11 Diagnostics and servicing

Since we offer this service worldwide, the support is provided in

English. The service itself is free of charge, the only costs involved are the normal call charges.

4 … 20 mA signal

Error Cause

4 … 20 mA signal not stable Fluctuating measured value

4 … 20 mA signal missing Electrical connection faulty

Voltage supply missing

Current signal greater than

22 mA, less than 3.6 mA

11.3 Diagnosis, fault messages

Connect a multimeter in the suitable measuring range according to the wiring plan. The following table describes possible errors in the current signal and helps to eliminate them:

Operating voltage too low, load resistance too high

Sensor electronics defective

Rectification

Set damping

Check connection, correct, if necessary

Check cables for breaks; repair if necessary

Check, adapt if necessary

Replace device or send in for repair depending on device version

LED illuminated ring

Colour 8)

Green

Yellow

Red

The 360° status indication on the device (see chapter " Configuration ") shows the following:

• Device status

Operating status 7)

This enables simple on-site diagnosis without tools, see the following table:

Permanent light voltage supply on, operation without failure voltage supply on, operation with failure

Flashing

Message acc. to NE 107 " Maintenance required " available

-

Message acc. to to NE 107 " Function check ", " Out of specification " or " Simulation state " is displayed

Note:

For devices with M12 x 1 stainless steel plug, the 360° status indication is not available.

11.4 Status messages according to NE 107

The instrument features self-monitoring and diagnostics according to NE 107 and VDI/VDE 2650. In addition to the status messages in the following tables there are more detailed error messages available under the menu item " Diagnostics " via the respective adjustment module.

7) Signalling of process pressure ranges by colour and flashing, adjustable via

VEGA Tools app or PACTware/DTM.

8) Delivery status; adjustable via VEGA Tools app or PACTware/DTM

VEGABAR 38 • Two-wire 4 … 20 mA 43

11 Diagnostics and servicing

Status messages The status messages are divided into the following categories:

• Failure

Function check

Out of specification

• Maintenance required and explained by pictographs:

1 2

Fig. 29: Pictographs of the status messages

1 Failure - red

2 Out of specification - yellow

3 Function check - orange

4 Maintenance required - blue

3 4

Malfunction (Failure):

Due to a malfunction in the instrument, a fault signal is output.

This status message is always active. It cannot be deactivated by the user.

Function check:

The instrument is being worked on, the measured value is temporarily invalid (for example during simulation).

This status message is inactive by default.

Out of specification:

The measured value is unreliable because an instrument specification was exceeded (e.g. electronics temperature).

This status message is inactive by default.

Maintenance required:

Due to external influences, the instrument function is limited. The measurement is affected, but the measured value is still valid. Plan in maintenance for the instrument because a failure is expected in the near future (e.g. due to buildup).

This status message is inactive by default.

Failure

Code

Text message

F013 no measured value available

F017

Adjustment span too small

F036 no operable sensor software

Cause

Failed or interrupted software update

Rectification

Hardware error in the area of the measuring cell

Adjustment not within specification

Send instrument for repair

Change adjustment

Repeat software update

44 VEGABAR 38 • Two-wire 4 … 20 mA