reference response will increase as the setting of
N5-03 is increased.
0.00 to
100.00
1.0
No No No No A 5B2H
4-20
6-141
N5-04
Response frequency for speed command
Sets the response frequency to a speed command in units of 0.01 Hz.
Used when the machine rigidity is high and the N5-
03 is correctly adjusted.
Usually, setting is not required.
0.00 to
50.00
40.00
Hz
No No
* The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter for 0.4 kW is given.
No No A 5B3H
4-20
6-141
User Constant Tables
Digital Operator Constants: o
The following settings are made with the Digital Operator constants (o constants): Multi-function selections and the copy function.
Monitor Select: o1
User constants for Digital Operator Displays are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page o1-01 o1-02 o1-03
Monitor selection
Monitor selection after power up
Frequency units of reference setting and monitor
Set the number of the monitor item to be displayed in the earliest 4 monitor items.
(U1 )
The output monitor voltage
(factory setting) can be changed.
Sets the monitor item to be displayed when the power is turned on.
1: Frequency reference
2: Output frequency
3: Output current
4: The monitor item set for o1-01
Sets the units that will be set and displayed for the frequency reference and frequency monitor.
0: 0.01 Hz units
1: 0.01% units
(Maximum output frequency is 100%)
2 to 39: min
-1
units (Sets the motor poles.)
40 to 39999:
User desired display
Set the desired values for setting and display for the max. output frequency.
4 to 99
1 to 4
0 to
39999
6
1
0
Yes
Yes
No
A
A
A
A
A
A
A
A
A
A 500H -
A 501H 6-147
A 502H
6-147
6-164
Set 4-digit number excluding the decimal point.
Set the number of digits below the decimal point to display.
Example: When the max. output frequency value is
200.0, set 12000
5-
69
5
-70
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page o1-04 o1-05
Setting unit for frequency constants related to V/ f characteristics
Set the setting unit for frequency reference-related constants.
0: Hz
1: min
− 1
LCD brightness adjustment
LCD Contrast
Set a smaller value to lighten the LCD and a larger value to darken the LCD (standard:
3).
0 or 1
0 to 5
0
3
No
Yes
No
A
No
A
No
A
A
A
503H 6-147
504H -
Multi-function Selections: o2
User constants for Digital Operator key functions are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page o2-01 o2-02
LOCAL/
REMOTE key enable/ disable
STOP key during control circuit terminal operation o2-03
User constant initial value o2-04 kVA selection
Sets the Digital Operator
Local/Remote Key
0: Disabled
1: Enabled (Switches between the Digital
Operator and the constant settings.)
Sets the Stop Key in the run mode.
0: Disabled (When the Run
Command is issued from and external terminal, the
Stop Key is disabled.)
1: Enabled (Effective even during run.)
Clears or stores user initial values.
0: Stores/not set
1: Begins storing (Records the set constants as user initial values.)
2: All clear (Clears all recorded user initial values)
When the set constants are recorded as user initial values, 1110 will be set in A1-
03.
Do not set unless using a control board from an
Inverter with a different capacity.
0 or 1
0 or 1
0 to 2
0 to FF
1
1
0
0
*
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A 505H 6-147
A 506H 6-148
A 507H
4-17
6-148
A 508H -
User Constant Tables
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page o2-05 o2-06 o2-07 o2-08 o2-10
Frequency reference setting method selection
Operation selection when digital operator is disconnected
When the frequency reference is set on the Digital
Operator frequency reference monitor, sets whether the Enter Key is necessary.
0: Enter Key needed
1: Enter Key not needed
When set to 1, the Inverter accepts the frequency reference without Enter Key operation.
Sets the operation when the
Digital Operator is disconnected.
0: Disabled (Operation continues even if the
Digital Operator is disconnected.)
1: Enabled (OPR is detected at Digital Operator disconnection. Inverter output is cut off, and fault contact is operated.)
Cumulative operation time setting
Sets the cumulative operation time in hour units.
Operation time is calculated from the set values.
Cumulative operation time selection
Fan operation time setting
0: Cumulative time when the Inverter power is on.
(All time while the
Inverter power is on is accumulated.)
1: Cumulative Inverter run time. (Only Inverter output time is accumulated.)
Set the initial value of the fan operation time using time units.
The operation time accumulates from the set value.
0 or 1
0 or 1
0 to
65535
0 or 1
0 to
65535
0
0
0 hr
0
0 hr
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A o2-12 o2-14
Fault trace/ fault history clear function
Output power monitor clear selection
0: Disabled (U2 and U3 constants are on hold.)
1: Enabled (Initializes U2 and U3 constants.)
0: Holds output power monitor.
1: Initializes output power monitor. (Returns to 0.)
0 or 1
0 or 1
0
0
No
No
A
A
* The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
509H 6-148
50AH -
50BH 6-148
50CH
50EH 6-148
510H -
-
512H 5-77
5-
71
5
-72
Copy Function: o3
User constants for the copy function are shown in the following table.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page o3-01
Copy function selection
0: Normal operation
1: READ (Inverter to
Operator)
2: COPY (Operator to
Inverter)
3: Verify (compare)
0 to 3 0 No A A A A 515H 6-150 o3-02
Read permitted selection
0: Read prohibited
1: Read permitted
0 or 1 0 No A A A A 516H 6-150
User Constant Tables
T: Motor Autotuning
The following settings are made with the motor autotuning constants (T constants): Settings for autotuning.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Page
T1-01
Autotuning mode selection
Set the location where the autotuned motor constants are to be stored.
1: E1 to E2 (motor 1)
2: E3 to E4 (motor 2)
Set the autotuning mode.
0: Rotational autotuning
1: Stationary autotuning 1
2: Stationary autotuning for line-to-line resistance only
4: Stationary autotuning 2
1 or 2
0 to 2
*1
0 to 2,
4
*1
1
2
*8
No Yes Yes Yes Yes 700H 4-13
No Yes Yes Yes Yes 701H 4-10
Set the output power of the motor in kilowatts.
0.00 to
650.00
0.40 kW
*4
No Yes Yes Yes Yes 702H 4-13
Set the rated voltage of the motor in volts.
0.0 to
255.0
*2
200.0 V
*2
No No No Yes Yes 703H 4-13
Set the rated current of the motor in amps.
0.32 to
6.40
*3
1.90 A
*4
Set the base frequency of the motor in hertz.
0.0 to
400.0
*7
0.0 to
300.0
*5
60.0
Hz
No Yes Yes Yes Yes 704H 4-13
No No No Yes Yes 705H 4-13
Set the number of motor poles.
2 to 48 poles
4 poles No No No Yes Yes 706H 4-13
Set the base speed of the motor in min
-1
.
0 to
24000
1750 min
-1
No No No Yes Yes 707H 4-13
T1-08
Number of
PG pulses when turning
Set the number of pulses per revolution for the PG being used (pulse generator or encoder) without any multiplication factor.
Set the current value recorded in the motor’s test results for a motor without a load.
Displayed only when Stationary autotuning 2 is selected (T1-01 = 4).
0 to
60000
0.00 to
1.89
*6
600
1.20A
*4
No
No
No
No
No
No
No
Yes
Yes 708H 4-13
Yes 709H 4-13
* 1. Set T1-02 and T1-04 when 2 is set for T1-01. Only set value 2 is possible for V/f control or V/f control with PG.
* 2. These are values for a 200 V Class Inverter. Values for a 400 V Class Inverter are double.
* 3. The setting range is from 10% to 200% of the Inverter rated output current. The value for a 200 V Class Inverter for 0.4 kW is given.
* 4. The factory setting depends on the Inverter capacity. The values for a 200 V Class Inverter for 0.4 kW are given.
* 5. When C6-01 = 1, the upper limit is 400.00.
* 6. The setting range depends on the Inverter capacity. The value for a 200 V Class Inverter for 0.4 kW is given.
* 7. When C6-01 = 0, the upper limit is 150.0.
* 8. When the control method is changed, the factory setting will change. The V/f control factory setting is given.
5-
73
5
-74
U: Monitor Constants
The following settings are made with the monitor constants (U constants): Setting constants for monitoring in drive mode.
Status Monitor Constants: U1
The constants used for monitoring status are listed in the following table.
Constant
Number
U1-01
U1-02
Name
Frequency reference
Output frequency
U1-03
Output current
Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Monitors/sets the frequency reference value.*
Monitors the output frequency.*
Monitors the output current.
10 V: Max. frequency
(0 to ± 10 V possible)
10 V: Max. frequency
(0 to ± 10 V possible)
10 V: Inverter rated output current
(0 to +10 V, absolute value output)
0.01
Hz
0.01
Hz
0.1
A
A
A
A
A
A
A
A
A
A
A
A
A
40H
41H
42H
U1-04
Control method
Checks the current control method.
(Cannot be output.) A A A A 43H
U1-05 Motor speed
Monitors the detected motor speed.*
10 V: Max. frequency
(0 to ± 10 V possible)
0.01
Hz
No A A A 44H
U1-06
Output voltage
Monitors the output voltage reference value in the
Inverter.
10 V: 200 VAC (400 VAC)
(0 to +10 V output)
U1-07
U1-08
DC bus voltage
Output power
Monitors the main DC voltage in the Inverter.
Monitors the output power
(internally detected value).
10 V: 400 VDC (800 VDC)
(0 to +10 V output)
10 V: Inverter capacity
(max. applicable motor capacity)
(0 to ± 10 V possible)
U1-09
Torque reference
Monitor in internal torque reference value for vector control.
10 V: Motor rated torque
(0 to ± 10 V possible)
* The unit is set in o1-03 (frequency units of reference setting and monitor).
0.1
V
1 V
0.1 kW
A
A
A
A
A
A
A
A
A
A
A
A
45H
46H
47H
0.1% No No A A 48H
User Constant Tables
Constant
Number
Name Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
U1-10
Input terminal status
Shows input ON/OFF status
U1-10=
1: FWD command
(S1) is ON.
1: REV command
(S2) is ON.
1: Multi input 1
(S3) is ON.
1: Multi input 2
(S4) is ON.
1: Multi input 3
(S5) is ON.
1: Multi input 4
(S6) is ON.
1: Multi input 5
(S7) is ON.
1: Multi input 6
(S8) is ON.
(Cannot be output.) A A A A 49H
U1-11
Output terminal status
U1-12
Operation status
Shows output ON/OFF status.
U1-11=
1: Multi-function contact output
(M1-M2) is ON.
1: Multi-funtion contact output 1
(P1) is ON.
1: Multi-funtion contact output 2
(P2) is ON.
Not used (always 0).
1: Error output
(MA/AB-MC) is ON.
(Cannot be output.)
Inverter operating status.
U1-12=
1: Run
1: Zero speed
1: Reverse
1: Reset signal
input
1: Speed agree
1: Inverter
ready
1: Minor fault
(Cannot be output.) -
A
A
A
A
A
A
A
A
4AH
4BH
U1-13
1: Major fault
Cumulative operation time
Monitors the total operating time of the Inverter.
The initial value and the operating time/power ON time selection can be set in o2-07 and o2-08.
U1-14
Software
No. (flash memory)
(Manufacturer’s ID number)
U1-15
U1-16
Terminal
A1 input voltage
Terminal
A2 input current
(voltage)
(Cannot be output.)
(Cannot be output.)
Monitors the input voltage of the voltage frequency reference. An input of 10 V corresponds to 100%.
10 V: 100% (10 V)
(0 to ± 10 V possible)
Monitors the input current of the multi-function analog input.
An input of 20 mA corresponds to 100%.
20 mA: 100% (4 to 20 mA)
(0 to 10 V, sible)
0 to ±10 V pos-
1 hr
-
A
A
A
A
A
A
A
A
4CH
4DH
0.1% A A A A 4EH
0.1% A A A A 4FH
5-
75
5
-76
Constant
Number
U1-17
U1-18
Name
Terminal
A3 input voltage
Motor secondary current (Iq)
Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Monitors the input voltage of the multi-function analog input.
An input of 10 V corresponds to 100%.
10 V: 100% (10 V)
(0 to ±10 V possible)
Monitors the calculated value of the motor secondary current.
The motor rated secondary current corresponds to
100%.
10 V:Motor rated secondary current)
(0 to ±10 V output)
0.1% A A A A 050H
0.1% A A A A 51H
U1-19
Motor exciting current
(Id)
Monitors the calculated value of the motor excitation current.
The motor rated secondary current corresponds to
100%.
10 V:Motor rated secondary current)
(0 to ±10 V output)
0.1% No No A A 52H
U1-20
Output frequency after soft-start
Monitors the output frequency after a soft start.
The frequency given does not include compensations, such as slip compensation.
The unit is set in o1-03.
U1-21 ASR input
Monitors the input to the speed control loop.
The maximum frequency corresponds to 100%.
10 V: Max. frequency
(0 to ± 10 V possible)
10 V: Max. frequency
(0 to ± 10 V possible)
U1-22 ASR output
U1-24
U1-26
U1-27
U1-28
PID feedback value
Monitors the output from the speed control loop.
The motor rated secondary current corresponds to
100%.
Monitors the feedback value when PID control is used.
The input for the max. frequency corresponds to
100%.
Output voltage reference (Vq)
Monitors the Inverter internal voltage reference for motor secondary current control.
Output voltage reference (Vd)
Software
No. (CPU)
Monitors the Inverter internal voltage reference for motor excitation current control.
(Manufacturer’s CPU software No.)
10 V:Motor rated secondary current)
(0 to ± 10 V possible)
10 V: Max. frequency
(0 to ± 10 V possible)
10 V: 200 VAC (400 VAC)
(0 to ± 10 V possible)
10 V: 200 VAC (400 VAC)
(0 to ± 10 V possible)
(Cannot be output.)
0.01
Hz
0.01
%
0.01
%
0.01
%
0.1
V
0.1
V
-
A
No
No
A
No
No
A
A
A
A
A
No
No
A
A
No
No
A
A
A
A
A
A
A
A
A
A
A
53H
54H
55H
57H
59H
5AH
5BH
User Constant Tables
Constant
Number
Name Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
U1-29
Output power lower
4 digits
Monitors the Inverter’s output power. The display is split into upper digits and lower digits in the following way.
U1-30
U1-30
.
kWH
U1-29
Output power upper
5 digits
Example: If the output power is 12345678.9 kWh, the display will be as follows:
U1-29: 678.9 kWH
U1-30: 12345 MWH
Range: 0.0 to 32767999.9
(Cannot be output.)
U1-31 LED check
U1-32
U1-33
Lights all LEDs on the Digital Operator JVOP-161.
(Cannot be output.)
ACR output of q axis
Monitors the current control output value for the motor secondary current.
10 V: 100%
(0 to ± 10 V possible)
ACR output of d axis
Monitors the current control output value for the motor excitation current.
10 V: 100%
(0 to ± 10 V possible)
U1-34
U1-35
U1-36
OPE fault constant
Zero-servo movement pulses
PID input volume
Shows the first constant number where an OPE fault was detected.
(Cannot be output.)
Shows the number of PG pulses times 4 for the movement range when stopped at zero.
(Cannot be output.)
PID feedback volume
Given as maximum frequency/100%
10 V: Max. frequency
(0 to ± 10 V possible)
U1-37
U1-38
PID output volume
PID target value
PID control output
Given as maximum frequency/100%
PID target value
Given as maximum frequency/100%
10 V: Max. frequency
(0 to ± 10 V possible)
10 V: Max. frequency
U1-39
MEMO-
BUS communications error code
Shows MEMOBUS errors.
U1-39=
1: CRC error
1: Data length error
Not used (always 0).
1: Parity
error
1: Overrun
error
1: Framing
error
1: Timeout
Not used (always 0).
(Cannot be output.) kWH
MW
H
0.1
%
0.1
%
1
0.01
%
0.01
%
0.01
%
-
-
-
A
A
A
No
No
A
No
A
A
A
A
A
A
A
No
No
A
No
A
A
A
A
A
A
A
A
A
A
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
05CH
05DH
3CH
5FH
60H
61H
62H
63H
64H
65H
66H
5-
77
5
-78
Constant
Number
Name Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
U1-40
U1-44
U1-45
Cooling fan operating time
Monitors the total operating time of the cooling fan.
The time can be set in 02-
10.
ASR output without filter
Monitors the output from the speed control loop (i.e., the primary filter input value). 100% is displayed for rated secondary current of the motor.
Feed forward control output
(Cannot be output.)
10 V: Rated secondary current of motor
(-10 V to 10 V)
Monitors the output from feed forward control. 100% is displayed for rated secondary current of the motor.
10 V: Rated secondary current of motor
(-10 V to 10 V)
1 hr
0.01
%
0.01
%
A
No
No
A
No
No
A
No
No
A
A
A
68H
6BH
6CH
User Constant Tables
Fault Trace: U2
User constants for error tracing are shown in the following table.
Constant
Number
Name Description
Output Signal Level
During Multi-Function
Analog Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
U2-01
Current fault
U2-05
Output current at fault
The contents of the current fault.
U2-02
U2-03
Previous fault
The contents of the error that occurred just prior to the current fault.
Reference frequency at fault
The reference frequency when the previous fault occurred.
U2-04
Output frequency at fault
The output frequency when the previous fault occurred.
The output current when the previous fault occurred.
-
-
0.01
Hz
0.01
Hz
0.1
A
A A A A 80H
A A A A 81H
A A A A 82H
A A A A 83H
A A A A 84H
U2-06
Motor speed at fault
The motor speed when the previous fault occurred.
0.01
Hz
No A A A 85H
U2-07
U2-08
U2-09
Output voltage reference at fault
The output reference voltage when the previous fault occurred.
DC bus voltage at fault
Output power at fault
The main current DC voltage when the previous fault occurred.
The output power when the previous fault occurred.
(Cannot be output.)
U2-10
U2-11
Torque reference at fault
The reference torque when the previous fault occurred. The motor rated torque corresponds to 100%.
Input terminal status at fault
The input terminal status when the previous fault occurred.
The format is the same as for
U1-10.
0.1
V
1 V
0.1 kW
0.1% No
-
A
A
A
A
A
A
A
No
A
A
A
A
A
A
A
A
A
A
A
86H
87H
88H
89H
8AH
U2-12
U2-13
Output terminal status at fault
The output terminal status when the previous fault occurred. The format is the same as for U1-11.
Operation status at fault
The operating status when the previous fault occurred. The format is the same as for U1-12.
-
A
A
A
A
A
A
A
A
8BH
8CH
U2-14
Cumulative operation time at fault
The operating time when the previous fault occurred.
1 hr
A A A A 8DH
Note 1. The following faults are not included in the fault trace: CPF00, 01, 02, 03, UV1, and UV2.
2. If the PUF fault is already indicated in U2-xx or U3-xx, even if the PUF fault is detected again, the fault trace is not updated. (SPEC: E or later only)
5-
79
5
-80
Fault History: U3
User constants for the error log are shown in the following table.
Constant
Number
Name Description
Output Signal Level During Multi-Function Analog
Output
Min.
Unit
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
U3-01
Most recent fault
The error contents of 1st previous fault.
U3-02
U3-03
U3-04
U3-05
Second most recent fault
Third most recent fault
The error contents of 2nd previous fault.
The error contents of 3rd previous fault.
Fourth most recent fault
The error contents of 4th previous fault.
Cumulative operation time at fault
The total operating time when the 1st previous fault occurred.
(Cannot be output.)
-
-
-
-
1 hr
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
90H
91H
92H
93H
94H
U3-06
U3-07
Accumulated time of second fault
The total operating time when the 2nd previous fault occurred.
Accumulated time of third fault
The total operating time when the 3rd previous fault occurred.
1 hr
1 hr
A
A
A
A
A
A
A
A
95H
96H
U3-08
Accumulated time of fourth fault
The total operating time when the 4th previous fault occurred.
1 hr
A A A A 97H
Note 1. The following errors are not recorded in the error log: CPF00, 01, 02, 03, UV1, and UV2.
2. If the PUF fault is already indicated in U2-xx or U3-xx, even if the PUF fault is detected again, the fault trace is not updated. (SPEC: E or later only)
User Constant Tables
Factory Settings that Change with the Control Method (A1-02)
The factory settings of the following user constants will change if the control method (A1-02) is changed.
Constant
Number
Name b3-01 Speed search selection b3-02 Speed search operating current b8-02 Energy-saving gain
Setting Range
0 to 3
0 to 200
0.0 to 10.0
Unit
1
1%
0.1
V/f Control
A1-02=0
2
Factory Setting
V/F with
PG
A1-02=1
Open
Loop
Vector
A1-02=2
3 2
Flux
Vector
A1-02=3
-
120
-
-
-
100
0.7
-
1.0
b8-03 Energy-saving filter time constant
C3-01 Slip compensation gain
C3-02
Slip compensation primary delay time constant
C4-02
Torque compensation primary delay time constant
C5-01 ASR proportional (P) gain 1
C5-02 ASR integral (I) time 1
C5-03 ASR proportional (P) gain 2
C5-04 ASR integral (I) time 2
0.00 to 10.00
0.0 to 2.5
0 to 10000
0 to 10000
0 to 300.00
0.000 to 10.000
0.00 to 300.00
0.000 to 10.000
0.01 s
0.1
1 ms
1 ms
0.01
0.001 s
0.01
0.001 s
-
0.0
2000
200
-
-
-
-
-
-
-
200
0.20
0.200
0.02
0.050
0.50
*1
1.0
200
20
-
-
-
-
0.01
1.0
-
-
*1
20.00
0.500
20.00
0.500
E1-04
E3-02
E1-05
Max. output frequency (FMAX)
E3-03 Max. voltage (VMAX)
*4
40.0 to 400.0
*2
40.0 to 300.0
*5
0.0 to 255.0
(0.0 to 510.0)
0.0 to 400.0
*2
0.1 Hz
0.1 V
60.0
*3
200.0
*3
60.0
*3
200.0
*3
60.0
200.0
E1-06
E3-04
E1-07
E3-05
Base frequency (FA)
Mid. output frequency (FB)
0.0 to 300.0
*5
0.0 to 400.0
*2
0.0 to 300.0
*5
0.0 to 255.0
(0.0 to 510.0)
0.1 Hz
0.1 Hz
60.0
*3
3.0
*3
60.0
*3
3.0
*3
60.0
3.0
E1-08
E3-06 Mid. output frequency voltage (VC)
*4 0.1 V
15.0
*3
15.0
*3
11.0
E1-09
E3-07
Min. output frequency (FMIN)
E1-10
E3-08 Min. output frequency voltage (VMIN)
*4
F1-09 Overspeed detection delay time
L8-18 Soft CLA selection
0.0 to 400.0
*2
0.0 to 300.0
*5
0.0 to 255.0
(0.0 to 510.0)
0.0 to 2.0
0, 1
0.1 Hz
0.1 V
0.1 s
1
1.5
*3
9.0
*3
-
1
1.5
*3
9.0
*3
1.0
1
0.5
2.0
-
1
* 1. For Inverters with a capacity of 55 kW or more, the factory setting is 2.00 for open-loop vector control and 0.05 for flux vector control.
* 2. When C6-01 = 0, the upper limit is 150.0.
* 3. Settings vary as shown in the following tables depending on the Inverter capacity and E1-03.
* 4. The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
* 5. When C6-01 = 1, the upper limit is 400.0.
60.0
200.0
60.0
0.0
0.0
0.0
0.0
0.0
0
5-
81
5
-82
200 V and 400 V Class Inverters of 0.4 to 1.5 kW
Constant
Number
Unit
E1-03
0 1 2
E1-04 Hz 50.0
60.0
60.0
6
Factory Setting
7 8
60.0
60.0
50.0
9 A B C D E F
50.0
60.0
60.0
90.0
120.0
180.0
60.0
Open
Loop
Vector
Control
Flux
Vector
Control
E1-05
*
V 200.0
200.0
200.0
E1-06 Hz 50.0
60.0
50.0
200.0
60.0
200.0
50.0
200.0
50.0
200.0
60.0
200.0
60.0
200.0
50.0
200.0
50.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
E1-07 Hz 2.5
E1-08
*
V 15.0
3.0
15.0
3.0
15.0
3
72.0
3.0
15.0
4
50.0
25.0
25.0
35.0
5
50.0
50.0
30.0
30.0
35.0
50.0
2.5
19.0
2.5
24.0
3.0
19.0
3.0
24.0
3.0
15.0
3.0
15.0
3.0
15.0
3.0
15.0
60.0
60.0
3.0
11.0
0.0
0.0
E1-09 Hz 1.3
E1-10
*
V 9.0
1.5
9.0
1.5
9.0
1.5
9.0
1.3
8.0
1.3
9.0
1.5
8.0
1.5
9.0
1.3
11.0
1.3
1.5
1.5
13.0
11.0
15.0
1.5
9.0
1.5
9.0
1.5
9.0
1.5
9.0
0.5
2.0
0.0
0.0
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
200 V and 400 V Class Inverters of 2.2 to 45 kW
Constant
Number
E1-03
Unit
0 1 2
E1-04 Hz 50.0
60.0
60.0
E1-05
*
3 4 5
72.0
50.0
50.0
6
Factory Setting
7 8
60.0
60.0
50.0
9 A B C D E F
50.0
60.0
60.0
90.0
120.0
180.0
60.0
Open
Loop
Vector
Control
Flux vector control
60.0
60.0
V 200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
60.0
E1-06 Hz 50.0
60.0
50.0
E1-07
*
Hz 2.5
3.0
3.0
E1-08
*
V 14.0
E1-09 Hz 1.3
14.0
1.5
14.0
1.5
E1-10
*
V 7.0
7.0
7.0
3.0
25.0
25.0
14.0
35.0
50.0
1.5
7.0
1.3
6.0
1.3
7.0
30.0
30.0
2.5
35.0
50.0
18.0
1.5
6.0
1.5
7.0
1.3
9.0
2.5
1.3
11.0
3.0
1.5
9.0
3.0
1.5
13.0
3.0
23.0
18.0
23.0
14.0
1.5
7.0
3.0
1.5
7.0
3.0
1.5
7.0
3.0
14.0
14.0
14.0
1.5
7.0
3.0
11.0
0.5
2.0
0.0
0.0
0.0
0.0
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
200 V Class Inverters of 55 to 110 kW and 400 V Class Inverters of 55 to 300 kW
Constant
Number
E1-03
Unit
0 1 2
E1-04 Hz 50.0
60.0
60.0
6
Factory Setting
7 8
60.0
60.0
50.0
9 A B C D E F
50.0
60.0
60.0
90.0
120.0
180.0
60.0
Open
Loop
Vector
Control
Flux vector control
E1-05
*
V 200.0
200.0
200.0
E1-06 Hz 50.0
60.0
50.0
200.0
60.0
200.0
50.0
200.0
50.0
200.0
60.0
200.0
60.0
200.0
50.0
200.0
50.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
200.0
60.0
E1-07 Hz 2.5
E1-08
*
V 12.0
3.0
12.0
3.0
12.0
3
72.0
3.0
12.0
4
50.0
25.0
25.0
35.0
5
50.0
50.0
30.0
30.0
35.0
50.0
2.5
15.0
2.5
20.0
3.0
15.0
3.0
20.0
3.0
12.0
3.0
12.0
3.0
12.0
3.0
12.0
60.0
60.0
3.0
11.0
0.0
0.0
E1-09 Hz 1.3
E1-10
*
V 6.0
1.5
6.0
1.5
6.0
1.5
6.0
1.3
5.0
1.3
6.0
1.5
5.0
1.5
6.0
1.3
7.0
1.3
9.0
1.5
7.0
1.5
11.0
1.5
6.0
1.5
6.0
1.5
6.0
1.5
6.0
0.5
2.0
0.0
0.0
* The settings shown are for 200 V Class Inverters. The values will double for 400 V Class Inverters.
User Constant Tables
Factory Settings that Change with the Inverter Capacity (o2-04)
The factory settings of the following user constants will change if the Inverter capacity (o2-04) is changed.
200 V Class Inverters
Constant
Number
o2-04 b8-03 b8-04
Name
Inverter Capacity kVA selection
Energy-saving filter time constant
Energy-saving coefficient
Unit kW 0.4
0.75
0 1
s
288.20
223.70
C6-01 CT/VT selection -
1
0
1
0
C6-02
-
Carrier frequency selection (when VT is selected)
*1 *4
Carrier frequency selection upper limit (when
VT is selected)
*1
-
6
6
*2
6
6
*2
1.5
6
2
1
0
6
*2
2.2
3
Factory Setting
3.7
6
4
5.5
5
0.50 (Open loop vector control)
169.40
156.80
6
1
0
*2
6
122.90
1
0
*2
6
94.75
1
0
6
7.5
6
72.69
1
0
6
11
7
70.44
6
1
0
6
*2
15
6
8
63.13
1
0
6
*2
E2-01
(E4-01)
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
Motor rated current
Motor rated slip
Motor no-load current
Motor line-to-line resistance
Motor leak inductance
A
Hz
A
Ω
%
1.90
2.90
1.20
9.842
18.2
3.30
2.50
1.80
5.156
13.8
6.20
2.60
2.80
1.997
18.5
8.50
2.90
3.00
1.601
18.4
14.00
2.73
4.50
0.771
19.6
19.60
1.50
5.10
0.399
18.2
26.60
1.30
8.00
0.288
15.5
39.7
1.70
11.2
0.230
19.5
53.0
1.60
15.2
0.138
17.2
E2-10
L2-02
L2-03
Motor iron loss for torque compensation
Momentary power loss ridethru time
Min. baseblock (BB) time
W s s
14
0.1
0.1
26
0.1
0.2
53
0.2
0.3
77
0.3
0.4
112
0.5
0.5
172
1.0
0.6
262
1.0
0.7
245
1.0
0.8
272
2.0
0.9
L2-04 Voltage recovery time
L2-08
Frequency reduction gain at KEB start
° s
C
0.3
95
0.3
95
0.3
95
0.3
95
0.3
95
0.3
95
0.3
95
0.3
95
0.3
95
L8-02 Overheat pre-alarm level ° C 95 95 95 100 95 95 95 95 90
N5-02 Motor acceleration time s 0.178
0.142
0.166
0.145
0.154
0.168
0.175
0.265
0.244
5-
83
5
-84
Constant
Number
o2-04 b8-03 b8-04
Name
Inverter Capacity kVA selection
Energy-saving filter time constant
Energy-saving coefficient
Unit kW
-
s
18.5
9
57.87
22
A
30
B C
Factory Setting
37
0.50 (Open loop vector control)
51.79
46.27
38.16
45
D
35.78
55
E
75
F
90
10
110
11
2.00 (Open loop vector control)
31.35
23.10
20.65
18.12
C6-01 CT/VT selection -
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
C6-02
-
Carrier frequency selection (when VT is selected)
*1 *4
Carrier frequency selection upper limit (when
VT is selected)
*1
E2-01
(E4-01)
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
Motor rated current
Motor rated slip
Motor no-load current
Motor line-to-line resistance
Motor leak inductance
E2-10
L2-02
Motor iron loss for torque compensation
Momentary power loss ridethru time
L2-03
Min. baseblock (BB) time
L2-04 Voltage recovery time
-
-
A
Hz
A
Ω
%
W s s s
6
6
*2
65.8
1.67
15.7
0.101
20.1
505
2.0
1.0
0.6
6
*2
6
77.2
1.70
18.5
0.079
19.5
538
2.0
1.0
0.6
6
105.0
1.80
21.9
0.064
20.8
699
2.0
1.1
0.6
3
4
*2
131.0
1.33
38.2
0.039
18.8
823
2.0
1.1
0.6
3
4
*2
160.0
1.60
44.0
0.030
20.2
852
2.0
1.2
1.0
3
4
*2
190.0
1.43
45.6
0.022
20.5
960
2.0
1.2
1.0
2
4
*2
260.0
1.39
72.0
0.023
20.0
1200
2.0
1.3
1.0
2
4
*2
260.0
1.39
72.0
0.023
20.0
1200
2.0
1.5
1.0
1
1
*2
260.0
1.39
72.0
0.023
20.0
1200
2.0
1.7
1.0
L2-08
Frequency reduction gain at KEB start
° C 95 95 95 95 95 95 95 95 95
L8-02 Overheat pre-alarm level ° C 100
N5-02 Motor acceleration time s 0.317
90
0.355
90
0.323
95
0.320
100
0.387
105
0.317
110
0.533
100
0.592
110
*3
0.646
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V Class
Inverters with outputs of 0.4 to 11 kW.
* 1. The factory settings when VT is selected are given.
When CT is selected, the factory settings are as follows for Inverters of any capacity:
Carrier frequency selection: 1 (2.0 kHz)
Carrier frequency selection upper limit: 2.5 kHz
* 2. The setting of C6-02 changes the carrier frequency selection as follows:
0: Low-noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz
* 3. 95 for Inverter SPEC Type A.
* 4. When setting the carrier frequency of 200 V Class Inverters of 30 kW or more to a value larger than the factory setting, reduce the value of the Inverter rated output current.
User Constant Tables
400 V Class Inverters
Constant
Number
o2-04 b8-03 b8-04
Name
Inverter Capacity kVA selection
Energy-saving filter time constant
Energy-saving coefficient
Unit kW 0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
20 21 22 23 24 25 26 27
s
576.40
447.40
338.80
0.50 (Open loop vector control)
313.60
Factory Setting
245.80
236.44
189.50
145.38
11
28
140.88
15
29
126.26
C6-01 CT/VT selection -
1
0
1
0
1
0
1
0
1
0
1
0
11
0
1
0
1
0
1
0
C6-02
-
Carrier frequency selection (when VT is selected)
*1 *3
Carrier frequency selection upper limit (when
VT is selected)
*1
-
-
6 *2
6
6 *2
6 6
6 *2
6
6 *2
6
6 *2 6 6 *2
6 6 6
6 *2
6
6 *2
6
E2-01
(E4-01)
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
Motor rated current
Motor rated slip
Motor no-load current
Motor line-to-line resistance
Motor leak inductance
A
Hz
A
W
%
1.00
2.90
0.60
38.198
18.2
1.60
2.60
0.80
22.459
14.3
3.10
2.50
1.40
10.100
18.3
4.20
3.00
1.50
6.495
18.7
7.00
2.70
2.30
3.333
19.3
7.00
2.70
2.30
3.333
19.3
9.80
1.50
2.60
1.595
18.2
13.30
1.30
4.00
1.152
15.5
19.9
1.70
5.6
0.922
19.6
26.5
1.60
7.6
0.550
17.2
E2-10
L2-02
Motor iron loss for torque compensation
Momentary power loss ridethru time
W s
14
0.1
26
0.1
53
0.2
77
0.3
130
0.5
130
0.5
193
0.8
263
0.8
385
1.0
440
2.0
L2-03
Min. baseblock (BB) time s 0.1
0.2
0.3
0.4
0.5
0.6
0.6
0.7
0.8
0.9
L2-04 Voltage recovery time s
L8-02 Overheat pre-alarm level ° C
0.3
95
0.3
95
0.3
95
0.3
90
0.3
95
0.3
95
0.3
95
0.3
90
0.3
95
0.3
95
N5-02 Motor acceleration time s 0.178
0.142
0.166
0.145
0.154
0.154
0.168
0.175
0.265
0.244
5-
85
5
-86
Constant
Number
o2-04 b8-03
Name
Inverter Capacity kVA selection
Energy-saving filter time constant
Unit kW
s
18.5
2A
22
2B
30
2C
37
2D
Factory Setting
45
2E
0.50 (Open loop vector control)
55
2F
75
30
90
31
110
32
132
33
2.00 (Open loop vector control) b8-04
Energy-saving coefficient
115.74
103.58
92.54
76.32
71.56
67.20
46.20
38.91
36.23
32.79
C6-01 CT/VT selection -
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
C6-02
-
Carrier frequency selection (when VT is selected)
*1 *3
Carrier frequency selection upper limit (when
VT is selected)
*1
-
6
6
*2
6
6
*2
4
6
*2
4
6
*2
4
6
*2
4
6
*2
3
4
*2
3
4
*2
3
4
*2
2
4
*2
E2-01
(E4-01)
Motor rated current A 32.9
38.6
52.3
65.6
79.7
95.0
130.0
156.0
190.0
223.0
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
Motor rated slip
Motor no-load current
Motor line-to-line resistance
Motor leak inductance
Hz
A
Ω
%
1.67
7.8
0.403
20.1
1.70
9.2
0.316
23.5
1.80
10.9
0.269
20.7
1.33
19.1
0.155
18.8
1.60
22.0
0.122
19.9
1.46
24.0
0.088
20.0
1.39
36.0
0.092
20.0
1.40
40.0
0.056
20.0
1.40
49.0
0.046
20.0
1.38
58.0
0.035
20.0
E2-10
L2-02
Motor iron loss for torque compensation
Momentary power loss ridethru time
W s
508
2.0
586
2.0
750
2.0
925
2.0
1125
2.0
1260
2.0
1600
2.0
1760
2.0
2150
2.0
2350
2.0
L2-03
Min. baseblock (BB) time s 1.0
1.0
1.1
1.1
1.2
1.2
1.3
1.5
1.7
1.7
L2-04 Voltage recovery time s 0.6
0.6
0.6
0.6
0.6
1.0
1.0
1.0
1.0
1.0
L8-02 Overheat pre-alarm level ° C 98
N5-02 Motor acceleration time s
78 85 85 90 90 98 108 100 110
0.317 0.355 0.323 0.320 0.387 0.317 0.533 0.592 0.646 0.673
User Constant Tables
Constant
Number
o2-04 b8-03 b8-04
Name
Inverter Capacity kVA selection
Energy-saving filter time constant
Energy-saving coefficient
Unit
30.13
Factory Setting kW 160 185 220 300
34 35 36 37 s
2.00 (Open loop vector control)
30.57
27.13
21.76
C6-01 CT/VT selection -
1
0
1
0
1 1
C6-02
-
Carrier frequency selection (when VT is selected)
*1 *3
Carrier frequency selection upper limit (when
VT is selected)
*1
-
2
4
*2
2
2
*2
1
1
*2
1
1
*2
E2-01
(E4-01)
E2-02
(E4-02)
E2-03
(E4-03)
E2-05
(E4-05)
E2-06
(E4-06)
Motor rated current
Motor rated slip
Motor no-load current
Motor line-to-line resistance
Motor leak inductance
A
Hz
A
Ω
%
270.0
1.35
70.0
0.029
20.0
310.0
1.30
81.0
0.025
20.0
370.0
1.30
96.0
0.020
20.0
500.0
1.25
130.0
0.014
20.0
E2-10
L2-02
Motor iron loss for torque compensation
Momentary power loss ridethru time
W s
2850
2.0
3200
2.0
3700
2.0
4700
2.0
L2-03
Min. baseblock (BB) time
L2-04 Voltage recovery time s 1.8
1.9
2.0
2.1
s 1.0
1.0
1.0
1.0
L8-02 Overheat pre-alarm level ° C 108 95 100 108
N5-02 Motor acceleration time s 0.777 0.864 0.910 1.392
Note Attach a Momentary Power Interruption Compensation Unit if compensation for power interruptions of up to 2.0 seconds is required for 200 V Class
Inverters with outputs of 0.4 to 11 kW.
* 1. The factory settings when VT is selected are given.
When CT is selected, the factory settings are as follows for Inverters of any capacity:
Carrier frequency selection: 1 (2.0 kHz)
Carrier frequency selection upper limit: 2.5 kHz
* 2. The setting of C6-02 changes the carrier frequency selection as follows:
0: Low-noise PWM, 1: 2.0 kHz, 2: 5.0 kHz, 3: 8.0 kHz, 4: 10.0 kHz, 5: 12.5 kHz, 6: 15.0 kHz
* 3. When setting the carrier frequency of 400 V Class Inverters of 30 kW or more to a value larger than the factory setting, reduce the value of the Inverter rated output current.
5-
87
Constant Settings by
Function
Application and Overload Selections ...........................6-2
Frequency Reference ..................................................6-6
Run Command...........................................................6-15
Stopping Methods ......................................................6-17
Acceleration and Deceleration Characteristics ..........6-25
Adjusting Frequency References...............................6-35
Speed Limit (Frequency Reference Limit Function)...6-41
Improved Operating Efficiency...................................6-43
Machine Protection ....................................................6-49
Continuing Operation.................................................6-66
Inverter Protection .....................................................6-76
Input Terminal Functions............................................6-78
Output Terminal Functions.........................................6-88
Monitor Constants......................................................6-90
Individual Functions ...................................................6-95
Digital Operator Functions .......................................6-147
Options ....................................................................6-156
Using Inverters for Elevating Machines ...................6-168