11 Diagnostics and servicing
Since we offer this service worldwide, the support is provided in
English. The service itself is free of charge, the only costs involved are the normal call charges.
4 … 20 mA signal
Error Cause
4 … 20 mA signal not stable Fluctuating measured value
4 … 20 mA signal missing Electrical connection faulty
Voltage supply missing
Current signal greater than
22 mA, less than 3.6 mA
11.3 Diagnosis, fault messages
Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:
Operating voltage too low, load resistance too high
Sensor electronics defective
Rectification
Set damping
Check connection, correct, if necessary
Check cables for breaks; repair if necessary
Check, adapt if necessary
Replace device or send in for repair depending on device version
LED illuminated ring
Colour 8)
Green
Yellow
Red
The 360° status indication on the device (see chapter " Configuration ") shows the following:
• Device status
Operating status 7)
This enables simple on-site diagnosis without tools, see the following table:
Permanent light voltage supply on, operation without failure voltage supply on, operation with failure
Flashing
Message acc. to NE 107 " Maintenance required " available
-
Message acc. to to NE 107 " Function check ", " Out of specification " or " Simulation state " is displayed
Note:
For devices with M12 x 1 stainless steel plug, the 360° status indication is not available.
11.4 Status messages according to NE 107
The instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item " Diagnostics " via the respective adjustment module.
7) Signalling of process pressure ranges by colour and flashing, adjustable via
VEGA Tools app or PACTware/DTM.
8) Delivery status; adjustable via VEGA Tools app or PACTware/DTM
VEGABAR 38 • Two-wire 4 … 20 mA 43
11 Diagnostics and servicing
Status messages The status messages are divided into the following categories:
• Failure
Function check
Out of specification
• Maintenance required and explained by pictographs:
1 2
Fig. 29: Pictographs of the status messages
1 Failure - red
2 Out of specification - yellow
3 Function check - orange
4 Maintenance required - blue
3 4
Malfunction (Failure):
Due to a malfunction in the instrument, a fault signal is output.
This status message is always active. It cannot be deactivated by the user.
Function check:
The instrument is being worked on, the measured value is temporarily invalid (for example during simulation).
This status message is inactive by default.
Out of specification:
The measured value is unreliable because an instrument specification was exceeded (e.g. electronics temperature).
This status message is inactive by default.
Maintenance required:
Due to external influences, the instrument function is limited. The measurement is affected, but the measured value is still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).
This status message is inactive by default.
Failure
Code
Text message
F013 no measured value available
F017
Adjustment span too small
F036 no operable sensor software
Cause
Failed or interrupted software update
Rectification
Hardware error in the area of the measuring cell
Adjustment not within specification
Send instrument for repair
Change adjustment
Repeat software update
44 VEGABAR 38 • Two-wire 4 … 20 mA
advertisement
Related manuals
advertisement
Table of contents
- 4 1 About this document
- 4 1.1 Function
- 4 1.2 Target group
- 4 1.3 Symbols used
- 5 2 For your safety
- 5 2.1 Authorised personnel
- 5 2.2 Appropriate use
- 5 2.3 Warning about incorrect use
- 5 2.4 General safety instructions
- 5 2.5 Installation and operation in the USA and Canada
- 7 3 Product description
- 9 3.2 Principle of operation
- 12 3.3 Adjustment
- 12 3.4 Packaging, transport and storage
- 13 3.5 Accessories
- 14 4 Mounting
- 14 4.1 General instructions
- 16 4.2 Process pressure measurement
- 18 4.3 Level measurement
- 19 5 Connecting to power supply
- 19 5.1 Preparing the connection
- 19 5.2 Connection procedure
- 22 5.3 Wiring plan - Two-wire 4 … 20 mA
- 23 5.4 Switch-on phase
- 24 6 Access protection
- 24 6.1 Bluetooth radio interface
- 24 6.2 Protection of the parameterization
- 25 6.3 Storing the codes in myVEGA
- 26 7 Set up with the integrated display and adjustment unit
- 26 7.1 Adjustment system
- 27 7.2 Measured value and menu item display
- 28 7.3 Parameter adjustment
- 35 8 Setup with smartphone/tablet (Bluetooth)
- 35 8.1 Preparations
- 35 8.2 Connecting
- 36 8.3 Sensor parameter adjustment
- 37 9 Setup with PC/notebook (Bluetooth)
- 37 9.1 Preparations
- 37 9.2 Connecting
- 38 9.3 Parameter adjustment
- 39 10 Menu overview
- 39 10.1 Display and adjustment unit (on site)
- 40 10.2 VEGA Tools app and DTM (Bluetooth)
- 42 11 Diagnostics and servicing
- 42 11.1 Maintenance
- 42 11.2 Rectify faults
- 43 11.3 Diagnosis, fault messages
- 43 11.4 Status messages according to NE
- 45 11.5 Software update
- 46 11.6 How to proceed if a repair is necessary
- 47 12 Dismount
- 47 12.1 Dismounting steps
- 47 12.2 Disposal
- 48 13.1 Radio licenses
- 48 13.2 Approvals for Ex areas
- 48 13.5 Conformity
- 48 13.6 NAMUR recommendations
- 49 13.7 Environment management system
- 50 14 Supplement
- 50 14.1 Technical data
- 58 14.2 Dimensions
- 63 14.3 Industrial property rights
- 63 14.4 Licensing information for open source software
- 63 14.5 Trademark