3.0 Installation Precautions
Based on the 4200FA UPS external dimensions and the way the outer panels are removed; minimum amounts of unobstructed space around the unit are necessary for ventilation and maintenance access. The following section and Fig. 3.1 shows the minimum clearances required for proper UPS site installation.
3.1 Equipment Placement
1) Do not install the UPS on an inclined surface, or areas that are subject to frequent vibrations or jolting. This could damage UPS circuits.
REAR
15-30 kVA Premium – 6 in. (152 mm)
15-30 kVA Base – 12 in. (304 mm)
50 kVA Premium – 12 in. (304 mm)
25/50 kVA Seismic – 12 in. (304 mm)
2) Do not allow liquids or foreign objects to get inside the UPS.
3) Allow at least the following spacing for air ventilation and maintenance access.
Front: 20 in. (500 mm)
Sides: 6 in. (152 mm)
Back:
15/25/30kVA Premium - 6 in. (152 mm)
LEFT
6 in.
(152 mm)
RIGHT
6 in.
(152 mm)
15-30kVA Base - 12 in. (304 mm)
50kVA Premium - 12 in. (304 mm)
25/50kVA Seismic - 12 in. (304 mm)
4) Do not install the UPS in a location that is subject to high humidity. Also, do not install the unit in areas that are exposed to direct sunlight, or contaminated areas subject to high levels of airborne dust, metal particles, or flammable gasses.
5) Verify the ventilation and air conditioning system at the site is capable of removing the heat generated by the UPS.
Ambient temperature range for operating the
FRONT
20 in. (500 mm)
Fig 3.1
UPS is 32 – 104 °F (0 – 40 °C); 77 °F
(25 °C) is the recommended operating
temperature for maximum battery life.
6) Avoid installation near sources of electrical noise. Always make sure that the unit's ground is intact to prevent electrical shock and help prevent electrical noise.
7) This UPS generates and radiates radio-frequency energy during operation. Although RFI noise filters are installed inside the unit there is no guarantee that the UPS will not influence some sensitive devices, which are operating in near proximity. If such interference occurs, the UPS should either be installed farther away from the affected equipment and/or powered from a different source than the affected equipment.
4200FA Installation and Operation Manual 17
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 11 GENERAL SAFETY INSTRUCTIONS
- 12 EQUIPMENT WARNING LABELS
- 15 IMPORTANT SAFETY INSTRUCTIONS
- 19 Product Description
- 19 Theory of Operation
- 19 Application and Use
- 19 Power Backup
- 19 Power Conditioning
- 20 Product Unpacking / Inspection / Storage / Disposal
- 20 Unpack the Premium 15/25/30 kVA UPS (with Casters)
- 21 Unpack the Base and Seismic model 15/25/30 kVA UPS (without Casters)
- 22 Unpack the Premium 50 kVA UPS (with Casters)
- 23 Unpack the Base and Seismic 50 kVA UPS (without Casters)
- 24 Inspect UPS equipment After Unpacking
- 24 Permanent Anchoring for Premium 15/25/30/50 kVA UPS (with Casters)
- 25 Permanent Anchoring for Base and Seismic model 15/25/30/50 kVA UPS (without Casters)
- 26 Storage of UPS equipment
- 26 Disposal
- 27 Installation Precautions
- 27 Equipment Placement
- 28 System Preparation (Pre-Power)
- 28 Operating Precautions
- 29 UPS Connections
- 29 Power Connections
- 29 Power Connections 15/25/30 kVA with Internal Batteries
- 30 Power Connections 15/25/30 kVA with Internal Transformer
- 31 Recommended Wire Size and Torque Requirements for 15/25/30kVA
- 32 Power Connection Cable Routing and Conduit Placement 15/25/30 kVA
- 33 Control Circuit and External Battery Interface Connections 15/25/30 kVA
- 34 Recommended Wire Size and Torque Requirements
- 35 Power Connections 50 kVA
- 36 Recommended Wire Size and Torque Requirements for 50kVA
- 37 Power Connection Cable Routing and Conduit Placement 50 kVA
- 38 Control Circuit and External Interface Connections 50 kVA
- 39 4.4.1 Recommended Wire Size and Torque Requirements
- 40 Communication Interface
- 40 Remote Contact
- 41 RS-232C
- 42 UPS Shutdown (via RS-232C)
- 43 Specifications
- 44 4200FA 15 / 25 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
- 45 4200FA 15/25 kVA w/Internal Transformer
- 46 Transformer
- 47 4200FA 30 kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
- 48 4200FA 30 kVA w/Internal Transformer
- 49 Transformer
- 50 4200FA 50kVA @ 208 VAC Input/ 208 VAC Output w/Internal Batteries
- 51 4200FA 50kVA w/Internal Transformer
- 52 4200FA Efficiencies and Thermal Losses at Various Loads
- 53 Operating the UPS
- 53 AC Input Mode (Normal Operation)
- 54 Bypass Mode
- 54 Bypass Mode for Optional Alternate Input Models
- 55 Battery Backup Mode
- 56 Battery Backup Time and Discharge Process
- 56 Battery Low Voltage Tolerances
- 57 Battery Recharging
- 58 Front Panel Layout (All Units)
- 58 EPO (Emergency Power Off) Function
- 59 Audible Alarm Functions
- 59 LED (Light Emitting Diode) Functions
- 60 LED (Light Emitting Diode) System Status
- 60 LCD (Liquid Crystal Display) Functions
- 60 Line-1 System Messages
- 61 Line-2 System Fault Messages
- 61 Line-3 System Messages
- 61 Line-4 System Messages
- 62 Menu Tree
- 62 Initial Battery Charge
- 63 Start-up Procedure
- 64 Shutdown Procedure
- 65 Maintenance Bypass Procedure
- 65 Switch from UPS to Maintenance Bypass
- 65 Switch from Maintenance Bypass to UPS
- 67 Keypad Overview
- 68 Key Functions
- 69 BATT Key
- 69 MENU, F1, ENTER, UP, & DOWN Keys
- 69 BATT TEST Key
- 70 BUZZ STOP Key
- 70 RESET Key
- 71 Menu Data Screens
- 71 Settings for Calendar and Clock
- 71 Adjusting the Buzzer Volume
- 71 Settings for Display Duration
- 72 Run Switch Select
- 72 Serial Com Station Address
- 73 Output Voltage Adjustment
- 73 Equalize Charge Mode Select
- 74 Reset to Default Settings
- 74 Overload Operation
- 75 Backup History and Fault History
- 77 UPS Protection System
- 77 System Protection Features
- 77 System Protection Functions
- 78 Start-up / Scheduled Maintenance / Part Replacement
- 78 Start-up
- 78 Preventive Maintenance
- 79 Parts Replacement
- 80 External Dimensions / Shipping Dimensions / Weights
- 80 External Dimensions – 15/25/30 kVA with Casters
- 81 External Dimensions – 15/25/30 kVA without Casters
- 82 External Dimensions – 50kVA with casters
- 83 External Dimensions – 50kVA without Casters
- 84 Dimensions and Weights
- 84 Cabinet Color
- 85 APPENDIX A – Seismic Anchorages
- 89 APPENDIX B – Installation Planning Guides