advertisement
![Appendix J: Clock Codes. American Time SiteSync IQ Wired System | Manualzz Appendix J: Clock Codes. American Time SiteSync IQ Wired System | Manualzz](http://s1.manualzz.com/store/data/068320865_1-d707ccba2f669653b2a0946c947d3a01-360x466.png)
SiteSync IQ Wired Installation Manual
Appendix J: Clock Codes
CLOCK CODE = 01
3-WIRE SYNCHRONOUS (59th MINUTE)
Hourly Correction = 8 second signal from HH:57:54 to
HH:58:02
12 Hour Correction = 14 second signal from 05:57:54 to
05:58:08
Clock Types Covered:
American Time - A****(A,B or L)A***, B****(A,B or L)A***,
U****(A,B or L)A***
Cincinnati - *D-10, *D-12
Dukane - 24SS* Series
Edwards - *010 & *012
Faraday/Standard Electric Time - 2315*, 2316*, 2335*, 2336*,
2370*, 2372*, 2380*, 2382* Series
IBM - 77* Series
Lathem - Type SS*
Simplex - 77* Series, 82* Series, 2310-92* Series, 6310-92*
Series
CLOCK CODE = 02
3-WIRE MINUTE IMPULSE (59th MINUTE)
Every Minute from HH:59 through HH:49 - Pulse (2 sec)
Between 58 and 00 Seconds (Lines A & B)
Every Minute from HH:50 through HH:58 - Pulse (2 sec)
Between 58 and 00 Seconds (A LINE ONLY)
HOURLY - 59th MINUTE CORRECTION - 20 pulses between
10 and 50 seconds (Line A only)
Clock Types Covered:
American Time - A****(J or F)***, B****(J or F)***
Cincinnati - *D2, *D4
Edwards - Impulse *02, *04
Lathem - Type ISC* (3-wire hourly only correction)
Simplex/IBM - 55*, 75* & 80* Series, 6310-90* Series, 2310-
90* Series
CLOCK CODE = 03
STANDARD ELECTRIC TIME DUAL MOTOR
Normal Operation - 120/24VAC continuous (RUN Only)
Hourly Correction - 29 second signal from HH:59:30 to
HH:59:59 - RUN Power is Disconnected
12 Hour Correction - 15 minute signal from 5:12:00 to
5:27:00 (AM & PM) - RUN Power is Connected
Clock Types Covered:
American Time & Signal - X****(G or H)A***
Faraday - 2420 through 2431 Series
Standard Electric Time - CR & GRC 109106 through 109155,
J109106 through J109155 and 105047 through 105066
CLOCK CODE = 04
STANDARD ELECTRIC TIME AR-2A TWO WIRE DUAL VOLTAGE
Every Minute - EXCEPT 59TH MIN - 24 VDC PULSE (2 SEC)
FROM RUN RELAY
59th Minute - from 50 SEC to 00 SEC - HIGHER VOLTAGE
(48VDC) PULSE FROM CORRECTION RELAY
Clock Types Covered:
Standard Electric Time - AR-2A
CLOCK CODE = 05
3-WIRE MINUTE IMPULSE (58th MINUTE)
Every Minute between XX:58 and XX:48 - Pulse (2 sec)
Between 58 and 00 Seconds (Lines A & B)
Every Minute from XX:49 through XX:57 - Pulse (2 sec)
Between 58 and 00 Seconds (Line A only)
HOURLY - 58th MINUTE CORRECTION - 20 pulses between
10 and 50 seconds (Line A only)
Clock Types Covered:
3-WIRE MINUTE IMPULSE (58th MINUTE)
CLOCK CODE = 06
SYNCHRONOUS WIRED 2
Hourly Correction - 55 second signal from HH:58:05 to
HH:59:00
12 Hour Correction - 10 signals (95 sec ON, 25 sec OFF) from 05:05:00 to 05:24:35
Clock Types Covered:
American Time - H****(A or B)H***
Cincinnati - *D8, WS*
Honeywell - ST402A*
Faraday - 2310*, 2311*, 2320*, 2321*, 2330*, 2331*, 2313*,
2314*, 2333*, 2334*, and 1310 through 1431
CLOCK CODE = 07
TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)
Every Minute from HH:59:SS through HH:49:SS (at :58 to :00
SEC) - POSITIVE POLARITY (RUN RELAY)
Every Minute from HH:50:SS through HH:58:SS (at :58 to :00
SEC) - NEGATIVE POLARITY (CORRECTION RELAY)
59th Minute - 20 PULSES - NEGATIVE POLARITY
(CORRECTION RELAY)
Clock Types Covered:
American Time - A****FF***, B****FF***
Lathem - Type ISC* (2-wire hourly correction only)
Cincinnati - *D3
Edwards - *03
Faraday - 2373* Series, 2383* Series
Simplex - 2310-90* Series, 6310-90* Series
CLOCK CODE = 08
TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)
WITH 12 HR CORRECTION
Every Minute from XX:59:XX to XX:49:XX (at :58 to :00 SEC)
- POSITIVE POLARITY (RUN RELAY)
Every Minute from XX:50:XX to XX:58:XX (at :58 to :00 SEC)
- NEGATIVE POLARITY (CORRECTION RELAY)
59th Minute - 20 PULSES - NEGATIVE POLARITY
(CORRECTION RELAY)
12 HOUR CORRECTION - Every Minute From 6:02:10 through 6:44:55 - 20 PULSES - NEGATIVE POLARITY
Clock Types Covered:
American Time - A****FG***
Lathem - ISC* (with 12 hour correction installed)
Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.
© American Time
65
Appendix J: Clock Codes
SiteSync IQ Wired Installation Manual
66
CLOCK CODE = 09
SIMPLEX 59th MINUTE DUAL MOTOR
Normal Operation
Hourly Correction
- 120/24 VAC continuous (RUN only)
- 54 second signal from HH:58:05 to
HH:58:59 - RUN Power is Disconnected
Clock Types Covered:
Simplex - *M*
CLOCK CODE = 10
SIMPLEX 45th MINUTE DUAL MOTOR
Normal Operation - 120/24 VAC continuous (RUN only)
Hourly Correction - 54 second signal from HH:44:05 to
HH:44:59 - RUN Power is Disconnected
Clock Types Covered:
SIMPLEX/IBM - *M*
CLOCK CODE = 11
RAULAND/NATIONAL SYNCHRONOUS WIRED (25 second hour, 25 pulses 12 hour)
Hourly Correction = 25 SECOND signal at first minute of every hour
12 Hour Correction - 25 signals (25 sec ON, 35 sec OFF) from 06:00:00 to 06:24:25
Clock Types Covered:
National Time - EX-HH and EX-LL
Dukane - 240* Series
Rauland - 2460 Series
CLOCK CODE = 14
HONEYWELL
Hourly Correction - 55 second signal from HH:58:05 to
HH:59:00
12 Hour Correction - 12 signals (65 sec ON, 25 sec OFF) from 05:05:00 to 05:22:35
Clock Types Covered:
American Time - H****(A or B)H***
Cincinnati - *D8, WS*
Honeywell - ST402A*
Faraday - 2310*, 2311*, 2320*, 2321*, 2330*, 2331*, 2313*,
2314*, 2333*, 2334*, and 1310 through 1431
CLOCK CODE = 15
STRAIGHT FREQUENCY ELECTRONIC CLOCK
PREP: Every Hour from HH:57:00 to HH:59:00 - 2 Minute
Signal on GENERATOR PRESTART Line
HOURLY CORRECTION: Every Hour (except 5) from
HH:57:54 to HH:58:02 - 8 Second Signal on START SIGNAL
Line
12 HOUR CORRECTION: From 5:57:54 to 5:58:08 - 14
Second Signal on START SIGNAL Line
Clock Types Covered:
Simplex/IBM
CLOCK CODE = 12
CINCINNATI D6 - 2 WIRE REVERSE POLARITY MIN. IMPULSE
(59th Min) W/12 HR Correction
Every Minute from XX:59:XX through XX:49:XX (at :58 to :00
SEC) - POSITIVE POLARITY and Every Minute from 4:49 to
5:55 AM&PM (at :58 to :00 SEC)
Every Minute from XX:50:XX through XX:58:XX (at :58 to
:00 SEC) - NEGATIVE POLARITY ** EXCEPT from 4:49 to 5:55
AM&PM **
HOURLY CORRECTION - 59th Minute - 20 PULSES -
NEGATIVE POLARITY
12 HOUR CORRECTION - Every Minute From 5:00:10 through 5:30:50 - 20 PULSES - NEGATIVE POLARITY
Clock Types Covered:
American Time - B****FG***
Cincinnati - *D6
Edwards - *06
Faraday - 2376*, 2386*
CLOCK CODE = 16
3-WIRE MINUTE IMPULSE (59th MINUTE) W/12 HR
CORRECTION
Every Minute from XX:59 through XX:49 - Pulse (2 sec)
Between 58 and 00 Seconds (Lines A & B)
Every Minute
HOURLY
from XX:50 through XX:58 - Pulse (2 sec)
Between 58 and 00 Seconds (A LINE ONLY)
- 59th MINUTE CORRECTION - 20 pulses between
10 and 50 seconds
12 HOUR CORRECTION - Every Minute From 6:02:10 through
6:44:55 - 20 PULSES
Clock Types Covered:
American Time - A****JG***
Lathem - Type ISC* (3-wire with 12 Hour correction)
CLOCK CODE = 17
STANDARD ELECTRIC TIME AR-2 TWO WIRE DUAL VOLTAGE
Every Minute - EXCEPT 58TH MIN - 24 VDC PULSE FOR 2
SEC
58th Minute - from 58:50 to 59:00 - HIGHER VOLTAGE
(48VDC) PULSE
Clock Types Covered:
Standard Electric Time - AR-2 CLOCK CODE = 13
RAULAND/NATIONAL SYNCHRONOUS WIRED (25 second hour, 25 min 12 hour)
Hourly Correction = 25 SECOND signal at first minute of every hour
12 Hour Correction = 25 MINUTE signal from 6:00:00 to
6:25:00
Clock Types Covered:
National Time - EX-HH and EX-LL
Dukane - 240* Series
Rauland - 2460 Series
CLOCK CODE = 18
NATIONAL SYNCHRONOUS WIRED
Hourly Correction = 28 SECOND signal at first minute of every hour
12 Hour Correction = 27 MINUTE signal from 6:00:00 to
6:27:00
Clock Types Covered:
American Time - G Series
National Time - EX-HH and EX-LL
Dukane - 240* Series
Rauland - 2460 Series
Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.
© American Time
SiteSync IQ Wired Installation Manual
Appendix J: Clock Codes
CLOCK CODE = 19
STROMBERG SYNCHRONOUS WIRED (56th MINUTE)
Hourly Correction = 8 second signal from HH:56:10 to
HH:56:18
12 Hour Correction = 14 second signal from 11:56:36 to
11:56:50
Clock Types Covered:
Stromberg - WX*
CLOCK CODE = 20
NATIONAL SYNCHRONOUS WIRED (NO 12 HR CORRECTION)
Hourly Correction = 28 SECOND signal at first minute of every hour
12 Hour Correction = NONE
Clock Types Covered:
National Time
CLOCK CODE = 21
CINCINNATI D1
2nd THROUGH 58TH MINUT E - 24 VDC PULSE FOR 2 SEC
59th THROUGH 1st MINUTE - 60 VDC PULSE FOR 2 SEC
HOURLY CORRECTION - HH:59:10 to HH:01:49 - THREE
SETS OF TWENTY PULSES (24VDC)
Clock Types Covered:
Cincinnati - *D1
CLOCK CODE = 22
DUKANE SYNCHRONOUS WIRED
Hourly Correction = 55 second signal from HH:57:00 to
HH:57:55
12 Hour Correction = 11 signals - 55 sec ON, 65 sec OFF at
5:59:00 AM & PM
Clock Types Covered:
Dukane - 24A*, 24B*, 24C*, 24D*, and 24E* Series
CLOCK CODE = 23
STANDARD ELECTRIC TIME DUAL MOTOR (HOURLY
CORRECTION ONLY)
Normal Operation - 120/24 VAC continuous (RUN only)
Hourly Correction - 29 second signal from HH:59:30 to
HH:59:59 - RUN Power is Disconnected
Clock Types Covered:
Standard Electric Time
CLOCK CODE = 25
INDUSTRIAL ELECTRONIC SERVICE MASTER CLOCK (DIGITAL
CLOCKS)
NORMAL OPERATION - Black Wire 24 VDC Positive with
Respect to White Wire
MINUTE RESET - Secondary Clocks Advance 2 Minutes per
Second of Polarity Reversal
12 HOUR RESET - Power is removed from the Secondary
Clocks at 11:59:57 AM and PM for 3 Seconds
Clock Types Covered:
Industrial Electronic Service - TBD
CLOCK CODE = 26
STROMBERG 2 WIRE MINUTE IMPULSE (58th MINUTE,
HOURLY CORRECTION ONLY)
Every Minute from XX:06:XX through XX:57:XX (at :58 to
:00 SEC) - NEGATIVE POLARITY
Every Minute from XX:58:XX through XX:05:XX (at :58 to
:00 SEC) - POSITIVE POLARITY
58th Minute - From XX:58:10 to XX:58:50 - 20 PULSES -
NEGATIVE POLARITY
12 HOUR CORRECTION - NONE
Clock Types Covered:
Stromberg
CLOCK CODE = 27
DIGITAL CLOCK RESET - 12:00 AM/PM
NORMAL OPERATION - RELAYS CLOSED - 24/120VAC TO
SECONDARY CLOCKS
12 HR CORRECTION - RESET AT 12:00 AM (and PM, for
Noon versions)
CLOCK CODE = 36
SYNCHRONOUS WIRED 2, WITH NOON & MIDNIGHT SYNC
Hourly Correction = 55 second signal from HH:58:05 to
HH:59:00
12 Hour Correction - 10 signals (95 sec ON, 25 sec OFF) from 05:05:00 to 05:24:35
CLOCK CODE = 37
TWO WIRE NONCORRECTIVE MINUTE IMPULSE
Every Minute - XX:XX:58 through XX:XX:00 - POSITIVE
POLARITY
CLOCK CODE = 38
TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)
WITH 12 HR CORRECTION
Every Minute from XX:59:XX to XX:49:XX (at :59 to :00 SEC)
- POSITIVE POLARITY
Every Minute from XX:50:XX to XX:58:XX (at :59 to :00 SEC)
- NEGATIVE POLARITY
HOURLY CORRECTION - 59th Minute - 24 PULSES -
NEGATIVE POLARITY from HH:59:02 through HH:59:48
12 HOUR CORRECTION - Each Minute from 6:01:02 through 6:39:48 - 24 PULSES - NEGATIVE POLARITY
Clock Types Covered:
American Time - A****FG***
Lathem - ISC* (with 12 hour correction installed)
Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.
© American Time
67
advertisement
Related manuals
advertisement
Table of contents
- 4 Introduction
- 4 SiteSync IQ System Controller Standard Features
- 6 System Controller Installation
- 7 System Controller Setup Wizard
- 12 Standard GPS Installation
- 14 GPS Plus Installation
- 16 Ethernet Installation
- 20 Wired Clock Circuit Option
- 22 Wired Signal Circuit Installation
- 23 Wired Signal Circuit Programming
- 40 Settings & Configurations
- 50 Clock Troubleshooting
- 49 Troubleshooting Wired Signal Circuit
- 45 Troubleshooting Remote Connect
- 51 Appendix A: Ethernet Timekeeping
- 52 Appendix B: Supported Time Zones
- 53 Appendix C: Tone Generator Wiring
- 54 Appendix D: Wired Signal Circuit Programming Examples
- 57 Appendix E: Checking IQ System Controller Status Information
- 58 Appendix F: USB/Flash Drive
- 59 Appendix G: System Controller Port Diagrams
- 59 Appendix H: Maintenance Guide
- 60 Appendix I: Clock Circuite Wiring Diagrams
- 65 Appendix J: Clock Codes
- 68 Glossary