Inverter Specifications. Omron VS MINI J7
Advertentie
Advertentie
Inverter Specifications
Chapter 9-1
9-1 Inverter Specifications
3-phase
200-V AC models
Model CIMR-J´7AZ
Power supply
Rated voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Power supply capacity (kVA)
(See note 1.)
Heat radiation (W)
Weight (kg)
Cooling method
20P1 20P2 20P4 20P7
3-phase 200 to 230 V AC at 50/60 Hz
–15% to 10%
±5%
21P5 22P2 24P0
0.4 0.9 1.6 2.7 4.3 5.9 9.3
13.0 18.0 28.1 45.1 72.8 94.8 149.1
0.5 0.5 0.8 0.9 1.3 1.5 2.1
Natural cooling Cooling fan
Singlephase
200-V AC models
Model CIMR-J7AZ
Power supply
Rated voltage and frequency
Allowable voltage fluctuation
Allowable frequency fluctuation
Power supply capacity (kVA)
(See note 1.)
Heat radiation (W)
(See note 2.)
Weight (kg)
Cooling method
B0P1 B0P2 B0P4 B0P7
Single-phase 200 to 240 V AC at 50/60 Hz
B1P5
–15% to 10%
±5%
0.5 0.9 1.6 2.7 4.3 ---
14.1 20.0 31.9 51.4 82.8 ---
0.5 0.5 0.9 1.5 1.5 ---
Natural cooling Cooling fan
---
---
---
---
---
Max. applicable motor capacity (kW)
Output specifications
Rated output capacity (kVA)
Rated output current (A)
Rated output voltage (V)
Control characteristics
Max. output frequency
Harmonic-current countermeasures
Control method
Carrier frequency
Frequency control range
Frequency precision
(temperature characteristics)
Frequency setting resolution
Output frequency resolution
0.3 0.6 1.1 1.9 3.0 4.2 6.7
3-phase 200 to 240 V AC (according to the input voltage)
400 Hz parameter setting
DC reactor (option) connection possible
Sine wave PWM (V/f control)
2.5 to 10.0 kHz (in vector control)
0.1 to 400 Hz
Digital commands: ±0.01% (–10°C to 50°C)
Analog commands: ±0.5% (25°C ±10°C)
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
0.01 Hz
132
Inverter Specifications
Chapter 9-1
Control characteristics
Overload capacity
External frequency set signal
Acceleration/deceleration time
Braking torque
150% of rated output current for 1 min
Selectable with FREQ adjuster: 0 to 10 V DC (20 kW), 4 to 20 mA (250
W), and 0 to 20 mA (250 W)
0.0 to 999 s (Independent acceleration and deceleration time settings:
2 types)
Approx. 20% (Braking Resistor and Braking Unit cannot be connected.)
Set a user V/f pattern
Protection function
Environment
Voltage/frequency characteristics
Motor protection
Instantaneous overcurrent protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power interruption compensation
(selection)
Cooling fin overheating
Grounding protection
Protection by electronic thermal
Stops at approx. 250% of rated output current
Stops in 1 min at approximately 150% of rated output current
Stops when main-circuit DC voltage is approximately 410 V
Stops when main-circuit DC voltage is approximately 200 V
(160 V for single-phase 200-V AC model)
Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s.
Detects at 110°C ±10°C
Protection at rated output current level
Charge indicator (RUN indicator) Lit when the main circuit DC voltage is approximately 50 V or less.
Location Indoors (with no corrosive gas, oil spray, or metallic dust)
Ambient temperature
Ambient humidity
Operating: –10°C to 50°C
Operating: 95% max. (with no condensation)
Ambient temperature
Altitude
Insulation resistance
Vibration resistance
–20°C to 60°C
1,000 m max.
5 MWmin. (Do not carry out any insulation resistance or withstand voltage tests)
9.8 m/s2max. between 10 to 20 Hz 2.0 m/s2max. between 20 and
50 Hz
Degree of protection Panel-mounting models: Conforms to IP20
3-phase
400-V AC models
Note 1.
The power supply capacity is the capacity for the Inverter’s rated output. It will vary depending on the impedance at the input power supply. (This is due to fluctuations in the power factor. The power factor can be improved by inserting an AC reactor.) There will also be variations in the ratio between the rated current of the motor that is used and the rated output current of the Inverter.
2.
The heat radiation is the electric power consumed in the Inverter at the
Inverter’s rated output.
Model CIMR-J7AZ
Power supply
Rated voltage and frequency
Allowable voltage fluctuation
40P2
–15% to 10%
40P4 40P7
3-phase 380 to 460 V AC at 50/60 Hz
41P5 42P2 44P0
Allowable frequency fluctuation
Power supply capacity (kVA)
(See note 1.)
±5%
1.3 1.9 3.6 5.1 5.9 9.1
Heat radiation (W) (See note 2.) 23.1 30.1 54.9 75.7 83.0 117.9
Weight (kg) 1.0 1.1 1.5 1.5 1.5 2.1
Cooling method Natural cooling Cooling fan
133
Inverter Specifications
Chapter 9-1
Max. applicable motor capacity (kW)
Output specifications
Rated output capacity (kVA)
Rated output current (A)
Rated output voltage (V)
Control characteristics
Max. output frequency
Harmonic-current countermeasures
Control method
Carrier frequency
Frequency control range
Frequency precision
(temperature characteristics)
0.9 1.4 2.6 3.7 4.2 6.6
1.2 1.8 3.4 4.8 5.5 8.6
3-phase 380 to 460 V AC (according to the input voltage)
400 Hz parameter setting
DC reactor (option) connection possible
Sine wave PWM (V/f control)
2.5 to 10.0 kHz (in vector control)
0.1 to 400 Hz
Digital commands: ±0.01% (–10°C to 50°C)
Analog commands: ±0.5% (25°C ±10°C)
Frequency setting resolution
Output frequency resolution
Overload capacity
External frequency set signal
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
0.01 Hz
150% of rated output current for 1 min
Selectable with FREQ adjuster: 0 to 10 V DC (20 kW),
4 to 20 mA (250 W), and 0 to 20 mA (250 W)
Acceleration/deceleration time 0.0 to 999 s (Independent acceleration and deceleration time settings:
2 types)
Braking torque
Voltage/frequency characteristics
Approx. 20% (Braking Resistor and Braking Unit cannot be connected.)
Set a user V/f pattern
Protective functions
Motor protection
Instantaneous overcurrent protection
Overload protection
Overvoltage protection
Undervoltage protection
Momentary power interruption compensation (selection)
Protection by electronic thermal
Stops at approx. 250% of rated output current
Stops in 1 min at approximately 150% of rated output current
Stops when main-circuit DC voltage is approximately 820 V
Stops when main-circuit DC voltage is approximately 400 V
Stops for 15 ms or more. By setting the Inverter to momentary power interruption mode, operation can be continued if power is restored within approximately 0.5 s.
Environment
Cooling fin overheating Detects at 110°C ±10°C
Grounding protection Protection at rated output current level
Charge indicator (RUN indicator) Lit when the main circuit DC voltage is approximately 50 V or less.
Location
Ambient temperature
Indoors (with no corrosive gas, oil spray, or metallic dust)
Operating: –10°C to 50°C
Ambient humidity
Ambient temperature
Altitude
Insulation resistance
Vibration resistance
Degree of protection
Operating: 95% max. (with no condensation)
–20°C to 60°C
1,000 m max.
5 MWmin. (Do not carry out any insulation resistance or withstand voltage tests)
9.8 m/s2max. between 10 to 20 Hz 2.0 m/s2max. between 20 and
50 Hz
Panel-mounting models: Conforms to IP20
1.
The power supply capacity is the capacity for the Inverter’s rated output. It will vary depending on the impedance at the input power supply. (This is due to fluctuations in the power factor. The power factor can be improved by inserting an AC reactor.) There will also be variations in the ratio between the rated current of the motor that is used and the rated output current of the Inverter.
2.
The heat radiation is the electric power consumed in the Inverter at the
Inverter’s rated output.
134