At a Glance. Schneider Electric TSX 57/PCX 57 Implementation
விளம்பரம்
விளம்பரம்
TSX SCY 11601/21601
7.1
At a Glance
At a Glance
TSX SCY 11601:
General
The TSX SCY11601 communication module is used to communicate via a JBUS/
MODBUS link.
It comprises a communication channel, channel 0, mono-protocol, isolated RS485 asynchronous serial link supporting the JBUS/MODBUS protocol.
TSX SCY 21601:
General
The TSX SCY 21601 communication module is used to host PCMCIA communication cards.
It comprises two communication channels: l A multi-protocol built-in channel (channel 0), isolated RS485 asynchronous serial link, supporting UNI-TELWAY, Jbus/Modbus or Character Mode protocols.
l A PCMCIA host channel (channel 1) which supports the following protocols: l
UNI-TELWAY, Jbus/Modbus and Character Mode on an RS 232-D, Current
Loop, or RS 485 link, corresponding to cards TSX SCP 111, 112 and 114.
l
FIPWAY cell network corresponding to the TSX FPP 20card.
Notes for the two modules
Note: Important: The built-in channel on TSX SCY 11601/21601 modules is only compatible with a two wire RS 485 link.
Note: The TSX SCY 11601/21601 communication modules are only compatible with SV software version
≥
3.0 Premium/Atrium processors (as indicated on the side label of the processor module).