Installation Dimensions
30" (76.2 cm), 36" (91.4 cm), or 48" (121.9
cm) cabinet opening width
(If installed between cabinets)
18" (45.7 cm) min. clearance upper cabinet to countertop
Vent cover (if used)
Canopy
Min. cabinet opening width
X
Bottom of canopy to cooking surface
13" (33.0 cm)
A B
■
■
■
The vent system must have a damper. If the roof or wall cap has a damper, do not use the damper supplied with the range hood.
Use caulking to seal exterior wall or roof opening around the cap.
The size of the vent should be uniform.
Cold weather installations
An additional back draft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.
The break should be as close as possible to where the vent system enters the heated portion of the house.
Makeup air
Local building codes may require the use of makeup air systems when using ventilation systems greater than specified CFM of air movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your area.
Venting Methods
36" (91.4 cm) countertop height
A. For installations with canopy only:
78" (198.1 cm) minimum above electric cooking surface
84" (213.4 cm( minimum above gas cooking surface
B. For installations with optional duct cover:
90" (228.6 cm) minimum above electric cooking surface
96" (243.8 cm) minimum above gas cooking surface
IMPORTANT:
Minimum distance “X”: 24" (61 cm) from electric cooking surfaces
Minimum distance “X”: 30" (76.2 cm) from gas cooking surfaces
Suggested maximum distance “X”: 36" (91.4 cm)
■
Venting Requirements
Vent system must terminate to the outdoors.
■
■
■
■
Do not terminate the vent system in an attic or other enclosed area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Use metal vent only. Rigid metal vent is recommended.
Plastic or metal foil vent is not recommended.
The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.
For the most efficient and quiet operation:
■ Use no more than three 90° elbows.
■
■
■
Make sure there is a minimum of 24" (61.0 cm) of straight vent between the elbows if more than 1 elbow is used.
Do not install 2 elbows together.
Use clamps to seal all joints in the vent system.
Typical Internal Blower Motor System Venting Installations
A 10" (25.4 cm) round vent system is needed for installation (not included). The hood exhaust opening is 10" (25.4 cm) round.
NOTE: Flexible vent is not recommended. Flexible vent creates back pressure and air turbulence that greatly reduce performance.
Vent system can terminate either through the roof or wall.
Roof Venting Wall Venting Wall Venting
A
B
A. Roof cap
B. 10" (25.4 cm) round vent
B
A. Wall cap
B. 10" (25.4 cm) round vent
A
B
A. Wall cap
B. 10" (25.4 cm) round vent
A