Machine Protection. YASKAWA Varispeed f7
تبلیغات
تبلیغات
Machine Protection
Machine Protection
This section explains functions for protecting the machine.
Limiting Motor Torque (Torque Limit Function)
The motor torque limit function is enabled with flux vector control and open-loop vector control.
In the open-loop vector control and flux vector control, the user-set value is applied to the torque limit by calculating internally the torque output by the motor. Enable this function if you do not want a torque above a specified amount to be applied to the load, or if you do not want a regeneration value above a specified amount to occur.
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
Control Methods
V/f
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
L7-01
L7-02
L7-03
L7-04
L7-06
L7-07
Forward drive torque limit
Sets the torque limit value as a percentage of the motor rated torque.
Four individual regions can be set.
Reverse drive torque limit Output torque
Positive torque
Forward regenerative torque limit
Reverse
Regenerative state
Regenerative state
No. of motor rotations
Forward
Reverse regenerative torque limit
Negative torque
Integral time setting for torque limit
Set the integral time for the torque limit. When integral control is set for the torque limit, reduce this setting to increase the change in frequency for the torque limit.
Control method selection for torque limit during acceleration and deceleration
Select the control method for the torque limit during acceleration and deceleration.
0: Proportional control (integral control during constant speed)
1: Integral control
Usually, this constant does not need to be set.
For applications in which the torque limit will be reached during acceleration and deceleration, torque control can be given priority by selecting integral control.
When the torque is limited, the acceleration and deceleration times may increase or the motor speed may not agree with the speed reference value.
0 to
300
0 to
300
0 to
300
0 to
300
5 to
10000
0 or 1
200%
200%
200%
200%
No
No
No
No
200 ms No
0 No
No No A
No No A
No No A
No No A
A 4A7H
A 4A8H
A 4A9H
A 4AAH
No No A No 4ACH
No No A No 4C9H
6-
49
6
-50
Multi-function Analog Input ( H3-05, H3-09)
Setting
Value
Function Contents (100%)
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
No No Yes Yes 10
11
12
15
Positive torque limit
Negative torque limit
Regenerative torque limit
Positive/negative torque limit
Motor's rated torque
Motor's rated torque
Motor's rated torque
Motor's rated torque
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes Yes
Note The forward torque limit is the limit value when the analog input signal generates forward torque. This torque limit setting is enabled even when the analog input signal generates forward torque while the motor is operating (regeneration).
Setting the Torque Limit in Constants
Using L7-01 to L7-04, you can set individually four torque limits in the following directions: Forward drive, reverse drive, forward regeneration, and reverse regeneration.
Set the Torque Limit Value Using an Analog Input
You can change the analog input level torque limit value by setting the torque limit in multi-function analog input terminals A2 and A3 .
The analog input terminal signal level is factory-set as follows:
Multi-function analog input terminal A2: 4 to 20 mA
Multi-function analog input terminal A3: 0 to 10
The following diagram shows the relationship between the torque limits.
Output torque
Positive
Positive/negative torque limits
Forward torque limit
Regenerative torque limit
Reverse operation
Negative torque limit
Negative
Fig 6.36 Torque Limit by Analog Input
No. of motor rotations
Forward operation
Regenerative torque limit
Positive/negative torque limits
Machine Protection
Setting Torque Limits Using Constants and an Analog Input
The following block diagram shows the relationship between torque limit using constants and torque limit using an analog input.
The lowest torque limit set from among the following is enabled: Torque limit using constants, torque limit using an analog input, 150% of Inverter rating (when set to CT), or 120% of Inverter rating (when set to VT) set in C6-01.
Multi-function analog input
Terminal or A3
(set value = 10)
Constants
Negative torque limit
(set value = 11)
Regenerative torque limit
(set value = 12)
Positive/negative torque limit
(set value = 15)
Positive forward drive torque
Reverse drive reverse torque
Reverse positive regenerative torque
Forward negative regenerative torque
Forward torque limit
(L7-01)
Reverse torque limit
(L7-02)
Forward regenerative torque limit (L7-03)
Reverse regenerative torque limit (L7-04)
150% (when set to CT) or 120% (when set to VT) of Inverter rated current
Min: Minimum value priority circuit
Forward torque limit
Reverse torque limit
Forward regenerative torque limit
Reverse regenerative torque limit
Fig 6.37 Torque Limit Using Constants and an Analog Input
Selecting the Control Method for Torque Limit during Acceleration and Deceleration
(SPEC: E or later only)
L7-07 is used to select the control method for the torque limit during acceleration and deceleration. The selections are proportional control and integral control. For applications, in which the torque limit will be reached during acceleration and deceleration, torque control can be given priority by selecting integral control. To increase the change in frequency for the torque limit when integral control is selected, decrease the value set for L7-06 (Integral Time Setting for Torque Limit).
Setting Precautions
•
•
•
When the torque limit function is operating, control and compensation of the motor speed is disabled because torque control is given priority. Therefore, the acceleration and deceleration times may increase or the number of motor rotations may decrease.
When using the torque limit to raise and lower loads, do not carelessly lower the torque limit value, as this may result in the motor falling or slipping.
Torque limits using an analog input are the upper limit value (during 10 V or 20 mA input) of 100% of the motor rated torque. To make the torque limit value during 10 V or 20 mA input 150% of the rated torque, set the input terminal gain to 150.0 (%). Adjust the gain for multi-function analog input terminal A2 using
H3-10 and for multi-function analog input terminal A3 using H3-06.
•
•
The torque limit accuracy is ±5% at the output frequency of 10 Hz or above. When output frequency is less than 10 Hz, accuracy is lowered.
When the torque is limited while L7-07 is set to 1 (integral control), the acceleration and deceleration times may increase or the motor speed may not agree with the speed reference value.
6-
51
6
-52
Preventing Motor Stalling During Operation
Stall prevention during operation prevents the motor from stalling by automatically lowering the Inverter's output frequency when a transient overload occurs while the motor is operating at a constant speed.
Stall prevention during operation is enabled only during V/f control. If the Inverter output current continues to exceed the setting in constant L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or disable deceleration time using constant L3-05. Set the deceleration time using C1-02 (Acceleration time 1) or
C1-04 (Acceleration Time 2).
If the Inverter output current reaches the set value in L3-06 - 2% (Inverter Rated Output Current), the motor will accelerate again at the frequency set or the acceleration time set.
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
L3-05
Stall prevention selection during running
0: Disabled (Runs as set. With a heavy load, the motor may stall.)
1: Deceleration time 1 (the deceleration time for the stall prevention function is C1-
02.)
2: Deceleration time 2 (the deceleration time for the stall prevention function is C1-
04.)
0 to 2 1 No A A No No 493H
L3-06
Stall prevention level during running
Effective when L3-05 is 1 or 2.
Set as a percentage of the
Inverter rated output current.
Usually setting is not necessary.
The factory setting reduces the set values when the motor stalls.
30 to
200
120%
*
150%
*
* C6-01= 1: 120 %, C6-01= 0: 150 %
No A A No No 494H
Machine Protection
Changing Stall Prevention Level during Operation Using an Analog Input
If you set H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-function
Analog Input Terminal A3 Function Selection) to 8 (stall prevention level during run), you can change the stall level during operation by setting H3-10 [Gain (Terminal A2)] and H3-11 [Bias (Terminal A2)] or H3-06 [Gain (Terminal A3)] and H3-07 [Bias (Terminal A3)
The stall prevention level during operation enabled is the multi-function analog input terminal A2 or A3 input level or the set value in constant L3-06, whichever is the smaller.
Stall prevention level during operation
Multi-function analog input terminal A2, A3 input level
(4 mA) (8.8 mA) (20 mA)
Fig 6.38 Stall Prevention Level during Operation Using an Analog Input
If the motor capacity is smaller than the Inverter capacity or the motor stalls when operating at the factory settings, lower the stall prevention level during operation.
INFO
Using Frequency Detection
Set these constants when outputting one of the frequency agree or frequency detection signals from a multifunction output. When using flux vector control, the motor speed is detected.
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
L4-01
Speed agreement detection level
L4-02
Speed agreement detection width
Effective when “Desired frequency (ref/setting) agree 1,”
“Frequency detection 1,” or
“Frequency detection 2" is set for a multi-function output.
Frequencies to be detected are set in Hz units.
Effective when “Frequency
(speed) agree 1,” “Desired frequency (speed) agree 1,” or
“Frequency (FOUT) detection
1,” Frequency (FOUT) detection
2 is set for a multi-function output.
Sets the frequency detection width in Hz units.
0.0 to
400.0
*1
0.0 to
300.0
*2
0.0 to
20.0
0.0 Hz
2.0 Hz
No
No
A
A
A
A
A
A
A 499H
A 49AH
6-
53
6
-54
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
L4-03
L4-04
Speed agreement detection level (+/
-)
Effective when “Desired frequency (speed) agree 2,” “Frequency (FOUT) detection 3,” or
“Frequency (FOUT) detection
4" is set for a multi-function output.
Frequency that should be detected is set in Hz units.
Speed agreement detection width (+/
-)
Effective when “Frequency
(speed) agree 2,” “Desired frequency (speed) agree 2,” Frequency (FOUT) detection 3 or
“Frequency detection 4" is set for a multi-function output.
Frequency detection width is set in Hz units.
-400.0 to
+400.0
*3
-300.0 to
+300.0
*4
0.0 to
20.0
0.0 Hz
2.0 Hz
No
No
A
A
A
A
A
A
A 49BH
A 49CH
* 1. When C6-01 = 0, the upper limit is 150.0.
* 2. When C6-01 = 1, the upper limit is 400.0.
* 3. When C6-01 = 0, -150.0 to +150.0.
* 4. When C6-01 = 1, -400.0 to +400.0
Constants and Output Signals
User Constant Number
L4-01
Name
Speed agree detection level
L4-02
L4-03
L4-04
Speed agree detection width
Speed agree detection level (+/-)
Speed agree detection width (+/-)
Function
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2
Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2
Fref/Set Agree 2
Frequency Detection 3
Frequency Detection 4
Fref/Fout Agree 2
Fref/Set Agree 2
Frequency Detection 3
Frequency Detection 4
Set the corresponding setting in the multi-function output (H2-01 to H2-03) to output the desired Fref/Fout
Agree signal, Fref/Set Agree signal, or Frequency Detection signal.
Function
Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2
Fref/Fout Agree 2
Fref/Set Agree 2
Frequency Detection 3
Frequency Detection 4
Setting
2
3
13
14
4
5
15
16
Machine Protection
Timing Chart for Frequency Detection Operation
Related constant
L4-01: Speed Agree Level
L4-02: Speed Agree Width
Fref/Fout Agree 1
L4-03: Speed Agree Level +/ −
L4-04: Speed Agree Width +/ −
Fref/Fout Agree 2
Frequency reference
Fref/Fout
Agree
Output frequency or motor speed
L4-02
Frequency reference
Output frequency or motor speed
L4-04
L4-02
Fref/Fout Agree 1 OFF ON
(Multi-function output setting = 2)
Fref/Set Agree 1
(ON at the following conditions during frequency agree)
Fref/Fout Agree 2 OFF ON
(Multi-function output setting = 13)
Fref/Set Agree 2
(ON at the following conditions during frequency agree)
Fref/Set
Agree
Output frequency or motor speed
L4-01
Fref/Set Agree 1 OFF ON
(Multi-function output setting = 3)
Frequency (FOUT) Detection 1
(L4-01 > | Output frequency | )
L4-02
L4-02
L4-01
L4-02
L4-01
Output frequency or motor speed
L4-01
Frequency
Detection
Freq. Detection 1
ON OFF
(Multi-function output setting = 4)
Frequency (FOUT) Detection 2
(L4-01 < | Output frequency | )
L4-02
L4-02
L4-01
Output frequency or motor speed
Freq. Detection 2
OFF ON
(Multi-function output setting = 5)
L4-01
L4-02
Output frequency or motor speed
Fref/Set Agree 2 OFF ON
(Multi-function output setting = 14)
Frequency (FOUT) Detection 3
(L4-03 > Output frequency)
Output frequency or motor speed
Freq. Detection 3
ON OFF
(Multi-function output setting = 15)
Frequency (FOUT) Detection 4
(L4-01 < Output frequency)
Output frequency or motor speed
Freq. Detection 4 OFF ON
(Multi-function output setting = 16)
L4-04
L4-03
L4-04
L4-03
L4-04
L4-03
6-
55
6
-56
Detecting Motor Torque
If an excessive load is placed on the machinery (overtorque) or the load is suddenly lightened (undertorque), you can output an alarm signal to multi-function output terminal M1-M2, P1-PC, or P2-PC.
To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection NO/
NC) in one of the following constants: H2-01 to H2-03 (multi-function output terminals M1-M2, P1-PC, and
P2-PC function selection).
The overtorque/undertorque detection level is the current level (Inverter rated output current 100%) in V/f control, and the motor torque (motor rated torque 100%) in vector control.
Related Constants
Constant
Number
L6-01
L6-02
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Torque detection selection
1
0: Overtorque/undertorque detection disabled.
1: Overtorque detection only with speed agreement; operation continues after overtorque (warning).
2: Overtorque detected continuously during operation; operation continues after overtorque
(warning).
3: Overtorque detection only with speed agreement; output stopped upon detection (protected operation).
4: Overtorque detected continuously during operation; output stopped upon detection (protected operation).
5: Undertorque detection only with speed agreement; operation continues after overtorque (warning).
6: Undertorque detected continuously during operation; operation continues after overtorque
(warning).
7: Undertorque detection only with speed agreement; output stopped upon detection (protected operation).
8: Undertorque detected continuously during operation; output stopped upon detection (protected operation).
0 to 8 0
Torque detection level 1
Open loop vector control: Motor rated torque is set as 100%.
V/f control: Inverter rated current is set as 100%.
0 to 300 150%
No
No
A
A
A
A
A
A
A 4A1H
A 4A2H
Machine Protection
Constant
Number
Name Description
L6-03
L6-04
L6-05
L6-06
Torque detection time 1
Sets the overtorque/undertorque detection time in 1-second units.
Torque detection selection
2
Torque detection level 2
Output of torque detection 1 is enabled by setting B or 17 for
H2 and output of torque detection 1 is enabled by setting
18 or 18 for H2 .
Torque detection time 2
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
0.0 to
10.0
0.1 s No A A A A 4A3H
0 to 8
0 to
300
0.0 to
10.0
0
150%
0.1 s
No
No
No
A
A
A
A
A
A
A
A
A
A 4A4H
A 4A5H
A 4A6H
Multi-function Output (H2-01 to H2-03)
Setting
Value
B
17
18
19
Function
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Yes Yes Yes Yes
Overtorque/undertorque detection 1 NO (NO contact: Overtorque/undertorque detection at ON)
Overtorque/undertorque detection 1 NC (NC Contact: Overtorque/undertorque detection at OFF)
Overtorque/undertorque detection 2 NO (NO Contact: Overtorque/undertorque detection at ON)
Overtorque/undertorque detection 2 NC (NC Contact: Overtorque/undertorque detection at OFF)
Yes Yes Yes Yes
Yes Yes Yes Yes
Yes Yes Yes Yes
6-
57
6
-58
L6-01 and L6-04 Set Values and LED Indications
The relationship between alarms displayed by the Digital Operator when overtorque or undertorque is detected, and the set values in L6-01 and L6-04, is shown in the following table.
Set
Value
0
Function
LED Indications
Overtorque/
Undertorque
Detection 1
Overtorque/
Undertorque
Detection 2
-
1
2
3
4
5
6
7
8
Overtorque/undertorque detection disabled.
Overtorque detection only with speed matching; operation continues after overtorque (warning).
Overtorque detected continuously during operation; operation continues after overtorque (warning).
Overtorque detection only with speed matching; output stopped upon detection (protected operation).
Overtorque detected continuously during operation; output stopped upon detection (protected operation).
Undertorque detection only with speed matching; operation continues after overtorque (warning).
Undertorque detected continuously during operation; operation continues after overtorque (warning).
Undertorque detection only with speed matching; output stopped upon detection (protected operation).
Undertorque detected continuously during operation; output stopped upon detection (protected operation).
OL3 flashes
OL3 flashes
OL3 lit
OL3 lit
UL3 flashes
UL3 flashes
UL3 lit
UL3 lit
OL4 flashes
OL4 flashes
OL4 lit
OL4 lit
UL4 flashes
UL4 flashes
UL4 lit
UL4 lit
Setting Example
The following diagram shows the time chart for overtorque and undertorque detection.
• Overtorque Detection
Motor current (output torque)
* *
L6-02 or L6-05
Overtorque detection 1 NO or overtorque detection 2 NO
L6-03 or
L6-06
L6-03 or
L6-06
ON ON
* Overtorque detection disabled band is approximately 10% of the Inverter rated output
current (or motor rated torque).
Machine Protection
• Undertorque Detection
Motor current (output torque)
L6-02 or L6-05
*
Undertorque detection 1 NO or Undertorque detection 2 NO
L6-03 or
L6-06
L6-03 or
L6-06 ON ON
The undertorque detection disabled margin is approximately 10% of the Inverter rated output
current (or motor rated torque)
Changing Overtorque and Undertorque Detection Levels Using an Analog Input
If you set constant H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-
(Multi-function Analog Input Terminal A3 Function Selection) to 7 (overtorque/undertorque detection level), you can change the overtorque/undertorque detection level.
If you change the overtorque/undertorque detection level using the multi-function analog input, only overtorque/undertorque detection level 1 will be enabled.
The following diagram shows the overtorque/undertorque detection level using an analog input.
Detection level
Multi-function analog input terminal A2, A3 input level
(4 mA) (20 mA)
Fig 6.39 Overtorque/Undertorque Detection Level Using an Analog Input
Multi-Function Analog Input ( H3-05, H3-09)
Setting
Value
7
Function Contents (100%)
Overtorque/undertorque detection level
Motor rated torque for vector control
Inverter rated output current for V/f control
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Yes Yes Yes Yes
6-
59
6
-60
Motor Overload Protection
You can protect the motor from overload using the Inverter's built-in electronic thermal overload relay.
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
E2-01
E4-01
L1-01
L1-02
Motor rated current
Motor 2 rated current
Motor protection selection
Motor protection time constant
Sets the motor rated current in 1
A units.
These set values will become the reference values for motor protection, torque limits and torque control.
This constant is automatically set during autotuning.
Sets the motor rated current in 1
A units.
These set values will become the reference values for motor protection, torque limits and torque control.
This constant is automatically set during autotuning.
Sets whether the motor overload function is enabled or disabled at electric thermal overload relay.
0: Disabled
1: General-purpose motor protection
2: Inverter motor protection
3: Vector motor protection
In some applications when the
Inverter power supply is turned off, the thermal value is reset, so even if this constant is set to
1, protection may not be effective.
When several motors are connected to one Inverter, set to 0 and ensure that each motor is installed with a protection device.
Sets the electric thermal detection time in seconds units.
Usually setting is not necessary.
The factory setting is 150% overload for one minute.
When the motor's overload resistance is known, also set the overload resistance protection time for when the motor is hot started.
0.32 to
6.40
*2
0.32
to 6.40
*2
0 to 3
0.1 to
5.0
1.90 A
*1
1.90 A
*1
1
1.0 min
No
No
No
No
Q
A
Q
A
Q
A
Q
A
Q
A
Q
A
Q
A
Q
A
* 1. The factory settings depend on the Inverter capacity. The values for a 200 V Class Inverter of 0.4 kW are given.
* 2. The setting range is 10% to 200% of the Inverter's rated output current. The value for a 200 V Class Inverter of 0.4 kW is given.
MEMO
BUS
Register
30EH
321H
480H
481H
Machine Protection
Multi-Function Outputs (H2-01 to H2-03)
Setting
Value
Function
1F
Motor overload (OL1, including OH3) pre-alarm (ON: 90% or more of the detection level)
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
Yes Yes Yes Yes
Setting Motor Rated Current
Set the rated current value on the motor nameplate in constants E2-01 (for motor 1) and E4-01 (for motor 2).
This set value is the electronic thermal base current.
Setting Motor Overload Protection Characteristics
Set the overload protection function in L1-01 according to the applicable motor.
The induction motor's cooling abilities differ according to the speed control range. Consequently, you must select the electronic thermal protection characteristics to match the applicable motor's tolerance load characteristics.
The following table shows the motor type and tolerance load characteristics.
L1-01
Set
Value
Motor Type Tolerance Load Characteristics Cooling Ability
Electronic Thermal
Operation (at 100%
Motor Load)
1
General-purpose motor (standard motor)
Short time 60 s.
Rated rotation speed
= 100% speed
Continuous
Frame number
Max. speed of 200
LJ min.
Frame number Max. speed of 160 MJ to 160 LJ min.
Frame number Max. speed of 132 MJ
Use this motor for operations using a commercial power supply. This motor construction yields best cooling effect when operating at 50/
60 Hz.
When operating continuously at 50/60 Hz or less, motor overload detection
(OL1) is detected. The
Inverter outputs the error contact, and the motor coasts to a stop.
Rotation speed (%)
2
Inverter motor
(constant torque)
(1:10)
Short time 60
Rated rotation speed
= 100% speed
Continuous
Frame number Max. speed of 200 LJ min.
Frame number Max. speed of 160 MJ to 180 LJ
Frame number Max. speed of 132 MJ
This motor yields a cooling effect even when operating at low speeds (approx.
6 Hz).
Operates continuously at 6 to 50/60 Hz.
Rotation speed (%)
6-
61
6
-62
L1-01
Set
Value
Motor Type Tolerance Load Characteristics
Short time 60 s.
Rated rotation speed
= 100% speed
Cooling Ability
3
Vector motor
(1:100)
Electronic Thermal
Operation (at 100%
Motor Load)
Continuous
Frame number
Max. speed of
200 LJ min.
Frame number Max. speed of 160 MJ to 180 LJ
Frame number Max. speed of 132 MJ
This motor yields a cooling effect even when operating at extremely low speeds
(approx. 0.6 Hz).
Operates continuously at
0.6 to 60 Hz.
Rotation speed (%)
Setting Motor Protection Operation Time
Set the motor protection operation time in L1-02.
If, after operating the motor continuously at the rated current, a 150% overload is experienced, set the (hot start) electronic thermal protection operation time. The factory setting is resistance to 150% for 60 seconds.
The following diagram shows an example of the characteristics of the electronic thermal protection operation time (L1-02 = 1.0 min., operation at 60 Hz, general-purpose motor characteristics, when L1-01 is set to 1)
Operating time (min.)
Cold start
Hot start
Motor current (%)
E2-01 is set to 100%
Fig 6.40 Motor Protection Operation Time
Setting Precautions
• If multiple motors are connected to one Inverter, set constant L1-01 to 0 (disabled). To protect the motor, install a thermal relay in the motor power cable, and perform overload protection on each motor.
• With applications where the power supply is often turned ON and OFF, there is a risk that the circuit cannot be protected even if this constant has been set to 1 (enabled), because the thermal value will be reset.
• To detect overloads in good time, set the set value in constant L1-02 to a low setting.
• When using a general-purpose motor (standard motor), the cooling ability will be lowered by f 1/4 (frequency). Consequently, the frequency may cause motor overload protection (OL1) to occur, even below the rated current. If operating using the rated current at a low frequency, use a special motor.
Machine Protection
Setting the Motor Overload Pre-Alarm
If the motor overload protection function is enabled (i.e., L1-01 is set to other than 0) and you set H2-01 to
H2-03 (multi-function output terminals M1-M2, P1-PC, and P2-PC function selection) to 1F (motor overload
OL1 pre-alarm), the motor overload pre-alarm will be enabled. If the electronic thermal value reaches minimum 90% of the overload detection level, the output terminal that has been set will be turned ON.
Motor Overheating Protection Using PTC Thermistor Inputs
Perform motor overheating protection using the thermistor temperature resistance characteristics of the PTC
(Positive Temperature Coefficient) built into the windings of each motor phase.
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
L1-03
L1-04
L1-05
Alarm operation selection during motor overheating
Set Multi-function input terminal
A3 (H3-05)
or A2 (H3-09) to E and select the operation when the input motor temperature (thermistor) input exceeds the alarm detection level [1.17 V
(±5%)].
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09.
3: Continue operation (H3 on the Operator flashes).
Motor overheating operation selection
Set Multi-function input terminal A3 (H3-05) or A2 (H3-09) to E and select the operation when the motor temperature
(thermistor) input exceeds the operation detection level [2.34V
(±5%)].
0: Decelerate to stop
1: Coast to stop
2: Emergency stop using the deceleration time in C1-09.
Motor temperature input filter time constant
Set Multi-function input terminal A3 (H3-05) or A2 (H3-09) to E and set the primary delay time constant for motor temperature (thermistor) inputs in seconds.
0 to 3
0 to 2
0.00 to
10.00
3
1
0.20 s
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
482H
483H
484H
6-
63
6
-64
PTC Thermistor Characteristics
The following diagram shows the characteristics of the PTC thermistor temperature to the resistance value.
Resistance (ohms)
Class F
150
°
C
Class H
180
°
C
1330
Tr: Temperature threshold value
550
Temperature
Tr
Tr 5 Tr Tr+5
Fig 6.41 PTC Thermistor Temperature-Resistance Value Characteristics
Operation during Motor Overheating
Set the operation if the motor overheats in constants L1-03 and L1-04. Set the motor temperature input filter time constant in L1-05. If the motor overheats, the OH3 and OH4 error codes will be displayed on the Digital
Operator.
Error Codes If the Motor Overheats
Error Code
OH3
OH4
Details
Inverter stops or continues to operate, according to the setting in L1-03.
Inverter stops according to the setting in L1-04.
By setting H3-09 (Multi-function Analog Input Terminal A2 Function Selection) or H3-05 (Multi-function
Analog Input Terminal A3 Function Selection) to E (Motor temperature input), you can detect alarm OH3 or OH4 using the PTC temperature-resistance characteristics, and protect the motor. The terminal connections are shown in the following diagram. Set H3-08 〔 Signal level selection (terminal A2) 〕 (H3-04 when A3 is used) to 0 (0 to + 10 V).
Inverter
Multi-function contact input
Multi-function contact output
Fault contact output
Branch resistance
18 k Ω
PTC thermistor
A2, A3
(0-10 V) *
Multi-function
PHC output
* When using terminal A2, set DIP switch S1-2 to OFF (0 to 10 V).
Fig 6.42 Mutual Connections During Motor Overheating Protection
Machine Protection
Limiting Motor Rotation Direction
If you set motor reverse rotation prohibited, a Reverse Run Command will not be accepted even if it is input.
Use this setting for applications in which reverse motor rotation can cause problems (e.g., fans, pumps, etc.)
Related Constants
Constant
Number
Name Description b1-04
Prohibition of reverse operation
0: Reverse enabled
1: Reverse disabled
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
0 or 1 0 No A A A A 183H
6-