PC Communication and Bus control function. MJB Controls SY8600 Series
Reklama
Reklama
SY8600 High Performance Vector Control Inverter User Manual
Fig. 6-31 Traverse operation
PC Communication and Bus control function
Pc.00
Baud rate selection
Select baud rate of serial communication
Setting range:0~5
0:1200BPS 1:2400 BPS 2:4800 BPS 3:9600 BPS 4:19200 BPS 5:38400 BPS
Pc.01 Data Format
Data format of serial communication protocol:
0: 8,N,2 For RTU (MODBUS) (Default)
1: 8,E,1 For RTU (MODBUS)
2: 8,O,1 For RTU (MODBUS)
3: 7,N,2 For ASCII (MODBUS)
4: 7,E,1 For ASCII (MODBUS)
5: 7,O,1 For ASCII (MODBUS)
6: 8,N,1 free communication format
Setting range:0~8
7: 8,E,1 free communication format
8: 8,O,1 free communication format
Pc.02
Local address
Setting range:1~32
When the host is communicating with several inverters, inverter's address is defined in this function code.
。
Pc.03
Communication timeout detect
Setting range:0.0、0.1~100.0s
The setting value is 0:No communication overtime protection.
The setting value isn't 0, in RS485 communication control mode, if the communication between the inverter and the host is still abnormal in the time defined by Pc.03, ER05 fault is displayed and the inverter acts according to the setting value ofPc.05.
Pc.04
Response delay
Setting range:0 ~1000ms
Response delay refers to the time from the drive receiving and executing the command of the host to returning reply frame to the host.
Pc.05
EEROM Store function Setting range:0、1
101
Atsisiųsti
Reklama