Step
5
6
Action
Verify if the shared folder exists in drive C, or add the following:
C:\ProgramData\Schneider Electric\EcoStruxure Augmented Operator Advisor Builder
\LocalBuilder
Click Apply & Restart .
Result: This user can log in to the local Builder.
Launching the EcoStruxure Augmented Operator
Advisor Builder
To launch the cloud Builder:
Step
1
2
Action
Start a web browser and enter the following URL: https://app.schneider-electric.com/ecostruxureaugmented-operator-advisor .
Log in using email address and password, or request a new login by clicking Register here .
To launch the local Builder:
Step
1
2
Action
In the list of installed Windows programs, click EcoStruxure Augmented Operator Advisor
Local Builder .
>
Log in using your Username and Password .
If logging in for the first time, use the default username and password (admin/admin), then enter a new password.
Installing the EcoStruxure Augmented Operator
Advisor Runtime
Overview
The EcoStruxure Augmented Operator Advisor Runtime can be installed on any of the following:
• Harmony GTU: Harmony HMIG5U21, HMIG5U22 Open Box
30 EIO0000003000.12
• Harmony iPC: HMIBMI, HMIBMO, HMIBMU, HMIBMP, HMIPSP
• Harmony P6: HMIP6
• Standard Windows PC
Prerequisites
The following minimum requirements must be met:
• Operating system: Windows 10
• Hard disk space: 600 MB (minimum)
• RAM: 4 GB
• Screen resolution: 1024 x 768 (minimum)
The following web browsers can be used:
• Google
®
Chrome
™
(version 101 or later)
• Mozilla
®
Firefox
™
(version 100 or later)
• Microsoft
®
Edge
™
(version 101 or later)
The following prerequisites must be satisfied before installing the EcoStruxure Augmented
Operator Advisor Runtime:
• Microsoft .NET Framework version 4.7.2 or later must be installed.
• The physical access to the runtime device must be secured by installing it in a closed cabinet inside your site or building.
• The EcoStruxure Augmented Operator Advisor Runtime must be installed only by a user with administrator rights on the runtime device.
• All folders and files installed and used by the software must be stored in a location where administration rights are required.
• The hard drive on which EcoStruxure Augmented Operator Advisor Runtime is installed must be encrypted to secure the user database, for example, using BitLocker.
• Only authorized users are allowed to deploy the project. Setup permissions to restrict the access to the project data folder on the runtime device.
EIO0000003000.12
31
Installing EcoStruxure Augmented Operator Advisor
Runtime
NOTE:
• The OS logging can trace the access to the device.
• There is no specific mechanism to store events linked to deployment.
• The EcoStruxure Operator Terminal Expert signature is used to ensure consistency between the runtime device and EcoStruxure Operator Terminal Expert Runtime.
To install the EcoStruxure Augmented Operator Advisor Runtime:
Step
1
2
6
7
3
4
5
Action
Go to the URL www.se.com
and search for EcoStruxure Augmented Operator Advisor.
Click the relevant link and follow the instructions to download the EcoStruxure Augmented
Operator Advisor Runtime.
Unzip the downloaded file.
On the runtime device, launch the installation file.
Result: The installation wizard starts.
Follow the installation wizard instructions to complete the installation process.
When choosing the destination folder, you can click Next to install to default destination folder or
Change to change the destination folder.
If a message appears during installation, proceed as follows:
• If the message indicates that the Microsoft Visual C++ installation has failed, click Yes to continue. The installation will continue normally.
• If the message indicates an issue with the cabinet file Data1.cab, then close the message window and stop the installation. Restart the installation procedure again at step 3.
However, when unzipping, install to a different destination folder, or if possible, install to a different disk drive on your device.
Click Finish to exit the installer after the installation process ends.
Install an SSL certificate, page 33
to complete the installation.
Apply relevant local IT rules and best practices to secure and backup your device.
EcoStruxure Augmented Operator Advisor Runtime is started automatically each time the runtime device is restarted. When you close the runtime user interface, you can choose to stop the runtime background services, or to leave them running. To manually start
EcoStruxure Augmented Operator Advisor Runtime, click EcoStruxure Augmented
Operator Advisor > Runtime in the list of installed Windows programs.
32 EIO0000003000.12
Installing the SSL Certificate
Step
1
2
3
4
5
6
To use a secure connection (HTTPS), you must acquire and install an SSL certificate.
You can install:
• either a certificate, signed by a public certificate authority,
• or a self-signed certificate, signed by your certificate authority
Action
In the Windows menu, click EcoStruxure Augmented Operator Advisor .
Open the Runtime Certificate folder .
Copy the certificate and associated key files provided by the certificate authority in this folder.
Rename the certificate file to server.crt
and the key file to server.key
.
Launch the EcoStruxure Augmented Operator Advisor Runtime and click the Settings tab.
Define the Runtime (server) port to 443 and select the HTTPS checkbox.
Augmented Operator Advisor – Runtime Version x.y
Project
Port setting
Runtime (server)
Documents
HTTPS
Internal communication + Node-RED
Operator Terminal Expert / Blue
Settings
Diagnosis
Node-RED
EcoStruxure Machine Advisor
Status
Https Proxy
Language
443
8082
8080
Launch
Not available
Connect
Apply
AOA Manager
7
8
Server started
Click Apply .
If you are using a self-signed certificate, the certificate authority file must be installed on any tablets using EcoStruxure Augmented Operator Advisor App, and on any PCs using EcoStruxure
Augmented Operator Advisor Manager.
Contact your local IT department to install the certificate authority file.
EIO0000003000.12
33
Testing the Configuration
Step
1
2
Action
Launch the EcoStruxure Augmented Operator Advisor
Windows programs, and click Settings .
>
Runtime from the list of installed
Click Launch to run the configuration.
Check ports
Runtime (server)
Internal communcation + Node-RED 8082
Operator Terminal Expert / Blue
443
8080
Connection successful
Connection successful
Process stopped
• Take note of the Runtime (server) port number. This will be required by the operator user when configuring the application on the tablet (see EcoStruxure Augmented Operator
Advisor, App, User Manual).
• If you use Node-RED, the same Internal communication + Node-RED port number should be used while configuring Augmented Operator Server node in Node-RED editor to communicate with EcoStruxure Augmented Operator Advisor Runtime.
• Node-RED and Operator Terminal Expert / Blue need to be started separately.
• EcoStruxure Augmented Operator Advisor Runtime is running correctly when Runtime
(server) and Internal communication + Node-RED are indicated as Connection successful .
• If any port is not available it is highlighted in red and the process using that port is indicated.
Close the Check ports window.
34 EIO0000003000.12
Step
3
Action
You can then change the specific ports manually. If you modify, click Apply and wait until the confirmation message appears.
Augmented Operator Advisor – Runtime Version x.y
Project
Port setting
Runtime (server)
Documents
HTTPS
Internal communication + Node-RED
Operator Terminal Expert / Blue
Settings
Diagnosis
Node-RED
EcoStruxure Machine Advisor
Status
Https Proxy
Language
443
8082
8080
Launch
Not available
Connect
Apply
AOA Manager
4
Server started
Click OK to close the confirmation window.
Click Launch to verify if the newly requested ports are available.
To verify the secure connection, open a web browser and type this URL: https://localhost:<PORT> where <PORT> is the port number configured for Runtime (server) in Settings .
If the SSL connection and the certificate installation are successful, a lock icon the URL address field.
appears beside
Configuring the Windows Firewall
To configure the firewall when using the Windows Firewall, follow this procedure to open the required TCP port:
Step
1
2
Action
From the Windows Start menu, open Control Panel .
Select Windows Firewall .
EIO0000003000.12
35
8
9
10
Step
3
4
5
6
7
Action
Select Advanced settings in the left column of the Windows Firewall window.
Select Inbound Rules in the left column of the Windows Firewall with Advanced Security window.
Select New Rule in the right column.
Select Port in the New Inbound Rule Wizard and then click Next .
NOTE: You must create a Port rule. Do not create a Program rule.
Select which protocol this rule will apply to TCP , select Specific local ports , type the
port number configured for Runtime, page 34
in Settings , and then click Next .
Select Allow the connection and then click Next .
Select when this rule applies (check all of them for the port to always stay open) and then click
Next .
Give this rule a name and then click Finish to add the new rule.
If you are using a firewall other than the Windows Firewall, consult the documentation of the manufacturer.
Importing a Project to EcoStruxure Augmented Operator
Advisor Runtime
Before you can import a project, copy the built project .zip file created in EcoStruxure
Augmented Operator Advisor Builder to the EcoStruxure Augmented Operator Advisor runtime device.
To import a project:
Step
1
2
Action
Launch the EcoStruxure Augmented Operator Advisor Runtime and click Project .
Click Import New Project and browse the project zip file, then click Open .
Result : The project is imported to the EcoStruxure Augmented Operator Advisor Runtime. The project information is displayed.
NOTE: If you reinstall the EcoStruxure Augmented Operator Advisor Runtime, you need to import the project again.
36 EIO0000003000.12