Options
This section explains the Inverter option functions.
Performing Speed Control with PG
This section explains functions with V/f control with PG and flux vector control .
Related Constants
Constant
Number
Name
F1-01 PG constant
F1-02
Operation selection at
PG open circuit (PGO)
F1-03
Operation selection at overspeed
(OS)
F1-04
Operation selection at deviation
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Sets the number of PG (pulse generator or encoder) pulses.
Sets the number of pulses per motor revolution.
Sets the PG disconnection stopping method.
0: Ramp to stop (Deceleration stop using Deceleration
Time 1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-09.)
3: Continue operation (To protect the motor or machinery, do not normally make this setting.)
Sets the stopping method when an overspeed (OS) fault occurs.
0: Ramp to stop (Deceleration stop using Deceleration
Time 1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-09.)
3: Continue operation (To protect the motor or machinery, do not normally make this setting.)
Sets the stopping method when a speed deviation (DEV) fault occurs.
0: Ramp to stop (Deceleration stop using Deceleration
Time 1, C1-02.)
1: Coast to stop
2: Fast stop (Emergency stop using the deceleration time in C1-09.)
3: Continue operation (DEV is displayed and operation continued.)
0 to
60000
0 to 3
0 to 3
0 to 3
600
1
1
3
No
No
No
No
No
No
No
No
Q
A
A
A
No
No
No
No
Q
A
A
A
380H
381H
382H
383H
Options
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
F1-05 PG rotation
F1-06
F1-07
0: Phase A leads with Forward
Run Command. (Phase B leads with Reverse Run
Command.)
1: Phase B leads with Forward
Run Command. (Phase A leads with Reverse Run
Command.)
PG division rate (PG pulse monitor)
Sets the division ratio for the PG speed control board pulse output.
Division ratio = (1+ n) /m (n=0 or 1 m=1 to 32)
F1-06 n m
This constant is only effective when a PG-B2 is used.
The possible division ratio settings are: 1/32 ≤ F1-06 ≤ 1.
Integral value during accel/ decel enable/ disable
Sets integral control during acceleration/deceleration to either enabled or disabled.
0: Disabled (The integral function isn't used while accelerating or decelerating; it is used at constant speeds.)
1: Enabled (The integral function is used at all times.)
0 or 1
1 to 132
0 or 1
0
1
0
No
No
No
No
No
No
A
A
A
F1-08
F1-09
F1-10
F1-11
F1-12
F1-13
Overspeed detection level
Overspeed detection delay time
Sets the overspeed detection method.
Frequencies above that set for
F1-08 (set as a percentage of the maximum output frequency) that continue to exceed this frequency for the time set in F1-09 are detected as overspeed faults.
0 to 120 115%
0.0 to
2.0
0.0 s
*
Excessive speed deviation detection level
Excessive speed deviation detection delay time
Sets the speed deviation detection method.
Any speed deviation above the
F1-10 set level (set as a percentage of the maximum output frequency) that continues for the time set in F1-11 is detected as a speed deviation.
Speed deviation is the difference between actual motor speed and the reference command speed.
Number of
PG gear teeth
1
Sets the number of teeth on the gears if there are gears between the PG and the motor.
Number of
PG gear teeth
2
Input pulses from PG 60 F1-13
F1-01 F1-12
A gear ratio of 1 will be used if either of these constants is set to
0.
0 to 50
0.0 to
10.0
0 to
1000
10%
0.5 s
0
0
No
No
No
No
No
No
No
No
No
No
No
No
A
A
A
A
A
A
F1-14
PG open-circuit detection time
Used to set the PG disconnection detection time. PGO will be detected if the detection time continues beyond the set time.
0.0 to
10.0
2.0 s No No A
* The factory setting will change when the control method is changed. The flux vector control factory setting is given.
No
No
No
No
No
No
No
No
No
No
A
A
MEMO
BUS
Register
384H
385H
No 386H
A
A
A
387H
388H
389H
A 38AH
No 38BH
No 38CH
A 38DH
6-
157
6
-158
Using PG Speed Control Board
There are four types of PG Speed Control Board that can be used in V/f control with PG.
• PG-A2: A-phase (single) pulse input, compatible with open collector or complimentary outputs.
•
•
•
PG-B2: A/B-phase pulse input, compatible with complimentary outputs.
PG-D2: A-phase (single) pulse input, compatible with line drivers.
PG-X2: A/B/Z-phase pulse input, compatible with line drivers.
There are two types of PG Speed Control Boards that can be used for flux vector control.
• PG-B2: A/B phase pulse inputs, complementary outputs
• PG-X2: A/B/Z phase pulse inputs, line driver outputs
For the connection diagram, refer to page 2-36 to 2-38.
Setting Number of PG Pulses
Set the number of PG (Pulse Generator/Encoder) pulses in pulses/rotation. Set the number of A-phase or Bphase pulses per 1 motor rotation in F1-01.
Matching PG Rotation Direction and Motor Rotation Direction
Constant F1-05 matches the PG rotation direction and the motor rotation direction. If the motor is rotating forwards, set whether it is A-phase driven or B-phase driven. Make this setting when using PG-B2 or PG-X2.
Inverter
Motor PG (encoder)
Forward
Command
A-phase driven when set value = 0
A-phase
B-phase
Pulse output
B-phase driven when set value = 1
A-phase
B-phase
Example: Forward rotation of standard Yaskawa motor (PG used: Samtack (KK))
Forward
Command
Motor output axis rotates counter-clockwise during Inverter Forward Command.
Rotation
(CCW)
A-phase
B-phase
Yaskawa standard PG used is A-phase driven (CCW) when motor rotation is forward.
Fig 6.78 PG Rotation Direction Setting
Generally, PG is A-phase driven when rotation is clockwise (CW) see from the input axis. Also, motor rotation is counter-clockwise (CCW) seen from the output side when Forward Commands are output. Consequently, when motor rotation is forward, PG is normally A-phase driven when a load is applied, and B-phase driven when a load is not applied.
Options
Setting Number of Gear Teeth Between PG and Motor
Set the number of PG gear teeth in F1-12 and F1-13. If there are gears between the motor and PG, you can operate the motor by setting the number of gear teeth.
When the number of gear teeth has been set, the number of motor rotations within the Inverter is calculated using the following formula.
No. of motor rotations (min
− 1
.) = No. of input pulses from PC × 60 / F1-01 × F1-13 (No. of gear teeth on load side) / F1-12 (No. of gear teeth on motor side)
Matching Motor Speed During Acceleration and Deceleration to Frequency Reference
You can select whether to enable or disable integral operation during acceleration and deceleration when using
V/f with PG control.
To match the motor speed as closely as possible to the frequency reference even during acceleration and deceleration, set F1-07 to 1.
If F1-01 is set to 1, overshoot or undershoot may occur easily immediately after acceleration and deceleration. To minimize the possibility of overshoot or undershoot occurring, set F1-01 to 0.
IMPORTANT
Setting PG Pulse Monitor Output Dividing Ratio
This function is enabled only when using PG speed control board PG-B2. Set the dividing ratio for the PG pulse monitor output. The set value is expressed as n for the higher place digit, and m for the lower place 2 digits. The dividing ratio is calculated as follows:
Dividing ratio = (1 + n)/m (Setting range) n: 0 or 1, m: 1 to 32
F1-06 = n
m
The dividing ratio can be set within the following range: 1/32 ≤ F1-06 ≤ 1. For example, if the dividing ratio is
1/2 (set value 2), half of the number of pulses from the PG are monitor outputs.
Detecting PG Open Circuit
Select the stopping method when PG cable disconnected is detected and the PG open circuit (PGO) detection time.
When the Inverter is operating with the frequency reference set to 1% minimum (except when operating on direct current), if the speed feedback from PG is greater than the time setting in F1-14, PGO is detected.
Detecting Motor Overspeed
An error is detected when the number of motor rotations exceeds the regulated limit. An overspeed (OS) is detected when a frequency that exceeds the set value in F1-08 continues for longer than the time set in F1-09.
After detecting an overspeed (OS), the Inverter stops according to the setting in F1-03.
Detecting Speed Difference between the Motor and Speed Reference
An error is detected when the speed deviation (i.e., the difference between the designated speed and the actual motor speed) is too great. Speed deviation (DEV) is detected after a speed agreement is detected and when the speed reference and actual workpiece speed are within the setting of L4-02, if a speed deviation great than the set value in F1-10 continues for longer than the time set in F1-11. After a speed deviation is detected, the
Inverter stops according to the setting in F1-04.
6-
159
6
-160
Using Digital Output Boards
There are two types of Inverter digital output boards:
• DO-02C
Relay contact output (DPDT contact)
• DO-08
6 photocoupler output channels (shared commons)
2 (independent) relay contact output channels (NC contact)
Inverter control panel
3CN 3CN
+24 V
NC NO
TD
1
2
3
4
NC
NO 5
6
CH1
CH2
Relay contact
DO-02C Digital Output Board
Inverter control panel
3CN 3CN
Photocoupler
TD5
CH1 Photocoupler
TD6
CH2
TD7
CH3
TD8
CH4
TD9
CH5
TD10
TD11
TD1
TD2
TD3
TD4
CH6
COM (0 V common)
CH7
Relay contact
CH8
DO-08 Digital Output Board
Fig 6.79 Digital Output Boards
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
F5-01
Channel 1 output selection
F5-02
F5-03
F5-04
F5-05
F5-06
Channel 2 output selection
Channel 3 output selection
Channel 4 output selection
Channel 5 output selection
Channel 6 output selection
Effective when a Digital Output
Board (DO-02C or DO-08) is used.
Set the number of the multifunction output to be output.
Effective when a Digital Output
Board (DO-02C or DO-08) is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
0 to 37
0 to 37
0 to 37
0 to 37
0 to 37
0 to 37
0
1
2
4
6
37
No
No
No
No
No
No
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A
A 39AH
A 39BH
A 39CH
A 39DH
A
399H
39EH
Options
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
F5-07
Channel 7 output selection
F5-08
Channel 8 output selection
F5-09
DO-08 output mode selection
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the number of the multifunction output to be output.
Effective when a DO-08 Digital
Output Board is used.
Set the output mode.
0: 8-channel individual outputs
1: Binary code output
2: Output according to
F5-01 to F5-08 settings.
0 to 37
0 to 37
0 to 2
0F
0F
0
No
No
No
A
A
A
A
A
A
A
A
A
A 39FH
A 3A0H
A 3A1H
Setting Output Items for the DO-02C Digital Output Board
If using DO-02C Digital Output Board, set the output items using F5-01 and F5-02.
Setting Output Items for the DO-08 Digital Output Board
If using DO-08 Digital Output Board, select one of the following three output modes according to the setting in F5-09.
F5-09 Set to 0
Set Value
0: 8 separate outputs
Terminal
Number
TD5-TD11
TD6-TD11
TD7-TD11
TD8-TD11
Overcurrent (SC, OC, GF)
Overvoltage (OV)
Inverter overload (OL2)
Fuse blown (PUF)
Output Details
TD9-TD11 Overspeed (OS)
TD10-TD11 Inverter overheated (OH1) or motor overload (OL1)
TD1-TD2 Zero-speed detected
TD3-TD4 Speed agreement
6-
161
6
-162
F5-09 Set to 1
Set Value
1: Binary code output
Terminal
Number
TD5-TD11 bit 0
TD6-TD11
TD7-TD11
TD8-TD11 bit 1 bit 2 bit 3
TD9-TD11 Zero-speed detected
TD10-TD11 Speed agreement
TD1-TD2
TD3-TD4
Operating
Minor fault
Output Details
Encoded output
(Refer to table below)
The following table shows the code outputs.
Bits 3, 2, 1, and 0
0000 No error
0001
Output Details
Overcurrent (SC, OC, GF)
0010
0011
0100
0101
0110
0111
Overvoltage (OV)
Inverter overload (OL2)
Inverter overheated (OH, OH1)
Overspeed (OS)
Fuse blown (PUF)
Dynamic braking resistor (RH)
Injection brake transistor error (RR)
F5-09 Set to 2
Output depends on the settings in F5-01 to F5-08.
Bits 3, 2, 1, and 0
1000
Output Details
External fault (EFxx)
1001 Control board error (CPFxx)
1010
1011
1100
1101
1110
Motor overload (OL1)
Not used
Power loss (UV1, UV2, or UV3)
Speed deviation (DEV)
PG open circuit (PGO)
1111 Not used
Using an Analog Reference Board (SPEC: E or Later Only)
AI-14B provides 3 channels of bi-polar inputs with 13-bit A/D conversion accuracy (and a + sign bit). The function of each channel is determined by the setting of F2-01.
AI-14U provides 2 channels of bi-polar inputs with 14-bit A/D conversion accuracy. Channel 1 is a voltage input and channel 2 is a current input. The sum of channels 1 and 2 is a frequency input. F2-01 does not need to be set for the AI-14U.
Options
Related Constants
Constant
Number
Name
F2-01
Bi-polar or uni-polar input selection
Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
Sets the functions for channel 1 to 3 which are effective when the AI-14B Analog Reference
Board is used.
0: 3-channel individual (Channel 1: terminal A1, Channel
2: terminal A2, Channel 3: terminal A3)
1: 3-channel addition (Addition values are the frequency reference)
When set to 0, select 1 for b1-
01. In this case the multi-function input “Option/Inverter selection” cannot be used.
0 or 1 0 No A A A A 38FH
Setting Precautions
Always set b1-01 (Reference selection) to 1 (control circuit terminal) when using the AI-14B for three channels of independent inputs. When this is done, H1-01 to H1-06 (multi-function contact inputs) cannot be set to
2 (Option/Inverter selection).
Using a Digital Reference Board (SPEC: E or Later Only)
When using a DI-08 or DI-16H2 Digital Reference Board, set b1-01 (Reference selection) to 3 (Option
Board).
The DI-16H2 can be used to set a frequency using a 16-bit digital reference. The DI-08 can be used to set a frequency using a 8-bit digital reference.
Related Constants
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register
F3-01
Digital input option
Sets the Digital Reference Board input method.
0: BCD 1% unit
1: BCD 0.1% unit
2: BCD 0.01% unit
3: BCD 1 Hz unit
4: BCD 0.1 Hz unit
5: BCD 0.01 Hz unit
6: BCD special setting (5-digit input)
7: Binary input
6 is only effective when the DI-
16H2 is used.
When o1-03 is set to 2 or higher, the input will be BCD, and the units will change to the o1-03 setting.
0 to 7 0 No A A A A 390H
6-
163
6
-164
Constant
Number
Name Description
Setting
Range
Factory
Setting
Change during
Operation
V/f
Control Methods
V/f with
PG
Open
Loop
Vector
Flux
Vector
MEMO
BUS
Register o1-03
Frequency units of reference setting and monitor
Sets the units that will be set and displayed for the frequency reference and frequency monitor.
0: 0.01 Hz units
1: 0.01% units (Maximum output frequency is 100%)
2 to 39: min
-1
units (Sets the motor poles.)
40 to 39999:
User desired display
Set the desired values for setting and display for the max. output frequency.
0 to
39999
0 No A A A A 502H
Set 4-digit number excluding the decimal point.
Set the number of digits below the decimal point to display.
Example: When the max. output frequency value is 200.0, set
12000
Selecting Input Terminal Functions for the DI-16H2 Digital Reference Board
The frequency reference from the DI-16H2 Board is determined by the setting of F3-01 and the 12/16-bit switch on the option board. The possible settings are listed in the following table.
Options
Terminal
TC1
TC2
TC3
3
4
1
2
5
9
10
7
8
6
7
8
9
3
4
1
2
5
6
Pin No.
12-bit Binary with Sign
F3-01 = 7
S1: 12 bit
Bit 1 (2
0
)
16-bit Binary with Sign
F3-01 = 7
S1: 16 bit
Bit 1 (2
0
)
Bit 1 (2
1
)
Bit 1 (2
2
)
Bit 1 (2
Bit 1 (2
1
2
)
)
Bit 1 (2
3
)
Bit 1 (2
4
)
Bit 1 (2
5
)
Bit 1 (2
6
)
Bit 1 (2
Bit 1 (2
Bit 1 (2
Bit 1 (2
3
4
5
6
)
)
)
)
3-digit BCD with
Sign
F3-01 = 0 to 5
S1: 12 bit
1
2
4
BDC digit 1
(0 to 9)
4-digit BCD with
Sign
F3-01 = 0 to 5
S1: 16 bit
4-digit BCD without Sign
F3-01 = 6
S1: 16 bit
1 2
2
4
BDC digit 1
(0 to 9)
4
8
BDC digit 1
(2 to 9)
8
1
2
4
BDC digit 2
(0 to 9)
8
1
2
4
BDC digit 2
(0 to 9)
1
2
4
8
BDC digit 2
(0 to 9)
Bit 1 (2
Bit 1 (2
Bit 1 (2
Bit 1 (2
Bit 1 (2
-
-
-
-
7
8
9
10
11
)
)
)
)
)
Bit 1 (2
7
)
Bit 1 (2
8
)
8
1
Bit 1 (2
9
) 2
Bit 1 (2
10
) 4
Bit 1 (2
11
) 8
Bit 1 (2
12
)
Bit 1 (2
13
)
Bit 1 (2
14
)
Bit 1 (2
15
)
Sign signal (0: Forward, 1: Reverse)
SET (read) signal (1: Read)
Input signal common (0 V)
Shield wire connection terminal
BDC digit 3
(0 to 9)
-
-
-
-
8
1
2
4
8
1
2
4
8
BDC digit 3
(0 to 9)
BDC digit 4
(0 to 9)
1
2
4
8
1
2
4
8
1
2
BDC digit 3
(0 to 9)
BDC digit 4
(0 to 9)
BDC digit 5
(0 to 3)
Application Precautions
•
•
The maximum frequency (100% speed) reference will be used when the binary input is set (setting: 6 or 7) and all bits are 1.
Setting F3-01 to 6 is valid only when the D1-16H2 is used. Using this setting, a frequency from 0.00 to
399.8 Hz can be set in BCD. The sign bit is used as a data bit, so only positive (plus) data can be set. Also, the digit starts from 0, so the minimum setting is 0.02 Hz.
Selecting the Input Terminal Function for a DI-08 Digital Reference Board
The frequency reference from a DI-08 Board is determined by the setting of F3-01, as shown in the following table.
6-
165
6
-166
Terminal
TC
3
4
1
2
5
6
7
8
9
10
11
Pin No.
8-bit Binary with Sign
F3-01 = 7
Bit 1 (2
0
)
Bit 1 (2
1
)
Bit 1 (2
2
)
Bit 1 (2
3
)
Bit 1 (2
4
)
Bit 1 (2
5
)
Bit 1 (2
6
)
Bit 1 (2
7
)
Sign signal
SET (read) signal
Reference common signal (0 V)
2-digit BCD with Sign
F3-01 = 0 to 5
1
2
4
BDC digit 1
(0 to 9)
8
1
2
BDC digit 2
(0 to 15)
4
8
Application Precautions
The DI-08 will not function if F3-01 is set to 6
Selecting the Digital Reference
The range of the digital references is determined by the combination of the settings of o1-03 and F3-01. The information monitored in U1-01 (Frequency reference) will also change.
DI-16H2 Reference Ranges
When using the DI-16H2, the following ranges can be set depending on the settings of the constants.
o1-03 F3-01
0 or 1
0
1
2
3
4
5
6
7
Switch
S1
Reference Input Mode
12 bits 3-digit BCD with sign, 1%
16 bits 4-digit BCD with sign, 1%
12 bits 3-digit BCD with sign, 0.1%
16 bits 4-digit BCD with sign, 0.1%
12 bits 3-digit BCD with sign, 0.01%
16 bits 4-digit BCD with sign, 0.01%
12 bits 3-digit BCD with sign, 1 Hz
16 bits 4-digit BCD with sign, 1 Hz
12 bits 3-digit BCD with sign, 0.1 Hz
16 bits 4-digit BCD with sign, 0.1 Hz
12 bits 3-digit BCD with sign, 0.01 Hz
16 bits 4-digit BCD with sign, 0.01 Hz
16 bits 5-digit BCD without sign, 0.01 Hz
12 bits 12-bit binary with sign, 100%/4095
16 bits 16-bit binary with sign, 100%/30000
Reference Setting
Range
-110 to 110%
-110 to 110%
-110.0 to 110.0%
-110.0 to 110.0%
-15.99 to 15.99%
-110.0 to 110.0%
-400 to 400 Hz
-400 to 400 Hz
-159.9 to 159.9 Hz
-400.0 to 400.0 Hz
-15.99 to 15.99 Hz
-159.99 to 159.99 Hz
000.00 to 399.98 Hz
-4095 to 4095
-33000 to 33000
U1-01 Monitor Unit o1-03 = 0 o1-03 = 1
0.01 Hz 0.01%
Options o1-03 F3-01
2 to 39
40 to
39999
-
-
-
Switch
S1
Reference Input Mode
12 bits 3-digit BCD with sign, 1 rpm
16 bits 4-digit BCD with sign, 1 rpm
12 bits
3-digit BCD with sign, 100%/(1- to 4digit setting of o1-03)
16 bits
4-digit BCD with sign, 100%/(1- to 4digit setting of o1-03)
10000 x = 1 to 3
16 bits 4-digit BCD with sign, 100%/10000
Reference Setting
Range
-1599 to 1599 rpm
-15999 to 15999 rpm
U1-01 Monitor Unit o1-03 = 0 o1-03 = 1
1 rpm
1 rpm
-4095 to 4095
-10999 to 10999
(when o1-03 = 9999)
-11000 to 11000
5th digit of o1-03 setting:
X = 0, unit: 1
X = 1, unit: 0.1
X = 2, unit: 0.01
X = 3, unit: 0.001
DI-08 Reference Ranges
When using the DI-08, the following ranges can be set depending on the settings of the constants.
F3-01 Reference Input Mode Reference Setting Range
U1-01 Monitor Unit o1-03 = 0 o1-03 = 1
0 2-digit BCD with sign, 1% -110 to 110%
3
4
1
2
5
6
2-digit BCD with sign, 0.1%
2-digit BCD with sign, 0.01%
2-digit BCD with sign, 1 Hz
2-digit BCD with sign, 0.1 Hz
2-digit BCD with sign, 0.01 Hz
-
-15.9 to 15.9%
-1.59 to 1.59%
-159 to 159 Hz
-15.9 to 15.9 Hz
-1.59 to 1.59 Hz
0.01 Hz 0.01%
7
12-bit binary with sign, 100%/
4095
-255 to 255
6-
167