PE Factory reserved. MJB Controls SY8600 Series
広告
広告
SY8600 High Performance Vector Control Inverter User Manual
Pd.13
Act selection at under voltage fault
Setting range:0、1、2
0: When under voltage occurs, fault relay does not act, and fault code will not be saved.
1: When under voltage occurs during running, fault relay acts and fault code will be saved. When under voltage occurs during stop state, fault relay does not act, and fault code will not be saved.
2: When under voltage occurs in running or stopping state, fault relay acts and fault code will be saved.
Pd.14 Input phase loss function Setting range:0~1
0:Disable
The input phase loss function is disabled.
1:Enable
The input phase loss function is enabled. ( only available on three phase input above 110kw inverter)
Pd.15 Output phase loss function Setting range:0~1
0: Disable
The output phase loss function is disabled.
1:Enable
The output phase loss function is enabled.
Pd.16 Under voltage point Setting range:360~440
Default value is 400v (DC voltage). In some case when the input voltage is low or not stable, the value can be adjusted to avoid under voltage fault.
PE Factory reserved
PE.00~PE.05
are reserved parameters for individual consumer.
PF Factory reserved
PF.00~PF.19
are reserved parameters for individual consumer.
PH Display function
PH.00 selection
SY8600 drive has 15 state parameters in running state. User can scroll through them by pressing
►► key during running process. Function code PH.00 defines the default display parameter after starting, which includes:
105
SY8600 High Performance Vector Control Inverter User Manual
0: Frequency setting
1: Running frequency
2: Output current
3: Output voltage
4: Bus voltage
5: Overload rate
6: Preset line speed
7: Running line speed
8: Output torque
9: PI reference
10: PI feedback
11: Analog input AI1
12: Analog input AI2
13: I/O status(0~511)
14: External counting value
Inpt/output IO status correspond as blow: relay1
Bit8
Y1
Bit7
X7 X6 X5
Bit6 Bit5 Bit4
X4 X3 X2 X1
Bit3 Bit2 Bit1 Bit0
PH.01
Display parameters at stop
Setting range:0~8
SY8600 drive has 9 state parameters in stopping state. User can scroll through them by pressing
►► key during stop state.
Function code PH.01 defines the default display parameter upon power on, which includes:
0: Frequency setting
1: Preset line speed
2: DC Bus voltage
3: Analog input AI1
4: Analog input AI2
5: I/O status
106
SY8600 High Performance Vector Control Inverter User Manual
6: external counting value
7: PI reference
8:PI feedback
PH.02
Line speed factor
Setting range:0.1~100
When line speed is displayed, line speed = Output frequency × Line speed factor
PH.03 Reserved
PH.04
IPM heat sink temperature
1
PH.05
IPM heat sink temperature
2
Display IPM heat sink temperature.
PH.06
1st fault type
PH.07
2nd fault type
Setting range:0~100
℃
Setting range:0~100
℃
Setting range:
Setting range:
PH.08
3rd fault type
Setting range:
PH.06~PH.08 are used for memorizing the latest three fault types, and can record the voltage, current, frequency and terminal state at the last fault (in
PH.09~PH.13) for checking.
Please refer to Chapter 7 for fault descriptions.
PH.09
Bus voltage at last fault
(V)
PH.10
Output current at last fault
(A)
Setting range:0~999
Setting range:0~999.9
PH.11
Frequency setting at last fault
(Hz) Setting range:0~400.0
PH.12
Running frequency at last fault
(Hz)
Setting range:0~400.0
PH.13
I/O state at last fault
PH.14
Total operating time
Setting range:0~511
Setting range:0~9999
PH.15
Software version
PH.16 Keyboard
Software version
PH.12At last time, I/O Status corresponds as blow:
Setting range:0~9.99
Setting range:0~9.99 relay1
Bit8
Y1
Bit7
X7 X6 X5
Bit6 Bit5 Bit4
X4 X3 X2 X1
Bit3 Bit2 Bit1 Bit0
107