Initial Settings
Chapter 5-1
This section explains the basic settings required to operate and stop the
Inverter. The settings of parameters described here will be sufficient for simple Inverter operations. First, make these basic settings, then skip to the explanations of those special functions, even when your application requires special functions, such as stall prevention, carrier frequency setting, overtorque detection, torque compensation, slip compensation. Refer to
Chapter 6 Advanced Operation.
5-1 Initial Settings
• The following initial settings are required.
Parameter Write-prohibit Selection/Parameter Initialization (n01): Set n01 to 1 so that n01 through n79 can be set or displayed.
Rated Motor Current (n32): Check the rated current on the motor nameplate and set the parameter.
Setting the Parameter Write-prohibit Selection/Parameter Initialization (n01)
• Set n01 to 1 so that n01 through n79 can be set or displayed.
n01 No
Setting range
0, 1, 6, 8, 9
Parameter Write-prohibit Selection/
Parameter Initialization
Unit of setting
1
Changes during operation
Default setting 1
Note This parameter makes it possible to write-prohibit parameters, change the parameter set or displayed range, or initialize all parameters to default values.
0
1
6
8
Set Value
9
Value Description
Only n01 can be displayed and set. The n02 through n79 parameters can be displayed only.
The n01 through n79 parameters can be displayed and set.
Only the error log memory is cleared.
Enables the initialization of all parameters in 2-wire sequence so that the parameters will return to default values.
Enables the initialization of all parameters in 3-wire sequence.
Setting the Rated Motor Current (n32)
Set the rated motor current (n32) in order to prevent the motor from burning due to overloading.
Check the rated current on the motor nameplate and set the parameter.
• This parameter is used for the electronic thermal function for motor overload detection (OL1). By setting the correct parameter, the overloaded motor will be protected from burning.
n32 Rated Motor Current
Setting range
0.0% to 120% (A) of rated output current of Inverter
Unit of setting
0.1 A
Changes during operation
Default setting
No
(see note 1)
Note 1.
The standard rated current of the maximum applicable motor is the default rated motor current.
2.
Motor overload detection (OL1) is disabled by setting the parameter to 0.0.
50