Appendix J: Clock Codes. American Time SiteSync IQ Wired System

Add to My manuals
69 Pages

advertisement

Appendix J: Clock Codes. American Time SiteSync IQ Wired System | Manualzz

SiteSync IQ Wired Installation Manual

Appendix J: Clock Codes

CLOCK CODE = 01

3-WIRE SYNCHRONOUS (59th MINUTE)

Hourly Correction = 8 second signal from HH:57:54 to

HH:58:02

12 Hour Correction = 14 second signal from 05:57:54 to

05:58:08

Clock Types Covered:

American Time - A****(A,B or L)A***, B****(A,B or L)A***,

U****(A,B or L)A***

Cincinnati - *D-10, *D-12

Dukane - 24SS* Series

Edwards - *010 & *012

Faraday/Standard Electric Time - 2315*, 2316*, 2335*, 2336*,

2370*, 2372*, 2380*, 2382* Series

IBM - 77* Series

Lathem - Type SS*

Simplex - 77* Series, 82* Series, 2310-92* Series, 6310-92*

Series

CLOCK CODE = 02

3-WIRE MINUTE IMPULSE (59th MINUTE)

Every Minute from HH:59 through HH:49 - Pulse (2 sec)

Between 58 and 00 Seconds (Lines A & B)

Every Minute from HH:50 through HH:58 - Pulse (2 sec)

Between 58 and 00 Seconds (A LINE ONLY)

HOURLY - 59th MINUTE CORRECTION - 20 pulses between

10 and 50 seconds (Line A only)

Clock Types Covered:

American Time - A****(J or F)***, B****(J or F)***

Cincinnati - *D2, *D4

Edwards - Impulse *02, *04

Lathem - Type ISC* (3-wire hourly only correction)

Simplex/IBM - 55*, 75* & 80* Series, 6310-90* Series, 2310-

90* Series

CLOCK CODE = 03

STANDARD ELECTRIC TIME DUAL MOTOR

Normal Operation - 120/24VAC continuous (RUN Only)

Hourly Correction - 29 second signal from HH:59:30 to

HH:59:59 - RUN Power is Disconnected

12 Hour Correction - 15 minute signal from 5:12:00 to

5:27:00 (AM & PM) - RUN Power is Connected

Clock Types Covered:

American Time & Signal - X****(G or H)A***

Faraday - 2420 through 2431 Series

Standard Electric Time - CR & GRC 109106 through 109155,

J109106 through J109155 and 105047 through 105066

CLOCK CODE = 04

STANDARD ELECTRIC TIME AR-2A TWO WIRE DUAL VOLTAGE

Every Minute - EXCEPT 59TH MIN - 24 VDC PULSE (2 SEC)

FROM RUN RELAY

59th Minute - from 50 SEC to 00 SEC - HIGHER VOLTAGE

(48VDC) PULSE FROM CORRECTION RELAY

Clock Types Covered:

Standard Electric Time - AR-2A

CLOCK CODE = 05

3-WIRE MINUTE IMPULSE (58th MINUTE)

Every Minute between XX:58 and XX:48 - Pulse (2 sec)

Between 58 and 00 Seconds (Lines A & B)

Every Minute from XX:49 through XX:57 - Pulse (2 sec)

Between 58 and 00 Seconds (Line A only)

HOURLY - 58th MINUTE CORRECTION - 20 pulses between

10 and 50 seconds (Line A only)

Clock Types Covered:

3-WIRE MINUTE IMPULSE (58th MINUTE)

CLOCK CODE = 06

SYNCHRONOUS WIRED 2

Hourly Correction - 55 second signal from HH:58:05 to

HH:59:00

12 Hour Correction - 10 signals (95 sec ON, 25 sec OFF) from 05:05:00 to 05:24:35

Clock Types Covered:

American Time - H****(A or B)H***

Cincinnati - *D8, WS*

Honeywell - ST402A*

Faraday - 2310*, 2311*, 2320*, 2321*, 2330*, 2331*, 2313*,

2314*, 2333*, 2334*, and 1310 through 1431

CLOCK CODE = 07

TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)

Every Minute from HH:59:SS through HH:49:SS (at :58 to :00

SEC) - POSITIVE POLARITY (RUN RELAY)

Every Minute from HH:50:SS through HH:58:SS (at :58 to :00

SEC) - NEGATIVE POLARITY (CORRECTION RELAY)

59th Minute - 20 PULSES - NEGATIVE POLARITY

(CORRECTION RELAY)

Clock Types Covered:

American Time - A****FF***, B****FF***

Lathem - Type ISC* (2-wire hourly correction only)

Cincinnati - *D3

Edwards - *03

Faraday - 2373* Series, 2383* Series

Simplex - 2310-90* Series, 6310-90* Series

CLOCK CODE = 08

TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)

WITH 12 HR CORRECTION

Every Minute from XX:59:XX to XX:49:XX (at :58 to :00 SEC)

- POSITIVE POLARITY (RUN RELAY)

Every Minute from XX:50:XX to XX:58:XX (at :58 to :00 SEC)

- NEGATIVE POLARITY (CORRECTION RELAY)

59th Minute - 20 PULSES - NEGATIVE POLARITY

(CORRECTION RELAY)

12 HOUR CORRECTION - Every Minute From 6:02:10 through 6:44:55 - 20 PULSES - NEGATIVE POLARITY

Clock Types Covered:

American Time - A****FG***

Lathem - ISC* (with 12 hour correction installed)

Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.

© American Time

65

Appendix J: Clock Codes

SiteSync IQ Wired Installation Manual

66

CLOCK CODE = 09

SIMPLEX 59th MINUTE DUAL MOTOR

Normal Operation

Hourly Correction

- 120/24 VAC continuous (RUN only)

- 54 second signal from HH:58:05 to

HH:58:59 - RUN Power is Disconnected

Clock Types Covered:

Simplex - *M*

CLOCK CODE = 10

SIMPLEX 45th MINUTE DUAL MOTOR

Normal Operation - 120/24 VAC continuous (RUN only)

Hourly Correction - 54 second signal from HH:44:05 to

HH:44:59 - RUN Power is Disconnected

Clock Types Covered:

SIMPLEX/IBM - *M*

CLOCK CODE = 11

RAULAND/NATIONAL SYNCHRONOUS WIRED (25 second hour, 25 pulses 12 hour)

Hourly Correction = 25 SECOND signal at first minute of every hour

12 Hour Correction - 25 signals (25 sec ON, 35 sec OFF) from 06:00:00 to 06:24:25

Clock Types Covered:

National Time - EX-HH and EX-LL

Dukane - 240* Series

Rauland - 2460 Series

CLOCK CODE = 14

HONEYWELL

Hourly Correction - 55 second signal from HH:58:05 to

HH:59:00

12 Hour Correction - 12 signals (65 sec ON, 25 sec OFF) from 05:05:00 to 05:22:35

Clock Types Covered:

American Time - H****(A or B)H***

Cincinnati - *D8, WS*

Honeywell - ST402A*

Faraday - 2310*, 2311*, 2320*, 2321*, 2330*, 2331*, 2313*,

2314*, 2333*, 2334*, and 1310 through 1431

CLOCK CODE = 15

STRAIGHT FREQUENCY ELECTRONIC CLOCK

PREP: Every Hour from HH:57:00 to HH:59:00 - 2 Minute

Signal on GENERATOR PRESTART Line

HOURLY CORRECTION: Every Hour (except 5) from

HH:57:54 to HH:58:02 - 8 Second Signal on START SIGNAL

Line

12 HOUR CORRECTION: From 5:57:54 to 5:58:08 - 14

Second Signal on START SIGNAL Line

Clock Types Covered:

Simplex/IBM

CLOCK CODE = 12

CINCINNATI D6 - 2 WIRE REVERSE POLARITY MIN. IMPULSE

(59th Min) W/12 HR Correction

Every Minute from XX:59:XX through XX:49:XX (at :58 to :00

SEC) - POSITIVE POLARITY and Every Minute from 4:49 to

5:55 AM&PM (at :58 to :00 SEC)

Every Minute from XX:50:XX through XX:58:XX (at :58 to

:00 SEC) - NEGATIVE POLARITY ** EXCEPT from 4:49 to 5:55

AM&PM **

HOURLY CORRECTION - 59th Minute - 20 PULSES -

NEGATIVE POLARITY

12 HOUR CORRECTION - Every Minute From 5:00:10 through 5:30:50 - 20 PULSES - NEGATIVE POLARITY

Clock Types Covered:

American Time - B****FG***

Cincinnati - *D6

Edwards - *06

Faraday - 2376*, 2386*

CLOCK CODE = 16

3-WIRE MINUTE IMPULSE (59th MINUTE) W/12 HR

CORRECTION

Every Minute from XX:59 through XX:49 - Pulse (2 sec)

Between 58 and 00 Seconds (Lines A & B)

Every Minute

HOURLY

from XX:50 through XX:58 - Pulse (2 sec)

Between 58 and 00 Seconds (A LINE ONLY)

- 59th MINUTE CORRECTION - 20 pulses between

10 and 50 seconds

12 HOUR CORRECTION - Every Minute From 6:02:10 through

6:44:55 - 20 PULSES

Clock Types Covered:

American Time - A****JG***

Lathem - Type ISC* (3-wire with 12 Hour correction)

CLOCK CODE = 17

STANDARD ELECTRIC TIME AR-2 TWO WIRE DUAL VOLTAGE

Every Minute - EXCEPT 58TH MIN - 24 VDC PULSE FOR 2

SEC

58th Minute - from 58:50 to 59:00 - HIGHER VOLTAGE

(48VDC) PULSE

Clock Types Covered:

Standard Electric Time - AR-2 CLOCK CODE = 13

RAULAND/NATIONAL SYNCHRONOUS WIRED (25 second hour, 25 min 12 hour)

Hourly Correction = 25 SECOND signal at first minute of every hour

12 Hour Correction = 25 MINUTE signal from 6:00:00 to

6:25:00

Clock Types Covered:

National Time - EX-HH and EX-LL

Dukane - 240* Series

Rauland - 2460 Series

CLOCK CODE = 18

NATIONAL SYNCHRONOUS WIRED

Hourly Correction = 28 SECOND signal at first minute of every hour

12 Hour Correction = 27 MINUTE signal from 6:00:00 to

6:27:00

Clock Types Covered:

American Time - G Series

National Time - EX-HH and EX-LL

Dukane - 240* Series

Rauland - 2460 Series

Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.

© American Time

SiteSync IQ Wired Installation Manual

Appendix J: Clock Codes

CLOCK CODE = 19

STROMBERG SYNCHRONOUS WIRED (56th MINUTE)

Hourly Correction = 8 second signal from HH:56:10 to

HH:56:18

12 Hour Correction = 14 second signal from 11:56:36 to

11:56:50

Clock Types Covered:

Stromberg - WX*

CLOCK CODE = 20

NATIONAL SYNCHRONOUS WIRED (NO 12 HR CORRECTION)

Hourly Correction = 28 SECOND signal at first minute of every hour

12 Hour Correction = NONE

Clock Types Covered:

National Time

CLOCK CODE = 21

CINCINNATI D1

2nd THROUGH 58TH MINUT E - 24 VDC PULSE FOR 2 SEC

59th THROUGH 1st MINUTE - 60 VDC PULSE FOR 2 SEC

HOURLY CORRECTION - HH:59:10 to HH:01:49 - THREE

SETS OF TWENTY PULSES (24VDC)

Clock Types Covered:

Cincinnati - *D1

CLOCK CODE = 22

DUKANE SYNCHRONOUS WIRED

Hourly Correction = 55 second signal from HH:57:00 to

HH:57:55

12 Hour Correction = 11 signals - 55 sec ON, 65 sec OFF at

5:59:00 AM & PM

Clock Types Covered:

Dukane - 24A*, 24B*, 24C*, 24D*, and 24E* Series

CLOCK CODE = 23

STANDARD ELECTRIC TIME DUAL MOTOR (HOURLY

CORRECTION ONLY)

Normal Operation - 120/24 VAC continuous (RUN only)

Hourly Correction - 29 second signal from HH:59:30 to

HH:59:59 - RUN Power is Disconnected

Clock Types Covered:

Standard Electric Time

CLOCK CODE = 25

INDUSTRIAL ELECTRONIC SERVICE MASTER CLOCK (DIGITAL

CLOCKS)

NORMAL OPERATION - Black Wire 24 VDC Positive with

Respect to White Wire

MINUTE RESET - Secondary Clocks Advance 2 Minutes per

Second of Polarity Reversal

12 HOUR RESET - Power is removed from the Secondary

Clocks at 11:59:57 AM and PM for 3 Seconds

Clock Types Covered:

Industrial Electronic Service - TBD

CLOCK CODE = 26

STROMBERG 2 WIRE MINUTE IMPULSE (58th MINUTE,

HOURLY CORRECTION ONLY)

Every Minute from XX:06:XX through XX:57:XX (at :58 to

:00 SEC) - NEGATIVE POLARITY

Every Minute from XX:58:XX through XX:05:XX (at :58 to

:00 SEC) - POSITIVE POLARITY

58th Minute - From XX:58:10 to XX:58:50 - 20 PULSES -

NEGATIVE POLARITY

12 HOUR CORRECTION - NONE

Clock Types Covered:

Stromberg

CLOCK CODE = 27

DIGITAL CLOCK RESET - 12:00 AM/PM

NORMAL OPERATION - RELAYS CLOSED - 24/120VAC TO

SECONDARY CLOCKS

12 HR CORRECTION - RESET AT 12:00 AM (and PM, for

Noon versions)

CLOCK CODE = 36

SYNCHRONOUS WIRED 2, WITH NOON & MIDNIGHT SYNC

Hourly Correction = 55 second signal from HH:58:05 to

HH:59:00

12 Hour Correction - 10 signals (95 sec ON, 25 sec OFF) from 05:05:00 to 05:24:35

CLOCK CODE = 37

TWO WIRE NONCORRECTIVE MINUTE IMPULSE

Every Minute - XX:XX:58 through XX:XX:00 - POSITIVE

POLARITY

CLOCK CODE = 38

TWO WIRE REVERSE POLARITY MINUTE IMPULSE (59th MIN)

WITH 12 HR CORRECTION

Every Minute from XX:59:XX to XX:49:XX (at :59 to :00 SEC)

- POSITIVE POLARITY

Every Minute from XX:50:XX to XX:58:XX (at :59 to :00 SEC)

- NEGATIVE POLARITY

HOURLY CORRECTION - 59th Minute - 24 PULSES -

NEGATIVE POLARITY from HH:59:02 through HH:59:48

12 HOUR CORRECTION - Each Minute from 6:01:02 through 6:39:48 - 24 PULSES - NEGATIVE POLARITY

Clock Types Covered:

American Time - A****FG***

Lathem - ISC* (with 12 hour correction installed)

Note: * indicates prefix or suffix of alpha and/or numeric characters (size, shape, mounting, etc.) that are not relevant to the master clock timing protocol.

© American Time

67

advertisement

Related manuals